FIELD AGING OF ETHYLENE-PROPYLENE-RUBBER (EPR) CABLES UNDER NORMAL AND ACCELERATED VOLTAGE STRESS AT MEMPHIS LIGHT, GAS AND WATER DIVISION

Size: px
Start display at page:

Download "FIELD AGING OF ETHYLENE-PROPYLENE-RUBBER (EPR) CABLES UNDER NORMAL AND ACCELERATED VOLTAGE STRESS AT MEMPHIS LIGHT, GAS AND WATER DIVISION"

Transcription

1 FIELD AGING OF ETHYLENE-PROPYLENE-RUBBER (EPR) CABLES UNDER NORMAL AND ACCELERATED VOLTAGE STRESS AT MEMPHIS LIGHT, GAS AND WATER DIVISION Philip E. Cox, PE Underground Electric Systems Engineer, Member IEEE Memphis Light, Gas And Water Division Memphis, Tennessee - USA Abstract This document describes the project criteria and alternating-current breakdown test results from medium-term (9-14 years) field aged EPR URD type cables. These cables have been field aged under normal and accelerated voltage stress. This is intended to be an interim report, with additional testing as the field aged cable reaches 21 years of service. Keywords Distribution cable, field aging, EPR. I. Introduction In 1980, Memphis Light, Gas and Water Division (MLGW) changed it s underground cable specifications to require ethylene-propylene rubber (EPR) type insulation and a LLDPE cable jacket. This was in response to a high failure rate of the existing cable system consisting of unjacketed high-molecular weight polyethylene (HMWPE) insulated URD type cables. 1 In late 1981 or early 1982, MLGW was approached by The Texas Instruments Corporation to participate in field aging studies of different types of concentric neutral constructions of unjacketed URD type cables. The types of concentric neutral wires to be studied consisted of galvanized-coated steel-clad copper, mild-steel coated copper and tin-coated copper #14 awg wires. These cables were to be removed at one, two, three, five, seven and ten years to determine corrosion rates of the neutral wires. The (then) supervisor of Materials Management at MLGW, Ed Rogers, saw this as an excellent opportunity to electrically test field-aged cables of various types of EPR compounds in conjunction with neutral corrosion studies. The intent behind the EPR field aging portion of the study was to provide a correlation between laboratory aging and in-service field aging. This was to be accomplished by well documented cable manufacturing and installation; with a statistically significant number of tests for each type of cable and test interval. Laboratory aging of the same manufacturing runs of cable used in field aging were to be used to provide comparative data. Because there has always been a greater amount of laboratory aging data, this project was to be biased toward collection of field aged data. The specifications for the cables to be tested were written in such a manner to have three types of neutral construction and two types of insulation construction. 2 Six different companies bid on the project, which included providing the cables specified and provide alternating-current break-down (ACBD) testing at the intervals noted in the preceding paragraph. The types are noted as follows: Type I - #2 awg Cu Conductor, 260 mils EPR insulation, 10#14 Galvanized Coated Steel Clad Cu Concentric Neutral. Type II - #2 awg Cu Conductor, 260 mils EPR insulation, 10#14 Mild Steel Coated Cu Concentric Neutral. Type III - #2 awg Cu Conductor, 175 mils EPR insulation, 10#14 Sn-Coated Cu Concentric Neutral. Three cable companies provided bids which were within the budget constraints of the project. Table I, Bid Award Cable Types, indicates the types and specifications of the cables awarded to the three manufacturers. Approximately five (5), three-thousand (3000) foot reels of each type of cable, shown in Table I, were supplied for installation. Each cable company utilizes a different EPR compound. Although the insulation/cable classifications listed in ICEA S , Standard For Concentric Neutral Cables Rated 5 through 46 kv, did not exist in 1982, the insulations/cable constructions used in this project, would fall into the current classifications shown in Table I. Preliminary Report Page 1 of 10

2 Table I Bid Award Cable Types Manufacturer Neutral Type Neutral 175 Mil Wall 260 Mil Wall ICEA Classification Mfr A I Zn-Stl-Cu X I Mfr A III Sn-Cu X I Mfr B II Stl-Cu X IV Mfr B III Sn-Cu X IV Mfr C II Stl-Cu X III Mfr C III Sn-Cu X III II. Cable Installation Over a period of approximately one and one-half (1-1/2) years, in 1983 and 1984, these cables were installed in nine (9) subdivisions/apartment complexes in the Memphis area. These installations were retro-fit installations to replace direct buried unjacketed highmolecular weight polyethylene (HMWPE) #2 awg Cu cables. 1 The cables supply 23 kv system voltage (13.2 kv-to-ground) to single-phase 50 to 100 kva (50 kva typical) grounded-front pad-mounted transformers in a URD loop, normally-open-point design configuration. The retro-fit installation provided a conduit(ed) system with two parallel conduit runs between pad mounted transformers. One conduit contains a MLGW standard #2 EPR cable, and the other contains the cable under test. The test cables were not installed from the source to the first transformer. The MLGW standard cable was used to energize the subdivision/apartment complex initially; and the test cable was terminated with a capped separable-insulated-connector elbow. After all test cable installations were complete, each span of test cable was placed into service, with the parallel standard cable elbow capped for future use. All of the test cables were energized within five calendar days. The test cables were marked with tags indicating the manufacturer and type of cable, the MLGW standard cable was marked with operating instructions in the event of a test cable failure and each transformer was marked with a sign inside the hood of the transformer to call engineering in the event of a test cable failure. Table II, Cable Types - Quantity Installed & Stored, indicates the quantity of cable installed by type and manufacturer. 3 A quantity of each type of cable was held in reserve for future laboratory testing. This cable was stored indoors in a heated, but not cooled, water pumping station building. Because of the quantity of water moving through the building, in addition to air flow from basement areas, the summer temperature usually did not exceed 90 F (32 C). Note: With-in several months of installation, The Texas Instruments Corporation discontinued sponsoring the project. All remaining funding, paid by TI for administration of the project, was refunded by MLGW. Table II Cable Types - Quantity Installed & Stored Manufacturer Type Quantity Installed Quantity Stored Mfr A I 9,113 Ft 925 Ft Mfr A III 9,287 Ft 2,630 Ft Mfr B II 9,403 Ft 3,117 Ft Mfr B III 9,903 Ft 3,027 Ft Mfr C II 5,983 Ft 3,090 Ft Mfr C III 8,110 Ft 3,130 Ft Total= 51,799 Ft 15,919 Ft Preliminary Report Page 2 of 10

3 III. Aging Conditions Because all of the test cables are subjected to the same service voltage, and the cables are designed with 175 and 260 mil wall thicknesses, the electrical stresses are different. Because a 260 mil wall is considered to be a normal wall thickness for 25 kv Class cables, the 175 mil wall cables can be considered to be under a moderately accelerated aging condition. It should also be noted that a #2 awg conductor size is a nonstandard diameter for 25 kv Class cables. Because the conductors used in the test cable are smaller in diameter than 1/0 awg, which is the minimum standard conductor diameter for 25 kv class cables, the maximum insulation stress is greater in all of the test cables compared to typical installations of 15 kv and 25 kv class cables. Table III, Typical Test Cable Electrical Aging Stress, indicates these comparisons. All of the test cables were installed in 2 PVC conduit at a depth of ~42, with an estimated ambient temperature of F (7-21 C). The conduits containing the test cable were typically filled with water through-out the year. 4 The typical loop loading was ~400 kva (7 to 12, 50 kva transformers, typical). Table III Test Cable Electrical Aging Stress, V/Mil Conductor Wall Thickness Max Stress Percent Typical Min Stress Percent Typical Average Stress Percent Typical # # #1/ Based upon MLGW Phase-To-Ground Voltage, kv, in V/Mil 1/0 awg, Class B Compressed Conductor with 260 Mils Insulation IV. Testing Of Field Aged Cables The specifications of the project required ACBD testing of 25 samples of each type of cable at the intervals noted in the Introduction, in addition to testing cables shortly after manufacturing. The actual test intervals (thus far) have been zero, two, five and nine years. The number of samples tested for each set of data has raged from 19 to 33 samples, with only two sets of data being less than 25 samples (19 and 23). Generally, enough cable has been removed from service to allow for rejected tests because of termination failures, which are not included in the test data. The ACBD test protocol used in this project requires an active test length of 25 feet. Each test begins at 13 kv phase-to-ground (approximately service voltage), with 5 kv increments every five (5) minutes until insulation breakdown. All of the testing has been performed with AC resonant test sets and utilized de-ionized water type terminations. All field aged ACBD tests have been performed at the company which manufactured the cable. Each sample is dissected in the area of the test failure and documented on the test data sheet designed for this project. 5 In addition to testing cable originally installed in this project, two additional sets of data are shown in this document. These cables are MLGW specification cables which were installed during routine construction. A span of ten (10) year service aged cable was removed because of an impulse failure which occurred in service. 6 A span of cable from the first shipment of EPR cable delivered to MLGW was removed after 14 years of service and tested just for curiosity. Each of these cable falls into Class IV of the current ICEA S specification. Year zero cables were tested after typical offgassing time under factory storage conditions. Samples were taken from the beginning, middle and end of the manufacturing run. All other cables were removed from service, at the intervals noted. The cable was reeled onto a metal reel for transport to the MLGW materials testing laboratory. At the MLGW-MTL the cable was cut into thirty-nine (39) foot lengths, each cable end was sealed, the samples were then placed in individual 1-1/2 PVC conduits; the conduits were then partially filled with tap water and capped. The cables were then shipped direct to the cable manufacturer s HV testing laboratory and remained in the water-filled conduits until within several hours of ACBD testing. The data is presented graphically in two formats. The first two graphs indicate Preliminary Report Page 3 of 10

4 average, minimum, and maximum ACBD values versus time in a linear format. Graphs 3-8 indicate each cable type in a Weibull format, showing all data points. 7 Over 645 ACBD tests were performed to develop this data. This represents over 16,125 feet of active length of test cable and over 25,155 feet of cable removed, shipped and prepared for testing. 8 AC Breakdown Voltage Vs Time 260 Mil Wall Thickness AC Breakdown Values, kv (b Avg) (b Min) (Field Impulse MLGW) (1980 MLGW) "A" - (Red) - Center "B" - (Blue) - Right "C" - (Black) - Left (1984) Time,Years (2005) AC Breakdown Values, kv AC Breakdown Voltage Vs Time 175 Mil Wall Thickness "A" - (Red) - Center "B" - (Blue) - Right "C" - (Black) - Left (1984) (2005) Time,Years Preliminary Report Page 4 of 10

5 Preliminary Report Page 5 of 10

6 Preliminary Report Page 6 of 10

7 Preliminary Report Page 7 of 10

8 Table IV Average AC Breakdown, V/Mil 260 Mil Wall Cables Year Mfr A Mfr B Mfr C Mil Wall Cables Year Mfr A Mfr B Mfr C IV. Testing Of Laboratory Aged Cables As noted in Section I, this project has been biased toward the collection of field aged data, with cables held in reserve for supplemental laboratory aged data. Because of MLGW s involvement in the cable industry (primarily through the efforts of Ed Rogers, at that time) this project did not go unnoticed. The Electric Research Power Institute (EPRI) modeled Project 2713 after this project at MLGW. The major differences were: (1) the data collection in the EPRI project was biased toward laboratory aged data, supplemented with field aged data and (2) the insulation types under test included both cross-linked polyethylene (XLPE) and EPR. Because of the differences in EPR compounds available for medium-voltage utility application, engineers at MLGW strongly encouraged EPRI project managers to include more than one EPR compound. Once the project was well underway, EPRI indicated that it would have been wise to have included additional EPR compounds in the test, and EPRI would be interested in acquiring the field aged data generated in the MLGW project thus far (Mid-1992). MLGW agreed to provide this data in exchange for laboratory testing of shelfaged MLGW project cable, with the test data to be mutually beneficial to both parties. MLGW supplied the teat data to EPRI, and shipped some of the shelf-aged cable to an independent laboratory under contract with EPRI. This laboratory aged the cable for 9+ months and performed some testing as shown in Table V, Shelf- Aged/Laboratory Aged Test Results. It was intended to collect significantly more data, however EPRI ceased funding of this testing. The independent laboratory removed the cables and scrapped them before notification to MLGW. MLGW contacted this laboratory and they could provide no explanation as to why this had been done, and could not produce the raw data from the testing. It is currently under consideration to perform additional laboratory testing on the remaining cable in storage, at the cable manufacturer s HV laboratories. Preliminary Report Page 8 of 10

9 ACBD after 13 Years of Storage All ACBD in V/MIL Table V Shelf-Aged/Laboratory Aged Test Results Voltage Class Manufacturer ACBD New ACBD Shelf Aged % of New 15 Mfr A Mfr B Mfr C Mfr A Mfr B Mfr C Lab aging, 30 C±3, 19 kv to Ground, 9 months, 80kV impulse 3 times/week Voltage Class Manufacturer ACBD No Imp ACBD w/ Imp % New No Imp % New w/ Imp % Shelf Aged % Shelf aged, Impulse 15 Mfr A Mfr B Mfr C Lab aging, 30 C±3, 30 kv to Ground, 9 months, 80kV impulse 3 times/week Voltage Class Manufacturer ACBD No Imp ACBD w/ Imp % New No Imp % New w/ Imp % Shelf Aged % Shelf aged, Impulse 25 Mfr A Mfr B Mfr C V. Conclusions This is intended to be an interim report and will supply the utility and research industry with statistically significant, well documented, in-service field aged test data. It appears that all of the cable insulations under moderately accelerated aging have stabilized at an average AC breakdown value greater than eight (8) times the normal in-service voltage. 9 And at least two of the cable insulations under normal aging have stabilized at an average AC breakdown value almost seven (7) times the normal in-service voltage. 10 This rather simplistic approach is not intended to be a rigorous, or final, analysis of the data in this project. 1 See Service Life And Field Aging Of Medium Voltage Cables In Memphis Light, Gas Water Division s Underground Electric Distribution System By Ed Rogers, Presented IEEE Chicago, Illinois See Appendix 1 For Ordering Description Used In The Bids. 3 See Appendix 2 For Detailed Listing Of Locations And Quantity. 4 Only Two Conduits Were Found To Be Dry During Cable Removal In Preparation For Testing. Preliminary Report Page 9 of 10

10 5 See Appendix 3 For Example Of Typical Test Data Sheet. 6 The Impulse Which Caused The Cable Failure Also Caused The Failure Two Pad-Mounted Transformers, The Riser Pole Arrester And The Termination/Arrester Bracket. 7 See Appendix 4 For Raw Data In Tabular Form. 8 Cable Quantities Do Not Include Amounts Which Were Removed, But When Divided Into Test Lengths Did Not Meet The Required 39 Foot Test Length; Also, This Does Not Include Cable From Invalid Tests, Typically Termination Failures. 9 Based upon 175 mil wall cables being operated on a 12 kv system voltage, 7.2 kv-to-ground, and an average ACBD value of ~60 kv, >340 V/Mil. 10 Based upon 260 mil wall cables being operated on a 23 kv system voltage, 13.2 kv-to-ground, and an average ACBD value of ~90 kv, >340 V/Mil. Preliminary Report Page 10 of 10

11 Appendix 1 Type I 2/C, 260 Mil Wall, Hot Dip galvanized Coated Steel Clad Concentric Neutral URD Cable 1/C #2 awg 7-Strand, soft-annealed copper wires Class B concentric lay stranding conforming to the latest edition of ANSI/ASTM B-33, Standard Specification For Tinned Soft or Annealed Copper Wire For Electrical Purposed, (one and one-half (1-1/2) percent minimum and three (3) percent maximum compressed strands required)with an average minimum wall of of extruded semiconducting thermosetting, minimum average wall of of ethylene propylene rubber insulation, outside diameter range over the insulations shall be minimum and maximum, minimum average wall of of freestripping semiconducting thermosetting insulation shielding material, outside diameter range shall be minimum to maximum and 1/C consisting of ten (10) strands of #14 awg hot dip galvanized coated steel clad copper wires, applied helically and evenly spaced over the insulation shielding. The copper core shall have a nominal diameter of to which is metallurgically bonded a layer of low carbon steel with a thickness of , the wire shall be hot dip galvanized with a nominal 0.5 ounce of zinc per square foot (neutral wire available through Texas Instruments). Rated cable voltage 25 kv. Type II 2/C, 260 Mil Wall, Rust Inhibited Coated Concentric Neutral URD Cable 1/C #2 awg 7-Strand, soft-annealed copper wires Class B concentric lay stranding conforming to the latest edition of ANSI/ASTM B-33, Standard Specification For Tinned Soft or Annealed Copper Wire For Electrical Purposes, (one and one-half (1-1/2) percent minimum and three (3) percent maximum compressed strands required)with an average minimum wall of of extruded semiconducting thermosetting, minimum average wall of of ethylene propylene rubber insulation, outside diameter range over the insulations shall be minimum and maximum, minimum average wall of of freestripping semiconducting thermosetting insulation shielding material, outside diameter range shall be minimum to maximum and 1/C consisting of ten (10) strands of #14 awg rust inhibited coated steel clad copper wires, applied helically and evenly spaced over the insulation shielding. The copper core shall have a nominal diameter of to which is metallurgically bonded a layer of low carbon steel with a thickness of , the wire shall be hot dip galvanized with a nominal 0.5 ounce of zinc per square foot (neutral wire available through Texas Instruments). Rated cable voltage 25 kv. Type II 2/C, 175 Mil Wall, Coated Copper Concentric Neutral URD Cable 1/C #2 awg 7-Strand, softannealed copper wires Class B concentric lay stranding conforming to the latest edition of ANSI/ASTM B- 33, Standard Specification For Tinned Soft or Annealed Copper Wire For Electrical Purposes, (one and one-half (1-1/2) percent minimum and three (3) percent maximum compressed strands required)with an average minimum wall of of extruded semiconducting thermosetting, minimum average wall of of ethylene propylene rubber insulation, outside diameter range over the insulations shall be minimum and maximum, minimum average wall of of freestripping semiconducting thermosetting insulation shielding material, outside diameter range shall be minimum to maximum and 1/C consisting of ten (10) strands of #14 awg soft annealed copper wires, conforming to ANSI/ASTM B-33, Standard Specification For Tinned Soft or Annealed Copper Wire For Electrical Purposes, applied helically and evenly spaced over the insulation shielding. Rated cable voltage 15 kv.

12 Appendix 2 Date Sketch Location Mfr A - I Mfr A - III Mfr B - II Mfr B - III Mfr C - II Mfr C - III 11.Feb B Summer Trace Apartments Mar A Releigh Woods Aprtments Mar A Willow Wyck Townhomes Oct A Bennington SD Sep Bavarian Village 02.Sep A Northwood Hills SD Aug A Ridgeway Estates SD Oct A Willaimsburg park SD - Sec I Apr A Wildwood Manor - Sec A Totals >>

13 Appendix 3

14 Appendix 4A 260 Mil Wall Cable Raw Test Data A I-0 B II-0 C II-0 A I-2 A I - 2b* B II-2 C II-2 A I-5 B II-5 C II-5 A I-9 B II-9 C II-9 B - 10 B Does not include first Values in A I

15 Appendix 4B 175 Mil Wall Cables Raw Test Data A III-0 B III-0 C III-0 A III-2 B III-2 C III-2 A III-5 B III-5 C III-5 A III-9 B III-9 C III

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED

More information

2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G

2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G Seattle Cit y Light 1 of 4 2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G 1. Scope This standard covers the detailed requirements

More information

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both

More information

KNOW YOUR OPTIONS: 230 KV POWER CABLES

KNOW YOUR OPTIONS: 230 KV POWER CABLES KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common

More information

Section 5 161 kv Power Cables

Section 5 161 kv Power Cables Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper

More information

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks Introduction This document presents the fundamental aspects of cable and conductor selection for connecting pad mounted shunt

More information

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

The Contractor shall furnish and install all shielded power cable suitable for use on this project. Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT

More information

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO. SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.

More information

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE DC Hi Pot Testing Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE (FOR INFORMATIONAL PURPOSES ONLY) Page 1 of 6 DC HIGH POTENTIAL TESTING DC Hi-Pot testing can be applied as a withstand test (a

More information

VIPERFLEX ELECTRIC CABLE

VIPERFLEX ELECTRIC CABLE VIPERFLEX Flexible Low Voltage Electric Cable - 0.6/1kV (Rubber insulated) H07 RN-F & H07 BN-F Single Core 2-Core 2-Core and Earth 3-Core and Earth 4-Core and Earth Multi-Core and Earth H07 RCN-F & H07

More information

Industrial Cable Solutions for Variable Frequency Drives

Industrial Cable Solutions for Variable Frequency Drives Industrial Cable Solutions for Variable Frequency Drives Tough challenges call for innovative solutions, and General Cable is your worldwide source for new products and a wide range of industry-leading

More information

100% EMI Emission Containment

100% EMI Emission Containment 100% EMI Emission Containment Designed for Longer Service Life Highly Flexible for Easier Handling and Faster Installation Authorized Distributor Industrial VFD Cables Index n Variable Frequency Drive

More information

2.4 kv to 34.5 kv SP-1099

2.4 kv to 34.5 kv SP-1099 Specifications for Customer Electric Service 2.4 kv to 34.5 kv SP-1099 FORWARD...1 CHAPTER 1 - PRIMARY METERED SERVICE...4 General Service Information...4 CA-206...6 CA-208A...7 Section 1...8 Existing

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

SECTION 18370 SIGNAL WIRE AND CABLE

SECTION 18370 SIGNAL WIRE AND CABLE SECTION 18370 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for all cable and wire required for signal and signal power system wiring to wayside shelters, junction boxes, and factory

More information

OFFICE OF CIVIL ENGINEERING UNITED STATES COAST GUARD WASHINGTON, D.C. APRIL 1996 MARINE CABLE, POWER AND CONTROL SPECIFICATION NO.

OFFICE OF CIVIL ENGINEERING UNITED STATES COAST GUARD WASHINGTON, D.C. APRIL 1996 MARINE CABLE, POWER AND CONTROL SPECIFICATION NO. OFFICE OF CIVIL ENGINEERING UNITED STATES COAST GUARD WASHINGTON, D.C. APRIL 1996 MARINE CABLE, POWER AND CONTROL SPECIFICATION NO. G-SEC-390E 1. SCOPE 1.1 Purpose. This specification establishes the basic

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables

More information

SECTION 260513 MEDIUM VOLTAGE CABLE

SECTION 260513 MEDIUM VOLTAGE CABLE SECTION 260513 MEDIUM VOLTAGE CABLE PART 1 - GENERAL 1.1 SUMMARY A. Related Documents: 1. Drawings and general provisions of the Subcontract apply to this Section. 2. Review these documents for coordination

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation

Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning

More information

Hook-Up and Lead Wire

Hook-Up and Lead Wire 3.1 Hook-Up and Lead Wire 3 Table of Contents Hook-Up & Lead Wire Page Introduction: UL Style & CSA Type Listings 3.2 PVC 3.3 3.8 300V, 80 C 3.3 300V, 105 C 3.4 600V, 105 C 3.5 (Type MW) MIL-W-76C-PVC:

More information

Network Standard Advice No. 1420C 9/6/2011

Network Standard Advice No. 1420C 9/6/2011 Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides

More information

0095.05 June 30. 2011 July 18, 2014 1 of 7

0095.05 June 30. 2011 July 18, 2014 1 of 7 Standard Number: Superseding: Effective Date: Page: 0095.05 June 30. 2011 July 18, 2014 1 of 7 Pole Attachments, Automated Meter Reading and Cellular Phone Antennas 1. Scope 2. Application This standard

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime

More information

Type XHHW-2 or RHH/RHW-2/USE-2 GenFree II LSZH XLPO Single Conductor

Type XHHW-2 or RHH/RHW-2/USE-2 GenFree II LSZH XLPO Single Conductor TABLE OF CONTENTS SECTION I. SUBJECT SCOPE 2 II. APPLICABLE DOCUMENTS 2 III. CONDUCTOR 3 IV. SEPARATOR 3 V. INSULATION 3 A. 3-4 B. Electrical Properties 4 C. Flame Resistance 5 D. Smoke and Halogen Testing

More information

UGVCL/SP/591/11KV HT AB CABLE

UGVCL/SP/591/11KV HT AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase

More information

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope 3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service

More information

Session Five: Modern XLPE Materials for Extruded Energy Cable Systems

Session Five: Modern XLPE Materials for Extruded Energy Cable Systems Session Five: Modern XLPE Materials for Extruded Energy Cable Systems Abstract Hakan Lennartsson Senior Technical Service Manager, Borouge Hong Kong Pte. Ltd. The first medium voltage cables using extruded

More information

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application ENERGY TECWATER S1BN8-F 0,6/1 kv Cable for Water Application Technical Data Electrical parameters Thermal parameters Trademark Type designation Specification Approval Application Rated voltage Maximum

More information

Uptown Campus, Primary Electric Master Plan - Program Study State University of New York At Albany, SUCF Project No. 01832 V.

Uptown Campus, Primary Electric Master Plan - Program Study State University of New York At Albany, SUCF Project No. 01832 V. V. DESIGN STANDARDS i. Medium Voltage Cables ii. iii. iv. Separable Connectors Splices & Fault Indicators Manholes & Ductbanks Primary Switches & Medium Voltage Transformers v. Metering, Monitoring, &

More information

Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE

Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE Type FLX Freezer Floor Frost Heave Protection DESIGN GUIDE Commercial Products Type FLX TM Freezer Floor Frost Heave Protection DESIGN GUIDE Contents Introduction...2 Application Information... 2-3 Product

More information

HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & PROJECTS GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001

HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & PROJECTS GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001 NEW POL DEPOT AT HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & S GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001 TECHNICAL SPECIFICATION OF XLPE, FRLS LT CABLES

More information

Instrumentation Cable...14-17. Power Cable...2-11. Assembly Solutions...32

Instrumentation Cable...14-17. Power Cable...2-11. Assembly Solutions...32 Severe Cold Durability Exceeds CSA Cold Bend / Cold Impact (-0 C/-35 C) Drilling Mud Resistant Flame Retardant Certified to IEC 9-3 (33-3A) and IEEE 580 Oil Resistant Assemblies...3-33 Ester Based Mud

More information

MEDIUM VOLTAGE CABLES Up to and including 36 KV

MEDIUM VOLTAGE CABLES Up to and including 36 KV MEDIUM VOLTAGE CABLES Up to and including 6 KV NOTICE As this catalogue is not intendedto cover all of LIBAN CABLES SAL possibilities in special cables manufacturing, the hereafter listing of the types

More information

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities RELY ON OUR EXPERIENCE... EXPERIENCE OUR CAPABILITIES For close to half a century, Silec

More information

PART 1 - INTRODUCTION...

PART 1 - INTRODUCTION... Table of Contents PART 1 - INTRODUCTION... 3 1.1 General... 3 1.2 Sensor Features... 3 1.3 Sensor Specifications (CDE-45P)... 4 Figure 1-1 CDE-45P Sensor Dimensions (standard, convertible style)... 4 PART

More information

ScottishPower Distribution Cables & Equipment. Metal Theft

ScottishPower Distribution Cables & Equipment. Metal Theft ScottishPower Distribution Cables & Equipment Metal Theft April 2012 As an aid to deterring to metal theft this booklet has been put together to help identify the types of utility power cables and associated

More information

3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables 15. 8.7/15 kv XLPE insulated cables 25. 12/20 kv XLPE insulated cables 35

3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables 15. 8.7/15 kv XLPE insulated cables 25. 12/20 kv XLPE insulated cables 35 CONTENTS INTRODUCTION 1 Cable selection, cable specification, cable services CABLES Constructional data: 3.6/6 kv XLPE insulated cables 5 SECTION 1 6/10 kv XLPE insulated cables 15 SECTION 2 8.7/15 kv

More information

W-2. Stranding Comparison

W-2. Stranding Comparison Wire Knowledge W-1 W-2 Stranding Comparison Conductor Coatings/Coverings PURPOSE To facilitate stripping of components applied over the conductor To prevent compound fall-in Improve solderability Prevent

More information

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test

More information

Flexible cables for submersible products

Flexible cables for submersible products Flexible cables for submersible products Standards SUBCAB cables complies with the following general standards: IEC 6045 (general) IEC 608 class 5 (conductor) IEC 608-- CLAUSE 9 (oil resistant) IEC 608--

More information

Insulation Resistance Testing of Low Voltage Cables in the Field

Insulation Resistance Testing of Low Voltage Cables in the Field Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4

More information

Medium Voltage Terminations, 5 kv 46 kv

Medium Voltage Terminations, 5 kv 46 kv Medium Voltage Terminations, 5 kv 46 kv Over 30 years ago, 3M pioneered cold shrink technology. Since then, field use and laboratory analysis have repeatedly proven its merits and reliability. Through

More information

CIR. Index. Gexol. Standard CIR UL Listed Type TC-ER. Crush and Impact Resistant Without External Armoring. Arctic CIR UL Listed Type TC-ER-HL*

CIR. Index. Gexol. Standard CIR UL Listed Type TC-ER. Crush and Impact Resistant Without External Armoring. Arctic CIR UL Listed Type TC-ER-HL* Gexol CIR Crush and Impact Resistant Without External Armoring Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL n Available in Standard and Arctic Grade Jackets n Highly

More information

APPLICATION ORIENTED DESIGN OF CABLES

APPLICATION ORIENTED DESIGN OF CABLES APPLICATION ORIENTED DESIGN OF CABLES Mrs. Rohini Bhattacharyya, Dubai cables Ltd.P. O. Box 11529,Dubai. rohinib@ducab.com Mr. Nawaf Ahmad Al Mohaideb Dubai Cables Ltd. P. O. Box 11529, Dubai. Nawaf@ducab.com

More information

General Calculations. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE

General Calculations. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE Excerpt from PRYMIAN WIRE AND CABLE ENGINEERING GUIDE Page 1 of 0 Voltage Rating The selection of the cable insulation level to be used in a particular installation shall be made on the basis of the applicable

More information

Caledonian Submersible Pump Cables for Oil Industry >> IEEE 1018 >> IEEE 1019 >> API RP 11S5

Caledonian Submersible Pump Cables for Oil Industry >> IEEE 1018 >> IEEE 1019 >> API RP 11S5 Caledonian Submersible Pump Cables for Oil Industry >> IEEE 1018 >> IEEE 1019 >> API RP 11S5 Caledonian Windmill Cables COMPANY PROFILE Table of Content Caledonian, established in 1978, offers one of the

More information

Cables, Cable Laying & Accessories Manual

Cables, Cable Laying & Accessories Manual Distribution Business Cables, Cable Laying & Accessories Manual Database ref: File Ref: Title Page & Revision Log For Cables & Access v4 - Nov 2003.doc Manual Name: Cables & Accessories Manual Version

More information

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/ 1 X C-UA- LTXLPE/2006) MAHARASHTRA STATE ELECTRICITY

More information

Gexol. Gexol. The Global Cable Solutions Company. Designed for safe, reliable performance in the harshest oil and gas operating environments

Gexol. Gexol. The Global Cable Solutions Company. Designed for safe, reliable performance in the harshest oil and gas operating environments Gexol Gexol World Class World Class Designed for safe, reliable performance in the harshest oil and gas operating environments Power Control Instrument VFD The Global Cable Solutions Company Gexol World

More information

CATHODIC PROTECTION SYSTEM DESIGN

CATHODIC PROTECTION SYSTEM DESIGN CATHODIC PROTECTION SYSTEM DESIGN Presented By DENIS L ROSSI P.E. CORROSION ENGINEER New England C P Inc. Corrosion Fundamentals What is corrosion? It is defined as the degradation or deterioration of

More information

THE OKONITE COMPANY. Ramsey, New Jersey 07446. 201.825.0300. Fax: 201.825.3524. www.okonite.com

THE OKONITE COMPANY. Ramsey, New Jersey 07446. 201.825.0300. Fax: 201.825.3524. www.okonite.com THE OKONITE COMPANY Ramsey, New Jersey 07446. 201.825.0300. Fax: 201.825.3524. www.okonite.com Since its founding in 1878, the cornerstone of The Okonite Company s philosophy has been the complete evaluation

More information

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET

More information

Chapter 9. Bonding and Grounding

Chapter 9. Bonding and Grounding Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and

More information

Flygt flexible cables

Flygt flexible cables Flygt flexible cables Contents Standards General SUBCAB 4 Screened SUBCAB 6 Rubber cable type: NSSHÖU-J 7 Screened rubber cable type: NSSHÖU../E + ST 8 FGB screened rubber cable 9 PUR control cable 0 HCR

More information

MEDIUM VOLTAGE POWER CABLES

MEDIUM VOLTAGE POWER CABLES MEDIUM VOLTAGE POWER CABLES CONTENTS 1 GENERAL INTRODUCTION 4 TECHNICAL INFORMATION 15 25 35 45 Single Core XLPE Insulated PVC Sheathed Cables UNARMOURED CABLES COPPER UNARMOURED CABLES ALUMINUM ALUMINUM

More information

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION

DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit

More information

261000 Medium Voltage Electrical Distribution

261000 Medium Voltage Electrical Distribution Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal

More information

Building Cables and Wires

Building Cables and Wires Building Cables and Wires 4 Introduction alfanar is equipped with state-of-the-art manufacturing facilities such as latest machineries, instrumentation, quality control and testing laboratory, etc., for

More information

CONFLEX ELECTRIC CABLE

CONFLEX ELECTRIC CABLE CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard

More information

345 kv Underground Report

345 kv Underground Report POWER ENGINEERS, INC. February 24, 2010 345 kv Underground Report PROJECT NUMBER: 117910 PROJECT CONTACT: Mike Mueller Richard C. Mues, PE EMAIL: mike.mueller@powereng.com rmues@powereng.com PHONE: 314-851-4050

More information

STABILOY BRAND FEEDER SOLUTIONS ASSISTED LIVING FACILITIES

STABILOY BRAND FEEDER SOLUTIONS ASSISTED LIVING FACILITIES STABILOY BRAND FEEDER SOLUTIONS ASSISTED LIVING FACILITIES Introduction General Cable understands that assisted living facilities require complex building designs that must address a wide range of systems

More information

Stephen G. Whitley, Senior Vice President & Chief Operating Officer

Stephen G. Whitley, Senior Vice President & Chief Operating Officer Peter T. Brandien Vice President, System Operations To: Stephen G. Whitley, Senior Vice President & Chief Operating Officer From: Peter T. Brandien Re: Discussion of Cable Technologies Under Evaluation

More information

SMALL GAS OPERATOR OPERATION AND MAINTENANCE PLAN

SMALL GAS OPERATOR OPERATION AND MAINTENANCE PLAN SMALL GAS OPERATOR OPERATION AND MAINTENANCE PLAN Facility Name: Address: QUALIFIED PERSONNEL All tasks shall be completed by a person that is qualified to that task (see operators qualification of individuals

More information

How To Test For Safety On A Power Cable

How To Test For Safety On A Power Cable T H E M A G A Z I N E O F 7 x 2 4 E X C H A N G E I N T E R N AT I O N A L A Green Approach to Building a Superior Data Center S P R I N G 0 9 BUILD FOR TODAY. EXPAND ON DEMAND. Modularity in the data

More information

How To Get A Power Line Extension

How To Get A Power Line Extension GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs

More information

Standard Wire & Cable Co.

Standard Wire & Cable Co. MIL-DTL-27500 (NEMA WC27500) Cable Designation All MIL-DTL-27500 cables are designated by a combination of digits and letters (not to exceed 6) which indicates the exact construction of each cable. Please

More information

WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS

WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS CONDUCTORS Conductors are needed to complete the path for electrical current to flow from the power source to the working devices and back to the power source. Special wiring is needed for battery cables

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

PROFIBUS cable. for PROFIBUS-PA and -DP 10/63-6.46 EN

PROFIBUS cable. for PROFIBUS-PA and -DP 10/63-6.46 EN for PROFIBUS-PA and -DP 10/63-6.46 EN CPN 080/CPE 080-Ex PROFIBUS-PA basis cable AWG 18, 0.88 mm 2 Use For fixed installation indoor and outdoor, on racks and in conduits. Application Fieldbus cable for

More information

STREETLIGHT SYSTEM GROUNDING AND BONDING

STREETLIGHT SYSTEM GROUNDING AND BONDING Page: 1 of 8 STREETLIGHT SYSTEM GROUNDING AND BONDING 1. Scope This Construction Standard covers the grounding and bonding requirements for single phase streetlight systems served by the Looped Radial

More information

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED

More information

ELECTRICAL: WIRE, CABLE, AND TERMINATIONS

ELECTRICAL: WIRE, CABLE, AND TERMINATIONS ELECTRICAL: WIRE, CABLE, AND TERMINATIONS BASIS OF DESIGN This section applies to the design and installation of wire and cable systems and terminations. Design Criteria Medium Voltage Review and modify

More information

MESSENGERS FOR AERIAL CABLE

MESSENGERS FOR AERIAL CABLE MESSENGERS FOR AERIAL CABLE COPPERWELD - EHS, 30% CONDUCTIVITY MES(size)CUWELD Size O.D. Stranding Breaking Strength Wgt./Mft. MES1/4CUWELD 1/4".242 7 #12 5,783 lbs. 128 MES5/16CUWELD 5/16".306 7 # 10

More information

Quality Reliability Innovation. ISO 9001 : 2000 CERTIFIED BY AFAQ No. QUAL / 1997 / 7034 a COPPER TELECOMMUNICATION CABLES

Quality Reliability Innovation. ISO 9001 : 2000 CERTIFIED BY AFAQ No. QUAL / 1997 / 7034 a COPPER TELECOMMUNICATION CABLES Quality Reliability Innovation ISO : CERTIFIED BY AFAQ No. QUAL / 7 / 7 a COPPER TELECOMMUNICATION CABLES COPPER TELECOMMUNICATION CABLES CONTENTS 7 NOTICE INTRODUCTION QUALITY ASSURANCE RECOMMENDED ORDERING

More information

East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

East Central College 14434.03 HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE SECTION 260519 - BUILDING WIRE AND CABLE PART 1 - GENERAL 1.1 WORK INCLUDES A. Base and Alternate Bids: 1. Contractor Provide: a. Building wire and cable as shown on drawings or specified including feeders,

More information

Modeling of Transmission Lines

Modeling of Transmission Lines Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

A Study of a MV Cable Joint

A Study of a MV Cable Joint SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 7, No. 1, May 2010, 1-11 UDK: 621.315.35:537.212 A Study of a MV Cable Joint Radiša Dimitrijević 1, Neda Pekarić-Nađ 2, Miodrag Milutinov 3 Abstract: Construction

More information

18 AWG thru 8 AWG Not greater than 100/30 100/30. 6 AWG thru 1/0 AWG Not greater than 200/60 100/30

18 AWG thru 8 AWG Not greater than 100/30 100/30. 6 AWG thru 1/0 AWG Not greater than 200/60 100/30 Commercial Products COMMERCIAL PRODUCTS: RIGID AND IMC FITTINGS s Used to support cables in vertical raceways or risers. Relieves the strain that would be placed on terminations, the interior of panels,

More information

Specification SFTP CAT6 Network Cable 23AWG CU

Specification SFTP CAT6 Network Cable 23AWG CU Specification SFTP CAT6 Network Cable 23AWG CU S/FTP CAT6 Shielded S/FTP PVC Cable 23AWG 4pair Solid, Wooden drum 1000 Grey CAT6 600MHZ CM Shielded (S/FTP) Solid Cable: Our CAT6 600MHZ Shielded (S/FTP)

More information

PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE

PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE FORM A PTS HELICAL PIERS INSTALLATION SPECIFICATIONS NOTICE The following suggested specifications are written as a guide to assist the specifier in writing his own specifications. Specific circumstances

More information

Errors Related to Cable Resistance Imbalance in Three Wire RTDs

Errors Related to Cable Resistance Imbalance in Three Wire RTDs Errors Related to Cable Resistance Imbalance in Three Wire RTDs 1.0 Introduction There are multiple sources of error that can impact the accuracy of an RTD measurement. The cable incorporated into the

More information

The Basics of Loop Vehicle Detection

The Basics of Loop Vehicle Detection The Basics of Loop Vehicle Detection There are a number of ways to detect vehicles, ranging from hose style detection to ultra-sonic, to inductive loop. For traffic control or drive-thru, inductive loop

More information

Cable Failure, Diagnostics and. Steven Boggs

Cable Failure, Diagnostics and. Steven Boggs Cable Failure, Diagnostics and Rejuvenation Steven Boggs The History PE Cables The Zeigler catalyst was invented in 1953 and mass production of HDPE started in the late 1950 s. Chemically cross linked

More information

home site map help ECMS Project: 70197 Standard / Federal Oversight Advertised

home site map help ECMS Project: 70197 Standard / Federal Oversight Advertised Page 1 of 6 S PECIAL PROVISION home site map help ECMS BP ADMIN Project: 70197 Standard / Federal Oversight Advertised Short Description: US 422 Schuylkill River Bridge - D/B: Retaining Wall; ITS Devices;

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Three-Phase Electric Power Distribution for Computer Data Centers

Three-Phase Electric Power Distribution for Computer Data Centers Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of

More information

Radial Distribution Test Feeders

Radial Distribution Test Feeders Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published

More information

IN USE: CABLE AGING MANAGEMENT

IN USE: CABLE AGING MANAGEMENT IN USE: CABLE AGING MANAGEMENT ISSUE STATEMENT Concerns exist that cable aging-related failures may impact nuclear plant safety and reliability. As a result, plant owners and regulators are requiring the

More information

MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES

MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES Riccardo BODEGA, Prysmian Cables and Systems, The Netherlands, riccardo.bodega@prysmian.com Henk GEENE,

More information

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

08. SEK IDC CONNECTORS

08. SEK IDC CONNECTORS . IDC CONNECTORS connectors for flat cables enable simple and, cost-optimized device configuration. connectors are preferably used for connection within the device. HARTING offers a broad range of these

More information

Investigation of VLF Test Parameters. Joshua Perkel Jorge Altamirano Nigel Hampton

Investigation of VLF Test Parameters. Joshua Perkel Jorge Altamirano Nigel Hampton Investigation of VLF Test Parameters Joshua Perkel Jorge Altamirano Nigel Hampton 1 Introduction - why IEEE400.2 is in use with recommendations of test times and test voltages At the start of the CDFI

More information

The MC Cable Revolution is Gaining Ground REMKE

The MC Cable Revolution is Gaining Ground REMKE The MC Cable Revolution is Gaining Ground June 2014 MC Cable Installation Continues to Improve with Advances in Materials and Fittings As the use of Metal Clad Cable grows, contractors are demanding better

More information