SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General
|
|
|
- Ann Wilson
- 10 years ago
- Views:
Transcription
1 SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General A. Electrical usage on the Brown campus is presently monitored by a Siemens-brand, web-based central metering system, which includes a central file server and individual ION-type (Integrated Object Network) building meters and submeters, which are interconnected via the campus Ethernet system. The metering system is presently configured to operate on Siemens WinPM.NET supervisory software B. Metering and consumption data is stored locally within each meter as well as archived within the main file server located in the Facilities Management Building. C. High Temperature Hot Water, Medium Temperature Hot Water as well as district cooling system Chilled Water are also reported to and stored by the Siemens central metering system. Information for BTU meters includes interval and total to date flow rates and BTU consumption, as well as instantaneous supply and return temperature information. D. Building gas consumption is also monitored by the Siemens central metering system. E. Large emergency generators are monitored and supervised by the Siemens central metering system for energy usage and alarm monitoring. This system is separate and distinct from the Johnson Controls and Andover (TAC) building automation and control systems. 2. Electrical Metering: A. All building projects that interface with the building electrical distribution system shall provide a digital electric meter if not already present. B. Metering of incoming electrical power, as well submetering of major systems (Lighting, HVAC, Etc.) is required in new building construction as well as gut renovations of existing buildings. Metering of incoming electrical power is required in the course of electrical and mechanical systems renovations to existing buildings. C. In general, there are three types of electric meters presently being specified: power quality, energy, and power meters, as follows: 1. Power quality meters are high end meters that measure voltage/current per phase, average, unbalance, real power, reactive power, apparent power, power factor, energy, and 16002C 1 Campus Central Metering System
2 harmonics up to the 63 rd order; monitor voltage sag / swells; capture, display and store phasor representations of the system. Power quality meters shall have an Ethernet port, and log data for up to one year. Meter shall be provided with a minimum of 10 MB of on-board memory. The model number for this meter is Siemens Energy meters measure voltage/current per phase, average, unbalance, real, reactive and apparent power; power factor, energy and harmonics up to the 15 th order. Energy meters shall have an Ethernet port, and log data for up to one year. The model number for this meter is Siemens Power meters measure voltage/current per phase, average, unbalance, real, reactive and apparent power; power factor, energy, and total harmonic distortion. Power meters shall be Modbus capable and have an RS-485 port. The model number for this meter is Siemens These meters shall only be used in conjunction with an adequately configured Power Quality or Energy meter that has sufficient on-board memory to locally store 1 year of power meter data, in addition to its own memory storage requirements. D. All new electrical meters and submeters shall match and be fully compatible with the existing metering system components and software. E. Proposed meter locations and the specific type of meter shall be reviewed by the Brown University Engineering Office and shall be specified in the project design documents. Medium-voltage switchgear feeders and buildings with research or a large proportion of Information Technology systems, research, or other equipment sensitive to power quality issues shall be provided with type 9510 power quality meters. Normal building services shall be provided with type 9330 energy meters. Small submetered building loads shall be monitored with type 9200 power meters series meters shall be programmed in the central metering system software for data logging of all essential voltage, amperage and power parameters. F. Electric meter installation requirements: 1. In addition to provision of the actual meters, all required system configuration and programming shall be included for the integration of any new building meters and submeters into the existing central metering and data archiving system. The contractor will be responsible for obtaining the software setup and meter configuration from Siemens C 2 Campus Central Metering System
3 2. See Sections 16003C-Campus Metering Network Connection Criteria for typical utility meter interconnection wiring to the campus Ethernet, and Section 16004C for typical utility meter interconnection wiring details. Unless otherwise noted, all materials and wiring are to be provided by the Contractor, as well as all required meter and campus metering system programming and setup. 3. For retrofit applications and for new building loads that are served via small panelboards, prewired metering enclosures, as supplied by Siemens, shall be installed adjacent to the metered equipment. The enclosure shall generally consist of a meter (type as required), interconnection wiring terminal strips, and shorting blocks for connection to the current transformers. The Contractor shall be responsible to install and wire the meter. Required interconnections include split-core current transducers (supplied by Siemens, size as required, fused voltage inputs (three phase plus neutral and ground) and a 120 VAC power supply connection. 4. For larger building loads that are served via a new distribution switchboard(s), the meters shall be installed directly within a dedicated, barriered metering compartment that is designed within the switchboard. The metering compartment shall be factory prewired, to terminal strips, with all required three-phase current transducers, voltage inputs and 120 VAC meter power supply. The Contractor shall be responsible to install the meter, make all interconnection wiring connections, 3. High Temperature Hot Water, Medium temperature Hot Water and Chilled Water Metering: A. All new building construction and renovation projects that have provisions for high temperature hot water for heating use, or district chilled water for air-conditioning use shall include a BTU (flow) meter if not already present. The BTU meter shall be selected, configured, programmed, and mapped to the campus central metering system software for data logging via a building electric meter, to provide for monitoring and trending of the building thermal loads. B. High temperature hot water and chilled water is being metered by the following type of meter: 1. Ultrasonic-type flowmeters are GE Panametrics, model DF868 series, Flexim Instruments model 7407, or approved equal, and communicate with the electric meter via Modbus interface. Required data includes flow and temperature of the supply and 16002C 3 Campus Central Metering System
4 return water, net water flow, instantaneous building BTU consumption, net and peak BTU demands. 2. Flow meter shall have the capability to log all measured and calculated values for up to one year. Meter shall be provided with the following outputs: Modbus output, for connection to the Brown campus metering system Ethernet output, for direct access with thermal meter manufacturer s software via the campus Ethernet 4-20mAmp outputs, for water flow and BTU consumption, for connection(s) to the building automation system C. Proposed meter locations, the specific type of meter and meter options and accessories shall be reviewed by the Brown University Engineering Office and shall be specified in the project design documents. D. BTU flow meter installation requirements: 1. Flow meters shall be wired back to the nearest accessible Siemens electrical meter via a Modbus output and Belden # 9841, run in ¾ conduit. Flow meters shall also be wired back to the building energy management system network-level controller, via multiple Belden # 9841, run in ¾ conduit. 2. Panametrics brand BTU meters are installed with an insert spool piece installed on the incoming water line. The spool piece contains the wetted flow transducer elements as well as an RTD temperature probe thermowell. In addition, an RTD temperature probe thermowell shall also be installed in the return water line. Flexim brand BTU meters are installed with the flow transducer elements and temperature elements mounted to existing piping. Regardless of meter type, the contractor shall connect and wire all field sensor wiring back to the controller, per the manufacturer s requirements and provide a 120VAC dedicated power supply to the meter. 3. Each BTU meter shall be provided with an Ethernet data drop connection to enable remote system diagnostics, programming and data collection. 4. See Section 16005C-Thermal (BTU) Meter Interconnection Criteria for typical meter interconnection wiring connections. Unless otherwise noted, all materials and wiring are to be provided by the Contractor C 4 Campus Central Metering System
5 4. Gas Metering: 5. In addition to provision of the actual flow meters, all required flow meter system configuration and programming shall be included. Also, all required system configuration and programming shall be included for the integration of the BTU meters into the existing campus central metering system software. The contractor will be responsible for obtaining the software setup and meter configuration from the BTU meter vendor and Siemens. A. All new building construction and renovation projects that have provisions for natural gas shall provide a gas meter incorporating a pulse output if not already present. B. Pulse outputs from the gas meters shall be wired back to the nearest accessible Siemens electrical meter via a Modbus output and Belden # 9841, run in ¾ conduit. C. In addition to provision of the actual gas meters, all required system configuration and programming shall be included for the integration of any new gas meters into the existing Siemens central metering and data archiving system. The contractor will be responsible for obtaining the software setup and meter configuration from Siemens. 5. Emergency Generator Metering and Alarm Monitoring A. All critical use and new large (150 KW and up) emergency generators, are to be provided with a dedicated power meter and input/output controller for supervisory monitoring and remote control of the generator and associated automatic transfer switches. The Power meter and components shall match, and be fully compatible with, the existing campus central metering system components and software B. The generator power meter shall generally comprise a 9350 series Siemens Power Meter with Ethernet connection, Ethergate connections for Modbus Communications, expanded on-board memory for data logging, and minimum of 4 assignable output contacts for system control. Meter shall be provided with an additional Input/Output controller, Siemens Model S7io, incorporating digital inputs for equipment status, serial communications capacity for transfer switch and generator status monitoring and digital outputs for transfer switch load shed and manual transfer functions, and generator remote start/stop. Meter, 120VAC power supply and Input/Output controller shall be furnished, installed and prewired complete within a common 20 X 20 (nominal) Nema 4/12 Enclosure, with all required wall mounting hardware, ready for field installation. Factory-prewired LED s shall be provided to illuminate when 16002C 5 Campus Central Metering System
6 remote load transfer and generator start/stop functions are active for troubleshooting purposes. C. Generator power meter shall be configured to monitor generator load via generator-mounted ct s and generator voltage inputs. When so required for load-shed purposes, the meter shall be programmed to provide a minimum of (4) user-programmable dry contact outputs to the BAS system or other system, to enable the BAS to enable various load shed sequences as may be required. D. Generator power meter shall be programmed to allow for remote and generator start/stop and remote activation of transfer switch control via discrete contact outputs to the generator control panel and to each controlled transfer switch. E. Generator power meter shall be programmed to allow for remote monitoring of the emergency generator and each connected automatic transfer switch. The Power meter shall be configured to monitor the following status points from each connected transfer switch: Load (amps), voltage, switch position (load connected to normal, load connected to Emergency, and remote test switch position status. Meter shall also be configured to monitor the generator run status and alarm status panel alarm points. Meter monitoring shall be via MODBUS (RS 485) connection to each transfer switch and generator. F. Provide the services of a qualified Siemens programmer/technician for integration of the generator power meter, its associated monitoring and controls functions into the existing campus central metering system components and software. Programming to include setup and trend logs for meter interval data and all system status alarm points, setup of custom graphic display screens denoting system status points and setup of password protected, remote system start-stop and transfer switch control from the campus head end. The Contractor is responsible to coordinate this programming effort with the generator and transfer switch suppliers. G. See Section 16006C-Emergency Generator Power Meter & Load Shed Interconnection Criteria for typical power meter interconnection wiring to the campus Ethernet, emergency generator and automatic transfer switch(es). END OF SECTION 16002C 6 Campus Central Metering System
Metering for today s systems
Metering for today s systems The sub-meter gathers data on the building side of the utility company meter. This allows us to break out usage so data can be collected from individual circuits, a single
Case Study - University at Buffalo State University of New York. Lower Energy Usage Costs with Real Time Monitoring, Campus-wide
Case Study - University at Buffalo State University of New York Lower Energy Usage Costs with Real Time Monitoring, Campus-wide Reduce Energy Consumption through Awareness of Energy Use Analyze Power Quality
SECTION 16911 WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM
WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM PART 1 GENERAL 01 02 03 04 SCOPE This section describes the metering, communications, and visualization requirements for a modular, scalable Web-based Power
Application Note: Monitoring Branch Circuit Loads in Critical Facilities
Application Note: Monitoring Branch Circuit Loads in Critical Facilities Description of application: The AcquiSuite data acquisition server (DAS) from Obvius is used to monitor the electrical loads and
scalable data centre energy management solution
scalable data centre energy management solution scalable data centre energy management solution EcoMeasure - Scalable Data Centre Energy Management & Efficiency Measurement Solution by Workspace Technology
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
Electrical Network Management System
Electrical Network Management System Optimisation of the electrical network Measure to understand Understand to control Control to optimise Cost of power and fluids Power quality Power availability 2 Improvement
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design
Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,
Energy and Flow Measurement for Hydronic Systems
Energy and Flow Measurement for Hydronic Systems Presented By: George Szyszko Applications Consultant MCR for ONICON Incorporated Why Measure Thermal Energy? To control something, you must first measure
Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
Products Range Overview. Products Range Overview. The ZigBee Plug & Play wireless Network for Building and Industrial Applications
The ZigBee Plug & Play wireless Network for Building and Industrial Applications Energy Management Renewable Monitoring Environment Monitoring Open Modbus Integration Products Range Overview Products Range
Eaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
Energy Depot GmbH PRODUCT AND APPLICATION GUIDE. Total Monitoring Solution for PV. Delivering Solutions for Energy Management
Energy Depot GmbH Delivering Solutions for Energy Management PRODUCT AND APPLICATION GUIDE Total Monitoring Solution for PV SOLAR LOGGER & ANALYSIS DC STRING MONITORING Residential Comprehensive Solar
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor
F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems
F ox W hi t e Paper Reduce Energy Costs and Enhance Emissions Monitoring Systems A Technical White Paper from Fox Thermal Instruments Rich Cada, VP Sales & Marketing, Fox Thermal Instruments, Inc. 399
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
Square D Power Management Services. Complete Custom Solutions for Your Power System
Square D Power Management Services Complete Custom Solutions for Your Power System The Total Power Management Solution Power. Managing it more efficiently and productively can give you a competitive edge.
Simple Electrical Utility Cost Allocation Solutions
Simple Electrical Utility Cost Allocation Solutions PowerLogic High Density Metering Advanced Submetering and Multi-Tenant Metering Buildings Retail Multi Residential DATA CENTER SOLUTIONS For More Information:
Applications. diris_826_a_1_gb_cat
Measurement units NEW diris_824_a_1_cat Energy monitoring and management of low voltage/ high voltage electrical installations Function are measurement units which can provide all the functions offered
TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM
TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution
Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D
7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values
Nu-Lec Training Modules
PTCC Controller Nu-Lec Training Modules Product Training Operator Training PTCC The Basics An overview of the construction and physical features of the Pole Top Control Cubicle PTCC Operation and Features
O C M III. Open Channel Flow Monitor
O C M III Open Channel Flow Monitor Part 1. General 1.1 Scope A. This section describes the requirements for an ultrasonic flow transmitter with sensor and temperature compensation probe. B. Under this
ZigBee Wireless Sensor Networks
ZigBee Wireless Sensor Networks Wireless Devices for Monitoring and Data Harvesting Home & Building Automation Automated Meter Reading Energy Management Renewable Monitoring Environment Monitoring ZigBee
SECTION 13421 PROGRAMMABLE LOGIC CONTROLLERS AND COMPUTER CONTROL SYSTEM PART 1 GENERAL. 1.01 Summary. A. Section Includes:
SECTION 13421 PROGRAMMABLE LOGIC CONTROLLERS AND COMPUTER CONTROL SYSTEM PART 1 GENERAL 1.01 Summary A. Section Includes: 1. The ISS shall furnish all labor, materials, equipment, services and incidentals
MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter
Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases
Electronic Control Devices The European Product Catalogue 2007
FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
THERMAL MANAGEMENT SOLUTIONS
t2000 Series Electronic heat-tracing controller Product Overview /COMMUNICATIONS INTERACE CARRIER REQ TO SEND The DigiTrace heat trace controller is designed to provide the benefits associated with single
Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.
Data Bulletin 1210DB0002R3/05 03/2005 LaVergne, TN, USA Communications Wiring for POWERLINK G3 Systems Class 1210 Retain for future use. ABOUT THIS BULLETIN This data bulletin describes the proper wiring
Power Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
System integration oriented data center. planning. In terms of ATEN's eco Sensors DCIM solution
System integration oriented data center planning In terms of ATEN's eco Sensors DCIM solution 1. Introduction The reliability of an enterprise data center servicing either external or internal clients
Comprehensive Data Center Energy Management Solutions
FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara Framework to provide full convergence of
The Access Engine. Building Integration System - The Access Engine. Security Systems
The Access Engine 1 What is BIS Access Engine? It is one of the central software modules of the Building Integration System It s a fully integrated access control solution with corresponding access hardware
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
Micro Motion Net Oil Computer Software and NOC System
Instruction Manual P/N 20006444, Rev. A May 2007 Micro Motion Net Oil Computer Software and NOC System Configuration and Use Manual 2007, Micro Motion, Inc. All rights reserved. ELITE and ProLink are registered
Quick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
Comprehensive Data Center Energy Management Solutions
FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara framework to provide full convergence of
Thermal Mass Flow Meter (Series MST)
Overview MaxiFlo TM MST series Thermal Mass Flow Meter is the instrument of choice for reliable and accurate measurement of mass flows for various gases. It measures the mass flow of gas based on constant
Fusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
F453. TiF453. User guide 10/11-01 PC
F453 TiF453 User guide 10/11-01 PC 2 TiF453 User guide Contents 1. Hardware and Software requirements 4 2. Installation 4 1.1 Minimum Hardware requirements 4 1.2 Minimum Software requirements 4 3. Fundamental
PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions
PMCS Integrated Energy Management Solution Unlock the Full Potential of Power Networks Through Integration Power Management Control System (PMCS) is a highly customizable, fully integrated end-to-end Energy
JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410
The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a
Complete SCADA solution for Remote Monitoring and Control
Complete SCADA solution for Remote Monitoring and Control FF-Automation (founded 1976) manufactures AutoLog RTUs, designs and supplies complete automation SCADA solutions for remote monitoring and control
* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2
COMMERCIAL INSTALL GUIDE 2 Contents How to Use This Guide: The first section of this guide is designed to assist you with the installation of your DECK Monitoring hardware. The revenue grade meter and
THE TOWN OF GROTON IS REQUESTING PROPOSALS FOR A WIRELESS ALARM MONITORING AND CONTROL SYSTEM WITH INTERNET BASED DATA ACCESS
THE TOWN OF GROTON IS REQUESTING PROPOSALS FOR A WIRELESS ALARM MONITORING AND CONTROL SYSTEM WITH INTERNET BASED DATA ACCESS The proposal shall be for supplying pre-wired cellular ready to install field
Chapter-5 Introduction to Building Automation System (BAS)
Chapter-5 Introduction to Building Automation System (BAS) Chapter-5 Introduction to Building Automation System (BAS) ၅.၁ Introduction Building Automation System(BAS) sub system equipment service monitor
Communicate and view data from meters with one simple device
Communicate and view data from meters with one simple device PowerLogic EGX300 integrated gateway-server Web Monitoring Communications Plug and Play Plug into your energy usage with a simple mouse click
INTEGRAL REMOTE MANAGEMENT SOLUTION cirwatt b series
Communication system for the management of electrical installations INTEGRAL REMOTE MANAGEMENT SOLUTION cirwatt b series MID Approval Technology for energy efficiency PLC Communications (Power Line Communication)
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Paralleling Switchgear
Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more
A project to optimise quality and energy efficiency must include metering
EMDX 3 : Energy Metering A project to optimise quality and energy efficiency must include metering Metering upstream identifies the critical points and ensures optimum targeting of the actions to be taken,
DATA CENTER PHYSICAL INFRASTRUCTURE
Is your datacenter running with maximum performance? Datacenter managers have been challenged to maintain or increase availability, maximize efficiency, and optimize the use of existing capacity. However,
Table of Contents. TransformerIQ FAQs 1
[12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is
Dyeing Programmer DP - 01
Dyeing Programmer DP - 01 Display and Controls. 1) Display: 16/2 alphanumeric display 2) Temperature range: 0 to 150 degree. 3) Resolution: 1 degree. 4) Accuracy: +/- 1 degree. 5) Temperature control setting:
Electrical Monitoring and Control System Solution. Guideform Specification
Electrical Monitoring and Control System Solution Guideform Specification 1 SYSTEM... 2 1.1 Overview... 2 1.2 System Solution Functional... 2 1.2.1 Monitoring... 2 1.2.2 Power Quality... 4 1.2.3 Cost Allocation
TrueAlarm Fire Alarm Systems
TrueAlarm Fire Alarm Systems UL, ULC, CSFM Listed; FM Approved; MEA (NYC) Acceptance* Fire Alarm System Accessories, 4190 Series PC Annunciator with Multi-Client Capability Features Fire alarm control
The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY
The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY PowerGate - Cost effective solutions for F 1 Horsepower Rating 001 1-40 HP (208V) 075 1-75 HP (480V) Input Voltage 2V 208-240V 4V 380-480V Disconnect
Switchgear Capabilities. NexGear is a Division of PowerSecure NASDAQ: POWR
Switchgear Capabilities NexGear is a Division of PowerSecure NASDAQ: POWR Discussion Points Introducing PowerSecure Introducing NexGear Solutions Offered Scope of Services Examples of Work Q & A NexGear,
FX07 Field Controller
Product Bulletin FX07 Field Controller Issue Date March 25, 2008 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,
Doc 10. UTM Standards: Card Access Security System
Doc 10 UTM Standards: Card Access Security System 1. GENERAL... 2 1.1. GENERAL REQUIREMENTS.... 2 1.2. SUMMARY OF WORK INCLUDED... 2 1.3. OVERVIEW... 2 1.4. MANDATORY REQUIREMENTS... 3 1.5. ACCESS CONTROL
FX07 Field Controller
Product Bulletin FX07 Field Controller Issue Date May 5, 2011 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,
Sentron Series Circuit Breakers
Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of
Counter for Energy. We make energy measurable and secure your future. www.g-mw.de
Counter for Energy We make energy measurable and secure your future www.g-mw.de 10 reasons for GMW Customer oriented solutions Individual consultancy Satisfied customers in all continents Large range of
SWITCHGEAR. EGP Switchgear
SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all
COMBIMASS. Technical Data COMBIMASS eco-bio +
COMBIMASS Technical Data THE SYSTEM COMBIMASS The field transmitters of the COMBIMASS eco series are suitable for gas flow measurement and cover a wide range of different applications. The instruments
Device Support in PowerLogic ION Enterprise 5.6 Service Pack 2
70072-0189-00 TECHNICAL 08/2008 Device Support in PowerLogic ION Enterprise 5.6 Service Pack 2 This document outlines support in ION Enterprise 5.6 Service Pack 2 for PowerLogic CM3000 series/cm4000 series,
300 MY HOME Energy management
300 MY HOME COTETS. MY HOME oad control management General features. 302 General rules for installation. 308 Configuration 311 Wiring diagrams. 314 MY HOME 301 GEERA FEATURES The end of the black-out The
Remote Monitoring and REC 501 Control Unit Product Guide
Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the
PowerCommand iwatch 100 Remote Network Monitoring
PowerCommand iwatch 100 Remote Network Monitoring Description The PowerCommand iwatch provides a convenient means for remotely monitoring generator sets and transfer switches. The Microsoft Internet Explorer
DigitalFlow GF868. Panametrics Flare Gas Mass Ultrasonic Flowmeter with Extended Performance Range. GE Sensing & Inspection Technologies.
GE Sensing & Inspection Technologies DigitalFlow GF868 Panametrics Flare Gas Mass Ultrasonic Flowmeter with Extended Performance Range Applications The DigitalFlow GF868 flowmeter is a complete ultrasonic
Industrial Control Solutions
Industrial Control Solutions NGC-30 Advanced Heat-Tracing Control System industrial heat tracing solutions www.pentairthermal.com Raychem ngc-30 Raychem NGC-30 is an advanced electronic multipoint control,
NETWORK ENABLED EQUIPMENT MONITOR
NETWORK ENABLED EQUIPMENT MONITOR Remotely Monitor Sensors over the Internet Connect Sensors to the Web to Remotely Monitor Equipment, Processes or Other Applications A Complete, Easy to Deploy, Stand-Alone
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Application/Connection Examples
This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.
Panorama Electricity meters For reliable values of energy consumption
Panorama Electricity meters For reliable values of energy consumption Why measure Electrical Energy Energy cost is on the rise. It is therefore in the interest of both private and commercial customers
Titelgrau belassen! Leere Vorlage
Titelgrau belassen! Leere Vorlage MAVOWATT 20 Energy Platform Energy and Power Analyzer MAVOWATT 20 The new Energy and Power Analyzer 2 Klaus-Peter Richter Product Management 10.3.2010 Page 2 Applications
A Systems Approach to HVAC Contractor Security
LLNL-JRNL-653695 A Systems Approach to HVAC Contractor Security K. M. Masica April 24, 2014 A Systems Approach to HVAC Contractor Security Disclaimer This document was prepared as an account of work sponsored
Submetering A Practical Approach
Submetering A Practical Approach By Lou Mane GE Sales Development Retail and Property Management Every increase in the cost of a barrel of oil just magnifies the importance of conserving energy and you
Executive Summary. Technical Description
Executive Summary The Cellwatch system is built using modules. The majority of the system is constructed with Data Collection Modules (DCMs). The DCMs are optically linked to Control Units (CUs) that in
Power Proportional Distribution (PPD)
1. Description The feature supplies the user with a reasonably calculated apportionment of the total power consumption by the Daikin air-conditioning system to individual indoor units in the system. Because
920 Series. Dual-point heat-tracing control system. Product overview. 920*E4FWL*SIS302*SS3102 shown
Self-Regulating 920 Series Dual-point heat-tracing control system Power-Limiting Mineral Insulated 920*E4FWL*SIS302*SS3102 shown Product overview The DigiTrace 920 is a compact, full-featured, microprocessor-based,
PRODUCT LIST Facility DDC Access WebXL DDC
PRODUCT LIST Facility DDC Access WebXL DDC Effective from 01/10/2014 Sphere Systems Pty Ltd Unit 6 / 9 Mirra Crt Bundoora Victoria Australia 3083 ABN 98 006 579 004 Phone +61 3 9470 8844 Fax +61 3 9470
H.V.A.C. Design Plumbing Design
H.V.A.C. Design H.V.A.C. Design Mira Costa College Arts Complex CP Upgrade 1. PART 1 GENERAL 1.1. DESCRIPTION SECTION 23 09 00 HVAC INSTRUMENTATION AND CONTROL 2. PART 2 - PRODUCTS 2.1. Materials
Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems
Suitable for Emergency, Peak and Prime Power System Applications Low Voltage Automatic Transfer Switch Systems THE POWER AUTHORITY THE POWER AUTHORITY ASCO s experience and commitment to excellence in
Sentinel LCT. Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement. GE Measurement & Control Solutions. Benefits.
GE Measurement & Control Solutions Sentinel LCT Panametrics Ultrasonic Flowmeter for Liquid Custody Transfer Measurement Benefits Extremely reliable and highly accurate flowmeter, designed specifically
Distributing Power to Blade Servers
Distributing Power to Blade Servers Ten steps to selecting the optimal power distribution design With the growth in blade servers with dual or triple power supplies, a single rack of equipment can easily
How To Use A Ds340 (Dsp)
Ideal for monitoring dust levels in the exhaust gas of industrial combustion or air filtration processes. Innovative Dynamic Detection Principle (DDP) measurement technique Immune to gradual reductions
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
FIRE ALARM SYSTEM. reliable fire detection and alarm signalling system
FIRE ALARM SYSTEM reliable fire detection and alarm signalling system Satel fire alarm devices allow to implement reliable and modern systems responsible for fire safety. A combination of 20-year experience
Fundamentals of HVAC Control Systems
ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 5 Control Diagrams and Sequences 2007 ASHRAE Hong
Power & Environmental Monitoring
Data Centre Monitoring Made Easy Power & Environmental Monitoring Features & Benefits Packet Power provides the easiest, most cost effective way to capture detailed power and temperature information for
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
Communication Capabilities via a Touch Screen or a Web Browser Further Expand Air-Conditioning Control Possibilities.
Communication Capabilities via a Touch Screen or a Web Browser Further Expand Air-Conditioning Control Possibilities. More Freedom to Administrators Connectable up to 128 Indoor Unit Groups (256 indoor
PowerCommand Paralleling System Digital MasterControl
PowerCommand Paralleling System Digital MasterControl Description The PowerCommand Digital MasterControl is a systemlevel controller designed to interface directly with Cummins Power Generation PowerCommand