Cable Solutions for Servo and Variable Frequency Drives (VFD)
|
|
|
- Ralph Reed
- 9 years ago
- Views:
Transcription
1 Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect to the application. Standard drive systems consist of three-phase, alternating-current, asynchronous motors and related controls via frequency converters. A frequency converter consists of two Insulate Gate Bipolar Transistor (IGBT)-controlled units: 1) a rectifier that is connected to a three-phase, alternating current with a given frequency f 1 (e.g. 50 or 60 Hz), which generates a pulsating direct current; 2) an inverter that reconverts the direct current in a new alternating voltage with variable level and frequency f 2 (0 to 400 Hz). Using the motor supply cable, the speed of the servo motor can be precisely controlled by changing the frequency f 2. Negative Effects The benefits of frequency converters precise and continuous variable torque and speed control come along with certain negative effects that should be taken into consideration: - Strong electromagnetic interference through the motor power supply cable - High overvoltage in the supply cable - High leakage and interference currents The strong electromagnetic interference results from the extremely short turn-on and turn-offtimes of the IGBTs (nanoseconds) and from the high pulse frequencies of the frequency
2 converter (up to 20 khz). This leads to a very high proportion of harmonic waves of the sinusoidal output voltage of the converter. The strong electromagnetic emissions, emanated especially from motor supply cables, result in major interference with the distribution network, the devices and data transfer. As a consequence, the European standard EN (July 2005) specifies the maximum interference level of drive systems in order to ensure that signal transmissions are adequately protected against interference. This regulation, which differentiates between category C1 residential areas and category C3 industrial areas, establishes the maximum permissible interference levels of the radio interference voltage from 0.15 MHz up to 30 MHz, and of the radiated electromagnetic interference from 30 MHz up to 1,000 MHz (1 GHz). However, interference can be avoided if well-shielded cables and, in special cases, cables with additional line filters are used. Problems with Electrical Surge The voltage generated by the frequency converter has a fundamental wave with an approximate sinusoidal course and an impressed frequency between 0 and 400 Hz, depending on the set motor speed. That process also creates harmonics in a high frequency range of approximately 100 MHz. The fundamental wave and the harmonics are transmitted to the motor via the motor supply cables. When the characteristic impedance of the motor supply cable is changed, impulse waves are generated at the beginning and end of the cable, which in turn generate electrical surge through reflection of the harmonics (called reflected wave phenomenon). This only occurs if the length of the motor supply cable is greater than the wavelength of the harmonic. With short cable lengths, i.e. if the cable length is shorter than the wavelength, transient responses appear at the frequency converter output. As a result voltages are generated that are two to three times greater than the motor voltage. Those voltage peaks place a recurring load on the insulation of the motor supply cable. For this reason the insulation must be dimensioned in such a way that those voltage peaks do not have any harmful effects (e.g. failure of cable due to arcing between conductors to shield). The high frequencies at the converter output mean that high capacitance leakage currents are generated, which flow over the shield and the motor housing to the earth, and thus determine the cross-section of the braided shields and the shield connections. The shield
3 must be designed in such a way that it is not excessively heated by the current flowing through it. Especially with long cable lengths, high earth capacitance can result in reactive currents, which burden the frequency converter. Due to the inverter's over-current limit, it might no longer be possible to transmit the necessary active power to the motor. Adequate care must also be taken to properly ground these currents and not change the voltage potential which will affect the clock timing. Using a HELUTOP EMC cable gland and attaching the cable ground wire to the panel bus ground terminal are good practices to help prevent this problem. The reactive current does not contribute to torque generation at the motor and flows to the ground as current leakage via the shield and metallic motor parts. It can also flow through the ball bearing of the motor shaft, which can result in damage, such as depressions in the ball bearing rings. In order to compensate for the above-mentioned effects of frequency converter technology, HELUKABEL offers motor supply cables with optimized characteristics. Both the material used and the design are specially adapted for this application. HELUKABEL TOPFLEX -EMV UL/CSA The electromagnetic compatibility (EMC) requirements according to EN are fulfilled by a double shielding of special aluminum foil and an optimized braided shield of tinned copper wire with a high degree of coverage (approx. 80%). The special suitability in the frequency range from 30 to 1,000 MHz is easily demonstrated using comparative measurements of the radiated electromagnetic noise from unshielded power supply cables and shielded EMC power supply cables from HELUKABEL. For the low frequency range of 1 MHz up to 30 MHz the high interference protection is shown by the extremely low coupling resistance of the shielded cables. EMC Tests on Motor Supply Cables The measurements were made in an EMC laboratory
4 The results of the interference level measurements show clearly that the HELUKABEL motor supply cable with an optimal shield did not exceed the limit values for interference field strength according to EN Moreover, the interference field strengths of the unshielded cable are significantly above the limit values for industrial and residential areas, especially at low frequencies. Results of Measurements of the Coupling Resistance Rk (Ohm/km) Cable type: Manufacturer: TOPFLEX -EMV 2YSLCY J 0.6/1kV HELUKABEL GmbH In the low frequency range between 1 MHz and 30 MHz a low coupling resistance was measured, resulting in low interference field strength in the surrounding area. No. conductors x cross-sec. (mm 2 ) 1 MHz Ohm/km 4 x 2.5 (AWG 14) x 4 (AWG 12) x 6 (AWG 10) x 10 (AWG 8) x 16 (AWG 6) MHz Ohm/km
5 4 x 25 (AWG 4) x 35 (AWG 2) x 50 (AWG 1) x 70 (AWG 2/0) x 95 (AWG 3/0) 1 50 The conductor insulation of TOPFLEX -EMV and TOPFLEX MOTOR-EMV cables consists of electrically high-quality materials based on polyethylene (PE). The special insulation is designed for the permanent voltage peaks of the converter's nominal voltage. Nominal voltage: Max. permissible operating voltage: U o = 600 V U b = 1200 V The frequency converter output can also be equipped with an electrical filter which filters out the high-frequency harmonics and smoothes out the voltage peaks. Impedance Matched Cables Due to the low dielectric constant of the special conductor insulation the TOPFLEX -EMV and the TOPFLEX MOTOR-EMV have a lower operating and shield capacitance than traditional PVC-insulated motor supply cables. As a result the capacitance disturbance currents are considerably reduced, enabling low-loss power transmission from the converter to the motor. Moreover, the high quality of the cable insulation provides a long service life. These characteristics are further improved by a symmetrical cable structure with three balanced power conductors and a ground conductor which is divided into thirds ( conductor design) in the cable types TOPFLEX - EMV 3 PLUS and TOPFLEX MOTOR-EMV 3/3 cables. This results in an additional optimization of the power transmission from the frequency converter to the motor. Reeling after braiding at the HELUKABEL factory HELUKABEL MOTORFLEX-EMV cable TC-ER and Continuous Flex Applications In addition to high-end motor cables, HELUKABEL offers a wide range of tray rated cables according to UL 1277, NFPA and CSA FT4 for fixed or continuous flex applications. The TRAYCONTROL 600 and TOPSERV 600 VFD cable possess a superior oil performance of Oil Res I and II and are designed for use in dry, high humidity and damp environments and in the open unprotected installation in the cable tray or track.
100% EMI Emission Containment
100% EMI Emission Containment Designed for Longer Service Life Highly Flexible for Easier Handling and Faster Installation Authorized Distributor Industrial VFD Cables Index n Variable Frequency Drive
WHITEPAPER. Cable and Connector for Hiperface dsl motor drive applications
WHITEPAPER Cable and Connector for Hiperface dsl motor drive applications information for cable manufacturers Version 02 Content Information for cable manufacturers...3 Communication...3 Crosstalk & shielding...3
Flexible Control Cables
Works photo: KUKA Flexible Control Cables A Flexible Control Cables Since generations people try to build machines and plants which shall take on different functions. To raise, sink, slide, drill, transport
SICK AG WHITEPAPER. Information for cable manufacturers Note-2_03
SICK AG WHITEPAPER Cable and connector for HIPERFACE DSL motor drive applications Information for cable manufacturers Note-2_03 Juergen Funkhaenel Application Engineer at SICK STEGMANN GmbH Donaueschingen
Relés e Contatores de Estado Sólido SIRIUS
Relés e Contatores de Estado Sólido SIRIUS Coletânea de dados técnicos ( product data sheet ) Agosto/212 SSR - 3RF21 22,5 mm Ponto Zero SSR - 3RF2 45 mm Ponto Zero SSR - 3RF22 45 mm Ponto Zero Trifásico
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
Servo Motor & Drive Cables
Servo Motor & Drive Cables Servo-Motor & Drive Cable Contents Servo-SM (Servo-Motor & Feedback Cables to Siemens Specifications) 970 SERVO-SM5-6FX5008-1BD.. UL/CSA/CE SHLD PVC Feedback Cable- Green 971
Energy Management Energy Meter Type EM23 DIN
Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy
Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER. www.ep2000.com 800.500.
Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER Introduction Heat in the System The modern facility has been revolutionized by advancements
Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
Features. Picture. Specifications
Type: for level measurement Order No.: see Table 1 / Page 4 Features Picture Two wire system Piezoresistive measuring element Output signal 4-20 ma Conformity error ±0.5 % FS or Standard DIN measuring
Analog signal converters CC-E I/I Current / current isolators
ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between
EMI in Electric Vehicles
EMI in Electric Vehicles S. Guttowski, S. Weber, E. Hoene, W. John, H. Reichl Fraunhofer Institute for Reliability and Microintegration Gustav-Meyer-Allee 25, 13355 Berlin, Germany Phone: ++49(0)3046403144,
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
Installation Considerations for IGBT AC Drives
Installation Considerations for IGBT AC Drives G. Skibinski Rockwell Automation 6400 W. Enterprise Drive Mequon, WI 53092 Abstract: In the last four years, Adjustable Speed ac Drive (ASD) manufacturers
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
Consideration of a high-capacity foil cable:
Consideration of a high-capacity foil cable: Newly discovered ancient knowledge. The old RF-developers already knew the benefits of longplanar lines and have been used (electronic) Eonen (times) thin flat
Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ
Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac & 230Vac NEC Class 2 / Limited
CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number: 900-4602-0000
Electrical Specification for: CPCI-3U-AC-300W-R Rugged 300W AC Input 3U CompactPCI Power Supply Telkoor Part Number: 900-4602-0000 GENERAL SCALE RELEASE DATE 12/9/06 SHEET 1 OF 6 REVISION HISTORY Rev Level
Technical Description. Transistor D.C. Chopper Controller Type GS 24 S
Technical Description Transistor D.C. Chopper Controller Type GS 24 S Table of contents 1. Getting started guide 2. General information 2.1. Characteristics 2.2. Accessories 3. Information about the Machine
PROFIBUS cable. for PROFIBUS-PA and -DP 10/63-6.46 EN
for PROFIBUS-PA and -DP 10/63-6.46 EN CPN 080/CPE 080-Ex PROFIBUS-PA basis cable AWG 18, 0.88 mm 2 Use For fixed installation indoor and outdoor, on racks and in conduits. Application Fieldbus cable for
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
Nexus Technology Review -- Exhibit A
Nexus Technology Review -- Exhibit A Background A. Types of DSL Lines DSL comes in many flavors: ADSL, ADSL2, ADSL2+, VDSL and VDSL2. Each DSL variant respectively operates up a higher frequency level.
Unarmored Variable Frequency Drive (VFD) Cable Termination Guide
Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored
Understanding Shielded Cable
Understanding Shielded Cable Industrial applications such as the factory floor are typically electrically noisy environments. Electrical noise, either radiated or conducted as electromagnetic interference
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
WIND TURBINE TECHNOLOGY
Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems
STRATO LED Drivers 70W, Single output
Features STRATO switch mode driver technology is designed to generate one constant current output from a wide range AC input. The size and performance of these products make them the ideal choice for LED
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
C 060 CCTV Coaxial Cable
C 060 CCTV Coaxial Cable These cables are used for video transmissons of CCTV applications..4...... Coaxial Cable (C 060).. Inner Conductor : Ø 0.60 mm Bare Copper.. Insulation : Ø.80 mm Gas-injected Foam
Photo: HELUKABEL. Cables according to International Approvals N 1
Photo: HELUKABEL Cables according to International Approvals N 1 Cables according to International Approvals The installation of cables and wires according to overseas standards is getting more and more
80 Series - Modular timers 16 A. Features 80.01 80.11
80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h
TEST REPORT EN 55014-2 (1997) +A1 (2001)
Page 1 of 23 TEST REPORT EN 55014-2 (1997) +A1 (2001) Electromagnetic compatibility - Requirements for household appliances, electric tools and similar apparatus Part 2: Immunity Report Reference No....
80 Series - Modular timers 16 A. Features 80.01 80.11
80 Series - Modular timers 6 A 80. Multi-function and mono-function timer range - Multi-function & multi-voltage 80. - ON delay, multi-voltage 7.5 mm wide Six time scales from 0.s to 24h 35 mm rail (EN
DSD 70 Dual Channel Hall Effect Speed Sensor for Railway Applications, compliant with EN 50155
DSD 70 Dual Channel Hall Effect Speed Sensor for Railway Applications, compliant with EN 50155 Technical information Version: 07.14 General Function The speed sensors family DSD.70 are suitable for generating
Technical Article. EMC filters for medical devices
Technical Article EMC filters for medical devices September 2010 EMC filters for medical devices Schaffner, the market leader in EMC filters and power quality, has supplemented its proven IEC inlet filter
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
Simulation and Analysis of PWM Inverter Fed Induction Motor Drive
Simulation and Analysis of PWM Inverter Fed Induction Motor Drive C.S.Sharma, Tali Nagwani Abstract Sinusoidal Pulse Width Modulation variable speed drives are increasingly applied in many new industrial
< SD 200 C TP Continuously flexible TPE/PUR paired data cable with coloured cores and overall copper screen... 10
CONTENT General < The Company..................................................................................... 3 Customized cables for different applications < Data / POF Cables POF-LWL and hybrid
DATA SHEET SERVO LK SMS FX8PLUS SIGNAL
Application LAPP servo cables according to Siemens * (see footnote) Standard FX8008 PLUS SIGNAL are a new generation of very highly flexible screened signal (encoder and resolver)- cables (P/Ns 00277101
CIR. Index. Gexol. Standard CIR UL Listed Type TC-ER. Crush and Impact Resistant Without External Armoring. Arctic CIR UL Listed Type TC-ER-HL*
Gexol CIR Crush and Impact Resistant Without External Armoring Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL n Available in Standard and Arctic Grade Jackets n Highly
UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS
Page 1 UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS By Henry Ott Consultants Livingston, NJ 07039 (973) 992-1793 www.hottconsultants.com [email protected] Page 2 THE BASIC
Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ
Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac, > 89.0% @ 230Vac NEC Class
Power transformers. Special transformers Railway
Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together
Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG
Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range
with coloured cores and overall copper screen UL/CSA... 17
CONTENT Cable Track Cables y SD 200 extremely flexible TPE/PUR data cable with coloured cores for continuous movement..... 6 y S 200 extremely flexible TPE/PUR control cable with numbered cores for continuous
Screened cable and data cable segregation
December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE Karl M. Hink, Executive Vice President Originally presented at the Power Quality 99 Conference ABSTRACT Motor protection
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Classically both cables have a single AWG 8 copper conductor or a cross section of
Voltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase
EMC Basics. Speaker : Alain Lafuente. [email protected]
EMC Basics Speaker : lain Lafuente [email protected] WHT IS EMC? 2 CE Marking With the formation of the single European market, standardization was required to remove technical barriers to trade.
Type: DILM32 10(24V50HZ) Article No.: 277247
Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,
LOW LOSS CABLE PAG. 1
LOW LOSS CABLE PAG. 1 INTRODUCTION Following many requests we received regarding the need for low-loss custom cable assemblies, we have set up a special production of high performance coaxial cable assemblies
Specification guide no. 9 Active harmonic conditioner from 20 to 480 A
Active harmonic conditioner from 20 to 480 A Contents 1 - Installations concerned... 2 1.1 - New installations... 2 1.2 - Existing installations... 2 2 - General... 2 2.1 - Scope... 2 2.2 - Applicable
with Component Rating A Simple Perspective
Cat-6A UTP and Shielded with Component Rating A Simple Perspective Asef Baddar RCDD, DCD Sr. Technical Manager Leviton Middle East Category Specifications Agenda Terminology International & North America
Solving Signal Problems Effective shielding is key to enhancing the reliability and performance of broadcast cables.
Solving Signal Problems Effective shielding is key to enhancing the reliability and performance of broadcast cables. by Marty Van Der Burgt Belden Article for Broadcast Engineering There is perhaps no
Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE
Local Area Networks (LAN) Servers Data centers Internet centers (ISP/ASP/POP) Industrial PLCs EPOS (Electronic Point of Sale) Systems Emergency devices (lights/alarms) Electro-medical devices Telecommunication
FN2001-A1 Network module (SAFEDLINK) Mounting Installation
FN00-A Network module (SAFEDLINK) Mounting Installation A6V050_f_en_-- 05-0-6 Building Technologies Division Legal notice Legal notice Technical specifications and availability subject to change without
75 Ω Transmission System
NRAO NTC-DSL Laboratory Report Dynamic Spectroscopy Laboratory Report Series Report 03 September, 2006 75 Ω Transmission System Chaitali R. Parashare Department of Electrical and Computer Engineering,
EMC Standards: Standards of good EMC engineering
Electromagnetic Compatibility (EMC) IEEE Definition Origin, control, and measurement of electromagnetic effects on electronic and biologic systems. IEEE EMC Society Areas of Interest EMC Standards: Standards
EMOSAFE EN-100. Network Isolators for PCB assembly 1 GENERAL DESCRIPTION. Product Data Sheet ENGLISH
ENGLISH EMOSAFE EN-100 Product Data Sheet Network Isolators for PCB assembly November 2013 1 GENERAL DESCRIPTION The EMOSAFE EN-100 Network Isolator interrupts all galvanically conducting connections (conductors
RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
Thermistor motor protection
Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor
Waveguide Access Point WGA631. Product Guide
Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................
CHALLENGES AND REQUIREMENTS IN VFD CABLE DESIGN BASTIAN GÖRICKE STEFAN GRUNWALD CHARLOTTE, NC VERSION 1.1
CHALLENGES AND REQUIREMENTS IN VFD CABLE DESIGN BASTIAN GÖRICKE STEFAN GRUNWALD CHARLOTTE, NC VERSION 1.1 Lutze, Inc. 13330 South Ridge Drive [email protected] Charlotte, NC 28273 +1-800-447-2371 Table of
38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
Thermistor motor protection relays CM-MSS.22 and CM-MSS.23
Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,
Separation of power and information technology cabling
Technical bulletin Separation of power and information technology cabling Date: 08/2006 This technical bulletin provides you with information on specific technical subjects. It is based on the current
GenTech Practice Questions
GenTech Practice Questions Basic Electronics Test: This test will assess your knowledge of and ability to apply the principles of Basic Electronics. This test is comprised of 90 questions in the following
Subminiature Load Cell Model 8417
w Technical Product Information Subminiature Load Cell 1. Introduction... 2 2. Preparing for use... 2 2.1 Unpacking... 2 2.2 Using the instrument for the first time... 2 2.3 Grounding and potential connection...
Telephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
Uniprise Solutions COAX 101. White Paper. www.commscope.com
Uniprise Solutions COAX 101 White Paper www.commscope.com Structured cable systems have very thorough standards for fiber optic and twisted pair installations. The cabling components and installed systems
RC NETWORKS SALES GUIDE
SALES GUIDE INTRODUCTION TO Recent developments in electronic equipment have shown the following trends: Increasing demands for numerical control machines, robotics and technically advanced appliances
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Specification SFTP CAT6 Network Cable 23AWG CU
Specification SFTP CAT6 Network Cable 23AWG CU S/FTP CAT6 Shielded S/FTP PVC Cable 23AWG 4pair Solid, Wooden drum 1000 Grey CAT6 600MHZ CM Shielded (S/FTP) Solid Cable: Our CAT6 600MHZ Shielded (S/FTP)
Introduction. Harmonics and IEEE 519 Page 1 of 19
Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy
What Are the Benefits of Using VFD Motors?
Introduction Choosing the Right Cable for your Variable Frequency Drive (VFD) System By Brian Shuman, Senior Product Development Engineer Belden Table of Contents Introduction.............................
Good EMC Design Principles: cable routing
Good EMC Design Principles: cable routing Keith Armstrong describes three important techniques for cable routing in metal cabinets, whether the cables are bundles of individual wires, or individual or
Industrial Cable Solutions for Variable Frequency Drives
Industrial Cable Solutions for Variable Frequency Drives Tough challenges call for innovative solutions, and General Cable is your worldwide source for new products and a wide range of industry-leading
Clamp Filters that Suppress Emission Noise Provide Immunity Against Surge Noise
TDK EMC Technology Product Section Clamp Filters that Suppress Emission Noise Provide Immunity Against Surge Noise TDK Shonai Corporation Satoru Saito Reduce Emission Noise from Cables Even if an electronic
PI734D - Technical Data Sheet
PI734D - Technical Data Sheet PI734D SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
PI734B - Technical Data Sheet
PI734B - Technical Data Sheet PI734B SPECIFICATIONS & OPTIONS STANDARDS Newage Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international
Magnet field- and Radiation Tolerant New Power Supply System MARATON - Technical Overview. 22-Sep-03 1
Magnet field- and Radiation Tolerant New Power Supply System MARATON - Technical Overview 22-Sep-03 1 Modular Power Supply System MARATON 2 Versions: To power crates (UEP6..) or generic electronics (PL5..)
Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
Cable Guide. Cables, Connectors & Tools for installation of quality networks. TRIAX - your ultimate connection
Cable Guide Cables, Connectors & Tools for installation of quality networks TRIAX - your ultimate connection A Selection of the best Triax TX Cable range optimised for digital reception Simplification
Fault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
Communication, Signal & Data Cables
Communication, Signal & Data Cables Used for indoor installation and interconnection of transmission, telephone, telegraph and electronic equipment as well as media equipments www.alfanar.com Communication
15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE
Series - Electronic step relay and dimmer SERIE Features.91.51.81 Electronic step relay and dimmer for control of lighting levels Suitable for incandescent and halogen lighting loads (with or without transformer
Series 6000 Torque measured metal bellow coupling
Properties Free of float metal bellow coupling with integrated torque measurement Non-contact measurement system, high robustness High torsional stiffness Limited torque of inertia Performance Measurement