SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

Similar documents
Checking Capacitor Banks for Failed Capacitors

Monitoring Underground Power Networks

Eaton s E-Series protective relay family

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

PSEG-LONG ISLAND SMART GRID SMALL GENERATOR INTERCONNECTION SCREENING CRITERIA FOR OPERATING IN PARALLEL WITH LIPA S DISTRIBUTION SYSTEM

Applications. diris_826_a_1_gb_cat

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

Typical Data Requirements Data Required for Power System Evaluation

PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions

PowerCommand Paralleling System Digital MasterControl

Energy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management

Electrical Network Management System

ISIO 200. Binary Input/Output (I/O) Terminal with IEC Interface

Electric Power Distribution

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114.

Controller Automation, Model II+

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

New Supervisory Control and Data Acquisition (SCADA) Based Fault Isolation System for Low Voltage Distribution Systems

A Proposed Integration of Hierarchical Mobile IP based Networks in SCADA Systems

Design and Implementation of SCADA System Based Power Distribution for Primary Substation ( Monitoring System)

Power Meter Series 700

AORC Technical meeting 2014

SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General

Inverter / Charger Installation General Operations and AC and DC Connections

OVR Three-Phase Recloser and PCD Control Style Guide 1VAL SG October 13, 2009 Revision F

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F

CalMod Design-Build Electrification Services

Monitoring & Control of Small-scale Renewable Energy Sources

Metering Devices IQ Analyzer 6400/6600 Series

Computer Controlled Generating Stations Control and Regulation Simulator, with SCADA SCE

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

1. INTRODUCTION FEATURES 2. PROGRAMMING

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

SECTION SYSTEMS INTEGRATION TESTING

7. Reactive energy compensation

User Manual V SDM220MODBUS. Single-Phase Two Module DIN rail Meters

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Switchgear and Metal-Enclosed Bus

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

Power factor correction and harmonic filtering. Rectimat 2 Automatic capacitor banks. Catalogue. Building a New Electric World

ATTACHMENT G. Network Operating Agreement

Configuring Alarms & Relays in the Enhanced Transformer Advantage

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014

Evolution of Control for the Smart Transmission Grid

Introduction To SCADA and Telemetry

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

6. The estimated costs here do not include any applicable ITCC tax

Before You Start 1 Overview 2 Supported Devices 4 Public (User LAN) and Private (APC LAN) Networks 5. Initial Configuration Requirements 6

Gas Genset Controls. Genset Control Panel (GCP2) with PCS (PowerCommand Supervisor) Features. Description

Wireless Communications for SCADA Systems Utilizing Mobile Nodes

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

ADMS(Advanced Distribution Management System ) in Smart Grid

How To Choose A Transformer

Fusible Disconnect Switch

Online Transformer Insulation Monitoring System BushingGard Product Focus. Maximizing Transformer Uptime and Reliability

Primary and Secondary Electrical Distribution Systems

NC-12 Modbus Application

GENe Software Suite. GENe-at-a-glance. GE Energy Digital Energy

WIRELESS REMOTE MONITORING OF CATHODIC PROTECTION SYSTEMS. John Hawkyard MICorr Deputy General Manager Rawabi Corrosion Technology Co Ltd Al-Khobar

Distribution System Automation

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date Rev.

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

PowerCommand iwatch 100 Remote Network Monitoring

PowerLogic ION7550 / ION7650

SPECIFICATION COG-2007

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

30 ms High Speed Transfer System (HSTS) Product Description

INTELLIGENT DISTRIBUTION NETWORK ANALYSIS AND INFORMATION ARCHITECTURE DESIGN

Liebert GXT MT+ CX UPS, 1000VA VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity

Network-wide Diagnostics

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

Electrical Shore Connections / Cold Ironing

Teleprotection Schemes and Equipment. James W. Ebrecht Young Power Equipment Scottsdale, AZ

HIGH VOLTAGE CALCULATIONS / EVALUATIONS. West Virginia Office of Miners Health, Safety & Training

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

OVR-3SP Recloser with PCD Control Style Guide 1VAL SG March 30, 2009 Revision B

Contractors Guide Central Inverter System Installation

Paralleling Switchgear

*.ppt 11/2/ :48 PM 1

Kurz Instruments Inc. Document AV Document Title: MFTB Event Code Definitions. MFT B-Series Event Codes

Application/Connection Examples

Process Control and Automation using Modbus Protocol

Technical Training Module ( 30 Days)

ABB PSPS Erich Steinmann; Generator control-2013

DNP Points List and Implementation

Automatic Transfer Switch-Controller ATS-C by Eaton. Automatic Transfer Switch- Controller ATS-C 96 and C 144

Power monitoring unit type VAMP 260

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

Electronic Multi-Measuring Instrument

SECTION WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Product Guide. Low voltage grounding system. Answers for industry.

Agenda do Mini-Curso. Sérgio Yoshio Fujii. Ethan Boardman.

AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810

Power network telecommunication

Transcription:

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor banks and harmonic filter banks can provide many benefits that are not available in standard metal-enclosed capacitor banks. A SCADA controlled automatic capacitor bank provides local and remote control, failure prediction and detection, reduced operating cost, and an ability to boost distribution and transmission system performance with supervisory control. This Technical Note provides information on the benefits of SCADA controlled multi-step capacitor banks as well as a common SCADA control package provided by Northeast Power Systems, Inc. (NEPSI). Detailed specifications on SCADA controlled multi-step metal-enclosed capacitor banks and harmonic filter banks are available from NEPSI by email. You may request a copy at: Sales@nepsi.com Background Figure 1 SCADA Controlled Automatic Capacitor Banks Offer Many Benefits Over Conventional Metal-Enclosed Capacitor Banks Conventional multi-step automatic capacitor banks consist of 2 to 5 steps of shunt capacitors with total bank kvar ratings to 10,000 kvar. The capacitors steps are automatically energized and de-energized with vacuum switches to regulate voltage, power factor, or VARs on distribution substations ranging in voltages from 4.16kV to 34.5kV. The banks are shipped fully assembled and ready for interconnection. All switching devices (including air-disconnect switches), protection and control features

are neatly packaged into a single unit to allow for direct connection to the main bus of a distribution substation. A concrete pad, external current transformer signal, three power cables, and a ground wire is all that is required to connect these banks to your system. A SCADA controlled bank offers the same benefits as conventional metal enclosed banks, but goes one step further and allows for connection to a SCADA system. These SCADA controlled banks provide the following key benefits: SCADA controls offer the ability to over-ride automatic controls of the bank to provide voltage or var support to the distribution, sub-transmission, and transmission systems. SCADA controls can alert utility personnel of capacitor and fuse failures. This will increase capacitor bank reliability and minimize downtime. SCADA controls reduce operating cost by reducing crew trips to the substation. SCADA provides for remote monitoring of the status of all protection and control devices within the bank. SCADA controls provide remote monitoring of all power system parameters (i.e. harmonic distortion, voltage, power factor, etc.) associated with the capacitor bank. This provides for a key diagnostic tool when power quality concerns arise. SCADA Control Figure 1 shows a typical block diagram of a SCADA controlled metal-enclosed automatic capacitor bank. Key elements shown in the diagram are as follows: SUPERVISORY CONTROL SWITCH This switch is typically located on the control panel of the metal enclosed automatic capacitor bank. When the supervisory control switch is in the "DISABLED" position, all SCADA controls are disabled and the bank can only be operated from the control panel. When the Supervisory Control Switch is in the "DISABLED" mode, the SCADA system will continue to receive indication of the capacitor bank's status, but SCADA controls received by the bank will be ignored. When the Supervisory control switch is in the "ENABLED" position, the bank can be controlled by the SCADA system, but will remain in the automatic control mode until an over-ride command is sent. Once in over-ride command is sent (i.e. SCADA command to turn stage 3 on), automatic mode is disabled and complete capacitor bank control is based upon commands received by the SCADA system. Automatic control can be re-initiated by SCADA with a Return to Automatic Control signal. MAN/OFF/AUTO SWITCH These switches are only functional when the bank is not being controlled by the SCADA system (i.e. when the Supervisory Control

Switch is in the "DISABLED" or when the bank is in automatic control mode). These switches are 3-Position. When in the ON Position, the stage associated with the MAN/OFF/AUTO switch is forced on. When in the OFF position, the associated stage is forced off. When in the AUTO position the bank is controlled by the Power Factor Controller. Re-energization of a stage in less than 5-minutes is prevented by the controls. MODICON PLC The Modicon PLC controls many of the functional requirements of the SCADA control system. PROTECTION SYSTEM This system is composed of the neutral unbalance protection system, over-current relay(s), and over-voltage relay(s) (Note: overvoltage and over-current relays are not always installed in multi-step capacitor banks. Requirements for these relays are system dependent). SENSORS The PT s, CT s and other devices required to provide SCADA and automatic control signals as outlined in Table 1 of this specification. STAGE VACUUM SWITCH These switches are part of the capacitor bank and are responsible for energizing and de-energizing the capacitor bank. NEUTRAL SENSOR(S) These sensors are typically located in the neutral of most capacitor banks and will be either a current transformer or voltage transformer. Their purpose is to provide a voltage or current signal to the unbalance relay on the loss of a capacitor fuse. METERING This meter shall monitor the power system parameters as listed in Table 1. The power system parameters shall be available to the PLC for detection of alarm and fault conditions as well as to the RTU for the SCADA System. A common communication protocol (RTU or DNP 3 needs to exists between the RTU, Metering device(s), and the PLC. AUTO CONTROLLER The auto controller, controls the capacitor bank stages based upon system power factor, voltage, or vars. The auto controller is only allowed to control the bank when it is not being controlled by the SCADA system.

Figure 1 Block Diagram of SCADA System SCADA Input/Output Requirements Table 1 below shows the typical I/O requirements of the RTU. NEPSI can install and prewire the RTU and communication devices at the factory or can leave space in the automatic metal-enclosed control cabinet for installation by the customer. Table 1 - SCADA Controlled Capacitor Bank I/O Requirements Name Type Functional Description Supervisory Control Enabled Indicator/Output Provides indication if Automatic Capacitor Bank can be supervisory controlled. Supervisory Control Disabled Indicator/Output Provides indication that supervisory controls are This mode of operation can only be performed by throwing a switch on the capacitor bank control panel and is primarily used for testing. Return to Automatic Control Control/Input Returns control back to the capacitor banks automatic power factor correction control system. Stage 1 On Control/Input Turns Stage 1 on when supervisory control is enabled Stage 1 Off Control/Input Turns Stage 1 off when supervisory control is enabled Stage 2 On Control/Input Turns Stage 2 on when supervisory control is enabled

Stage 2 Off Control/Input Turns Stage 2 off when supervisory control is enabled disabled Stage 3 On Control/Input Turns Stage 3 on when supervisory control is enabled Stage 3 Off Control/Input Turns Stage 3 off when supervisory control is enabled disabled Stage 1 On Indicator/Output Indicates if Stage 1 is on Stage 1 Off Indicator/Output Indicates if Stage 1 is off Stage 2 On Indicator/Output Indicates if Stage 2 is on Stage 2 Off Indicator/Output Indicates if Stage 2 is off Stage 3 On Indicator/Output Indicates if Stage 3 is on Stage 3 Off Indicator/Output Indicates if Stage 3 is off (Repeat above Stage indicators for each stage) Data Acquisition Parameters Output Via DNP/Modus Protocol to RTU (Specify communication requirement of RTU) Three Phase Voltage, Average Voltage, L-L Voltage, Phase Currents, Voltage Unbalance, Current Unbalance, Line Frequency, Phase KW, Total KW, Phase Kvar, Total Kvar, Phase KVA, Total KVA, Phase Power Factor, KW Thermal Demand, KVAR Thermal Demand, KVA Thermal Demand, Maximum KW Demand, Maximum Kvar Thermal Demand, Maximum KVA Thermal Demand, Maximum Total kw, Maximum Total Kvar, Maximum Total KVA, Minimum Average Current, Total kvarh, Net kvarh, Total kvarh, Max Phase Voltage THD, Maximum Phase Current THD Provides warning against a blown capacitor fuse condition. Provides indication that bank tripped on a blown capacitor fuse condition. Neutral Unbalance Indicator/Output Alarm Neutral Unbalance Indicator/Output Trip Over-Voltage Alarm Indicator/Output Provides indication of an over-voltage alarm (Only required when bank is equipped with an overvoltage relay) Over-Voltage Trip Indicator/Output Provides indication that the capacitor bank tripped an over-voltage. (Only required when bank is equipped with an overvoltage relay) Over-Current Trip Indicator/Output Provides indication that the capacitor bank tripped on over-current. (Only required when the bank is equipped with an over-current relay) Conclusion This Technical Note presented the benefits of SCADA controlled automatic capacitor banks. It also presented a SCADA control scheme and the input and output requirements of the scheme. It is important that the customer properly specifies the requirements of the SCADA system and anticipates the I/O requirements of the RTU. It is

in the customer s best interest to specify an RTU and communication device that is compatible with the Master SCADA system. To ensure a fully functional automatic capacitor bank SCADA control system, the manufacturer should be requested to install and test the SCADA control system with the desired RTU. Northeast Power Systems, Inc. 66 Carey Road Queensbury, New York 12804 Phone: 518-792-4776 Fax: 518-792-5767 E-mail: sales@nepsi.com Website: www.nepsi.com Copyright 1999-2012 Northeast Power Systems, Inc.