TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012
|
|
|
- Sharon Simmons
- 9 years ago
- Views:
Transcription
1 TIA 569 Standards Update Pathways & Spaces Ignacio Diaz, RCDD April 25, 2012
2 The purpose of this Standard is to standardize specific pathway and space design and construction practices in support of telecommunications media and equipment within buildings. Scope limited to telecommunications aspect of building design but influences design of other building services (i.e. HVAC, electrical power, etc) Define requirements for key spaces Building Spaces Access & Service Provider Spaces Multi tenant Building Spaces Building Pathways Cabling distribution should try to find a solution that will: Cabling distribution should try to find a solution that will: Accommodate cabling changes Minimize occupant disruption when horizontal pathways are accessed Allow for future growth
3 A standard established for rooms, pathways, and areas into and through which structured cabling, components, and equipment are installed. Appliesto: Conduits Under floor ducts and Floor Boxes Access floor (Raised Floors) Ceiling pathways (J Hooks & Rings) Cable tray systems Perimeter pathways Raceways Telecommunications Closet & Equipment Room Sizes & Provisions
4 Building Spaces: General Requirements General Requirements apply to Distributor Room Common Distributor Room Entrance Room Access Provider Space Service Provider Space Temperature & humidity guidelines per ASHRAE Thermal Guidelines for Data Processing Environments Temperature & humidity in telecommunications i space shall hllmeet requirements for ASHRAE Class 3 UPS larger than 100kVA located in separate room Bonding & grounding system shall be provided per ANSI/TIA 607 B
5 Building Spaces: General Requirements Plywood backboard ¾ in plywood (at least one wall) Painted with two coats fire retardant paint No longer required to be painted white Ceilings Ceiling height min, 8 ft clear space (10ft between finished floor and lowest point of ceiling) Recommend for max flexibility not to use suspended ceiling Floor loading Static & dynamic capacity shall be sufficient to bear both distributed & concentrated loads Shall consult structural engineer Lighting Min 500 lux in horizontal plane Min 200 lux in vertical plane Measured 1 m (3 ft) above finished floor Powered separately from telecommunications equipment Should not use dimmer switches Doors Minimum of 36 x 80 (optional 72 x 90 )
6 Building Spaces: Distributor Room Common access for cabling subsystems & building pathways Contains telecommunications equipment, cable terminations, & cross connect In a commercial building it is called an equipment room or telecommunications room depending on what isin in it Should follow general guidelines Multiple distributor rooms on same floor interconnected by minimum of one metric designator 78 (trade size 3) conduit or equivalent pathway
7 Building Spaces: Distributor Room Distributor B (i.e. intermediate cross connect (IC) in commercial building) min. of 10 m 2 (100 ft 2 ) Distributor C (i.e. MC in commercial building) min. 12 m 2 (120 ft 2 ) for building with gross area up to 50,000 m 2 (500,000 ft 2 ) Increase 1 m 2 (10 ft 2 ) per 10, m 2 (100, ft 2 ) increase in building size Minimum 1 distributor room per floor Minimum two dedicated 120 VAC /20A outlets 6 ft spacing; 6 in above floor
8 Building Spaces: Entrance Room / Space Entrance Room /Space Entrance for outside plant & pathways shall meet requirements of ANSI/TIA 758 B (Outside Plant ) standard In buildings up to 10,000 sq m (100,000 sq ft), wall mounting terminating hardware may be suitable Minimum of two dedicated 120 VAC /20 A outlets Distributor Enclosure Centrally located Lighting, measured in distributor enclosure, minimum 500 lux Minimum of one dedicated 120 VAC /20 A outlet
9 Access & Service Provider Spaces Used for the location of transmission, reception, and support equipment Minimum Access & Service Provider Space :1.5 m x 2 m (4ft x 6 ft) Should be close to Distributor C (i.e. MC) At least one dedicated 120 VAC/20 A, non switched duplex electrical receptacle for equipment
10 TIA 569 Pathways & Spaces Standard Building Spaces: Racks & Cabinets Minimum 3 ft front clearance; 4 ft is preferable Minimum Minimum 2 ft rear clearance; 3 ft is preferable 2 ft rear clearance; 3 ft is preferable Equipment may require additional clearance Suggest using cabinets 6 in deeper or wider than l largest equipment i Should have adjustable mounting rails Rails should have markings Rails should have markings
11 TIA 569 Pathways & Spaces Standard Building Spaces: Racks & Cabinets Cabinets shall be selected & configured to provide adequate cooling (some suggestions listed below) Forced airflow using fans g Natural airflow between hot & cold aisles Hot aisle/cold aisle cabinet arrangement Use of blanking panels and baffles Sealing air leaks around cable ingress points Sealing air leaks around cable ingress points Vertical cable manager shall be installed between racks and at both ends of every row (at least 3.25 in wide) Horizontal management sufficient to provide strategic growth of up to 100% but not impair cooling
12 Building Pathways Consider quantity, size & bend radius requirements of cable when determining size of pathway Allow for growth Not tlocated din elevator shafts hft Areas above ceilings may be used as pathway for telecommunications cables & for connecting hardware Co installation of telecommunications cable & typical branch circuit (120/240 VAC/ 20A) must meet requirements of NFPA 70
13 Building Pathways Zero pathway separation permitted when telecommunications cables & power cables both enclosed in metallic pathways (min wall thickness of 1 mm (0,04 in) of steel or 1.5 mm (0,06 in)aluminum) Provides table with guidelines for separation of telecommunications pathways for balanced twisted pair cabling from adjacent power wiring Balanced TP cabling separated from fluorescent lamps/fixtures by minimum of 125 mm (5 in)
14 Building Pathways Pathway separation from sources of electromagnetic energy: Condition <2KVA 2-5KVA >5KVA Unshielded Power Lines in proximity to open PVC Pathways 5 in 12 in 24 in Unshielded Power Lines in 12 in in proximity to Grounded in Metallic Pathways Power Lines enclosed in Metal Grounded Pathways <1 in 3 in 6 in in proximity to Grounded Metallic Pathways
15 Building Pathways Minimum 75 mm (3 in) clear vertical space available above ceiling tiles if using as pathway Min. 300 mm (12 in) clearance above cable tray system or runway Trays may be divided with barrier for physical separation between power & TP cable Non continuous supports located at intervals not to pp exceed 1.5 m (5 ft)
16 Building Pathways Cable Trays Planned for initial max calculated fill ratio of 25% Note: A calculated fill ratio of 50% for 4 pair & similar cable will physically fill entire tray due to spaces between cables Cable Runway Stacked no higher than 150 mm (6 in) Pathways free from burrs, sharp edges or projections Trays and wireways may be divided with a barrier to allow for physical separation of different types of services. If nonmetallic trays and wireways are located in the plenum, they shall be plenum rated.
17 Building Pathways Ceiling Pathway (J Hooks & Bridle Rings) Spacing 48 to 60 off center (eliminate copper degradation) Maximum of Q(75) 4Pair UTP Over Q(75) add another J Hook or migrate to Cable Tray
18 Building Pathways Conduit Sections between pull points shall not exceed 30 m (100 ft) in runs that total more than 30m (100 ), insert pull boxes so that no segment between pull points exceeds the 30m (100 ) limit. No section shall contain more than two 90 degree bends Conduits with internal diameter of 50 mm (2 in) or less, inside bend radius of a bend in conduit shall be at least 6 times the internal diameter Conduits with an internal diameter of more than 50 mm (2 in), the inside radius of a bend in conduit shall be at least 10 times the internal diameter. Bonded to ground, in accordance to national or local requirements Has reference table for pull box sizes Maximum fllf fill for furniture pathways is 40%
19 Building Pathways Conduit (RIGID, EMT, ENT, PVC, HDPE) Must be a minimum of 3/4 40% Fill Ratio (NEC) applies Fire Codes apply and must be respected regarding the use of polymers
20 Pull Boxes and Splices Pull Box Installation Locate pull boxes in easily accessible locations. Horizontal cable boxes should be installed above suspended ceilings. Should be used when installing a pull string or cable, fishing the conduit s run, and pulling and looping the cable in the next length of conduit. Pull boxes should be used when: Conduits runs are more than 30m (100 ) Contain more than two 90º bends. Pull P boxes shall not be used for splicing cable. Splice boxes Intended to be used for splicing in addition to pulling cable. A slip sleeve is a conduit sleeve that is larger than the main conduit, and slipped over an opening in a conduit run after the cable is in place. A gutter is a square, sheet-metal housing, which is placed over an opening in a conduit. Slip sleeves or gutters cannot be used for splices, but can be used in place of a pull box, are more economical to install, and will provide more space for pulling.
21 Other Pathway Types Power pole specifications Power poles standard sizes accommodate 3m (10 ), 3.7m (12 ), and 4.6m (15 ) ceiling heights. Power pole installation Mount rigidly between the ceiling support channel grid and carpeted or tiled floor. Utility columns may be attached to the cross rails only if the rails are securely anchored to the main ceiling support channel. Poke thru specification Poke thru distribution is usually implemented by installing cable from the ceiling of the floor below, to a point where service is desired on that same floor, then poking thru the floor to allow the cable to be attached to telecommunications device. Poke thru installation Poke thru installation should be done in accordance to all local and national codes, in strict accordance with the Underwriters Laboratories procedures found in the Fire Resistance Directory, and the poke thru addendum 4 to ANSI/TIA/EIA 569 A.
22 Building Pathways The NEC and local codes take precedence when installing conduit, choices in conduit type shall be ofthe type permitted under the appropriate electrical codes.
23 Backbone Backbone pathways consist of: Interbuilding backbone pathways which extend between buildings Intrabuilding backbone pathwayswhichwhich are contained within a building
24 Backbone Intrabuilding pathways consist of: Ceiling pathways Conduits Sleeves Slots Trays
25 Backbone Slots Sleeves Trays
26 Backbone Sleeves An opening, usually circular, through the wall, ceiling, or floor to allow the passage of cables and wires. Slots An opening through a wall, floor, or ceiling, usually rectangular, to allow the passage of cables and wires.
27 Firestopping
28 New Version! New revision work has been going on for past year Reference for all premise standards No longer specific to commercial buildings New revision ii just approved for publication as ANSI/TIA 569 C Other Changes include Removed 60% fill max limit for furniture pathways for growth; only recommends initially designing to 40% fill Power & noise separation apply to all applications; no new recommendations dti for 10Gb/s applications
29 Accommodating New ASHRAE Guidelines TIA 569 C draft was almost complete when ASHRAE changed guidelines Two phase approach to including changes 1. Added new class names editoriallyto TIA 569 C No change to requirements for TIA 569 C 2. Working on addendum to harmonize Will be TIA 569 C C.1 May be complete by end of year 29
30 ASHRAE changes to Thermal Guidelines for Data Processing Environments Class 1 & 2 now A1 & A2 Two new classes, A3 & A4 A1, A2, A3 & A4 have allowable & recommended ranges No change with A1 & A2 Expanded dallowable range for A3 & A4 Class 3 & 4 replaced by Class B & C with no changes 30
31 TIA 569 Pathways & Spaces Standard ASHRAE changes to Thermal Guidelines for Data Processing Environments
32 Other Standards and TIA 569 Because ANSI/TIA-569-C is now a generic reference for pathways, specific requirements unique to an application will be specified in the application standard. For example, specific pathway and spaces requirements for commercial buildings will be specified in ANSI/TIA-568-C.1. Specific pathway and spaces requirements for healthcare facilities will be specified in ANSI/TIA Let s take a look! 32
33 TIA 1179 Healthcare Facilities Standard Healthcare vs. Premises Broader scope of application specific IP devices Sensitive installation environment Larger pathways Larger Telecom Rooms Greater Workstation densities
34 TIA 1179 Healthcare Facilities Standard Unique Cabling Challenges Redundant and high density pathways (conduits, cable tray) High levels of EMI, high temperature, chemicals and gasses maybe present Cable selection dependent on attributes to comply with atmospheric conditions Cable selection affects pathways Application specific, high termination work area densities Stringent codes and regulations
35 TIA 1179 Healthcare Facilities Standard Pathway Guidelines Pth Pathways should not compromise operation of the facility Enclosed pathway systems in air handling spaces to meet Infection Control lrequirements (ICR) Segregation of cables for different networks & applications (due to safety ft protocols)
36 TIA 1179 Healthcare Facilities Standard Et Entrance Facilities (EF) &E Equipment tr Rooms (ER) Route diversity two separate pathways from the entrance facility to the equipment room Demarcationpoint of outside access providersmaybe determined by federal or local regulations. Accommodation of other systems may increase size (BAS, nurse call, security, CATV, biomedical systems) Twice the size of a data/telecommunications closet (allowing for future double growth rate)
37 TIA 1179 Healthcare Facilities Standard Telecommunications Rooms (TR) andtelecom Enclosures (TE) Non telecommunications services (i.e. gasses, fluids) not allowed Larger TR than office building 12m 2 (130 ft 2 ) or larger TE serves smaller floor area or where TR is not allowed (be aware of exposure of magnetic fields, radiation, chemicals, etc)
Standards. www.nordx.com 5 ANSI/TIA/EIA-569-A (CSA T530)
The primary focus of this standard is to provide design specifications and guidance for all building facilities relating to telecommunications cabling systems and components. This standard identifies and
Minimum Standards for Data/Voice Infrastructure in New Building Construction
UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall
Intelligent Cable Management Systems
Intelligent Cable Management Systems Bringing Practical Application Karen Pearson - Leviton Why Cable Management Matters Performance Cooling and air-handling Maintenance ANSI/TIA 569* Telecommunication
ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers
ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Jonathan Jew [email protected] J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center working group Co-chair BICSI data centers standards
ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers
ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers
Specifications for Communication Cabling Distribution Systems
Washington University in St. Louis Specifications for Communication Cabling Distribution Systems General Overview Listed below are the separate sub-systems of Washington University s structured cabling
DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
Building Telecommunications Infrastructure Requirements
Building Telecommunications Infrastructure Requirements This page identifies specific requirements for the design of telecommunications infrastructure for buildings at Clemson University. (Revised October,
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc [email protected]
Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc [email protected] J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME)
SPACE TYPE: AUTOMATED DATA PROCESSING CENTER (ADP) (MAINFRAME) Construction Criteria The unit costs for ADP Mainframe space types are based on the construction quality and design features in the following
The Telecommunications Closet and Building Services
APPENDIX G Telecommunications Building & Network Standards 1. Expectations...2 2. Definitions...2 3. Contractor Requirements...2 4. Design Elements...3 4.1. Spaces...3 4.1.1. Building Service Entrance...3
SECTION 25110 TELECOMMUNICATION ROOMS
PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication
Unified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
Telecommunications Systems Narrative Page 1 The Engineering Enterprise
I. TELECOMMUNICATIONS GENERAL REQUIREMENTS A. The project consists of a renovation to the historic Clinical Sciences building, originally built in 1933. The existing building has a total area of 105,000
UT Southwestern Medical Center Information Resources Cable Installation Standard
UT Southwestern Medical Center Information Resources Cable Installation Standard PART 1- GENERAL 1.01 SUMMARY A. Furnish and install wire, cable, devices, equipment, and accessories for a complete system
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011
TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS IT Services Infrastructure Services October 2011 Table of Contents 1 Introduction... 4 1.1 Planning and Design... 4 1.2.1 Roles and Responsibilities...
Telecommunications Infrastructure Standard for Data Centers. 802.3 Tutorial
Telecommunications Infrastructure Standard for Data Centers 802.3 Tutorial Prepared by: Jonathan Jew - J&M Consultants and Chris DiMinico - MC Communications - Co-chairs TR42.1.1 TR42: Data Center Standard
TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING
TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING October 1998 Table of Contents SECTION I: New Construction Programming 1.0 New Construction 1.1 Design Elements..................................
800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines
SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines This document contains critical information regarding the installation of a certified SYSTIMAX SCS that meets or exceeds performance
TIA-942 Data Centre Standards Overview WHITE PAPER
TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and
TIA-942: Data Center Standards
plantemoran.com TIA-942: Data Center Standards Sri Chalasani Merit 2010 Conference May 25, 2010 Objectives What are concerns in the data center? Data center standards & best Practices Data Center Definition
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
Washington University in St. Louis Building: Communication Specification: Research Voice/Network/Typical 1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
Cabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
Enclosure and Airflow Management Solution
Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...
Purpose of the ANSI/TIA/EIA-569-A Standard
For more information, see anixter.com/standards Purpose of the ANSI/TIA/EIA-569-A Standard As the complexity of voice and data telecommunications has increased, standards have been established to ensure
Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 [email protected] www.chatsworth.com All products
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Structured and Point to Point Network Cabling for Industrial Automation
Structured and Point to Point Network Cabling for Industrial Automation Introduction Industrial automation systems are undergoing dramatic transformations that require businesses to adopt new strategies
TCTC Cabling Specifications
TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,
Healthcare. Carol Everett Oliver, RCDD, ESS. Berk-Tek, a Nexans Company
Cabling for Healthcare Carol Everett Oliver, RCDD, ESS Marketing Analyst, Berk-Tek, a Nexans Company Healthcare Digital Movement 1970 s First computer usage for administration (billing, etc.) Early 90
Code Compliance for Spring Steel Fasteners Based on the 2005 NEC
Code Compliance for Spring Steel Fasteners Based on the 2005 NEC B-Line has recognized the need for a reference source, detailing the National Electrical Code requirements for Spring Steel Fasteners. The
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
Network Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12
SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications
ANSI/TIA/EIA - 568-A, Commercial Building Telecommunications Cabling Standard.
WIRING STANDARD INTRODUCTION This standard defines a telecommunications wiring system for North Dakota State Agencies, offices or buildings that will support a multi-product environment. The purpose of
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
ADC-APC Integrated Cisco Data Center Solutions
Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
University of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions
Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging
Data Center Cabling Design Trends
Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY
SPACE TYPE: LABORATORY (WET) FOR CHEMISTRY AND BIOLOGY Construction Criteria The unit costs for (Wet) space types are based on the construction quality and design features in the following table. This
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS A. SCOPE 1. This information is intended to assist contractors, installers and code officials in the proper design and installation of flexible
OCTOBER 2010. Layer Zero, the Infrastructure Layer, and High-Performance Data Centers
Layer Zero, the Infrastructure Layer, and The demands on data centers and networks today are growing dramatically, with no end in sight. Virtualization is increasing the load on servers. Connection speeds
Fibre Optic Wiring Guide for Multiple Dwelling Units (MDUs)
Fibre Optic Wiring Guide for Multiple Dwelling Units (MDUs) Greenfield/Brownfield Renovations Table of Contents Future-Proof your Building... 1 MTS Fibre Optics Installation Guidelines... 2 MTS Fibre Optics
Organizing and Managing Equipment Rooms
Organizing and Managing Equipment Rooms How you organize and maintain your equipment room can be just as important as maintaining the operating systems on the boxes themselves. Although many companies
1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.
Issued 2005/06/01 Section 16743 Data System Page 1 of 7 PART 1 GENERAL 1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications..2 Data system equipment
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Specifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
BICSI NxtGEN & Global Data Center Standards Update
BICSI NxtGEN & Global Data Center Standards Update Bob Faber, RCDD/NTS Siemon Global Accounts Manager Chair NEMA High Performance Wire & Cable Chair BICSI Standards Committee Vice Chair BICSI TI&M Committee
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
Session 14 Cable Support Systems
Session 14 Cable Support Systems Cable Support Systems in the IEC World A new IEC Standard, IEC61537 2001 has been developed If full details of the cabling layout are available then the likely cable load
ANSI/TIA/EIA-606. Administration Standard for the Telecommunications Infrastructure of Commercial Buildings
ANSI/TIA/EIA-606 Administration Standard for the Telecommunications Infrastructure of Commercial Buildings Distributed by NDS INFORMATION- TELECOM SYSTEM --------------------------------------------- Head
Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman
Standards and Guidelines for Telecommunications Wiring Design and Installation Montana State University-Bozeman This document defines the standards used for voice and data wiring in buildings used by MSU
TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities
1 TELUS Residential Service Conduit Requirements for Stand Alone Homes and Duplexes in Fibre Only Communities Beginning in January 2010 TELUS began designing new subdivisions within the Top 48 population
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
Errata NFPA 70. Proposed 2014 Edition
Errata NFPA 70 National Electrical Code (Report on Proposals) Reference: 12-109 (Log #1618) Panel Meeting Action Proposed 2014 Edition The National Electrical Code Technical Correlating Committee notes
PUBLIC RESTROOMS, DESIGN INTENT
PUBLIC RESTROOMS, DESIGN INTENT 1.01 STRUCTURAL A. Where feasible, metal stud partitions will be constructed on a 6 high concrete curb. 1.02 MECHANICAL A. Restrooms will have a minimum of 15 air changes
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding
AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding A Guide for California Developers of Com m ercial Property This guide consists of
Small Data / Telecommunications Room on Slab Floor
Small Data / Telecommunications Room on Slab Floor Small Data / Telecommunications Room on Slab Floor During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure
Great Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
InstaPATCH Cu Cabling Solutions for Data Centers
SYSTIMAX Solutions InstaPATCH Cu Cabling Solutions for Data Centers Design Guidelines August 2008 www.commscope.com Contents Overview 1 Instapatch Cu Solution Specification 2 Harness Assembly Design 3
Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD
Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,
Healthcare Infrastructure. Planning. Standards Compliance & Best Practices. J M t Jose Mozota National Sales Manager Legrand Data Communications
Healthcare Infrastructure J M t Jose Mozota National Sales Manager Legrand Data Communications Planning Standards Compliance & Best Practices Agenda Technology Challenges Regulations & Requirements Structured
What is a Datacenter?
What is a Datacenter? Telecom Room Primarily Cross Connect Equipment and switches. Computer room A room whose primary function is to house computer equipment. (Servers, Storage) 5 or less cabinets Small
with Component Rating A Simple Perspective
Cat-6A UTP and Shielded with Component Rating A Simple Perspective Asef Baddar RCDD, DCD Sr. Technical Manager Leviton Middle East Category Specifications Agenda Terminology International & North America
IT&T Infrastructure Standards
Technology Services IT&T Infrastructure Standards Version 1.5 17 th April 2015 Page 1 Table of contents 1 CHANGE HISTORY... 3 1.1 DOCUMENT HISTORY... 3 1.2 REVIEWERS... 3 1.3 APPROVALS... 3 2 INTRODUCTION...
Electrical Code (NEC) Snake Tray Cable Management Solutions
Cable Pathway Use and Selection and the National Electrical Code (NEC) By Eric J. Sadler, BSME MIT Snake Tray Cable Management Solutions References: All references to the NEC in this presentation are taken
Data Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS)
NUIG Campus Network - Structured Cabling System Standards Information s Solutions & Services (ISS) Revision date 28 th January 2014 The purpose of this document is to assist Building Refurbishment and
DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
3.0 DFCM REQUIREMENTS 3.6 ELECTRICAL. PART 2: Communications and Security Wiring Systems DFCM DESIGN MANUAL UNIVERSITY OF UTAH SUPPLEMENT
3.0 DFCM REQUIREMENTS 3.6 ELECTRICAL PART 2: Communications and Security Wiring Systems DFCM DESIGN MANUAL UNIVERSITY OF UTAH SUPPLEMENT November 1, 2013 The University of Utah FACILITIES MANAGEMENT FACILITIES
SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)
Cable Specification Category 5e CMP HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP) This cable specification complies with the electrical transmission
B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.
DIVISION 16 ELECTRICAL Section 16740 Telephone System PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
Structured Cabling Statement of Work
Structured Cabling Statement of Work Multiple Locations June 15, 2010 Page 1 A. GENERAL a. San Joaquin County (referred to as Owner ) is requesting proposals for a new structured cabling infrastructure
Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs
WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute
CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute Cable Tray Wiring Systems Have Many Cost Advantages Cost is usually a major consideration in the selection of a wiring system.
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The