White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection
|
|
|
- Mavis Weaver
- 10 years ago
- Views:
Transcription
1 White paper SACE Tmax XT Circuit-Breaker Terminals and Connection
2
3 Circuit-Breaker Terminals and Connections Index Introduction Components used for wiring Electrical Flexibility of an electrical cable: flexible and rigid Cable end: cable terminals (lugs) and rigid bars Description of terminals Circuit-breaker wiring SACE Tmax XT SACE Tmax XT SACE Tmax XT SACE Tmax XT Annex A...24 A.1 Conversion table: AWG-mm A.2 Std. IEC tables: al areas and current carrying capacity...24 ABB Circuit-Breaker Terminals and Connections 1
4 Introduction The reliability but above all the safety of an electrical plant depends not only on the quality of the design and components but also on the methods of installation. Among the components of an electrical plant, the and the bars play an important role. Besides taking into consideration the project (choice of the conductor type, cable sizing and method of installation, etc.), an aspect requiring particular attention is the connection method of the protective device to the terminal. As a matter of fact it is of fundamental importance to connect properly the cable or the bar to the circuit-breaker taking some particular measures and following some useful advices. Thus, some inconveniences can be avoided, e.g. the problems deriving from local heating near the circuit-breaker terminals, blackening marks on the insulating material and on the conductor, premature aging of the part of cable near to the circuit-breaker, etc., aspects which cannot be neglected since the cable may be the cause of flame ignition with dangerous consequences from the point of view of the safety of people and goods. For this reason, the analysis presented in the following pages is aimed at giving useful hints for the connection of the /bars to the circuit-breaker terminals. This document is accompanied by numerous tables which privilege the information about the connection cable/bar-terminal, trying to limit to the necessary the descriptions of the different components (, bars, cable terminals, etc.) already documented by the manufacturing companies. This White Paper is divided into three main parts: components used for wiring: this part gives a description of the components mentioned in this paper; ABB SACE offer: this part offers a panorama of the connection terminals of ABB SACE circuit-breakers: wiring cable terminal-circuit-breaker: making use of userfriendly tables this part gives information about the cable/ bar connection to the ABB circuit-breakers (maximum in relation to the terminal, tightening according to the cable size, etc.). 2 Circuit-Breaker Terminals and Connections ABB
5 1. Components used for wiring Here are described the main components used to connect the circuit-breakers to the electrical plant. The descriptions are limited to the necessary information since these products are not the main subject of this paper. 1.1 Electrical An electrical cable is a component constituted by an assembly of conductors aimed at allowing the current flow. Cables are generally constituted by one or more elements called cores: therefore a cable can be single-core, that is formed by a single core, or it can be formed by more cores (two-core, three-core and multi-core ) enclosed in a protective sheath. Generally a cable used for LV electrical energy distribution is formed by the following elements (not always in a cable used for electrical wiring all these components are necessarily present): conductor: metal part, usually in copper (Cu) or aluminium (Al), intended to carry the current; insulating material: the main function of the insulation is insulating the conductors one from the other and from the exposed conductive part. According to the type of insulation the service and short-circuit temperature changes. In the low voltage field the which are used more can be divided into two main classes: - insulating with elastomeric material (ethylene propylene rubber EPR) - insulating with thermoplastic material (polyvinyl chloride PVC) sheath: the main function of the sheath is protecting the against the external aggression of the environment or of possible chemical agents; besides, in multi-core, the sheath encloses the whole of the different cores; shield: it is constituted of a thin copper strip which has the task of neutralizing the electric fields and the consequent disturbances; armor: the main function of the armor (if present) is protecting the cable against external agents (chemical agents, humidity, mechanical stresses, etc.); usually the armor is constituted by wires or steel or copper strips; filler: it has the function of filling the spaces among the cores of multi-core giving it a round shape; this material is usually constituted of textile fiber. Figure 1- Parts constituting a LV energy distribution cable sheath 2 identification mark 3 shield or armor 4 filler 5 IMQ identification wire or manufacturer mark 6 conductor 5 6 ABB Circuit-Breaker Terminals and Connections 3
6 1. Components used for wiring 1.2 Flexibility of an electrical cable: flexible cable and rigid cable A constructional feature diversifying a cable is its flexibility, namely its manageability. Such peculiarity derives mainly from the characteristic of the conductor in addition to the elasticity of the insulation: a cable formed of single wires is more rigid than a very thin braid of wires (strands). As regards this distinction the conductors have been divided by the Std. IEC into four classes: Class 1: solid conductors Class 2: stranded conductors Class 5: flexible conductors Class 6: flexible conductors which are more flexible than those in Class 5. Classes 1 and 2 refer to rigid conductors intended for fixed installation, more precisely solid and stranded conductors for Class 1 and Class 2 respectively; classes 5 and 6 refer to flexible conductors for use in fixed or mobile installations, more precisely Class 5 for flexible and Class 6 for very flexible. As regards LV energy distribution the more frequently used belong to classes 2 and 5, since the solid conductors of Class 1 represent a solution with limited al areas and therefore they cannot carry the currents involved in power distribution. Extra-flexible are generally intended for a mobile use, where connections subject to continuous bending (for instance in the robotics field) are required. With the same copper al area (to be meant as quantity of copper necessary for a determined current carrying capacity), a flexible conductor has a diameter bigger than a rigid cable (because of the interstices among the thin and numerous copper strands); for this reason the tables in Chapter 3 making reference to a defined terminal - show flexible conductors with maximum al areas smaller than those of rigid *. Example: Class 2 70 mm 2 rigid cable Class 5 70 mm 2 flexible cable able cr ec i XT1 rigid cable mm 2 XT1 flexible cable mm 2 70 mm 2 able cr ec i 50 mm 2 *however, all the s given can carry the maximum rated current of the circuit-breaker Single-core cable with solid conductor Class 1 Single-core cable consisting of a cord of stranded conductors Class 2 Single-core cable consisting of a cord of flexible conductors Class 5 Single-core cable consisting of a cord of extra-flexible conductors Class 6 4 Circuit-Breaker Terminals and Connections ABB
7 1.3 Cable terminals To connect the cable to the typologies of terminals available for molded-case circuit-breakers it is possible to use lugs, so that a good connection of the cable to the circuit-breaker is ensured. Generally, such connectors are obtained from copper or aluminium tubes and those mainly used in electric power distribution, where the s involved may be high, are those with eyelet end since they allow a solid and firm connection to the terminal. However, in applications where the s of the are not particularly big, lugs with tube end compatible with the front terminals for (FCCu) are also used. It is very important to crimp the cable to the terminal (a lug shall hold a power cable only) in the proper way, thus avoiding damages to the strands of the conductor or to part of the insulation; all the conducting material shall be contained inside the lug, taking care to strip only the part accepted by the connector. L D Crimping, that is the operation of fixing the cable to the terminal, shall be carried out so that the cable does not come out of the lug. In fact, if between the crimped lug and the beginning of the stripping there were a longer space, the disconnection of the cable could be possible. ABB SACE recommends the use of lugs with inspection hole so that the proper insertion of the cable can be checked. inserted cable ABB Circuit-Breaker Terminals and Connections 5
8 1. Components used for wiring 1.4 and flexible bars As regards the connections inside electrical switchboards, in some cases the use of the cable can result not suitable for the available space. As a matter of fact, for upper middle powers, the s of the involved, having a high bend radius, make it difficult to assembly the switchboard, but above all reduce the available space inside it, thus causing problems with heat dissipation and air exchange. bars Electric bars (bare or insulated), which are chiefly used for high powers, are rigid bars made of copper or aluminium; for the realization of electrical switchboards pre-punched bars, pre-punched and threaded bars or solid bars are mainly used. Very often it is possible to find colored bars, coated with special paints having particular dissipating properties. In fact such products allow an increase in irradiated heat without causing on the other hand a surface thermal insulation. In these cases both flexible as well as rigid bars are used. bars bars consist of bundles of copper or aluminium strips protected by insulating material (the most common is PVC). The main characteristic of this product is certainly the ease of shaping and this peculiarity does not impose limits on the minimum bend radius; therefore, as already mentioned, they allow a reduction in the overall dimensions, thus making easier the assembly of electrical switchboards. Insulation materials Strips 6 Circuit-Breaker Terminals and Connections ABB
9 2. Description of connection terminals Connection terminals allow the circuit-breaker to be connected to the plant in the most suitable way in relation to the installation requirements. The following terminals can be distinguished: front terminals, which allow the connection of or bars directly from the circuit-breaker front; rear terminals, which allow the installation of the circuitbreakers in segregated switchboards with rear access. A further categorization can be into: terminals for : for the connection of bare copper terminals for the connection of bars and cable lugs. The circuit-breakers of SACE Tmax XT series can be equipped with the following types of terminals: Front terminals (F - Front), intended for the connection of bars and cable lugs: standard supply in the fixed version. These terminals are integral with the fixed/moving contact of the circuit-breaker and do not increase the overall dimensions of the circuit-breaker. Front extended terminals (EF Extended Front), intended for the connection of bars and cable lugs. They are directly fixed to the front terminal F and increase the height of the circuit-breaker. Thanks to their particular form they are suitable for applications where higher heat dissipation is required. If necessary, due to insulation reasons, phase separators are supplied together with the terminal kit. Front extended spread terminals (ES), intended for the connection of bars and cable lugs: fixed directly to the front terminal F. Since they increase the pole pitch of the circuitbreaker, they allow the connection of bars with higher dimensions than those which can be connected to the simple front terminals or the front extended terminals. If necessary, due to insulation reasons, phase separators are supplied together with the terminal kit. Rear terminals orientated (R): intended for the connection of bars and cable lugs. They allow the connection of bars or cable lugs at the rear. They can be installed in 4 different positions (at intervals of 45 ). In the rear terminal kits also low terminal covers are included. FC CuAl front terminals (Cu Al Front Cable): terminals intended for the connection of bare copper and aluminium. Both the conductors of Class 2 (stranded conductors) as well as the conductors of Class 5 (flexible conductors) can be connected to these terminals. The terminal provides one or more holes for the connection of the cable previously stripped. Thanks to a security dowel it is possible to connect the cable complying with the given tightening torque. The dowel has a cone-shaped extremity to make easier the tightening of the different s of the. In the terminals intended for smaller s, the dowel is replaced with a plate which makes easier the tightening of the smallest s. On each terminal the tightening torque values, which depend on the size of the cable to be connected, are directly indicated. It is possible that, for the same terminal, two different values are specified according to the variations in the conductor. There are two types of FC CuAl terminals: standard and external. Standard terminals, once installed, do not increase the total overall dimensions of the circuit-breaker. In some cases standard terminals may require the installation of low terminal covers so that the clearances can be guaranteed. On the contrary, the external terminals, once installed, increase the total height of the circuit-breakers and usually require mounting of high terminal covers (HTC) so that the proper clearances are maintained. The terminal covers, if necessary, are supplied by default with the kit of terminals. FC Cu front terminals: terminals intended for the connection of bare copper. Both the conductors of Class 2 (stranded type) as well as the conductors of Class 5 (flexible type) can be connected to these terminals. These terminals are usually called loop terminals and provide an area to house the cable and a concave plate, whose function is fixing the cable and ensuring tightening. FC Cu terminals can hold in the same housing one or more copper with predefined s. FC Cu terminals are standard, in fact their installation does ABB Circuit-Breaker Terminals and Connections 7
10 2. Description of connection terminals not increase the overall dimensions of the circuit-breaker. Generally it is not necessary to use terminals covers, neither high nor low. Besides, allowing the tightening of flexible or rigid bare copper, FC Cu terminals allow also the connection of the, usually with reduced s, crimped with tube lugs. Front terminals for flexible bars: terminals intended for the connection of flexible bars. From a constructional point of view, these terminals are very similar to the FC Cu front terminals, with an only difference in the plate. In fact, the plate is not concave but has a flat surface to adhere perfectly to the bars. Given the dimension of the single bar, the minimum and maximum number of flexible bars which can be tightened there is indicated in Chapter 3. Multi-cable front terminals: terminals intended for the connection of copper or aluminium. These terminals are particular clamps used to house Cu or Al. Their peculiarity is that on the same terminal there are up to six holes for cable connection. For the tightening of each cable, dowels with conical extremity are used. On each terminal the tightening torque values, which depend on the al area of the cable to be connected, are directly indicated. It is possible that, for the same terminal, two different values of tightening torque are specified according to the variations in the conductor. Multi-cable terminals are typically external, that is they exceed the volume of the circuit-breaker and demand the use of high terminal covers. Terminals F - Frontal FCCuAI - Front terminals for Cu/Al EF - Extended front FB - For flexible bars ES - Front extended spread terminals MC - Multi-cable FCCu - Front terminals for copper R - Rear 8 Circuit-Breaker Terminals and Connections ABB
11 3. Wiring SACE Tmax XT1 Terminali anteriori divaricati F - Frontal EF - Extended front M6 6 Nm. ES - Front extended spread terminals M6 6 Nm. FCCuAl - Front terminal for Cu/Al internal external M5 5 Nm. M6 6 Nm. FCCu - Front terminals for Cu FB - For flexible bars MC - Multi-cable M6 6 Nm. Figure showing the circuit-breaker with its terminals and the tightening of the terminals to the circuit-breaker. R - Rear M5 5 Nm. ABB Circuit-Breaker Terminals and Connections 9
12 3. Wiring Tmax XT1 Cables/Bars FCCuAl FCCu MC Multi FB bars 30 mm 16 mm 16 mm 24 mm 12 mm 20 mm 10 mm Cu/AI Cu/AI Cu/AI Cu Cu No. of bars Section Terminal 7 Nm 1x x x x x x x mm Ø 14 mm Ø 24 mm Ø 8 mm 12 mm 7 Nm 13.5 Nm 31 Nm 6x Min. 2 6x Max 9 10x mm 11.5 mm Installation requirement* 9.6 mm Typology Internal External Internal External Internal 12 mm 7 Nm 50 mm 50 mm 7 Nm Supply on request Phase separator 100 mm n n n 200 mm n n n Terminal cover 50 mm n n n The terminals ES, FCCuAI, FCCu, FB and MC can be used also with plug-in version thanks to the following adapter: Fixed part adapter Plug-in circuit-breaker * phase separators are always delivered with the circuit-breakers. 10 Circuit-Breaker Terminals and Connections ABB
13 F Front terminals EF Front extended terminals ES Front extended spread terminal R Rear orientable terminals Maximum overall dimensions Maximum overall dimensions Maximum overall dimensions Ø6.5 Ø8.5 Ø8.5 Ø Ø6.5 Ø8.5 Ø Ø Bars/Cable lugs Bars/Cable lugs Bars/Cable lugs Bars/Cable lugs Supplied Suggested Suggested Suggested 6 M6 9 M8 9 M8 6 M6 Internal External Rear 100 mm 200 mm 20 mm n n n n n For fixed part of plug in version, the following standard connections are available: HR-VR Rear orientable terminals EF - Front extended terminals 100 mm Ø8.5 Ø 6 Ø8.5 Ø Suggested Suggested 9 M8 9 M6 ABB Circuit-Breaker Terminals and Connections 11
14 12 Circuit-Breaker Terminals and Connections ABB
15 3. Wiring SACE Tmax XT2 F - Frontal EF - Extended front M6 6 Nm. ES - Front extended spread terminals M6 6 Nm. FCCuAl - Front terminal for Cu/Al internal external M6 6 Nm. FCCu - Front terminals for Cu FB - For flexible bars MC - Multi-cable M6 6 Nm. R - Rear Figure showing the circuit-breaker with its terminals and the tightening of the terminals to the circuit-breaker. M5 5 Nm. ABB Circuit-Breaker Terminals and Connections 13
16 3. Wiring Tmax XT2 Cables/Bars FCCuAl FCCu MC Multi 30 mm 14 mm 20 mm 24 mm 33 mm 18 mm 14 mm 20 mm 10 mm Cu/AI Cu/AI Cu/AI Cu/AI Cu Cu x x Terminal x x x x Nm 14 mm Ø 18 mm Ø 24 mm Ø 16 mm Ø 8 mm 14 mm 25 Nm 31 Nm 12 Nm 7 Nm Installations requirement* 14 mm Typology Internal External Internal External 50 mm 60 mm 50 mm 14 mm 7 Nm Supply on request Phase separator 100 mm n n 200 mm n n Terminal cover 50 mm n n The terminals ES, FCCuAI, FCCu, FB and MC can be used also with plug-in and withdrawable version thanks to the following adapter: Fixed part adapter Plug-in circuit-breaker Withdrawable * phase separators are always delivered with the circuit-breakers. 14 Circuit-Breaker Terminals and Connections ABB
17 FB bars F Front terminals EF Front extended terminals ES Front extended spread terminal R Rear orientable terminals Maximum overall dimensions Maximum overall dimensions Maximum overall dimensions Ø6.5 Ø8.5 Ø10.5 Ø Ø6.5 Ø8.5 Ø Ø No. of bars Section Bars/Cable lugs Bars/Cable lugs Bars/Cable lugs Bars/Cable lugs Min. 2 10x0.8 Supplied Suggested Suggested Max 9 6 M6 9 M8 18 M10 9 M8 Suggested 14 mm Internal Internal External Rear 100 mm 200 mm 20 mm n n n n n n n n For fixed part of plug in and withdrawable version, the following standard connections are available: HR-VR Rear orientable terminals EF - Front extended terminals 100 mm 14 mm 7 Nm Ø8.5 Ø 6 Ø8.5 Ø Suggested Suggested 9 M8 9 M6 ABB Circuit-Breaker Terminals and Connections 15
18 16 Circuit-Breaker Terminals and Connections ABB
19 3. Wiring Terminali anteriori divaricati SACE Tmax XT3 F - Frontal EF - Extended front M6 6 Nm. ES - Front extended spread terminals M6 6 Nm. FCCuAl - Front terminal for Cu/Al internal external M6 6 Nm. FCCu - Front terminals for Cu FB - For flexible bars MC - Multi-cable M8 8 Nm. R - Rear Figure showing the circuit-breaker with its terminals and the tightening of the terminals to the circuit-breaker. M5 5 Nm. ABB Circuit-Breaker Terminals and Connections 17
20 3. Wiring Tmax XT3 Cables/Bars FCCuAl FCCu MC Multi 20 mm 20 mm 24 mm 42 mm 22 mm 12 mm 30 mm 15 mm Cu/AI Cu/AI Cu/AI Cu/AI Cu Cu x6 70 6x Terminal 1x x x x x mm 18 mm Ø 24 mm Ø 18 mm Ø 8 mm 18 mm 31 Nm 16 Nm 31 Nm 16 Nm 14 Nm 7 Nm 6x mm 18 mm Installations requirement* Typology Internal External Internal External 60 mm 60 mm 18 mm Supply on request Phase separator 100 mm n n 200 mm n n Terminal cover 60 mm n n The terminals ES, FCCuAI, FCCu, FB and MC can be used also with plug-in version thanks to the following adapter: Fixed part adapter Plug-in circuit-breaker * phase separators are always delivered with the circuit-breakers. 18 Circuit-Breaker Terminals and Connections ABB
21 FB bars F Front terminals EF Front extended terminals ES Front extended spread terminal R Rear orientable terminals Maximum overall dimensions Maximum overall dimensions Maximum overall dimensions Ø8.5 Ø10 Ø10.5 Ø Ø8.5 Ø10 Ø Ø No. of bars Section Bars/Cable lugs Bars/Cable lugs Bars/Cable lugs Bars/Cable lugs Min. 2 16x0.8 Supplied Suggested Suggested Max 10 8 M8 18 M10 18 M10 9 M8 Suggested Internal Internal External Rear 100 mm 200 mm 20 mm n n n n n n n n For fixed part of plug in version, the following standard connections are available: HR-VR Rear orientable terminals EF - Front extended terminals 100 mm 18 mm 12.5 mm 14 Nm Ø8.5 Ø 8.5 Ø8.5 Ø Suggested Suggested 9 M8 18 M8 ABB Circuit-Breaker Terminals and Connections 19
22 20 Circuit-Breaker Terminals and Connections ABB
23 3. Wiring SACE Tmax XT4 Terminali anteriori divaricati F - Frontal EF - Extended front M6 6 Nm. ES - Front extended spread terminals M6 6 Nm. FCCuAl - Front terminal for Cu/Al internal external M6 6 Nm. FCCu - Front terminals for Cu FB - For flexible bars MC - Multi-cable M M6 6 Nm. Figure showing the circuit-breaker with its terminals and the tightening of the terminals to the circuit-breaker. R - Rear M Nm. ABB Circuit-Breaker Terminals and Connections 21
24 3. Wiring Tmax XT4 Cables/Bars FCCuAl FCCu MC Multi FB bars 21 mm 42 mm 22 mm 24 mm 12 mm 30 mm 15 mm Cu/AI Cu/AI Cu/AI Cu Cu No. of bars Section Terminal 10 Nm 1x2.5x 150 1x2.5x 185-2x Ø 18 mm 17 mm Ø 24 mm 16 Nm 31 Nm - 1x Nm 1x x6 70 1x mm Ø 8 mm 7 Nm 6x Min. 2 6x Max 10 16x mm 18.5 mm 17 mm 18 mm Installation requirement* Typology Internal External Internal External Internal 60 mm 60 mm 14 Nm Supply on request Phase separator 100 mm n n n 200 mm n n n Terminal cover 60 mm n n n The terminals ES, FCCuAI, FCCu, FB and MC can be used also with plug-in and withdrawable version thanks to the following adapter: Fixed part adapter Plug-in circuit-breaker Withdrawable * phase separators are always delivered with the circuit-breakers. 22 Circuit-Breaker Terminals and Connections ABB
25 F Front terminals EF Front extended terminals ES Front extended spread terminal R Rear orientable terminals Maximum overall dimensions Maximum overall dimensions Maximum overall dimensions Ø8.5 Ø10 Ø10.5 Ø Ø8.5 Ø10 Ø Bars/Cable lugs Bars/Cable lugs Bars/Cable lugs Bars/Cable lugs Supplied Suggested Suggested Suggested 8 M8 18 M10 18 M10 9 M8 Internal External Rear 100 mm 200 mm 20 mm n n n n n For fixed part of plug in and withdrawable version, the following standard connections are available: HR-VR Rear orintable terminals EF - Front extended terminals 100 mm Ø Ø8.5 Ø 8.5 Ø8.5 Ø Suggested Suggested 9 M8 18 M8 ABB Circuit-Breaker Terminals and Connections 23
26 Annex A The following tables are extracts from the Std. IEC Table A1 Approximate relationship between mm2 and AWG/kcmil Rated mm 2 AWG/kcmil size Equivalent metric area mm k cmil k cmil k cmil k cmil k cmil k cmil 304 Table A2 Test copper conductors for test currents up to 400 A inclusive Range of test current Conductor size A mm 2 AWG/k cmil k cmil k cmil k cmil k cmil k cmil Table A2 Test copper conductors for test currents above 400 A and up to 800 A Range of test current A Metric Conductors k cmil Number Size mm 2 Number Size k cmil Table A2 Test copper conductors for test currents above 400 A and up to 3150 A Range of test current A Copper bars Number Dimensions mm 2 Dimensions (inches) x5 1x x5 1.25x x5 1.5x x5 2x x5 2.5x x5 3x x5 3x x5 3x x10 6x Circuit-Breaker Terminals and Connections ABB
27
28 Contact us ABB SACE A division of ABB S.p.A. L.V. Breakers Via Baioni, Bergamo - Italy Tel.: Fax: The data and illustrations are not binding. We reserve the right to modify the contents of this document on the basis of technical development of the products, without prior notice. Copyright 2011 ABB. All rights reserved. 1SDC007406G /2011
Copper and Aluminum busbars
Copper and Aluminum busbars Two metals are currently used as conductors in electric panel boards: copper and aluminum In particular, when in need to define a power distribution inside an electric panel
4 Technical Application Papers
4 Technical Application Papers December 2006 ABB circuit-breakers inside LV switchboards 1SDC007103G0202 ABB circuit-breakers inside LV switchboards Index Introduction... 2 1 Problems of overheating inside
INTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
Unarmored Variable Frequency Drive (VFD) Cable Termination Guide
Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored
CONFLEX ELECTRIC CABLE
CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard
New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager
New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager 2 1SDC200039B0201 New SACE Emax 2 for UL 1066 Circuit breakers switch power SACE Emax 2 manages it. SACE Emax 2 is the new benchmark of
ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket
Technical Datasheet SNK64D00 Catalogue Page SNK64S00 ZS4-S-T Screw Clamp Terminal Blocks Disconnect with blade - with test socket - Ease your test operations with the built-in test sockets, - Screwdriver
Operating Instructions
Operating Instructions Cable Glands Ex d and Ex e with Compound > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4
WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS
CONDUCTORS Conductors are needed to complete the path for electrical current to flow from the power source to the working devices and back to the power source. Special wiring is needed for battery cables
FIRE RESISTANT CABLE CONSTRUCTION OF CABLES
FIRE RESISTANT CABLE In all fire disasters, fire smoke, heat and toxic fumes are the main obstacles to safe evacuation of a building or area. A major contribution towards overcoming these hazards is the
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
ZS6-S Screw Clamp Terminal Blocks Disconnect with blade
Technical Datasheet SNK646D00 Catalogue Page SNK646S00 ZS6-S Screw Clamp Terminal Blocks Disconnect with blade - Ease your disconnect operations with the disconnect blade operated by hand or with a screwdriver,
ELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
VIPERFLEX ELECTRIC CABLE
VIPERFLEX Flexible Low Voltage Electric Cable - 0.6/1kV (Rubber insulated) H07 RN-F & H07 BN-F Single Core 2-Core 2-Core and Earth 3-Core and Earth 4-Core and Earth Multi-Core and Earth H07 RCN-F & H07
Technical catalog - Edition 2015. SACE Tmax PV Adaptability, versatility and complete freedom continue
Technical catalog - Edition 205 SCE Tmax PV daptability, versatility and complete freedom continue SCE Tmax PV automatic molded case circuit-breakers and molded case switch-disconnectors The Tmax PV line
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
ELEVATOR TRAVELING CABLE - DESIGN EVOLUTION
ELEVATOR TRAVELING CABLE - DESIGN EVOLUTION by Richard Laney Introduction Elevator traveling cable is a vital link between the elevator car and controller. In conventional elevators, all power and signal
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
ACTIV-8 PLUS Insulated Conductor Bar
ACTIV-8 PLUS Insulated Conductor Bar A product made in Australia www.conductix.com.au ACTIV-8 PLUS ACTIV-8 is the most widely used and stocked conductor rail in use in Australia. It was designed by Conductix
Fault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
Figure 1 (end) Updated document to corporate requirements Added text to Paragraph 2.4
This specification covers the requirements for application of ELCON Drawer Series Connectors: True Hot Plug, Blind Mating Mixed Signal and Power Connectors. These connectors are designed for use in pluggable
V REG.-Nr. 115719, Z E135149 Technical data 2-pole 4-pole Rated current 12 A 6 A SCHRACK. Accessories Miniature Relay PT. General Purpose Relays
Accessories Miniature Relay PT Easy replacement of relays on a densely packed DIN rail No reduction of protection class or creepage/clearance with plastic retainer Plug-in indicator- and protection modules
David O Brien, CMP Products ([email protected])
David O Brien, CMP Products ([email protected]) 1) Main Function of Cable Glands 2) Common Issues with Cable Glands 3) Compliance / Standards, changing times 4) How do we select Cable Glands?
Environmental Product Declaration. Registration number: S-P-00047. Rev. 0 11/06/03. Tmax T1. Low voltage circuit breaker.
Environmental Product Declaration Registration number: S-P-00047 Rev. 0 11/06/03 Tmax T1 Low voltage circuit breaker ABB SACE SpA Information about the company and the product This document aims to provide
ZS4-SF1-T Screw Clamp Terminal Blocks For 5 x 20 and 5 x 25 fuses - with test socket
Technical Datasheet SNK636D00 Catalogue Page SNK636S00 ZS-SF-T Screw Clamp Terminal Blocks For x 0 and x fuses - with test socket - Protect your circuit with x and x0 fuse terminal blocks (fuse not supplied
5.2. Overview. The better method to install solderless compression connectors on power cable
5.2 Overview The better method to install solderless compression connectors on power cable The Thomas & Betts method of installing compression connectors on power cables is designed to provide a high degree
INSTALLATION INSTRUCTIONS: Viewline 52 mm
-5 Safety information The product was developed, manufactured and inspected according to the basic safety requirements of EC Guidelines and state-of-the-art technology. The instrument is designed for use
ZS25 Screw Clamp Terminal Blocks Feed-through
Technical Datasheet SNK668D0 Catalogue Page SNK678S0 ZS Screw Clamp Terminal Blocks Feed-through Save space by connecting conductors up to mm² AWG in just mm 0.47 in spacing. SNK68V004 SNK004F0000 D CAD
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
Directory chapter 02 - DIN Power (to 6 A) Types D, E, F, FM, 2F, F9, interface connectors I/U 02. 01. Technical characteristics types D and E... 02.
Directory chapter 02 - () Types D, E, F, FM, 2F, F9, interface connectors I/U Page Technical characteristics types D and E.............................. 02.10 Type D connectors.................... 02.11
Solar Kit. Complete solution to optimize your photovoltaic system
Solar Kit Complete solution to optimize your photovoltaic system April 2012 Mounting and selection quick guide On Grid Solar Kit rooftop installation INSTALLATION WITH OVERLAID SUB-STRUCTURE (A.1, A.2)
4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters
8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article
Digital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
RE-ENTERABLE SPLICE CLOSURE KITS. (For Air Core None Pressurized Cable)
Triple T Broadband Public Co., Ltd. Outside Plant Standard Sector Specification No. OES-001-027-04 Issued: RE-ENTERABLE SPLICE CLOSURE KITS (For Air Core None Pressurized Cable) 1. SCOPE 1.1. This specification
A product made in Australia. Insulated Conductor Rail ACTIV-8 PLUS
A product made in Australia Insulated Conductor Rail ACTIV-8 PLUS ACTIV-8 PLUS The Industry Standard in Conductor Rails ACTIV-8 is the most widely used and stocked conductor rail in use in Australia. It
Checklist Testing and inspection without interconnection
Shams Dubai Checklist Testing and inspection without interconnection Version.0 AUGUST 205 TABLE OF CONTENTS Scope...5. PV PLANT AND INSPECTION DATA... 6 2 TESTING EQUIPMENT...7 3 DOCUMENTS... 8 3. Reference
ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application
ENERGY TECWATER S1BN8-F 0,6/1 kv Cable for Water Application Technical Data Electrical parameters Thermal parameters Trademark Type designation Specification Approval Application Rated voltage Maximum
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
Product and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits
ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS
Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document
Directory chapter 04
M Directory chapter 04 D-Sub Mixed subminiature D connectors New Page D-Sub mixed connector system general information................... 04.02 Contact arrangements............................................
EARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
Valu Guide Sheaths. Valu Guide Inserts. Optional Valu Guide Inserts. Typical Properties of Valu Guide Rail. and Hardware.
14 gauge stainless steel The Original, Long Life Sanitary Guide Rail Valu Guide rail incorporates two outstanding materials: stainless steel and UHMW. The 14 ga. stainless steel sheath provides rigid streamlined
AMPSEAL* Automotive Plug Connector and Header Assembly
AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2
SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
Depending on which elastic support you have you can secure the V2 power unit to the following seat bracket tubes: EXTERNAL DIAMETER 27.
ASSEMBLY 1 - EPS V2 POWER UNIT (SOLUTION 5) 1.1 - POSITIONING INSIDE THE SEAT TUBE WITH ELASTIC SUPPORT IN THE SEAT BRACKET TUBE Depending on which elastic support you have you can secure the V2 power
Industrial circular connectors
Industrial circular connectors M 16 M 58 010 CONINVERS - M16 to M58 circular connectors for industrial applications CONINVERS GmbH, an independent company, is the specialist for M16 to M58 circular connectors
6000 Series Buccaneer
Robust, instant connections for harsh environments 6000 Series Buccaneer - circular connectors that combine the ease of use of a push/pull coupling mechanism with proven environmental sealing. Available
Network Standard Advice No. 1420C 9/6/2011
Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides
20000068 WIRELESS REMOTE ASSEMBLY, 24VDC, 1 TRANS,1 REC
20000068 WIRELESS REMOTE ASSEMBLY, 24VDC, 1 TRANS,1 REC Fitment to MP-25 620 CR 4841, Haslet, TX 76052 Ph 817.439.1108 Fax 817.636.5675 www.machine-technologies.com Kit contents 1 Transmitter 2 button,
BNC, N, TNC Connectors
BNC, N, TNC Connectors ONLINE CATALOG AEP BNC, N, and TNC series connectors are specifically designed for use with miniature flexible and semi-rigid cable. They are available with goldplated or nickel-plated
LIEBERT VNSA Installation Sheet
LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
Basic Cable Assemblies DELIVERING QUALITY SINCE 1952.
Basic Cable Assemblies DELIVERING QUALITY SINCE 1952. Cable Types Cable Types Hook-up & Lead Wire Most Basic 2 Cable Types Cable Types Twisted Pair Cable A type of cable that consists of two independently
Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
Universal Vehicle Power Supply 9007AX01. Installation Instructions
Universal Vehicle Power Supply 9007AX01 Installation Instructions Disclaimer Honeywell International Inc. ( HII ) reserves the right to make changes in specifications and other information contained in
08. SEK IDC CONNECTORS
. IDC CONNECTORS connectors for flat cables enable simple and, cost-optimized device configuration. connectors are preferably used for connection within the device. HARTING offers a broad range of these
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
RAUFOSS EXPLOSIVE COMPRESSION FITTINGS
INSTRUCTION MANUAL FOR RAUFOSS EXPLOSIVE COMPRESSION FITTINGS Box 7 2831 Raufoss Norway Tlf.: +47 61 15 17 87 Fax: +47 61 15 25 56 25 January 2013, rev 2 Available on www.vpmetall.no Page 1 CONTENTS GENERAL
Amphenol C 091 A/B/D. Circular Connectors. Amphenol-Tuchel Electronics GmbH
Amphenol C 091 A/B/D Circular Connectors Amphenol-Tuchel Electronics GmbH C 091 A Main Features Metal threaded coupling acc. to IEC. Number of contacts are 2 to 8, 12 and 14. Internal metal strain relief
HARTING Ethernet Cabling 4-poles Overview
Overview RJ45 Connectors [on page 8] System cables [on page 10] Distribution modules and Outlets [on page 20] HARTING PushPull Connectors [on page 22] System cables [on page 24] Panel feed-throughs [on
SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM
Pyrotenax SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM Contents Introduction This section provides an overview of general circuit design considerations and installation guidelines for a Pyrotenax System
NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS
SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications
ScottishPower Distribution Cables & Equipment. Metal Theft
ScottishPower Distribution Cables & Equipment Metal Theft April 2012 As an aid to deterring to metal theft this booklet has been put together to help identify the types of utility power cables and associated
www.axon-cable.com Power distribution systems
www.axon-cable.com Power distribution systems Power distribution systems As vital components for electrical power distribution in telecommunication satellites and landbased weapon systems, the bus and
COB panel supports for multipole connectors
TCQ + TSFS (...CMS, alternative) CMS TSFS Use The system makes it possible to use multipole connectors within electric panels without the traditional metallic housing as protection is assured by the electric
Standard Buccaneer - Ethernet
IP6 rated compliant PUR jacket on cable Shielded system shielded coupler Shroud on RJ45 Screw coupling Rewireable flex connector PCB mounted panel connector IDC termination panel connector Earth lead version
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
Explosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
P System Cubicles. Certified for more safety
P System Cubicles Prisma Plus LV Switchboards Certified for more safety Prisma Plus, an offer thought out for greater professionalism With the Prisma Plus P system, Schneider Electric proposes high-performance
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
XL PREMIUM OIL COOLER KIT
-J05 REV. 0-0-0 XL PREMIUM OIL COOLER KIT GENERAL Kit Number 0008 Models For model fitment information, see the P&A Retail Catalog or the Parts and Accessories section of www.harley-davidson.com (English
e-mobility Special cables for electric vehicles Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies
www.echtzeit.com e-mobility Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies Special cables for electric vehicles Wittener Straße 271 D-42279 Wuppertal Phone +49(0)202.2681.228 Fax +49(0)202.2681.360
Gulf Cable & Electrical Ind. Co.
CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC
Cables. Accessories. For Force, Torque and Strain Sensors
Accessories Cables For Force, Torque and Strain Sensors Charge mode, high impedance piezoelectric measurement demands highly insulated coaxial cables and connectors to ensure an insulation resistance greater
General Purpose Relays Accessories. Accessories Miniature Relay PT
Miniature Relay PT n Easy replacement of relays on a densely packed DIN rail n No reduction of protection class or creepage/clearance with plastic retainer n Plug-in indicator- and protection modules n
Corporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS
Corporate Profile MODERN ROYAL ELECTRIC Ideal Power Solution ROYAL MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS MAJOR STOCKIST >>> CATHODIC PROTECTION CABLES >>> LOW VOLTAGE CABLES >>> MEDIUM
Arbiter Systems Test Leads: Engineered for Optimum Performance and Safety
Arbiter Systems Test Leads: Engineered for Optimum Performance and Safety Arbiter Systems, Inc. test equipment offers outstanding performance, flexibility, and value. Our test leads offer nothing less.
Jumper bar BJM. Assembled jumper bar BJD. Assembled jumper bar
BJ Jumper bar Use the BJ jumper bar to connect consecutive and nonconsecutive terminal blocks with the same spacing. Two types of jumper bars are available : an assembled unit and a nonassembled unit.
NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.
HARTING Ethernet Cabling 8-poles Overview
Ethernet Cabling 8-poles Overview RJ45 Connectors [on page 8] System cables [on page 12] Distribution modules and Outlets [on page 17] Connectors [on page 20] System cables [on page 26] Panel feed-throughs
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED
SENTRON Switching and Protection Devices Air Circuit Breakers
Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General
white paper Ferrules: Your Best Insurance Against Costly Connection Failure Executive Summary
Ferrules: Your Best Insurance Against Costly Connection Failure white paper Executive Summary Thanks to its superior flexibility, longer flex life*, and resistance to vibration, insulated stranded wire
Installation Manual. BYD Wall-mounted AC Charging Box
Installation Manual BYD Wall-mounted AC Charging Box BYD Wall-mounted AC Charging Box Installation Manual Version/Revision: A/0 Dedicated Service Commitment from BYD Auto Dear valuable customers: We are
Cable Guide. Cables, Connectors & Tools for installation of quality networks. TRIAX - your ultimate connection
Cable Guide Cables, Connectors & Tools for installation of quality networks TRIAX - your ultimate connection A Selection of the best Triax TX Cable range optimised for digital reception Simplification
Installation Guide of Sunrise Solartech PV Modules. Term 2013. Contents. Purpose of this guide. General. Safety precaution for installing a solar
Installation Guide of Sunrise Solartech PV Modules Term 2013 Contents Purpose of this guide General Safety precaution for installing a solar Photovoltaic system Product Identification Mechanical Installation
FLEXIBLE COPPER & ALUMINIUM CONNECTIONS. Product Range 1 VGL - ALLIED CONNECTORS
Product Range ROUND STRANDED COPPER CABLE Electrolytic Copper / Oxygen Free Copper Conforms to DIN 46438 Standards Finish: Bare Copper / Tinned / Silver-plated ROUND BRAID / ROUND STRANDED CABLE WITH OVERALL
Quick Connect Boxes Inside Gloveboxes
ULC Series Junction Boxes Quick Connect Boxes Inside Gloveboxes The ULC quick connect junction boxes are the essential elements to optimize the cabling inside gloveboxes. Large range Designed for nuclear
USB 3.0 Cables. Color. Black Black Black Black Black 3021003-03 3021009-06 3021015-10 3021021-16 3021027-16. Black Black Black Black Black
USB.0 CableS USB.0 and backwards compatible for USB.0 and. Supports high speed, 480Mbps Twisted-pair construction reduces cross talk to ensure error free transfer USB A male to USB B male 00-0 007-0 0-09-
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
User s Manual. BNC Mini-High Res, 75 Ohm Termination Kit Connector Installation Guide (60-073-01)
User s Manual BNC Mini-High Res, 75 Ohm Termination Kit Connector Installation Guide (60-073-01) BNC Termination Kit Instructions This document is a compilation of Extron s instructions, together with
RF & Microwave cable assemblies C291
ERTIFIED C AS 9100 RF & Microwave cable assemblies C291 B CONTENTS Pages Introduction... B-4 Specify the right cable for your application... B-5 Finder guide cables vs insertion loss... B-6 to B-7 Flexible
Comparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
Cutting and stripping tools
Cutting and stripping tools Introduction 2 Cutting and stripping tool 0.02-10 mm² (16 mm²) 3 Stripping tool for cables Ø 2.5-40 mm 4 Tools for cutting and stripping of conductors 0.5-6 mm² and for cutting
ZS10 Screw Clamp Terminal Block
Technical Datasheet 1SNK 161 004 D0201 ZS10 Screw Clamp Terminal Block Feed-through Catalogue Page 1SNK 161 004 S0201 10 mm² 6 AWG 8 mm 0.315 in Spacing Features and Benefits 53 2.09" Save space by connecting
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,