S&C Circuit-Switchers Mark VI



Similar documents
Specifications. Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply. SPECIAL TO THIS PRODUCT:

Specifications. S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Primary-Side Transformer Protection

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

CAPACITOR SWITCHING TRANSIENT MODELING AND ANALYSIS ON AN ELECTRICAL UTILITY DISTRIBUTION SYSTEM USING SIMULINK SOFTWARE

S&C BankGuard PLUS Control

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Secondary Unit Substations

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Schneider Electric Services: life-cycle solutions for electrical distribution equipment. Scopes of Work for Electrical Acceptance Testing

Hyperlinks are Inactive

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

Lightning Arresters P KVA P KVA. Description & Installation

Electrical Grounding. Appendix C

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

Joslyn Hi-Voltage Capacitor Switches

Unified requirements for systems with voltages above 1 kv up to 15 kv

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

SPECIFICATIONS. S&C Switch Operators Type PM SPECIFICATION BULLETIN For Field Retrofit on Manual PMH, PMS, and PME Pad-Mounted Gear

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Distribution Voltage Regulators

The following table shows approximate percentage wise the

S&C TripSaver Dropout Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

The Intelligent AX1 Switchgear for Medium Voltage

Industrial Automation Commonly-Used Terms

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

Residual Current Circuit Breaker

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX

Specifications. S&C Manual Vista Underground Distribution Switchgear Outdoor Distribution (15.5 kv through 38 kv)

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

Modular Systems wind portfolio overview Power Collection and Grid Connection products

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

Typical Data Requirements Data Required for Power System Evaluation

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

How To Build A Germany Power Plant

SECTION MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR

Step Voltage Regulators

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930

Product Guide. Low voltage grounding system. Answers for industry.

Arc Terminator Active Arc-Resistant Switchgear

Current Limiting Protector For Systems rated kV and continuous currents through 5000A.

Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.

Evaluating Fire- and Heat-Damaged Electrical Equipment

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Sample - No Commercial Use

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Primary and Secondary Electrical Distribution Systems

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

ASCO SERIES 185 Power Transfer Switches

Trip circuit supervision relay. Type RXTCS

Bypass transfer switch mechanisms

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

SECTION MEDIUM VOLTAGE SWITCHGEAR

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

Advantages of Fixed Circuit Breaker Switchgear

Power surges can also be generated by equipment in your facility such as:

RAILWAY CATENARY SYSTEMS. Components and Systems for the Electrification of Railway Lines. ibemo

Medium Voltage Motor Control Assemblies

Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy.

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

7. Reactive energy compensation

Customer Substation Manual 08/05/02

B. Related Sections: 1. Section Raceway and Boxes for Electrical Systems.

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

Permissible ambient temperature Operation Storage, transport

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance

Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power

Evaluating Water-Damaged Electrical Equipment

Medium Voltage Electrical Distribution

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

SPECIFICATION COG-2007

Switchgear Application Issues for Mission Critical Power Systems, Part One

CAPACITOR BANK TESTING SWP

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

Electrical Shore Connections / Cold Ironing

Diesel Engine Driven Generators Page 1 of 6

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Medium voltage indoor circuit breakers ANSI/IEC solutions

ELECTRICAL SAFETY RISK ASSESSMENT

Metal Enclosed Switchgears Metal Clad Switchgears Gas Insulated RMU's

Engineering innovation

Transcription:

S&C Circuit-Switchers Mark VI Outdoor Transmission (69 kv through 138 kv)

Mark VI Circuit-Switcher with Pre-insertion Inductors... the most reliable way to switch and protect substation capacitor banks Capacitor banks are a vital source of voltage support during peak periods, when the demand for electricity is high. Capacitor bank switching and protection requires a dependable switch one that s able to function reliably several times a day, year after year. Such a switch should require little maintenance beyond routine inspections. A capacitor switch must also be able to provide transient control to ensure high-quality power to customers. For many industrial customers, transient conditions at the substation capacitor-bank bus can cause nuisance tripping of adjustable-speed drives within their facility. Transient overvoltages can also cause wear on substation insulation, degrade control wiring, and cause extra operating duty for surge arresters. S&C s Mark V Circuit-Switcher has been the best choice for capacitor bank switching and protection... its robust design and repeatable, consistent performance has given it an industry-wide reputation for excellence. S&C has again advanced the state of circuitswitcher technology with the Mark VI Circuit- Switcher. Mark VI provides the same dependable performance you ve come to expect from S&C... but with added features and benefits to meet today s demanding system and operational requirements. Mark VI Circuit-Switcher Features: Higher-than-ever 31.5-kA fault-interrupting rating and 3-cycle interrupting time. Three-phase tripping by electrically linked interrupters provides tripping simultaneity of less than Z v cycle. Hermetically sealed interrupters eliminates the hassle of field-filling with SF 6 gas. Interrupters provide full dielectric ratings when open. Reliable performance Mark VI uses the same robust high-speed disconnect as Mark V Circuit- Switcher and the heavy-duty Mark VI CS-1A Switch Operator. 2

Mark VI Circuit-Switcher switch and protect single and back-to-back capacitor banks... locally The Mark VI Circuit-Switcher, with its 31.5-kA fault interrupting capability and 3-cycle interrupting time, can protect against faults on the capacitor bank bus, as well as bolted faults across a series group of capacitors. There is no need for a circuit breaker... either locally or downstream to interrupt fault current. Add S&C s pre-insertion inductors and the Mark VI Circuit-Switcher can switch, provide fault protection, and mitigate transient overvoltages... all with one device. Mark VI Circuit-Switcher for Single Shunt Capacitor Banks In single shunt capacitor-bank applications, like the one shown in Figure 1, Mark VI Circuit-Switcher offers an economical solution for switching and protection. Current transformers can be mounted directly on the Mark VI mounting pedestals. Add preinsertion inductors and Mark VI becomes an effective and economical means to combine switching, protection at full available fault current, and transient overvoltage control in one device. Mark VI Circuit-Switcher for Back-to- Back Shunt Capacitor Banks Mark VI Circuit-Switcher can also be used in backto-back applications on both banks, as shown in Figure 2. In the past, a device with higher protective interrupting capability might have been required for such applications: Figure 3 illustrates a circuit breaker applied upstream of the circuit-switchers to provide full-fault-current protection. With its 31.5 ka interrupting performance, Mark VI Circuit-Switcher allows a single type of device to switch and protect both banks eliminating the breaker. The Mark VI eliminates the timing and adjustment problems inherent to using controlled-closing circuit breakers for transient control, as well as the extra cost and maintenance associated with these special-purpose breakers. Adding pre-insertion inductors to the Mark VI Circuit-Switcher provides transient control without the need for a complicated operating scheme as is required for a controlled-closing breaker. C/S Circuit breaker C/S C/S C/S C/S Figure 1. Single shunt capacitor bank. Figure 2. Back-to-back shunt capacitor banks. Figure 3. Back-to-back shunt capacitor banks with upstream circuit breaker. 3

A Design Built on Tradition Enhanced by Innovation Mark VI Circuit-Switcher combines the robust vertical-break disconnect of the Mark V CircuitSwitcher with the innovative new interrupting technology of the Trans-Rupter II Transformer Protector providing 31.5-kA fault-interrupting ratings and increased installation flexibility. Integral Disconnect The integral disconnect is factory-assembled saving valuable installation time. The circuit-making and isolating disconnect, powered by the Mark VI CS-1A Switch Operator, is capable of opening and closing without hesitation under C v-inch ice formation. The disconnect features aluminum blades with silver-inlaid, hot-tin-dipped (except over silver inlay), high-conductivity cast-copper tongue contacts. The jaw contacts are of multi-finger, spring-loaded, silverinlaid, hard-drawn-copper reverse-loop construction to grip firmly against the tongue contact. The built-in blade-wiping action ensures a clean current-carrying surface and low-resistance current path all arcing Interrupter Quick connect control cable Disconnect blade assembly associated with switching is confined to the faultclosing contacts. The disconnect blade is positively toggled in the fully-closed position. The rigid galvanized steel bases simplify installation on steel structures or S&C Mounting Pedestals. Enhanced 31.5-kA Interrupters The SF6-gas-filled, single-gap, puffer-type interrupters are factory-filled to 75 PSIG, tested and permanently sealed. Field-filling is never needed, eliminating the risk of contaminating the interrupting medium and the need for gas-handling equipment saving installation time. The interrupters use lightweight, shatterproof, composite-polymer silicone insulation providing outstanding performance, even in contaminated environments. Each interrupter has its own permanently sealed stored-energy trip mechanism and charging motor. After the Circuit-Switcher has been called upon to trip and the disconnect has opened to establish a visible air gap, the charging motors close and charge the interrupters for coordinated operation. Each interrupter includes a built-in limit switch that prevents overcharging the trip mechanism, and ensures that the interrupter is either open or closed. Local indication of interrupter state closed or open is provided at the base of each interrupter and the interrupter position can also be monitored by SCADA Systems. Each interrupter also includes a temperature-compensated SF6 gas-pressure gauge, with two gas-indicator levels. A remote gas-density indicator, which provides indication of the two alarms, is optionally available. A wide variety of options are available: Interrupter pole-unit quick-connect control cable plug-style connector replaces butt-splice electrical connection at interrupter junction box Complete quick-connect control cable plugstyle connector replaces conduit between the interrupter, interrupter charging motor, and Mark VI CS-1A Switch Operator Trip mechanism (sealed inside interrupter) Grounding switch grounds jaw-contact terminal pads of Circuit-Switcher. Includes manual operating handle Remote gas-density indicator for remote indication of two-level low-gas-density alarms. Charging motor (closes interrupter) One pole-unit of 69-kV Mark VI Circuit-Switcher. 4

Mark VI Type CS-1A Switch Operator The operator s heavy-duty motor enables high-speed, high-torque closing and opening of the disconnect providing close interphase simultaneity and long life of closing contacts, and avoiding excessive switching transients due to prolonged or unstable pre-strike arcing. All interrupter and relay wiring connections are made within the operator enclosure. The operator includes external trip and close pushbuttons, and a decoupling mechanism that allows decoupling and locking of the disconnect-blade power train in the open position. A non-resettable operation counter and mechanical position indicator are also included. The Mark VI CS-1A Switch Operator includes eight-pole auxiliary adjustable switch contacts, coupled to the motor. The Mark VI CS-1A Switch Operator features sturdy welded-aluminum enclosure construction, with baffled louvers that allow air circulation while keeping out rain. It has a gasketed, flanged door design with cam-action latch for easy opening... and a clear, safetyplate glass window that allows visual inspection of the decoupling mechanism, mechanical position indicator, and the operation counter without opening the door. The Mark VI CS-1A Switch Operator can be padlocked for safety. Open-closed position indicators Optional key interlock Open-closed push buttons Optional position indicating lamps Disconnect operating handle Optional duplex receptacle and convenience light lampholder External decoupling handle Optional manual trip device Interior of Mark VI CS-1A Switch Operator. Available options include: Space heater thermostat, Long-lasting LED position-indicating lamps, Manual trip device, and Duplex receptacle and conveniencelight lamp holder. An assortment of auxiliary contacts are available to suit any control scheme or SCADA requirements. S&C Mounting Pedestals Make Installation Easy S&C Mounting Pedestals include all necessary interphase wiring and conduit, for a simplifying installation. They re available in heights of 96, 120, or 144 inches, with phase spacings of 51 or 84 inches at 69 kv, and 84, 96, or 102 inches at 115 kv and 138 kv. 138-kV Mark VI Circuit-Switcher on S&C Mounting Pedestals. 5

Pre-insertion Inductors... Reliable Transient Control Mark VI Circuit-Switchers are available with optional pre-insertion inductors for use in shunt capacitor-bank switching and protection applications. Pre-insertion inductors offer excellent performance compared to controlled-closing schemes and pre-insertion resistors for: Limiting inrush current and overvoltage at the capacitor bank bus and thus induced transient voltage disturbances in substation low-voltage control circuits, which can cause spurious signals, insulation puncture, and component damage. Limiting phase-to-phase switching-surge overvoltages produced at remote transformers as a result of energizing a capacitor bank... a phenomenon which can lead to decreased transformer life, or even transformer failure, because of the high voltage-stress concentrations which are imposed across the transformer windings. Limiting overvoltages on long open-ended lines. Such overvoltages can cause nuisance operation of surge arresters. Transient control has become increasingly important as utility customers require higher levels of power quality for sensitive process-related equipment, such as adjustable-speed drives. Transient control is also important for minimizing the stresses that surges cause on utility system equipment. Pre-insertion inductors are especially suited for limiting transient overvoltages which, through voltage magnification, can result in nuisance tripping of adjustable-speed drives and other sensitive electronic devices. Voltage magnification can occur where powerfactor correction capacitors and/or voltage control capacitors are applied on the utility distribution system or on a utility customer s low-voltage bus, and is caused by a near-resonant condition between the switched capacitor bus and the capacitances at lower voltage. Pre-insertion inductors offer distinct advantages over circuit breakers using a controlled-closing relay scheme. Controlled-closing breakers are set to close each phase at voltage zero adding significant mechanical complexity and extra cost. When commissioning a controlled-closing breaker, the installer must perform many switching operations to train the adaptive control relay system all the while putting transients on the system. And controlled-closing breakers must be periodically inspected to verify that the control system is indeed closing each phase at zero voltage and hasn t drifted... if most breakers don t close within 1.5 ms of the zero setting, damaging transients can still appear on the system. Circuit-breakers equipped with pre-insertion resistors operate similarly to Circuit-Switchers with pre-insertion inductors but are mechanically complex and prone to overheating. The resistor and main contacts of the breaker must be synchronized. Synchronization is usually achieved by connecting the resistor contact rod to the breaker main-contact control rod; this arrangement requires periodic adjustment of the contacts. Pre-insertion resistors also tend to have a much-shorter electrical life. Pre-insertion inductors, with their lower resistance and hollow core, offer greater durability and heatdissipating capability than resistors... providing longer operating life and enhanced reliability. More information on S&C Pre-insertion Inductors can be found in S&C Data Bulletin 711-95, S&C Circuit- Switchers Mark V: Pre-insertion Inductor Application Guide, 34.5 kv through 230 kv. Pre-insertion inductor core Stationary arcing contact Moving arcing rod Uncontrolled back-to-back bank inrush current Jaw contact Back-to-back bank inrush current with pre-insertion inductor Inrush current during switching of back-to-back capacitor bank, with and without pre-insertion inductors. 6 Each pre-insertion inductor is comprised of two or more close-coupled layers of stainless-steel or aluminum conductor, wound along with a resin-impregnated filament-fiberglass roving, to form a hollow glassreinforced tube. An integral counter-wound stainlesssteel damping winding limits voltage across the Circuit- Switcher during opening. A layer of roving separates the layers of conductor; other layers of roving add mechanical strength and stability. The outer roving is finished with silicone-alkyd paint for all-weather durability.

MARK VI CIRCUIT-SWITCHER 50/60-HZ RATINGS kv Amperes, RMS Nom. Max BIL Cont. 4-Hour Peak Withstand 1-Sec. Fault Closing, Duty-Cycle, Two-Time1 69 72.5 350 420 630 81 900 31 500 30 000 115 123 550 420 630 81 900 31 500 30 000 138 145 650 420 630 81 900 31 500 30 000 1 For complete information, refer to S&C Specification Bulletin 712-31. MARK VI CIRCUIT-SWITCHER INTERRUPTING RATINGS Class Application Qualifications Maximum Amperes, Interrupting, RMS, Symmetrical Load Dropping1 630 3-Time 31 500f Transformer Switching and Protection Duty-Cycle Fault Interrupting23 Secondary Faults4 Internal faults see both primary and secondary faults, above 5-Time 18 900 10-Time 9 450 30-Time 3 150 69 kv 4 200 115 kv and 138 kv 2 600 Capacitor-Bank Switching and Protection Bank Current Switching Grounded capacitor banks applied on solidly grounded systems only, through 138 kv 420 Ungrounded capacitor banks applied through 138 kv 420 Fault Interrupting23f 31 500 1 Mark VI Circuit-Switchers can close, carry, and interrupt the magnetizing current of the protected transformer. 2 Rating is based on transient-recovery voltage parameters defined in the following tables of IEC Standard 60056, Edition 4.0: 1987: For Circuit-Switchers rated 69 kv: Tables IIa, XVa, and XVIa. For Circuit-Switchers rated 115 kv and 138 kv: Tables IIc, XVc, XVIc, and XVII. 3 The interrupting ratings shown are applicable for the following dutycycles: O or CO. 4 Mark VI Circuit-Switchers are suitable for transformer-primary applications where the inherent secondary-fault current the secondary-side fault current as reflected on the primary side of the transformer, assuming an infinite (zero-impedence) source does not exceed this value for a fault external to the transformer. The inherent secondary-fault current may be calculated as follows: 57.8P I = (%Z)E where I = Inherent secondary-fault current, amperes P = Transformer self-cooled three-phase rating, kva E = Primary-side phase-to-phase voltage, kv %Z = Percent transformer primary-to-secondary impedance, referred to transformer self-cooled three-phase kva rating f Mark VI Circuit-Switchers cannot be applied on systems with shortcircuit currents in excess of this value. 7

Printed in U.S.A. Descriptive Bulletin 712-30 October 11, 2010 Offices Worldwide f www.sandc.com