Primary-Side Transformer Protection
|
|
|
- Delilah Walters
- 9 years ago
- Views:
Transcription
1 Primary-Side Transformer Protection Peter J. Meyer, S&C Electric Company, Chicago, Illinois Presented at the Doble Life of a Transformer Seminar; Laguna Beach, California February 21 25, 2005 INTRODUCTION There are many different protection schemes used today for distribution substation transformers, covering a wide range of expense and complexity from high-end ring bus and breaker-and-one-half schemes, to low-end flash bus and grounding switch schemes. Given the pressure to increase the continuity of service, more advanced protective devices are called for than a motor-operated disconnect switch to initiate a fault. Today, the best practice is to individually protect each transformer with a local protective device. Doing so eliminates the need to take off-line all transformers connected to the transmission line, when only one transformer has experienced a fault... unnecessary interruptions to service are avoided. Secondary-side bus faults are the most common type of event that a primary-side protective device must interrupt. But they may be difficult for some devices due the highfrequency transient recovery voltage (TRV). One might think that a device with a robust fault interrupting rating such as a 40-kA circuit breaker would be able to handle a relatively low-magnitude fault on the secondary-side of the transformer. But the secondary-fault interrupting rating of a device is dependant on the device s ability to withstand a fast-rise transient voltage much faster than that seen during high-current fault interrupting. Therefore, the device must be specifically tested to determine its ability to withstand and interrupt fast TRVs. A device with a 40-kA primary-fault interrupting rating may not necessarily be able to interrupt 4-kA secondary faults with a fast-rise transient voltage. Standards for testing a device for appropriate secondary-side fault interrupting capabilities which take into account high-frequency TRVs are currently being reviewed. The draft standard, PC37.016, Standard for AC High Voltage Circuit Switchers rated 15kV through 245kV, [1] provides the testing requirements to verify that a protective device can interrupt a fast TRV. C , Trial Use Guide for High-Voltage Circuit-Breakers Rated on a Symmetrical Current Basis Designated Definite Purpose for Fast Transient Recovery Voltage Rise Times, [2] does so as well, although the main C37.06 standard, AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis, [3] does not currently incorporate requirements for testing a breaker s ability to interrupt faults with associated fast-rise TRV, or to require a secondary-side fault interrupting rating. Manufacturers of purpose-built equipment for transformer protection, including the author s company, have traditionally tested for fast-transient TRVs and provide their equipment with a secondary-side fault interrupting rating. Given the position of the primary-side device and that most fault activity is on the secondary bus, this secondary-side interrupting rating is critical for a primary-side protective device. Before discussing how to select a primary-side protective device, let s examine the possible locations of faults and the subsequent response of the protective equipment. LOCATIONS OF FAULTS AFFECTING THE TRANSFORMER Primary-side protective devices are widely applied at loadtap transformers where the available primary fault current exceeds the device s primary-fault interrupting rating. Overlapping protection from statistically rare high-current primary faults is afforded by the line-terminal circuit breakers and first-zone phase- and ground-fault lineprotective relays. On systems using line-terminal circuit breakers, circuit interruption following a high-current primary fault is typically accomplished by the line breakers in 3 cycles. A local primary-side transformer protective device will respond to faults internal to the transformer and to faults on the secondary bus that is included in its zone of protection. It can also provide back-up protection for the secondary-side protective device(s). A properly applied transformer protective system will overlap some of the protection provided by the line-terminal circuit breakers and supplement the protection afforded by the secondary-side protective device(s). Page T79
2 To understand how a primary-side transformer protective device is applied, let s look at Figure 1. It shows a one-line diagram of the relay protection scheme used for a typical radially tapped transformer protective scheme including four locations where faults may occur. Line-Terminal Circuit Breakers Local Primary-Side Transformer Protective device. X Location 1 49 Optional X Location 2 N X X Location 3 Location 4 Feeder Protective Devices. Feeders Location 1: Faults on Bus Between Transformer Protective Device and Transformer, and Transformer Primary Bushing-to-Ground Faults The short length of bus and greater line-to-ground clearance make these types of faults rare. Fault current magnitudes in this area can be high because they are only limited by the upstream impedance of the system. This location is typically not part of the relaying for a primaryside protective device due to the location of the primaryside current transformers. It is important to remember that the current transformers for the transformer differential protection are typically located on the bushings of the transformer. Therefore, the primary-side protective Typical Transformer Protective Scheme Using Relayed Device. FIGURE 1 Page 2 device will not receive a trip signal for events on the primary bus, and this device will not get called on to clear full primary-side fault currents on the primary side. For example, primary arrester failures will be cleared by the line terminal breakers, as shown in Figure 1. Faults in this area cannot usually be detected by the relay schemes used with a local device. If current transformers are available at the primary-side protective device, a relay scheme could be used to cover this small section of the high-side bus but, due to the 3-cycle speed of operation of line-terminal circuit breakers, both devices would respond to the event unless an expensive pilot-wire blocking scheme is implemented. On more complex substation bus
3 arrangements like ring-bus or breaker-and-one-half schemes, the primary-side protective device usually has current transformers and is used to clear faults in this short section. Location 2: Transformer Primary Winding Faults Faults at the transformer primary winding are uncommon in a well-protected and well-maintained transformer. The fault current magnitude can be either high or low depending on the location of the fault within the winding. Typical winding faults are turn-to-turn or multiple-turn and are low magnitude, on the order of load current. Lesslikely winding-to-ground faults are limited by the winding impedance to low to moderate magnitude. A winding-toground fault near the high-voltage bushing results in high currents limited by the system impedance. These faults are detected by differential, overcurrent, or ground fault relaying, or by sudden pressure, gas analysis, or other overpressure detection methods. Depending on where they occur and the magnitude of the fault current, they will either be cleared by the line breakers or the primaryside protective device. Location 3: Transformer Secondary Winding Faults Secondary winding faults are also uncommon in a wellprotected and well-maintained transformer. The fault current magnitude can be either low or moderate depending on the location of the fault within the winding. Turn-to-turn and multiple-turn faults are typically low magnitude, limited by the winding impedance. Windingto-ground faults are of moderate magnitude and always less than the available secondary fault current limited by the transformer impedance. These faults are detected by differential, overcurrent, or ground-fault relaying, or by sudden pressure, gas analysis, or other overpressure detection methods, and are cleared by the primary-side transformer protective device without disturbing the transmission line. Location 4: Transformer Secondary Bus Faults and Secondary Bushing-to-Ground Faults Secondary bus and transformer secondary bushing-toground faults represent the majority of faults that a transformer protective device will have to interrupt. With its typically greater length and smaller phase-to-ground distance, it more likely that wildlife intrusion or nearby equipment problems will cause a fault on the secondary bus. The fault current magnitude is moderate because it is limited by the transformer impedance. Faults in this location are detected by secondary differential or overcurrent protective schemes, and are cleared by the primary-side transformer protective device without disturbing the transmission line. SECONDARY-SIDE FAULT INTERRUPTION Secondary-side faults, found in Location 4 in Figure 1 (above), are difficult to interrupt. Special attention must be paid to selecting a device that can interrupt these lowcurrent transformer-limited faults. Such faults are limited by the impedance of the transformer, so they have modest magnitudes, but the transient recovery voltage (TRV) frequency seen by the interrupting device after clearing the current is high because of the small bushing and winding capacitance of the transformer, compared to its large inductance. 1 F = 2π LC Page 3
4 To illustrate, a fault in Location 4 would be detected by the transformer s differential relaying, which would signal the primary-side device to open. (See Figure 1.) In a puffer-type SF 6 circuit-switcher or circuit breaker, during the opening operation, the SF 6 gas is compressed by moving the cylinder supporting the contact system, or by a piston which forces the SF 6 through the interrupting nozzle. Contact Arc-Interruption and Recovery Voltage FIGURE 2 This causes a rapid gas flow across the arc, which serves to cool the arc while the arc is lengthened as the contacts move farther apart. By controlling and cooling the arc, its conductivity can be rapidly decreased as the current passes through zero, such that the arc is extinguished and the circuit is interrupted. At that time, the transient recovery voltage across the gap between the contacts is impinged, as a race starts between the cooling processes within the transformer protective device due to increasing dielectric strength and rising recovery voltage across the contacts. If the cooling processes are successful, the interruption is successful and there is no resumption in current. When interrupting a secondary-side fault across a transformer, the reactance-toresistance ratio (X/R) is high, so fault current will significantly lag the voltage. See Figure 2. When current is at zero, the voltage is at or near peak. In general, the impedance of the transformer is high compared to the source, so there is a significant voltage (assumed to be.9 per unit. by C37.016) [3] trapped in the stray capacitance of the transformer. As this energy resonates back and forth between the electric field of the stray capacitance and the magnetic field of the transformer inductance, a substantial voltage excursion occurs on the terminals of the transformer protective device, which highly stresses the contact gap due to the high-frequency nature of this excursion typically on the order of 10 khz to 15 khz. If the insulation between the contacts recovers more quickly than the TRV, the interruption is successful. If the TRV creates too excessive a rise in voltage, re-ignition of the arc can occur. Page 4
5 TRV Comparison for a 230 kv Device Secondary Fault TRV Primary Fault TRV Voltage (kv) Time (micro-seconds) TRV Comparison for a 230 kv Device FIGURE 3 Many primary-side devices are assigned a secondary-fault interrupting rating and tested to ensure that they are capable of interrupting transformer-limited faults. In some cases, multi-purpose devices with high primary-fault interrupting ratings may not be able to interrupt fast TRVs testing with a fast TRV needs to be specified to ensure the device can handle this duty. See Figure 3. Secondary fault currents are typically in the range of 2 ka to 6 ka. To determine the fault current seen by the primaryside protective device for a fault on the secondary side, an infinite (zero-impedance) source is assumed. The value can be calculated using the following equation: 57.8P I = (% Z) E where I = Inherent secondary-fault current, amperes P = Transformer self-cooled three-phase rating, kva E = Primary-Side System phase-to-phase voltage, kv %Z = Percent transformer primary-to-secondary impedance, referred to transformer self-cooled three-phase kva rating For example, a 37.5/50/62.5 MVA transformer at 115 kv with 8% impedance will provide an inherent secondary-fault current of 2,356 amperes, calculated as follows: 57.8* 37,500kVA I = = 2, 356A 8*115kV Therefore, the maximum current on the high side of the transformer resulting from a fault on the secondary side bus will be 2,356 amperes with a high-frequency TRV. The primary-side protective device should be rated to clear this type of secondary fault. [4] Page 5
6 SELECTING TRANSFORMER PRIMARY-SIDE PROTECTIVE DEVICES Selecting a primary-side device for a new substation can be just as much an economic decision as a technical one. Smaller, less expensive transformers are often protected with power fuses. In the past, these transformers have been protected with remote protection schemes which rely on the line-terminal breakers to protect the transformer, as well as to provide back-up protection for the secondary-side protective device. Larger transformers and transformers serving critical loads are usually protected with devices that use relaying schemes from simple overcurrent relays to sophisticated combinations of differential, sudden pressure, overcurrent and instantaneous relays that fully coordinate with upstream and downstream devices. Once a device with the appropriate secondary-side interrupting rating requirements has been identified, the selection process largely becomes a matter of choosing the features and configuration appropriate to the installation. Factors such as available substation real estate, bus layout, seismic requirements, structure height requirements, equipment maintenance cycles, and system ratings are only a few of the factors that must be considered... the suitability of the device for a particular substation is usually a matter of utility preference. In some cases, a device is selected to upgrade a power fuse installation. In such instances, primary-side current transformers, substation batteries, and control power are usually not present in the substation, and the cost of installing this infrastructure is often weighed against the benefits of more-sophisticated relayed transformer protection. In other cases, a relayed device like a circuit-switcher or circuit breaker is selected to upgrade a remote protection scheme. Although widely used in the past, such schemes are slowly being phased out. Remote protection schemes clear secondary-side faults by creating a bolted primary fault, typically with a grounding switch, or use sacrificial switching or a flash bus. The primary fault is then cleared by line-terminal circuit breakers. The entire transmission line is thus interrupted for both primary- and secondary-side faults sensed by transformer relaying, decreasing service reliability. Faults also take longer to clear, as a result of the sequential operation of two independent systems: the local disconnect switch and the line breakers. Upgrading to a local transformer protective device protects the transformer against the stresses associated with the artificially induced primary-side fault, and will leave the transmission line undisturbed in the event of a secondary-side fault. Much of the relaying and communications used to trigger the protective scheme can be reused with the local protective device. Selection of a device can also be affected by the bus configuration of the substation. Transformers located on a radial tap off of the transmission line will usually use a single transformer protective device. If there is more than one transformer in the substation, the protective device may be coordinated with a tie switch. When used for transformer protection, circuit breakers or circuit-switchers typically have a minimum of secondary-side overcurrent and sudden pressure relaying. A more critical transformer may have differential relaying and back-up overcurrent relaying, and may also include a neutral overcurrent relay to detect ground faults. In substations with one or more available sources, the transformer protective device may be coordinated into an automatic switching or throw-over scheme. And in urban or dense industrial areas, double-bus or ring-bus arrangements are becoming increasingly more common as the demand for power reliability increases. In these cases, the transformer protective device will have to be rated for both primary and secondary fault interrupting duty as well as for short-line faults and the associated relay scheme will be quite elaborate. Explaining the different types of protective relay schemes that can be employed with a primary-side device is outside the scope of this discussion. For a detailed description of the types of relays and relay schemes that can be used with a protective device, refer to ANSI C , IEEE Guide for Protective Relay Applications to Power Transformers. [5] The following is a brief overview of the different local primary-side transformer protective devices available today. Page 6
7 Power Fuses Power fuses, shown in Figure 4 in a typical transformer protective application, provide protection that is both reliable and economical. They are inexpensive both in initial purchased cost and installed cost. When properly applied, their characteristics remain unchanged over their operational life. Power fuses are generally applied on transformers rated 10 MVA and smaller. Manual or motor-operated disconnect switch Power Fuses in Typical Transformer Protective Application FIGURE 4 The operating procedure for power fuses is straightforward. Typically, after a fuse has operated, the load-side circuit breaker, switch, or recloser is opened. (If no load-side device is in place, the main-secondary circuit breaker or recloser is opened.) Then the line-side series disconnect is opened. Transformer inspection and maintenance can then be performed, and the fuses replaced. To restore service, the line-side series disconnect is closed to pick up transformer magnetizing current. Then the load-side circuit breaker, switch, or recloser is closed. As mentioned previously, the advantage to using power fuses is their relative low-cost compared to a relayed transformer protective device. Disadvantages include the difficulty in coordinating fuses for secondary-side faults and single-phasing of downstream devices in the event of a single-phase fault. Also, there is no way to implement more advanced relay schemes using differential, neutral overcurrent, or sudden pressure relays. [5] Circuit-Switcher The author s company developed the first circuit-switcher in 1960 for use in capacitor switching and transformer protection. Early on, it was recognized that the main duty for a circuit-switcher applied for transformer protection would be in clearing secondary faults, so an extensive study of the frequency response of transformers was launched to develop a test method for ensuring that circuit-switchers could clear such faults. The work done at that time is the basis for the present proposed standard. Circuit-switchers use stored-energy operating mechanisms to drive the interrupters open, and have trip-free operating capability. In the event the circuit-switcher is closed into a fault, it will open immediately to interrupt the fault. Many circuitswitcher models are equipped with integral disconnect blades, which provide visual assurance of the device s state and provide working clearance for transformer maintenance or repair. Shown in Figure 5 is a typical primary-side transformer protection application. Circuit-switchers use the same type of protective relaying as circuit breakers and both devices provide a similar level of protection. The operating procedure for a circuit-switcher is similar to that of a circuit breaker. After the device has tripped, the circuit-switcher disconnect or separate line-side disconnect is opened either manually or, in some cases, automatically to isolate the transformer. Then the loadside series disconnect is opened. Transformer inspection and maintenance can now be performed. Page 7
8 1 2 Protective Zone of Circuit Breaker #1 Protective Zone of Circuit Breaker #2 C/S TC Protective Zone of Circuit-Switcher Feeders Circuit-Switcher in Typical Transformer Protective Application FIGURE 5 To restore service, the relays are reset, the load-side series disconnect is closed, and the circuit-switcher is then closed. Circuit-switchers have trip-free operation. So if either the circuit-switcher or the line-side disconnect is closed into a fault, the circuit-switcher will trip to clear the fault. Unlike circuit breakers, circuit-switchers typically have a short-time current rating higher than their interrupting rating. The reason for this goes back to the rarity of primary faults and the difficulty in coordinating a transformer protective device with line-terminal circuit breakers, which react to and clear high current faults within 3 cycles. For high current faults, a circuit-switcher typically does not interrupt either because it is located outside the local zone of protection, or because the line-terminal circuit breakers operate faster than the typical 5- to 8-cycle operating time of the circuitswitcher. It is common practice to apply a primary-side protective device that can carry but cannot interrupt the full available high-side fault current on the primary side of the transformer. Circuit-switchers are available in models from 34.5 kv through 345 kv, with primary-fault interrupting ratings from 8 ka up to 40 ka, secondary-side fault interrupting ratings from 2600 to 4200 amperes, and interrupting times between 3 and 8 cycles. Faults on the secondary side are low magnitude, so a 3, 6 or 8-cycle operating time will not have much effect on the amount of stress put on the transformer windings. Internal transformer faults are usually detected early in their development by differential or sudden-pressure relays, before much fault current is flowing. And obviously, an internal transformer faults will typically necessitate the removal of the transformer from service and untanking of the transformer for inspection and repair. Generally speaking, a complete rewinding is warranted regardless of whether the fault persisted for 3, 5, 6, or 8 cycles. For these reasons, the fault clearing time of a circuit-switcher isn t as important in selecting a transformer protective device as the ability to successfully interrupt secondary-side faults. Page 8
9 The advantages of circuit-switchers include their ability to provide economical transformer protection, and their ability to be used with a whole range of protective relay schemes. Many circuit-switchers include integral disconnect blades, which reduce the overall installation time in getting the installation on-line. Disadvantages are that they typically do not have high-speed reclosing or short-line fault capability. And, due to their live-tank design, the addition of current transformers is quite expensive. This excludes circuitswitchers from use in more complex bus schemes where the transformer protective device also acts as a line protective device. Transformer Protective Device The author s company has developed a low-cost power fuse and circuit-switcher replacement which utilizes a modular design. The transformer protective device features puffertype interrupters similar to that used in circuit-switchers. These interrupters provide a 31.5-kA fault interrupting rating and a 3-cycle interrupting time. Transformer protective devices have been tested for their ability to interrupt fast TRVs and are assigned a secondary-fault interrupting rating similar to circuit-switchers. Each pole-unit is self-contained with its own operating mechanism; the pole-units are filled with SF 6 and sealed. Two versions are available: one which requires an external power source and user-furnished relaying, and one with a self-contained overcurrent protection relay system. The selfpowered version is pictured below. (Figure 6.) Self-Powered Device Trips Self-Powered Device Δ Y (Optional secondary neutral relay) 50N N Transformer Protector with Overcurrent Protection in Typical Transformer Protective Application FIGURE 6 Page 9 The operating procedure for the self-powered version is similar to that of power fuses. After the device has tripped, the load-side circuit breaker, switch, or recloser is opened either manually or, in some cases, automatically to isolate the transformer. (If no load-side device is in place, the mainsecondary circuit breaker or recloser is opened.) Then the line-side series disconnect is opened. Transformer inspection and maintenance can now be performed. To restore service, the pole-units are manually closed and charged for the next opening with a charging tool provided with the device. Each
10 phase is charged separately. Thus, steps for visually verifying the charged status of each phase must be incorporated into the substation operating procedure. After the relay targets have been reset, the line-side series disconnect is closed, picking up transformer magnetizing inrush current. Then the load-side circuit breaker, switch, or recloser is closed. The self-powered version is trip-free; in the rare event that the line-side disconnect is closed into a fault, it will trip to clear the fault. The transformer protective device was specifically designed for application on distribution substation transformers. At full load current, it has a continuous current rating of 420 amperes. At 69 kv, it can protect up through a 30/40/50- MVA transformer and it has a 4200-ampere secondary-side fault interrupting rating. At 115 kv, it can protect up through a 37.5/50/62.5-MVA transformer. At 138 kv, it can protect up through a 50/66.5/83-MVA transformer and it has a 2600-ampere secondary-side fault interrupting rating. At the upper extremes of the application range, there are some limitations with respect to the minimum impedance of the transformer, so as to stay within the secondary fault rating of 2600 amperes. [4] [6] The advantages of transformer protective devices include their ability to provide very economical transformer protection, and their ability to be used with a whole range of protective relay schemes. The compact design and light weight of these devices make them suitable for application where there is little room for a larger protective device. The disadvantage is that some users operating practices do not allow energizing of a transformer using a disconnect switch although many users have been doing it for years for fuse applications. Circuit Breaker Circuit breakers are also used for transformer protection, as shown in Figure 7. Like circuit-switchers, circuit breakers are relay-activated. Breakers offer higher interrupting ratings than power fuses and circuit-switchers, are SCADAcompatible, and work with the same protective relay schemes as circuit-switchers. Breakers are generally used in complex bus schemes, such as ring-bus or breaker-and-onehalf schemes. In those situations, the breaker acts as both the transformer protective device and the protective device for the incoming lines thus the need for high-speed reclosing, short-line fault interrupting capability and, in many cases, high primary-fault current capability. In the United States, dead-tank breakers are typically used since current transformers can be economically applied. TC Circuit Breaker in Typical Transformer Protective Application FIGURE 7 Page 10
11 The latest designs of circuit breakers use puffer-type SF 6 - filled interrupters, as were previously discussed in the section on secondary-side fault interruption. Circuit breakers generally have a stored-energy mechanism that allows the breaker contacts to open and close one or more times after control power has been lost. These mechanisms can be pneumatic or hydraulic, and use compressed air or another compressed gas, or a motor-compressed spring. [3] For transformer protection, the high-speed reclosing capability of circuit breakers is often undesirable and, in most cases, should be blocked. When the primary-side transformer protection trips in a response to a fault internal to the transformer, it s generally for a good reason. A visit to the substation is usually necessary to determine if the transformer has been damaged. The transformer insulation is tested, and a gas or oil analysis may be performed to check for arc byproducts. In some cases, a turns-ratio test is performed. Since almost no transformer protective scheme uses high-speed reclosing, the feature is unnecessary. Circuit breakers are general purpose switching devices designed for application in a variety of areas on a utility system. Although circuit breakers often have an extremely robust interrupting rating, they are not always tested for their ability to interrupt the fast TRVs associated with secondaryside faults. This rating needs to be specified when purchasing a circuit breaker for transformer protection. COLUSION Providing a local primary-side protective device for each distribution substation transformer affords the best protection against secondary-side faults, and eliminates unnecessary disturbances on the transmission line. When selecting a primary-side protective device, careful examination must be made of its secondary-side fault interrupting capability. Other factors must be taken into consideration, including the cost of the transformer, the criticality of the load, and the available resources. REFEREES [1] IEEE PC37.016; DRAFT, Standard for AC High- Voltage Circuit-Switchers rated 15kV through 245kV. [2] ANSI/IEEE Standard C ; Trial Use Guide for High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis Designated Definite Purpose for Fast Transient Recovery Voltage Rise Times. [3] ANSI/IEEE C ; AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis Preferred Ratings and Required Capabilities. [4] IEC Standard 60056, High Voltage Alternating Current Circuit Breakers, Edition 4.0: [5] ANSI/IEEE C ; IEEE Guide for Protective Relay Applications to Power Transformers. [6] ANSI/IEEE C ; Guide for Transformer Through-Fault Current Duration. Page 11
Rule 5.500 Fast Track Analysis for National Life Insurance Co.
Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION
INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012
INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably
Low Voltage Transformer Through-Fault Protection: A System Approach
Data Bulletin 7400DB1001 Nashville, TN USA Low Voltage Transformer Through-Fault Protection: A System Approach Introduction Low Voltage Transformer Protection Criteria NEC Article 450 Transformers and
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
S&C Circuit-Switchers Mark VI
S&C Circuit-Switchers Mark VI Outdoor Transmission (69 kv through 138 kv) Mark VI Circuit-Switcher with Pre-insertion Inductors... the most reliable way to switch and protect substation capacitor banks
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION
ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò
Local Back-up Protection for an Electric Power System
MULTILIN GER-3178 GE Power Management Local Back-up Protection for an Electric Power System LOCAL BACK UP PROTECTION FOR AN ELECTRIC POWER SYSTEM J. BERDY TABLE OF CONTENTS Transmission Line Back-Up Protection...............................................
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit
SPECIFICATION COG-2007
Cleco Power LLC SPECIFICATION COG-2007 FOR PARALLEL OPPERATION OF CUSTOMER-OWNED GENERATION ON CLECO S ELECTRICAL SYSTEM Revised: March 7, 2014 CONTENTS ITEM NO. TITLE PAGE NO. 1.0 Scope 3 2.0 Policy On
High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution
High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS Claudio S. Mardegan [email protected] www.engepower.com Phone: 55 3579-8777
Step Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Typical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com [email protected] Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
Engineering Series Ratings: Is It Practical?
Engineering Series Ratings: Is It Practical? By the National Electrical Manufacturers Association The 2005 National Electrical Code (NEC) introduces a change regarding series ratings for circuit breakers
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
Engineering innovation
Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems
Power System Selectivity: The Basics of Protective Coordination
Feature Power System Selectivity: The Basics of Protective Coordination by Gary H. Fox, PE GE Specification Engineer The intent of this article is to provide a brief primer about the essence of coordinating
High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv
High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
WINDING RESISTANCE TESTING
WINDING RESISTANCE TESTING WINDING RESISTANCE TEST SET, MODEL WRT-100 ADWEL INTERNATIONAL LTD. 60 Ironside Crescent, Unit 9 Scarborough, Ontario, Canada M1X 1G4 Telephone: (416) 321-1988 Fax: (416) 321-1991
Transmission Protection Overview
Transmission Protection Overview 2012 Hands-On Relay School Brian Smyth Schweitzer Engineering Laboratories Pullman, WA Transmission Line Protection Objective General knowledge and familiarity with transmission
Specifications. S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)
Outdoor Transmission (69 kv through 230 kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under SPECIAL WARRANTY
PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES
Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES PURPOSE This section provides substation design information for Load Entities interconnected at transmission voltage
Permissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
TABLE OF CONTENTS 1.0 INTRODUCTION... 2 1.1 PURPOSE... 2 1.2 DEVIATION... 2 4.0 INTERTIE PROTECTION REQUIREMENTS... 4
Page: 1 of 14 KEY BULLETIN POINTS: THIS GUIDE OUTLINES MINIMUM REQUIREMENTS FOR CONNECTION OF CUSTOMER-OWNED EMERGENCY AND STANDBY (ESG) TO THE GEORGIA POWER COMPANY (GPC) DISTRIBUTION SYSTEM. THESE ARE
IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution
IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution Denis Dufournet Chairman IEC TC 17 & SC17A Fellow IEEE Senior Expert Areva T&D Mumbai, January,
DISTRIBUTION RELIABILITY USING RECLOSERS AND SECTIONALISERS
ABB DISTIBUTION ELIABILITY USING ECLOSES AND SECTIONALISES obert E. Goodin Chief Engineer ABB Inc. Lake Mary, FL Timothy S. Fahey, PE Sr. Application Engineer ABB Inc. aleigh, NC Andrew Hanson, PE Executive
Shunt Capacitor Bank Fundamentals and Protection
2003 Conference for Protective Relay Engineers - Texas A&M University April 8-10, 2003, College Station (TX) Shunt Capacitor Bank Fundamentals and Protection Gustavo Brunello, M.Eng, P.Eng Dr. Bogdan Kasztenny
Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.
Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional
ECE 586b Course Project Report. Auto-Reclosing
ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1
Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.
Fuseology Medium Voltage Fuses General Fuses above are classified under one of three classifications as defined in ANSI/IEEE C37.40. 1. General Purpose Current-Limiting Fuse: A fuse capable of interrupting
AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
15LINE PROTECTION WITH PILOT RELAYS
15LINE PROTECTION WITH PILOT RELAYS Pilot relaying is the best type for line protection. It is used whenever high-speed protection is required for all types of short circuits and for any fault location.
101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer
101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION Cutler-Hammer WELCOME Welcome to Module 3, Fundamentals of Electrical Distribution. If you have successfully completed Module
F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China
ELECTRIC POWER DISTRIBUTION SYSTEMS F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China Keywords: Distribution system planning, Load characteristics, Subtransmission Lines, Distribution
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
Proven vacuum switching technology from Siemens meets all requirements placed on circuit-breakers and contactors in medium-voltage switchgear up to
Proven vacuum switching technology from Siemens meets all requirements placed on circuit-breakers and contactors in medium-voltage switchgear up to 40.5 kv. 2 Contents Overview of medium-voltage components
Advantages of Fixed Circuit Breaker Switchgear
Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker
Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
TERMS AND CONDITIONS
Virginia Electric and Power Company TERMS AND CONDITIONS XXIV. GENERATOR INTERCONNECTION STANDARD Electric generator interconnection service includes only the ability to interconnect an electric generator
Overcurrent Protection for the IEEE 34 Node Radial Test Feeder
Power System Automation Lab 1 Overcurrent Protection for the IEEE 34 Node Radial Test Feeder Hamed B. Funmilayo, James A. Silva and Dr. Karen L. Butler-Purry Texas A&M University Electrical and Computer
Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.
Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,
S&C TripSaver Dropout Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv
S&C TripSaver Dropout Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing S&C s new TripSaver Dropout Recloser: A better solution for overhead lateral circuit protection at
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
The following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
Grounding of AC generators and switching the neutral in emergency and standby power systems
Power topic #6006 Part 2 of 2 Technical information from Cummins Power eneration rounding of AC generators and switching the neutral in emergency and standby power systems > White paper By Lawrence A.
STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS
STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS David D. Roybal, P.E. Senior Member, IEEE Cutler-Hammer, Inc. 3697 Mount Diablo Boulevard Lafayette,
S&C BankGuard PLUS Control
S&C BankGuard PLUS Control For Substation Capacitor Banks and Shunt Reactors Application S&C s BankGuard PLUS Control utilizes flexible, reliable microprocessor technology to: Protect substation shunt
TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection
Distance Protection Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you are strongly advised to study this note regarding to the pre-study questions
Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA
Discussion on Class I & II Terminology IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA What is Class I & II? C57.12.00 2010 is the only document we have that defined these terms. 5.10 Insulation
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING
Fault Characteristics in Electrical Equipment
1. Introduction Proper design and installation of electrical equipment minimizes the chance of electrical faults. Faults occur when the insulation system is compromised and current is allowed to flow through
Transformers. Special transformers Reactors products
Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having
SWITCHGEAR PROTECTION
LECTURE NOTES ON SWITCHGEAR PROTECTION IV B. Tech I semester (JNTUH-R09) Mr. P SHIVAKUMAR Assistant Professor ELECTRICAL AND ELECTRONICS ENGINEERING INSTITUTE OF AERONAUTICAL ENGINEERING DUNDIGAL, HYDERABAD
Impact of Distributed Resources on Distribution Relay Protection
Impact of Distributed Resources on Distribution Relay Protection A report to the Line Protection Subcommittee of the Power System Relay Committee of The IEEE Power Engineering Society prepared by working
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Outdoor vacuum circuit-breakers and reclosers for medium voltage. Switching technology for distribution networks. Answers for energy.
Outdoor vacuum circuit-breakers and reclosers for medium voltage Switching technology for distribution networks Answers for energy. Reliable quality for all your medium-voltage network needs Quality from
SMT POWER THERMISTORS
SMT POWER THERMISTORS Theodore J. Krellner Keystone Thermometrics, Inc. St. Marys, Pennsylvania ABSTRACT This article focuses on the construction and application of SMT power negative temperature coefficient
Mission Critical Data Center Systems
Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,
SF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation
2. INDUCTIVE VOLTAGE TRANSFORMERS Oil-paper insulation Gas insulation 123 kv Inductive Fingrid (Finland). 18 Instrument transformers igh voltage INTRODUCTION Inductive voltage transformers are designed
ACCURACY OF POTENTIALTRANSFORMERS
8 VOLTAGE TRANSFORMERS Two types of voltage transformer are used for protective-relaying purposes, as follows: (1) the "instrument potential transformer," hereafter to be called simply "potential transformer,"
Live Tank Circuit Breakers Application Guide
Live Tank Circuit Breakers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Tomas Roininen, Carl Ejnar Sölver, Helge Nordli, Anne Bosma, Per Jonsson, Anders
Medium voltage circuit breaker
Medium voltage circuit breaker IEC 60 056 and ANSI C37-06 define on one hand the operating conditions, the rated characteristics, the design and the manufacture; and on the other hand the testing, the
Siemens Fusesaver. Highest availability and cost savings for your MV distribution network. www.siemens.com/fusesaver
www.siemens.com/fusesaver Siemens Fusesaver Highest availability and cost savings for your MV distribution network Answers for infrastructure and cities. 2 In high demand: An intelligent solution Improving
Schneider Electric Services: life-cycle solutions for electrical distribution equipment. Scopes of Work for Electrical Acceptance Testing
Scopes of Work for Electrical Acceptance Testing Schneider Electric Services: life-cycle solutions for electrical distribution equipment Make the most of your energy SM Scopes of Work for Electrical Acceptance
Cahier technique no. 193
Collection Technique... Cahier technique no. 193 MV breaking techniques S. Théoleyre "Cahiers Techniques" is a collection of documents intended for engineers and technicians, people in the industry who
Residual Current Circuit Breaker
Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect
System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems
System Grounding and Ground-Fault Protection Methods for -Supplied Power Systems Bill Brown, P.E., Square D Critical Power Competency Center 1. INTRODUCTION The use of solid grounding for -supplied power
TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer
168-08 TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE APPARATUS A three-phase outdoor oil-immersed distribution transformer DESIGNATION 1000 kva SERIAL No. 1-08-112-01-0001 Rated power Rated voltage
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.
Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.06 Introduction to Power Systems Class Notes Chapter 4 Introduction To Symmetrical Components J.L. Kirtley
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Current Transformers Ratio / Polarity / Types
CT1 Current Ratio / Polarity / Types Application Current (CT s) are instrument transformers that are used to supply a reduced value of current to meters, protective relays, and other instruments. CT s
Considering the effects of UPS operation with leading power factor loads
Considering the effects of UPS operation with leading power factor loads Over the past five years, a new generation of data processing and communications equipment has become prevalent in modern data centers
HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE
Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Assessing The Hazards Of High and Low Voltage Single-Phase Arc-Flash By Albert Marroquin One common question
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
Loading Considerations When Paralleling Transformers
Application Guide 7400DB0701 02/2007 Nashville, TN, USA Loading Considerations When Paralleling Transformers Class 7400 Retain for future use. Introduction Principles of Paralleling This application guide
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters
Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy.
Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00 Answers for energy. Unit substation solution with type SIMOSEC primary switches, dry-type transformer
Protection from Short-circuit
Protection from Short-circuit Back-up Fuse-Link with ÜLA (controlled power dissipation) Test device for tripping device Special version with threat High-voltage Fuse-Link for voltage transformers (HSW)
Chapter 1. Network Structures
Chapter 1 Network Structures Definition Standard IEC 60038 defines voltage ratings as follows: Low voltage (): for a phase-to-phase voltage of between 100 V and 1,000 V, the standard ratings are: 400 V
Protection of Phase Angle Regulating Transformers
Protection of Phase Angle Regulating Transformers A report to the Substation Subcommittee of the IEEE Power System Relaying Committee prepared by Working Group K1 IEEE Special Publication Members of the
Transformer protection
8 Transformer protection 8.1 Introduction The inherent characteristics of power transformers introduce a number of unique problems that are not present in the protection of transmission lines, generators,
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
Brochure Introducing HVDC
Brochure Introducing HVDC ABB and HVDC The world s first commercial high-voltage direct current (HVDC) link, situated between the Swedish mainland and the island Gotland, was delivered by ABB already in
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
CT Application Guide for the 489 Generator Management Relay
g GE Power Management Technical Notes CT Application Guide for the 489 Generator Management Relay GE Publication No. GET-8402 Copyright 2002 GE Power Management Introduction A protection scheme operates
