Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
|
|
- Bruno Bradley
- 8 years ago
- Views:
Transcription
1 Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to become an open Cabling Provider you must attain a mark of at least 80 per cent in line with the regulatory authority s stringent requirements. Time Allowed: 1 hour and 5 minutes plus 10 minutes reading time Instructions: You may not make any notes during the reading time Do NOT mark this exam paper Enter all answers on the answer sheet provided All questions are of equal value Attempt all questions Non-programmable calculators are acceptable AS ACIF S008, S009 may be used as reference CPR 2000 may be used as reference
2
3 You must score a minimum of eighty per cent. For each question, identify the most correct response by placing a cross in the box of the identifying letter in the column corresponding to the question number on the answer sheet provided. If you make a mistake place a line through the incorrect answer and mark correct answer as before. If you chose B as the correct answer show it thus: Question A B C D 1 X 2 1. In the AS/CA S009:2013 the Building entry point is: a) Where the lead in terminates b) the point on customer premises at which the MDF or the first telephone socket is located c) The foyer of the building d) a point at which a line that is used to provide a carriage service to an enduser in a building meets the outer surface of that building 2. In the AS/CA S009:2013 Manual, the word should implies: a) a mandatory requirement b) an intention of a carrier c) a recommendation d) an intention of the licensing authority 3. The network boundary in customer premises where the telecommunications network supplies a carriage service to an end-user by means of a line that enters the building if there is a NTD and the line connects the distributor is: a) the network side of the campus/building distributor. b) the side of the NTD nearest the end-user. c) the floor distributor or local distributor within the customer s premises. d) the first telephone socket within the customer s premises. 1
4 4. When installing Optical fibre telecommunications cables the cabling provider shall ensure a) suitable protective eyewear and clothing is worn when preparing,cutting or jointing optical fibres. b) labels are removed that state it is a hazardous service.. c) segreagetion from harmful electrical services. d) Proper separation from LV and HV cables. 5. The installation of customer equipment or cabling must be such as to not cause harm nor interference to the public telecommunications network. Where such installation does pose a threat to the safety or proper functioning of the network: a) the carrier will rectify the equipment or wiring causing harm or interference. b) the carrier may cease to supply service to the licensee installing the equipment or cabling. c) the carrier may cease to supply service to the installation. d) the carrier may seek a review from the regulatory authority. 6. What is the requirement where it is not possible to place an installation in a location where the EPR hazard is less than that specified? a) it may only proceed on the basis of an engineered design prepared in compliance with the relevant codes agreed between the carrier and the supply authority. b) it may only proceed on the basis of an engineered design prepared in consultation with the licensed cable or equipment installer and the regulatory authority. c) it may only proceed on the basis of a formal agreement between the customer and the carrier absolving the carrier from any liability for the installation. d) all CE connected within the premises served by the installation shall have permitted line isolation units installed. 2
5 7. The network boundary in customer premises where the telecommunications network supplies a carriage service to an end-user by means of a line that enters the building if the line connects to one or more sockets in the building is: a) the network side of the sockets. b) the socket nearest the end-user. c) the floor distributor or local distributor within the customer s premises. d) the side nearest to the end-user of the first socket after the building entry point. 8. Cable and other cabling equipment installed for connection to carrier s network must be installed in accordance with the requirements of Technical Standard AS/CA S009:2013 and: a) in accordance with the requirements of Technical Standard TS 011 b) in accordance with the manufacturer s instructions and must comply with the product approval requirements of Technical Standard AS ACIF S008 c) in accordance with the product approval requirements of TS 007 d) in such a way that access to the cabling and equipment by unqualified and unauthorised personnel is prevented 9. A Open Cabling Provider allows the cabling provider to work: a) in part of a customer premises. b) on any cable in any type of domestic premises. c) beyond the network boundary in any type of customer premises. d) On the customer side of the Network Boundary in any type of customer premises. 10. It is necessary to provide records for documenting cables and crossconnects when: a) the carrier requests this provision from the licensed cable installer. b) two or more carriers provide a service to a customer. c) Cross connects are made by means of jumpers. d) cross-connects are missing from the distributor. 3
6 11. In AS/CA S009:2013 the protective earth conductor is: a) a system of earthing in which parts of an installation required to be earthed connect to the general mass of earth and to the neutral of the supply system. b) A conductor other than a main earthing conductor, connecting any portion of the electrical earthing system to the portion of the electrical installation or electrical equipment required to beearthed, or to any other portion of the electrical earthing system. c) a connection to the general mass of earth in such a way as to provide a functional requirement for the telecommunications cabling and equipment. d) a conductor for signalling and other functional telecommunications purposes having no personnel protective status. 12. It is necessary to select and install telecommunications equipment, including cabling and connecting hardware, for use in hazardous areas shall consult what standard? a) ACIF S008:2010, AS/CA S009:2013 and AS b) ACIF S008:2010, AS/CA S009:2013 and AS c) AS/CA S009:2013 for Class I areas and AS 3000 for Class II areas. d) Clauses to of AS/CA S009:2013 and AS/NZS A catenary wire support system in a ceiling carries telecommunications services. To what earth should the catenary wire bond? a) the telecommunications functional earth electrode. b) the neutral link in the main switchboard. c) either the protective earth or the TRC system. d) a catenary wire support system may bond to the protective earth. 14. The term Compliant means a) an item that has been labelled in accordance with the Telecommunications Labelling Notice. b) the carrier s standard terminating modules. c) any suitable CE permitted by the carrier. d) any type specified by the customer provided it is not of a type specified by an electrical regulatory authority for mains power reticulation. 4
7 15. What size cable must a TRC earth bar or terminal be capable of accepting? a) the earth bar or terminal must be capable of accepting at least 6 mm 2 cable. b) the earth bar or terminal must be capable of accepting at least 6 mm 2 cable or cable lugs designed to accept 6 mm 2 cable. c) the earth bar or terminal must be capable of accepting at least 6 mm 2 cable or cable lugs designed to accept 16 mm 2 cable. d) the earth bar or terminal must be capable of accepting at least 16 mm 2 cable or cable lugs designed to accept 16 mm 2 cable. 16. The height from the floor to the lowest termination of the NTD shall be? a) a distance of 150 mm from the floor or platform. b) a distance of 350 mm from the floor or platform. c) a distance of mm from the floor or platform. d) a distance of mm from the floor or platform. 17. Under what circumstances should all metallic components of a distributed cabling system bond to the TRC? a) the TRC is for functional purposes and not for personnel protective purposes. At no time should any metallic part of a cabling system connect to it. b) the TRC is for personnel protective purposes. All metallic parts of a cabling system must connect to it. c) only when the EPR hazard exceed 430 V AC. d) as required by the local power supply authority. 18. What is the minimum required separation between electrically conductive telecommunications cables installed in LDUPVC conduit in a shared trench with HV power cables installed in or under a protective covering complying with AS3000? a) no less than 100 mm. b) no less than 300 mm. c) no less than 450 mm. d) telecommunications cables cannot share a trench with HV cables. 5
8 19. In AS/CA S009:2013 a Distributor is: a) where the building backbone cables terminate and also facilitates connections to the campus backbone cable. b) where horizontal cabling emanating from the floor distributor may connect prior to connecting to telecommunication outlets. c) an assembly of strip-mounted wiring modules on which are terminated the lead-in cable(s) and provides cross connection to the customer cabling. d) a collection of components used to terminate cables and provides facilities for cross-connection (e.g. backmounts, termination equipment, jumpers, patch panels, patch cords). 20. Cable Support Systems shall: a) be only installed in the roof and attach to the CES b) be suitably secured and supported as necessary to maintain separation from hazardous services and maintain safe passage for persons to pass. c) be of such type and installed in such a manner to prevent the ingress of dust and moisture. d) be earther only to the TRC 21. In a domestic premises where the lead-in cable terminates directly on one or more telephone sockets a licensed cable installer may connect customer cabling at: a) the first telephone socket or any point in the lead-in cable providing the lead-in cable is not cut. b) the terminal strip of customer equipment where there is no socket or any point in the lead-in cable providing the lead-in cable is not cut c) the first telephone socket, the terminal strip of customer equipment where there is no socket or any point in the lead-in cable. d) the first telephone socket, the terminal strip of customer equipment where there is no socket or any point in the customer cabling providing the leadin cable is not cut. 6
9 22. What is the required minimum separation between the conductors and terminations of telecommunications cables in the campus/building distributor and the single insulated conductors and terminations in the 415 V main electrical switchboard? a) the required separation is 150 mm or a permanent rigidly fixed barrier of durable insulating material or earthed metal. b) the required separation is 300 mm or a permanent rigidly fixed barrier of durable insulating material. c) HV terminations cannot share a common enclosure with those of telecommunications conductors and terminations. d) the location of the campus/building distributor should be within its own room remote from the electrical switchboard. 23. Marking of distributors shall : a) be alphabetically designated, from left to right,omitting the letters I and O. b) in a sequential manner starting at the uppermost floor. c) in accordance with the guidelines of AS ACIF S006 d) in an updatable manner in accordance with AS/CA S009: Class 1 surge suppression devices located in the MDF and installed in the customer cabling and connect between telecommunication line conductors and earth must have: a) a nominal firing voltage greater than 160V b) a nominal firing voltage greater than 230V c) a nominal firing voltage greater than 330V d) a nominal firing voltage greater than 500V 7
10 25. When can a cabling provider remove cross-connects at the MDF distributor? a) under no circumstances can a licensed cable installer remove a crossconnection on the carrier s side of the campus/building distributor. b) a licensed cable installer can remove a redundant cross-connection on the carrier s side of the campus/building distributor provided they take all reasonable steps to ensure a working service is not adversely affected. c) a licensed cable installer can remove any cross-connection on the carrier s side of the campus/building distributor provided they take all reasonable steps to ensure it is a working service. d) a licensed cable installer can remove a cross-connection on the carrier s side of the campus/building distributor provided it is a working service and the connection is on a one-for-one basis of an existing cross-connection for the purpose of maintenance or repair. 26. Joints in internal customer cables must be: a) wholly concealed in a suitable enclosure or wall, floor or ceiling space. b) suitably manufactured, enclosed, positioned and supported to prevent the ingress of dust or moisture. c) suitably concealed from public view and protected interference or damage. d) suitably insulated and protected to prevent injury to customers. 27. Cable entry holes in a distributor: a) must be free of sharp edges and burrs. b) must have an insulating grommet fitted. c) must be free of sharp edges or burrs or must have an insulating grommet fitted. d) require no further attention. 28. Pipes containing flammable liquid or gas, or of a temperature exceeding 60 C are examples of: a) harmful services. b) dangerous services. c) hazardous services. d) non-electrical harmful services. 8
11 29. The supply, installation and maintenance of customer cabling connected to a telecommunications network, on the customer side of the network boundary is open to: a) all suitably qualified persons. b) those persons entitled to perform electrical contract work. c) persons in the employ of the carriers. d) all cabling provders or in appropriate circumstances under the supervision of a cabling provider. 30. What is the resistance of the communications earth system cable between the point of connection to the protective earth system and the earth bar or terminal at any distributor? a) no greater than 0.5 b) no greater than 2 c) no greater than 5 d) no greater than If the level of low frequency induction exceeds the permissible limit, the installation should only proceed: a) on the basis of an engineered design prepared in compliance with AS/CA S009:2013. b) on the basis of an engineered design prepared in compliance with AS ACIF S008. c) if suitable shielding is placed around the customer cables in accordance with the relevant Codes agreed between the carrier and the power supply authority. d) on the basis of an engineered design prepared in compliance with the relevant Codes agreed between the carrier and the power supply authority. 32. Who provides and terminates the lead-in cable(s) a) the customer. b) the building owner. c) the licensed cable installer. d) the carrier. 9
12 33. Which side of the MDF must be capable of mounting the carrier s standard terminating modules? a) the lead-in side. b) the customer side. c) both lead-in and customer sides d) any approved terminating module is suitable for both lead-in and customer sides. 34. The MDF distributor enclosure located on an external wall must satisfy the minimum requirements of: a) IPX3 b) IPX4 c) IPX6 d) IPX8 35. Telecommunications cabling containing electrically conductive elements, other than under-carpet cables, require permanent separation form LV cables. Which of the following methods ensures the required separation? a) a minimum distance of 150 mm or a barrier of durable insulating material or a timber or metal stud, nogging or joist of any thickness. b) a minimum distance of 150 mm or a barrier of durable insulating material or metal or a timber or metal stud, nogging or joist of any thickness. c) a minimum distance of 50 mm or a barrier of durable insulating material or metal or a timber or metal stud, nogging or joist of any thickness. d) a minimum distance of 50 mm or a barrier of durable insulating material or a timber or metal stud, nogging or joist of any thickness. 36. What is the minimum required separation between electrically conductive telecommunications cables installed in LDUPVC conduit in an exclusive trench where they cross above LV power cables installed in or under a protective covering complying with AS3000? a) no less than 100 mm. b) no less than 300 mm. c) no less than 450 mm. d) no further protection is necessary. 10
13 37. What is the required minimum separation between cables, the conductors and terminations of telecommunications services and non-electrical hazardous services? a) the required separation is 150 mm. b) the required separation is 100 mm or a permanent rigidly fixed barrier of durable insulating material or earthed metal. c) the required separation is 150 mm or a permanent rigidly fixed barrier of durable insulating material or earthed metal. d) the required separation is 300 mm or a permanent rigidly fixed barrier of durable insulating material. 38. Outdoor customer cables having steel wire armouring that terminates to the protective earth are exempt from the separation requirements for LV and HV electrical cables of AS/CA S009:2013 provided: a) additional shielding is provided. b) the electrical cables also have an earthed steel wire armouring. c) the electrical cables also have an earthed steel wire armouring and the live conductors are protected by an earth leakage circuit breaker. d) The installation satisfies the separation requirements of AS What is the height above the ground for aerial customer cables installed in non-trafficable areas? a) no less than 2.7 m. b) no less than 3.7 m. c) no less than 4.9 m. d) no less than 5.4 m. 40. What type of connector block may a cabling provder provide on the customer side of the distributor a) any permitted type that complies with the labelling notice b) the carrier s standard terminating modules. c) any suitable type permitted by the electrical supply authority. d) any type specified by the customer provided it is not of a type specified by an electrical regulatory authority for mains power reticulation. 11
14 41. Aerial customer cabling containing electrically conductive elements cannot cross aerial power lines of:? a) HV classification. b) a voltage exceeding 33 kv. c) a voltage exceeding 330 kv. d) a voltage exceeding 100 kv. 42. A 100 mm diameter pipe encloses a 100 pair underground customer cable. Installation of the customer cable places it in a shared trench above a multi-core high voltage cable enclosed in orange HDUPVC conduit. If the installation is under a roadway at what depth must the top of the HV conduit be for the installation to comply with AS/CA S009:2013? a) no less than 800 mm b) no less than 850 mm c) no less than 900 mm d) no less than 950 mm 43. What is the requirement for installing a telecommunication outlet in a damp situation outside the restricted zones? a) a permitted line isolation unit is installed in each conductor prior to installation of the socket b) Telecommunication outlets are not installed in any damp situation c) There is no requirement for the installation of Telecommunication outlets outside the restricted zones d) Telecommunication outlets in damp situations outside the restricted zones are installed in such a manner to minimise the ingress of moisture 44. In AS/CA S009:2013 the First Socket is? a) a cable within a customer s building which terminates a carrier s lead-in cabling, i.e. there is no intermediate distributor or NTD. b) a socket (telecommunications outlet) within a customer s building which terminates a carrier s lead-in cabling, i.e. there is no intermediate distributor or NTD. c) the first socket after the Network Boundary. d) The NTD. 12
15 45. Where aerial customer cables containing electrically conductive elements share poles in a parallel run with power lines the separation, at the pole, between the customer cables and any insulated mains power conductor or service lead: a) is at least 300 mm. b) is at least 600 mm. c) is at least 1.2 m. d) is at least 1.8 m. 46. An installation requires a CAE and the customer equipment requires a TRC. What is the colour and minimum size of the conductor of the TRC cable connecting the floor distributor and the CAE earth terminals? a) violet 2.5 mm 2 b) green and yellow 4 mm 2 c) violet 4 mm 2 d) violet 6 mm There are two buildings on the same premises. Building A is the main building containing the campus/building distributor and main electrical switchboard. Building B is a temporary erection. Building B has 4 power outlets and 5 lights directly connected to the main switchboard (in Building A). The maximum allowable resistance of the TRC between the campus/building distributor (in Building A) and the building distributor (in Building B) is: a) not exceeding 5 Ohm b) in excess of 2 Ohm using 6 mm 2 cable c) there is no maximum resistance for TRC in temporary buildings d) up to 5 Ohm provided the TRC earth bar or terminal at the floor distributor bonds to the protective earth 48. What is the size and colour of the equipotential bonding conductor? a) green and yellow 4 mm 2 b) violet 4 mm 2 c) green and yellow 6 mm 2 d) violet 6 mm 2 13
16 49. Terminations and cross-connections used for lines providing power feeding exceeding SELV shall? a) use any approved terminating tool and advise the building owner or manager of the changes. b) Be exempt from the requirements of AS ACIF S c) Be free of danger. d) be clearly identified in the records and by appropriate labelling or marking of the distributor connection modules. 50. What is the size and colour of the cable connecting the CET to any distributor in the communications earth system? a) green and yellow 2.5 mm 2 b) violet 4 mm 2 c) green and yellow 6 mm 2 d) violet 6 mm 2 14
AUSTRALIAN STANDARD AS/ACIF S009:2006 Installation requirements for customer cabling (Wiring rules)
AUSTRALIAN STANDARD AS/ACIF S009:2006 Installation requirements for customer cabling (Wiring rules) Adopted for regulatory purposes Australian Standard Installation requirements for customer cabling (Wiring
More informationFor business. Wiring your business for broadband. What happens when copper is required?
For business Wiring your business for broadband Your cabling requirements are dependent on the size and complexity of your business. Smaller businesses should follow the wiring recommendations for residential
More informationStructured Cabling, Earthing & Equipotential Bonding
White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,
More informationOutdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationUnion County Public Schools. Facilities Department. Electrical. Safe Work Practices
1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County
More informationDavid O Brien, CMP Products (David.OBrien@cmp-products.com)
David O Brien, CMP Products (David.OBrien@cmp-products.com) 1) Main Function of Cable Glands 2) Common Issues with Cable Glands 3) Compliance / Standards, changing times 4) How do we select Cable Glands?
More information33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
More informationElectrical Practices for Construction Work
1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in
More informationElectrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
More information800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
More informationElectrical Safety Products
Electrical Safety Products Trelleborg Electrical Safety Products A safe working environment is important in all industries, but in the electrical generation and supply industry, it is paramount. Trelleborg
More information**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT. YOU COULD PUT YOUR FAMILY AND WORLDLY POSSESSIONS IN DANGER!!!
More informationRESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
More informationEARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
More informationElectrical Wiring Methods, Components and Equipment for General Use. Approved for Public Release; Further Dissemination Unlimited
Electrical Wiring Methods, Components and Equipment for General Use Approved for Public Release; Further Dissemination Unlimited At the completion of this unit you shall be able to: 1. Utilize section
More informationDOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation
More informationIT&T Infrastructure Standards
Technology Services IT&T Infrastructure Standards Version 1.5 17 th April 2015 Page 1 Table of contents 1 CHANGE HISTORY... 3 1.1 DOCUMENT HISTORY... 3 1.2 REVIEWERS... 3 1.3 APPROVALS... 3 2 INTRODUCTION...
More informationELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist
More informationINSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
More informationFAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
More informationQuestions and Answers for Heating and A/C Contractors
1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded
More informationA guide to connecting to fibre optic networks for homeowners, architects, builders and developers.
A guide to connecting to fibre optic networks for homeowners, architects, builders and developers. Chorus is New Zealand s largest telecommunications utility company. We maintain and build the local access
More informationELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
Original Certificate DETAILS OF THE CLIENT Certificate reference: ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Name: Address: PURPOSE
More informationNORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS
SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications
More informationListed are common requirements that apply to existing solar installations when altered, added to or reconfigured.
SOLAR ALTERATIONS REQUIREMENTS August 2015 These requirements address typical alterations to solar installations; they cannot address every scenario. In Victoria, an alteration to a solar installation
More information12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
More informationAS/NZS 3000:2007 Amendment 2
AS/NZS 3000:2007 Amendment 2 Published 14 December 2012 Under Victorian legislation the day a revised standard is published it becomes the requirement. The aim of this document is to highlight the important
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationErrata NFPA 70. Proposed 2014 Edition
Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes
More informationCHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
More informationCHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE
CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE 8.1 SYSTEM 8.1.1 Armoured, screened underground cables are used for control communication in electrified areas to limit induction effect. 8.2
More informationINSIDE TELEPHONE WIRING FOR Business
Do It Yourself Guide INSIDE TELEPHONE WIRING FOR Business As of March 1, 2015 all single line business customers that have a demarcation point such as but not limited to a Network Interface Device (NID),
More information2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
More informationChapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
More informationPresenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
More informationTop Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
More informationDENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS
PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is
More informationGUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
More informationPower Separation Guidelines for SYSTIMAX Installations
SYSTIMAX Solutions Power Separation Guidelines for SYSTIMAX Installations Design and installation guidelines August 2011 www.commscope.com 1.0 General These guidelines are based on extensive testing and
More informationAuthority to alter facilities in residential and small business premises
Authority to alter facilities in residential and small business premises Engineering Document number F0002-31-11678 Document category Guide Author Engineering Approver (owner) National Engineering Manager,
More informationThe National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
More informationSeparation of common services (above and below ground) INDUSTRY BULLETIN. Background. Separation distances. Proximity of services below ground
Government of Western Australia Department of Commerce Separation of common services (above and below ground) The purpose of this industry bulletin is to remind building practitioners of their responsibilities
More informationBuilding Regulations P.4. Socket Outlets P.6. Other Considerations P.10. Training Seminars P.24
1 Introduction For well over one hundred years the Wiring Regulations have provided the rules which must be followed to make sure that electrical installations are safe. The introduction of the 17 th Edition
More informationSpecifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
More informationHOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12
SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications
More informationINDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23
INDUSTRY WIDE LABOR-MANAGEMENT SAFETY COMMITTEE SAFETY BULLETIN #23 GUIDELINES FOR WORKING WITH PORTABLE POWER DISTRIBUTION SYSTEMS AND OTHER ELECTRICAL EQUIPMENT "ADDENDUM C" WORKING WITH 480 VOLT SYSTEMS
More informationInstructions for Safe Use
Instructions for Safe Use (Certification N:o VTT 08 ATEX 029) Thank you for choosing Slam Trans portable transformer for your job site. Purpose of this manual is to provide you all the necessary safety
More informationFREQUENTLY ASKED QUESTIONS
September 2011 FREQUENTLY ASKED QUESTIONS Wiring Rules The new edition of the Australian/New Zealand Standard for Wiring Rules (AS/NZS 3000:2007) was released in November 2007 and revised by Amendment
More informationSECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 62305-3 Edition 2.0 2010-12 colour inside Protection against lightning Part 3: Physical damage to structures and life hazard INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE
More informationPROTECTION AGAINST ELECTRIC SHOCK by John Ware
16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created
More informationAdvantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
More informationELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
More informationHomeowner Information Guide Electrical Safety. British Columbia Safety Authority
Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in
More informationCooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
More informationElectrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
More informationBroadBand PowerShield. User Manual
BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains
More information270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer
More informationELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity
More informationEmergency Telephone Systems
Standard Issued Date: 22 May 2014 Important Warning This document is one of a set of standards developed solely and specifically for use on the rail network owned or managed by the NSW Government and its
More informationIP DSLAM IDL-2402. Quick Installation Guide
IP DSLAM IDL-2402 Quick Installation Guide Table of Contents Package Contents... 3 Overview... 4 Setup the IDL series IP DSLAM... 5 Safety Instruction... 5 Hardware Installation... 6 WEB Configuration...
More informationStand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation
Stand Alone POTS Fiber Optic System P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit Description & Installation Printed in USA 09/11 TO466 Rev. A Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT
More informationInformation and Communication Technology Network Cabling Infrastructure Standard
Approved on Dec-2005 by Eugene Formato Manager, Communications Services Last Amended Aug-2009 by Jarren Beveridge Network Engineer, Communications Services Scheduled for Review Jan-2010 Information and
More informationBETAtrans. Cables and Systems for Rolling Stock. Edition 2006
BETAtrans Cables and Systems for Rolling Stock. Edition 2006 Info Consulting and Sales By Phone To ask for Information or to place an order please use the following number: +49 (0)9172-6844-11 By Fax For
More informationPLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.
PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to August 1, 2013. It is intended for information and reference purposes only.
More informationBATHROOM HEATER. User's Manual. Page 2...A515 Page 9...A716
BATHROOM HEATER User's Manual Page 2...A515 Page 9...A716 BATHROOM HEATER User's Manual A515 SAVE THESE INSTRUCTIONS AND READ ALL INSTRUCTIONS BEFORE USING THE HEATER. Dear customers, Thank you for selecting
More informationHeading FACT SHEET. Overview. www.safeworkaustralia.gov.au
ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks
More informationTECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT
TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.
More informationOntario Electrical Safety Code 25 th Edition/ 2012
Ontario Electrical Safety Code 25 th Edition/ 2012 Ted Olechna Director, Codes and Standard Chief Engineer 1 What I Will Cover ESA s role is as the regulator Highlight of 2012 Code changes The Code and
More informationGROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
More informationELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
More informationRegulations for the Installation of Electrical Wiring, Electrical Equipment and Air Conditioning Equipment
Regulations for the Installation of Electrical Wiring, Electrical Equipment and Air Conditioning Equipment Qatar General Electricity & Water Corporation KAHRAMAA Customer Services Department State of Qatar
More informationESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check
More informationRequirements for Electrical Installations
ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This
More informationPlease check with your local inspection authority for any additional requirements before installation.
Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be
More informationLSA-PLUS Series 2 Connection and Disconnection Modules and Accessories
LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories 2015 PRODUCT CATALOG 2ND EDITION LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories A technically and commercially
More informationIMPACT DAMAGE RESISTANT WALL SYSTEMS
IMPACT DAMAGE RESISTANT WALL SYSTEMS CONTENTS Introduction 2 Advantages 2 2 Material Specifications 2 Design Considerations 3 Framing 5 Plasterboard Installation 5 Health, Safety & Warranty 6 Contact Details
More informationSECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES
SECTION 611 ACCEPTANCE PROCEDURES FOR TRAFFIC CONTROL SIGNALS AND DEVICES 611-1 Description. This Section sets forth Contract acceptance procedures for installations of traffic control signals and devices
More informationStandards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)
The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and
More informationElectrical safety of grid-connected solar installations in Western Australia December 2011
Electrical safety of grid-connected solar installations in Western Australia December 2011 Level 1, 303 Sevenoaks Street (cnr Grose Avenue) Cannington, Western Australia 6107 PO Box 135 Cannington WA 6987
More informationCode of Practice Electricity transmission and distribution asset management. February 2009
Code of Practice Electricity transmission and distribution asset management February 2009 CONTENTS 1 PREFACE...4 2 APPLICATION AND OBJECTIVES...5 3 SCOPE...6 4 DEFINITIONS...7 5 DESIGN AND CONSTRUCTION...11
More informationDRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationRapide Inline Ceiling Extractor Fan, White Fascia 41800040590. Rapide Inline Ceiling Extractor Fan, Chrome Fascia 41800040580
Any Queries Call : 08000 23 23 23 Rapide Inline Ceiling Extractor Fan, White Fascia 41800040590 Rapide Inline Ceiling Extractor Fan, White Fascia Illuminated 41800040670 Rapide Inline Ceiling Extractor
More informationDEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
More informationFault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
More informationDaily use. Never use alcohol or other solvents to clean any part of the loudspeakers!
BeoLab 6002 Guide WARNING: To reduce the risk of fire or electric shock, do not expose this appliance to rain or moisture. Do not expose this equip ment to dripping or splashing and ensure that no objects
More informationSolar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
More informationVerizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012
Verizon NEBS TM Compliance: Data Center Equipment NEBS Requirements Verizon Technical Purchasing Requirements VZ.TPR.9703 Issue 2, March 2012 CHANGE CONTROL RECORD: Version Date Action* Reason for Revision
More informationMEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
More informationNEW ZEALAND ELECTRICAL CODE OF PRACTICE. for ELECTRICAL SAFE DISTANCES
NZECP 34:2001 ISSN 0114-0663 NEW ZEALAND ELECTRICAL CODE OF PRACTICE for ELECTRICAL SAFE DISTANCES NZECP 34:2001 NEW ZEALAND ELECTRICAL CODE OF PRACTICE for ELECTRICAL SAFE DISTANCES Issued by: Manager,
More informationWhitepaper. Modular Substation Cable Termination Design. Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada
Whitepaper Modular Substation Cable Termination Design Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada Abstract The methods for cable penetrations into modular industrial substations are
More informationHigh PoE Midspans NPD-6001A NPD-9501A. en Installation Manual
High PoE Midspans NPD-6001A NPD-9501A en Installation Manual High PoE Midspans Table of Contents en 3 Table of contents 1 Safety 4 1.1 About this Manual 4 1.2 Legal Information 4 1.3 Safety Precautions
More informationLightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
More informationGrounding Demystified
Grounding Demystified 3-1 Importance Of Grounding Techniques 45 40 35 30 25 20 15 10 5 0 Grounding 42% Case 22% Cable 18% Percent Used Filter 12% PCB 6% Grounding 42% Case Shield 22% Cable Shielding 18%
More informationSURGE PROTECTIVE DEVICES
SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood
More informationANSI/TIA/EIA-606. Administration Standard for the Telecommunications Infrastructure of Commercial Buildings
ANSI/TIA/EIA-606 Administration Standard for the Telecommunications Infrastructure of Commercial Buildings Distributed by NDS INFORMATION- TELECOM SYSTEM --------------------------------------------- Head
More information