1 TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets 17th April 2012

2 Session 2 Technological challenges to cope with in TWENTIES field tests 17. April 2012 WORKSHOP EWEA

3 DC-breaker prototype: challenges and advances Wolfgang Grieshaber, Alstom Grid 17. April 2012 WORKSHOP EWEA

4 DC-breaker prototype: challenges and advances 1. Differences between AC and DC current interruption 2. DC breaker options Choosing the breaker concept. 3. Key Performance Indicators (KPI) Dielectric withstand. Short Time Withstand Current. Reduction of electromagnetic forces. Duration of current interruption. 4. Demonstrator duties Selecting the duties to demonstrate. 5. Current interruption & let-through current 6. Advances 4

5 1 - Fault in AC loop 200 Current (ka) 50 Hz, 80 ka rms Opportunities for current interruption Magnetic energy in the system Time (ms) Attempt to interrupt when I 0 rapid variation of magnetic flux overvoltage Current interruption succeeds when magnetic energy 0

6 1 - Fault clearance in DC loop Fault inception current rises Magnetic energy in network increases Breaker inserts element limiting the over voltage & absorbing energy Energy transferred to energy management system Limitation of overvoltage + absorption of magnetic energy = prerequisites for DC current interruption

7 2 - DC breaker options MRTB Solid State Switch CB Fast switch Solid State Circuit Breaker without auxiliary circuit arc / power electron. arc chamber arc chamber + power electronics power electronics power electronics development needed none synchronous switch, capacitor load circuit new concept new concept smallest break time 27ms to 41ms 19ms for contact separation + 8ms to 22ms arcing time 27ms 19ms for contact separation + 8ms arcing time ~ 2ms ~0.1ms on-state losses <1 mohm <1 mohm <100 mohm ~1 Ohm max break current ~4 ka (possibly 8kA) 5 ka possibly 10kA ~10 ka ~10 ka complexity low medium high high

8 3 - Key Performance Indicators KPI were defined at beginning of Twenties Project (early 2010) No standard available! 1. Dielectric withstand in open state Lightning Impulse Withstand (indicator = U peak / 650kV) Target: indicator > 1 2. Current above 1500A (1 min.) in closed state Indicator = current / 3000A Target: indicator > 1 3. What harm can be prevented (force reduction) Indicator = (peak prospective current / peak interrupted current)² Target: indicator > (1.1)² 4. How fast is the interruption Comparison to AC breaker ; Indicator = 40ms / interruption time Target: indicator > 1 Prospective current: current without DC-breaker action. Later analysis led to extend the duties to be tested!

9 4 - Demonstrator duties All breaker duties Open state Without power With power Normal condition DC fault condition Dielectric withstand (BIL, SIL, DC) Closing Let-through current Let-through current Load switching Closed state DC dielectric withstand to ground Let-through current Close on fault Opening On idle line or cable: no current, no TRV no problem Load switching Terminal fault (highest rate of rise of current, highest prospective fault current) Without power: At least one breaker terminal is connected to a network that has only stored energy (trapped charges) but neither power source nor load nor network faults. Normal condition : The breaker is connected to power sources (and loads), but no faults. DC fault condition : a breaker has on one side a power source and on the other side a network fault.

10 4 - Demonstrator duties Selection for Twenties Open state Closed state Without power Dielectric withstand (BIL, SIL, DC) Normal condition With power DC dielectric withstand to ground Let-through current (must withstand, but not to interrupt) DC fault condition Opening Load switching Terminal fault (highest rate of rise of current, highest prospective fault current) Power tests Let-through current Wave forms as a function of time. The 4 wave forms are individual tests Adc until dt/dt<1 C/hour Adc for 1 minute 3. 5kA sin(2π 50Hz t) for 10ms 4. 10kA sin(2π 313Hz t) for 1.6ms No standard available Interrupted current had to be described in simple manner

11 5 - Current interruption Specification of breaker performance: Transient Interruption Voltage ( TIV < Network insulation level) Prospective current 3 or 5 parameter envelope function (similar to TRV in IEC ) Prospective current I load +I fault Rate of rise of prospective current Prospective current = no breaker action I load 0 t 0 Instant of fault inception t 0 + t 3 time

12 5 - Current interruption Specification of breaker performance: Transient Interruption Voltage ( TIV < Network insulation level) Prospective current 3 or 5 parameter envelope function (similar to TRV in IEC ) Energy to absorb Prospective current I load +I fault I load Breaking of prospective current Energy absorption Current zero 0 t 0 t 0 + t 3 time

13 5 - Interruption and let-through Target values to be exceeded Prospective current 1.5kA, 7.5kA, 0.6ms Transient Interruption Voltage 180kV Energy to absorb Prospective current 7.5kA 1.5kA Black line = performance target Depends on test circuit in the 100kJ to 1MJ range Let-through current 10kA, 1.6ms 5kA, 10 ms 3kA, 60 s 1.5kA, infinitely ms Let-through 10 ka current 5 ka 3 ka 1.5 ka time ms 10 ms 60 s time

14 6 Advances & outlook Breaker is designed Patent application in progress. Subassembly qualification tests started Temperature rise tests target in reach. Dielectric tests on subcomponents target in reach. Test circuit Circuit is designed. Prospective current range will be verified by test. Power test of demonstrator Scheduled for end of RtE and independent observer to witness the tests.

15 Thanks for your attention! Any question? 15

16 Thank you for your attention Questions to DEMO3 DCCB?

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS

SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS SUITABILITY OF DIFFERENT TEST VOLTAGES FOR ON-SITE TESTING OF XLPE CABLE SYSTEMS Michael Hensel HIGHVOLT Prüftechnik Dresden GmbH 2 3 Content 1 Introduction Test parameters and their significance Differences

More information

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

The standards mentioned in this document

The standards mentioned in this document The standards mentioned in this document Where can you order IEC publications? Central Offices of the International Electrotechnical Commission 1, rue de Varembé Geneva - Switzerland. The documentation

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

The complete range of consumer switchboards and switchgear

The complete range of consumer switchboards and switchgear Power Distribution The complete range of consumer switchboards and switchgear www.nhp.com.au/mod6 The MOD6 range of consumer switchboards and switchgear is specifically designed for domestic and commercial

More information

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window

More information

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

Type: DILM32 10(24V50HZ) Article No.: 277247

Type: DILM32 10(24V50HZ) Article No.: 277247 Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,

More information

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.

48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0. 48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according

More information

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA Discussion on Class I & II Terminology IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA What is Class I & II? C57.12.00 2010 is the only document we have that defined these terms. 5.10 Insulation

More information

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional

More information

A Practical Guide to Dielectric Testing

A Practical Guide to Dielectric Testing Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance

More information

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution Denis Dufournet Chairman IEC TC 17 & SC17A Fellow IEEE Senior Expert Areva T&D Mumbai, January,

More information

49 Series - Relay interface modules 8-10 - 16 A. Features

49 Series - Relay interface modules 8-10 - 16 A. Features Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole

More information

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution

High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

Type: DILM9 10(24VDC) Article No.: 276705

Type: DILM9 10(24VDC) Article No.: 276705 Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters

RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main

More information

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830

Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase

More information

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208

Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Standards in Marine Power Systems APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Need is Driven by Electrification Oasis of the Seas DDG

More information

Why Buy HVI VLF Products?

Why Buy HVI VLF Products? Very Low Frequency AC Hipots AC testing of cables and electrical apparatus is now easier than ever. Since the introduction of the High Voltage, Inc. line of portable and affordable VLF hipots, there is

More information

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bulletin 150 SMC Flex Smart Motor Controller Specifications Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering

More information

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units Automotive Powering business worldwide Aerospace Eaton delivers the hundreds of power distribution products that are answering the demands of today s fast changing world. We help our customers worldwide

More information

Safety technique. Emergency stop module BO 5988 safemaster

Safety technique. Emergency stop module BO 5988 safemaster Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1

More information

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51

34 Series - Slim electromechanical PCB relays 6 A. Features SERIES 34.51 34 Series - Slim electromechanical PCB relays 6 34 SERIES Features 34.51 Ultra-slim 1 Pole - 6 relay Printed circuit mount - direct or via PCB socket 35 mm rail mount - via screw, screwless or push-in

More information

SURGE PROTECTIVE DEVICES

SURGE PROTECTIVE DEVICES SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood

More information

Cahier technique no. 193

Cahier technique no. 193 Collection Technique... Cahier technique no. 193 MV breaking techniques S. Théoleyre "Cahiers Techniques" is a collection of documents intended for engineers and technicians, people in the industry who

More information

F05D Meeting on Damped AC Voltage Testing

F05D Meeting on Damped AC Voltage Testing October 28 th, 2008 from 03.30-5.30 pm in San Antonio, TX Agenda F05D Damped AC Voltage Testing 1 Agenda F05D Damped AC Voltage Testing Welcome: Introduction On-site testing voltages e.g. IEC 60060-3 High

More information

DS 600. A contact free flux gate based current measurement sensor 600A rms

DS 600. A contact free flux gate based current measurement sensor 600A rms DS 600 A contact free flux gate based current measurement sensor 600A rms DS 600 is member of the small housing sensor family. The family includes a 200A and a 600A version. 600A rms - 900A peak Maximum

More information

48 SERIES Relay interface modules 10 A

48 SERIES Relay interface modules 10 A 48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply

More information

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Reyrolle Protection Devices 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy Siemens Protection Devices Limited 2 7PG17 XR101 & XR102 Intertripping Relay

More information

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6. 38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC

More information

21 st Century Facilities

21 st Century Facilities Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

Joslyn Clark Controls, Inc.

Joslyn Clark Controls, Inc. Joslyn Clark Controls, Inc. CAPACITOR SWITCHING VACUUM CONTACTORS vs. AIR BREAK CONTACTORS APPLICATION PRECAUTIONS & CALCULATIONS TO LIMIT HIGH FREQUENCY & HIGH CURRENT 2 QUESTION: WHY IS A VACUUM CONTACTOR

More information

White paper. ABB solutions for switching and protection of low speed wind turbines

White paper. ABB solutions for switching and protection of low speed wind turbines White paper ABB solutions for switching and protection of low speed wind turbines ABB solutions for switching and protection of low speed wind turbines Index 1 Introduction...2 2 Full converter configuration...4

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

80 Series - Modular timers 16 A. Features 80.01 80.11

80 Series - Modular timers 16 A. Features 80.01 80.11 80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h

More information

Trip circuit supervision relay. Type RXTCS

Trip circuit supervision relay. Type RXTCS Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Tmax MCCBs. Molded case circuit breakers. Tmax

Tmax MCCBs. Molded case circuit breakers. Tmax Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high

More information

DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS

DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display

More information

Fixed - Over/Under voltage limits, (0.75...1.2) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

Fixed - Over/Under voltage limits, (0.75...1.2) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits Features 71.11.8.230.0010 71.11.8.230.1010 1 - Phase 230 V Over & Under voltage monitoring relays 71.11.8.230.0010 - Fixed Over & Under voltage detection - Link selectable 5 or 10 minute lock-out delay

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

Medium voltage circuit breaker

Medium voltage circuit breaker Medium voltage circuit breaker IEC 60 056 and ANSI C37-06 define on one hand the operating conditions, the rated characteristics, the design and the manufacture; and on the other hand the testing, the

More information

UFES Active protection for switchgear

UFES Active protection for switchgear Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document

More information

Electrical Shore Connections / Cold Ironing

Electrical Shore Connections / Cold Ironing STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version

More information

Contact expansion modules

Contact expansion modules Gertebild ][Bildunterschrift Kontakterweiterungen Contact for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs: 4 safety contacts

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - 39 Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic

More information

CAPACITOR BANK TESTING SWP

CAPACITOR BANK TESTING SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.

More information

Lightning current simulation in the laboratory - parameters, procedures and test equipment -

Lightning current simulation in the laboratory - parameters, procedures and test equipment - Lightning current simulation in the laboratory - parameters, procedures and test equipment - Dipl.-Ing. J. Schönau, Dr.-Ing. M. Naß, CE-LAB GmbH Prof. Dr.-Ing. F. Berger, Ilmenau University of Technology

More information

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy. s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage

More information

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

Panel Meters and Controllers Modular Panel Meter Type EDM 35

Panel Meters and Controllers Modular Panel Meter Type EDM 35 Panel Meters and Controllers Modular Panel Meter Type EDM 35 Modular digital panel meter, 3 1/2-digit Indicating or controlling current, voltage, resistance, temperature, tacho or frequency. Easy programming

More information

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

Power over Ethernet plus Isolation requirements. David Law 3Com David_Law@3Com.com

Power over Ethernet plus Isolation requirements. David Law 3Com David_Law@3Com.com Power over Ethernet plus Isolation requirements David Law 3Com David_Law@3Com.com Agenda History 10BASE2 and 10BASE5 10BASE-T DTE Power via MDI Analyses of Differences in DTE Power via MDI Recommendation

More information

How To Choose A Transformer

How To Choose A Transformer Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV

More information

Contact expander modules

Contact expander modules Gertebild ][Bildunterschrift Kontakterweiterungen Contact expansion module for increasing the number of available contacts Approvals Zulassungen Unit features Gertemerkmale Positive-guided relay outputs:

More information

WINGLIKE ELECTRONICS CO.,LTD

WINGLIKE ELECTRONICS CO.,LTD WINGLIKE ELECTRONICS CO.,LTD SPECIFICATION FOR APPROVAL AC/DC ADAPTOR CUSTOMER: CUSTOMER SPECS INPUT: 100-240V AC 50-60HZ, 5V/2A ADAPTOR OUR MODEL NO.: GM-050200 (UL) E321192 SPECIFICATION NO.: WL1105102

More information

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms

Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity

More information

DS1 Diode-based transient-free capacitor switch

DS1 Diode-based transient-free capacitor switch Medium voltage products DS1 Diode-based transient-free capacitor switch Power and productivity for a better world TM Compensation of reactive power DS1 the future of switches Compensation of reactive power

More information

Electronic overload relay EF19 and EF45

Electronic overload relay EF19 and EF45 Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

Residual Current Circuit Breaker

Residual Current Circuit Breaker Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect

More information

Gas Discharge Tube (GDT) Products CG5 and SL0902A Series. CG5 and SL0902A Series

Gas Discharge Tube (GDT) Products CG5 and SL0902A Series. CG5 and SL0902A Series Description Agency Approvals AGENCY AGENCY FILE NUMBER E128662 2 Electrode GDT Graphical Symbol Littelfuse Broadband Optimized SL0902A Series offers high surge ratings in a miniature package. Special design

More information

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System Summary Report November 2009 Technical Report on using EHV

More information

AMSC s Superconductor Cable Technologies for Electric Utilities

AMSC s Superconductor Cable Technologies for Electric Utilities International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,

More information

IEC specifications for LV assembly switchboards

IEC specifications for LV assembly switchboards Technical set IEC specifications for LV assembly switchboards In conformity with IEC 61439-1&2 standard Specifier Guide Introduction Within the IEC 61439 series of standards for low-voltage switchgear

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

T 3000. Substation Maintenance and Commissioning Test Equipment

T 3000. Substation Maintenance and Commissioning Test Equipment T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy

More information

General information Circuit breakers for power distribution T1 T3

General information Circuit breakers for power distribution T1 T3 Circuit breakers for power distribution T1 T3 T1 T2 T3 T1 1P T1 T2 T3 UL 489 CSA C22.2 Frame size A 100 100 100 225 Number of poles Nr 1 3, 4 3, 4 3, 4 Rated voltage AC (50-60 Hz) V 277 600Y / 347V 480

More information

Instrument Transformers Application Guide

Instrument Transformers Application Guide Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden

More information

Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions

Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions Dr. Detlev Kirsten & Herbert Piereder Solid State SSFCL

More information

Top Microsystems Proprietary Specification P/N: W090015HK-XP 022410RB-082709V.A0 SPECIFICATION

Top Microsystems Proprietary Specification P/N: W090015HK-XP 022410RB-082709V.A0 SPECIFICATION SPECIFICATION High Quality Switching Wallmount Adapter Interchangeable AC Plugs 90-264VAC Input 13.5W 9VDC 1.5A Output P/N: W090015HK-XP ** Specification Approval** This specification (total 11 pages including

More information

Electronic overload relay EF65, EF96 and EF146

Electronic overload relay EF65, EF96 and EF146 Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.

More information

Fundamentals of Power

Fundamentals of Power Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection

More information

TISP4600F3, TISP4700F3 OBSOLETE

TISP4600F3, TISP4700F3 OBSOLETE *RoHS COMPLIANT TISP4600F3, TISP4700F3 HIGH OLTAGE BIDIRECTIONAL THYRISTOR OEROLTAGE PROTECTORS TISP4600F3, TISP4700F3 Ion-Implanted Breakdown Region Precise and Stable oltage Low oltage Overshoot under

More information

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview

BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview BETA Switching Siemens AG 200 5TT5 Insta contactors, AC technology Overview The 5TT5 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features gang engertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS

DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display

More information

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents

More information

Safety automation solutions

Safety automation solutions Operating principle, characteristics Preventa safety s types XPS AV,, For and switch monitoring Operating principle Safety s XPS AV, and are used for monitoring circuits conforming to standards EN/ISO

More information