1 NEW POL DEPOT AT HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & S GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI TECHNICAL SPECIFICATION OF XLPE, FRLS LT CABLES FOR DEPOT 1

2 NEW POL DEPOT AT 1.1 GENERAL : a) The cables will be used for connection of power, control and instrumentation circuits of the auxiliary electrical systems. b) Cables are to be suitable for transmission of signals and measuring values, which require protection against disturbances caused by stray fields. c) Cables will be generally laid in ladder type trays or, drawn through rigid steel conduits. For interplant connection cables may be directly buried in ground. d) The insulation and sheath materials shall be resistant to oil, acid and alkali and shall be tough enough to withstand mechanical stresses during handling. e) For continuous operation at specified rating, maximum conductor temperature shall be limited to permissible value as per relevant standard and / or this specification. f) Armoring shall be single round wire of galvanized steel for multicore cables and aluminium for single core cables g) Core identification for multicore cables shall be provided by colour coding. h) Multicore control cables shall generally have commissioning spare cores in accordance with the following chart when used for control and indication, interlock and annunciation purpose 1.2 OPERATING CONDITION : All equipment and materials will be selected and rated for use at the following site conditions. a) Electric system b) System Voltage : 433 V +/- 10% c) Frequency : 50 Hz. +/- 3% Environment 2

3 NEW POL DEPOT AT d) Ground temperature : 40 C. e) Ambient air temperature : 45 C. f) Earth resistivity : 120 C. cm/w presssumed g) Atmospheric conditions : Humid, salty and dusty 1.3 SCOPE : The scope shall cover supplying, testing, Inspection, Transport and loading of low voltage power and control XLPE FRLS cables. This specification gives the general requirement of cables. However, it is the responsibility of the vendor to take the joint measurement and obtain client s approval before the placement of orders to the main supplier / manufacturer. 1.4 DESIGN CONDITION : The following standards and rules shall be applicable: IS: 7098 Part I - XLPE Insulated electric cables (heavy duty). IS: Aluminum conductors for insulated cables. IS : Conductors for insulated electric cables and flexible cords. IEC : 228 Conductors of Insulated Cables. IS: (Pt 58) Methods of test for cables : Part 58 Oxygen Index test IS: (Pt 61) Methods of test for cables : Part 61 Flame retardant test IS: (Pt 62) Methods of test for cables : Part 62 Flame retardant test for bunched cables IEC : 502 Extruded solid dielectric-insulated power cables for rated voltage from 1 KV upto 30 KV. IS:1885-(Part32) Electro Technical vocabulary - electric cables (1993) IS:3961-(Part4) Recommended current ratings for Polyethylene insulated cables. 3

4 NEW POL DEPOT AT (1968) IS:3975-(1988) Mild steel wire, formed wires and tapes for armouring of cables. IS: 5831-(1984) Specification for PVC insulation and sheath of electric cables. IS: 6474-(1984) Specification for Polyethylene insulation and sheath of electric cables. IS: (1982) Drums for electric cables. IS:10462(Part1) Fictitious calculation method for determination of dimensions of protective (1983) coverings of cables IEC:60540&60540A Test methods for insulation & sheaths of electric cables IEC:230 (1966) Impulse tests on cables and their accessories IEC:60332(3Parts) Tests on electric cables under fire conditions IEC:811(5Parts) Test methods for insulating and sheathing materials of electric cables. ASTM:D2863 Standard method for test for flammability of plastics using oxygen index Method IECAS Thermoplastic insulated wire & cable for transmission & distribution of NEMA-WC5 electrical energy IECAS Cross linked thermosetting poly ethylene insulated wire & cable for NEMA-WC5 transmission & distribution of electrical energy IEC : 287 Calculations of continuous current rating of cables (100% load factor). IS : PVC insulation & sheath of electrical cables. Indian Electricity Act and Rules. 1.5 MEASUREMENTS : The cables will be measured in meters. The unit rate shall include packing, loading, insurance, transportation, delivery to stores/site as per work order, testing of cables at their works etc. of low voltage cable. 4

5 NEW POL DEPOT AT 1.6 MATERIAL : The low voltage cable shall be XLPE insulated. PVC outer sheathed, aluminium or copper conductor, armoured conforming to IS: 7098 Part I. 1.7 TYPE : The cables shall be circular, single/multi core, annealed copper or aluminium conductor, XLPE/ FRLS insulated and PVC outer sheathed, armoured. 1.8 GENERAL DESCRIPTION: A) The LT power cable shall be designed, manufactured and tested in accordance with IS: 1554, IS: 8130, IS: 5831, IS: The cable shall be 1100 V grade, 85 Deg.C rating heavy duty, HR (Heat Resistant) PVC power cable. Conductor : Stranded and compacted plain Aluminium of grade H2 and class 2 for all sizes. Insulation : Extruded XLPE Compound conforming to type C. The insulation shall be of cross linked polyethylene (XLPE) compound with anti oxidant stabilisers and shall conform to IS-7098, Part-1. (As applicable) Inner Sheath: Inner sheath is provided over the laid up cores. It is provided to give circular shape to the cable and it provides bedding for the armouring. PVC Compound conforming to type ST2 for three core cables. Single core cables shall have no inner sheath. Armour: Galvanized single round steel wire armour for three core cables. Non- magnetic hard-drawn aluminium single round wire conforming to H4 grade for single core cable. (1) Armouring shall be one of the following: - 5

6 NEW POL DEPOT AT (a) (b) (c) Galvanized round steel wire Galvanized steel strip Any metallic non-magnetic wire/strip. (2) Where the cable diameter below armour does not exceed 13mm, the armour shall consist of galvanized round steel wires. Where the diameter below armouring is greater than 13mm, the armour shall consist of either galvanized round steel wires or galvanized steel strips. (3) The joints in armour wires or strips shall be made by brazing or welding and any surface irregularities shall be removed. Overall Sheath: Extruded PVC compound conforming to ST2. Outer sheath shall be of an extruded type layer of suitable PVC material compatible with the specified ambient temp. 50 deg. C and operating temperature of cables. The sheath shall be resistant to water, ultraviolet radiation, fungus, termite and rodent attacks. The colour of outer sheath shall be black. Sequential length marking required at every 1.0 mtr. interval on outer sheath. B) The LT control cable shall be designed, manufactured and tested in accordance with IS: 1554, IS: 8130, IS: 5831, IS: The cable shall be 1100 V grade, 70 Deg.C rating ordinary PVC control cable. Conductor: Stranded, non-compacted and circular, class 2 high conductivity untinned annealed copper. Insulation: Extruded XLPE Compound conforming to type A Inner Sheath :PVC Compound conforming to type ST1 for three core cables. Single core cables shall have no inner sheath. Armour: Galvanized single round steel wire armour for three core cables. Non-magnetic harddrawn aluminium single round wire conforming to H4 grade for single core cable. In case of armoured cables, generally galvanized steel wire / strip armouring is provided over the inner sheath in multicore cables and Aluminium Round Wire or Aluminium Strip over the insulation in 6

7 NEW POL DEPOT AT single core cables. It provides mechanical protection to inside cores and it carries earth return current in case of a short circuit of a core with armour. As per I.S (Part I) 1988, round wire armouring is provided in cable, where calculated diameter under armour is up to 13 mm. Above this the armouring is either with round wire or strip of size 4 mm x 0.80 mm. As strip construction is economical, the manufacturers always provide steel strip armouring unless wire armouring is specially specified. 1.9 CORE IDENTIFICATION : Cores of cable shall be identified by colour coding of PVC insulation by adopting the following scheme. 1 core : Red, black, yellow, blue or natural Two core : Red and Black Three core : Red, Yellow and Blue Three & Half core : Red, Yellow, Blue and Black Four core : Red, Yellow, Blue and Black Single core : Green, Yellow for earthing Black shall always be used for neutral. The core identification shall be done by printing numbers or by providing colored strips all along cores. The insulation of cores shall be of the same colour and numbered sequentially. The numbers shall be printed in Hindu-Arabic numerals on the outer surface of cores. The numbers shall be repeated at regular intervals along the core and the spacing between consecutive numbers shall not exceed 50mm ASSEMBLY : Two, three or four insulated conductors shall be laid up, filled with non-hygroscopic material and covered with an additional layer of thermoplastic material. 7

8 NEW POL DEPOT AT 1.11 GENERAL REQUIREMENT : All cables shall be adequately protected against any risk of mechanical damage to which they may be liable in normal conditions of handling during transportation, loading, etc. The cable shall be supplied in single length i.e. without any intermediate joint or cut unless specifically approved by the client. The cable ends shall be suitably sealed against entry of moisture, dust, water etc. with cable compound as per standard practice INSPECTION & TESTING : 1 Inspection and testing shall be carried out in accordance with relevant standards. Routine tests shall be witnessed by HPCL approved Third Party Inspection Agency like BV/ EIL/ IRS/ DNV/ TUV. Test certificates for type test shall be furnished. Vendor shall quote unit rate for witnessing such type test by TPI Agency. 2 Vendor shall submit blank formats where in the test results/readings are to be entered. This format shall give minimum acceptable value as per the relevant standards. 3 The inspector shall have free access to the manufacturer s works for the purpose of inspecting the process of manufacture in all stages and he will have the power to reject any material which appears to him to be of unsuitable description or of unsatisfactory quality. The vendor shall give at least 2 weeks prior notice to the purchaser, regarding the date of testing to enable him or his representative to witness the tests. A) FINISHED CABLE TESTS AT MANUFACTURER S WORKS: All routine tests, acceptance tests, type tests & additional type tests for improved fire performance shall be carried out as listed in IS-7098 (Part-1). 8

9 NEW POL DEPOT AT The finished cables shall be tested at manufacturer s works. Following routine tests for each and every length of cable and copy of test results shall be furnished for each length of cable along with supply. If specified, the cables shall be tested in presence of client s representative. a) VOLTAGE TEST: Each core of cable shall be tested at room temperature at 2.5 KV A.C. for duration as specified in relevant IS. b) CONDUCTOR RESISTANCE TEST: The D.C. Resistance of each conductor shall be measured at room temperature and the results shall be corrected to 20 c. to check the compliance with the values specified in IS c) THE TEST FOR RESISTANCE TO ULTRAVIOLET RADIATION: This test shall be carried out as per DIN or ASTM-G-53 on outer sheath. The retention value of tensile strength & ultimate elongation value after the test shall be minimum 60% of the tensile strength and elongation value before the test. The test certificates with respect to this test (not older than 1 year) from recognized testing laboratory to be furnished for review by PMC before dispatch clearance of cables. In case test certificates are not available, test is to be conducted by vendor at his own cost in any recognized test laboratory or in-house testing laboratory, before dispatch clearance of cables. Sampling for this test is to be carried out one for each order, provided the outer sheath remains the same. d) Acceptance tests as per IS-1554 Part-1 and IS-7098 Part-1 and the following special tests to be performed on the cables as per the sampling plan. This tests are to be witnessed by PMC/ Owner before the dispatch of cables: a) Accelerated Water absorption test for insulation as per NEMA WC-5 (For PVC insulated cables) and as per NEMA WC-7 (For XLPE insulated cables). Test certificates with respect to this test (not older than one year) from recognized testing laboratory to be furnished for review by PMC before dispatch, clearance of cables. In case test certificates are not available, test is to be conducted by vendor at his own cost in any recognized test laboratory or in- 9

10 NEW POL DEPOT AT house testing laboratory, before dispatch clearance of cables. Sampling for this test is to carried out one for each order. 1. Dielectric Retention test: The dielectric strength of the cable insulation tested in accordance with NEMA WC-5 at 75 ± 1 o C shall not be less than 50% original dielectric strength. Test certificates with respect to this test (not older than one year) from recognized testing laboratory to be furnished for review by PMC before dispatch, clearance of cables. In case test certificates are not available, test is to be conducted by vendor at his own cost in any recognized test laboratory or in-house testing laboratory, before dispatch clearance of cables. Sampling for this test is to carried out one for each order. 2. Oxygen Index Test: The test shall be carried out as per ASTM D2863 or applicable Indian Standard specifications. Sampling to be done for every offered lot / size as per sampling plan. 3. Flammability Test: The test shall be carried out on finished cable as per IS (part 61 & 62). Sampling for this test is to be carried out one for each order, provided the outer sheath remains the same. The acceptance criteria for tests conducted shall be as under: Part-61: The cable meets the specifications if there is no visible damage on the test specimen within 300 mm from its upper end. Part-62: The maximum extent of charred portion measured on the test sample should not have reached a height exceeding 2.5m above the bottom edge of the burner at the front of the ladder. 4. Test for rodent & termite repulsion property: The vendor shall furnish details to analyze the property by chemical method. Sampling to be done for every offered lot / size as per the sampling plan. e) CABLE TEST BEFORE AND AFTER LAYING OF CABLES AT SITE: a) Insulation Resistance test between phases and phase to Neutral and phase to earth. b) Continuity test of all the phases, neutral and earth continuity conductor. 10

11 NEW POL DEPOT AT c) Sheathing continuity test. d) Earth resistance test of all the phases and neutral. All tests shall be carried out in accordance with relevant Indian Standard Code of practice and Indian Electricity Rules. The Vendor shall provide necessary instruments, equipments and labour for conducting the above test and shall bear all expenses in connection with such tests. B) TEST REPORTS: The report from third party inspecting agency shall be submitted to HPCL for along with the material. No material will be accepted without third party inspection clearance report. C) TEST CERTIFICATES: Test reports shall be completed with all details and shall also contain IS specified limit values, wherever applicable, to facilitate review. 1.2 CABLE MARKING : EMBOSSING ON OUTER SHEATH: The outer sheath shall be legibly embossed with following legend throughout the length. i) Manufactures name or Trademark ii) Voltage Grade iii) Size : 3.5 C x mm ² iv) Year of Manufacture v) Type of Insulation vi) vii) viii) Type of outer sheath ISI mark Owner s identification 11

12 NEW POL DEPOT AT 1.3 CABLE LAYING : The cables shall be laid in trenches, trays, racks or conduits/pipes. No cable shall be directly buried in the ground. The cables of different voltage grade shall be laid in different trays. Power & control cables shall be laid in different trays. 1.4 SEALING, DRUMMING & PACKING: 1 After tests at the manufacturer s works, both ends of the cable shall be sealed by means of nonhygroscopic sealing material to prevent the ingress of moisture during transportation and storage. Also, PVC /Rubber end caps shall be supplied free of cost for each drum with a minimum of eight per thousand metre length. 2 Cable shall be supplied in length of 500 ± 5% meters, packed non-returnable drums of sufficiently sturdy construction. The vendor shall indicate in the offer, the maximum length of cable, which can be accommodated on one drum. The actual length supplied on each drum shall be within tolerance limit of +5%. The drum length shall be as per the cable quantity list. 3 Cables of length more than 250 meters shall also be supplied on non-returnable drums. The wood used for construction of the drum shall be properly seasoned, free from defects and wooden preservatives shall be applied to the entire drum. All ferrous parts shall be treated with a suitable rust preventive finish or coating to avoid rusting during transit or storage. 4 The spindle hole shall be 110 mm minimum diameter. 5 Each drum shall bear on the outside flange, legibly and indelibly in the English literature, a distinguishing number, the manufacturer s name and particulars of the cable i.e. voltage grade, length, conductor size, cable type, insulation type and gross weight shall also be clearly visible. The direction for rolling shall be indicated by an arrow. The drum flange shall also be marked with manufacturer s name and year of manufacturing etc. 6 The following information shall be stencilled on each drum. 12

13 NEW POL DEPOT AT (a) (b) (c) (d) (e) (f) (g) (h) (i) (j) (k) (l) (m) (n) Name of manufacturer, brand name or trademark. Nominal cross sectional area of conductor Number of cores. Type of cable and voltage grade. Cable code Length of cable on the drum. Number of lengths on drum (if more than one). Drum number. Direction of rotation of drum (by means of an arrow). Reference standard Approx. gross weight. Job number. Country of manufacture Year of manufacture. A tolerance of +/- 3% shall be permissible for each drum. However, overall tolerance for each size of cable shall be limited to +/ - 2%. Offer with short / non-standard lengths are liable for rejection. If non- standard drum lengths are specified in the data sheet, then same shall be supplied. 1.5 CABLE QUANTITY The bidder shall quote unit rates for all types of cables as indicated in the Job Schedule List. 1.6 TRANSPORTATION & DELIVERY: The cable shall be supplied in the actual length as per detailed purchase order. The cable shall be dispatched at client s stores or at site as per detailed instructions given by client at later stage. 13

14 NEW POL DEPOT AT The cable shall be loaded from the main vendor s store and properly stacked as per instruction of client s local representative. All such labour and transportation charges shall be clearly mentioned in the offer. 14

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO. SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.

More information

UGVCL/SP/591/11KV HT AB CABLE

UGVCL/SP/591/11KV HT AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched

More information

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/ 1 X C-UA- LTXLPE/2006) MAHARASHTRA STATE ELECTRICITY

More information

CONFLEX ELECTRIC CABLE

CONFLEX ELECTRIC CABLE CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard

More information

Gulf Cable & Electrical Ind. Co.

Gulf Cable & Electrical Ind. Co. CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC

More information

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test

More information

3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables 15. 8.7/15 kv XLPE insulated cables 25. 12/20 kv XLPE insulated cables 35

3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables 15. 8.7/15 kv XLPE insulated cables 25. 12/20 kv XLPE insulated cables 35 CONTENTS INTRODUCTION 1 Cable selection, cable specification, cable services CABLES Constructional data: 3.6/6 kv XLPE insulated cables 5 SECTION 1 6/10 kv XLPE insulated cables 15 SECTION 2 8.7/15 kv

More information

TECHNICAL SPECIFICATION OF 11 / 22 KV XLPE POWER CABLE FOR SUB-STATION

TECHNICAL SPECIFICATION OF 11 / 22 KV XLPE POWER CABLE FOR SUB-STATION GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara 390 007 TECHNICAL SPECIFICATION OF 11 / 22 KV XLPE POWER CABLE FOR SUB-STATION GETCO/E/TS PCBL025/RO DT.07-03-2008

More information

OFFICE OF CIVIL ENGINEERING UNITED STATES COAST GUARD WASHINGTON, D.C. APRIL 1996 MARINE CABLE, POWER AND CONTROL SPECIFICATION NO.

OFFICE OF CIVIL ENGINEERING UNITED STATES COAST GUARD WASHINGTON, D.C. APRIL 1996 MARINE CABLE, POWER AND CONTROL SPECIFICATION NO. OFFICE OF CIVIL ENGINEERING UNITED STATES COAST GUARD WASHINGTON, D.C. APRIL 1996 MARINE CABLE, POWER AND CONTROL SPECIFICATION NO. G-SEC-390E 1. SCOPE 1.1 Purpose. This specification establishes the basic

More information

Specializing in the cable business for over 38 years, PT. SUPREME CABLE

Specializing in the cable business for over 38 years, PT. SUPREME CABLE Specializing in the cable business for over 38 years, PT. SUPREME CABLE MANUFACTURING & COMMERCE Tbk. (PT. SUCACO Tbk) has grown steadly to become a largest and leading cable manufacturer, with international

More information

Corporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS

Corporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS Corporate Profile MODERN ROYAL ELECTRIC Ideal Power Solution ROYAL MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS MAJOR STOCKIST >>> CATHODIC PROTECTION CABLES >>> LOW VOLTAGE CABLES >>> MEDIUM

More information

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED

More information

VIPERFLEX ELECTRIC CABLE

VIPERFLEX ELECTRIC CABLE VIPERFLEX Flexible Low Voltage Electric Cable - 0.6/1kV (Rubber insulated) H07 RN-F & H07 BN-F Single Core 2-Core 2-Core and Earth 3-Core and Earth 4-Core and Earth Multi-Core and Earth H07 RCN-F & H07

More information

ScottishPower Distribution Cables & Equipment. Metal Theft

ScottishPower Distribution Cables & Equipment. Metal Theft ScottishPower Distribution Cables & Equipment Metal Theft April 2012 As an aid to deterring to metal theft this booklet has been put together to help identify the types of utility power cables and associated

More information

Gulf Cable & Electrical Ind. Co.

Gulf Cable & Electrical Ind. Co. CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES Irrigation 1 Coaxial s for T.V/ Satellite Antenna etc 2 Data Transmission s - 4 pair 24 AWG 3 TELEPHONE CABLES Telephone cables CCP-LAP & CCP-LAP-SS

More information

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m FIREX Interlock Armored Cables TECK90 and MC Industrial Cables LEAD FREE O V E R 1 8 0 Y E A R S O F E X P E R I E N C E 866-663-9267 w w w. n e x a n s e n e r g y. c o m Interlock Armored Cables Introduction....2

More information

CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS.

CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS. CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS September 2006 Revision 7 Corning Cable Systems reserves the right to update

More information

MEDIUM VOLTAGE CABLES Up to and including 36 KV

MEDIUM VOLTAGE CABLES Up to and including 36 KV MEDIUM VOLTAGE CABLES Up to and including 6 KV NOTICE As this catalogue is not intendedto cover all of LIBAN CABLES SAL possibilities in special cables manufacturing, the hereafter listing of the types

More information

CLAMPS CONNECTORS & EQUIPOTENTIAL RING

CLAMPS CONNECTORS & EQUIPOTENTIAL RING CLAMPS CONNECTORS & EQUIPOTENTIAL RING March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables

More information

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters 8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article

More information

APPLICATION ORIENTED DESIGN OF CABLES

APPLICATION ORIENTED DESIGN OF CABLES APPLICATION ORIENTED DESIGN OF CABLES Mrs. Rohini Bhattacharyya, Dubai cables Ltd.P. O. Box 11529,Dubai. rohinib@ducab.com Mr. Nawaf Ahmad Al Mohaideb Dubai Cables Ltd. P. O. Box 11529, Dubai. Nawaf@ducab.com

More information

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES FIRE RESISTANT CABLE In all fire disasters, fire smoke, heat and toxic fumes are the main obstacles to safe evacuation of a building or area. A major contribution towards overcoming these hazards is the

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Session 14 Cable Support Systems

Session 14 Cable Support Systems Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load

More information

International Electrotechnical Commission Standards

International Electrotechnical Commission Standards International Electrotechnical Commission Standards Standard IEC 60028 IEC 60038 IEC 60050-461 IEC 60055-1 IEC 60055-2 IEC 60092-101 IEC 60092-350 IEC 60092-351 IEC 60092-352 IEC 60092-353 IEC 60092-354

More information

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR 1.1.0 SCOPE : This specification covers design, manufacture, testing at manufacture s works before

More information

KNOW YOUR OPTIONS: 230 KV POWER CABLES

KNOW YOUR OPTIONS: 230 KV POWER CABLES KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common

More information

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

The Contractor shall furnish and install all shielded power cable suitable for use on this project. Section 16122 PRIMARY POWER CABLES PART 1 GENERAL: WORK INCLUDED The Contractor shall furnish and install all shielded power cable suitable for use on this project. RELATED WORK Section 16020: Tests SUBMITTALS

More information

Cables, Cable Laying & Accessories Manual

Cables, Cable Laying & Accessories Manual Distribution Business Cables, Cable Laying & Accessories Manual Database ref: File Ref: Title Page & Revision Log For Cables & Access v4 - Nov 2003.doc Manual Name: Cables & Accessories Manual Version

More information

Communication, Signal & Data Cables

Communication, Signal & Data Cables Communication, Signal & Data Cables Used for indoor installation and interconnection of transmission, telephone, telegraph and electronic equipment as well as media equipments www.alfanar.com Communication

More information

Section 5 161 kv Power Cables

Section 5 161 kv Power Cables Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper

More information

LT/HT Power & Control Cables

LT/HT Power & Control Cables LT/HT Power & Control s Catalogue 2014 HT Power s upto 66kV 1.1 kv Power s 1.1 kv Copper Control s ISO-9001/ 14001/18001 Certified Certification Building customer confidence by providing a wide range of

More information

Fault location on power cables. Fault location on power cables

Fault location on power cables. Fault location on power cables Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables

More information

XLPE PRODUCTION PLANT FOR THIRUVALLA UNIT OF TRACO CABLE LTD

XLPE PRODUCTION PLANT FOR THIRUVALLA UNIT OF TRACO CABLE LTD PROJECT PROFILE ON XLPE PRODUCTION PLANT FOR THIRUVALLA UNIT OF TRACO CABLE LTD Prepared by: TRACO CABLE COMPANY LIMITED IV TH FLOOR, KSHB OFFICE COMPLEX PANAMPILLY NAGAR KOCHI-682036 September 2012 PROJECT

More information

Outside Telephone Cable

Outside Telephone Cable Outside Telephone Cable Filled Core. Moisture Barrier. Description Soft copper wires insulated with high density polyethylene, foam skin or solid. Filled core, conformed by groups of pairs or by unit of

More information

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both

More information

Flexible cables for submersible products

Flexible cables for submersible products Flexible cables for submersible products Standards SUBCAB cables complies with the following general standards: IEC 6045 (general) IEC 608 class 5 (conductor) IEC 608-- CLAUSE 9 (oil resistant) IEC 608--

More information

100% EMI Emission Containment

100% EMI Emission Containment 100% EMI Emission Containment Designed for Longer Service Life Highly Flexible for Easier Handling and Faster Installation Authorized Distributor Industrial VFD Cables Index n Variable Frequency Drive

More information

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application ENERGY TECWATER S1BN8-F 0,6/1 kv Cable for Water Application Technical Data Electrical parameters Thermal parameters Trademark Type designation Specification Approval Application Rated voltage Maximum

More information

FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR

FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR Standards : CENELEC HD 22.4 NF C 32-102-4 DIN VDE 0282-1 and VDE 0282-4 BS 6007 and BS 6500 IEC 60245-4 Rated voltage Rated voltage: 450/750 V (Use up to

More information

TECHNICAL SPECIFICATION FOR LOW-FREQUENCY CABLES AND WIRES WITH PVC INSULATION AND PVC SHEATH

TECHNICAL SPECIFICATION FOR LOW-FREQUENCY CABLES AND WIRES WITH PVC INSULATION AND PVC SHEATH Rev. 1:2007 TECHNICAL SPECIFICATION FOR LOW-FREQUENCY CABLES AND WIRES WITH PVC INSULATION AND PVC SHEATH Suruhanjaya Komunikasi dan Multimedia Malaysia Off Pesiaran Multimedia, 63000 Cyberjaya, Selangor

More information

COATING & WRAPPING OF UNDERGROUND PIPING

COATING & WRAPPING OF UNDERGROUND PIPING CONSTRUCTION STANDARD SPECIFICATION DOCUMENT NO :SEC-PJ-000-SPC-PI-008 TOTAL PAGES : 8 Page 1 of 8 CONTENTS 1. SCOPE 2. DEFINITION 3. CODES AND STANDARDS 4. MATERIALS Page 2 of 8 1. SCOPE This specification

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

High Voltage Systems. Today. The history of cables

High Voltage Systems. Today. The history of cables High Voltage Cables High Voltage Systems Today Prysmian Cables and Systems B.V. is part of the Prysmian Group, a leading player in the industry of high-technology cables and systems for energy and telecommunications,

More information

LT/HT Power & Control Cables

LT/HT Power & Control Cables LT/HT Power & Control Cables Price List w.e.f. July, 2014 HT Single Core Power Cables HT Three Core Power Cables LT Aluminium Power Cables LT Copper Cables - Power and Control ISO-9001/ 14001/18001 Certified

More information

450-750 VOLTS - Copper conductor PVC insulated SSA 1320, IEC 60227 & BS 6004 HO 7V - U With Solid Conductor - TYPE 60227 IEC 01. Insulation Thickness

450-750 VOLTS - Copper conductor PVC insulated SSA 1320, IEC 60227 & BS 6004 HO 7V - U With Solid Conductor - TYPE 60227 IEC 01. Insulation Thickness 450 50 VOLTS Copper conductor PVC insulated SSA 320, IEC 6022 & BS 6004 HO V U With Solid TYPE 6022 IEC 0 For internal wiring equipment rated voltage up to 000 V AC and up to 50 V to earth. Catalogue Number

More information

Electrical Safety Products

Electrical Safety Products Electrical Safety Products Trelleborg Electrical Safety Products A safe working environment is important in all industries, but in the electrical generation and supply industry, it is paramount. Trelleborg

More information

2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G

2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G Seattle Cit y Light 1 of 4 2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G 1. Scope This standard covers the detailed requirements

More information

PROFIBUS cable. PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications

PROFIBUS cable. PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications Data Sheet 10/63-6.47-EN Rev. D PROFIBUS cable PROFIBUS DP cables Non-Ex (Hazardous) applications Ex (Hazardous) applications PROFIBUS PA cables Non-Ex (Hazardous) applications Ex (Hazardous) applications

More information

Power and Wiring Cables

Power and Wiring Cables 1 Single-Core PVC 1X...................... 1: Single-Core PVC/PVC 1Y.................. 1: Flat Twin & Flat Three Core PVC /Y........ 1: Multicore XLPE/LSF/SWA/LSF BS Control Cable.............................

More information

LT/HT Power & Control Cables

LT/HT Power & Control Cables LT/HT Power & Control Cables Price List w.e.f. July, 2013 HT Single Core Power Cables HT Three Core Power Cables LT Aluminium Power Cables LT Copper Cables - Power and Control ISO-9001/ 14001/18001 Certified

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

Flexible Control Cables

Flexible Control Cables Works photo: KUKA Flexible Control Cables A Flexible Control Cables Since generations people try to build machines and plants which shall take on different functions. To raise, sink, slide, drill, transport

More information

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing

More information

White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection

White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection White paper SACE Tmax XT Circuit-Breaker Terminals and Connection Circuit-Breaker Terminals and Connections Index Introduction... 2 1. Components used for wiring... 3 1.1. Electrical...3 1.2. Flexibility

More information

PROFIBUS cable. for PROFIBUS-PA and -DP 10/63-6.46 EN

PROFIBUS cable. for PROFIBUS-PA and -DP 10/63-6.46 EN for PROFIBUS-PA and -DP 10/63-6.46 EN CPN 080/CPE 080-Ex PROFIBUS-PA basis cable AWG 18, 0.88 mm 2 Use For fixed installation indoor and outdoor, on racks and in conduits. Application Fieldbus cable for

More information

Festoon 715 P PUR cable for flexible application in festoon systems

Festoon 715 P PUR cable for flexible application in festoon systems CABLES FOR CRANE AND CONVEYOR APPLICATIONS Festoon 715 P PUR cable for flexible application in festoon systems S AB BRÖCKSKES D-VIERSEN Festoon 715 P 1 x 16.0 mm 2 C Marking for Festoon 715 P 07150162:

More information

LT/HT Power & Control Cables

LT/HT Power & Control Cables LT/HT Power & Control Cables Price List w.e.f. July, 1 (Rev. 01) HT Single Core Power Cables HT Three Core Power Cables LT Aluminium Power Cables LT Copper Cables - Power and Control ISO-9001/ 1001/18001

More information

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS

LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON

More information

David O Brien, CMP Products (David.OBrien@cmp-products.com)

David O Brien, CMP Products (David.OBrien@cmp-products.com) David O Brien, CMP Products (David.OBrien@cmp-products.com) 1) Main Function of Cable Glands 2) Common Issues with Cable Glands 3) Compliance / Standards, changing times 4) How do we select Cable Glands?

More information

The Instrumentation Cable Experts

The Instrumentation Cable Experts 1 The Instrumentation Cable Experts Facilities Head office & factory 1300 Industrial Boulevard Mt Pleasant, Texas 75455, USA www.dekoroncable.com Stocking Centres USA Mt Pleasant and Houston Singapore

More information

Instrumentation Cable...14-17. Power Cable...2-11. Assembly Solutions...32

Instrumentation Cable...14-17. Power Cable...2-11. Assembly Solutions...32 Severe Cold Durability Exceeds CSA Cold Bend / Cold Impact (-0 C/-35 C) Drilling Mud Resistant Flame Retardant Certified to IEC 9-3 (33-3A) and IEEE 580 Oil Resistant Assemblies...3-33 Ester Based Mud

More information

www.ptranscable.com We specialize in low voltage cables including: Stranded Single Cable H07V-R Flexible Single Cable H05V-K

www.ptranscable.com We specialize in low voltage cables including: Stranded Single Cable H07V-R Flexible Single Cable H05V-K P-trans, meaning power transistor, is a well known cable manufacturer based in Aan - Jordan. The production plant produces all sorts of high quality low tension cables and is a leader in the industry supplying

More information

MEDIUM VOLTAGE POWER CABLES

MEDIUM VOLTAGE POWER CABLES MEDIUM VOLTAGE POWER CABLES CONTENTS 1 GENERAL INTRODUCTION 4 TECHNICAL INFORMATION 15 25 35 45 Single Core XLPE Insulated PVC Sheathed Cables UNARMOURED CABLES COPPER UNARMOURED CABLES ALUMINUM ALUMINUM

More information

Contents. All Rights Reserved

Contents. All Rights Reserved Electricity Specification 400C8 Issue 6 October 2015 LV Service Cables Contents 1 Scope 2 Definitions 3 General Requirements for Approvals and Assurance 4 Conditions of Installation 5 Conditions of Operation

More information

Fire Resistant Cables

Fire Resistant Cables 109/4 Fire Resistant Cables SR 114H Standard - SR 114E Enhanced BS 5839-1 BS 7629-1 BS 6387 BS 8434-1/2 BS 6425 BS 7622 EN 50200 World-wide recognized high quality cables Firecel SR114 are used in: Data

More information

Removal of EP 20 10 00 02 SP High Voltage Cable

Removal of EP 20 10 00 02 SP High Voltage Cable TN 018: 2014 Technical Note For queries regarding this document standards@asa.transport.nsw.gov.au www.asa.transport.nsw.gov.au TN 018: 2014 Issued date 12 March 2014 Effective dates 12 March 2014 Subject:

More information

Caledonian Submersible Pump Cables for Oil Industry >> IEEE 1018 >> IEEE 1019 >> API RP 11S5

Caledonian Submersible Pump Cables for Oil Industry >> IEEE 1018 >> IEEE 1019 >> API RP 11S5 Caledonian Submersible Pump Cables for Oil Industry >> IEEE 1018 >> IEEE 1019 >> API RP 11S5 Caledonian Windmill Cables COMPANY PROFILE Table of Content Caledonian, established in 1978, offers one of the

More information

Flygt flexible cables

Flygt flexible cables Flygt flexible cables Contents Standards General SUBCAB 4 Screened SUBCAB 6 Rubber cable type: NSSHÖU-J 7 Screened rubber cable type: NSSHÖU../E + ST 8 FGB screened rubber cable 9 PUR control cable 0 HCR

More information

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET

More information

Network Standard Advice No. 1420C 9/6/2011

Network Standard Advice No. 1420C 9/6/2011 Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides

More information

Chemical resistance Accidental

Chemical resistance Accidental Industrial flexible cable, insulation and outer sheath in elastomer Description Application TITANEX flexible cable is intended for installations with moving equipment, electric appliances and for building

More information

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE 8.1 SYSTEM 8.1.1 Armoured, screened underground cables are used for control communication in electrified areas to limit induction effect. 8.2

More information

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT

TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.

More information

Quality Reliability Innovation. ISO 9001 : 2000 CERTIFIED BY AFAQ No. QUAL / 1997 / 7034 a COPPER TELECOMMUNICATION CABLES

Quality Reliability Innovation. ISO 9001 : 2000 CERTIFIED BY AFAQ No. QUAL / 1997 / 7034 a COPPER TELECOMMUNICATION CABLES Quality Reliability Innovation ISO : CERTIFIED BY AFAQ No. QUAL / 7 / 7 a COPPER TELECOMMUNICATION CABLES COPPER TELECOMMUNICATION CABLES CONTENTS 7 NOTICE INTRODUCTION QUALITY ASSURANCE RECOMMENDED ORDERING

More information

DELHI METRO RAIL CORPORATION LIMITED. (A Joint Venture of Govt. of India & GNCTD) MASS RAPID TRANSPORT SYSTEM PHASE III. Contract: - CE -16 VOLUME-6

DELHI METRO RAIL CORPORATION LIMITED. (A Joint Venture of Govt. of India & GNCTD) MASS RAPID TRANSPORT SYSTEM PHASE III. Contract: - CE -16 VOLUME-6 DELHI METRO RAIL CORPORATION LIMITED (A Joint Venture of Govt. of India & GNCTD) MASS RAPID TRANSPORT SYSTEM PHASE III TURNKEY PROJECT OF DESIGN, SUPPLY, LAYING, JOINTING, TESTING AND COMMISSIONING OF

More information

FLEXIBLE COPPER & ALUMINIUM CONNECTIONS. Product Range 1 VGL - ALLIED CONNECTORS

FLEXIBLE COPPER & ALUMINIUM CONNECTIONS. Product Range 1 VGL - ALLIED CONNECTORS Product Range ROUND STRANDED COPPER CABLE Electrolytic Copper / Oxygen Free Copper Conforms to DIN 46438 Standards Finish: Bare Copper / Tinned / Silver-plated ROUND BRAID / ROUND STRANDED CABLE WITH OVERALL

More information

TECHNICAL SPECIFICATIONS OF 66 KV 1C 630 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE

TECHNICAL SPECIFICATIONS OF 66 KV 1C 630 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF 66 KV 1C 630 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GETCO/E/TS

More information

LOW VOLTAGE POWER CABLES

LOW VOLTAGE POWER CABLES LOW VOLTAGE POWER CABLES CONTENTS 1 4 GENERAL INTRODUCTION TECHNICAL BARE SOFT DRAWN STRANDED CONDUCTORS 38 39 44 48 52 53 56 59 60 63 68 72 75 76 79 82 83 INFORMATION COPPER PVC INSULATED PVC SHEATHED

More information

R=Required by Lab S=May be subcontracted IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT COMMITTEE OF TESTING LABORATORIES

R=Required by Lab S=May be subcontracted IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT COMMITTEE OF TESTING LABORATORIES IEC SYSTEM FO CONFOMITY TESTING AND CETIFICATION OF ELECTICAL EQUIPMENT COMMITTEE OF TESTING LABOATOIES TESTING AND MEASUING EQUIPMENT/ALLOWED SUBCONTACTING Power cables with extruded insulation and their

More information

Industrial Cable Solutions for Variable Frequency Drives

Industrial Cable Solutions for Variable Frequency Drives Industrial Cable Solutions for Variable Frequency Drives Tough challenges call for innovative solutions, and General Cable is your worldwide source for new products and a wide range of industry-leading

More information

TECHNICAL SPECIFICATIONS OF 66 KV 1C 300 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE

TECHNICAL SPECIFICATIONS OF 66 KV 1C 300 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF 66 KV 1C 300 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GETCO/E /TS

More information

Catalogue Câbles d Energie

Catalogue Câbles d Energie Catalogue Câbles d Energie Conductores Tecnológicos S.A. www.contecsa.es Index Page Introduction 13 RV 14 RVMV 15 RVSV 16 RVFV 17 Conductores Tecnológicos S.A. 2 www.contecsa.es INTRODUCTION Câbles d Energie

More information

KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET

KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET 1 KALPANA INDUSTRIES LTD. TECHNICAL DATA SHEET KI XL - 03 / KI-SC 10 TWO COMPONENT AMBIENT CURABLE POLYETHYLENE COMPOUND FOR INSULATION OF LOW VOLTAGE POWER CABLE DESCRIPTION : KI polyethylene compound

More information

ECS 02-0019 INSTALLATION OF UNDERGROUND CABLES - LV TO 132KV

ECS 02-0019 INSTALLATION OF UNDERGROUND CABLES - LV TO 132KV THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: ECS 02-0019 ENGINEERING CONSTRUCTION STANDARD ECS 02-0019 INSTALLATION OF UNDERGROUND CABLES - LV TO 132KV

More information

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1

Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1 Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader

More information

the quality par excellence Meghna Industries Manufacturer of : All types of fiberglass Cables

the quality par excellence Meghna Industries Manufacturer of : All types of fiberglass Cables the quality par excellence Meghna Industries Manufacturer of : All types of fiberglass Cables ABOUT US Since our beginning in 1995, We - MEGHNA INDUSTRIES have been one of the fastest growing manufacturer

More information

CABLE SPECIFICATION CAN CAB RJ45-SUBD9

CABLE SPECIFICATION CAN CAB RJ45-SUBD9 CABLE SPECIFICATION All technical information contained in this document is the exclusive property of STI and may neither be used nor disclosed without its prior written consent. AAV 33801 1/8 Connector

More information

Marine & Shipboard Cable JIS C 3410(1999) IEC 60092-350, 353, 354, 376

Marine & Shipboard Cable JIS C 3410(1999) IEC 60092-350, 353, 354, 376 T o t a l S o l u t i o n o f M a r i n e C a b l e Marine & Shipboard Cable JIS C 3410(1999) IEC 60092-350, 353, 354, 376 Marine & Shipboard cable Total Solution of Marine Cable JIS C 3410(1999), IEC

More information

Important Information: Complete Terms and Conditions are printed on sales invoices

Important Information: Complete Terms and Conditions are printed on sales invoices Important Information: Complete Terms and Conditions are printed on sales invoices Notice: L&H Group is continually working to improve and add new products to the Cable Express product range. For this

More information

Fire Performance Standard

Fire Performance Standard Fire Performance Standard At present, in cable industry, Fire Retardant, Low Smoke Halogen Free (LSZH), Low Smoke Fume (LSF) and Fire Resistant cables are all described as Fire survival Cables. Flame Retardant

More information

Gexol. Gexol. The Global Cable Solutions Company. Designed for safe, reliable performance in the harshest oil and gas operating environments

Gexol. Gexol. The Global Cable Solutions Company. Designed for safe, reliable performance in the harshest oil and gas operating environments Gexol Gexol World Class World Class Designed for safe, reliable performance in the harshest oil and gas operating environments Power Control Instrument VFD The Global Cable Solutions Company Gexol World

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

The original heating cable just got better

The original heating cable just got better The making of the DEVIflex heating cable IEC 60800:2009 approved PVC outer sheath Install down to -5 C Round construction 360 full screening The original heating cable just got better DEVIflex Strong.

More information

Global cable expertise for rolling stock

Global cable expertise for rolling stock Global cable expertise for rolling stock Global cable expertise for rolling stock Single and multicore Low voltage control cables Jumper cables HV roof cables (25 kv) rubber cables for power needs of locomotives

More information

Airdac CNE and SNE, 600/1000V, Polyethylene Sheath, SANS 1507, NRS 063 & NRS 017

Airdac CNE and SNE, 600/1000V, Polyethylene Sheath, SANS 1507, NRS 063 & NRS 017 Airdac CNE and SNE, 600/1000V, Polyethylene Sheath, SANS 1507, NRS 063 & NRS 017 Conductor: Hard Drawn Copper Conductor Class 2 Insulation: LV-XLPE Phase Color Code(SNE): Red, Black & Bare Copper Phase

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials

VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials VDE Information General Information The voltage which can be applied to a terminal depends on the relevant regulations, the installation conditions and, of course, the dimensions and insulating materials

More information

CABLE 101. The Basics of Wire & Cable. Copyright 2007, Belden Inc.

CABLE 101. The Basics of Wire & Cable. Copyright 2007, Belden Inc. CABLE 101 The Basics of Wire & Cable Copyright 2007, Belden Inc. KEY TERMS Insulations Jacket Capacitance Attenuation Velocity of propagation Dielectric strength Dielectric constant Working voltage Elongation

More information