Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34.

Size: px
Start display at page:

Download "Specifications. S&C Power Fuses Types SM and SMLa. For use with SM Refill Units or SMU Fuse Units. Indoor Distribution (4.16 kv through 34."

Transcription

1 S&C Power Fuses s SM and SMLa Indoor Distribution (4.16 through 34. ) For use with SM Refill Units or SMU Fuse Units Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 10 apply, except as modified under WARRANTY QUALIFICATIONS on pages 2 and 3. SPECIAL TO THIS PRODUCT: NOTE: S&C SM and SML Power Fuses are available separately only when the ultimate user is an electric utility (investor-owned, municipal, federal, state, county, or RUS-financed cooperative) or other qualified power user. These fuses are available to other users in the form of S&C Metal-Enclosed Gear; please refer to your nearest S&C Sales Office. SM and SML Power Fuses are also available separately to qualified original-equipment manufacturers, for subsequent installation in metal enclosures in accordance with S&C s applicable minimum construction specifications, as set forth under WARRANTY QUALIFI- CATIONS appearing on pages 2 and 3. INCLUSIONS: Complete mountings include a base, Cypoxy d Insulators, and fuse live parts. Complete mountings are factory-assembled and adjusted, and ready for installation.,, S, and SM-20 Power Fuses: and Power Fuses are offered in both the disconnect and non-disconnect styles; S Power Fuses in the non-disconnect style only; and SM-20 Power Fuses in the disconnect style only. These power fuses (in either style) consist of three distinct components: a fuse mounting, a holder (,, and S Power Fuses) or fuseunit end fittings including Silencer (SM-20 Power Fuses), and a refill unit (,, and S Power Fuses) or fuse unit (SM-20 Power Fuses). Each component is ordered separately as described on page 3 under How to Order a Complete Power Fuse. These power fuses are not designed for live-switching duties. and Power Fuses: These power fuses are available in the disconnect style only. The Power Fuse consists of three distinct components: a fuse mounting including Uni-Rupter and the same base as the SM-20 Power Fuse, fuse-unit end fittings (including Silencer) identical to those for the SM-20 Power Fuse, and the same SMU-20 Fuse Unit used with the SM-20 Power Fuse. The Power Fuse consists of three distinct components: a fuse mounting including Uni-Rupter and the same base as the SM-20 and Power Fuses, a fuse holder similar to the Holder except for the provision of contacts used to operate Uni-Rupter, and the same SM-4 Refill Unit used with Power Fuses. ( Holders are not interchangeable with Holders in the same mounting.) Components for SML Power Fuses are ordered separately as described on page 3 under How to Order a Complete Power Fuse. and Power Fuse Mountings with Uni- Rupter provide -ampere single-pole live switching of single-phase and three-phase circuits (on systems where line-to-line voltage does not exceed ). EXCLUSIONS: Complete mountings and live parts do not include holders, fuse-unit end fittings, refill units, or fuse units. Complete mountings and live parts do not include connectors. Various connectors are available as listed in the table on page 12. Specify quantity and catalog number of connectors desired. SPECIFICATION DEVIATIONS,, S, and SM-20 Power Fuses: Mountings for these power fuses can be supplied less insulators. Add suffix -Z1 to the catalog number. Mountings for these power fuses can be supplied less bases but including insulators. Add suffix -Z4 to the catalog number. These mountings cannot be supplied for back connection. Live parts for these power fuses can be purchased separately. See tables on pages 4 and 6. When these mountings are to be provided with special connectors, consult your nearest S&C Sales Office for availability. Mountings can be supplied with tin-plated terminal pads. To specify, add suffix -Z to the catalog number. Not applicable to SM-20 Power Fuses, which are equipped with tin-plated terminal pads as a standard feature. Disconnect style parallel Power Fuses are furnished with aluminum terminal pads as a standard feature. m Cypoxy is the S&C trademark for S&C s cycloaliphatic epoxy resin system. Cypoxy is nontracking, self-scouring, nonweathering... there s never a compromise of insulation integrity. S&C Cypoxy station post insulators meet or exceed the electrical and mechanical-strength requirements established in ANSI C29.9 for porcelain standard-strength station post insulators. w S&C Power Fuses s SM and SML are manufactured in accordance with a quality system certified to ISO April 14, 8 S&C Electric Company Specification Bulletin 2-31

2 S&C Power Fuses s SM and SML Conditions of Sale Continued and Power Fuses: Mountings for these power fuses cannot be supplied less insulators. Mountings for these power fuses cannot be supplied less bases but including insulators. These mountings cannot be supplied for back connection. Live parts for these power fuses cannot be purchased separately. When these mountings are to be provided with special connectors, consult your nearest S&C Sales Office for availability. Application Notes For and Power Fuses only: S&C Power Fuses with Uni-Rupter are designed for the following single-pole live-switching duties in single-phase or three-phase circuits of distribution systems rated 14.4 or : Live Switching Opening Transformer switching transformer load currents up through amperes, as well as transformer magnetizing currents associated with the applicable loads. Line-switching load splitting (parallel or loop switching) and load dropping of currents up through amperes; also line dropping (charging currents typical for distribution systems of these voltage ratings). Cable switching load splitting (parallel or loop switching) and load dropping of currents up through amperes; also cable dropping (charging currents typical for distribution systems of these voltage ratings). Live Switching Closing Circuit closing inrush currents associated with the above opening duties. Duty-cycle j fault closing one-time capability equal to the interrupting rating of the fuse (in amperes RMS asymmetrical): For the 22,400 at 14.4, 20,000 at : For the 20,000 at 14.4, 1,000r at. And two-time capability of 13,000 amperes RMS asymmetrical at 14.4 and. A Note on Single-Pole Switching In single-pole switching of ungrounded-primary threephase transformers or banks (or single-phase transformers connected line-to-line), circuit connections or parameters may, in some cases, produce excessive overvoltages. In particular, for the following applications above 22, single-pole switching by any means including Uni- Rupter should be performed only under the conditions stated in italics: Switching unloaded or lightly loaded delta-connected or ungrounded-primary wye-wye connected three-phase transformers or banks (or line-to-line connected singlephase transformers), rated 10 A or less three-phase, or 0 A or less single-phase or of any A when combined with unloaded cables or lines where maximum system operating voltage exceeds 22. Singlepole switching should be performed only if each phase is carrying % load or more, or if the transformer or bank is temporarily grounded at the primary neutral during switching. Switching loaded or unloaded ungrounded-primary wyedelta connected three-phase transformers or banks alone or combined with unloaded cables or lines where maximum system operating voltage exceeds 22. Single-pole switching should be performed only if each phase is carrying % load or more and if the lightingload phase is always switched open first (or switched closed last); or if the transformer or bank is temporarily grounded at the primary neutral during switching. WARRANTY QUALIFICATIONS: For the standard warranty contained in seller s standard conditions of sale (as set forth in Price Sheet 10) to apply to S&C Power Fuses s,,, S, SM-20, or when installed in indoor, outdoor, or indoor-outdoor enclosures of other than S&C manufacture, the enclosures must be constructed in accordance with S&C s applicable minimum construction specifications to be found in the current revision of one of the following publications: DATA BULLETIN 2-62: S&C Power Fuses SM Indoor Distribution (4.16 through 34. ) DATA BULLETIN 2-64: S&C Power Fuses SML Indoor Distribution ( and ) Minimum Construction Specifications For Indoor and Outdoor Metal Enclosures with Fuses Minimum Construction Specifications For Indoor and Outdoor Metal Enclosures with Fuses j These values represent the fault-closing capabilities of the fuse with Uni-Rupter when the fuse is closed with a purposeful thrust without hesitation. The values are the available fault currents into which the fuse can be closed the specified number of times (once or twice), with Uni-Rupter remaining operable and able to carry and interrupt rated current. r 20,000 amperes RMS asymmetrical when applied on solidlygrounded-neutral systems only with fuses connected by single-conductor, concentric-neutral type cable (or directly coupled) to a transformer or transformers. 2 S&C Specification Bulletin 2-31

3 S&C Power Fuses s SM and SML DATA BULLETIN : S&C Alduti-Rupter Switches with Power Fuses Indoor Distribution (4.8 and ) DATA BULLETIN 7-60: S&C Mini-Rupter Switches with Power Fuses Indoor Distribution (4.8 and 14.4 ) Minimum Construction Specifications For Metal Enclosures Indoor and Outdoor Minimum Construction Specifications For Metal Enclosures Indoor and Outdoor For the standard warranty contained in seller s standard conditions of sale (as set forth in Price Sheet 10) to apply to live parts when purchased separately, the live parts must be assembled on mountings in accordance with instructions to be found in the current revision of one of the following publications: INSTRUCTION SHEET 2-0: S&C Power Fuses s and Indoor Distribution INSTRUCTION SHEET 2-10: S&C Power Fuses s,, and S Indoor Distribution INSTRUCTION SHEET 2-3: S&C Power Fuses SM-20 Indoor Distribution Live Parts for Disconnect Style Live Parts for Non-Disconnect Style Live Parts for Disconnect Style With respect to S&C Power Fuses s SM or SML when installed in submersible enclosures of other than S&C manufacture, warranty does not apply unless enclosures are furnished by an approved supplier and are of watertight construction providing proper electrical clearances and proper space for fuse handling. The standard warranty contained in seller s standard conditions of sale (as set forth in Price Sheet 10) does not apply when fuses of other than S&C manufacture are used in S&C SM or SML Mountings or when S&C Holders, Refill Units, or Fuse Units are used in mountings of other than S&C manufacture. How to Order a Complete Power Fuse s,,, and S 1. Obtain the catalog number of the desired mounting from the Mounting column on pages 4 through 6. If only live parts are desired, refer to the Live Parts column. Note: Live parts for Power Fuses cannot be purchased separately. 2. Obtain the catalog number of the applicable holder from the Holder column on pages 4 through 6, reading from the same line in which the selected mounting is listed. 3. Obtain the catalog number of the applicable refill unit from the tables on pages 9 through 11, taking care to match the refill unit type to that of the mounting, and to select the voltage rating of the refill unit as directed in the refill unit tables. Note: For each mounting rated 720E amperes, order two holders and two refill units. 4. Obtain the catalog number of the desired connector from the table on page 12. Order two connectors for each mounting or set of live parts. Note: Parts, insulating barrier assemblies, and switch blades listed on pages 13 and 14 are ordered using the method outlined above. s SM-20 and 1. Obtain the catalog number of the desired mounting from the Mounting column on pages 4 and. If only live parts are desired, use the Live Parts column. Note: Live parts for Power Fuses cannot be purchased separately. 2. Obtain the catalog number of the applicable fuse unit end fittings from the same table used to select the mounting. 3. Obtain the catalog number of the applicable fuse unit from the tables on pages 7 and 8, taking care to match the voltage rating of the fuse unit to that of the mounting. 4. Obtain the catalog number of the desired connector from the table on page 12. Order two connectors for each mounting or set of live parts. Note: Parts, insulating barrier assemblies, and switch blades listed on pages 13 and 14 are ordered using the method outlined above. How to Order Handling Tools Obtain the catalog number(s) of recommended handling tool(s) from the table on page 1. Refer to Specification Bulletin S&C Specification Bulletin

4 S&C Power Fuses s SM and SML SM POWER FUSES Disconnect Style Less Connectors and Less Refill Units or Fuse Units Style Fuse Nom. Max BIL Max, RMS Interrupting1 (Sym.) Mounting2 (including Live Parts, less Fuse-Unit End Fittings or Holder) Fuse-Unit End Fittings3 (SM-20) or Holder4 ( or ) Live Parts (less Fuse- Unit End Fittings or Holder) Page Reference for Dimensional Information SM SM SM Disconnect 4 Opening Silencer Vertical R R2d n 6 0 SM R R a 86632R2 v 86633R R Disconnect 4 Opening Snuffler Vertical r 000r SM R3 8710R4m 87442R3 8712R4m 87073R j 86641R2d 86641R2d 86642R2 v 86642R2 v 86643R R R2 8719R R2 8719R R R Symmetrical ratings assigned are based on available short-circuit current at locations where the X/R ratio is 1. The interrupting ratings expressed in amperes RMS asymmetrical are 1.6 times the symmetrical ratings listed. Higher symmetrical ratings have been determined for these fuses where X/R = 10 and X/R =. These higher ratings as well as asymmetrical ratings are given in S&C Descriptive Bulletin These mountings cannot be supplied for back connection. 3 Includes Silencer. 4 Includes Silencer () or Snuffler (). n is 12,00 amperes RMS symmetrical when applied on solidly grounded-neutral systems only with fuses connected by single-conductor, concentric-neutral type cable (or directly coupled) to a transformer or transformers. r Applies to 7.2- refill unit in 7.2- holder for 4.8- system voltage only. is 37,00 amperes RMS symmetrical for refill unit in 7.2- holder for system voltages through a Supersedes 34.-, 10- BIL SM-4 Mounting and 34.-, - BIL SM-4 Mounting 18734R1. m Two holders required with each mounting. j Supersedes 34.-, 10- BIL SM- Mounting and 34.-, - BIL SM- Mounting 18744R2. d Rated 7.2 nominal, for use in listed 4.8- mountings for system voltages through 4.8, or in discontinued 7.2- mountings for system voltages through 7.2. v Rated 14.4 nominal, for use in listed - mountings or in discontinued mountings. 4 S&C Specification Bulletin 2-31

5 S&C Power Fuses s SM and SML SML POWER FUSES Disconnect Style Less Connectors and less Refill Units or Fuse Units Style Fuse Nom. Max BIL Max, RMS Load Dropping1 Interrupting2 (Sym.) Mounting3 (including Live Parts, less Fuse-Unit End Fittings or Holder) Fuse-Unit End Fittings4 () or Holder4 () Page Reference for Dimensional Information Disconnect 4 Opening Silencer Vertical m SML-4 SML a The Uni-Rupter associated with these fuses can carry and interrupt load current up to and including the emergency peak-load capabilities of the fuses. Furthermore, the fuse with Uni-Rupter has a one-time duty-cycle fault-closing capability equal to the interrupting rating of the fuse (expressed in amperes RMS asymmetrical), and a two-time dutycycle fault-closing capability of 13,000 amperes RMS asymmetrical. The duty-cycle fault-closing capability defines the level of available fault current into which the fuse can be closed the specified number of times (once or twice), without quick-make mechanism and when operated vigorously through its full travel without hesitation at any point, with the Uni-Rupter remaining operable and able to carry and interrupt current up to the emergency peak-load capabilities of the fuse. 2 Symmetrical ratings assigned are based on available short-circuit current at locations where the X/R ratio is 1. The interrupting ratings expressed in amperes RMS asymmetrical are 1.6 times the symmetrical ratings listed. Higher symmetrical ratings have been determined for these fuses where X/R = 10 and X/R =. These higher ratings as well as asymmetrical ratings are given in S&C Descriptive Bulletin These mountings cannot be supplied for back connection. 4 Includes Silencer. m is 12,00 amperes RMS symmetrical when applied on solidly grounded-neutral systems only with fuses connected by single-conductor, concentric-neutral type cable (or directly coupled) to a transformer or transformers. a Rated 14.4 nominal, for use in listed - mountings. S&C Specification Bulletin 2-31

6 S&C Power Fuses s SM and SML SM POWER FUSES Non-Disconnect Style Less Connectors and less Refill Units Style Fuse Nom. Max BIL Max, RMS Interrupting1 (Sym.) Mounting2 (including Live Parts, less Holder) Holder3 Live Parts (less Holder) Page Reference for Dimensional Information Non- Disconnect Silencer Vertical n 6 0 SM-4 87R R R a 86801R2d 86802R2 v 86803R R Non- Disconnect Snuffler Vertical r SM R R3 8703R j 86811R2d 86812R2 v 86813R R2 8709R S Non- Disconnect Super Snuffler Vertical m SM R3 S 86402R2 v 8709R Symmetrical ratings assigned are based on available short-circuit current at locations where the X/R ratio is 1. The interrupting ratings expressed in amperes RMS asymmetrical are 1.6 times the symmetrical ratings listed. Higher symmetrical ratings have been determined for these fuses where X/R = 10 and X/R =. These higher ratings as well as asymmetrical ratings are given in S&C Descriptive Bulletin These mountings cannot be supplied for back connection. 3 Includes Silencer (), Snuffler (), or Super Snuffler (SM SS). n is 12,00 amperes RMS symmetrical when applied on solidly grounded-neutral systems only with fuses connected by single-conductor, concentric-neutral type cable (or directly coupled) to a transformer or transformers. r Applies to 7.2- refill unit in 7.2- holder for 4.8- system voltage only. is 37,00 amperes RMS symmetrical for refill unit in 7.2- holder for system voltages through m 60-hertz only. a Supersedes 34.-, 10- BIL SM-4 Mounting and 34.-, - BIL SM-4 Mounting R1. j Supersedes 34.-, 10- BIL SM- Mounting and 34.-, - BIL SM- Mounting R2. d Rated 7.2 nominal, for use in listed 4.8- mountings for system voltages through 4.8, or in discontinued 7.2- mountings for system voltages through 7.2. v Rated 14.4 nominal, for use in listed - mountings or in discontinued mountings. 6 S&C Specification Bulletin 2-31

7 S&C Power Fuses s SM and SML SMU-20 FUSE UNITS (For use in SM-20 or Mountings) Nominal, Max K s E s DR s S&C K TCC 16-2 TCC a TCC 13-2 TCC S&C Very Slow TCC S&C DR TCC K 703 3DR 623 6K 706 E 61 4DR 624 8K 708 7E 617 DR 6 10K E DR 6 12K E DR K E DR K E DR K 7020 E K E K E K E K E K E K E K E K E E E These fuse units are equally suitable for use in SMD-20 Outdoor Distribution Mountings; and also, for use with SME-20 Fuse-Unit End Fittings listed in Specification Bulletin 66-31, S&C Manual PME Pad-Mounted Gear and Specification Bulletin , S&C Remote Supervisory PME Pad-Mounted Gear. a This fuse unit is not E rated. TABLE CONTINUED c S&C Specification Bulletin

8 S&C Power Fuses s SM and SML SMU-20 FUSE UNITS (For use in SM-20 or Mountings)1 Nominal, Max23 K s E s DR s S&C K TCC 16-2 TCC 11-2 S&C DR TCC a TCC 13-2 TCC S&C Very Slow TCC K DR K E DR K E DR K E DR K E DR K E DR K E DR K 7030 E K E K E K E K E K E K E K E K E E E Nominal, 38 Max K s E s DR s S&C K TCC 16-2 TCC a TCC 13-2 TCC S&C Very Slow TCC S&C DR TCC K DR K E DR K E DR K E DR K E DR K E DR K E DR K 7040 E K E K E K E K E K E K E K E K E E E These fuse units are equally suitable for use in SMD-20 Outdoor Distribution Mountings. 2 These fuse units are equally suitable for use with SME-20 Fuse-Unit End Fittings listed in Specification Bulletin 66-31, S&C Manual PME Pad-Mounted Gear and Specification Bulletin , S&C Remote Supervisory PME Pad-Mounted Gear. 3 Also suitable for protection of single-phase-to-neutral circuits (lines or transformers) on 20/34. GrY- systems. a This fuse unit is not E rated. 8 S&C Specification Bulletin 2-31

9 S&C Power Fuses s SM and SML SM-4 REFILL UNITS (For use in SM-4 and SML-4 Holders) 7.2 Nominal, 8.3 Max Nominal, Max TCC R R4 TCC 13-4 TCC TCC R4 122R4 TCC 13-4 TCC S&C Coord. TCC E 12100R4 1R4 E R4 1R4 7E R R4 10E 12101R R4 13E R R4 1E 1210R4 10R4 1220R4 20R4 20E R4 1030R R4 2030R4 E R4 1040R R4 2040R4 30E 12100R4 100R R4 200R4 40E R4 1060R R4 2060R4 0E 12107R4 107R R4 207R4 6E R4 1100R R4 2100R4 80E 1211R4 11R4 1221R4 21R4 100E 12110R4 110R R4 210R4 1E 121R4 1R4 122R4 2R4 10E 1210R4 10R4 1220R4 20R4 17E 121R4 1R4 122R4 2R4 E R4 1300R R4 2300R R4j Nominal, Max2 34. Nominal, 38 Max TCC 11-4 TCC R R R R4 TCC 13-4 TCC TCC 13-4 TCC E 12300R R4 E R R4 7E R R4 10E 12301R R4 13E R R4 1E 1230R4 30R4 1240R4 40R4 20E R4 3030R R4 4030R4 E R4 3040R R4 4040R4 30E 12300R4 300R R4 400R4 40E R4 3060R R4 4060R4 0E 12307R4 307R R4 407R4 6E R4 3100R R4 4100R4 80E 1231R4 31R4 1241R4 41R4 100E 12310R4 310R R4 410R4 1E 123R4 3R4 124R4 4R4 10E 1230R4 30R4 1240R4 40R4 17E 123R4 3R4 124R4 4R4 E R4 3300R R4 4300R4 1 Rated 7.2 nominal, for use in SM-4 Holders rated 7.2 when applied in listed mountings rated 4.8 or in discontinued mountings rated These refill units are also suitable for use with SME-4Z Holders listed in Specification Bulletin 66-31, S&C Manual PME Pad-Mounted Gear and Specification Bulletin , S&C Remote Supervisory PME Pad- Mounted Gear. 3 Rated 14.4 nominal, for use in SM-4 Holders rated 14.4 when applied in listed mountings rated or in discontinued mountings rated j This S&C Coordinating refill unit should be applied where the maximum continuous load current does not exceed amperes and where all fault currents below 1000 amperes will be cleared by another fuse. S&C Specification Bulletin

10 S&C Power Fuses s SM and SML SM- REFILL UNITS (For use in SM- Holders) 4.16 Nominal, 4.76 Max1 7.2 Nominal, 8.3 Max2 TCC 11-4 TCC R R4 TCC 13-4 TCC S&C Coord. TCC R R4 TCC 13-4 TCC S&C Coord. TCC E 13000R R4 E R R4 7E R R4 10E 13001R R4 13E R R4 1E 1300R4 2600R4 1310R4 20E R R R4 E R R R4 30E 13000R R R4 40E R R R4 0E 13007R R R4 6E R R R4 80E 1301R4 2601R4 1311R4 100E 13010R R R4 1E 130R4 260R4 131R4 10E 1300R4 2600R4 1310R4 17E 130R4 260R4 131R4 E R R R4 0E R R R R4 300E 13000R R R R4 400E R R R R R4mj R4j R4mj R4j 1 2 TCC R4 132R4 TCC Nominal, Max3 Nominal, Max TCC S&C Coord. TCC TCC R R4 TCC 13-4 TCC E 13R R4 E 137R R4 7E R R4 10E 13201R R4 13E R R4 1E 1320R4 2620R4 1330R4 2630R4 20E R R R R4 E R R R R4 30E 13200R R R R4 40E R R R R4 0E 13207R R R R4 6E R R R R4 80E 1321R4 2621R4 1331R4 2631R4 100E 13210R R R R4 1E 132R4 262R4 133R4 263R4 10E 1320R4 2620R4 1330R4 2630R4 17E 132R4 262R4 133R4 263R4 E R R R R4 0E R R R R4 300E 1300R4 2600R R R4 400E R R R4j R4j TABLE AND FOOTNOTES CONTINUED c 10 S&C Specification Bulletin 2-31

11 S&C Power Fuses s SM and SML FOOTNOTES 1 Rated 4.16 nominal, for use in SM- Holders rated 7.2 when applied in listed mountings rated 4.8 for system voltages through Rated 7.2 nominal, for use in SM- Holders rated 7.2 when applied in listed mountings rated 4.8 for 4.8- system voltage only, or in discontinued mountings rated 7.2 for system voltages of 4.8 through Rated 14.4 nominal, for use in SM- Holders rated 14.4 when applied in listed mountings rated or in discontinued mountings rated m numbers are in italics because these are 7.2- refill units. Interrupting ratings are those listed in S&C Descriptive Bulletin 2-30 for 7.2- Power Fuses applied to systems rated 2.4/4.16 Y. j These S&C Coordinating refill units should be applied where the maximum continuous load current does not exceed 400 amperes and where all fault currents below 3000 amperes for s R4 and R4 and 4000 amperes for s R4 and R4 will be cleared by another fuse. SM- REFILL UNITS (For use in SM- Holders) 34. Nominal, 38 Max 1 2 TCC R R4 TCC 13-4 TCC E 13400R4 E R4 7E R4 10E 13401R4 13E R4 1E 1340R4 2640R4 20E R R4 E R R4 30E 13400R R4 40E R R4 0E 13407R R4 6E R R4 80E 1341R4 2641R4 100E 13410R R4 1E 134R4 264R4 10E 1340R4 2640R4 17E 134R4 264R4 E R R4 0E R R4 300E 13400R R4 S&C Specification Bulletin

12 S&C Power Fuses s SM and SML CONNECTORS Applicable Power Fuse Illustration and Description Accommodating Conductor Disconnect Styles Upper Terminal Pad Lower Terminal Pad Non-Disconnect Styles Upper Terminal Pad Lower Terminal Pad Bronze Body, Tin Plated, Single Z\x C\v0 Galvanized Steel Bolt No. 2 solid (33.6 mm 2 ) through 00 kc mil (33 mm 2 ) stranded copper or aluminum SM-20 SM-20 S S 4749 Bronze Body, Tin Plated, Single Z\x Z\v0 Galvanized Steel Bolt No. 2 solid (33.6 mm 2 ) through 00 kc mil (33 mm 2 ) stranded copper or aluminum 394 Aluminum Alloy Body, Tin Plated, Two Z\x Z\x0 Galvanized Steel Bolts No. 2 solid (33.6 mm 2 ) through 00 kc mil (33 mm 2 ) stranded copper or aluminum SM-20 S S 4744 Aluminum Alloy Body, Tin Plated, Two Z\x Z\v0 Galvanized Steel Bolts No. 2 solid (33.6 mm 2 ) through 00 kc mil (33 mm 2 ) stranded copper or aluminum 4746 No. 6 solid (13.3 mm 2 ) through 0 kc mil (168 mm 2 ) copper or aluminum SM R1-A S S 464R1-B Standard Bronze Pad Terminal, Tin Plated, Four-Bolt. Includes Z\x-inch galvanized steel hardware for attachment to terminal pads of fuses 1/0 solid (3. mm 2 ) through 00 kc mil (33 mm 2 ) copper or aluminum 2/0 stranded (89 mm 2 ) through 800 kc mil (39 mm 2 ) copper or aluminum SM-20 SM-20 46R1-A S S 46R1-B 467R1-A S S 467R1-B 12 S&C Specification Bulletin 2-31

13 S&C Power Fuses s SM and SML PARTS For use with,,, and S Power Fuses Item Rated (, Nominal) For Holder Spare Spring-and-Cable Assembly 4.8 or 7.2 a For use only in holders carrying an arrow-shaped nameplate. Springand-cable assemblies for holders which do not carry an arrow-shaped nameplate are no longer available so a new holder with the appropriate voltage rating must be ordered. SM-4S or r Product discontinued. To replace an SM-4S Snuffler ( FA ), order one Silencer as listed, plus one fuse pivot, S j Not usable in disconnect style mounting. FA-972 FA-2341a or 14.4 SM-4S or FA-973 FA FA or 14.4 FA-2342a 23 or 34. SM-4S or SM-4S or FA-974 FA-2343a FA-97 FA-2344a Spare Silencer All ratings or FDA-1079 Spare Snuffler All ratings SM-4S S FA r FDA-106 FA j PARTS For use with SM-20 and Power Fuses Item Rated (, Nominal) For Power Fuses Spare Silencer All ratings SM-20 or FDA-1103 S&C Specification Bulletin

14 S&C Power Fuses s SM and SML INSULATING BARRIER ASSEMBLIES For use with SM and SML Power Fuses Item Rated (, Nominal) For Power Fuses Three-Phase Insulating-Barrier Assembly 1 Replacement Barrier SA B-770 SA B-771 SA B-772 or S SA B-773 SM-20,, or SA B-774 Insulating Barriers SA B-796 SA B-797 SM-20,, or SA B SA B SA B-42-9 SM-20 SA B Includes four C\zn-inch (4.8 mm) NEMA Grade GPO3 fiberglassreinforced polyester barriers, plus a complete set of mounting hardware and adjustable-length interbarrier spacers. 2 Replacement NEMA Grade GPO3 fiberglass-reinforced polyester barriers listed in this specification bulletin must only be installed with barriers of similar design and construction. 3 Includes one C\zn-inch (4.8 mm) NEMA Grade GPO3 fiberglassreinforced polyester barrier; does not include mounting hardware or interbarrier spacers. For mounting hardware sufficient to mount one barrier, specify two (2) fastener assemblies, CA For interbarrier spacers, refer to the nearest S&C Sales Office. SWITCH BLADES1 Item Nominal Max, Cont. Switch Blades, for use in lieu of Holders in SML-4 Mountings Switch Blades, for use in lieu of SMU-20 Fuse Units in Mountings Switch Blades, for use in lieu of Holders in SM-4 Mountings Switch Blades, for use in lieu of Holders in SM- Mountings When switch blades are used in lieu of Holders or SMU-20 Fuse Units, the Uni-Rupter associated with these switches can carry and interrupt load currents up to and including the emergency peakload capabilities of the fuses. Furthermore, the switches with Uni- Rupter have a one-time duty-cycle fault-closing capability equal to the interrupting ratings of the fuses (expressed in amperes RMS asymmetrical) and a two-time duty-cycle fault-closing capability of 13,000 amperes RMS asymmetrical. The duty-cycle fault-closing capability defines the level of available fault current into which the switch can be closed the specified number of times (once or twice), without quickmake mechanism and when operated vigorously through its full travel without hesitation at any point, with the Uni-Rupter remaining operable and able to carry and interrupt currents up to the emergency peak-load capabilities of the fuse. For switches with Uni-Rupter, the one-second rating is 14,000 amperes RMS symmetrical. For - switches with Uni- Rupter, the one-second rating is 12,00 amperes RMS symmetrical. The momentary ratings of the switches equal or exceed the interrupting ratings of the fuses. 14 S&C Specification Bulletin 2-31

15 S&C Power Fuses s SM and SML RECOMMENDED HANDLING TOOLS Item Style For Power Fuse Grappler Disconnect 4 Opening SM-20,m,m, 4423 Large Clamp Disconnect 4 Opening j 4410R3 Locking Prong Non-Disconnect,m,j S 4404 Universal Pole Refer to Specification Bulletin m Rated and below. SMU-20 Fuse Units and Holders rated 34. can be removed by hand after properly grounding the upper and lower live parts of the mounting. j Rated and below. Holders rated or 34. can be removed by hand after properly grounding the upper and lower live parts of the mounting. S&C Specification Bulletin

16 S&C Power Fuses s SM and SML SM-20 Disconnect, 4 Opening Max,,, and 34. Nom. Max BIL Amps, Max Mounting1 (including Live Parts, less Fuse- Unit End Fittings) Fuse-Unit End Fittings2 Live Parts (less Fuse- Unit End Fittings) Dimensions in Inches A 1 A 2 B C D F M R Mtg. Net Weight, Lbs. Fuse-Unit End Fittings SM SM Z\, 8Z\, 6Z\v 22C\, Z\x 17Z\v 23Z\x 12 1 SM SM C\, 9C\, 7Z\x 26C\v 3Z\v 22Z\v 34Z\x 18Z\x SM SM M\, 11M\, 10 32C\v 3Z\v 28Z\v These mountings cannot be supplied for back connection. 2 Includes Silencer. 16 S&C Specification Bulletin 2-31

17 S&C Power Fuses s SM and SML and Disconnect, 4 Opening, 300, and 400 Max, 4.8,, and m These holes may be used for attachment of barriers only when the minimum recommended energized part-to-barrier clearance and minimum recommended barrier-to-ground clearance (in vicinity of energized parts), as listed in S&C Data Bulletin 2-62, have been met or exceeded. Amps, Max Nom. Max BIL Mounting1 (including Live Parts, less Holder) SM-4 SM-4 SM-4 SM- SM- SM R R R R R R1 Holder R2d Live Parts (less Holder) 86632R2r R R2d 86642R2r 86643R2 1 These mountings cannot be supplied for back connection. 2 Includes Silencer () or Snuffler () R R R2 d Rated 7.2 nominal, for use in listed 4.8- mountings for system voltages through 4.8, or in discontinued 7.2- mountings for system voltages through 7.2. Dimensions in Inches Net Weight, Lbs. A 1 A 2 B C D E F G H J K L M R Mtg. Holder B\, 8Z\, 6C\v 9Z\v 7Z\x 14B\, 1C\v 14 B\, 8Z\, 6C\v 9Z\v 7Z\x 14B\, 1 C\v C\v C\v 4Z\, 4Z\, 4Z\, M\, 12Z\x 7 8M\, 16Z\x 7 8M\, 20C\v 7Z\x Z\x 16Z\x 20C\v 7 7 7Z\x 4Z\v 4Z\v 4Z\v 4Z\v 7C\v 7C\v 6 7C\v 7C\v M\, Z\x 13C\v 29 3M\, 30M\, 16Z\v 34 3M\, 41 22M\, 3 4M\, 29Z\v 1Z\v 3 4M\, 34Z\x 17C\v 40 4M\, 44Z\, 24Z\v Z\x r Rated 14.4 nominal, for use in listed - mountings or in discontinued mountings. 32 S&C Specification Bulletin

18 S&C Power Fuses s SM and SML and Disconnect, 4 Opening and 300 Max, 34. Amps, Max Nom. Max BIL Mounting1 (including Live Parts, less Holder) Holder2 Live Parts (less Holder) Dimensions in Inches Net Weight, Lbs. D E K L M R Mtg. Holder SM d 86634R Z\, 8M\, 4 3M\, 48 24C\v SM r 86644R R M\, 0M\, 26Z\, These mountings cannot be supplied for back connection. 2 Includes Silencer () or Snuffler (). d Supersedes 34.-, 10- BIL SM-4 Mounting, ; and 34.-, - BIL SM-4 Mounting, 18734R1. r Supersedes 34.-, 10- BIL SM- Mounting, ; and 34.-, - BIL SM- Mounting, 18744R2. 18 S&C Specification Bulletin 2-31

19 S&C Power Fuses s SM and SML Disconnect, 4 Opening 720 Max, 4.8 and Amps, Max Nom. Max BIL Mounting1 (including Live Parts, less Holder) SM- SM- 8710R4 8712R4 Holder R2d 86642R2r 1 These mountings cannot be supplied for back connection. 2 Holders are rated 400 amperes maximum. Two holders required with each mounting. 3 Includes Snuffler. Live Parts (less Holder) 8719R3 8719R3 Dimensions in Inches Net Weight, Lbs. A B C F M R Mtg. Holder C\v 8Z\v 7 Z\x Z\x 16Z\x 29B\, 3C\, 1Z\x Z\x d Rated 7.2 nominal, for use in listed 4.8- mountings for system voltages through 4.8, or in discontinued 7.2- mountings for system voltages through 7.2. r Rated 14.4 nominal, for use in listed - mountings or in discontinued mountings. S&C Specification Bulletin

20 S&C Power Fuses s SM and SML Disconnect, 4 Opening Max, and Amps, Max Nom. Max BIL 1 Mounting1 (including Live Parts, less Fuse-Unit End Fittings) Fuse-Unit End Fittings2 Dimensions in Inches Net Weight, Lbs. 1 These mountings cannot be supplied for back connection. 2 Includes Silencer A 1 A 2 C D F J M R Mtg. 8C\, 9Z\x 8 Z\, 9 C\, 22C\, 26 C\v 4 3Z\v 18 22Z\v 6Z\v 7Z\v 31Z\x 34C\v 19Z\x 20 B\, Fuse-Unit End Fittings S&C Specification Bulletin 2-31

21 S&C Power Fuses s SM and SML Disconnect, 4 Opening Max, and Nom. Max BIL Amps, Max 1 Mounting1 (including Live Parts, less Holder) SML-4 SML Holder2 Dimensions in Inches Net Weight, Lbs. 9232r 9233 A 1 A 2 C F J M R Mtg. Holder 8C\, 9Z\x 8 Z\x 9 C\v 22C\, 26 C\v 17C\v 22Z\v 6Z\v 7Z\v 33 36C\v Z\, These mountings cannot be supplied for back connection. 2 Includes Silencer. r Rated 14.4 nominal, for use in listed - mountings. S&C Specification Bulletin

22 S&C Power Fuses s SM and SML,, and S Non-Disconnect, 300, and 400 Max, 4.8,, and Nom. Max BIL Amps, Max Mounting1 (including Live Parts, less Holder) SM-4 SM-4 SM-4 SM- SM- SM- 87R R R R R3 8703R1 Holder R2d 86802R2w 86803R R2d 86812R2w Live Parts (less Holder) R2 8709R2 Dimensions in Inches Net Weight, Lbs. A 1 A 2 B C D E F H J K N P R Mtg. Holder B\, 8Z\, 6B\, 9Z\, 7Z\x Z\, Z\, 14B\, 1 B\, C\v Z\, M\, 8C\, 6M\, 9C\, 7Z\x Z\v Z\v 86813R2 8709R2 14M\, 1M\, C\v Z\v 12 8C\, 8C\, 8C\, 12Z\x 16Z\x 20C\v 4Z\v 4Z\v 7C\v 7C\v 6 4Z\x 4Z\x 4Z\x 3Z\, 3Z\, 3Z\, C\, C\, C\, 13 1Z\x 33Z\x SM R3 S 86402R2w 8709R2 8C\, 9C\, 7Z\x 32 Z\v 12Z\x 16Z\x 4Z\v 7C\v Z\v 3B\, 6Z\x These mountings cannot be supplied for back connection. 2 Includes Silencer (), Snuffler (), or Super Snuffler (SM SS). d Rated 7.2 nominal, for use in listed 4.8- mountings for system Z\x 16Z\x 20C\v 4Z\v 4Z\v 7C\v 7C\v 6 Z\v Z\v Z\v 3B\, 3B\, 3B\, 6Z\x 6Z\x 6Z\x 22 1Z\x 18 24B\, Z\x voltages through 4.8, or in discontinued 7.2- mountings for system voltages through 7.2. w Rated 14.4 nominal, for use in listed - mountings or in discontinued mountings S&C Specification Bulletin 2-31

23 S&C Power Fuses s SM and SML and Non-Disconnect and 300 Max, 34. K Nom. Max BIL Amps, Max Mounting1 (including Live Parts, less Holder) Holder2 Live Parts (less Holder) Dimensions in Inches Net Weight, Lbs. A 1 A 2 D E K N P R Mtg. Holder SM d 86804R C\, 17 C\, Z\, 8C\, 4Z\x 3Z\, C\, 23C\v SM r 86814R2 8709R2 16B\, 17 B\, Z\v 11 Z\v 3B\, 6Z\x 26Z\v These mountings cannot be supplied for back connection. 2 Includes Silencer () or Snuffler (). d Supersedes 34.-, 10- BIL SM-4 Mounting, ; and 34.-, - BIL SM-4 Mounting, R1. r Supersedes 34.-, 10- BIL SM- Mounting, ; and 34.-, - BIL SM- Mounting, R2. S&C Specification Bulletin

Specifications. S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv)

Specifications. S&C Manual PME Pad-Mounted Gear Outdoor Distribution (14.4 kv and 25 kv) Outdoor Distribution (14.4 kv and 25 kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under WARRANTY QUALIFICATIONS

More information

Specifications. S&C Manual Vista Underground Distribution Switchgear Outdoor Distribution (15.5 kv through 38 kv)

Specifications. S&C Manual Vista Underground Distribution Switchgear Outdoor Distribution (15.5 kv through 38 kv) Outdoor Distribution ( kv through kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply. SPECIAL TO THIS PRODUCT: INCLUSIONS: S&C Vista

More information

SPECIFICATIONS. S&C Switch Operators Type PM SPECIFICATION BULLETIN 669-31. For Field Retrofit on Manual PMH, PMS, and PME Pad-Mounted Gear

SPECIFICATIONS. S&C Switch Operators Type PM SPECIFICATION BULLETIN 669-31. For Field Retrofit on Manual PMH, PMS, and PME Pad-Mounted Gear S&C Switch Operators Type PM Outdoor Distribution For Field Retrofit on Manual PMH, PMS, and PME Pad-Mounted Gear SPECIFICATIONS Conditions of Sale STANDARD: Seller s standard conditions of sale set forth

More information

Specifications. S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

Specifications. S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv) Outdoor Transmission (69 kv through 230 kv) Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified under SPECIAL WARRANTY

More information

S&C TripSaver Dropout Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

S&C TripSaver Dropout Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv S&C TripSaver Dropout Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing S&C s new TripSaver Dropout Recloser: A better solution for overhead lateral circuit protection at

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

S&C Power Fuses Types SM-4 and SM-5 242-30. For use with SM Refill Units Outdoor Distribution (4.16 kv through 34.5 kv) DESCRIPTIVE BULLETIN

S&C Power Fuses Types SM-4 and SM-5 242-30. For use with SM Refill Units Outdoor Distribution (4.16 kv through 34.5 kv) DESCRIPTIVE BULLETIN S&C Power Fuses Types SM-4 and SM-5 For use with SM Refill Units Outdoor Distribution (4.16 kv through 34.5 kv) Supersedes Descriptive Bulletin 242-30 dated 7-12-93 2000 S&C ELECTRIC COMPANY DESCRIPTIVE

More information

Specifications. Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply. SPECIAL TO THIS PRODUCT:

Specifications. Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply. SPECIAL TO THIS PRODUCT: Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply. SPECIAL TO THIS PRODUCT: INCLUSIONS: S&C Switch Operators Type CS-1A are high-speed

More information

Installation. S&C Loadbuster Disconnect Switches Branch Feeder, Main Feeder, Crossarm, and Station Styles

Installation. S&C Loadbuster Disconnect Switches Branch Feeder, Main Feeder, Crossarm, and Station Styles S&C Loadbuster Disconnect Switches Branch Feeder, Main Feeder, Crossarm, and Station Styles Outdoor Distribution (14.4 kv through 34.5 kv) Installation Table of Contents Section Page Section Page Introduction

More information

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal

More information

LIVE-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV

LIVE-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV Manual Live-Front TYPE PSI/II MANUAL LIVE-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV The PSI/II is Federal Pacific's line of live-front pad-mounted switchgear (available as UL Listed) built to IEEE C37.74

More information

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS)

Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) August, 2009 Vertical Break Parallel (VBP) / Vertical Break Slant (VBS) Type VBPA (Aluminum) / Type VBPC (Copper) Type VBSA (Aluminum) / Type VBSC (Copper) PASCOR Air Break Switch Technology PASCOR offers

More information

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd

OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

Bypass switches. Type B-1 and type B-2. Answers for energy.

Bypass switches. Type B-1 and type B-2. Answers for energy. Bypass switches Type B-1 and type B-2 Answers for energy. Eliminate voltage regulator bypass switch problems with type B-1 and type B-2 Overview Type B-1 The Bridges Electric type B-1 regulator bypass

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv S&C TripSaver II Cutout-Mounted Recloser For enhanced lateral circuit protection at 15 kv and 25 kv Introducing S&C s TripSaver II Cutout-Mounted Recloser: A better solution for overhead lateral circuit

More information

S&C Cypoxy Insulators Indoor and Outdoor Distribution

S&C Cypoxy Insulators Indoor and Outdoor Distribution New Publication 1988 Page 1 of 7 Introduction Porcelain insulators traditionally have been the most widely applied insulators in electrical transmission and distribution systems. Although porcelain has

More information

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope 3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service

More information

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric

More information

Corner-Grounded Delta (Grounded B Phase) Systems

Corner-Grounded Delta (Grounded B Phase) Systems Data Bulletin 2700DB0202R03/12 09/2012 Replaces 2700DB0202R2/09 dated 02/2009 Corner-Grounded Delta (Grounded B Phase) Systems Class 2700 Retain for future use. Introduction Corner-grounded delta systems

More information

SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR

SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80 Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.

Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional

More information

Customer Substation Manual 08/05/02

Customer Substation Manual 08/05/02 Customer Substation Manual Table of Contents Section Page 2 of 85 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation

More information

Primary and Secondary Electrical Distribution Systems

Primary and Secondary Electrical Distribution Systems Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility

More information

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches

More information

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES

PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium

More information

SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS

SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS PRIMARY METER POLE ELECTRIC SYSTEM BULLETIN No. 753 JUNE 1993, 2 ND PRINTING APRIL 2002 (Supersedes issue dated March 1983 and incorporates Nov.

More information

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

This section applies to the design and installation of transformers.

This section applies to the design and installation of transformers. ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior

More information

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR MEDIUM VOLTAGE METAL CLAD SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, connection and testing of the medium voltage switchgear. 1.2 SWITCHGEAR FEATURES

More information

S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014)

S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014) 1.0 GENERAL S. C. Electric Cooperative s Specification for a Three-Phase, Padmounted URD Transformer (Revised 12/2014) 1.1 This specification covers the electrical and mechanical characteristics of Three-Phase,

More information

Current Transformers

Current Transformers Supersedes December 2002 General Description Eaton s low voltage current transformers are available in both solid core and split core designs. Engineered for electronic metering applications, all solid

More information

OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B

OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B The OVR-3SP three-phase recloser style guide aids in the proper selection of your OVR-3SP style number. The OVR-3SP

More information

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy

More information

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1 How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module

More information

Distribution Dry Type Transformers

Distribution Dry Type Transformers 8 TRASFORMERS Distribution Dry Type Transformers Table (Contact Sales office for List Price) (commonly used) 1a. 115 C Rise F 1b. 80 C Rise B 4. Wall Brackets1 W 6. Low noise XdB below std. LX Type bg

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

Cable/Conduit Conversion

Cable/Conduit Conversion Cable/Conduit Conversion Busway can be used in many applications where cable and conduit are more commonly used. The question arises, Why use busway instead of conventional cable and conduit? Benefits

More information

Type K current limiting fuse canister Technical information and installation guide

Type K current limiting fuse canister Technical information and installation guide Transformer components Type K current limiting fuse canister Technical information and installation guide The Type K current limiting fuse canister provides an air-insulated receptacle for general-purpose

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES PURPOSE This section provides substation design information for Load Entities interconnected at transmission voltage

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document

More information

PREFACE. The products covered by this Guide are:

PREFACE. The products covered by this Guide are: PREFACE UL has developed the Molded-Case Circuit Breaker (MCCB) Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in

More information

SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR

SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed

More information

TOP RUNNING SINGLE GIRDER BRIDGE CRANE

TOP RUNNING SINGLE GIRDER BRIDGE CRANE SECTION 14630 TOP RUNNING SINGLE GIRDER BRIDGE CRANE 1.01 SUMMARY PART 1- GENERAL A. The work required under this section shall include the designing, manufacturing, shipping, installing and field testing

More information

Metallic and Non-Metallic Air Conditioning Disconnects. A Complete Family of. Disconnects with Exclusive Time Saving Features

Metallic and Non-Metallic Air Conditioning Disconnects. A Complete Family of. Disconnects with Exclusive Time Saving Features Metallic and Non-Metallic Air Conditioning Disconnects A Complete Family of Disconnects with Exclusive Time Saving Features Enclosed Molded Case Disconnect Switch Not-Fusible The preferred molded case

More information

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.

More information

2.4 kv to 34.5 kv SP-1099

2.4 kv to 34.5 kv SP-1099 Specifications for Customer Electric Service 2.4 kv to 34.5 kv SP-1099 FORWARD...1 CHAPTER 1 - PRIMARY METERED SERVICE...4 General Service Information...4 CA-206...6 CA-208A...7 Section 1...8 Existing

More information

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16465 PAGE 1 SECTION 16465

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16465 PAGE 1 SECTION 16465 KNOXVILLE, TENNESSEE SECTION 16465 PAGE 1 SECTION 16465 PART 1 - GENERAL 1.01 The switchgear shall be in accordance with the one-line diagram, and shall conform to the following specification. 1.02 The

More information

Linear Luminaire with LED Series EXLUX 6402/2

Linear Luminaire with LED Series EXLUX 6402/2 > Latest LED technology with a high luminous efficacy and a long service life > As pendant light fitting or side entry lamp > Central locking > All-pole disconnection by means of an N/C switch when the

More information

PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property.

PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property. INTRODUCTION These rules are issued for use by Customers, builders, electrical contractors, architects, engineers, etc. The rules require the installation of safe and adequate wiring and electrical equipment,

More information

261000 Medium Voltage Electrical Distribution

261000 Medium Voltage Electrical Distribution Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

16300 MEDIUM VOLTAGE DISTRIBUTION

16300 MEDIUM VOLTAGE DISTRIBUTION 16300 MEDIUM VOLTAGE PART 1: GENERAL 1.01 SYSTEM DESCRIPTION A. Most new loads will be served from the underground electric distribution system. This system is a primary open loop configuration served

More information

B. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems.

B. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems. SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes wall switches; wall dimmers; receptacles; multioutlet assembly; and device plates and decorative box covers. B. Related

More information

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase

More information

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability

More information

Approved Meter Sockets and Cabinets

Approved Meter Sockets and Cabinets Single Unit Residential Guide 1 PHASE, 120/240 VOLT S METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to center of meter ± 100 mm ( 4

More information

Sample - No Commercial Use

Sample - No Commercial Use COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort

More information

Featuring Manual, Remote Supervisory, and Source-Transfer Models S&C Vista Underground Distribution Switchgear

Featuring Manual, Remote Supervisory, and Source-Transfer Models S&C Vista Underground Distribution Switchgear Featuring Manual, Remote Supervisory, and Source-Transfer Models S&C Vista Underground Distribution Switchgear Outdoor Distribution, 15.5 kv through 38 kv Vista Underground Distribution Switchgear Addresses

More information

GTEC transfer switch open transition

GTEC transfer switch open transition GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility

More information

Square D Safety Switches

Square D Safety Switches Square D Safety Switches Power isolation solutions for daily activities and emergencies TM Make the most of your energy SM Square D Safety Switches Setting the standard for perfomance, quality, and reliability

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

Electrical Service Guidelines

Electrical Service Guidelines Electrical Service Guidelines Middle Tennessee Electric Membership Corporation Revised: May 23, 2013 MTEMC's Electrical Guidelines TABLE OF CONTENTS Right-of-Way Clearance Guide 3 MTEMC Requirements 4

More information

AMPSEAL* Automotive Plug Connector and Header Assembly

AMPSEAL* Automotive Plug Connector and Header Assembly AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2

More information

S & C E L E C T R I C C O M P A N Y

S & C E L E C T R I C C O M P A N Y Descriptive Bulletin 811-30 September 11, 2006 Supersees Descriptive Bulletin 811-30 ate 5-12-03 2006 Here Are Five Reasons Why Loabuster Is the Better Way: 1 Range S&C s Loabuster unlike loabreak cutouts

More information

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit

More information

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001 > As wall, ceiling and pendant light fitting or side entry lamp > Version with 2 lamps: 18 W, 36 W and 58 W > Central locking > All-pole disconnection by means of an N/C switch when the lamp is opened

More information

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

Learning Module 13: Panelboards and Switchboards. 101 Basic Series Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and

More information

Note: Maintenance personnel shall seek Engineering assistance in applying this specification to the procurement and installation of this equipment.

Note: Maintenance personnel shall seek Engineering assistance in applying this specification to the procurement and installation of this equipment. Section 16311 Underground Distribution Switchgear 15 kv Class Note: Maintenance personnel shall seek Engineering assistance in applying this specification to the procurement and installation of this equipment.

More information

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement

More information

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions

More information

Cable Accessories. for Extruded Dielectric Cable 69kV - 230kV Rated. Catalog Python13

Cable Accessories. for Extruded Dielectric Cable 69kV - 230kV Rated. Catalog Python13 Cable Accessories for Extruded Dielectric Cable 69kV - 230kV Rated Components used in cable systems 100% Tested Factory Molded For outdoor applications through 230kV For gas insulated substations and transformers

More information

Explosion-Proof Electric Unit Heaters

Explosion-Proof Electric Unit Heaters Type FX4 FX4 Explosion-Proof Electric Air Heaters FX4 heaters are UL listed and/or CSA certified for use in hazardous locations. They are designed for dry indoor industrial applications such as oil refineries,

More information

S&C Circuit-Switchers Mark VI

S&C Circuit-Switchers Mark VI S&C Circuit-Switchers Mark VI Outdoor Transmission (69 kv through 138 kv) Mark VI Circuit-Switcher with Pre-insertion Inductors... the most reliable way to switch and protect substation capacitor banks

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

Instructions For SF 6 Refill Kit

Instructions For SF 6 Refill Kit S&C Vista Underground Distribution Switchgear UnderCover, Vault-Mounted, and Pad-Mounted Styles Instructions For SF 6 Refill Kit TABLE OF CONTENTS Section Page Section Page INTRODUCTION..................................

More information

Equipment. Metering. Metering Equipment 1. Contents

Equipment. Metering. Metering Equipment 1. Contents 1 October 00 Utilities Servicing Texas Metering Equipment Contents Page Logic ing System.................................... Product Selection by Utility CenterPoint Energy (Reliant & HL&P).............................

More information

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee

More information

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules. Fuseology Medium Voltage Fuses General Fuses above are classified under one of three classifications as defined in ANSI/IEEE C37.40. 1. General Purpose Current-Limiting Fuse: A fuse capable of interrupting

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12 Bulletin DB-111B12 TP-C2 Motor Operator CLEAVELAND / PRICE INC. 14000 Rt. 993, Trafford, PA 15085 (724) 864-4177 FAX (724) 864-9040 Email: sales@cleavelandprice.com Cleaveland/Price Type TP-C2 Motor Operator

More information

Bolted contact switches. Pringle switches

Bolted contact switches. Pringle switches Bolted contact switches Pringle switches Eaton s Pringle bolted contact switches History Eaton s PringleT switches have helped pioneer the development of high-quality electrical products for commercial

More information

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED

More information

Mini Power-Zone Unit Substation

Mini Power-Zone Unit Substation Catalog 7440CT0901 2009 Class 7440 CONTENTS Description............................................. Page Product Description...........................................2 General Information...........................................3

More information

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content

More information