Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ
|
|
|
- Dale Nicholson
- 10 years ago
- Views:
Transcription
1 Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ 2011 Raritan Inc.
2 Overview Data center managers are faced with increasingly challenging demands: supplying additional computing power using less energy in a smaller space, while staying within budget constraints and maintaining mission-critical reliability. These demands often create a culture of frequent and predictable change without compromising the end product. Unfortunately, it can also stress some existing data centers, making them unsustainable for several reasons. These reasons can include: the inability to quickly adapt to changes in computer equipment capacity, the fact that many data centers are nearing or have surpassed the limitations of their power distribution system and the lack of efficiency due to an outdated or non-existent power monitoring infrastructure. This white paper will address the power distribution and monitoring solutions that have been successful in meeting these demands, and how data centers can be designed to create sustainable IT environments that are capable of satisfying evolving business, financial and regulatory goals. Trends Data center managers are looking for ways to increase energy efficiency while providing a highly adaptable IT environment to support service-oriented architectures and rapid changes in demand. Although software, systems and storage are all becoming highly adaptable, nothing in the data center can adapt quickly unless the power infrastructure is also adaptable. Problems include the following power-related issues: IT equipment is changing with a much higher frequency than the typical life expectancy of the data center. Typical data centers are designed with a life expectancy of 10 to 15 years. However, most IT equipment refresh cycles are 2 to 5 years. More powerful equipment often results in an undersized power supply system. The facility design must take a variety of power conditions into consideration: Medium density (5-10 kw/rack) and high density (15-30 kw/rack) equipment Blade servers, storage and high density networking fabrics Single-phase and three-phase power requirements, often mixed within a given rack Physical receptacle requirements Corporate and regulatory requirements for energy usage. Beyond the cost of energy, the goals and requirements for Power Usage Effectiveness (PUE), peak demand and carbon footprints must be addressed. A growing component of this system is the ability to measure energy usage on a granular level, driving the energy considerations to the point of use. Smart grid implementation will likely have additional implications for the energy infrastructure. Uptime requirements. High levels of uptime are assumed and table stakes are generally taken for granted. The impact of these trends on data center electrical design is obvious: the need for flexible, adaptable, electrical power distribution and monitoring systems. Page 1
3 Traditional Power Solutions: Too Much or Too Little Traditional data center power distribution designs consist of power distribution units (PDUs ) delivering power to remote power panels (RPPs), which in turn deliver power to racks via whips power cabling routed underneath a raised floor. While such implementations are well known and represent a low risk for the design engineer and electrical contractor, the drawbacks of such designs are well established: valuable floor space is consumed by distribution equipment; raised floors are costly; under-floor cabling becomes congested, disrupting air flow used for cooling; requirements to remove unused cables, which tend to be abandoned; and risk of human error while working with circuit breakers and cables that are not clearly associated with a given load. Equally important, traditional data center power implementations are neither flexible nor adaptable, and are therefore expensive and time consuming to change. When designing a data center with traditional electrical systems, engineers or designers must pre-plan every outlet from dedicated hard wired conductors for each power outlet through overhead or raised floors back to main distribution panels and circuit breakers. It is nearly impossible to predetermine the power requirements for each rack in each location when the data center goes live, let alone plan for future requirements. As a result, data center managers either overbuild the current system with a much higher investment, or build a system that will meet current planned demand, but increase the operating expense when costly changes are required. When inevitable changes occur as a result of growth, equipment upgrades or changed plans, the costs for electrical changes can be significant, both in terms of labor costs and the risk of outages. Today s Power Solutions: Flexible and Adaptable In recent years, power management solutions have evolved to the point where they are both flexible and easily adaptable to changing requirements. They are also scalable for change and growth and typically provide the lowest long-term cost of ownership. Solutions include overhead busway systems, intelligent PDUs and intelligent power management software, working together seamlessly: Overhead busway systems are comprised primarily of busway sections (straight lengths containing busbars and a slot for continuous access) and tap boxes (plug-in units containing circuit protection and wiring devices). Systems are available up to 400 amps and 600 volts, AC and DC. Intelligent PDUs include switched, non-switched and metered PDUs and inline meters that provide environment and power metering, monitoring and management. Power management software lets you baseline, monitor and report energy usage and environmental conditions at any level data center, rack, department and equipment type. It also provides centralized monitoring, graceful OS shutdown, outlet control, powerful analytics of your costs, line capacities, carbon footprint and rack temperature. Page 2
4 Overhead Track Busways: Easy, Fast and Inexpensive to Change The STARLINE Track Busway system can be tapped at any location with a variety of plug-in units, eliminating panel boards, long runs of conduit and wire and expensive installation costs for dedicated power outlets. Dedicated circuit breakers located at the point of use make troubleshooting outages or reconfiguring supplies very easy. The cost to install the STARLINE system is competitive with traditional power distribution systems. Where greater savings come in is when power needs to change. With an overhead bus system, there is no need to work on live panels or schedule outages to add, move or change outlets. Overhead bus systems eliminate the need to remove and scrap short or undersized cable whips and run new longer or larger ones. Therefore, the risk of unintended potential power outages is avoided. Racks can be installed or moved without disrupting operations. Any location in the data center can have the racks installed, moved, reconfigured or removed without affecting anything else in the space, and without risking an unplanned outage. Power can be accessed at any location along the busway system, eliminating the need for power boards, long runs of wire and expensive installation costs. Sustainable Overhead bus systems can be reusable for years for future facility changes and growth. With the busway, as compared with individual cables, less copper is used and the reusable components save energy and reduce waste for the cost of mining, smelting and transporting replacement items. Traditional power distribution methods in a raised floor environment can restrict vital HVAC air flow. A clean, organized power busway system simplifies power distribution and can lower HVAC costs. Page 3
5 Ever-increasing server densities are causing an increase in kw power density, resulting in increased cooling requirements in today s data centers. For every kw increase in power, an equal amount of cooling capacity is required. This never-ending cycle of increasing power and cooling requirements translates into more and larger power cables under the floor stealing valuable cooling space. With an overhead bus system, there is no jungle of wires to obstruct air flow under the floor, making it one of the most energy efficient and safe power systems available in the market today. Scalable Data center electrical designs are often outdated before they are ever istalled. Day one requirements are often different from the original plan, which forces electrical outlet locations and types to be reconfigured, increasing costs and causing schedule delays. STARLINE is completely scalable, enabling components and power circuits to be added as needed without tying up capital and wasting resources rather than completely building out the entire facility in the beginning. This is very beneficial for co-location and other facilities that are built out over time. It also enables a greener data center because changes to increase resource utilization are not hampered by an inability to quickly supply the correct power at a new location. More Usable Data Center Space With data center floor space at a premium, every square foot is critical. Overhead bus systems eliminate RPPs, which result in more usable space in the data center for IT equipment and server racks. In addition, miles of power cables are eliminated when power outlets or drops can be located exactly where they are needed. Monitored Power Usage It is important for data center managers to have the ability to monitor and know the exact power usage of the data center. All too often, as new equipment is added to a rack, the cable ratings can be exceeded, trip the circuit breakers and cause an unplanned outage. STARLINE Track Busway systems provide power feed monitoring units to measure and display each phase current in real time, perform alarm functions and provide remote communication. With complete system power monitoring, data center managers can intelligently plan for the future. They know the exact capacity and load of each rack or system and therefore know where they can install new or upgraded equipment. In addition, monitoring helps ensure the electrical system is balanced across phases, leading to better energy efficiency and ultimately costs savings. Page 4
6 400V Intelligent Rack PDUs: Accurate, Intelligent Power Delivery, Monitoring and Management Maintaining 400V power to the IT equipment rack minimizes transmission losses. Typically, 480V three-phase power enters a data center and is converted to 208V/120V. This conversion causes about a 4% transmission loss. Keeping the power to the rack at 400V means virtually no loss. Cost Savings Within the rack PDU, the hot lines are wired to the neutral, resulting in 230V at the rack PDU outlets. (The 400V is the voltage measured between two hot lines, e.g., L1 + L2. Tying a hot line to the neutral, e.g., L1 + N, drops the voltage Baseline: 208 VAC 3-Phase UPS PDU Transformer Floor/Wall PDU Rack PDU 480 V 480 V 208 V 208 V 1- or 208 V 1- or- 120 V 120 V 415 VAC 3-Phase UPS Floor/Wall PDU w/ Autotransformer Rack PDU 480 V 480 V 415 V 240 V 240 V UPS w/ Autotransformer Floor/Wall PDU Rack PDU 480 V 415 V 415 V 240 V 240 V Page 5
7 to 230V {400V/1.732}.) Virtually all modern IT equipment has a universal power supply capable of operating between 100V and 240V, so 230V is a safe operating voltage. In fact, there are additional power savings since operating processors at 120V leads to an 18% loss whereas operating processors at 230V leads to a 15% loss, an efficiency gain of 3%. Taken together, the total net improvement is 7% (4% + 3%). By eliminating unnecessary voltage transformations, 400V power reduces energy costs by approximately 2-3% vs. 208V distribution; and approximately 4-5% vs. 120V distribution. Power to Spare Supplying 400V power to each rack minimizes step-down transformation and line transmission loss while simultaneously reducing copper utilization. Typically, 400V three-phase power is connected to two intelligent rack power distribution units (ipdus) in each cabinet. The rack PDU, with internal line-to-neutral (three-phase Wye) wiring, supplies each server with 240V, single-phase power which is well within the operating range of the power supplies of virtually any IT equipment. A typical configuration of the rack PDU described above is three input lines and three circuits (L1 + N, L2 + N and L3 + N). In North America, the National Electrical Code (NEC) requires branch circuits to be protected from overloads at 20A or less. Therefore, each of the three circuits has a 20A circuit breaker (or fuse). Intelligent rack PDUs may monitor the circuit breakers and send alerts when a circuit breaker gets close to tripping. Intelligent rack PDUs may also monitor the three lines and send alerts if the lines become unbalanced. For example, if 20A loads were plugged into circuits #1 (L1 + N) and #2 (L2 + N) but there wasn t any load in circuit #3, this would leave L3 out of balance with L1 and L2. Such imbalances can overload the neutral wire and cause other problems such as harmonics. Environmental Monitoring Intelligent rack PDUs meter power, in some cases at the individual outlet level. Metering can include current, voltage, power (kva, kw) and consumption (kwh). Ideally, kwh should be measured at +/- 1% billing-grade accuracy. Intelligent rack PDUs can also support environmental monitoring at the rack. Ideally, the rack PDU should support optional plug-and-play environmental sensors, such as temperature and humidity, which then don t require additional network connections or hardware. The American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) recommends placing temperature sensors on the cool air inlet side of a rack at the bottom, middle and top. An intelligent rack PDU should also support monitoring temperature with user-adjustable high and low temperature thresholds. When the thresholds are crossed, alerts are sent so the temperature can be lowered if too hot or raised if too low, thereby Page 6
8 wasting power by overcooling. Monitoring humidity is also important but since it doesn t change much with respect to location on a rack, one humidity sensor per rack is sufficient. Recently, ASHRAE raised the high end of the allowable inlet temperature range to 27 C (81 F). IT equipment vendors ensure that with this inlet temperature, IT equipment will operate safely. By raising the ambient temperature in a data center, IT managers can reduce the energy consumed by air-conditioning. As a global vendor of rack power distribution units, Raritan provides a very large range of product configurations that accept 400V input. While 400V distribution is relatively new in North America, Raritan has deployed 400V systems in Australia and in many European countries where it is the nominal standard. Data Center Power Management Software: Powerful Data Collection and Reporting at Your Fingertips Data center power management software should be able to gather information from a variety of rack PDUs and metered devices since data centers have a variety of meters and vendors. The software should be able to consolidate the information and present it in reports that can be organized to meet the needs of the data center. For example, it might be useful to look at power data organized by data center location or power usage by department or check the efficiency of different servers. If greenhouse gas cap and trade becomes significant, reports on a data center s carbon footprint will be useful. It also makes sense for the data center power management software to gather and manage data center rack environmental information such as temperature and humidity. ASHRAE has established, in cooperation with IT equipment vendors, recommended temperature and humidity ranges for the air at the cool air inlets of IT equipment. The higher the temperature at the cool air input, the less energy is being expended on air-conditioning. It would also be useful for the power management software to configure rack PDUs. Since a data center may have hundreds of rack PDUs, some way to speed up their configuration would be a welcome feature for most data center managers. An example of ipdus, environmental sensors and power management software working together to display temperature and humidity data points in the data center. Data center power management software gathers data from sensors and ipdus and displays information on a single, organized dashboard. Page 7
9 Product Selection Track busway selection should follow these considerations: Continuous access slot design provides the greatest flexibility in plug density and positioning Section lengths should be as long as possible (up to 20 feet) to reduce the number of electrical joints Tap boxes should have a comprehensive range of ratings and wiring devices Tap boxes should have a minimum number of parts and connection points for greatest reliability Joints and connection points should be lifetime maintenance-free Supplier should have proven track record of performance and delivery Intelligent rack PDU selection should follow these considerations: Outlet-level switching so outlets can be turned on and off to control the provisioning of power. Unswitched outlets may be desirable for situations and applications where switching off power could present problems, e.g., 24/7 mission-critical servers Rich and accurate power data collection including current (A), voltage (V), power (kva, kw), power factor and energy consumption (kwh) with billinggrade +/- 1% accuracy Built-in support for plug-and-play environmental sensors Buffering of power and environmental data so as not to tax network bandwidth Monitor branch circuit breaker current and trip status For three-phase power, monitor balance of current draw across the three phases Intelligent power management software allows you to monitor branch circuit breaker current and trip status down to the outlet level. Page 8
10 Power management software selection should follow these considerations: Multi-vendor management User-configurable dashboard Clean presentation of information via reports and charts energy consumption via device, rack or customer Monitoring and notifications Advanced cooling analytics Powering the Data Centers of the Future Change is inevitable, and data centers should be designed with this undeniable precept in mind. Companies that cannot shift with the times or trends because of antiquated technology and infrastructure lose business to more agile competitors. Power management solutions play a fundamental role in implementing more versatile data centers that can quickly evolve to address the demands and challenges of the future. For More Information The STARLINE Track Busway system is the leader in this product category. Other Universal Electric Corporation products include STARLINE Plug-In Raceway and U-S Safety Trolley. Visit for your Flexible Power Solutions. Raritan Commitment Raritan is a longtime industry leader in providing advanced technology products for data center management. Raritan s brands include Paragon and Dominion secure out-of-band access and control of servers; the PX family of intelligent PDUs; Power IQ data center power and energy management software; and now dctrack an advanced, full-functioned DCIM for data center change and capacity management with workflow best practices. Raritan s products have always distinguished themselves as easy-to-use and best-in-class performers. As your organization begins to explore DCIM tools, we invite you to consider Raritan s dctrack as your solution. Based in Somerset, NJ, Raritan has 38 offices worldwide, serving 76 countries. For more information, please visit Choose the solution that will not only let you monitor and manage the devices you ll deploy in the future, but the resources you have now Raritan Inc. All rights reserved. Raritan, Know more. Manage smarter., Dominion, Paragon, PX, Power IQ and dctrack are registered trademarks or trademarks of Raritan Inc. or its wholly-owned subsidiaries. All others are registered trademarks or trademarks of their respective owners. C1034
EO 13514 and Smart Federal Government Data Center Management
1 Overview In fiscal year 2009, the U.S. government used an astounding 1,095.7 trillion BTUs of energy. This total included everything from keeping the lights on at the Lincoln Memorial to maintaining
Power Management. Raritan Description. http://www.raritan.com/products/power-management/
Raritan Description Raritan is a proven innovator of power management, infrastructure management, KVM and serial solutions for data centers of all sizes. In more than 50,000 locations worldwide, our hardware
dctrack Data Center Infrastructure Management Visualize, Manage and Track IT and Facilities Systems dctrack
dctrack Data Center Infrastructure Management Visualize, Manage and Track IT and Facilities Systems dctrack An all-in-one solution for efficient data center management, spanning facilities, networking
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
Data Center Power Distribution and Capacity Planning:
Data Center Power Distribution and Capacity Planning: Understanding what you know and don t know about power usage in your data center 2009, Raritan Inc. About This Series Raritan, a leading provider of
Data Center Infrastructure Management (DCIM) Demystified
software is quickly becoming the core engine of data center operations. Only 5 years ago, manual spreadsheets, sometimes supplemented with Visio diagrams, were accepted as the default tools for data center
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning 2009, Raritan Inc. Overview Corporate America is more dependent than ever on computing
An Introduction to Data Center Infrastructure Management
An Introduction to Data Center Infrastructure Management 2010 Raritan Inc. Overview Worldwide demand for new and more powerful IT-based applications, combined with the economic benefits of consolidation
Server Technology, Inc.
Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill
EO 13514 and Smart Federal Government Data Center Management
EO 13514 and Smart Federal Government Data Center Management 2011 Raritan Inc. Overview In fiscal year 2009, the U.S. government used an astounding 1,095.7 trillion BTUs of energy. This total included
Management and Wireless in the Data Center
SOLUTIONS BRIEF Management and Wireless in the Data Center High Performance Wireless Networks Management and Wireless in the Data Center Worldwide demand for new and more powerful IT-based applications,
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE Highly efficient solutions for power distribution, management and monitoring POWER DISTRIBUTION WIRE-FREE MONITORING LEAK DETECTION Daxten provides comprehensive
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Energy Savings in the Data Center Starts with Power Monitoring
Energy Savings in the Data Center Starts with Power Monitoring As global competition intensifies, companies are increasingly turning to technology to help turn mountains of data into a competitive edge.
5 Reasons. Environment Sensors are used in all Modern Data Centers
5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center
Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability
Considerations for a Highly Available Intelligent Rack Power Distribution Unit A White Paper on Availability Introduction Data centers are currently undergoing a period of great change. Data center managers
Energy Management Solutions
Energy Management Solutions Introducing the world s most innovative intelligent Power Distribution Units (ipdus) designed to simplify rack energy and environmental management of your data center. Enlogic
Server Technology Inc.
Server Technology Inc. Efficiency Gains with 480V/277V Power at the Cabinet Level White Paper STI-100-012 2011-May-2 Headquarters Server Technology, Inc. 1040 Sandhill Drive Reno, NV 89521 United States
Measuring Power in your Data Center
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There
Server Technology, Inc.
Server Technology, Inc. Cabinet Power Monitoring, Management & Control Within the Data Center White Paper STI-100-011 2010-Sept-27 by Calvin Nicholson, Senior Director Software and Strategic Alliances,
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture By Neil Rasmussen White Paper #129 Executive Summary Significant improvements in efficiency, power density, power monitoring,
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more
Data Centre Infrastructure Assessment
Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.
SmartDesign Intelligent, Integrated Infrastructure For The Data Center. Solutions For Business-Critical Continuity
SmartDesign Intelligent, Integrated Infrastructure For The Data Center Solutions For Business-Critical Continuity Prepare Your Data Center For What s Next Efficiency. Availability. Capacity. Control. One
Power & Environmental Monitoring
Data Centre Monitoring Made Easy Power & Environmental Monitoring Features & Benefits Packet Power provides the easiest, most cost effective way to capture detailed power and temperature information for
Server Technology Inc.
Server Technology Inc. Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 2013-April-18 By Steve Hammond, Product Manager, Server Technology Headquarters Server Technology,
Improve competiveness of IDC and enterprise data centers with DCIM
Improve competiveness of IDC and enterprise data centers with DCIM This paper studies the implementation of modern DCIM systems for data centers to improve operational competitiveness with ATEN's DCIM
Preparing for Your First DCIM System Deployment: Auto-Discovery and Data Collection
Table of Contents What is Auto-Discovery? Where is My Data and How Can I Get It? Why Auto-Discovery is Not Enough Where to Go to Start Collecting Your Data What Does an Operational DCIM System Provide?
Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers
Data Center Power Overload Protection: Circuit breakers and branch circuit protection for data centers 2009, Raritan Inc. Introduction Over the past few years, average power consumption per server has
Alternative data center power
Alternative data center power A quantitative TCO comparison of 400V AC and 600V AC power systems Abstract Power efficiency has become a critical focus for IT and facilities managers as they struggle to
DCIM Software and IT Service Management - Perfect Together
DCIM Software and IT Service Management - Perfect Together A White Paper from Raritan 2014 Raritan Inc Overview Information Technology is so fundamental to every business today that every organization
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture White Paper 129 Revision 1 by Neil Rasmussen > Executive summary Significant improvements in efficiency, power density,
Intelligent Power Distribution in the Data Center
Rack Power Intelligent Power Distribution in the Data Center Agenda Data Centre Power UPS Power Distribution Rack Mount PDU s UPS Power problems Configuration Capacity Power Distribution Types of Distribution
Revolutionizing Data Center Infrastructure Management
Infrastructure Management & Monitoring for Business-Critical Continuity TM Revolutionizing Data Center Infrastructure Management The Trellis Platform A Real-Time Solution to Continuous Performance Improvement
How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring
How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring Brian Rehnke e-pdu Business Development Manager November, 2011 The Problems Energy Usage in most data centers
High-Efficiency AC Power Distribution for Data Centers
High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies
Data Center Power Distribution at the Cabinet Level: The top 12 questions you need to ask to improve data center energy effciency
Data Center Power Distribution at the Cabinet Level: The top 12 questions you need to ask to improve data center energy effciency White Paper STI-100-010 November 2013 HEADQUARTERS - NORTH AMERICA Server
Power to the adaptable data center
Business Unit Manager, Data Center Solutions, Eaton s electrical group IT managers have more options than ever to tailor the power infrastructure to their unique data center and business requirements.
Comprehensive Data Center Energy Management Solutions
FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara framework to provide full convergence of
Is an energy-wasting data center draining your bottom line?
Abstract Is an energy-wasting data center draining your bottom line? New technology options and power distribution strategies can dramatically reduce the cost and carbon footprint of your data center.
(Examples of various colocation sites)
Overview The largest factor involved in maintaining business servers today are the fixed costs associated with data centers. The Colocation Environment is an outsourcing model whereby a colocation company
Three-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
Comprehensive Data Center Energy Management Solutions
FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara Framework to provide full convergence of
Packet Power. Data Center Solutions. Packet Power for Data Centers. Benefits. Features. The Packet Power Solution. Data Center Monitoring Made Easy
Data Center Solutions Packet Power for Data Centers Packet Power provides the easiest, most cost-effective way to capture detailed power and temperature information for both single-site and large multi-facility
PX Intelligent Rack PDUs
PX Intelligent Rack PDUs Rack Power Distribution Units for Your Data Center Raritan s PX intelligent rack PDU series offers more than just power distribution -- it s a launch pad for real-time remote power
CenterMind P+ Intelligent Power Management for your Data Center
CenterMind P+ Intelligent Power Management for your Data Center Intelligent Power Management for your Data Center monitor and manage your data center power consumption and connectivity efficiently The
Alternating Phase Power Distribution at the Data Center Rack PDU
Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 November 2013 - Updated August 2014 By Steve Hammond, Product Manager, Server Technology Marc Cram, Director of
Server Room Solutions: How small to midsize IT businesses can make their IT budgets appear larger than they are
Server Room Solutions: How small to midsize IT businesses can make their IT budgets appear larger than they are 2011, Raritan Inc. Server Room Solutions: How small to midsize IT businesses can make their
Australian Government Data Centre Strategy 2010-2025
Australian Government Data Centre Strategy 2010-2025 Better Practice Guide: Data Centre Power June 2013 17/06/2013 4:12 PM 17/06/2013 4:12 PM Contents Contents 2 1. Introduction 3 Scope 3 Policy Framework
Data Center Infrastructure Management: How to Optimize Data Center Operations
Data Center Infrastructure Management: How to Optimize Data Center Operations Khaled Nassoura, PE [email protected] General Manager Raritan, Inc. Question of the Day Question: Would any CFO run
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
8 Intelligent PDUs. Intelligent Power Distribution Units for Data Centers
BRC_PDU_US_B_BRC_IcePack 4/30/13 11:31 AM Page 2 8 Intelligent PDUs Intelligent Power Distribution Units for Data Centers Intelligent Power Distribution Units Siemon s line of intelligent PDUs provide
Types of Electrical Meters in Data Centers
Types of Electrical Meters in Data Centers White Paper 172 Revision 1 by David Kidd and Wendy Torell > Executive summary There are several different types of meters that can be designed into a data center,
Data Centre Solutions... energy efficient by design. APC by Schneider Electric Elite Data Centre Partner. APC s leading Elite Data Centre Solutions
Data Centre Solutions... energy efficient by design APC by Schneider Electric Elite Data Centre Partner APC s leading Elite Data Centre Solutions Partner providing customers with expert advice, integration
Panduit Infrastructure Management Software for Data Centers and Enterprises
Panduit Infrastructure Management Software for Data Centers and Enterprises SmartZone Rack Energy Kits Energy and Environmental Monitoring for Small Data Centers SmartZone Rack Energy Kits Features: Simple
Foreseer Services. Product application guide. Table of contents
Product application guide Foreseer Services Table of contents 1.0 General.......................................... 2 1.1 What are Foreseer Software and Engineering Services.... 3 1.1.1 Foreseer Service
AUTOMSOFT and POWER ANALYTICS - Data Center White Space Management Realized
Executive Summary Power Analytics has been a leading edge provider of analytical software for the Data Center market and related industries for over six years. In that time, Power Analytics has been involved
Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications
W H I T E P A P E R Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications Executive Summary One of the fundamental decisions in the design of data centers, server rooms
Sensor Monitoring and Remote Technologies 9 Voyager St, Linbro Park, Johannesburg Tel: +27 11 608 4270 ; www.batessecuredata.co.
Sensor Monitoring and Remote Technologies 9 Voyager St, Linbro Park, Johannesburg Tel: +27 11 608 4270 ; www.batessecuredata.co.za 1 Environment Monitoring in computer rooms, data centres and other facilities
Scalable. Affordable. Flexible. Fast.
Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations
Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM
Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity
Packet Power. Data Center Solutions. Packet Power. Packet Power for Data Centers. Benefits. Features. The Packet Power Solution
Data Center Solutions for Data Centers provides the easiest, most cost-effective way to capture detailed power and temperature information for both single-site and large multi-facility operations. Gain
Understanding the Promise of (DCIM)
Understanding the Promise of Data Center Infrastructure Management (DCIM) Chuck Kramer, RCDD, NTS, CDCP, CDFOM Senior Solutions Consultant Emerson Network Power What is DCIM? The monitoring, collection
CenterMind P+ Solution for efficient power management
CenterMind P+ Solution for efficient power management Overview Over last decade DC become significant power consuming facilities Information Technology Equipment (ITE) continue to increase computing capabilities
MAXIMIZING YOUR DATA CENTER INFRASTRUCTURE: CENTRALIZED MANAGEMENT AND WIRE-FREE ENVIRONMENTAL MONITORING
MAXIMIZING YOUR DATA CENTER INFRASTRUCTURE: CENTRALIZED MANAGEMENT AND WIRE-FREE Chris C. Gaskins Vice President of Product Development RF Code, Inc. AUGUST 2010 Shawn Griggs Director of Product Management
Evaluating the Opportunity for DC Power in the Data Center
A White Paper from the Experts in Business-Critical Continuity Evaluating the Opportunity for Power in the Data Center by Mark Murrill and B.J. Sonnenberg, Emerson Network Power Summary With data center
Top 8. Considerations for Choosing the Right Rack Power Distribution Unit to Fit Your Needs
Power design in data centers is getting substantial attention particularly by facilities and engineering personnel as organizations pursue constant improvements in reliability and energy efficiency. At
Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring
Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring A White Paper from the Experts in Business-Critical Continuity Summary The first decade of the 21st century
Improving Data Centers Energy Reliability & Efficiency. December 2015
Improving Data Centers Energy Reliability & Efficiency December 2015 Background The challenges Alternative solutions SATEC approach Advantages Cases Summary Data Centers Energy Challenges Worldwide Data
Increasing safety, reliability and efficiency for today s data centers
Increasing safety, reliability and efficiency for today s data centers Products and expertise for data center success Drawing upon vast experience in complex industries where uptime is critical, ABB provides
Five Essential Components for Highly Reliable Data Centers
GE Intelligent Platforms Five Essential Components for Highly Reliable Data Centers Ensuring continuous operations with an integrated, holistic technology strategy that provides high availability, increased
Emerson Network Power Rack PDU Solutions Rack Power Distribution For Critical IT Equipment. AC Power For Business-Critical Continuity
Emerson Network Power Rack PDU Solutions Rack Power Distribution For Critical IT Equipment AC Power For Business-Critical Continuity Enhanced Performance And Management Of Dynamic IT Spaces IT space is
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
Microsoft Technology Center: Philadelphia
A Customer Success from the Experts in Business-Critical Continuity TM. Background Microsoft Technology Center: Philadelphia Microsoft Technology Centers are collaborative, state-of-the-art facilities
QuickSpecs. Overview. HP Power Distribution Rack. HP Power Distribution Rack. DA - 12859 North America Version 5 August 22, 2008 Page 1
Overview It's getting harder to manage a data center efficiently, with rising utility bills and ever-increasing demands due to processor power and server density increases. Growing user requests mean heavier
The Avocent Data Center Planner Real-World Insight for Smarter Data Center Management
Infrastructure Management & Monitoring for Business-Critical Continuity TM The Avocent Data Center Planner Real-World Insight for Smarter Data Center Management EXECUTION AVAILABILITY EFFICIENCY What s
Reducing Data Center Loads for a Large-Scale, Net Zero Office Building
rsed Energy Efficiency & Renewable Energy FEDERAL ENERGY MANAGEMENT PROGRAM Reducing Data Center Loads for a Large-Scale, Net Zero Office Building Energy Efficiency & Renewable Energy Executive summary
DCIM Software and IT Service Management - Perfect Together DCIM: The Physical Heart of ITSM
1 Overview Information Technology is so fundamental to every business today that every organization needs to establish formal processes to ensure that IT services are continually aligned to the business,
Case Study Nottingham Trent University
Data Centre Solutions...energy efficient by design Case Study Nottingham Trent University Nottingham Trent University deploys Modular Data Centre Technology (MDC) Designed & Manufactured by Workspace Technology
Model #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V
SmartPro VS Tower UPS System Intelligent, line-interactive power management system Model #: SMART2200VS 2200VA / 2.2kVA line interactive tower UPS Maintains 120V nominal output over an input range of 79
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of