A Study of a MV Cable Joint
|
|
|
- Brendan Stewart
- 10 years ago
- Views:
Transcription
1 SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 7, No. 1, May 2010, 1-11 UDK: : A Study of a MV Cable Joint Radiša Dimitrijević 1, Neda Pekarić-Nađ 2, Miodrag Milutinov 3 Abstract: Construction parameters of a medium voltage (MV) cable joint were examined in order to reduce the electric field magnitude inside the joint. The joint was covered with a heat shrinkable tube made of two or three layers. The permittivity of the layers was varied. The termination angle of the cable dielectric was also considered. Keywords: Electric field reduction, Dielectric properties. 1 Introduction Cross linked polyethylene (XLPE) cables have been in widespread use for decades. Manufactured cable lengths are typically below 1000 m, so several sections of cable may be needed to create a long distance cable line. Consequently, the line quality depends strongly on the reliability of the cable joints. It depends equally on the quality of terminations, but they are considered elsewhere. More details on the cable considered here are listed in Table 1. Numerical modelling of the cable joints offers an elegant way to study the electric and magnetic fields inside them, to identify critical spots, improve design and to reduce manufacturing costs [1]. In order to make a joint, the conductors of two consecutive sections of cable are stripped of insulator and joined together with a copper or aluminium ferrule. Sophisticated multilayer materials may be used to insulate the ferrule and fill in the space left by the missing dielectric. The joint is covered with heat shrinkable tube (HST) for protection. Different cable joints are in use, most often with capacitive/geometric, refractive or resistive control of the electric field inside the joint [2]. Two joints from Fig. 1 are described in this work. They combine geometric and high permittivity regulation of the field. The joints may come partially or entirely prefabricated or may be made on site. Good electrical properties of the cable joints depend on the skill of the technicians who assemble them. The termination angle of the cable dielectric is sometimes made according to their 1 Research Institute, Holding Kablovi a.d., Gine Pajevic 14, Jagodina, Serbia; [email protected] 2 Faculty of Engineering, FTN, University of Novi Sad, Trg Dositeja Obradovica 6, Novi Sad, Serbia; [email protected] 3 Faculty of Engineering, FTN, University of Novi Sad, Trg Dositeja Obradovica 6, Novi Sad, Serbia; [email protected] 1
2 R. Dimitrijević, N. Pekarić-Nađ, M. Milutinov individual experience. Factory prefabricated parts are preferred in order to minimize human error as much as possible and to reduce assembling time [3]. Accordingly, the goal of this work was to increase the number of prefabricated parts and to reduce the possibility of individual error. Table 1 Manufacturing data for the Al/XLPE/PVC cable (1 120mm 2, 12/20kV). Conductor (1) Cross-section (mm 2 ) 120 Material Copper or Aluminium Diameter (mm) 15 Conductor screen Thickness (mm) 0.5 Cable insulation (2) Material XLPE Thickness (mm) 5.5 Insulation screen (3) Thickness (mm) 0.5 Metal screen Cross section (mm 2 ) 16 Outer PVC tubing Thickness (mm) 2 Outer diameter (mm) 34 Fig. 1 Medium voltage cable joint constructions: CJ1 - upper, CJ2 - lower. Legend: 1 - conductor, 2 - dielectric, 3 - cable screen end, 4 - ferrule insulation, 5 - ferrule, 6 - high permittivity layer or wrap (HPW), 7 - EP rubber, 8 - semiconducting layer. HST1: HST2:
3 A Study of a MV Cable Joint Item Table 2 Some data on the joint parts. Geometry Relative permittivity, ε r Dielectric end (2) θ = Ferrule (5) Length 100 mm (70 mm Cu, 133 mm Al), φ = 20 mm N/A Ferrule insulation (4) High permittivity layer, HPW (6) 1 3 mm thick EP Rubber (7) 3 mm thick 3.4 Semiconducting layer (8) 1.5 mm thick 100 Some joint data may be found in Table 2. The first type of joint, labelled CJ1, was designed with a three-layer heat shrinkable tube, HST1. The second type of joint, labelled CJ2, was designed with high permittivity wrap, HPW, placed only on top of the cable screen end, under the two-layer heat shrinkable tube, HST2. A range of different values of permittivity were explored for the HPW and for the inner layer of HST1, but in the end both were designed from the same material for ease of comparison. 2 Numerical results According to our experience [4], cable joints need to be designed with increased permittivity materials and with carefully controlled geometry. Both CJ1, with three-layer heat shrinkable tube HSTl, and CJ2, the lower cost joint with two-layer heat shrinkable tube, from Fig. 1, were considered. The electric field inside the joints was calculated using a commercially available finite element method program. The calculations explored: 1. Permittivity of ferrule insulation, ε, (layer 4 from Fig. 1), 2. Angle θ at the boundary between the ferrule insulation and cable insulation, 3. Permittivity ε of the bottom layer (layer 6, from Fig. 1) of the HSTl as well as permittivity of the HPW of CJ2, 4. Thickness of layer 6 both for the HSTl and for the HPW of CJ2. 3
4 R. Dimitrijević, N. Pekarić-Nađ, M. Milutinov In order to choose the appropriate set of joint parameters, two quantities were calculated: 1. Maximum electric field strength, E, and max 2. Tangential electric field component E. tan Many calculations were peormed in search of the best way to reduce the maximum field magnitude, E, max and if possible at the same time to reduce the tangential component E tan (magnitude of the electric field vector parallel to the boundary suace). The area affected by the increased field intensity was also assessed. The relative permittivity, ε, of the ferrule insulation was found to play a great role in field formation. In the case of CJ1, a higher permittivity forced the electric field out of the ferrule insulation, so that the highest magnitude of field was compressed in the narrow space inside HSTl. As pointed to by the arrow in Fig. 2, the voltage gradient was very high both at the top of the ferrule insulation and on the upper edge of the cable dielectric. Not shown here, in the case of CJ2, there was a bit more room inside HST2. The ferrule insulation was made of a rubber-based material with good plasticity. A lower ferrule insulation permittivity, ε, between 5 and 10, turned out to be better at reducing the total field. It allowed more room for the field to expand into. The voltage gradient was less abrupt on top of the ferrule insulation (see Fig. 3). The main electric stress was located close to the conductor, at the cable dielectric end, as pointed to by the arrow. The family of curves in Fig. 4 were calculated for different angles θ, ranging from 10 to 90 degrees. Different angles gave different geometries for the dielectric cone: for θ = 90 no dielectric cone around the conductor, for θ= mm long cone, for θ = mm long cone and for θ= mm long cone. Larger θ (shorter cone at the end of the cable insulation) resulted in a lower total field magnitude. Smaller θ (longer cone) was found to reduce the tangential field component along the cable insulation boundary but at the same time significantly increased the maximum total field magnitude inside the joint. Although the tangential field component may be important, the total field magnitude is crucial. Fig. 4 illustrates how the maximum strength of the total electric field inside joint CJ1 changes as a function of the ferrule insulation relative permittivity. The range was explored numerically. As can be seen from Fig. 4, a relative permittivity in the range 5 10 was found to be best for total field reduction. A larger permittivity, ε = 10 and more, as in semiconducting or 4
5 A Study of a MV Cable Joint conducting materials, was found to produce an extremely high total field at certain points and thus obstruct the quality of the joint. The idea of having conducting or semiconducting parts in the joint was tested based on some earlier designs of high voltage cables [4]. In this case, for a given geometry, the introduction of additional conducting or semiconducting material did not prove beneficial. Fig. 2 A detail of the calculated voltage of CJ1-40/90 (ferrule insulation ε = 40, cable end boundary angle θ = 90 ). Fig. 3 A detail of the calculated voltage of CJ1-7/28 (ferrule insulation ε = 7, cable end boundary angle θ = 28 ). 5
6 R. Dimitrijević, N. Pekarić-Nađ, M. Milutinov Emax(k V/mm) Relative ferrule insulation permittivity θ=90 θ=28.8 θ=15.3 θ=10.4 Fig. 4 Maximum electric field strength of CJ, as a function of ferrule insulation permittivity ε, and of boundary angle θ. Fig. 5 represents the calculated radial and axial change of electric field inside CJ1-7/28. Observe how the field magnitude drops in the high permittivity layers. Both the inner layer of the three-layer HST1 and the HPW of CJ2 were designed from the same material with a relative permittivity ε = 10 or ε = 40. The electric field strength changes both with radial and axial distance from the centre of the joint, as can be observed in Fig. 5. The centre of the joint corresponds to the height z = 0. The height z = 0.08 m is closer to the cable dielectric end and the height z = 0.1 m is closer to the cable screen end. The ε, pushes the field outside the layer and the high permittivity of layer 6, maximum total field strength in the neighbourhood goes up. This is one of the main reasons why, to compensate, the ferrule insulation relative permittivity must be kept below 10. At the most critical height, at the cable screen end, the maximum total field strength was calculated as E max = 5.28 MV/m, for ε = 10, compared to E max = 4.83 MV/m, for ε = 40 (See Figs. 5a3 and 5b3). The higher permittivity ε = 40 seems to work better. 6
7 A Study of a MV Cable Joint z = 0 (a1); z = 0 (b1); z = 0.08m (a2); z = 0.08m (b2); z = 0.1m (a3); z = 0.1m (b3); Fig. 5 The electric field radial profile at different axial distances from the centre of joint CJ1-7/28, ε = 7, θ = 28 ; (a) ε = 10 ; (b) ε = 40. 7
8 R. Dimitrijević, N. Pekarić-Nađ, M. Milutinov It is worth mentioning that a relative permittivity ε = 40 simultaneously reduced the tangential component of field in CJ1 to an acceptable value below 500 kv/m: Inside CJ1-7/28, we calculated a maximum tangential component E tan = 621 kv/m for ε = 10, compared to a maximum E tan = 362 kv/m for ε = 40. The higher permittivity ε = 40 seems to fulfil both search criteria. A relative permittivity higher than ε = 40 may affect the creep distance and was not considered for safety reasons. The thickness explored for the HPW was in the range from 1 to 3 mm. The electric field at the cable screen end was well controlled by a 1 mm thick high permittivity bottom layer of HST1, in the case of CJ1. In the case of CJ2, a 1 mm thick HPW was used. A greater thickness was found unnecessary. For electric field regulation at the cable screen end (layer 3 in Fig. 1), a cover with increased permittivity was found essential. 3 Experimental results According to the calculations, both designs, CJ1 and CJ2 should have similar electrical properties. CJ2 may have 10 20% cheaper parts but it has a longer installation time and offers more opportunity for human error. The price reduction does not seem to justify the effort to assemble CJ2. For this reason, only CJ1 was manufactured and tested experimentally. The total length of the joint was chosen so that the voltage would not damage the insulating material. According to IEC 112, the creep distance for fair conditions should be kept above 16 mm/kv. In our design, tracking between the two consecutive cable screen ends was set to 320 mm for a 20 kv copper cable or to 390 mm for a 20 kv aluminium cable. Only CJ1 was chosen for experimental studies. The main conclusions from the numerical results - that better joints may be made with moderate permittivity, below 10, for the ferrule insulation and with an angle θ between 28 and 90 degrees, were tested experimentally. Three different samples of CJ1 were prepared for experimental testing. The results of the experimental tests are summarized in Table 3. The first design, labelled CJ1-40/90, was manufactured with an increased ferrule insulation permittivity of ε = 40 and with boundary angle θ = 90 (no cone at the dielectric end). The second, labelled CJ1-7/28, had a lower ferrule insulation permittivity of ε = 7 and a boundary angle θ = 28.8 (10 mm long cone). Both constructions peormed well and both passed the tests according to the VDE 0278 standard. CJ1-7/28 peormed slightly better in respect of partial discharges, as can be seen from row 11 of Table 3. In spite of the good 8
9 9 A Study of a MV Cable Joint numerical results, an angle θ = 90 was not considered convenient for jointmaking. Perpendicular inteaces make it difficult to install the ferrule insulation. Because of this, joints with small cones up to 10 mm in length ( θ between 28 and 90 degrees) were considered to be better adapted to fabrication. Table 3 The peormance tests results according to VDE Legend: CJ1-40/90 (ferrule insulation permittivity ε = 40 and θ = 90 ), CJ1-7/28 (ferrule insulation permittivity ε = 7 and θ = 28 ). No. Item Test voltage (kv) CJ1-40/90 CJ1-7/28 1. AC 50Hz, 1 min 55 Passed Passed 2. Partial discharges 24 0 pc 0 pc Impulse voltage (10 3. positive, 10 negative, 1.2/50 μ S) 125 Passed Passed Current cycling 4. (5+3 hours, cond. temp. 30 Passed Passed 95 C 3 cycles) 5. Partial discharges 24 0 pc 0 pc 6. Current cycling (5+3 hours, cond. temp. 30 Passed Passed 95 C 60 cycles) 7. Partial discharges 24 4 pc 0 pc 8. Current overload 1 sec. 250 C Passed Passed 9. Partial discharges pc 4 pc 10. Current cycling (5+3hours, cond. temp. 30 Passed Passed 95 C, 63 cycles) 11. Partial discharges pc 10 pc 12. DC voltage 30 min 96 Passed Passed 13. AC voltage 50 5 min 5 min 60 30s* 30s* *Flashover at cable termination The third manufactured cable joint, labelled CJl-100/28, with semiconducting material on top of the ferrule, of relative permittivity ε = 100 and boundary angle θ = 28.8 (10 mm long cone), did not pass the test. Such an outcome confirmed the numerical prediction that the ferrule insulation must not be replaced by semiconducting material.
10 R. Dimitrijević, N. Pekarić-Nađ, M. Milutinov 4 Conclusion There are many solutions for MV cable joints. Our efforts were directed at improving the design, based on numerical calculations and on site experience. The main goal of this study was to reduce the maximum field strength, E, max and tangential component, E tan, parallel to the boundary suaces, as much as possible, thus protecting the cable joint from accelerated aging. Two parameters were monitored in order to choose the best joint design: 1. Total electric field strength and 2. Tangential field components along boundaries. Two similar cable constructions were explored. The first type, CJ1, incorporated a three-layer heat shrinkable tube, HST1. The second type incorporated a two-layer heat shrinkable tube, HST2, on top of the HPW. The electric field magnitude inside the joints was calculated by the finite element method. The calculations showed that: The maximum electric field strength in the joint is affected a great deal by the permittivity of the ferrule insulation, ε. A relative permittivity of the ferrule insulation, ε, between 5 and 10 was found to be the most suitable. Materials with higher permittivity must not be used. The angle between the ferrule insulation and cable insulation, θ, affects the peak magnitudes of both the total field and tangential components of field along the boundary suaces. These demands oppose each other. A smaller θ was able to reduce the tangential components but at the same time it increased the total field magnitude, which was not permissible. An angle θ in the range was found to be acceptable. A larger θ is better in theory, but not practical in reality. High permittivity of the HST1 inner layer, in the case of CJ1, as well as of the HPW, in the case of CJ2, ε, was essential in order to reduce the field magnitude at the cable screen end. A value ε = 40 was found to be suitable. Increased thickness of either the inner layer of the HST1 or of the HPW, in the case of CJ2, did not affect the field to any large extent. A thickness of 1 mm was found to be appropriate. Besides this, the cable insulation should be left intact as much as possible; a longer insulation cone results in a larger contact suace that has to be 10
11 A Study of a MV Cable Joint additionally treated on site with sandpaper and lubricated with silicon oil. A larger contact suace may also cause more micro discharges. As a result of this work, a cutting tool can be designed for on site preparation of an optimally shaped dielectric cone. All other parts of the joint labelled CJ1, including ferrule, ferrule insulator and three-layer HST1, can be factory prefabricated. Future work should employ a genetic algorithm-based search or some other optimization technique for the best possible joint design. 5 Acknowledgement The work is a part of the TR project of the Ministry of Science and Technology Development of Serbia. The financial support is highly appreciated. 6 References [1] B. Jaekeli: Numerical Simulation for Investigating EMC Problems in Industrial Life, Serbian Journal of Electrical Engineering, Vol. 5, No. 1, May 2008, pp [2] K.H. Osteohldt, U. Glockner, R. Bach: Technological Change of the Medium Sets, Elektrizitaetswirtschaft, Vol. 96, No. 20, 1997, pp [3] Y. Nakanishi, A. Fujimori, S. Fukunaga, T. Tanabe, M. Kobayashi, N. Shiseki, K. Ando: Development of Prefabricated Joint for 275 kv XLPE Cable, IEEE Transaction on Power Delivery, Vol. 10, No. 3, July 1995, pp [4] S. Nikolajevic, N. Pekaric-Nadj, R. Dimitrijevic: A New Concept in Construction of Cable Termination for Medium Voltages, IEEE Transaction on Power Delivery, Vol. 13, No. 3, July 1998, pp
Fault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003
MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU
UGVCL/SP/591/11KV HT AB CABLE
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched
Development of 22-kV XLPE Cable and Joint with Reduced Insulation Thickness Having Water-Impervious Aluminum Layer
Development of 22-kV XLPE Cable and Joint with Reduced Insulation Thickness Having Water-Impervious Aluminum Layer by Hiroyuki Mabuchi *, Satoru Koizumi *, Haruki Nozawa *, Yoshihiro Maeda * 2, Hideo Kawahara
CABLE ACCESSORIES 110-220 kv
CABLE ACCESSORIES 110-220 kv Termination 110 kv Technical description Termination MKB 126 / 145 with composite type insulator uses for cable line joints with other elements of power-supply systems. Termination
SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS
SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS Michael Hensel HIGHVOLT Prüftechnik Dresden GmbH 2 3 Content 1 Introduction Test parameters and their significance Differences
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
APPLICATION ORIENTED DESIGN OF CABLES
APPLICATION ORIENTED DESIGN OF CABLES Mrs. Rohini Bhattacharyya, Dubai cables Ltd.P. O. Box 11529,Dubai. [email protected] Mr. Nawaf Ahmad Al Mohaideb Dubai Cables Ltd. P. O. Box 11529, Dubai. [email protected]
KNOW YOUR OPTIONS: 230 KV POWER CABLES
KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common
Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable
Investigation of the Residual-charge Technique for Diagnosis of Water-tree Deteriorated Cross-linked Polyethylene Cable Dr. Uchida Katsumi*, Youichi Katou*, Dr. Hiroyuki Kon, Dr. Kazuo Watanabe and Takenori
EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES
EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES Sverre Hvidsten*, Peter Werelius**, Jørgen Christensen*** * SINTEF Energy Research (SEfAS),
Network Standard Advice No. 1420C 9/6/2011
Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides
Section 5 161 kv Power Cables
Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper
THE PATHWAY TO POWER HIGH-VOLTAGE CABLES
THE PATHWAY TO POWER HIGH-VOLTAGE CABLES TABLE OF CONTENTS HIGH-VOLTAGE CABLES 3 Advantages of XLPE-insulated cable systems 3 PROPOSAL 4 Cable systems 4 Providing System Solutions 4 Continuous temperature
Development of a 500-kV DC XLPE Cable System
by Satoru Maruyama *, Noboru Ishii *, Michihiro Shimada *, Shinji Kojima * 2, Hideo Tanaka * 3, Mitsumasa Asano * 4, Tetsuya Yamanaka * 4, and Shin ichi Kawakami * 4 This paper describes development work
AORC Technical meeting 2014
http : //www.cigre.org B1-196 AORC Technical meeting 214 Evaluation of Insulating Materials for HVDC Transmission Cable using Space Charge Measurement Y. TANAKA Tokyo City University Japan SUMMARY Some
KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE
Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both
ELECTRIC FIELD LINES AND EQUIPOTENTIAL SURFACES
ELECTRIC FIELD LINES AND EQUIPOTENTIAL SURFACES The purpose of this lab session is to experimentally investigate the relation between electric field lines of force and equipotential surfaces in two dimensions.
1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide
1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
Medium Voltage Joints & Terminations
Medium Voltage Joints & Terminations 59 Medium Voltage - Cold Shrink Joints Supporting Core Radially shinkable elastomeric splice Semi-conductive layer High permitivity insulation layer Semi-conductive
Modelling of Electrostatic Ignition Hazards in Industry: too Complicated, not Meaningful or only of Academic Interest?
A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 31, 2013 Guest Editors: Eddy De Rademaeker, Bruno Fabiano, Simberto Senni Buratti Copyright 2013, AIDIC Servizi S.r.l., ISBN 978-88-95608-22-8; ISSN
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
SPACE CHARGE ACCUMULATION UNDER THE EFFECTS OF TEMPERATURE GRADIENT ON SOLID DIELECTRIC DC CABLE
ISBN 978--658-9 Proceedings of the 6 th International Symposium on High Voltage Engineering Copyright c 9 SAIEE, Innes House, Johannesburg SPACE CHARGE ACCUMULATION UNDER THE EFFECTS OF TEMPERATURE GRADIENT
Transformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities
HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities RELY ON OUR EXPERIENCE... EXPERIENCE OUR CAPABILITIES For close to half a century, Silec
VIPERFLEX ELECTRIC CABLE
VIPERFLEX Flexible Low Voltage Electric Cable - 0.6/1kV (Rubber insulated) H07 RN-F & H07 BN-F Single Core 2-Core 2-Core and Earth 3-Core and Earth 4-Core and Earth Multi-Core and Earth H07 RCN-F & H07
No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint
M Cold Shrink Medium Voltage Joints & Terminations M Cold Shrink Joint Splice bodies 00% factory tested - ensures reliability Capacitive Stress Relief No Heat No Flames No Special Tools No Shoving Unique
How To Test For Safety On A Power Cable
T H E M A G A Z I N E O F 7 x 2 4 E X C H A N G E I N T E R N AT I O N A L A Green Approach to Building a Superior Data Center S P R I N G 0 9 BUILD FOR TODAY. EXPAND ON DEMAND. Modularity in the data
T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A
T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test
4 SENSORS. Example. A force of 1 N is exerted on a PZT5A disc of diameter 10 mm and thickness 1 mm. The resulting mechanical stress is:
4 SENSORS The modern technical world demands the availability of sensors to measure and convert a variety of physical quantities into electrical signals. These signals can then be fed into data processing
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED
Coaxial Cable Feeder Influence on Yagi Antenna Dragoslav Dobričić, YU1AW [email protected]
Coaxial Cable Feeder Influence on Yagi Antenna Dragoslav Dobričić, YU1AW [email protected] Introduction o far, in several previous articles [1, 2, 3], we investigated how boom radius and its S distance
The new 525 kv extruded HVDC cable system
The new 525 kv extruded HVDC cable system World s most powerful extruded cable system Anders Gustafsson, Markus Saltzer, Andreas Farkas, Hossein Ghorbani, Tobias Quist, Marc Jeroense High Voltage Cables
High Voltage Systems. Today. The history of cables
High Voltage Cables High Voltage Systems Today Prysmian Cables and Systems B.V. is part of the Prysmian Group, a leading player in the industry of high-technology cables and systems for energy and telecommunications,
MV CABLE TYPE C 33-226
MV CABLE TYPE C 33-226 Standards : CENELEC HD 620 C 33-226 Rated voltage Rated voltage : 12/20 (24) kv Design 1 Stranded aluminium, class 2 conductor 2 Extruded conducting screen on conductor 3 XLPE insulation
R=Required by Lab S=May be subcontracted IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT COMMITTEE OF TESTING LABORATORIES
IEC SYSTEM FO CONFOMITY TESTING AND CETIFICATION OF ELECTICAL EQUIPMENT COMMITTEE OF TESTING LABOATOIES TESTING AND MEASUING EQUIPMENT/ALLOWED SUBCONTACTING Power cables with extruded insulation and their
Unarmored Variable Frequency Drive (VFD) Cable Termination Guide
Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Classically both cables have a single AWG 8 copper conductor or a cross section of
25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
CONFLEX ELECTRIC CABLE
CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard
I-PEX MHF4 Micro Coaxial Connector
PRODUCT SPECIFICATION I-PEX MHF4 Micro Coaxial Connector Plug P/N 20448-001R-81 Receptacle P/N 20449-001E RF Connector, RF Cable & Antenna Manufacturer E-mail: [email protected] Tel: +886-2-24239376
EDITION 2012 CABLE SYSTEMS
EDITION 2012 CABLE SYSTEMS Cable fittings for high voltage networks Welcome to the CABLE SYSTEMS Centre of Competence. Our range of cable accessories offers solutions for virtually all applications in
Festoon 715 P PUR cable for flexible application in festoon systems
CABLES FOR CRANE AND CONVEYOR APPLICATIONS Festoon 715 P PUR cable for flexible application in festoon systems S AB BRÖCKSKES D-VIERSEN Festoon 715 P 1 x 16.0 mm 2 C Marking for Festoon 715 P 07150162:
Space charge build-up in XLPE-cable with temperature gradient
Downloaded from orbit.dtu.dk on: Dec 5, 205 Space charge build-up in XLPE-cable with temperature gradient Holbøll, Joachim; Henriksen, Mogens; Hjerrild, Jesper Published in: Proceeding of Annual Report
ScottishPower Distribution Cables & Equipment. Metal Theft
ScottishPower Distribution Cables & Equipment Metal Theft April 2012 As an aid to deterring to metal theft this booklet has been put together to help identify the types of utility power cables and associated
Flexible cables for submersible products
Flexible cables for submersible products Standards SUBCAB cables complies with the following general standards: IEC 6045 (general) IEC 608 class 5 (conductor) IEC 608-- CLAUSE 9 (oil resistant) IEC 608--
1. A wire carries 15 A. You form the wire into a single-turn circular loop with magnetic field 80 µ T at the loop center. What is the loop radius?
CHAPTER 3 SOURCES O THE MAGNETC ELD 1. A wire carries 15 A. You form the wire into a single-turn circular loop with magnetic field 8 µ T at the loop center. What is the loop radius? Equation 3-3, with
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.
SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.
Cutting and stripping tools
Cutting and stripping tools Introduction 2 Cutting and stripping tool 0.02-10 mm² (16 mm²) 3 Stripping tool for cables Ø 2.5-40 mm 4 Tools for cutting and stripping of conductors 0.5-6 mm² and for cutting
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
Effect of design parameters on temperature rise of windings of dry type electrical transformer
Effect of design parameters on temperature rise of windings of dry type electrical transformer Vikas Kumar a, *, T. Vijay Kumar b, K.B. Dora c a Centre for Development of Advanced Computing, Pune University
Bending, Forming and Flexing Printed Circuits
Bending, Forming and Flexing Printed Circuits John Coonrod Rogers Corporation Introduction: In the printed circuit board industry there are generally two main types of circuit boards; there are rigid printed
3. ELECTRICAL PERFORMANCE PROPERTY TEST CONDITION PERFORMANCE 3. 1 Contact Resistance 1) Center Push 100mΩ Max
1. GENERAL 1. 1 Application : This specification is applied to MULTI WAY SWITCH for electronic equipment. 1. 2 Operating Temperature Range :-25 ~ 70 1. 3 Storage Temperature Range :-0 ~ 85. However, 96
DEHN + SÖHNE. DEHNconductor System No Problems with Proximities
DEHN + SÖHNE DEHNconductor System No Problems with Proximities DEHNconductor System - New Possibilities for controling Proximities. For preventing dangerous flashovers among parts of external lightning
Thermal Control of the Extrusion Press Container
Thermal Control of the Extrusion Press Container Prepared by -- Dennis Van Dine, Nazmi Gilada, Paul Robbins, Castool Tooling Solutions, Dr. V.I. (Mike) Johannes, BENCHMARKS, Shigeyoshi Takagi, Techno-Consul
MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
Cable Strippers: High, Low and Medium Voltage
Cable Strippers: High, Low and Medium Voltage Cable Strippers: Low, Medium and High voltage It is extremely important to use the right tool for each job - this will avoid risks, save time and ensure the
Pulse Withstanding Thick Film Chip Resistor-SMDP Series. official distributor of
Product: Pulse Withstanding Thick Film Chip Resistor-SMDP Series Size: /// official distributor of Pulse Withstanding Thick Film Chip Resistor-SMDP Series 1. Scope -This specification applies to ~ sizes
Metal-Oxide Varistors (MOVs) Surface Mount Multilayer Varistors (MLVs) > MLN Series. MLN SurgeArray TM Suppressor. Description
MLN SurgeArray TM Suppressor RoHS Description The MLN SurgeArray Suppressor is designed to help protect components from transient voltages that exist at the circuit board level. This device provides four
CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR
47 CHAPTER 4 DESIGN OF INTEGRAL SLOT AND FRACTIONAL SLOT BRUSHLESS DC MOTOR 4.1 INTRODUCTION This chapter deals with the design of 24 slots 8 poles, 48 slots 16 poles and 60 slots 16 poles brushless dc
COMPUTATION OF THREE-DIMENSIONAL ELECTRIC FIELD PROBLEMS BY A BOUNDARY INTEGRAL METHOD AND ITS APPLICATION TO INSULATION DESIGN
PERIODICA POLYTECHNICA SER. EL. ENG. VOL. 38, NO. ~, PP. 381-393 (199~) COMPUTATION OF THREE-DIMENSIONAL ELECTRIC FIELD PROBLEMS BY A BOUNDARY INTEGRAL METHOD AND ITS APPLICATION TO INSULATION DESIGN H.
SPACE CHARGE MEASUREMENTS IN XLPE INSULATED MID VOLTAGE CABLE: CORRELATION WITH CABLE PERFORMANCE
SPACE CHARGE MEASUREMENTS IN XLPE INSULATED MID VOLTAGE CABLE: CORRELATION WITH CABLE PERFORMANCE Idalberto TAMAYO, Univ. Politècnica de Catalunya (ETSEIAT), (Spain), [email protected] Jordi ÒRRIT,
08. SEK IDC CONNECTORS
. IDC CONNECTORS connectors for flat cables enable simple and, cost-optimized device configuration. connectors are preferably used for connection within the device. HARTING offers a broad range of these
3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables 15. 8.7/15 kv XLPE insulated cables 25. 12/20 kv XLPE insulated cables 35
CONTENTS INTRODUCTION 1 Cable selection, cable specification, cable services CABLES Constructional data: 3.6/6 kv XLPE insulated cables 5 SECTION 1 6/10 kv XLPE insulated cables 15 SECTION 2 8.7/15 kv
How To Read A Pipe From A Sensor
Liquid Level Sensor Installation on pipes. Sensing by means electrostatic capacity and is not influenced by the color of the pipe or liquid. Available in 8 to mm dia. and to mm dia. models to enable sensing
OLI. Oil level indicator
OLI Oil level indicator Oil level indicator Unexpected or accidental oil leakages may occur randomly along transformer s lifetime. Clear indication of oil level inside transformer tank and on load tap
48 SERIES Relay interface modules 10 A
48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply
The DC Motor. Physics 1051 Laboratory #5 The DC Motor
The DC Motor Physics 1051 Laboratory #5 The DC Motor Contents Part I: Objective Part II: Introduction Magnetic Force Right Hand Rule Force on a Loop Magnetic Dipole Moment Torque Part II: Predictions Force
Precision Miniature Load Cell. Models 8431, 8432 with Overload Protection
w Technical Product Information Precision Miniature Load Cell with Overload Protection 1. Introduction The load cells in the model 8431 and 8432 series are primarily designed for the measurement of force
DOING PHYSICS WITH MATLAB COMPUTATIONAL OPTICS RAYLEIGH-SOMMERFELD DIFFRACTION INTEGRAL OF THE FIRST KIND
DOING PHYSICS WITH MATLAB COMPUTATIONAL OPTICS RAYLEIGH-SOMMERFELD DIFFRACTION INTEGRAL OF THE FIRST KIND THE THREE-DIMENSIONAL DISTRIBUTION OF THE RADIANT FLUX DENSITY AT THE FOCUS OF A CONVERGENCE BEAM
6 ELECTRICAL PARAMETERS
6 ELECTRICAL PARAMETERS For power, low voltage and medium voltage cables, cross section nominal areas are calculated in taking into account several parameters as: permissible current carrying capacities
Draka Industrial Cable GmbH
A) Preparation of cable ends To enable the stranding of the cores after connecting main and earth cores, each of the cable ends to be connected are laid in a double loop with righthand turn and then fixed
EDS 02-0027 11KV TRIPLEX CABLE
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 02-0027 ENGINEERING DESIGN STANDARD EDS 02-0027 11KV TRIPLEX CABLE Network(s): EPN, LPN, SPN Summary:
48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.
48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope
Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope Rakesh Sidharthan 1 Gnanavel B K 2 Assistant professor Mechanical, Department Professor, Mechanical Department, Gojan engineering college,
Flexible Control Cables
Works photo: KUKA Flexible Control Cables A Flexible Control Cables Since generations people try to build machines and plants which shall take on different functions. To raise, sink, slide, drill, transport
1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide
1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover
Catalog May 2015. Cable Accessories < 1 kv
Catalog May 2015 Cable Accessories < 1 kv Table of content Cable Accessories 1 Cable Accessories 1 kv Product range 2 Universal cleats 3 List of content 4 Notes 5 We reserve the right to make technical
Voltage Detection and Indication by Electric Field Measurement
Voltage Detection and Indication by Electric Field Measurement William McNulty, P.E. Technical Director Voltage Detection and Indication by Electric Field Measurement William McNulty, P.E. HD Electric
Power Resistor Thick Film Technology
Power Resistor Thick Film Technology LTO series are the extension of RTO types. We used the direct ceramic mounting design (no metal tab) of our RCH power resistors applied to semiconductor packages. FEATURES
Comparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
Experimental results for the focal waveform and beam width in the focusing lens with a 100 ps filter
EM Implosion Memos Memo 51 July, 2010 Experimental results for the focal waveform and beam width in the focusing lens with a 100 ps filter Prashanth Kumar, Carl E. Baum, Serhat Altunc, Christos G. Christodoulou
Electrical tests on PCB insulation materials and investigation of influence of solder fillets geometry on partial discharge
, Firenze, Italy Electrical tests on PCB insulation materials and investigation of influence of solder fillets geometry on partial discharge A. Bulletti, L. Capineri B. Dunn ESTEC Material and Process
Respecting the environment
MAIN FEATURE CHAPTER I RESEARCH WITH AN EYE ON THE FUTURE Respecting the environment Low power losses and a lesser visual impact on the landscape make Gas-Insulated Lines (GIL) a very environmentally friendly
UPSETTING OF BIMETALLIC COMPONENTS IN CLOSED DIE
Engineering Review Vol. 31, Issue 2, 105-109, 2011. 105 UDC 621.961:621.792.3:539.378.2 UPSETTING OF BIMETALLIC COMPONENTS IN CLOSED DIE Miroslav PLANČAK Zlatan CAR Dragiša VILOTIĆ Dejan MOVRIN Marko KRŠULJA
0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N
55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils
General Calculations. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE
Excerpt from PRYMIAN WIRE AND CABLE ENGINEERING GUIDE Page 1 of 0 Voltage Rating The selection of the cable insulation level to be used in a particular installation shall be made on the basis of the applicable
MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES
MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES Riccardo BODEGA, Prysmian Cables and Systems, The Netherlands, [email protected] Henk GEENE,
Direct Attach Cable with Micro Coaxial Wire for Data Center
FEATURED TOPIC Direct Attach Cable with Micro Coaxial Wire for Data Center Yasuhiro MAEDA*, Kensaku SHIMADA, Yuki ISOYA, Tatsunori HAYASHISHITA and Michiko HARUMOTO ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
HV Submarine Cable Systems Design, Testing and Installation
HV Submarine Cable Systems Design, Testing and Installation CIGRE Ireland Technical Seminar 6 th October 2010 Robert Donaghy Senior Consultant Engineer, ESB International Presentation Overview Applications
FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR
FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR Standards : CENELEC HD 22.4 NF C 32-102-4 DIN VDE 0282-1 and VDE 0282-4 BS 6007 and BS 6500 IEC 60245-4 Rated voltage Rated voltage: 450/750 V (Use up to
Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow
ingle Conductor Cable Copper heathed Cable heath Currents ingle conductor cables present certain application considerations that do not arise in multiconductor cable installations. These considerations
Gulf Cable & Electrical Ind. Co.
CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC
HSP GmbH Zum Handwerkerhof 2 90530 Wendelstein Tel. 09129 / 2852-0 Fax: 09129 / 2852-11 Web: www.hsshsp.de EMAIL: [email protected] NTG-3000.
NTG-3000 Transducer Data Sheet Document Version 2.8 Page 1 of 10 Versions / Revisions: Document Creation Author Description version date 2.0 2012-07-25 P. Compensis First official version 2.1 2012-08-24
Vert-X 16-5V / 10...90% Ub. Applications Servodrives Dancer arm Operating table
Version MH-C MH-C2 Electrical data Measuring range 0... 360 - Indep. linearity % meas. range ±0.3 - Max. hysteresis 0.1 - Resolution bit 12 - Max. repeatability 0.1 - Sample rate fast mode khz (5) - Sample
Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness
Product Information Mylar polyester film Electrical Properties Mylar offers unique design capabilities to the electrical industry due to the excellent balance of its electrical properties with its chemical,
A new technology for high current, low insertion force, low resistance and long cycle life power connectors
A new technology for high current, low insertion force, low resistance and long cycle life power connectors Abstract Methode has developed a new class of patented power connector named PowerBud TM that
The Contractor shall furnish and install all shielded power cable suitable for use on this project.
Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS