Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable

Size: px
Start display at page:

Download "Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable"

Transcription

1 Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable Dr. Uchida Katsumi*, Youichi Katou*, Dr. Hiroyuki Kon, Dr. Kazuo Watanabe and Takenori Tokutake Water-tree deterioration in XLPE cable is one of the factors that reduce breakdown strength. To assure stable power supply, an effective technique has been needed to estimate the degree of the water-tree deterioration in XLPE cable. We have been investigating the application of the residual-charge technique for this purpose. We have confirmed the effectiveness of the residual-charge technique on the diagnosis for water-tree deteriorated XLPE cables, and possibility of application of oscillating wave (OSW) to the residual-charge technique, which is effective on the field measuring because it leads to downsizing of the apparatus. We also propose a new technique to estimate the degree of watertree deterioration. This technique could make it possible to detect the existence of the localized and heavy water tree deterioration in XLPE cable. 1. Introduction It is well known that there is a possibility of watertrees formation in cable insulation, if cross-linked polyethylene (XLPE) cable is used under the wet conditions for a long time. Water trees influence the dielectric performance in XLPE cable such as breakdown strength. It has been about 3 years, which is thought as a life span of XLPE cable, since XLPE cable without water impervious layer started to be used 1). The possibilities of water-tree formation and degradation of breakdown voltage due to its formation are considered in case of old fashioned and poor manufacturingprocess-cables subjected to a long-term immersion in water and service aging. The development of the method to estimate the degree of water-tree deterioration in XLPE cable has been highly necessitated. There are currently several methods to estimate the degree of deterioration due to water trees. It has been reported that conventional methods such as leakage current,tan δ etc. are difficult to apply to 22 to 33 kv XLPE cable and that the estimated value has little correlation with breakdown voltage. On the other hand, new methods have been proposed to solve the problem. We have been investigating the residual-charge technique as a method for diagnosing for water-tree deterioration of XLPE cable. The effectiveness of the residual-charge technique and new estimation techniques are reported. * Chubu Electric Power Co., Inc. 2. Principle of Residual-charge Technique Fig.1 and 2 show the principle of this method and the pattern of voltage application, respectively 2). DC voltage is applied to a cable as a pre-stress. Charges DC high voltage generator 6.6kV : 15kV 22 kv : 3kV R AC testing transformer Low-pass filter Cable Fig. 1. Principle of Residual-charge Technique. 5min DC Cd Rd ~ 1kV/s 1min 4s AC Output ~ 1kV/s Fig. 2. Pattern of Applied Voltage in Residual-charge Measurement. Fujikura Technical Review, 21 65

2 are accumulated in water trees by DC voltage application. AC voltage is applied to it after short-circuiting. Charges accumulated in water trees are released during AC voltage application, which produce a DC current component. Though the current flowing during AC voltage application includes both AC and DC current components, DC component can be detected by using a low-pass filter. Fig.3 shows a typical result. Such a current signal shown in Fig.3 can be detected if the XLPE cable contains water trees. The residual charge is obtained by integration of a current signal. 3. Experimental 3.1 Samples Test cables were prepared by frequency-accelerated aging with hot-water immersion by using XLPE insulated cable of 6.6 kv with conductor of 6 mm 2 and 22 kv with conductor of 2 mm 2. The details of the accelerated aging conditions are listed in Table 1. For convenience, we classified the samples as Type 6-1 ~ 6-4 and Type 22- and The water-tree distributions of the samples aged as above are shown in Fig.4. All of the water trees observed in the samples were bow-tie type. It can be said that the degree of deterioration of is higher than that of, because the total number of water trees increases as aging time. Classification Table 1. Conditions of Frequency Acceleration Condition of applied voltage Condition of temperature (Equivalent time to 6 Hz) 6.6kV XLPE cable / 6mm 2, t = 4 mm, length of the cable : 1 m, length of immersed region in hot water : 4. m Type 6- Frequency : 11,98 1-3kHz Applied voltage : 8 C 36,53 1kV 55, ,583 22kV XLPE cable / 2mm 2, t = 7 mm, length of the cable : 2 m, length of immersed region in hot water : 4. m 1 1 Type 22- Frequency : 1-3kHz 8 C Applied voltage : 2kV 37,3 Current (na) 5 5 Charge (nc) Table 2. Conditions of Residual-charge Measurement Classifications DC voltage AC voltage Pattern of AC voltage application 12 Time (s) Fig. 3. Example of Residual-charge Measurement. 6.6kV XLPE cable 22kV XLPE cable 15kV/5min 3kV/5min 3.8kV 12.7kV Increasing rate of AC voltage : 1kV/s Keeping time of AC voltage : 6s. Decreasing rate of AC voltage : 1kV/s 5, Number of water trees 4, 35, 3, 25, 2, 15, 1, 5, 21~5 11~2 31~4 Number of water trees 4, 3, 2, 1, 21~5 11~2 31~4 Type 22- Classification of water tree length ( m) (a) 6.6kV CV Classification of water tree length ( m) (b) 22kV CV Fig. 4. Distribution of Water Trees in Frequency-accelarated Aged Cable. 66

3 3.2 AC Breakdown Test Conditions AC breakdown tests were carried out at about 8 C. 3.3 Residual-charge Measurement Residual charge was measured basically under the conditions listed in Table Results 4.1 AC Breakdown Tests The results of AC breakdown tests are shown in Fig.5. Breakdown voltage decreased with aging time. Aging time means the equivalent time to service frequency. As mentioned above, cables were deteriorated by water trees as aging time, therefore, the decrease in breakdown voltage is thought to correspond to water-tree deterioration. 4.2 Residual-charge Measurement The aging time dependence of residual charge is shown in Fig.6. Residual charge was first observed in, and increased with aging time. This tendency was also observed in the Type 22 samples. AC breakdown field strength (kv/mm) Residual charge (nc) Type 6- Type 22-2, AC testing was carried out at 8 C 6.6kV cable 22kV cable 4, 6, 8, 1, 12, 14, Fig. 5. Agingt Time vs. AC Breakdown Field Strength Type 6- Type kV : DC 15kV/5min, AC3.8kV 22kV : DC 3kV/5min, AC12.7kV 2, 4, 6, 8, 1, 12, 14, Fig. 6. Aging Time vs. Residual Charge. Considering the time dependence of the distribution of water trees in these samples, the tendency of residual charge with aging time corresponds to the deterioration due to water trees. 4.3 Correlation of Residual Charge and Breakdown Strength Fig.7 shows the correlation between residual charge and breakdown field strength of the 6.6 kv and 22 kv XLPE cable. Residual charges shown in Fig.7 are measured with AC field strength of 1. kv/mm. Despite the different rated voltage of cable, 6.6 kv and 22 kv, residual charge has a good correlation with breakdown field strength. This indicates that the residual-charge technique is an effective method for diagnosing water-tree deterioration in XLPE cable. 5. Residual-charge Technique in Field Diagnosis 5.1 Application of Oscillating Wave (OSW) to Residual-charge Measurement It is necessary to prepare the AC high-voltage source with quite large electrical capacity, which becomes physically large, to measure residual charge of the cables spanning a few km. The size of AC high-voltage source is one of the factors that make the residual-charge measurement in field difficult. We investigated the possibility of substituting an oscillating wave (OSW) for AC voltage source. It is expected to be effective on field measurement because electrical capacity of OSW generator is smaller which leads to more compact equipment than the AC high-voltage generator of service frequency. Applying OSW to residual-charge technique, some drawbacks have to be resolved, such as the effect of OSW on water trees. It has been reported that OSW application to water-tree deteriorated XLPE cable has a possibility to initiate an electrical tree from a water tree 3). AC breakdown field strength (kv/mm) Residual charge (nc) 6.6kV : 6mm 2 22kV : 2mm 2 Fig. 7. Residual Charge vs. Breakdown Field Strength. 4 5 Fujikura Technical Review, 21 67

4 1 water electrodes 2mm 2mm 1 water electrodes Outer semiconducting layer Thickness of insulation : 3mm 2mm 1mm XLPE Inner semiconducting layer Conductor Fig. 8. Location of Water Tree Modeled Electrodes. 3 Table 3. Results and Conditions of Investigation on OSW Voltage (kv) Classification Tno.1 Tno.2 Sample Depth Number of locations Test conditions Occurrence of electrical tree from water electrode 1mm 1 1 kv (peak voltage) 1mm No 2mm 1 1, times 2mm No 1mm 1 1 kv (peak voltage) 1mm No 8 times increasing at a 2mm 1 rate of 1kV/1 times 2mm Yes Time (ms) Fig. 9. Applied OSW Waveform Effect of OSW on Water Trees (1) Samples We prepared the sample cables with water electrodes modeled on a water tree generated from the outer semiconducting layer 3). The procedures are as follows, q Treeing needle is pricked from the outer semiconducting layer into cable insulation to the depth of about 1mm and 2mm. w Treeing needle is drawn out in water. e AC voltage is applied to the cable given the above treatment under the condition of 1kVrms for 24 hrs. in water of 8 C. The details of the prepared sample are shown in Fig.8. (2) Experimental The OSW shown in Fig.9 was applied repeatedly to the sample prepared as described above to investigate the effect of the OSW on the water trees in cable insulation. The effect on the water trees is determined by monitoring the sliced samples for occurrences of electrical trees initiated from water trees. (3) Results The results are listed in Table 3. No breakdown and electrical trees from water electrodes were observed after 1, times applications of OSW with a peak voltage of 1 kv. This indicated that OSW application with a peak of 1kV has no effect on water trees with a length below 2. mm from the outer Fig. 1. Electrical Tree from Tip of Water Electrode. semiconducting layer in the 6.6 kv XLPE cable. As for water trees from the inner semiconducting layer, which were thought to be the most harmful, it is inferred from the calculation of field strength that OSW application with a peak of 1kV has no effect on the water trees with a length of 1. mm. After 8 times OSW application with a peak of 1kV, increasing up to a voltage at a rate of 1kV/1 times leads to a breakdown at a peak voltage of 4 kv. Electrical trees were observed at 2mm-depth water electrodes (Fig.1), but not at 1mm-depth water electrodes. This result supported the above indication Residual-charge Measurement with OSW Next, we applied an OSW to residual-charge measurement. The pattern of voltage application was basi- 68

5 Residual charge (nc) 1 5 Type 6- Type 22-2, 6.6kV : DC 15kV/5min., OSW of 1kVpeak 22kV : DC 3kV/5min., OSW of 2kVpeak 4, 6, 8, 1, 12, 14, Normalized current ( / max value) s 4 6 Time (s) 1kV Pattern of AC voltage application Fig. 11. Results of Residual Charge by Using OSW. Fig. 12. Variation of Residual-charge Signal. cally the same as shown in Fig.2, the difference was only to use an OSW as a substitution of AC voltage. Applied OSW had a peak voltage of 1kV with a frequency of 5-6Hz for the 6.6 kv XLPE cables and a peak voltage of 2 kv with the same frequency as the above for the 22 kv XLPE cables. The peak voltage for 22 kv XLPE cable was determined by comparison of the differing thickness of the 6.6kV and 22kV XLPE cables; that is, the thickness of 22kV XLPE cable is nearly twice thick as the 6.6 kv XLPE cable. The OSW with a peak voltage of 1 kv is thought to have no effect on water trees in these samples, because samples were Type6- ~ 6-4 and Type22- and The longest water tree is about 5µm in these samples. The results are shown in Fig.11. Residual charge could be detected by using OSW, and the aging-time dependence of residual charge (Fig.11) showed the same tendency as in Fig.6, but the amount of residual charges was about.3 times less than that of the results by using AC voltage application of 1. kv/mm. These results indicate the effectiveness of substituting an OSW for AC voltage in residual-charge measurement. 5.2 Method for Long Cable Span The above results were obtained by testing the cable with a length of 1-2 m, and the deteriorated region due to water trees was about 4 m. This length (4 m) corresponded to the length immersed in hot water during frequency acceleration aging, and the distribution of water trees was almost uniform within this region. But considering the cables in field, the distribution of water trees is not thought to be so uniform. Generally speaking, it is difficult to discriminate the localized and heavy water-tree deterioration and light and uniform water-tree deterioration by using the conventional residual-charge measurement, since the obtained residual charge depends on cable length. In the case that the residual-charge measurement is carried out by using the cables of the same length with localized and heavy water-tree deterioration or light and uniform water-tree deterioration, it could lead to a conclusion that these two cables have almost the same degree of water-tree deterioration, even though the breakdown strength of the latter is lower than that of the former. We have been developing the new technique to discriminate them Relationship between Water-tree Distribution and Residual-charge Signal Fig.12 shows the current signals of residual charge from samples of ~ 6-4 obtained by using AC voltage application as increasing up to 1 kv at a rate of 1kV/6 sec. The waveforms in Fig.12 are normalized by the maximum value of each signal for the purpose of waveform characteristics comparison. The signal of increased as AC voltage and then decreases monotonically. On the other hand, the signal of and 6-4 did not decrease monotonically after increasing voltage application; that is, both signal had a moderate peak at higher AC voltage. This indicates that there is a component of residual charge that requires application of a higher AC voltage to be released from water trees in heavily deteriorated cables such as and 6-4. As shown in Fig.4, has a large amount of water trees of about 5 µm -length, but few of length exceeding 5 µm, and the number longer than 1 µm drastically increases in and 6-4 in comparison with. Considering the difference in the water-tree distribution between and and 6-4, the component of residual charge which requires a higher AC voltage to be released is thought to correspond to long water trees. How high a voltage is required for a given length is not clear at this stage, and more investigation is needed. Fujikura Technical Review, 21 69

6 5.2.2 New Method for Detecting Long Water Trees As mentioned above, residual charge corresponding to long water trees is not released by a low AC voltage, but is released by higher voltage. Based on this characteristic, the method to detect long water trees is suggested here. For convenience, we assume two lengths of water tree in the insulation. The procedure is as follows (Fig.13). (1) A certain DC voltage is applied. (2) A low AC voltage is applied (Va). (3) A high AC voltage is applied (Vb). All of the residual charges corresponding to short water trees are released by a voltage application of Va, but residual charges corresponding to long water trees are not released at this stage. This residualcharge component is released by a voltage application of Vb. Therefore, we can obtain the information on the long water trees, that is, whether there are long water trees or not can be known by estimating the residual-charge component released by applying a high AC voltage. 6. Conclusion We reported the effectiveness of residual-charge measurement for diagnosing water tree deteriorated XLPE cable, the possibility of OSW application to conventional residual-charge measurement and new method for detecting long water trees. Conclusions from this study are as the follows: (1) Residual charge has a good correlation to breakdown voltage up to 22 kv/33 kv XLPE cable. This indicates that the residual-charge measurement is an effective diagnostic method for watertree deteriorated XLPE cable. Va Release of the residual charge corresponding to water trees with short length at Va Residual charge signal Case 1 Case 2 Pattern of AC voltage application Va Vb Release of the residual charge corresponding to water trees with long length at Vb Fig. 13. Pattern of Applied AC Voltage to Detect Highly Deteriorated Region. (2) The possibility of substituting OSW for AC voltage was confirmed. (3) A method was suggested for discriminating the signal corresponding to short and long water trees, of which the latter strongly affects the cable insulation performance. A method for detecting long water trees strongly affecting the dielectric performance of XLPE cable is thought to be the most effective, therefore, the improvement of this method is in progress. Vb References Time No heavily deteriorated region Heavily deteriorated region exists 1) Technical report of JIEE, No. 668, ) Technical report of CRIEPI W868 3) Uchida, et al. : Annual Conf. of JIEE, No. 186,

EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES

EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES Sverre Hvidsten*, Peter Werelius**, Jørgen Christensen*** * SINTEF Energy Research (SEfAS),

More information

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS Michael Hensel HIGHVOLT Prüftechnik Dresden GmbH 2 3 Content 1 Introduction Test parameters and their significance Differences

More information

SPACE CHARGE ACCUMULATION UNDER THE EFFECTS OF TEMPERATURE GRADIENT ON SOLID DIELECTRIC DC CABLE

SPACE CHARGE ACCUMULATION UNDER THE EFFECTS OF TEMPERATURE GRADIENT ON SOLID DIELECTRIC DC CABLE ISBN 978--658-9 Proceedings of the 6 th International Symposium on High Voltage Engineering Copyright c 9 SAIEE, Innes House, Johannesburg SPACE CHARGE ACCUMULATION UNDER THE EFFECTS OF TEMPERATURE GRADIENT

More information

HOW GOOD ARE ELECTRICAL DIAGNOSTIC TESTS TO PREDICT WATER TREES IN HV CABLES AN EVALUATION USING OPTICAL MICROSCOPY

HOW GOOD ARE ELECTRICAL DIAGNOSTIC TESTS TO PREDICT WATER TREES IN HV CABLES AN EVALUATION USING OPTICAL MICROSCOPY Journal of ELECTRICAL ENGINEERING, VOL. 56, NO. 1-2, 25, 31 35 HOW GOOD ARE ELECTRICAL DIAGNOSTIC TESTS TO PREDICT WATER TREES IN HV CABLES AN EVALUATION USING OPTICAL MICROSCOPY Motaheruddin Ahmed Mohammad

More information

Development of a 500-kV DC XLPE Cable System

Development of a 500-kV DC XLPE Cable System by Satoru Maruyama *, Noboru Ishii *, Michihiro Shimada *, Shinji Kojima * 2, Hideo Tanaka * 3, Mitsumasa Asano * 4, Tetsuya Yamanaka * 4, and Shin ichi Kawakami * 4 This paper describes development work

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B1-196 AORC Technical meeting 214 Evaluation of Insulating Materials for HVDC Transmission Cable using Space Charge Measurement Y. TANAKA Tokyo City University Japan SUMMARY Some

More information

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD

MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD MOBILE SYSTEM FOR DIAGNOSIS OF HIGH VOLTAGE CABLES (132KV/220KV) VLF-200 HVCD VERY LOW FREQUENCY (VLF) - PARTIAL DISCHARGES AND TANGENT DELTA HV/EHV POWER CABLES DIAGNOSTIC AND ON-SITE FIELD TESTING WITH

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

Development of 22-kV XLPE Cable and Joint with Reduced Insulation Thickness Having Water-Impervious Aluminum Layer

Development of 22-kV XLPE Cable and Joint with Reduced Insulation Thickness Having Water-Impervious Aluminum Layer Development of 22-kV XLPE Cable and Joint with Reduced Insulation Thickness Having Water-Impervious Aluminum Layer by Hiroyuki Mabuchi *, Satoru Koizumi *, Haruki Nozawa *, Yoshihiro Maeda * 2, Hideo Kawahara

More information

SPACE CHARGE MEASUREMENTS IN XLPE INSULATED MID VOLTAGE CABLE: CORRELATION WITH CABLE PERFORMANCE

SPACE CHARGE MEASUREMENTS IN XLPE INSULATED MID VOLTAGE CABLE: CORRELATION WITH CABLE PERFORMANCE SPACE CHARGE MEASUREMENTS IN XLPE INSULATED MID VOLTAGE CABLE: CORRELATION WITH CABLE PERFORMANCE Idalberto TAMAYO, Univ. Politècnica de Catalunya (ETSEIAT), (Spain), jose.antonio.diego@upc.edu Jordi ÒRRIT,

More information

A Study of a MV Cable Joint

A Study of a MV Cable Joint SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 7, No. 1, May 2010, 1-11 UDK: 621.315.35:537.212 A Study of a MV Cable Joint Radiša Dimitrijević 1, Neda Pekarić-Nađ 2, Miodrag Milutinov 3 Abstract: Construction

More information

Sub sea Cable Technology

Sub sea Cable Technology EERA DeepWind 2014 Sub sea Cable Technology Hallvard Faremo SINTEF Energy Research Brief presentation of: Wind Farm Cable R&D project Technology for a better society 1 High Voltage Subsea Cables Networking

More information

Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables

Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Classically both cables have a single AWG 8 copper conductor or a cross section of

More information

Asset management for power cable systems - Total cost optimization based on the Application of diagnostics -

Asset management for power cable systems - Total cost optimization based on the Application of diagnostics - 21, rue d Artois, F-75008 PARIS B1_212_2012 CIGRE 2012 http : //www.cigre.org Asset management for power cable systems - Total cost optimization based on the Application of diagnostics - T. NISHIKAWA Y.

More information

F05D Meeting on Damped AC Voltage Testing

F05D Meeting on Damped AC Voltage Testing October 28 th, 2008 from 03.30-5.30 pm in San Antonio, TX Agenda F05D Damped AC Voltage Testing 1 Agenda F05D Damped AC Voltage Testing Welcome: Introduction On-site testing voltages e.g. IEC 60060-3 High

More information

Cable Failure, Diagnostics and. Steven Boggs

Cable Failure, Diagnostics and. Steven Boggs Cable Failure, Diagnostics and Rejuvenation Steven Boggs The History PE Cables The Zeigler catalyst was invented in 1953 and mass production of HDPE started in the late 1950 s. Chemically cross linked

More information

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current. Application : The transducer RISH CON - CA/CV (Fig.1) converts a sinusoidal AC Current or AC Voltage into a load independent DC Current or a load independent DC Voltage proportional to the measured value.

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

Ordering Information. Cylindrical Proximity Sensor E2E/E2E2

Ordering Information. Cylindrical Proximity Sensor E2E/E2E2 Cylindrical Sensor E2E/E2E2 A New Series of Easy-to-use and Tough E2E/E2E2 Models Long-size E2E2 Sensor Conforms to CENELEC Ideal for a variety of applications. With a metal connector that can be tightened

More information

KNOW YOUR OPTIONS: 230 KV POWER CABLES

KNOW YOUR OPTIONS: 230 KV POWER CABLES KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common

More information

Product Specification

Product Specification Product Specification Model No.: DC-240-L01-00-TR Description: H=3.00mm Horizontal SMD DC Power Jacks Pin Shaft Diameter: 0.65mm Packing Method: Tape & Reel (600pcs./R) 1. General 1a. Scope The jacks should

More information

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line

ANN Based Fault Classifier and Fault Locator for Double Circuit Transmission Line International Journal of Computer Sciences and Engineering Open Access Research Paper Volume-4, Special Issue-2, April 2016 E-ISSN: 2347-2693 ANN Based Fault Classifier and Fault Locator for Double Circuit

More information

RoHS APPROVAL SHEET. ituner 12V/6.6A SERIES NO. (E17) EA10953A. ( ) Edac Power Electronics (Suzhou) Co., Ltd. 59 No.59, Chang Sheng Road, Sheng Pu,

RoHS APPROVAL SHEET. ituner 12V/6.6A SERIES NO. (E17) EA10953A. ( ) Edac Power Electronics (Suzhou) Co., Ltd. 59 No.59, Chang Sheng Road, Sheng Pu, APPROVAL SHEET CUSTOMER ituner CUSTOMER P/N DESCRIPTION EDAC MODEL 12V/6.6A SERIES NO. (E17) EA10953A DATE 2010-06-22 REVISION 0 APPROVED DESIGN PREPARE RoHS CONCLUSION APPROVED CONDITON CUSTOMER S APP

More information

Section 5 161 kv Power Cables

Section 5 161 kv Power Cables Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper

More information

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness

Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness Product Information Mylar polyester film Electrical Properties Mylar offers unique design capabilities to the electrical industry due to the excellent balance of its electrical properties with its chemical,

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

CABLE DIAGNOSIS USING VARIABLE FREQUENCY AND PARTIAL DISCHARGE DIAGNOSIS WITH DEFECT LOCATION AND CHARACTERIZATION G.C. Montanari J. Rickman D.

CABLE DIAGNOSIS USING VARIABLE FREQUENCY AND PARTIAL DISCHARGE DIAGNOSIS WITH DEFECT LOCATION AND CHARACTERIZATION G.C. Montanari J. Rickman D. CABLE DIAGNOSIS USING VARIABLE FREQUENCY AND PARTIAL DISCHARGE DIAGNOSIS WITH DEFECT LOCATION AND CHARACTERIZATION G.C. Montanari J. Rickman D. Kremer Abstract A new approach to cable diagnostics is discussed

More information

Explaining and avoiding faults Increasing availability

Explaining and avoiding faults Increasing availability Explaining and avoiding faults Increasing availability > Cables > Cable joints > Cable terminals Cables, cable joints, cable terminals Increasing availability A cable breakdown usually means an unexpected

More information

How To Test For Safety On A Power Cable

How To Test For Safety On A Power Cable T H E M A G A Z I N E O F 7 x 2 4 E X C H A N G E I N T E R N AT I O N A L A Green Approach to Building a Superior Data Center S P R I N G 0 9 BUILD FOR TODAY. EXPAND ON DEMAND. Modularity in the data

More information

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both

More information

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE Karl M. Hink, Executive Vice President Originally presented at the Power Quality 99 Conference ABSTRACT Motor protection

More information

Space charge build-up in XLPE-cable with temperature gradient

Space charge build-up in XLPE-cable with temperature gradient Downloaded from orbit.dtu.dk on: Dec 5, 205 Space charge build-up in XLPE-cable with temperature gradient Holbøll, Joachim; Henriksen, Mogens; Hjerrild, Jesper Published in: Proceeding of Annual Report

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

Telephone- and leased line modem for industrial applications TD-36

Telephone- and leased line modem for industrial applications TD-36 Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

MYTHBUSTING Takes on Shielded Cabling

MYTHBUSTING Takes on Shielded Cabling MYTHBUSTING Takes on Shielded Cabling Herb Congdon Brian Davis Objectives Take on myths of shielded cabling and use modern-day science to show what's real and what's fiction - through trial and error actually

More information

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO. SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.

More information

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?

TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta? TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables

More information

Offshore Platform Powered With New Electrical Motor Drive System

Offshore Platform Powered With New Electrical Motor Drive System Offshore Platform Powered With New Electrical Motor Drive System Authors: Jan O. Lamell, M.Sc E.E. ABB Automation Technologies Presenters: Thomas Johansson, M.Sc E.E. ABB Automation Technologies Timothy

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

CONFLEX ELECTRIC CABLE

CONFLEX ELECTRIC CABLE CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard

More information

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff

More information

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES THE PATHWAY TO POWER HIGH-VOLTAGE CABLES TABLE OF CONTENTS HIGH-VOLTAGE CABLES 3 Advantages of XLPE-insulated cable systems 3 PROPOSAL 4 Cable systems 4 Providing System Solutions 4 Continuous temperature

More information

Direct Attach Cable with Micro Coaxial Wire for Data Center

Direct Attach Cable with Micro Coaxial Wire for Data Center FEATURED TOPIC Direct Attach Cable with Micro Coaxial Wire for Data Center Yasuhiro MAEDA*, Kensaku SHIMADA, Yuki ISOYA, Tatsunori HAYASHISHITA and Michiko HARUMOTO ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

More information

WIRE AND CABLE ENGINEERING GUIDE

WIRE AND CABLE ENGINEERING GUIDE Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information

CC-Link Ver.1.10 Compatible

CC-Link Ver.1.10 Compatible Model Title CC-Link Ver.1.10 Compatible CC-Link Flexible Cable Conformance Test Specifications Management number : BAP-C0401-009 CC-Link Partner Association (1/12) Revisions Revision item Revision Description

More information

Development of High Voltage DC-XLPE Cable System

Development of High Voltage DC-XLPE Cable System SPECIAL ISSUE Development of High Voltage DC-XLPE Cable System Yoshinao MURATA*, Masatoshi SAKAMAKI, Kazutoshi ABE, Yoshiyuki INOUE, Shoji MASHIO, Seiji KASHIYAMA, Osamu MATSUNAGA, Tsuyoshi IGI, Masaru

More information

Rack mounted telephone- and leased line modem for industrial applications

Rack mounted telephone- and leased line modem for industrial applications Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as

More information

ALARMLINE ANALOGUE Linear Heat Detection System

ALARMLINE ANALOGUE Linear Heat Detection System ALARMLINE ANALOGUE Alarmline Analogue sensor cable senses temperature variations by continuously monitoring the resistance of specially doped N.T.C. polymeric insulation. A change in temperature produces

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information

More information

I-PEX MHF4 Micro Coaxial Connector

I-PEX MHF4 Micro Coaxial Connector PRODUCT SPECIFICATION I-PEX MHF4 Micro Coaxial Connector Plug P/N 20448-001R-81 Receptacle P/N 20449-001E RF Connector, RF Cable & Antenna Manufacturer E-mail: sales@wellshow.com.tw Tel: +886-2-24239376

More information

Designer-Oriented Electric Field Analysis System for Power Cable Accessories

Designer-Oriented Electric Field Analysis System for Power Cable Accessories ANALYSIS TECHNOLOGY er-oriented Electric Field Analysis System for Power Cable Accessories Yuuichi NAKAMURA*, Tomohiro KEISHI and Miki USUI Sumitomo Electric has worked on electric for more than 30 years.

More information

Product Catalogue. Relays with forcibly guided contacts

Product Catalogue. Relays with forcibly guided contacts Product Catalogue Relays with forcibly guided contacts Product Catalogue - Relays with forcibly guided contacts Edition / Publisher: ELESTA relays GmbH, Bad Ragaz, Switzerland All rights reserved. This

More information

6 ELECTRICAL PARAMETERS

6 ELECTRICAL PARAMETERS 6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Mirza Softić*, Amir Tokić**, Ivo Uglešić*** *Kreka - Dubrave e, Dubrave, Bosnia and Herzegovina (e-mail: softic_mirza@yahoo.com).

More information

RX-AM4SF Receiver. Pin-out. Connections

RX-AM4SF Receiver. Pin-out. Connections RX-AM4SF Receiver The super-heterodyne receiver RX-AM4SF can provide a RSSI output indicating the amplitude of the received signal: this output can be used to create a field-strength meter capable to indicate

More information

Li-ion Polymer Battery Specification

Li-ion Polymer Battery Specification Customer: ME1421A Li-ion Polymer Battery Specification Model:HPL302030-130mAh Checked & Approved by Prepared by Date Andy Liu Wang Wei 2014-7-18 History of revisions Edition Prepared by Approved by Date

More information

KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET

KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET 1 KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET KI XL - 03 / KI-SC 10 TWO COMPONENT AMBIENT CURABLE POLYETHYLENE COMPOUND FOR INSULATION OF LOW VOLTAGE POWER CABLE DESCRIPTION : KI polyethylene compound

More information

RY2 miniature industrial relays

RY2 miniature industrial relays 6 RY2 Relays of general application For plug-in sockets, 35 mm rail mount acc. to PN-EN 60715 or on panel mounting Flat insert connectors - faston x 0,5 mm Recognitions, certifications, directives: RoHS,

More information

Planar versus conventional transformer

Planar versus conventional transformer Planar versus conventional transformer Majid Dadafshar, Principal Engineer Gerard Healy, Field Application Engineer Pulse, a Technitrol Company Power Division Usually the first step on any power supply

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Series 8146/5-V37 and Series 8150/5-V37

Series 8146/5-V37 and Series 8150/5-V37 www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection

More information

49 Series - Relay interface modules 8-10 - 16 A. Features

49 Series - Relay interface modules 8-10 - 16 A. Features Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole

More information

CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number: 900-4602-0000

CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number: 900-4602-0000 Electrical Specification for: CPCI-3U-AC-300W-R Rugged 300W AC Input 3U CompactPCI Power Supply Telkoor Part Number: 900-4602-0000 GENERAL SCALE RELEASE DATE 12/9/06 SHEET 1 OF 6 REVISION HISTORY Rev Level

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac, > 89.0% @ 230Vac NEC Class

More information

CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS ADVANCED MATERIALS THE KEY TO PROGRESS

CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS ADVANCED MATERIALS THE KEY TO PROGRESS CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS ADVANCED MATERIALS THE KEY TO PROGRESS CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS VACUUMSCHMELZE GmbH & Co. KG (VAC) is one of the worldwide

More information

Network Standard Advice No. 1420C 9/6/2011

Network Standard Advice No. 1420C 9/6/2011 Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides

More information

HIGH VOLTAGE XLPE CABLE SYSTEMS. Technical User Guide

HIGH VOLTAGE XLPE CABLE SYSTEMS. Technical User Guide HIGH VOLTAGE XLPE CABLE SYSTEMS Technical User Guide Content 1. General information on High Voltage XLPE Cable Systems 1.1. Introduction 1.2. Cable selection process 1.3. Service life 3 3 3 4 2. Cable

More information

Why Buy HVI VLF Products?

Why Buy HVI VLF Products? Very Low Frequency AC Hipots AC testing of cables and electrical apparatus is now easier than ever. Since the introduction of the High Voltage, Inc. line of portable and affordable VLF hipots, there is

More information

Inductive Proximity Sensors

Inductive Proximity Sensors M12 Inductive Proximity Sensors Standard Length Mini's Extended Sensing 3 Wire DC 2 Wire DC 2 Wire AC (Wiring Schematic) 3 Wire DC PNP Normally Open (1) IMM32122C IMM35124C IMN32122C IMN35124C IMN32122M12

More information

UGVCL/SP/591/11KV HT AB CABLE

UGVCL/SP/591/11KV HT AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched

More information

SELECTION GUIDE INPUT CHARACTERISTICS. Voltage set point accuracy. Overall voltage error. Temperature coefficient of output voltage (slope)

SELECTION GUIDE INPUT CHARACTERISTICS. Voltage set point accuracy. Overall voltage error. Temperature coefficient of output voltage (slope) OBSOLETE NMPD0 Series SELECTION GUIDE Order Code Nominal Input Voltage Output Voltage Efficiency (Min.) Power (Max.) V V % W NMPD003C 3. 9.50 NMPD005C 5. 9.5 NMPD0C. 0 0.00 NMPD05C 5. 9 0.00 FEATURES RoHS

More information

DATA SHEET SURFACE-MOUNT CERAMIC MULTILAYER CAPACITORS General Purpose & High Capacitance Class 2, X7R

DATA SHEET SURFACE-MOUNT CERAMIC MULTILAYER CAPACITORS General Purpose & High Capacitance Class 2, X7R DATA SHEET SURFACE-MOUNT CERAMIC MULTILAYER CAPACITORS General Purpose & High Capacitance Class 2, 6.3 V TO 50 V 100 pf to 22 µf RoHS compliant & Halogen Free Product Specification October 13, 11 V.8 Product

More information

SOLUTION FOR INCREASING CAPACITANCE DEMAND HIGH CV TANTALUM CAPACITORS

SOLUTION FOR INCREASING CAPACITANCE DEMAND HIGH CV TANTALUM CAPACITORS SOLUTION FOR INCREASING CAPACITANCE DEMAND HIGH CV TANTALUM CAPACITORS T. Zednicek, AVX Czech Republic s.r.o., Dvorakova 328, 563 1 Lanskroun, Czech Republic Phone: +42 467 558 126 Fax: +42 467 558 128

More information

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities RELY ON OUR EXPERIENCE... EXPERIENCE OUR CAPABILITIES For close to half a century, Silec

More information

FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR

FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR Standards : CENELEC HD 22.4 NF C 32-102-4 DIN VDE 0282-1 and VDE 0282-4 BS 6007 and BS 6500 IEC 60245-4 Rated voltage Rated voltage: 450/750 V (Use up to

More information

WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors

WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors WW12X, WW08X, WW06X, WW04X ±1%, ±5% Thick Film Low ohm chip resistors Size 1206, 0805, 0603, 0402 *Contents in this sheet are subject to change without prior notice. Page 1 of 8 ASC_WWxxX_V12 Nov.- 2011

More information

Development of the Induction Motor for Machine Tool Spindles and Servo Amplifier SANMOTION S

Development of the Induction Motor for Machine Tool Spindles and Servo Amplifier SANMOTION S New Products Introduction Development of the Induction Motor for Machine Tool Spindles and Servo Amplifier SANMOTION S Takashi Sekiguchi Masahiro Kidou Yuusuke Shimura Yuji Ide Masahisa Koyama Michio Kitahara

More information

WINGLIKE ELECTRONICS CO.,LTD

WINGLIKE ELECTRONICS CO.,LTD WINGLIKE ELECTRONICS CO.,LTD SPECIFICATION FOR APPROVAL AC/DC ADAPTOR CUSTOMER: CUSTOMER SPECS INPUT: 100-240V AC 50-60HZ, 5V/2A ADAPTOR OUR MODEL NO.: GM-050200 (UL) E321192 SPECIFICATION NO.: WL1105102

More information

Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module

Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

Properties of electrical signals

Properties of electrical signals DC Voltage Component (Average voltage) Properties of electrical signals v(t) = V DC + v ac (t) V DC is the voltage value displayed on a DC voltmeter Triangular waveform DC component Half-wave rectifier

More information

Avoiding AC Capacitor Failures in Large UPS Systems

Avoiding AC Capacitor Failures in Large UPS Systems Avoiding AC Capacitor Failures in Large UPS Systems White Paper #60 Revision 0 Executive Summary Most AC power capacitor failures experienced in large UPS systems are avoidable. Capacitor failures can

More information

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS) MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed

More information

Cable Solutions for Servo and Variable Frequency Drives (VFD)

Cable Solutions for Servo and Variable Frequency Drives (VFD) Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect

More information

D1-306. Session 2004 CIGRÉ. 50 kv. 150 kv. Condition Assessment of High Voltage Power Cables. The Netherlands. E. Gulski * F.J.

D1-306. Session 2004 CIGRÉ. 50 kv. 150 kv. Condition Assessment of High Voltage Power Cables. The Netherlands. E. Gulski * F.J. 21, rue d'artois, F-75008 Paris http://www.cigre.org D1-306 Session 2004 CIGRÉ Condition Assessment of High Voltage Power Cables E. Gulski * F.J. Wester Ph. Wester E.R.S. Groot J. W. van Doeland Delft

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - 39 Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic

More information

Type-D EEG System for Regular EEG Clinic

Type-D EEG System for Regular EEG Clinic Type-D EEG System for Regular EEG Clinic Type-D EEG amplifier Specifications 1. For Type-D Amplifier Input channels: 12/24/36/48 Monopolar EEG + 12channels Bipolar EEG+12 channels PSG. Power supply: Internal

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

SECTION 13. Multipliers. Outline of Multiplier Design Process:

SECTION 13. Multipliers. Outline of Multiplier Design Process: SECTION 13 Multipliers VMI manufactures many high voltage multipliers, most of which are custom designed for specific requirements. The following information provides general information and basic guidance

More information

Safety automation solutions

Safety automation solutions Operating principle, characteristics Preventa safety s types XPS AV,, For and switch monitoring Operating principle Safety s XPS AV, and are used for monitoring circuits conforming to standards EN/ISO

More information