THE COPPER SOLUTION: Power Quality



Similar documents
Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc.

TC Grounding and Bonding for Telecommunications Systems

Element D Services Electrical

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

OPERATOR - FACILITY ADDRESS - DATE

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Minimum Standards for Data/Voice Infrastructure in New Building Construction

How to Estimate the Cost of a Clean Room and Data Center Equipment Electrical Work. Section 2 Types of Methods of Measurements page 4

Engineers Edge, LLC PDH & Professional Training

Electrical. This section applies to the design and installation of building power distribution systems.

NORTHERN VIRGINIA ONE (NoVa) DATA CENTER OVERVIEW

Electrical Code Regulation

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850

David Brender Copper Development Association Inc. Miramar, March 8, 2013

Power to the adaptable data center

Voltage Drop (Single-Phase)

Subject: County of Los Angeles Data Center Space Requirement

Re-examining the Suitability of the Raised Floor for Data Center Applications

BASIC NEC CODE RULES AND DESIGN PRACTICE

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

19 Site Location, Design and Attributes. Site Location, Design and Attributes

Top Commercial / Residential Electrical Requirements *

June July 18, of 7

Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Voltage Drop. Voltage Drop 1

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Parallel Redundant Uninterruptible Power Supply

ELECTRICAL INSPECTION BULLETIN (Effective )

Qualitative Analysis of Power Distribution Configurations for Data Centers

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers

415V DISTRIBUTION FOR GREEN DATA CENTERS

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

IRRIGATION PUMPING Table of Contents - Section 900

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM

How To Get A Power Line Extension

CHAPTER 2 EXAMPLES AND TABLES

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

APC 3Phase Power Distribution

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

COMMODITIZING THE DATA CENTER MARKET

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

Doc Ref: baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM

Fundamentals of Power

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

Addendum #2 Contract UK-11-13

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Multiple Meter Installation Amperes Per Position -Single Phase, Self-contained

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

High-Efficiency AC Power Distribution for Data Centers

Introduction to Data Centre Design

Data Centers and Mission Critical Facilities Operations Procedures

Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012

This presentation to be used in conjunction with:

TIA-942 Data Centre Standards Overview WHITE PAPER

800 Communications Circuits

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

Power Quality for Information Technology System

Midwest s Premier Carrier Neutral Colocation Data Center Greater Minneapolis St. Paul, Minnesota

Cable Tray Selection-

Data Centre Barrie, Ontario

Power and Cooling for Ultra-High Density Racks and Blade Servers

LEVEL 3 DATA CENTER ASSESSMENT

Chapter 9. Bonding and Grounding

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA)

Safeguard your critical IT assets in a highly secure, fully redundant, environmentally-conditioned and constantly monitored hosting space to receive

Errata NFPA 70. Proposed 2014 Edition

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

STREETLIGHT SYSTEM GROUNDING AND BONDING

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

Alternative data center power

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Digital Chicago. 600 south FeDeraL - chicago grand ave - FranKLin ParK 350 east cermak - chicago

Grounding & Bonding Why it is done And How to Install Properly

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

Session 14 Cable Support Systems

LEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT.

Is an energy-wasting data center draining your bottom line?

SYSTRUST CERTIFICATION REPORT FOR COLLOCATION AND DATA CENTER HOSTING SERVICES FOR THE PERIOD FROM JANUARY 1, 2013 TO DECEMBER 31, 2013

Transcription:

THE COPPER SOLUTION: Power Quality Copper Ensures Reliability, Power Quality at Boston Data Center Data centers have quietly become a significant portion of the national electrical infrastructure. The Federal Government alone was operating more than 1,100 in 2009. 1 Along with commercial facilities, the data centers are huge electric power users. The U.S. Environmental Protection Agency once projected that such centers would account for three percent of all electricity consumed in the country in 2011, but they surpassed that figure a year earlier. At a 10% cumulative annual growth rate (CAGR), consumption could double well before the decade is out. 2 Steve Collins, an Associate with Vanderweil Engineers, a leading engineering firm (see description below), estimates that the gross power consumed by these server farms will increase significantly as centers continue to proliferate and unit electrical loading in them rises to a projected 1,500 W/sq ft. Data centers differ from most other industries in that electrical power reliability and power quality are exceptionally high. A TIA 942 Tier 4-rated facility will have 100% reliability, but, allowing for human error, the standard allows or projects at least 99.995% average availability (0.4 h average annual downtime over five years), yet, the percentage is often higher than that. High power quality implies stable, correct voltage with undistorted waveform. Equipment is correctly installed, rigorously maintained, and, not incidentally, dependent on miles of copper for reliability. All of which brings us to One Summer Street, an 800,000-sq ft data center located in Boston s Downtown Crossing (Cover photo). Don t be misled by that Macy s sign; the data center occupies most of the 2½-acre, city-block-size building, including systems infrastructure located in the basement levels and multiple roof areas. As a data center, its advantages include a potentially large nearby customer base; eight utility feeds from

two substations for reliable power and service by no less than 40 national and international communication providers. The neutral colocation center is a true carrier hotel. It s the largest and arguably the most significant data center facility in the entire New England region. New Infrastructure The Markley Group built, owns and operates One Summer Street. The company is a leading data center developer with properties in the U.S. and Europe totaling more than three million square feet. Markley Group acquired the 70-year-old Macy s building in 1999 and has invested more than $150 million to create the kind of sophisticated infrastructure a facility of this importance requires. That infrastructure is the subject of this case study. The building itself was exceptionally sound, with features such as secure walls and high ceilings not found in some purpose-built centers (Figure 1). Its large, multitiered roof area was ideal for emergency generators, chillers and related equipment (Figure 2). And, with Macy s continuing to occupy the lower floors, the center itself is hidden in plain view not a trivial security consideration. The building s old electrical infrastructure was another story. Energy-hungry data centers didn t exist 70 years ago, so totally new electrical, grounding, IT and HVAC systems had to be installed. Power density exceeds 400 watts per square foot. The Markley Group assigned the building s makeover to Vanderweil Engineers, a Boston-based firm with more than 50 years experience with commercial, industrial and public facilities, including data centers. Besides design, Vanderweil undertook construction administration and oversight, recommended subcontractors, and even conducted detailed inspections during construction. They were also the systems-commissioning and integrated testing agents. Figure 1. Fifteen-foot ceilings at One Summer Street enable installation of 24 to 36 raised floors while maintaining ample overhead space for cable trays and racks. Fully Redundant Electrical Systems The building s utility vaults are designed for a 20-MW electrical service, which is expandable to 40 MW. The vaults are dedicated to the data center. Two entirely separate 13.8-kV, 10-MW utility feeds enter through the two vaults, each containing four liquid-cooled, 2,500- kva, 13.8 kv-480/277 V transformers, Figure 3. Three double-ended switchboards provide fully redundant Figure 2. More than 30 generators and HVAC equipment nearly blanket the building s 2½-acre, mulitiered roof. A total of 30 MW of emergency power plus more than 10 MW of rotary and battery UPS power ensure seamless transfer. Future build-out to 40 MW of generation will accommodate growing electrical loads. Figure 3. Four of eight 13.8 kv-480 V utility transformers located in a vault at One Summer Street. A similar set of transformers in a separate vault form the other half of the double-ended utility feed. Copper buswork seen at the upper left feeds distribution switchgear located in the basement. Utility ground straps are visible on the floor and rear wall. 2

services, referred to as the A and B circuits. The data center has never experienced an outage, although it is fully protected should one occur. The center s 480-V power is distributed from the basement to server floors via ten 4,000-A copper bus risers. Four 5,000-A bypasses connected to the 6000-A rated switchgear enable load-switching among the riser feeds in the event one service should fail (Figure 4). Power bus risers are physically separate from IT/data risers in order to avoid electrical noise on sensitive circuits. Approximately one hundred 480 V-208/120 V distribution transformers of various sizes feed servers and convenience outlets (Figure 5). Additional 480/277 V transformers serve lighting and HVAC requirements. All distribution transformers are copper-wound, dry-type, K-rated (mostly K13 and K20) units meeting NEMA TP-1 efficiency standards. Individually fed power distribution units (PDUs) feed branch circuit panels and remote power panels (RPPs). For redundancy, branch circuits are extended to each server cabinet in an A+B configuration from two unique PDUs. The redundancy at the branch circuit improves reliability and permits either half of the electrical system to be shut down for maintenance without disrupting power (Figure 6). Figure 4. Switchgear (in cabinets, bottom) and three of the ten 480-V, 4,000-A copper bus risers that feed power to upper floors (top of photo). Four 5,000-A bypasses enable switching among primary feeds. Figure 6. Power is fed to equipment cabinets via power distribution units (PDUs), seen here. Each PDU/cabinet is served by a minimum of two branch circuits providing 2N redundancy. Copper grounding conductors are run in ladder racks, above. Figure 5. Two (of more than 100) redundant 480 V-208/120 V distribution transformers feed customers servers and convenience outlets. All sub-distribution transformers are copperwound, dry-type, K-rated, and meet NEMA TP-1 efficiency standards. Going Beyond the Code Every Day The National Fire Protection Association s (NFPA) National Electrical Code (NFPA 70: NEC) is concerned primarily with safety. It doesn t fully address reliability or sensitive electronic equipment, which are dealt with in publications such as the Institute for Electrical and Electronics Engineers (IEEE) Gold 3 and Emerald 4 books, and the Telecommunications Industry Association standards 5, among others. Data centers could not guarantee the levels of reliability and power quality required if they were designed and built to the Code s minimum requirements. Electronic equipment especially IT and telecommunications equipment requires higher reliability and better power quality than the Code s minimum standards provides for. For example, Code-mandated wire sizes and voltage drop limits involve safety issues (overheating) but 3

can also affect reliability and power quality. Don Esson is the Markley Group s facilities manager at One Summer Street. The NEC is a minimum standard, he says, and we supersede it every day in every project we work on. Working strictly to Code practice, we would be running AWG #12 wire for a 20-A branch circuit. Our standard is to run #10 instead. It can handle 1.5 times the ampacity; it s more robust and therefore more reliable. Also, with #10, the customer has the built-in flexibility to upsize to 30-A receptacles in the future if he wishes. There s very little increase in materials and labor costs, but reliability improves and you usually don t have to upsize the conduit when upsizing copper, as you would with aluminum. We limit the number of outlets per branch circuit to between four and six, except for IT circuits, which are one-on-one, or actually two-on-one since all IT branch circuits are double-ended: each receptacle contains two #10 phase conductors and a neutral conductor for the A circuit and two more for the B circuit, plus separate full-size grounding conductors. Voltage drop is another important consideration. We always bump up one conductor size, so if you had a 100- A feeder, by Code you would typically run #4. We would probably run that with #2 wire. Voltage drop gets taken out of the equation at that point. The Code permits a two percent drop for feeders and three percent for branches, but we hold that to just two percent. Back-up Power The facility has approximately 20 MW of emergency generator capacity, and more than 10 MW of rotary (flywheel-type) and battery power in multiple UPS systems. Power cables from generators and UPS systems are in multiple sets of 500 750-kcmil conductors. Backup power is extremely important for a facility such as this, says Mr. Esson, and, while value engineering may give us a choice to save on cost, it is important for us to utilize quality components to maintain system reliability. Equipment testing, commissioning and integrated testing, along with proper scheduled maintenance, are essential for these equipment items and systems. all treated individually, which resulted in each tenant having their own electrical service entrance equipment, a scenario that created multiple ground current loops throughout the building. Grounding is critical in a data center, says Mr. McLean. Computer equipment is very sensitive to harmonics and high currents, so you want to isolate the equipment from transients, high frequencies and ground currents that might be placed on your grounding system at points of voltage and current transformation. We only have two levels of transformation, from 13.8-kV utility service to 480 volts and again from 480 volts to 208/120 volts, but they occur at hundreds of points where you re connecting neutral to ground at transformers, switchboards and other separately-derived systems. Any of those points could feed transients, stray currents or harmonics back to the computer equipment. Our enforcement of a single-point grounding system prevents that. The single point Mr. McLean refers to is the center s main grounding bar, a one-foot-high by three-feet-wide copper plate located in the building s subbasement (Figure 7). To that plate alone are bonded all ground leads from the building. There are actually two risers for the grounding system: one for the power distribution system, which includes generators, transformers and UPS equipment; the other for IT and communications circuits. Separating the two systems isolates IT/comm equipment from noise, harmonics and floating ground currents that may be present at ground-to-neutral bonds. The two systems are bonded together only at the main grounding bar. Single-point Grounding Christopher McLean, PE, LEED AP, is Vanderweil s Electrical Engineer at One Summer Street. From his employer s side, he s been personally responsible for almost all of the power distribution improvements during the several years he s been on the project. That responsibility includes the all-important grounding system. Prior to the inception of the Markley Group s ownership, tenants were Figure 7. The main grounding bar at One Summer Street is a three-foot by one-foot copper plate (right) located in the subbasement. All grounding conductors in the building s two grounding system branches terminate here. The smaller bar at left rear is an extension of the larger bar. 4

Extending earthward from the main grounding bar are multiple connections to building steel in walls and the subbasement floor, as well as to the water main on both sides of the meter. The building stands just 23 feet above sea level, making the floor and footings effective earthing points (Ufer grounds). Design ground resistance is five ohms. Connections to building steel (including the basement floor) are made only from the main grounding bar. McLean explains that All of the hundred-plus transformers throughout the building are connected to ground, plus we have many neutral-to-ground currents from unbalanced single-phase sources that ultimately put current to ground someplace. Had we connected to building steel from several points on the grounding system, the entire building steel system could have become one giant ground loop. That could compromise the ground-fault settings in switchgear and cause problems everywhere in the building. By connecting from only one point the main grounding bar in the basement we ve created a very robust grounding system that isolates those problems. Conduits are also bonded to the grounding system only at the main grounding bar to create a complete system. However and despite it being permitted by Code conduit is never used as the only grounding conductor. McLean explains: In almost all instances, conduit would not be an effective grounding path. We always run at least one separate grounding conductor for each feed. Where we run two parallel feeds in the same conduit, each gets its own green wire. One look at Article 250 in the Code would show you that the ampacity of the required copper grounding conductor is much higher than that of either galvanized conduit or electrical metallic tubing, EMT. Also, if we used the conduits as grounds, thousands of fittings and interconnections would then have to be inspected, torqued and tightened periodically, whereas a separate green wire only has to be inspected and torqued at the two end connections (Figure 8). Grounding connections between the main grounding bar and the two grounding system branches are made through separate risers in the building s corners, one for power distribution and one for IT equipment. Plans called for adding two more ground risers in the near future. Conductors from the main bar to the building floors are sized at 750 and 1,000 kcmil. They terminate at one-foot by three-foot copper grounding bars at each floor (Figure 9). Smaller conductors lead from those bars to multiple four-inch by one-foot collector bars located high on walls throughout the floor space Figure 8. Typical conduit runs at One Summer Street illustrate why the center relies on separate internal green wires rather than conduit itself as the grounding path. Copper is a better conductor than conduit steel. And, if conduits were used for grounding, thousands of connections and fittings would have to be inspected, torqued and tightened periodically, a hopeless task. Figure 9. A 1,000 kcmil grounding conductor (lower left) from the main grounding bar terminates at a ground bar serving one floor from one of the building s two ground risers. Smaller conductors bonded to the main floor bar (upper cables) lead to collector bars on the floor. 5

(Figure 10). Two sets of large and small grounding bars per floor serve power distribution and IT equipment, respectively. Grounding Overhead and Underfoot Equipment racks are grounded by overhead and underfloor systems. For overhead systems, individual cabinets are grounded with AWG #6 or #4 leading to overhead ladder racks. Grounding conductors from all cabinets in a row are bonded to a collector bus cable run in the racks. It may range from #2 to 4/0 in size depending on need (Figure 11). Collector bus cables are directed to the nearest collector bar. The ladder racks themselves are also grounded via the bars (Figure 12). Cable trays carrying 208-V power to servers are grounded to separate collector bars serving the power distribution branch of the grounding system. The raised-floor grounding system consists of grids of AWG #2 and 4/0 bare copper, (Figure 13). For approximately every 3000 sq ft of raised-floor area, one 4/0 grounding conductor is run from the grid to the wallmounted collector bar. Figure 12. Overhead cable trays and ladder racks are jumpered and grounded with AWG #2 bare copper. These conductors, along with the cable bus that collects ground leads from individual cabinets, are connected to the nearest wall-mounted collector bar. Figure 10. Multiple grounding collector bars are mounted on walls in server rooms. The AWG 2/0 conductor, top, leads to the riser bar, while #2 green cable, bottom, is a collector bus for a row of cabinets. Conductor sizes vary with clients needs. Figure 11. Green grounding conductors bond individual cabinets to an overhead collector bus. In this example, cabinet grounds are AWG #6 and the collector bus is #2, but larger sizes may be used. Figure 13. Bare copper grounding conductors are shown strung under a section of raised floor. Raised-floor grounding conductors from approximately every 3,000 sq ft of floor area are connected to a wall-mounted collector bar. 6

Planned Maintenance Important One Summer Street clearly has well thought out and executed electrical and grounding systems, but even these systems can degrade over time: Connections loosen, contact resistances rise and loads change, producing unexpected effects. The electrical and grounding systems at One Summer Street are, therefore, inspected and maintained according to a written program. Grounding connections are checked for tightness on a fixed schedule and re-torqued as needed. Power quality is monitored to ensure clean waveforms and voltage stability. Emergency generators and UPS units are periodically exercised. Systems are also regularly upgraded to meet changing needs. Data centers are indeed mission-critical facilities with unique reliability and power quality requirements. Toptier designers and owners like Vanderweil Engineers and The Markley Group, respectively, clearly provide their clients with both of these elements at One Summer Street. The key components are not surprising: sound design, careful installation, attentive management, regular maintenance... and the correct use of copper for circuitry and grounding. The Principals Donald J. Esson is the chief infrastructure engineer at One Summer Street. He can be reached at 617.451.2303 and at desson@markleygroup.com. Stephen R. Collins is an Associate at Vanderweil Engineers and has been the project manager for the One Summer Street projects. He can be reached at 617.423.7423 and scollins@vanderweil. com. Christopher K. McLean, PE, LEED AP, is an electrical engineer with Vanderweil Engineers assigned to One Summer Street. He can be reached at 617.574.8184 and cmlean@vanderweil.com. Endnotes 1 Office of Management and Budget, www.scribd.com/doc/27535844/data-center- Consolidation-Memo-02-26-10 2 www.energystar.gov/ia/partners/prod_development/downloads/epa_datacenter_ Report_Congress_Final1.pdf 3 The IEEE Gold Book: IEEE Standard 493, Recommended Practices for Grounding of Industrial and Commercial Power Systems, Institute of Electrical and Electronics Engineers, February 2007. Founded in 1950, Vanderweil Engineers is a full-service engineering firm committed to developing innovative solutions and solid working partnerships. It has earned a 90% repeat business ratio and is consistently ranked among the top U.S. engineering firms. Vanderweil can be reached at www.vanderweil. com or (617) 423-7423 4 The IEEE Emerald Book: ANSI/IEEE 1100, Recommended Practice for Powering and Grounding Electronic Equipment. Institute of Electrical and Electronics Engineers, December 2005. 5 TIA-942: Telecommunications Infrastructure Standard for Data Centers, Ed. V, March 2010, Telecommunications Industry Association. Over the past two decades, the Markley team has developed thirteen data center and telecom buildings throughout Europe and North America, with Markley's flagship facility located at One Summer Street in Boston. Markley Group can be contacted at www.markleygroup.com or (213) 622 3000. The Boston facility, in particular, can be contacted at (617) 451-6464. 7

This publication has been prepared solely as resource material for the use of individuals involved in the specification, design, selection and installation of electrical systems. It has been compiled from information provided by one or more of the parties mentioned herein and other information sources Copper Development Association Inc. (CDA) and/or the relevant parties believe to be competent. However, recognizing that each system must be designed and installed to meet particular circumstances, CDA and the parties mentioned in this publication assume no responsibility or liability of any kind, including direct or indirect damages in connection with this publication or its use by any person or organization, AND MAKE NO REPRESENTATIONS OR WARRANTIES OF ANY KIND RELATED TO ITS USE, ACCURACY, COMPLETENESS, UTILITY, AVAILABILITY OR DOCUMENTATION. A6134 XX/11