SECTION MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
|
|
|
- Pierce Williams
- 10 years ago
- Views:
Transcription
1 SECTION MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. This Section specifies the medium voltage switchgear and fusing for buildings and structures. 2. Provide all labor, materials, and equipment as necessary to complete all work as indicated on the drawings, and as specified herein for a complete operating system. 3. Furnish, install, and connect complete for operation new metal-enclosed primary switch unit and make all necessary wiring connections to the primary feeders as required by the drawings and for a complete working job. 4. Medium-voltage switchgear shall include the following items at a minimum: a. Medium voltage fusible interrupter switchgear b. Medium voltage fuses 1.3 SUBMITTALS A. Shop Drawings 1. Medium-voltage switchgear 2. Medium-voltage fuses 1.4 QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction. B. Comply with NFPA 70, National Electrical Code C. The switchgear shall conform to the following: MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
2 1. ANSI C IEEE Standard NEMA SG-5 4. National Electrical Code Article (e) D. Guarantee 1. Furnish full parts and labor warranty to cover the switchgear for two years from shipment 1.5 MATERIAL TURNED OVER TO OWNER A. Products Supplied But Not Installed Under This Section 1. Provide 3 spare primary fuses for each size used in the primary interrupter switches. 2. Portable control station with 50 ft. cord. 3. Test accessory. 4. Maintenance cable (nine pin). 5. 8'-0" jumper cable, two complete sets of three. 6. Two jumper storage bags. 7. Shotgun stick. 8. Shotgun stick storage bag. 9. Voltage tester with audio/visual signals. 10. Pentahead socket. 11. Universal Pole 8'-0" long. 12. Grappler handling tool. 13. Large clamp. 14. Any other miscellaneous components and accessories. PART 2 - PRODUCTS 2.1 MANUFACTURERS A. Basis-of-Design Product: S&C Electric. B. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. S&C Electric. 2. Eaton Corporation; Cutler-Hammer Products. 3. Square D; Schneider Electric. 4. Powercon Corporation. MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
3 2.2 GENERAL A. Medium voltage primary switch unit shall consist of two 15 KV fused primary selector switches with automatic throwover for the incoming feeders and 15 KV fused primary switch and shall be furnished complete with channels. B. Medium voltage substation primary feeders switches unit shall consist of two 15 KV fused primary selector switches manually operated for the two feeders and 15 KV primary termination compartment, as indicated on drawings, and shall be furnished complete with channels. C. The ratings for the integrated switchgear assembly shall be as follows: 1. kv, Nominal kv, Maximum Design kv, BIL Main Bus Continuous, Amperes Short-Circuit Ratings a. Amperes, RMS Symmetrical 25,000 b. MVA Three-Phase Symmetrical at Rated Nominal Voltage Duty-Cycle Fault-Closing Amperes, RMS Asymmetrical 40,000 D. The momentary and duty-cycle fault-closing ratings of switches, momentary rating of bus, and interrupting ratings of fuses shall equal or exceed the short-circuit ratings of the metal-enclosed switchgear. E. The interrupter switches shall have two-time duty-cycle fault-closing integrated switchgear assembly. These ratings define the ability to close the interrupter switch, either alone (unfused) or in combination with the appropriate power fuse, against a three-phase fault with asymmetrical current in at least one phase equal to the rated value, with the switch remaining operable and able to carry and interrupt rated current. Tests substantiating these ratings shall be performed at maximum design voltage applied for at least ten cycles and certified copies of tests submitted for record information. F. The switch unit shall be arranged to provide control of switches from the front as indicated on the drawing. Unit shall be free standing, consisting of cubicles arranged for bolting together on concrete pad. Cubicles shall be welded, reinforced sheet steel enclosures with hinged doors. Complete unit shall be rustproofed and painted two coats. G. The dimensions of the unit as indicated on the drawing are approximate. These shall be varied to suit the particular equipment furnished and such that overall dimensions of the completely assembled unit shall suit the space, subject to the approval of the Engineers. Complete shop drawings shall be submitted to the Engineers before fabrication. H. The main buss shall be non-insulated flat copper bar of a minimum 56%IACS conductivity, mounted on track resistant Cycloaliphatic bus supports. The ground bus shall consist of copper bar CA11-, square edge, hard temper per ASTM B187. The contact surface for each bus connection shall be silver plated and tightly bolted to insure maximum conductivity. MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
4 I. Primary switch unit shall have a ground bus extending through each compartment for its entire length. Provide connections to ground system as indicated on drawing. J. The bracing supporting the switches in the enclosure shall be of sufficient strength to permit laying the unit on its side. Also, the crating shall be arranged to permit laying the unit on its side for shipping. K. The primary switch unit shall be completely wired, assembled, and operationally checked at the factory. 2.3 SELECTOR SWITCHES A. Primary selector switches shall be fused, heavy duty, quick-make quick-break, 15 KV, 600 ampere, 3 pole, 95 KV BIL, with a minimum load interrupting rating of 600 amperes. B. Primary switch shall be provided with three 15 KV fuses sized to properly protect the unit substation transformer. Fuses shall be power type with condensers and minimum interrupting rating of 600 MVA. Fuses shall be S & C, General Electric, Bussmann, or Gould Shawmat. C. Each primary selector switch shall have diamond mesh expanded metal inner door with an engraved plate reading - WARNING - OPEN SWITCH BLADES ARE ENERGIZED -. D. Primary selector switch units shall each be provided with lugs inside enclosure for termination of 2/0 AWG or 350 KCMIL as necessary with outdoor type Class 1 terminations, 15 KV single conductor cable entering the compartment. E. Primary switches shall have mechanically interlocked doors to prevent access to switches or fuses when the switch is closed. 2.4 COMMON BUS PRIMARY-SELECTIVE AUTOMATIC THROWOVER A. The automatic throwover unit shall automatically close and open the primary selector switches by means of three 7.62KV-120 volt control transformers with primary fuses on each incoming line, and necessary motor drives, limit switches, relays, and accessories. The automatic throwover unit shall include the following features: 1. Provisions for disconnecting the motor operators from the primary selector switches for manual operation of the switches, and disconnecting mechanism to allow testing automatic transfer equipment without operating 600 amp, 15 KV selector switch. 2. Three phase sensing. 3. Interlock to prevent closing both primary selector switches simultaneously, except for manual operation. MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
5 4. Three current transformers and necessary relays shall be provided with necessary controls to prevent transfer in the event of a phase-to-phase bus fault. 5. Source selector to permit random selection of either incoming line as preferred or alternate source. 6. Field selection of Automatic Hold Return to select automatic return to a preferred source or holding on the alternate source after the initial automatic transfer operation. 7. Field selection of open transition or closed transition on automatic retransfer. 8. Field selection of Automatic-Manual operation. 9. Source-voltage indicating lamps of the push-to-test type that shall indicate presence of correct voltage on each high-voltage source. 10. A field-adjustable time delay between loss of voltage and initiation of automatic switching to confirm that loss of voltage on either source is not transient. The timer range shall be from 1/4 to 10 seconds. 11. A field-adjustable time delay between return of voltage and initiation of retransfer switching to confirm that return of voltage on either source is not temporary. The timer range shall be from 1/2 to 15 minutes. 12. An indicating lamp of the push-to-test type which shall indicate that all switch operators are coupled to their respective interrupter switches and are in the correct positions; that all doors providing access to interrupter switches powered by stored-energy switch operators are closed and latched; that the source-transfer control is in the automatic mode; and that all control circuitry is properly connected for automatic transfer. 13. Pushbutton test switches shall be provided to simulate loss of voltage on either source and to allow convenient field testing of the entire source-transfer scheme. 14. Controls located in a removable drawer and a low voltage compartment completely isolated from high voltage circuits. 15. Switch operating mechanism shall be removable for repairs and capable of decoupling without access to high-voltage compartment. It shall be in a grounded compartment. 16. Current transformer and relays for ground fault blocking to prevent transfer if fault occurs in this unit. B. Primary automatic throwover switch shall be S & C utilizing S & C Micro-AT Source-Transfer Control. MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
6 2.5 PRIMARY SWITCH ATS - EM A. Primary switch shall be fused, heavy duty, quick-make quick-break, 15 KV, 600 ampere, 3 pole, 95 KV BIL, with a minimum load interrupting rating of 600 amperes. B. Primary switch shall be provided with three 15 KV fuses sized to properly protect the unit substation transformer. Fuses shall be power type with condensers and minimum interrupting rating of 600 MVA. Fuses shall be S & C, General Electric, Bussmann, or Gould Shawmut. C. Switches shall be provided with lugs for No. 2/0 AWG, 15 KV cable connection and sufficient space for termination of cables and terminators. D. Primary switches shall have mechanically interlocked doors to prevent access to switches or fuses when the switch is closed. 2.6 OUTDOOR SWITCHGEAR A. Outdoor Finish 1. The enclosure finish shall conform to or exceed the applicable requirements of ANSI C During fabrication, the areas of structural parts which may later become inaccessible, such as folded edges and overlapping members, shall be given an iron-oxide zincchromate anticorrosion primer to ensure that all surfaces are protected. 3. Full coverage at joints and blind areas shall be achieved by processing enclosures independently of components such as doors and roofs before assembly into the unitized structures. 4. To remove oils and dirt, to form a chemically and anodically neutral conversion corrosion, all surfaces shall undergo a thorough pretreatment process comprised of a fully automated system of cleaning, rinsing, phosphatizing, sealing, drying, and cooling before any protective coatings are applied. By utilizing an automated pretreatment process, the enclosure shall receive a highly consistent thorough treatment, eliminating fluctuations in reaction time, reaction temperature, and chemical concentrations. 5. After pretreatment, protective coatings shall be applied that shall help resist corrosion and protect the steel enclosure. To establish the capability to resist corrosion and protect the enclosure, representative test specimens coated by the enclosure manufacturer s finishing system shall satisfactorily pass the following tests: a hours of exposure to salt-spray testing per ASTM B 117 with: i. Under-film corrosion not to extend more than 1/32 in. from the scribe, as evaluated per ASTM D 1654, Procedure A, Method 2 (scraping); and ii. Loss of adhesion from bare metal not to extend more than 1/8 in. from the scribe. MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
7 b hours of humidity testing per ASTM D 4585, with no blistering as evaluated per ASTM D 714. c. 500 hours of ultraviolet-accelerated weathering testing per ASTM G 53 using lamp UVB-313, with no chalking as evaluated per ASTM D 659, and no more than a 10% reduction of paint gloss as evaluated per ASTM D 523. d. Crosshatch-adhesion testing per ASTM D 3359 Method B, with no loss of paint. e. 160-inch-pound impact, followed by adhesion testing per ASTM D 2794, with no paint chipping or cracking. f cycles of abrasion testing per ASTM 4060, with no penetration to the substrate. g. Certified test abstracts substantiating the above capabilities shall be furnished upon request. 6. A heavy coat of insulating no-drip compound shall be applied to the inside surface of the roof structure to prevent condensation of moisture thereon. 7. After the enclosures are completely assembled and the components (switches, fuses, bus, etc.) are installed, the finish shall be inspected for scuffs and scratches. Blemishes shall be touched up to restore the protective integrity of the finish. 8. Touch-up materials with complete instructions shall be included with each shipment of metal-enclosed switchgear, for touch-up in the field. 9. The finish shall be light gray, satisfying the requirements of ANSI Standard Z55.1 for No. 61. TGIC polyester powder applied electro statically through air. Following paint application, parts shall be baked to produce a hard durable finish. The average thickness of the paint film shall be 2.0 mils. Paint film shall be uniform in color and free from blisters, sags, flaking and peeling. 10. Adequacy of paint finish to inhibit the buildup of rust on ferrous metal materials shall be tested and evaluated per paragraphs of ANSI C Salt spray withstand tests in accordance with ASTM #D-1654 and #B-117 shall be periodically performed on a sample to confirm conformance with the corrosion resistance standard of at least 2500 hours minimum (outdoor equipment). B. Outdoor Features 1. Enclosure Ventilation a. Ventilation openings shall be provided at the top and bottom on the front and rear of each bay. Ventilation openings on the front of arc-resistant switchgear shall be provided at the top only. b. Vents shall be rain-resistant and corrosion-resistant. c. Each vent shall have an inside screen and baffle to exclude insects and to protect against insertion of foreign objects. d. In consideration of exceptionally high concentrations of airborne dust, externally accessible glass-fiber filters shall be provided. 2. Lifting eyes shall be removable. Sockets for lifting eyes shall be blind-tapped. MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
8 3. Gasketing and Sealing a. Door openings and openings for hinged bolted panels (and bolted panels providing access to low-voltage components) shall have resilient compression gasketing to prevent water from entering the enclosure. b. Gasket seals shall be provided at the top and side edges of adjoining bays to prevent water entry between the double walls. c. The top and both sides of bus openings between bays shall be covered with channel gaskets as an additional protection against entrance of water, or external labyrinthine metal rainshields shall be provided over enclosure roof flanges between adjacent bays. d. Roofs shall be weather-sealed in place with a suitable sealant. 4. Space Heaters a. Space heaters 120V AC with sheaths of high-temperature chrome steel shall be provided to maintain air circulation inside the enclosure. b. There shall be a space heater in each bay. c. Space heaters shall be wired to generator load center. d. A low-voltage circuit breaker shall be provided in the strip heater circuit. 2.7 METERING SECTION A. Provide Metering Section with provisions for utility supplied PT s and CT s. 2.8 SUBSTATION PRIMARY FEEDERS SWITCHES A. Primary feeder switches shall be fused, heavy duty, quick-make quick-break, 15 KV, 600 ampere, 3 pole, 95 KV BIL, with a minimum load interrupting rating of 600 amperes. B. Primary feeder switches shall be provided with three 15 KV fuses sized to properly protect the unit substation transformer. Fuses shall be power type with condensers and minimum interrupting rating of 600 MVA. Fuses shall be S & C, General Electric, Bussmann, or Gould Shawmut. C. Each primary feeder switch shall have diamond mesh expanded metal inner door with an engraved plate reading - WARNING - OPEN SWITCH BLADES ARE ENERGIZED -. D. Primary switch units shall each be provided with lugs inside enclosure for termination of 2/0 AWG or 350 KCMIL as necessary with outdoor type Class 1 terminations, 15 KV single conductor cable entering the compartment. E. Incoming termination compartment shall be provided with lugs inside enclosure for termination of 2/0 AWG or 350 KCMIL as necessary with outdoor type Class 1 terminations, 15 KV single conductor cable entering the compartment. MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
9 2.9 SOURCE QUALITY CONTROL A. Before shipment of equipment, perform the following tests and prepare test reports: 1. Production tests on completed switchgear assembly according to IEEE C B. Assemble switchgear and equipment in manufacturer's plant and perform the following: 1. Functional tests of all features and control devices. 2. Functional test of all trip mechanisms. C. Prepare equipment for shipment. 1. Provide suitable crating, blocking, and supports so equipment will withstand expected domestic shipping and handling shocks and vibration. 2. Weatherproof equipment for shipment. Close connection openings to prevent entrance of foreign material during shipment and storage. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine elements and surfaces to receive switchgear for compliance with requirements for installation tolerances, required clearances, and other conditions affecting performance. 1. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. Anchor switchgear assembly to 4-inch (100-mm), channel-iron sill embedded in concrete base and attach by bolting. 1. Sills: Select to suit switchgear; level and grout flush into concrete base. 2. Concrete Bases as indicated on drawings. B. Temporary Lifting Provisions: Remove temporary lifting eyes, channels, and brackets and temporary blocking of moving parts from switchgear units and components. 3.3 IDENTIFICATION A. Identify field-installed conductors, interconnecting wiring, and components; provide warning signs as specified in Division 26 Section "Identification for Electrical Systems." 1. Provide engraved plastic-laminate signs, per Section , Identification for Electrical Systems, located on the front of each component, indicating the lines of information as follows: a. Incoming line Section 1) Designation (e.g., Incoming line 1 ). 2) Incoming line electrical characteristics (e.g., 13.2kV, 3PH, 3W, grounded ). b. Feeder Section MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
10 1) Designation (e.g., ATS-EM ). 2) Load served (e.g., Load served: Substation A - LBS-1 ). B. Diagram and Instructions: 1. Frame under clear acrylic plastic on front of switchgear. a. Operating Instructions: Printed basic instructions for switchgear, including control and key-interlock sequences and emergency procedures. b. System Power Riser Diagrams: Depict power sources, feeders, distribution components, and major loads. 2. Storage for Maintenance: Include a rack or holder, near the operating instructions, for a copy of maintenance manual. C. Phasing shall be marked at each termination location of 15KV cable in switchgear using 1 inch high, white, adhesive labels. Marking to be X, Y, Z reading left to right, or front to back while facing front of switchgear. 3.4 CONNECTIONS A. Cable terminations at switchgear are specified in Division 26 Section "Medium-Voltage Cables." B. Tighten bus joints, electrical connectors, and terminals according to manufacturer's published torque-tightening values. C. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical Systems." D. Connect wiring according to Division 26 Sections "Low-Voltage Electrical Power Conductors and Cables" and "Medium-Voltage Cables." 3.5 FIELD QUALITY CONTROL A. Prepare for acceptance tests as follows: 1. Test insulation resistance for each switchgear bus, component, connecting supply, feeder, and control circuit. 2. Test continuity of each circuit. B. Manufacturer's Field Service: Engage a factory-authorized service representative to perform the following: 1. Inspect switchgear, wiring, components, connections, and equipment installation. Test and adjust components and equipment. 2. Assist in field testing of equipment. 3. Report results in writing. C. Testing Agency: Engage a qualified independent testing and inspecting agency to perform field tests and inspections and prepare test reports. MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
11 D. Perform the following field tests and inspections and prepare test reports: 1. Perform each electrical test and visual and mechanical inspection stated in NETA ATS. Certify compliance with test parameters. Perform NETA tests and inspections for each of the following NETA categories: a. Switchgear. b. Source-Transfer Controls. c. Instrument transformers. d. Surge arresters. E. Remove and replace malfunctioning units and retest as specified above. 3.6 CLEANING A. On completion of installation, inspect interior and exterior of switchgear. Vacuum dirt and debris; do not use compressed air to assist in cleaning. Repair damaged finishes. 3.7 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain switchgear. END OF SECTION MEDIUM VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Sample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
SECTION 262413 SWITCHBOARDS
PART 1 - GENERAL... 1 1.1 RELATED DOCUMENTS... 1 1.2 SUMMARY... 1 1.3 DEFINITIONS... 1 1.4 SUBMITTALS... 2 1.5 QUALITY ASSURANCE... 3 1.6 DELIVERY, STORAGE, AND HANDLING... 3 1.7 PROJECT CONDITIONS...
IRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
RAY-MAX Integrated Solar Power Strip
RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...
Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
MEDIUM VOLTAGE METAL CLAD SWITCHGEAR
MEDIUM VOLTAGE METAL CLAD SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, connection and testing of the medium voltage switchgear. 1.2 SWITCHGEAR FEATURES
This section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
MCC Ratings. Voltage Rating
MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number
HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
Masterclad Medium Voltage Passive Arc-Resistant Switchgear
Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
A. Shop Drawing submittals shall include, but not be limited to, the following:
SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical
METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
A D D E N D U M # 3 QUESTIONS FROM BIDDERS: DATE: November 5, 2012. All Bidders. Jenne dos Santos, CBI Consulting Inc. City of Chelsea, MA
Page 1 of 10, Addendum No. 3 Temporary Garage Structure City of Chelsea, MA November 5, 2012 CBI Job No.: 12055-A A D D E N D U M # 3 DATE: November 5, 2012 TO: FROM: PROJECT: All Bidders Jenne dos Santos,
SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS
1 SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,
Display hidden notes to specifier. (Don't know how? Click Here) A. Advanced Upcoiling Security Grilles, power operated.
SECTION 08333 ADVANCED UPCOILING SECURITY GRILLE MODEL 600 ADV Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Advanced Upcoiling Security Grilles,
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium
DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT User Manual SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 - e-mail: [email protected]
PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE UL developed the Dead-Front Switchboard Marking Guide for code authorities, electric utilities, contractors, installers, users, designers, and other interested parties to aid in understanding deadfront
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
INSTALLATION INSTRUCTIONS FOR INTERNATIONAL 9000 SERIES ROOF TOP AIR CONDITIONERS
RV Products Division INSTALLATION INSTRUCTIONS FOR INTERNATIONAL 9000 SERIES ROOF TOP AIR CONDITIONERS Service Contact: Coast to Coast RV Services Pty Ltd. 20 George Young St. Auburn NSW 2144 Australia
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
SECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
PIP ELSSG02 Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv
Electrical Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv Table of Contents 1. Introduction...2 1.1 Purpose... 2 1.2 Scope... 2 2. References...2 2.1... 2 2.2 Industry
Switchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
DESIGN CLARIFICATION (DC)
DESIGN CLARIFICATION (DC) Owner: Victor Valley Wastewater Reclamation Authority Date: 03/03/2015 Contractor: W M Lyles Carollo Project No.: 8299A.20 Project Name: Subregional WRPs DC No.: 001 DC Title:
Customer Substation Manual 08/05/02
Customer Substation Manual Table of Contents Section Page 2 of 85 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR
METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. 1.02 RELATED
ELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety
PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
GTEC transfer switch open transition
GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility
Fusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
4505.85 2 of 23 December 22, 2005 October 29, 2015
1 of 23 Table of Contents 1. Foreword... 2 1.1 Scope... 2 1.2 Standards... 2 1.3 Conflict... 3 2. Ratings... 3 2.1 Basic Electrical... 3 2.2 Temperature Limitations... 3 3. Construction... 3 3.1 General...
B. Related Sections: 1. Section 26 05 33 - Raceway and Boxes for Electrical Systems.
SECTION 262726 - WIRING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section includes wall switches; wall dimmers; receptacles; multioutlet assembly; and device plates and decorative box covers. B. Related
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
Metallic and Non-Metallic Air Conditioning Disconnects. A Complete Family of. Disconnects with Exclusive Time Saving Features
Metallic and Non-Metallic Air Conditioning Disconnects A Complete Family of Disconnects with Exclusive Time Saving Features Enclosed Molded Case Disconnect Switch Not-Fusible The preferred molded case
ASCO SERIES 185 Power Transfer Switches
ASCO SERIES 185 Power Transfer Switches 4-hour protection no matter when trouble strikes ASCO Series 185 Power Transfer Switches An Automatic Transfer Switch helps prevent... Your business or home from
E2 Series Electric Furnaces
E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
Schneider Electric Services: life-cycle solutions for electrical distribution equipment. Scopes of Work for Electrical Acceptance Testing
Scopes of Work for Electrical Acceptance Testing Schneider Electric Services: life-cycle solutions for electrical distribution equipment Make the most of your energy SM Scopes of Work for Electrical Acceptance
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design
Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,
COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR
COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR Copyright Material IEEE Paper No. PCIC 2003-13 Eddie Wilkie Eaton Cutler-Hammer 3990 Old Tasso Road NE Cleveland, TN 37312 USA Abstract
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
SECTION 26 05 49 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes seismic restraints and other earthquake-damage-reduction measures for electrical
Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC
ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee
Power-Zone 4 Arc Resistant Low Voltage Switchgear
Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions
Type GM-SG-AR 5 kv and 15 kv arc-resistant metal-clad switchgear instruction manual. Answers for energy.
Type GM-SG-AR 5 kv and 15 kv arc-resistant metal-clad switchgear instruction manual Installation operation maintenance E50001-F710-A254-X-4A00 Answers for energy. Hazardous voltages and high speed moving
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE
2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE PAGE 1 OF 5 This Reference provides a very comprehensive list of aspects of a solar PV installation that could be reviewed, clarifying
Engineers Edge, LLC PDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior
OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE
OASIS-PLUS 120V INFORMATION & OPERATING INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE 56041852 WARNING:
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
Generator DoCKInG StatIonS
Generator DOCKING STATIONS TRYSTAR Portable Power Cable Cam to cam cable extensions 2000V, 100A-400A rated to NEC table 400.5 (B) All portable power cable sold is highly flexible and UL & C-UL or CSA Listed
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
How To Plan Out An Array Of Solar Panels
CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013
LOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete.
LOADING DOCK EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Loading dock equipment of the following types: 1. Dock lifts. 2. Control stations. 1.2 RELATED SECTIONS A. Section 03100 - Concrete Forms and
Learning Module 13: Panelboards and Switchboards. 101 Basic Series
Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and
SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS
SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS PRIMARY METER POLE ELECTRIC SYSTEM BULLETIN No. 753 JUNE 1993, 2 ND PRINTING APRIL 2002 (Supersedes issue dated March 1983 and incorporates Nov.
Low Voltage Switchgear
Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering
CalMod Design-Build Electrification Services
SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
SECTION 10680 MediaStation Model 125 Electric Lateral Files (ELF)
SECTION 10680 MediaStation Model 125 Electric Lateral Files (ELF) PART 1-GENERAL 1.01 RELATED WORK SPECIFIED IN OTHER SECTIONS A. Electrical connections see electrical specifications. 1.02 SUBMITTALS A.
SPECIFICATIONS. S&C Switch Operators Type PM SPECIFICATION BULLETIN 669-31. For Field Retrofit on Manual PMH, PMS, and PME Pad-Mounted Gear
S&C Switch Operators Type PM Outdoor Distribution For Field Retrofit on Manual PMH, PMS, and PME Pad-Mounted Gear SPECIFICATIONS Conditions of Sale STANDARD: Seller s standard conditions of sale set forth
Atlanta Chapter IEEE Industry Applications Society
Atlanta Chapter IEEE Industry Applications Society Electrical Equipment Room Design Considerations presented at the Sheraton Buckhead Hotel Atlanta, Georgia November 20, 2006 Outline 1. Definitions 2.
Packaged Terminal Air Conditioner Wall Sleeve Installation
Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation
Parallel Redundant Uninterruptible Power Supply
9 315 Parallel Redundant Uninterruptible Power Supply Installation/Operation Manual 164202013 Rev. D ------------------------------------------------------------------------ ------------------------------------------------------------------------
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
Multi-tap Transformers
Multi-tap Transformers Three-Phase Multi-tap Transformer for Electrical Submersible Applications Functional Specification Guide Functional Specification for Multi-tap Transformers for Electrical Submersible