1 A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture By Neil Rasmussen White Paper #129
2 Executive Summary Significant improvements in efficiency, power density, power monitoring, and reconfigurability have been achieved in data center power distribution. The past techniques of massive transformer-based power distribution units feeding under-floor hardwired circuits via rigid or flexible conduit are shown to be obsolete. This paper explains some the newer approaches to power distribution including modular power distribution and overhead power busway, and shows their advantages when compared to the legacy approach. 2
3 Introduction Most existing data centers utilize the same power distribution architecture that was developed for data centers approximately 40 years ago. This system is illustrated in Figure 1. Figure 1 Wiring of a traditional data center power distribution system Power Distribution Unit Underfloor power conduits for branch circuits IT equipment cabinets In the traditional system, the main data center power is distributed to power distribution units (typically rated from 50KW to 500KW). The power distribution units may contain large power transformers to convert voltage or provide power conditioning. The power distribution units in turn distribute a quantity of branch circuits (typically rated from 1.5KW to 15KW) to the IT equipment. Each IT enclosure uses one or more branch circuits. The wiring to the IT enclosures is usually required to be in flexible or rigid conduit, typically located beneath the raised floor, as illustrated in Figure 2. 3
4 Figure 2 Underfloor power distribution in hard pipes Since the introduction of this system, there have been dramatic changes in how power is utilized in data centers that have challenged this architecture, specifically driven by increasing power density, the increasing number of separate IT devices within the data center, and the need to add and remove IT devices on a continuous basis. This paper explains why the evolution of the data center has made the historical power distribution architecture obsolete, and describes a more effective power distribution system that can be implemented today. The improved system allows IT racks and even whole PDUs to be installed or changed without any new wiring, distributes power overhead, supports racks up to 30kW with a single flexible power feed, improves electrical efficiency, reduces copper consumption, is instrumented for power at the branch circuit, and has a standard capacity management system. Background When the traditional power distribution system was created, data centers consisted of a small number of large IT devices that were rarely changed except during the scheduled downtime of a major IT upgrade. The low power density of these facilities required a low volume of underfloor air, and typically less than one branch circuit for every 3 square meters of computer room. The modern data center has different characteristics which have challenged the traditional power distribution architecture: Instead of a few large IT devices, data centers may contain thousands of plug-in devices with separate power cords, requiring many more power receptacles IT devices within a rack enclosure are changed often within the lifetime of the data center, changing the power requirements or receptacle requirements at a rack location 4
5 Due to changing power requirements, new power circuits must frequently be added to a live data center without disturbing nearby existing IT loads The per-rack power density has increased greatly, often requiring multiple branch circuits per cabinet The number of power feeds has clogged the underfloor air plenum with conduits, blocking the airflow and making changes very difficult The number of IT devices that may be connected to a branch circuit breaker is often much greater than one, making it difficult to size branch circuits or determine impending overload conditions Dual power path systems are commonly implemented, requiring assurance that no circuit is loaded above 50%, yet there is typically no mechanism to monitor or plan this Although these issues are widely recognized, and there are a variety of products available to solve these problems, most data centers built today still use traditional methods and the result is that even newly built data centers suffer from the following unfavorable conditions: Data center operators are forced to make circuit changes on energized wiring ( hot work ) Data center operators cannot tell what branch circuits are near overload, or what circuits might overload in case of the loss of a power path Underfloor cooling plenums are blocked with cables, preventing the high volume air required by modern IT equipment Data center operators discover that the PDU units are taking up a significant fraction of the floor space and the floor load weight capacity Large transformer based PDU units cannot be fully utilized because they run out of branch circuits Large transformer based PDU units generate waste heat that must be cooled, decreasing data center efficiency A few photographs of wiring conditions in actual operating data centers illustrate some of the above difficulties and are shown in Figure 3. 5
6 Figure 3 Wiring congestion in actual data centers The power distribution architecture described in the next section addresses all of the problems described above. An optimized power distribution system An ideal power distribution system would have the following attributes: New circuits can be added or changed on a live system safely No underfloor cables needed All circuits monitored for power All breaker status remotely monitored IT zones and associated power distribution can be deployed over time All power levels supported using only a single cable to the IT enclosure Receptacle types can be changed at the IT enclosure by IT personnel Capacity and redundancy are managed on every circuit No excess copper is installed that is not needed High efficiency Power distribution systems have been evolving in response to the needs of the modern data center, and various improvements have been introduced to the power distribution system over time, most notably: Branch circuit power metering Overhead cable tray with flexible power cords 6
7 Overhead fixed busway with removable power taps High power, pluggable rack power distribution units Transformerless Power Distribution Units Power capacity management software The power distribution system shown in Figure 4 includes all of these elements in an architecture that is ideally suited for the modern high density data center. Figure 4 Illustration of a modular power distribution system From UPS Main power busway spans IT rows 250kW pluggable busway power tap Suspended cable tray for branch circuits to IT enclosures Typical 3-phase receptacle Half-rack 250kW modular PDU IT equipment cabinets 7
8 Description of the system The distribution system has two steps. For larger data centers the main critical bus power from the UPS is distributed to IT rows using one or more overhead busways as shown at the top of Figure 4. The busways are installed up front and traverse the entire planned IT rack layout. When a group of racks is to be installed, a low-footprint modular PDU is installed at the same time and plugged into the overhead busway. The connection to the busway is also shown in Figure 4. Figure 5 Example of a 250kW modular PDU with small footprint. Shown with 24 branch circuit modules installed Branch circuits exit from top Energy and status display Lockable door One of 24 branch circuit modules Rolls into position Instead of traditional circuit breaker panels with raw wire terminations, the modular PDU has a backplane into which pre-terminated shock-safe circuit breaker modules are installed. This arrangement allows the face of the PDU to be much narrower, and eliminates on-site termination of wires. The modular PDU initially has no branch circuit modules installed. The power circuits from the modular PDU to the IT racks are flexible cable that are plugged into the front of the modular PDU on site to meet the requirements of each specific rack as needed. The branch circuit cables to the IT enclosures are preterminated with breaker modules that plug into the shock-safe backplane of the modular PDU. An example of a branch circuit module is shown in Figure 6. 8
9 Figure 6 Branch circuit module that plugs into the modular power distribution unit Connection to IT enclosure Shock-safe plug-in connector on back 3 phase circuit breaker Integral energy and status monitoring For equipment that requires a dedicated branch circuit, such as most blade servers, a single cable from the PDU carries one, two, or three branch circuits that plug directly into the blade server, with no additional rack PDU (i.e. power strip) required. For mixed equipment in the rack, an assortment of rack PDUs are available that provide various receptacle and current ratings and can be interchanged. A typical rack PDU is shown in Figure 7; the connector shown in this figure plugs into the mating connectors shown in the previous Figure 6. Figure 7 Example of a 12kW 3-phase rack outlet strip designed for vertical mounting in the rear of an IT enclosure In this system, a PDU for a new row of IT enclosures, along with all of the associated branch circuit wiring and rack outlet strips, can be installed in an hour, without any wire cutting or terminations. Small zones or very high density In some cases there may be one or more zones within a data center where only a small number of branch circuits is needed. This can occur when there is a cluster of very high density racks, or when a small group of racks is isolated by room shape or other constraints. In these situations the full 24-branch circuit capability of the standard modular distribution system is not needed. 9
10 In these cases, the architecture includes a smaller version of the modular power distribution unit that can directly mount into an IT rack, consuming zero floor footprint and supporting up to 6 branch circuits. This PDU includes all of the status and energy monitoring capability of the larger floor standing unit in a 5U rack mount version. Figure 8 A small modular PDU that mounts directly into an IT enclosure that can provide power to 6 IT enclosures (door closed and door open views) Smaller data centers The system in Figure 4 is optimized for larger data centers with a large number of rows of IT racks, which may be deployed over time. The overhead busway is much easier to install than high-power wiring and allows PDUs to be added or changed. For smaller data centers of 300kW or less, a simplified approach using the same components and same principles can be used. For smaller data centers when the number of PDUs is restricted to one or two, the flexibility of deploying PDUs in phases is often unnecessary, and it may be cost effective to directly wire the modular PDU (Figure 5) to the critical bus with traditional conduit and wire. In this case the overhead busway is omitted. For very small data centers or data centers with irregular floor layouts the small modular PDU described in the previous section and illustrated in Figure 8 above may be appropriate. A further simplification is also possible in smaller data centers, where the modular PDU may be directly integrated with the UPS system into a compact arrangement that can be located in the IT room and integrated into a IT enclosure lineup. In this case the main bus wiring is eliminated and the need for a separate power room is eliminated. This convenient and popular approach for data centers of 200kW or below is illustrated in Figure 9. 10
11 Figure 9 Modular power distribution unit integrated with a UPS for smaller data centers Modular 120kW UPS Modular UPS Battery System Modular Power Distribution Unit Retrofit / upgrade applications A large number of data center projects involve the upgrade of an existing data center, with common projects being the addition of capacity or installation of a high-density zone. The modular distribution system is particularly well suited to these types of retrofit projects, because installation is much less disruptive than installing a traditional PDU. There is a long list of challenges when installing a new traditional PDU in an existing data center, most of which are addressed by the design of the modular distribution system. As a data center evolves, modular PDUs can operate alongside existing traditional PDUs. In these retrofit applications where traditional PDUs are often placed based on historical constraints, the overhead busway component of the architecture is not used, and traditional pipe and wire is used to connect each PDU to the main bus. One of the most important and overlooked benefits of the modular PDUs in the upgrade of a traditional data center is the fact that the installation adds no additional underfloor airflow blockages since the cables are run in overhead cable tray. This is often crucial in existing data centers where the floors are not deep and underfloor airflow is already a limiting factor in the cooling performance and even in the overall electrical efficiency of the data center. Power and status monitoring In a data center power distribution system there can be hundreds of circuit breakers that can be overloaded. This optimized distribution system uses higher capacity rack power feeds and uses 20-40% fewer breakers than a typical system, but there are still many circuits, which exist at 4 levels: 11
12 UPS main bus PDU input Branch circuit Outlet In the modular power distribution system, there is built-in current and energy monitoring on every circuit at all levels of the hierarchy (outlet-level monitoring is optional in some configurations). In addition, the branch circuit breakers in the PDU are monitored for status. All of the monitoring communicates via SNMP open standards protocol. Capacity management software is used to monitor every circuit in the system and enforce safety margins, verify redundancy, and identify available capacity. Voltage configuration The architecture described in this paper is global and suitable for all data center operating voltages. However, in North America there are two operating voltage configuration options. The most electrically efficient IT operating voltage for North America is 415/240V AC 3-phase power. This is the same distribution system used in Europe and most of the world, but is not commonly used in North America. The second option in North America is to use the traditional 208/120V AC 3-phase power common in North American buildings. This option requires more copper and PDU units with large integral power transformers, and is less efficient and more costly. For data centers in North America, the 415/240V AC system has a number of important advantages, as explained in APC White Paper #128, Increasing Data Center Efficiency by Using Improved High-Density Power Distribution. It is the recommended voltage choice. However, the recommended power distribution system described in this paper can also be implemented in a traditional North American 208/120V AC voltage configuration. Comparison with the traditional power distribution system The power distribution system described has been developed to address the many significant shortcomings of the traditional approach. The advantages of the new system are summarized in Table 1. 12
13 Table 1 Comparison of traditional power distribution with modular power distribution (best performance highlighted in blue) Issue Traditional distribution Modular distribution Adding branch circuits Removing branch circuits Ability to remove or change a rack cabinet Simplified planning Reliability Minimal floor footprint Safety Airflow interference Simplified engineering Up-front cost Efficiency New conduits must be installed, breakers sized and installed, and wires pulled and terminated. If system is live, electrician may need to work on live exposed electrical wiring. If circuit has power monitoring, new sensors and/or programming is typically required If system is live, electrician may need to work on exposed electrical wiring. Conduit needs to be extracted from complex network of underfloor wiring. If circuit has power monitoring, programming may need to be changed Branch circuit may need to be mechanically and/or electrically disconnected from the rack Typically the number and location of PDUs must be established early in the design, often before the final power density is known. In a raised floor installation, special underfloor mounting supports must be engineered Many wiring terminations are made in the field, resulting in loose connections and other defects. Mistakes during hot work can dislodge wires and trip breakers, disrupting other IT loads Transformer-based PDUs consume approximately 2.5 m 2 for every 100kW of IT load, or approximately 7% of computer room space Adding, removing, inspecting, and handheld current monitoring of branch circuits exposes operator to live electrical wiring Masses of cabling entering PDU from underfloor cause interference with underfloor airflow. Floor openings for wire create large bypass air paths that reduce air conditioner efficiency and capacity Complex tradeoffs between row length, density, ampacity, and cost must be made in each installation in order to optimally locate the PDUs PDUs are typically installed up front. Installation labor is significant. Built-out cost is incurred in the initial build Higher losses due to longer cable lengths. In North America 208/120V AC nearly 10 times the amount of losses compared to 415/240V AC system Plug-in, pre-made branch circuits. Can be installed in an energized system without exposure to live electrical wiring. Power monitoring included in each branch circuit and automatically configures when plugged in Branch circuit is unplugged from PDU, and may be re-used in another location Branch circuit unplugs at the rack, rack can be rolled out The number and location of PDUs do not need to be established up front. PDUs can be added later without special preparation Wiring terminations are pre-made in a controlled factory environment, improving reliability. Risk of interfering with other circuits during adds and changes is eliminated Consumes approximately 0.7 m 2 for every 100kW of IT load, or approximately 2% of computer room space Shock-safe plug-in installation of branch circuits. No field wiring required No underfloor cabling. No floor air leakage caused by extra openings in the floor Select from standard reference designs to meet requirements. Many decisions can be deferred to later phases Most of the power distribution cost is incurred only when and if needed Shorter cable lengths results in slightly lower losses 13
14 Alternative power distribution approaches The power distribution architecture described in this paper is not the only approach to solving the problems of the traditional distribution system. There are two other variations that have been described in the literature and have been used in real data centers; they are busway to the rack, and DC power distribution. These two alternatives are briefly described and compared with the system described in this paper. Busway to the rack Until the architecture described in this paper was introduced in 2008, using overhead busway to the rack was the best alternative approach to delivering power to IT enclosures. In the busway to the rack system, the IT enclosures directly connect into the overhead busway via breaker boxes as shown in Figure 10. Figure 10 - Busway to the rack showing power taps attached to an overhead power bus Bus tap breaker box Overhead power bus Track IT enclosures The busway is pre-installed over all IT equipment rows. This solves a number of the problems with traditional distribution, making changes easier and removing underfloor cabling. Busway was the first alternative to traditional distribution that achieved a flexible, reconfigurable distribution system. While busway to the rack remains a viable alternative to traditional approaches, there are a number of practical disadvantages of busway to the rack that are overcome by the new modular PDU architecture described in this paper. Busway to the Rack is compared to modular distribution in Table 2. 14
15 Table 2 Comparison of busway to the rack with modular power distribution to IT enclosures (best performance highlighted in blue) Issue Busway to the rack Modular distribution Ability to handle mixed and changing power density Ability to handle specialized room layouts Safe & secure access to circuit breakers Minimal floor footprint Standardized global solution Energy monitoring of each rack branch circuit Simplified engineering Minimal copper use Standard length final distribution cable Can be used in situations where overhead mounting is impractical Minimal up-front cost Efficiency Busway must be sized in advance to the maximum density and capacity otherwise adding an additional busway in the future is disruptive and impractical Busway must be installed in advance over all expected enclosure locations Breakers are mounted on the overhead busway, requiring ladder access. This is not permitted due to local codes in many cases. Chain or other actuators may be required Zero floor footprint Regulations for busway vary geographically, requiring different physical configurations or current ratings or data communications in different locations Busway systems typically only monitor the total power in the bus using optional equipment, and rely on Rack PDUs to report individual rack power Complex tradeoffs between row length, density, busway ampacity, and cost must be made in each installation, even in different rows within the data center, in order to optimize the result and ensure the busway is not overloaded Busway copper must be oversized to maximum power density The busway is always the same distance from the IT enclosure so all cable drops are the same length, simplifying spares inventory Busway cannot be installed underfloor in many locations due to regulations Most of the busway cost is incurred in the initial build Busway sized in advance for maximum capacity (i.e. the greatest amount of copper) resulting in slightly lower losses. Efficiency payback over 50 years given high cost of copper Power density is adjustable to suit the current configuration by adding or swapping branch circuits. Easier to install additional PDUs for extra capacity Flexible cable easily adapts to room obstructions, specialized IT cabinets, and constrained IT equipment floor plans All branch protectors behind a lockable door in one easily accessible location Consumes approximately 0.7 sq M for every 100kW of IT load, or approximately 2% of computer room space Standard architecture meets all international regulations and has a global standard for monitoring PDU supports auto-discovery for new branch circuits installed and has a single communication port for all branch circuits Monitors power for each IT enclosure, even if the enclosure does not use a rack PDU, such as blade servers Select from standard reference designs to meet requirements. Many decisions can be deferred to later phases Branch circuit copper is only deployed when needed and at the capacity needed The distance from the PDU and the IT enclosure vary, requiring different length cables. Long cables can be cut and reterminated by the user, but this is less convenient Power distribution cable trays can be suspended from overhead, mounted to the tops of the IT racks, or installed underfloor Most of the power distribution cost is incurred only when and if needed Copper sized more closely to actual load resulting in slightly more losses 15
16 While busway to the rack is a dramatic improvement over the traditional approach, and the architecture of this paper uses busway to distribute bulk power in the data center, Table 2 shows that the modular power distribution system has some advantages over busway for the final distribution to the IT enclosure. Busway for the final distribution has the advantage of zero footprint, but the modular distribution system is more scalable and adaptable to changing density, is standardized globally, and requires less up front planning and engineering. In general, for distribution to the rack, busway is best suited for very large facilities with an open floor plan with a very well defined IT equipment layout. The modular distribution system has the greatest advantage when locations are not precisely defined in advance, the room is constrained in shape or has obstructions, or the power density is expected to vary significantly through the room. Either of these approaches is vastly superior to the traditional underfloor conduit system, and a summary of key factors to consider in the selection between the approaches is provided in Table 3. Table 3 Factors to consider when choosing between busway and modular distribution to the IT enclosure Factors suggesting busway to the rack No floor space, even 5% of the space or less, can be used by the power distribution system Busway to the rack may not be the preferred choice when: The locations of future IT enclosures are poorly defined The power densities of future zones are not well known in advance Overhead mounting is impractical due to ceiling construction or other constraints A global standard solution is required Factors suggesting modular distribution The IT enclosure layout is not well defined in advance The layout is not a simple rectangle with defined rows. The room will have zones of different density Modular distribution may not be the best choice when: No IT floor space, even 5% of the space or less, can be devoted to the power distribution system DC power distribution DC power distribution has been proposed as an alternative to AC power distribution for data centers. There are actually 4 different DC approaches that have been described in the literature, using different DC voltage levels and wiring diagrams. The primary reason cited for moving to DC is improved electrical efficiency. A number of studies have claimed substantial expected efficiency advantages for a DC power system, from 10% to 40%. However, these studies assume very low efficiency for AC power systems. Since these studies first came out, newer high efficiency AC power distribution architectures have become widely 16
17 available with demonstrated efficiencies comparable with the hypothetical efficiency of DC systems. A quantitative analysis comparing AC vs DC power efficiency can be found in The Green Grid White Paper #16, Quantitative Efficiency Analysis of Power Distribution Configurations for Data Centers and APC White Paper #127, A Quantitative Comparison of High-Efficiency AC vs DC Power Distribution for Data Centers. These papers show that the best AC power distribution systems are nearly as efficient as DC, removing a key incentive to change the industry. The most important problem with DC power distribution is the lack of availability of compatible IT devices. While some IT devices are available with a 48V DC input option, this is the least efficient DC distribution voltage and consumes large amounts of copper wiring. If DC were to ever become a standard distribution system for data centers, most of the same issues of circuit distribution and monitoring to the racks would remain. The fundamental approaches of busway and modular distribution could still be used, but new connector systems would need to be developed and the devices might need to become larger to comprehend the increased safety clearances required for high voltage DC. The cost of transitioning the industry to DC would be very large and the lack of any significant cost or efficiency gains has removed the incentive to make this change. Therefore the industry is expected to remain AC based, although DC will be used as a distribution system within proprietary IT equipment including blade server chassis or racks, and within containerized servers. Conclusion This paper has described the significant limitations of the traditional power distribution architecture with underfloor conduit. Two alternative power distribution systems have been described, busway to the rack and modular distribution, both of which are major improvements over the traditional approach in terms of scalability, efficiency, reconfigurability, manageability, and power density. The modular power distribution system is shown to be particularly advantageous in practical data centers where layout is not precisely defined in advance, in retrofit applications, and in cases where the room layout includes unusual shaped floor plan or obstructions. 17
18 About the author Neil Rasmussen is the Senior VP of Innovation for APC- the IT Business Unit of Schneider Electric. He establishes the technology direction for the world s largest R&D budget devoted to power, cooling, and rack infrastructure for critical networks. Neil is currently working to advance the science of high-efficiency, highdensity, scalable data center infrastructure solutions and is the principal architect of the APC InfraStruXure system. Prior to founding APC in 1981, Neil received his Bachelors and Masters degrees from MIT in electrical engineering where he did his thesis on the analysis of a 200MW power supply for a tokamak fusion reactor. From 1979 to 1981, he worked at MIT Lincoln Laboratories on flywheel energy storage systems and solar electric power systems. 18
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture
A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture White Paper 129 Revision 1 by Neil Rasmussen > Executive summary Significant improvements in efficiency, power density,
Comparing Data Center Power Distribution Architectures
Comparing Data Center Power Distribution Architectures White Paper 129 Revision 3 by Neil Rasmussen and Wendy Torell Executive summary Significant improvements in efficiency, power density, power monitoring,
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
Strategies for Deploying Blade Servers in Existing Data Centers
Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling
High-Efficiency AC Power Distribution for Data Centers
High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies
Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment
Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment By Neil Rasmussen White Paper #27 Revision 2 Executive Summary Decisions made regarding the distribution of 208V or 120V power
Re-examining the Suitability of the Raised Floor for Data Center Applications
Re-examining the Suitability of the Raised Floor for Data Center Applications By Neil Rasmussen White Paper #19 Revision 1 Executive Summary The circumstances that gave rise to the development and use
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure White Paper 37 Revision 7 by Neil Rasmussen > Executive summary The physical infrastructure of data centers and network rooms
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure
Avoiding Costs from Oversizing Data Center and Network Room Infrastructure White Paper 37 Revision 6 by Neil Rasmussen > Executive summary The physical and power infrastructure of data centers and network
Guidelines for Specification of Data Center Power Density
Guidelines for Specification of Data Center Power Density By Neil Rasmussen White Paper #120 Executive Summary Conventional methods for specifying data center density are ambiguous and misleading. Describing
Guidelines for Specification of Data Center Power Density
Guidelines for Specification of Data Center Power Density White Paper 120 Revision 1 by Neil Rasmussen > Executive summary Conventional methods for specifying data center density are ambiguous and misleading.
AC vs DC Power Distribution for Data Centers
AC vs DC Power Distribution for Data Centers By Neil Rasmussen White Paper #63 Revision 4 Executive Summary Various types of DC power distribution are examined as alternatives to AC distribution for data
Overload Protection in a Dual-Corded Data Center Environment
Overload Protection in a Dual-Corded Data Center Environment White Paper 206 Revision 0 by Neil Rasmussen Executive summary In a dual-corded environment, the loss of power on one path will cause the load
AC vs. DC Power Distribution for Data Centers
AC vs. DC Power Distribution for Data Centers White Paper 63 Revision 6 by Neil Rasmussen > Executive summary DC power distribution has been proposed as an alternative to AC power distribution in data
Power and Cooling Capacity Management for Data Centers
Power and Cooling Capacity for Data Centers By Neil Rasmussen White Paper #150 Executive Summary High density IT equipment stresses the power density capability of modern data centers. Installation and
How To Calculate Total Cooling Requirements For Data Center
Calculating Total Cooling Requirements for Data Centers White Paper 25 Revision 3 by Neil Rasmussen > Executive summary This document describes how to estimate heat output from information technology (IT)
Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM
Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
Qualitative Analysis of Power Distribution Configurations for Data Centers
Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,
An Improved Architecture for High-Efficiency, High-Density Data Centers
An Improved Architecture for High-Efficiency, High-Density Data Centers By Neil Rasmussen White Paper #126 Executive Summary Data center power and cooling infrastructure worldwide wastes more than 60,000,000
How To Power A Bladecenter H Servers
Solutions Guide for IBM Data Center Architecture: IBM BladeCenter H Servers In today s high-demand enterprise environment, organizations need a reliable infrastructure to run compute-intensive applications
Improving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures
Electrical Efficiency Modeling of Data Centers
Electrical Efficiency Modeling of Data Centers By Neil Rasmussen White Paper 113 Executive Summary The conventional models used to estimate electrical efficiency of data centers are grossly inaccurate
Distributing Power to Blade Servers
Distributing Power to Blade Servers Ten steps to selecting the optimal power distribution design With the growth in blade servers with dual or triple power supplies, a single rack of equipment can easily
Improving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels White Paper 44 Revision 4 by Neil Rasmussen > Executive summary Unused vertical space in open frame racks and rack enclosures
Intelligent Power Distribution in the Data Center
Rack Power Intelligent Power Distribution in the Data Center Agenda Data Centre Power UPS Power Distribution Rack Mount PDU s UPS Power problems Configuration Capacity Power Distribution Types of Distribution
Electrical Efficiency Modeling for Data Centers
Electrical Efficiency Modeling for Data Centers By Neil Rasmussen White Paper #113 Revision 1 Executive Summary Conventional models for estimating electrical efficiency of data centers are grossly inaccurate
The Different Types of UPS Systems
White Paper 1 Revision 7 by Neil Rasmussen > Executive summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics. Each of these UPS types is
Calculating Space and Power Density Requirements for Data Centers
Calculating Space and Power Density Requirements for Data Centers White Paper 155 Revision 0 by Neil Rasmussen Executive summary The historic method of specifying data center power density using a single
Implementing Energy Efficient Data Centers
Implementing Energy Efficient Data Centers By Neil Rasmussen White Paper #114 Executive Summary Electricity usage costs have become an increasing fraction of the total cost of ownership (TCO) for data
The Different Types of UPS Systems
Systems White Paper 1 Revision 6 by Neil Rasmussen Contents Click on a section to jump to it > Executive summary There is much confusion in the marketplace about the different types of UPS systems and
Increase the efficiency of power distribution in your high-density data center
Increase the efficiency of power distribution in your high-density data center Abstract As power density in modern data centers increases, more focus has been placed on improving efficiency in the power
APC 3Phase Power Distribution
APC 3Phase Power Distribution North American 3 Phase Business Development Team All content in this presentation is protected 2008 American Power Conversion Corporation Objectives Understand the entire
The Different Types of UPS Systems
The Different Types of UPS Systems By Neil Rasmussen White Paper #1 Revision 5 Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics.
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Calculating Total Cooling Requirements for Data Centers
Calculating Total Cooling Requirements for Data Centers By Neil Rasmussen White Paper #25 Revision 2 Executive Summary This document describes how to estimate heat output from Information Technology equipment
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Raised Floors vs Hard Floors for Data Center Applications
Raised Floors vs Hard Floors for Data Center Applications White Paper 19 Revision 3 by Neil Rasmussen Executive summary Raised floors were once a standard feature of data centers, but over time a steadily
Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms
Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms By Neil Rasmussen White Paper #49 Executive Summary Avoidable mistakes that are routinely made when installing cooling
Specification of Modular Data Center Architecture
Specification of Modular Data Center Architecture White Paper 160 Revision 1 by Neil Rasmussen > Executive summary There is a growing consensus that conventional legacy data center design will be superseded
Rittal Liquid Cooling Series
Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de
LEVEL 3 DATA CENTER ASSESSMENT
Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments
Evaluating the Opportunity for DC Power in the Data Center
A White Paper from the Experts in Business-Critical Continuity Evaluating the Opportunity for Power in the Data Center by Mark Murrill and B.J. Sonnenberg, Emerson Network Power Summary With data center
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ
Power Distribution in Data Centers: STARLINE Track Busway, PX ipdus and Power IQ 2011 Raritan Inc. Overview Data center managers are faced with increasingly challenging demands: supplying additional computing
Power & Environmental Monitoring
Data Centre Monitoring Made Easy Power & Environmental Monitoring Features & Benefits Packet Power provides the easiest, most cost effective way to capture detailed power and temperature information for
Dynamic Power Variations in Data Centers and Network Rooms
Dynamic Power Variations in Data Centers and Network Rooms By Jim Spitaels White Paper #43 Revision 2 Executive Summary The power requirement required by data centers and network rooms varies on a minute
Creating Order from Chaos in Data Centers and Server Rooms
Creating from in Data Centers and Server Rooms By Dennis Bouley White Paper #119 Executive Summary Data center professionals can rid themselves of messy racks, sub-standard under floor air distribution,
Dynamic Power Variations in Data Centers and Network Rooms
Dynamic Power Variations in Data Centers and Network Rooms White Paper 43 Revision 3 by James Spitaels > Executive summary The power requirement required by data centers and network rooms varies on a minute
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
The Pros and Cons of Modular Systems
The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated
Data Center Trend: Distributed Power in the White Space
Data Center Trend: Distributed Power in the White Space By Jason Anderson Product Line Manager Eaton Executive summary Cloud computing vendors and colocation data centers make every effort to maximize
Creating Order from Chaos in Data Centers and Server Rooms
Creating from in Data Centers and Server Rooms White Paper 119 Revision 1 by Dennis Bouley > Executive summary Data center professionals can rid themselves of messy racks, sub-standard under floor air
> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.
The Role of Isolation Transformers in Data Center UPS Systems White Paper 98 Revision 0 by Neil Rasmussen > Executive summary Most modern UPS systems do not include the internal s that were present in
Essential Power System Requirements for Next Generation Data Centers
Essential Power System Requirements for Next Generation Data Centers White Paper #4 Revision 4 Executive Summary Effective mission critical installations must address the known problems and challenges
Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment
Alternative data center power
Alternative data center power A quantitative TCO comparison of 400V AC and 600V AC power systems Abstract Power efficiency has become a critical focus for IT and facilities managers as they struggle to
The Advantages of Row and Rack- Oriented Cooling Architectures for Data Centers
The Advantages of Row and Rack- Oriented Cooling Architectures for Data Centers By Kevin Dunlap Neil Rasmussen White Paper #130 Executive Summary Room cooling is an ineffective approach for next-generation
AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
Standardization and modularity as the foundation of data center UPS infrastructure
ABB White Paper Standardization and modularity as the foundation of data center UPS infrastructure - ABB Power Protection Product Group Doc name: Advantages of modular and standardized UPS Date: 19.11.2013
Power. When and where you need it.
Power Base Power. When and where you need it. Power Base is the only modular electrical system that delivers seamless plug-and-play power from the closet to the desktop. It s also the only system backed
Power to the adaptable data center
Business Unit Manager, Data Center Solutions, Eaton s electrical group IT managers have more options than ever to tailor the power infrastructure to their unique data center and business requirements.
Use of the Signal Reference Grid in Data Centers
Use of the Signal Reference Grid in Data Centers By Neil Rasmussen White Paper #87 Executive Summary Signal reference grids are automatically specified and installed in data centers despite the fact that
S c h n e i d e r E l e c t r i c BUSINESS IMPACT. Jack Hack Enterprise System Engineer 19 November 2015
S c h n e i d e r E l e c t r i c BUSINESS IMPACT Datacenter means business - create the bridge between IT en Facilities. Jack Hack Enterprise System Engineer 19 November 2015 1 Your ability to compete
(Examples of various colocation sites)
Overview The largest factor involved in maintaining business servers today are the fixed costs associated with data centers. The Colocation Environment is an outsourcing model whereby a colocation company
PX100 MBP with Configurable Distribution
PX100 MBP with Configurable Distribution High-performance, right-sized, 3-phase power protection with industry-leading efficiency, availability, and performance for small and medium data centers July 2012
Data Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert
Data Center Consolidation Trends & Solutions Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Agenda Traditional Data Centers Drivers of a Changing Environment Alternate
Mission Critical Data Center Systems
Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,
SMARTPLAY7. Increase your Deal Size and Profitability with SmartPlays
SMARTPLAY7 Increase your Deal Size and Profitability with SmartPlays - Comstor and Panduit have joined forces to promote the power and flexibility of UCS combined with market leading energy efficient enclosures.
Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions
Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging
Best Practices for Wire-free Environmental Monitoring in the Data Center
White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com [email protected] Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for
A Comparison of AC and DC Power Distribution in the Data Center Transcript
A Comparison of AC and DC Power Distribution in the Data Center Transcript Slide 1 Welcome to the Data Center University course on the A Comparison of AC and DC Power Distribution in the Data Center. Slide
Server Technology Inc.
Server Technology Inc. Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 2013-April-18 By Steve Hammond, Product Manager, Server Technology Headquarters Server Technology,
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Alternating Phase Power Distribution at the Data Center Rack PDU
Alternating Phase Power Distribution at the Data Center Rack PDU White Paper STI-100-012 November 2013 - Updated August 2014 By Steve Hammond, Product Manager, Server Technology Marc Cram, Director of
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE
RELIABLE AND FLEXIBLE POWER FOR YOUR DATA CENTRE Highly efficient solutions for power distribution, management and monitoring POWER DISTRIBUTION WIRE-FREE MONITORING LEAK DETECTION Daxten provides comprehensive
Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation
One Dell Way Round Rock, Texas 78682 www.dell.com Dell Enterprise White Paper Power Distribution Systems for the Dell PowerEdge M1000e Modular Server Enclosure - Selection and Installation January, 2008
Reducing Data Center Loads for a Large-Scale, Net Zero Office Building
rsed Energy Efficiency & Renewable Energy FEDERAL ENERGY MANAGEMENT PROGRAM Reducing Data Center Loads for a Large-Scale, Net Zero Office Building Energy Efficiency & Renewable Energy Executive summary
Three-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
Data Centre Infrastructure Assessment
Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions
AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 CABLING
Application Briefs: Remote Office Environment
Overview Remote offices are a definite sign of growth, but it can constitute an immense challenge from an IT infrastructure standpoint. Remote offices may include a wide variety of wiring closets and small
Calculating Total Power Requirements for Data Centers
Calculating Total Power Requirements for Data Centers By Richard Sawyer White Paper #3 Executive Summary Part of data center planning and design is to align the power and cooling requirements of the IT
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
InstaPATCH ZERO Solution Guide
SYSTIMAX Solutions InstaPATCH ZERO Solution Guide Rapid Server Deployment and Change Management North, South and Central Americas 1 As data centers face ever-increasing IT demands, growth demands and evolving
Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability
Considerations for a Highly Available Intelligent Rack Power Distribution Unit A White Paper on Availability Introduction Data centers are currently undergoing a period of great change. Data center managers
Rack Systems Solutions
Rack Systems Solutions Designed to simplify cable management and improve power distribution Engineered by APC by Schneider Electric for Dell, NetShelter S is the next-generation rack enclosure solution
Is an energy-wasting data center draining your bottom line?
Abstract Is an energy-wasting data center draining your bottom line? New technology options and power distribution strategies can dramatically reduce the cost and carbon footprint of your data center.
DATA CENTER RACK SYSTEMS: KEY CONSIDERATIONS IN TODAY S HIGH-DENSITY ENVIRONMENTS WHITEPAPER
DATA CENTER RACK SYSTEMS: KEY CONSIDERATIONS IN TODAY S HIGH-DENSITY ENVIRONMENTS WHITEPAPER EXECUTIVE SUMMARY Data center racks were once viewed as simple platforms in which to neatly stack equipment.