2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
|
|
|
- Ethan Powell
- 10 years ago
- Views:
Transcription
1 2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring
2 State of Idaho Division of Building Safety Electrical Bureau General Circuitry NEC , and In addition to the branch circuits installed to supply general illumination and receptacle outlets in dwelling units, the following minimum requirements apply: Two (min) 20-amp circuits for kitchen countertop receptacles One 20-amp circuit for the laundry receptacles One 20-amp circuit for the bathroom receptacles One separate, individual branch circuit for central heating equipment (Electric furnaces may have more than one.) One 20-amp circuit dedicated to the garage NEC Receptacles installed in the kitchen to serve countertop surfaces shall be supplied by the two or more 20-amp circuits for the kitchen receptacles. NEC Requires that the general lighting circuit be provided at 3 volt amps per square foot (600 Square feet per circuit for a 15 amp circuit or 800 square feet for a 20 amp circuit). NEC All conductors of the same circuit, including grounding and bonding conductors shall be contained in the same raceway, cable, or trench. NEC All circuits and circuit modifications shall be legibly identified as to purpose or use on a directory located on the face or inside of the electrical panel doors. Fuse or Circuit Minimum Wire Size Breaker Size Copper Aluminum 15 amp 14 n/a 20 amp 12 n/a 30 amp amp amp 6 4 NEC The rating of the fuse or circuit breaker generally determines the minimum size of the circuit conductor, per the following table: NEC Receptacle outlets shall be of the grounding type, be effectively grounded, and have proper polarity. NEC Receptacles shall not be installed within or directly over a bathtub or shower stall. NEC All 125-volt, 15- and 20-ampere receptacles shall be listed tamper-resistant. NEC Generally, receptacle outlets in habitable rooms shall be installed so that no point measured horizontally along the floor line in any wall space is more than 6' from a receptacle outlet. You will need a receptacle within 6 of any door, fireplace, or similar break in the walk and then the next would need to be within 12 of the first. You may
3 measure around corners. A receptacle shall be installed in each wall space 2 feet or more in width. NEC At kitchen countertops, receptacle outlets shall be installed so that no point along the wall line is more than 24" measured horizontally from a receptacle outlet in that space. You will need to install the first receptacle within 2 of the edge of the counter or sink and then the next within 4 of the first. Receptacles installed within cabinets do not count as one of these required receptacles. NEC A receptacle outlet shall be installed at each counter space 12" or wider, and at each island counter or peninsular space 24" by 12" or larger. Countertop spaces separated by, range tops, sinks or refrigerators are separate spaces NEC Outdoor receptacles, accessible at grade level and no more than 6.5' above grade, shall be installed at the front and back of a dwelling. NEC Laundry Areas, at least one receptacle outlet shall be installed for the laundry. NEC Basements at least one receptacle outlet shall be installed in addition to any provided for the laundry equipment. NEC Garages, at least one receptacle per car space will be provided. NEC Hallways, 10 feet or longer shall have at least one receptacle outlet. NEC All branch circuits supplying 125-volt, 15 and 20 ampere outlets ( point of use) in dwelling unit bedrooms shall be protected by a listed arc-fault circuit interrupter combination type device. Generally, these are circuit breaker type devices and cannot be installed on multi-wire branch circuits. Ground-Fault Protection NEC At dwellings, ground-fault circuit-interrupter (GFCI) protection shall be provided for all receptacle outlets installed in bathrooms, garages, grade-level portions of accessory buildings, crawl spaces, unfinished basements, kitchen countertops, wet-bar sinks, laundry counters with sinks, boathouses and outdoors. NEC A hydro massage bathtub, (defined as a permanently installed bathtub with a re-circulating piping system, designed to discharge water upon each use, and its associated components) shall have its own circuit and have ground-fault circuit-interrupter protection. If there is an internal heater, it may require another GFCI protected circuit. NEC All 125 volt receptacles not exceeding 30 amperes installed within 5 feet of the inside walls of the hydro massage bathtub shall be GFCI protected. NEC All equipment associated with a hydro massage bathtub shall be accessible without damaging the building structure or finish. Wiring Methods NEC All electrical boxes shall be securely supported by the building structure. NEC When boxes are used as the sole support for a ceiling paddle fan, they shall be listed and labeled for such use.
4 NEC Type NM (nonmetallic) cable shall be secured at intervals not exceeding 4.5 and within 12" of each box, 8 of single plastic boxes. Flat cables shall not be stapled on edge. NEC The outer jacket of NM cable shall extend into the box a minimum of ¼ inch. NEC The minimum length of conductors, including grounding conductors, at all boxes shall be 6". At least 3", of every conductor, shall extend outside the box. NEC Where cables are installed through bored holes in joists, rafters, or wood framing members, the holes shall be bored so that the edge of the hole is not less than 1¼ inch from the nearest edge of the wood member. Where this distance cannot be maintained, or where screws or nails are likely to penetrate the cable, it shall be protected by a steel plate at least 1/16" thick and of appropriate length and width. NEC Type NM cable shall not be installed in spaces used for environmental air, however NM is permitted to pass through perpendicular to the long dimension of such spaces. NEC ; 314.4; All electrical equipment, metal boxes, cover plates, and plaster rings shall be grounded. All switches, including dimmer switches, shall be grounded. NEC & Unused openings in boxes shall be effectively closed. When openings in non-metallic boxes are broken out and not used, the entire box must be replaced. NEC Only one conductor shall be installed under a terminal screw. In boxes with more than one ground wire, the ground wires shall be spliced with a wire tail or pig tail attached to the grounding terminal screw of the device. NEC Splices shall be made with an approved splice cap or wire nut and shall be made in approved electrical boxes or enclosures. Wire splicing means for direct burial shall be identified for such use. NEC & In a completed installation, all outlet boxes shall have a cover, lampholder, canopy for a luminaire, or device with an appropriate cover plate. NEC Junction boxes shall be installed so that the wiring contained in them can be rendered accessible without removing any part of the building. NEC The volume of electrical boxes shall be sufficient for the number of Conductor Size 14 gauge 12 gauge For each separate insulated wire 2 in in3 All ground wires (combined) 2 in in3 For each device (switch/receptacle) 4 in3 4.4 in3 All internal cable clamps (combined) 2 in in3
5 Sample Calculation: Four 14/2 w/ground MNB cables 8 insulated wires 8x2 16 in3 All ground wires 1x2 2 in3 1 switch 1x4 4 in3 1 receptacle 1x4 4 in3 All clamps (combined) 1x2 2 in3 Total box volume required = 28 in3 conductors, devices, and cable clamps contained within the box. Nonmetallic boxes are marked with their cubic inch capacity. Use the following table to properly calculate box size: (Plastic boxes have the number of wires printed inside them) NEC (C) Luminaires (lighting fixtures) installed in clothes closets shall have the following minimum clearances from the defined storage area (see the definition below): 12" for surface incandescent fixtures 6" for recessed incandescent fixtures 6" for fluorescent fixtures NEC Storage space, as applied to an electrical installation in a closet, is the volume bounded by the sides and back closet walls and planes extending from the closet floor vertically to a height of 1.8 m [6 ft] or the highest clothes-hanging rod and parallel to the walls at a horizontal distance of 600 mm [24"] from the sides and back of the closet walls respectively, and continuing vertically to the closet ceiling parallel to the walls at a horizontal distance of 300 mm [12"] or the shelf width, whichever is greater. NEC (B) Incandescent Luminaires with open or partially enclosed lamps and pendant fixtures or lamp-holders are not permitted in clothes closets. NEC Recessed lighting fixtures installed in insulated ceilings or installed within 13 mm [1/2"] of combustible material shall be approved for insulation contact and labeled Type IC. NEC Metal Flex is not approved outdoors. Equipment Listing and Labeling Idaho Rules All electrical equipment, including Luminaires, devices, and appliances shall be LISTED AND LABELED by a nationally recognized testing laboratory (NRTL) as having been tested and found suitable for a specific purpose. Underwriters Laboratories (UL) and the Canadian Standards Association (CSA) are two of the recognized agencies. NEC All electrical equipment shall be installed and used in accordance with the listing requirements and manufacturer s instructions. Electrical Services Always consult your power supplier, for meter location and mounting height and acceptable wiring methods and raceways for underground service entrance Conductors.
6 NEC (B)(7) 120/240 volt single phase dwelling services and feeders rated 100 to 400 amps and carrying the entire load associated with the dwelling, may be fed with conductors rated at 83% of the electric service rating. NEC Conductors of dissimilar metals shall not be intermixed in a terminal or splicing device unless the device is listed for the purpose. Listed anti-oxidant compound shall be used on all aluminum conductor terminations; unless information from the device manufacturer specifically states that it is not required. NEC Portions of raceways and sleeves subject to different temperatures (where passing from the interior to the exterior of a building) shall be sealed with an approved material to prevent condensation from entering the service equipment. NEC Where exposed to weather, service entrance conductors shall be arranged so that water will not enter service raceway or equipment. NEC Where raceways containing ungrounded conductors No. 4 or larger enter a cabinet, box, or enclosure, the conductors shall be protected by a conduit bushing providing a smoothly rounded insulating surface. NEC The electrical service disconnecting means shall be installed at a readily accessible location either outside a building or structure or inside nearest the point of entrance of the service entrance conductors. NEC & Electrical panels shall be readily accessible and shall not be located in bathrooms or in the vicinity of easily ignitable materials such as clothes closets. NEC Sufficient working space shall be provided around electrical equipment. When the voltage to ground does not exceed 150 volts, the depth of that space in the direction of access to live parts, shall be a minimum of 3'. The minimum width of that space in front of electrical equipment shall be the width of the equipment or 30" whichever is greater. This workspace shall be clear and extend from the floor to a height of 6½ '. This space shall not be used for storage. NEC All workspaces shall be provided with illumination. Grounding: NEC A premises electrical service shall be connected to any available grounding electrodes as in to form the grounding electrode system NEC Grounding Electrodes, Metal underground water pipe with 10 feet or more in contact of the earth (including well casings), Metal building frame, concert encased electrode of 4 AWG copper conductor 20 feet long or 20 feet of ½ bare reinforcing bar within and near the bottom of a concrete footing, and 8 foot ground rods. An additional electrode must supplement the buried water pipe electrode.
7 NEC & The grounding electrode conductor shall be unspliced. The size is determined by the size of the service-entrance conductors, per the following chart: The conductor that is the sole connection to a rod, pipe or plate electrode is not required to Service Entrance Conductor Equivalent Size of Service Size of the Grounding Electrode Conductor Copper Aluminum Copper Aluminum 4 AWG AWG 2/ /0 or 3/0 4/0 or be larger than #6 copper or #4 copper to a ufer. NEC A main bonding jumper or the green bonding screw provided by the panel manufacturer shall be installed in the service panel to electrically bond the grounded service conductor and the equipment grounding conductors to the service enclosure. NEC The interior metal water piping and other metal piping that may become energized shall be bonded to the service equipment with a bonding jumper sized the same as the grounding electrode conductor. Underground Wiring NEC Direct buried cable or conduit or other raceways shall meet the following minimum cover requirements: Rigid or Intermediate Non-Metallic Raceway Direct Burial Cable Metal Conduit (PVC) 24" 6" 18" Residential branch circuits rated 20 amps or less at 120 volts or less and with GFCI protection at their source are allowed a minimum cover 12 NEC Underground service laterals shall have their location identified by a warning ribbon placed in the trench at least 12" above the underground installation. NEC Where subject to movement, direct buried cables or raceways shall be arranged to prevent damage to the enclosed conductors or connected equipment. NEC Conductors emerging from underground shall be installed in rigid metal conduit, intermediate metal conduit, or Schedule 80 rigid nonmetallic conduit to provide protection from physical damage. This protection shall extend from 18" below grade or the minimum cover distance to the point of termination above ground.
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
Residential Electrical Inspection. Checklist
443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us Residential Electrical Inspection (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5743 TTY: (651) 297-4198 Checklist Generally, Minnesota
Residential Electrical Inspection Checklist
Residential Electrical Inspection Checklist Based on the 2008 National Electrical Code Generally, Minnesota law requires all electrical work to be performed by licensed, bonded and insured electrical contractors
Residential Electrical Inspection. Checklist
Electrical Licensing and Inspection 443 Lafayette Road North St. Paul, Minnesota 55155-4342 www.doli.state.mn.us 651-284-5064 Fax: 651-284-5743 TTY: 651-297-4198 1-800-DIAL-DLI Residential Electrical Inspection
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical
ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers
ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers This handout is intended to be a general overview of residential electrical requirements as noted in the 2014 National Electrical
HomeOwner Wiring. Please remember you are required to contact your inspector for inspections
HomeOwner Wiring Please remember you are required to contact your inspector for inspections South Dakota Electrical Commission 308 S. Pierre St. Pierre, SD 57501 1-800-233-7765 or (605) 773-3573 www.electrical.sd.gov
GENERAL ELECTRICAL REQUIREMENTS
GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of
INSPECTION GUDELINES
GENERAL REQUIREMENTS Building permit and approved set of plans Building permit on the card is the same as on the route "If this is not the first inspection, read inspection records and notes on permit
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
GENERAL WIRING RULES FOR HOUSES
GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat
Electrical Code Regulation
Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county
BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/20/2009)
BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/20/2009) PERMIT SUBMITAL CHECKLIST: Signed and completed Building Permit application form. 2 Copies of plans showing proposed layout and
Questions and Answers for Heating and A/C Contractors
1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port
Significant Changes in the 2011 NEC Prepared by Bryan Holland City of North Port Code-Wide Code Change Section 90.5(C). Fine Print Notes are now referred to as "Informational Notes." The purpose, intent,
Entrances to and from Electrical Equipment Rooms
Electrical Code Requirements for Commercial and Residential Buildings Presented by Bob Nuzzi State Electrical Inspector Entrances to and from Electrical Equipment Rooms 2005 NEC Section 110.26(C)(2) Large
800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
Electrical Wiring Guide
Electrical Wiring Guide In order to wire your own home, you must comply with the requirements of the 2011 edition of the National Electrical Code (NEC). NEC code articles are indicated by brackets ([ ]),
NEC 2014 Code Changes
NEC 2014 Code Changes Articles 400-408.55 CHANGES FROM 2011 TO 2014 CODE ARE IN RED Chapter 4 Equipment for General Use ARTICLE 400 Flexible Cords and Cables 400.4 Types Flexible cords and flexible cables
BRANCH CIRCUIT AND FEEDER REQUIREMENTS
CHAPTER 36 BRANCH CIRCUIT AND FEEDER REQUIREMENTS SECTION E3601 GENERAL E3601.1 Scope. This chapter covers branch circuits and feeders and specifies the minimum required branch circuits, the allowable
Typical Finished Basement Details
Fauquier County, Virginia Typical Finished Basement Details Based on the 2012 International Residential Code Finished basements must be constructed in conformance with this document. For requirements,
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
Electrical Installations A homeowner guide to the Winnipeg Electrical By-law requirements for a Single Family Dwelling, Detached Garage or Shed.
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT Electrical Installations A homeowner guide to the Winnipeg Electrical By-law requirements for a Single Family Dwelling, Detached Garage or Shed. October 2015
Residential Electrical System Aging Research Project. Dave Dini Sr. Research Engineer Underwriters Laboratories
Residential Electrical System Aging Research Project Dave Dini Sr. Research Engineer Underwriters Laboratories Aging Residential Electrical Systems Research Project Sponsors Fire Protection Research Foundation
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
Typical Finished Basement Details
Fairfax County, Virginia Typical Finished Basement Details Based on the 2012 International Residential Code Finished basements must be constructed in conformance with this document. For requirements, details
Code Compliance for Spring Steel Fasteners Based on the 2005 NEC
Code Compliance for Spring Steel Fasteners Based on the 2005 NEC B-Line has recognized the need for a reference source, detailing the National Electrical Code requirements for Spring Steel Fasteners. The
PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION
PALM BEACH COUNTY AMENDMENTS TO THE NATIONAL ELECTRICAL CODE, 1999 EDITION CODING: Words underlined are additions to the 1999 NEC Words stricken are deletions to the 1999 NEC Adopted by Ordinance 99-73
MOBILE HOME SERVICE REQUIREMENTS GAS
ELECTRIC AND GAS 1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 GENERAL 4.0 REFERENCE MATERIAL 5.0 TYPICAL UNDERGROUND UTILITY LAYOUT 6.0 METER PAD DETAILS 7.0 GENERAL INSTALLATION PROCEDURES 8.0 PEDESTAL SPECIFICATIONS
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a
Homeowner Information Guide Electrical Safety. British Columbia Safety Authority
Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in
Residential Questions and Answers 2011
Residential Questions and Answers 2011 1. I have an above ground swimming pool 18 ft. by 4 ft. deep, with metal T bar and upper ring for supports, that is set on a plastic mat or tarp ( high grade material),
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
Electrical Contractors. and the. New Jersey. Rehabilitation Code
Electrical Contractors and the New Jersey Rehabilitation Code Alan Chech Electrical Seminars 609-890-7072 www.alanchech.com Information is based on the presently adopted electrical subcode NEC 2005. Current
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared
The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
ELECTRICAL INFORMATION
ELECTRICAL INFORMATION 2014 NEC Edition MONTANA DEPARTMENT OF LABOR AND INDUSTRY BUSINESS STANDARDS DIVISION BUILDING CODES BUREAU PO BOX 200517 HELENA, MONTANA 59620-0517 (406) 841-2040 -- General Information
ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS
Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document
Electrical Service Guidelines
Electrical Service Guidelines Middle Tennessee Electric Membership Corporation Revised: May 23, 2013 MTEMC's Electrical Guidelines TABLE OF CONTENTS Right-of-Way Clearance Guide 3 MTEMC Requirements 4
FINISHED BASEMENT SUBMITTAL GUIDE
FINISHED BASEMENT SUBMITTAL GUIDE The text and illustrations included in this submittal guide represent the opinions of the Manheim Township Code Compliance Department. This guide is for education and
METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
Grounding & Bonding Why it is done And How to Install Properly
Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.
Requirements for Electrical Installations
ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This
FINISHED BASEMENT REQUIREMENT GUIDE
Basement Guide www.douglas.co.us FINISHED BASEMENT REQUIREMENT GUIDE Current Codes: 2012 International Residential Code 2009 International Energy Conservation Code 2014 National Electrical Code 2012 I-Code
ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist
CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov
CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov Finishing a basement to make additional living space in a house is a popular construction project for many homeowners.
Please check with your local inspection authority for any additional requirements before installation.
Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
ADOPTION OF THE NATIONAL ELECTRICAL CODE, 2005
ADOPTION OF THE NATIONAL ELECTRICAL CODE, 2005 That a certain code, three (3) copies of which are now on file and have been on file for a period of not less than 21 days in the office of the Village Clerk
PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.
PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to August 1, 2013. It is intended for information and reference purposes only.
ELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
County of Riverside Building and Safety Department
County of Riverside Building and Safety Department Mike Lara Director Photovoltaic Permitting Guidelines The information provided in this document is general and is intended only as a guide. Each project
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT. YOU COULD PUT YOUR FAMILY AND WORLDLY POSSESSIONS IN DANGER!!!
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
Single Family Residential Basement Finish
How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete
MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850
Montgomery County Regulation on: ADOPTION OF THE 2008 NATIONAL ELECTRICAL CODE DEPARTMENT OF PERMITTING SERVICES Issued by County Executive Regulation # 15-09 Authority: Code Section 17-2 and 17-3 Supersedes:
Residential Wiring Guide 12th Edition
2015 Residential Wiring Guide 12th Edition This guide is designed to help you install residential wiring safely and in accordance to the standards set by the 12th edition of the Manitoba Electrical Code
The purpose of this document is to provide standards for persons requesting or subject to County building inspections.
STANDARD OPERATING PROCEDURE BUILDING & SITE DEVELOPMENT Number: 310.1 Approval: Yves Khawam Effective Date: December 27, 2006 Subject: Requirements for County building inspections Page 1 of 7 1.0 PURPOSE:
Residential Code Requirements
Residential Code Requirements 2013 Adopted Codes effective January 1 st, 2014 The code requirements in this document are excerpts only, not a comprehensive list of all requirements that may apply to your
2. What building projects are exempted? (permit not required)
BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and
www.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
How To Build A Basement House
Single Family Basement Finish Purpose of Guide The purpose of this guide is to assist you in the permit process for your project. This handout is intended as a basic plan submittal under the 2009 International
Building Condition Assessment Report
Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.
Chapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
REHABILITATION OF MOBILE HOMES R4 34 606
REHABILITATION OF MOBILE HOMES R4 34 606 PURPOSE The purpose of this program is to provide minimum safety standards for homes manufactured before the implementation of the HUD Manufactured Home Construction
Georgia Association of Home Inspectors
Georgia Association of Home Inspectors Standards of Practice for Framing Inspections OVERVIEW The purpose of the GAHI (Georgia Association of Home Inspectors) Standards of Practice for Framing Inspections
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the
CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements
16600 Underground Electrical Duct Bank This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications
How To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
Electrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords?
Electrical Safety Electricity can be a friend, but it can also hurt if you do not treat it with respect. Everyday someone loses his or her home or business due to an electrical fire. These tragedies are
REQUIREMENT 5. Light Switches, Electrical Outlets, Thermostats, and Other Environmental Controls in Accessible Locations
Chapter Five: REQUIREMENT 5 Light Switches, Electrical Outlets, Thermostats, and Other Environmental Controls in Accessible Locations 5...covered multifamily dwellings with a building entrance on an accessible
How To Plan Out An Array Of Solar Panels
CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013
Uniform Construction Code (UCC) Building Permit Application Package
Uniform Construction Code (UCC) Residential Building Permit Application Package Per the Uniform Construction Code (UCC) all structures must be built per the standards of the most currently adopted International
The replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
Minimum Standards for Data/Voice Infrastructure in New Building Construction
UNIVERSITY OF WATERLOO Minimum Standards for Data/Voice Infrastructure in New Building Construction 12/17/2012 Offices 1. Two Work Area Outlets (WAO) on opposite walls, each with 2 jacks 2. Each WAO shall
Mobile Home Pre-Inspection Checklist
Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING
State of Wisconsin DEPARTMENT OF SAFETY AND PROFESSIONAL SERVICES. Electrical &Lighting Program Fall 2015 Code Panel Questions
State of Wisconsin DEPARTMENT OF SAFETY AND PROFESSIONAL SERVICES Electrical &Lighting Program Fall 2015 Code Panel Questions 1. I have a question in regards to the location of a 112.5 KVA dry type transformer.
HV AC CODE CHECKLISTS
The following text is informational only and shall serve as an informational guide for HV AC contractors, journeymen, and apprentices working in the Heating, Ventilation, and Air Conditioning industry.
Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained
Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase
COMPREHENSIVE PROPERTY INSPECTIONS
COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes
CANTEX INC. 301 Commerce Ste 2700 Fort Worth, Texas 76102 817-215-7000 Fax: 817-215-7001 Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes YOUR FULL
Installation Instructions For Slider Casement Air Conditioners
Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT
BUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
BASIC NEC CODE RULES AND DESIGN PRACTICE
BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,
Construction Electrical Terminology. Electricians
Construction Electrical Terminology Electricians Acknowledgments Winnipeg Technical College and the Department of Labour and Immigration of Manitoba wish to express sincere appreciation to all contributors.
IRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
BUILDING SAFETY UNIT
POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential
HVAC Code Requirements
one and two family dwellings? Answer: SECTION 2001: GENERAL 2001.1 Air supply. Fuel-burning equipment shall be provided with a supply of air for fuel combustion, draft hood dilution and ventilation of