Fault location on power cables. Fault location on power cables



Similar documents
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables

Network Standard Advice No. 1420C 9/6/2011

APPLICATION ORIENTED DESIGN OF CABLES

ScottishPower Distribution Cables & Equipment. Metal Theft

Sheath fault location on power cables. Sheath testing, Sheath fault location and Location of earth faults

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

Cables, Cable Laying & Accessories Manual

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

Gulf Cable & Electrical Ind. Co.

UGVCL/SP/591/11KV HT AB CABLE

KNOW YOUR OPTIONS: 230 KV POWER CABLES

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

The evolution of medium voltage power cables up to 36 kv

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities

Section kv Power Cables

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

How To Monitor Water Penetration In A Cable Screen

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES

HV Submarine Cable Systems Design, Testing and Installation

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

MEDIUM VOLTAGE CABLES Up to and including 36 KV

A Study of a MV Cable Joint

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

Unified requirements for systems with voltages above 1 kv up to 15 kv

Screened cable and data cable segregation

Catalogue Câbles d Energie

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

CONFLEX ELECTRIC CABLE

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

High Voltage Electrical Equipment Failure Diagnosis. Presented by: Spencer Tang & Terence Ng T&T Inspection & Engineering Sdn Bhd

AMSC s Superconductor Cable Technologies for Electric Utilities

High Voltage Systems. Today. The history of cables

Explaining and avoiding faults Increasing availability

INTERNATIONAL STANDARD

100% EMI Emission Containment

Cable Strippers: High, Low and Medium Voltage

Earthing Guidance Notes

Cable Solutions for Servo and Variable Frequency Drives (VFD)

3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables /15 kv XLPE insulated cables /20 kv XLPE insulated cables 35

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

Table of Contents. Fault Finding Solutions

Presentation to CIGRE Next Generation Network. Visit of Seine substation

MEDIUM VOLTAGE POWER CABLES

EDS KV TRIPLEX CABLE

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

Industrial Cable Solutions for Variable Frequency Drives

COAX Cables Radio Frequency Cables

Medium-voltage cables for reliable windpark infrastructure

International Electrotechnical Commission Standards

Cable Size Selection for Energy Efficiency

Transformer Bushings for GIS

W-2. Stranding Comparison

GroundRod AC Substation Earthing Tutorial

Current Ratings. TABLE BEC 107. (Continued) Current ratings for 6350/11000 volts grade PILC/SWA/PVC cable to BS6480/69

Linking sustainable ideas to real-world results

The optimum material solution for Low Voltage energy cables

Corporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection

)454, !,5-).)5- #!",% 3(%!4(3 #/.3425#4)/. ).34!,,!4)/.!.$ 02/4%#4)/. /& #!",%3!.$ /4(%2 %,%-%.43 /& /543)$% 0,!.43. )454 Recommendation,

MV CABLE TYPE C

Flexible and safe solutions, for decades. Cables for alarmand safety systems

HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & PROJECTS GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI

Development of a 500-kV DC XLPE Cable System

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

High Voltage Cable Systems

Offshore Wind China 2010 Bergen, 15th March Olivier Angoulevant Nexans Norway AS

Fault location in the outer sheath of power cables

Important Information: Complete Terms and Conditions are printed on sales invoices

Stephen G. Whitley, Senior Vice President & Chief Operating Officer

1ZSE en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Outside Telephone Cable

Condition Monitoring of equipment to improve quality of supply to customers by averting failures

David O Brien, CMP Products (David.OBrien@cmp-products.com)

Specializing in the cable business for over 38 years, PT. SUPREME CABLE

WIRE AND CABLE ENGINEERING GUIDE

No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint

Connect. Cable preparation and cutting tools

HIGH VOLTAGE XLPE CABLE SYSTEMS. Technical User Guide

How To Test For Safety On A Power Cable

CABLE 101. The Basics of Wire & Cable. Copyright 2007, Belden Inc.

Electrical Resistance Resistance (R)

6-36kV Medium Voltage Underground Power Cables. XLPE insulated cables

6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20

ELEVATOR TRAVELING CABLE - DESIGN EVOLUTION

Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable

Flexible cables for submersible products

Removal of EP SP High Voltage Cable

Contents. All Rights Reserved

SUPERCONDUCTING CABLE SYSTEMS

TECHNICAL SPECIFICATIONS OF 66 KV 1C 300 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE

CABLES FOR PHOTOVOLTAIC SOLAR ENERGY INSTALLATIONS FOR CLEAN ENERGY

Flexible Control Cables

CAVEL VS80205 MADE IN ITALY 1000 V

VIPERFLEX ELECTRIC CABLE

R=Required by Lab S=May be subcontracted IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT COMMITTEE OF TESTING LABORATORIES

Transcription:

Fault location on power cables Fault location on power cables

Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables is a very specialized area of electrical technology. The performance of efficient fault location is very much dependant on good logistics and knowledge. Fast and reliable fault location is dependent on these factors if prelocation of a fault is to be done with high accuracy. The following pinpointing procedure, for the exact location of the fault location, can be done on a very short segment of the cable. Cable testing, cable diagnosis and partial discharge measurements, will become of higher importance in the future. The condition based preventive maintenance of cable networks, will more and more replace the event oriented maintenance of cable installations. A good detailed knowledge of the construction of cable networks, cable types and their accessories, simplifies the evaluation of the measured results considerably. Many of these are processes are the essential grounds for correct decisions to be made. The types of cable faults and the required steps to do a cable fault location or a diagnosis are one of the most important details that the technician must be aware of. 2. Construction of power cables The purpose of power cables is for the efficient distribution of electrical energy, Distrubution must be done with a high degree of reliability and safety over a very long period of time. Depending on the application, external environmental and local factors, for example, ground water level, type of ground or voltage levels, different types of cables are used. Cables with impregnated insulation,such as PILC, were installed until the late 60 s and are still being installed in some areas. These cables are today mostly replaced by cables with PVC, EPR, PR or XLPE insulation. Resulting from the changing characteristics of cables their faults and testing have changed considerably. The following chapters cannot cover all of the possible different constructions and varieties of cables and their different materials, but it will concentrate on the most important details only. Many of the following details are not for the explanation of these said details, but more so to help understand and follow the used wording in our fault location guide. 2

Basic Cable construction Fig. Single core Multi core shielded Multi core unshielded 1.1. 2Conductor The purpose of the conductor is for current transmission and consists of soft electrolytic copper or pure aluminium. It can be round, sector shaped, single wire or multi stranded construction. 1.2. 3Insulation The purpose of the insulation is for voltage resistivity and potential separation of conductors from each other and from the metallic outer jacket (Lead Sheath, Armour). 1 to 10 kv: Mass impregnated paper (PILC) Polyvinylchloride (PVC) 1 to 30 kv: Mass impregnated paper (PILC) Cross linked Polyethylene (XLPE) Ethylene Propylene Rubber (EPR) From 60 kv Paper with Oil or Gas Cross linked Polyethylene (XLPE) Besides these typical materials, there are also different types of insulation in existance. 1.3. 4Semi conducting layers (at nominal voltages from 6 kv The purpose of semi-conducting layers is for the prevention of partial discharges (PD) and high electrical fields inside the cable. Semiconducting layers soften the electrical field which builds up around each single conductor strand and avoids discharge which may occur due to increased electrical fields which may cause damage to the cable Other types of semi conducting layers are today being used for the outer insulating sheath / jacket. The purpose here is for example, to locate sheath faults on cables that are installed in ducts, where the return for the fault current through earth is non existent. 3

1.4. 5Metallic sheath The purpose of the metallic sheath is for protection and sealing from humidity, conduction of leakage or earth fault currents, potential equalisation, earth conductor and neutral concentric. For very important cables and for sub sea cables it can also provide strong mechanical protection. 1.5. 6 (at MV- and HV cables) The purpose of the shield is for conduction of leakage, earth fault current and field control. Semiconductor Sheath / Jacket / Screen 1.6. 7Armour The purpose of the armour is for Mechanica protection, It can consists of steel bands, flat wires, round wires etc. In some cases this armouring can consist of several different layers. Insulation / Dielectric Inner Semiconductor Core / Conductor 1.7. 8Plastic sheath The purpose of the plastic sheath is for outer protection of the cable and it consists of PVC or PE. 4

1Cable faults Depending on the type of cable fault, a suitable procedure must be selected. In the cable fault location the general differentiation is divided into the following fault types. 1.8. 9Fault Conductor - conductor (parallel Fault) Connection between two or more conductors. The insulation resistance value of the fault can be between 0 Ohms (low resistivity) or several M Ohms (high resistivity). 2 1.9. 10Fault Conductor - shield (parallel Fault) Connection between Conductor and shield or Conductor/Conductor and shield. The insulation resistance value of the fault can be between 0 Ohms (low resistivity) or several M Ohms (high resistivity). Experience has shown, that most faults are in this category. 1.10. 11Flashing fault (parallel Fault) Very high resistance fault. The cable can be charged. The flashover happens typically at some kv and is very often located in Joints. The cable acts comparable to an arc gap, where the distance between the electrodes determines the voltage. The insulation resistance of this fault is typically infinite up to the breakdown voltage. 5

1.11. 12Serial fault (Open, Interrupt) Faults of this type can be very high resistive up to infinite (complete cut). Very often these type of faults are a combination of serial and parallel insulation resistances. The reason for this being a complete cut of the cable, or it is pulled out of the joint, which interrupts everything, but also permits flashovers in all possible variations. If the conductor is partially burned off (Aluminium) we speak of longitudinal faults. 1.12. 13Earth faults, sheath faults Faults between the metallic shield and surrounding soil in case of plastic insulated cables. Faults between the Conductor and surrounding soil on LV and plastic insulated cables. Especially for these type of faults the highest precaution must be taken when using high voltage, this is of utmost importance, since the voltage discharges directly to earth. Resulting an increased potential danger to man and animal. 6

1.13. 14Humid / wet faults On multi core cables, often all conductors are affected. The flashover does not always appear at the position where the water entered the cable. The fault resistance is in the range of several k Ohms. At the fault location, impedance changes do occur. Depending on the cable construction (e.g. longitudinal water sealing) these faults can be punctual or widespread throughout the cable. Humidity faults are the most difficult faults to locate. They have the tendency to change during the fault location procedure, partially in a very drastic manner, which occurs especially in Joints, the fault can become high resistive again after one or two discharges and then cannot be localised anymore. The water gets blown out of the joint and dries up. Other forms of humidity faults are underwater faults. Here the water pressure prevents an effective ignition of the fault during the HV application. The location of these faults can be very difficult to.pinpoint. Comments For fault resistance values there is a global differentiation between short circuit, resistive and high resistive faults. The details of this said information has a significant influence on the further procedures to be used during the fault location. These details are described in one of the following articles. 7