1 Metering Devices IQ Analyzer 6400/6600 Series Technical Data Supersedes TD.17.02A.T.E pages 1-8 dated May 2000 Description Page General Description Applications Logging Trends Extensive I/O and Communications Capability Meter Menu Screens Harmonic Analysis Screens Event/Alarm Analysis Screens Maximum/Minimum Thresholds Input/Output Capabilities Field Wiring Connections Definition of Power Quality Terms Dimensions and Drilling Patterns Specifications Ordering Information
2 Page 2 Effective: November 2001 IQ Analyzer 6400/6600 Series Applications Monitoring of over 150 electrical parameters. Power quality management. Energy management. Metered/Monitored Parameters rms sensing. Phase neutral, and ground currents. Volts: L-L, L-N, Avg. L-L, Avg. L-N, N-G. Power: real, reactive, apparent (system and per phase). Frequency. Power factor: apparent and displacement (system and per phase). Energy and demand (forward, reverse, net) real, reactive apparent at four different utility rates. Individual current and voltage harmonics: magnitude, phase angle. % THD: current and voltage. Waveform capture. Minimum/maximum values. Event logging/disturbance recording. ANSI C12.20 Class 0.5% revenue metering accuracy, ANSI C12.16, IEC687 Class 0.5%. Communications Optional interface capability to computer network for data collection, storage and/or printout via the Cutler-Hammer PowerNet System. Physical Characteristics Graphical reverse mode LCD display with LED backlight. Up to seven lines of information. Height: inches (260.4 mm). Width: 6.72 inches (170.7 mm). Depth: 4.70 inches (119.4 mm) without PONI, 5.83 inches (148.1 mm) with PONI. Membrane faceplate NEMA 3R and 12 rated. Listings/Certifications UL listed, File E62791, NKCR File E (CE versions). CUL listed # C22.2. CE mark EN (1993) EN (1994). Measurement Canada Electricity Meter AE CSA C22.2 # General Description IQ Analyzer-Comprehensive Electrical Distribution Monitoring The IQ Analyzer is a complete solution for users who want to monitor and manage all aspects of their electrical distribution system. Based on input from customers and consultants, it provides extensive metering, power quality analysis, remote input monitoring, control relaying, analog input/outputs and communications capability. Its high performance metering exceeds ANSI C12.16 (1%) specification for revenue meters and meets ANSI C12.20 Class 0.5%, provides quality true rms readings through the 50th harmonic, accurately measures nonsinusoidal waveforms up to a 3.0 crest factor, and displays even and odd multiples of the fundamental current and voltage through the 50th harmonic. Both magnitude and phase angle of the harmonics are displayed. Note: For definition of power quality terms, see Page 6. The unique operator interface, which includes a reverse mode LCD display, easy to use Meter Menu screens and detailed Analysis screens, is designed to allow a wealth of real-time and recorded information to be accessed easily by an operator. All programming can be accomplished through the faceplate or the communications port. The comprehensive on-line Help feature provides useful information on device operation, programming and troubleshooting. Disturbance Information With the communications option and our Cutler-Hammer PowerNet software and Waveform Display software, a Waveform Analysis will construct waveforms of up to 56 cycles of all currents and voltages (including neutral and ground) to help troubleshoot undervoltage/sag and overvoltage/swell conditions. (See CBEMA Trend Logging section, next page.) By programming a reset threshold, the duration of the voltage disturbance can also be indicated. The IQ Analyzer 6600 series with Graphic Waveform Display offers the ability to view the captured waveform right at the device. The 6600 series also offers the ability to detect and capture sub-cycle voltage disturbances. Extensive Harmonic Distortion Analysis Current and voltage distortion data are displayed at the device and accessible through the communications port. This includes % THD, K-Factor, Crest Factor, CBEMA Factor, and both magnitudes and phase angles of all harmonics through the 50th. A snapshot sample of this information may be activated by user commands, discrete inputs or programmable thresholds to capture distortion data during conditions of real interest. To help eliminate nuisance alarms, harmonic distortion information can be captured and relay outputs activated when THD exceeds a programmable percentage of fundamental or a programmable magnitude (e.g., amperes) threshold. Time of Use Metering The IQ Analyzer offers the ability to store energy usage data for time of use revenue metering. It can be programmed for any combination of weekday, Saturday, Sunday, 22 holidays, 8 seasons, 32 schedules, and 10 time periods per schedule. The IQ Analyzer will keep track of the following parameters for four different utility rates: Watt hours Var hours VA hours Current demand Watt demand VA demand Var demand Historical Trend Logging The IQ Analyzer is equipped with onboard logging capability, which includes the ability to log a total of 24 parameters with intervals ranging from 0.13 seconds (every 8 cycles) to twice a week (5040 minutes). The trending function can begin immediately or can be triggered upon receipt of a discrete input into the IQ Analyzer. Onboard logging provides a cost-effective means of distributed data storage where real-time communications may not be feasible or for applications where data storage redundancy is desired. Four trend data logs are stored in non-volatile memory aboard the IQ Analyzer and can be retrieved at the display or via communications for viewing using Cutler-Hammer software.
3 Effective: November 2001 Page 3 Up to 24 parameters with storage capacity for up to 90,000 data points. Up to 234 days of data can be stored when recording a parameter every 15 minutes. Trends 1, 2 and 3 can save data on a discrete contact input. Trend 4 can save data on a power quality or meter event. Minimum and maximum recording (min./max. 3-phase average current, max. I G, min./max. 3-phase average VLL and VLN, max. V NG, max. system Watts, vars, and VA, min./max. apparent and displacement PF). Using this feature, minimum and maximums reached during each trend interval are recorded. CBEMA Trend Logging The IQ Analyzer can be configured to store the necessary data so that PowerNet can display a sag or swell voltage event on the industry standard CBEMA (now ITIC) curve for predictive maintenance and troubleshooting. This application utilizes the IQ Analyzer waveform capture for high speed events along with historical trend logging for longer term voltage disturbances. Once this data is uploaded to a PC running the PowerNet Event Viewer the information is analyzed, displayed and stored. Automatic uploading of CBEMA events can be selected in PowerNet. A 3-phase event will be correctly displayed as a single point on the CBEMA curve. Event Logging The IQ Analyzer will store in nonvolatile memory the time and reason for the last 504 events. These events can be viewed from the graphical display or accessed via communications. In addition to all of the meter events listed in the Event Conditions section (Page 4), the following events are entered into the event log: Time and date of: Alarms Meter power up All resets All setting changes Communications established or lost Event logging is another powerful troubleshooting tool within the IQ Analyzer. Extensive I/O and Communications Capability One analog and three digital inputs are provided to interface with sensors and transducers. Four analog outputs and four relay contacts are furnished to share data with PLCs and control systems and to actuate alarms and control relays. Terminals are captive clamp type and finger safe. With the communications option, the device can be remotely monitored, controlled and programmed. Ratings Application to 500 kv, no PTs to 600V. CT ratios selectable from 5:5A to 10,000:5A. Standard 120/600V AC line. 3-phase power supply module, V AC. Separate source power supply module available, V AC or 100 to 250V DC. DC only separate source power module also available, 24 to 48V DC. Displayed Information Features All information accessible at device or through communications port via Cutler-Hammer PowerNet. Quality true rms readings through 50th harmonic. Complies with the accuracy portion of ANSI C12.20 Class 0.5% revenue metering specification. Accurate readings for nonsinusoidal waveforms with up to 3.0 crest factor. Screens display auto ranging units, kilo units, mega units as needed. 10-digit energy readings. Displays multiple parameters at the same time. Programmable custom screens. Meter Menu Screens The IQ Analyzer allows a user to view commonly used parameters by scrolling through its LED indicator Meter Menu. Meter Menu Examples of Meter Menu Custom Screen Custom Screen Meter Menu Displayed Information Phases A, B, C, Average Neutral Ground (separate CT) Phases A-B, B-C, C-A, Average Phases A-N, B-N, C-N, Average Neutral-Ground Power: Real (watts) Reactive (vars) Apparent (VA) Phases A, B, C, and system Energy (Forward, Reverse and Net): Real (kwh) Reactive (kvarh) Apparent (kvah) no reverse or net
4 Page 4 Effective: November 2001 Frequency, time and date. Demand: System current (amperes) Systems real power (kw) System reactive power (kvar) System apparent power (kva) Power Factor (Phases A, B, C, system): Displacement Apparent % THD Current: Phases A, B, C, N % THD Voltage: Phases A-B, B-C, C-A Phases A-N, B-N, C-N K-Factor. CBEMA (ITIC) derating factor (displayed as Z ). Crest Factor. Discrete input and output status. Analog input reading. Custom user may program four screens to show any combination of seven Meter Menu parameters per screen. Harmonic Analysis Screens Harmonic Spectrum Available with Model 6600 Minimum and Maximum Values: Phases A, B, C, N, G Phases A-B, B-C, C-A Phases A-N, B-N, C-N, N-G Power: Real (watts) Reactive (vars) Apparent (VA) Phases A, B, C and system. Power Factor: Apparent Displacement (3-Phase and system) Frequency. THD (amperes, volts, and %): Current (Phases A, B, C, N) Voltage (Phases A-B, B-C, C-A, A-N, B-N, C-N) All minimum/maximum values may be reset via reset pushbutton on faceplate, discrete input or communications command. Values are updated at least once every 16 line cycles. The F3 function key accesses the Harmonic Analysis screens. Two cycles of data sampled at 128 samples/cycle are simultaneously recorded for: Phases A, B, C, N, G Phases A-B, B-C, C-A Phases A-N, B-N, C-N Neutral to ground Magnitudes (or % of fundamental) of odd and even multiples of the fundamental from 2nd - 50th are displayed. The phase angle associated with each multiple of the fundamental is also displayed. Event/Alarm Analysis Screens Example of Event Analysis Screens Waveform Screen Available with Model 6600 Pressing the F2 function key accesses the Event Analysis screens. These display the following data for up to ten event/alarm conditions: Description, date, and time of event/alarm with 10 millisecond resolution. Current, voltages, power readings, demand readings, frequency and % THD at time of event/alarm. Current and voltage distortion information available on Harmonic Analysis screens. Event data is stored in non-volatile memory. If a reset threshold is programmed, the duration of the event (e.g., undervoltage) is also displayed. With the Cutler-Hammer PowerNet communications option and Series III software, waveforms and harmonic profiles may be displayed on a PC. Event Conditions Events may be triggered by up to seven of any of the following conditions: Voltage Disturbances Undervoltage/sag any V L-L, V L-N (40-100%). Note: 60% minimum for self-powered unit. Overvoltage/swell any V L-L, V L-N ( %). If zero time delay is programmed, any disturbance lasting 2 cycles (less if magnitude is sufficient to effect rms readings) will trigger a voltage disturbance event/alarm. Sub-cycle transient capture/excess dv/dt on V A-N, V B-N, V C-N. Sub-cycle voltage interruption on V A-N, V B-N, V C-N. Note: 6600 Series only. Maximum Threshold Exceeded Phases A, B, C, Neutral, and Ground Neutral to Ground System Power: Watts, VA, vars System Power Factor: Displacement and Apparent Demand Phase A, B, C and I AVG System Power: Watts, Vars, VA Frequency % THD or Magnitude THD. Phases A, B, C, neutral V A-N, V B-N, V C-N, V A-B, V B-C, V C-A
5 Effective: November 2001 Page 5 Minimum Threshold Exceeded Phases A, B, C System Power: Watts, vars, VA System Power Factor: Displacement and Apparent Frequency Voltage Phase Unbalance Voltage L-L, L-N Current Phase Unbalance Phases A, B, C Discrete Input Energized Input 1, 2, 3 Cutler-Hammer PowerNet Communications Remote command though communications port or front panel. All trigger conditions have programmable time delays from 0.1 to 60 seconds in 0.1 second increments (except Voltage Disturbances programmable from cycles in 2-cycle increments, and Cutler- Hammer PowerNet command no programmable delay). Demand Recording Peak Demands are date and time stamped for: Phases A, B, C, average System Power: Real (watts) Reactive (vars) Apparent (VA) Input/Output Extensive input/output capability is standard on the IQ Analyzer. In addition to monitoring 3-phase currents and voltages, separate inputs are provided for both ground and neutral currents. Voltage of neutral-to-ground is also monitored to indicate the presence of harmonics and potential downstream grounding problems. Analog and digital I/O provide interfaces for transducers, relays, PLCs and control systems. Current Inputs Five ampere secondary CT connections for: Phases A, B, C Ground Neutral Separate ground and neutral CT inputs. CT range 5:5 to 10,000:5 (any integer) Voltage Inputs Phases A, B, C (from 120V AC 500 kv AC). 120/240V AC control power input standard not required with optional line power module. Separate ground-to-neutral voltage reference. PT range 120:120 to 500,000:120 (any integer). External 120-volt secondary PTs are required above 600V AC, optional from V AC. Discrete Contact Inputs Three dry contact discrete inputs may be programmed by the user to: Trigger Event Analysis the information described in Event Analysis Screens, including Harmonic Analysis information, can be recorded when external devices trip or change state by wiring their auxiliary contacts into these inputs. Act as a synch-pulse input to synchronize power demand windows with utility provided synch pulse. Actuate a relay output. Reset relay output, peak demands, Trend Analysis records and Event Analysis records. With communications option, provide remote status indication on Cutler-Hammer PowerNet network. Status of input contacts is displayed in the Meter Menu Custom screen. Relay Output Contacts Four Form-C (NO/NC) relay contacts may be independently programmed to: Act as a kwh, kvarh or kvah pulse initiator output. Actuate on one or more event conditions including discrete input and Cutler-Hammer PowerNet command (through communications port). Reverse Sequence Alarm. Each Relay may be set for Auto or Manual Reset with 0 30 minute release delay (one second increments). Relays are Form-C NO/NC. Relay(s) programmed to actuate on undervoltage also have a programmable 0 30 minute delay on power-up for transfer applications. Analog Input and Outputs One analog input and four analog outputs may be configured as 0 20 or 4 20 ma. The analog input is displayed at the device as a percentage and is accessible through the communications port. The analog input provides an interface with gas flow meters, temperature transducers or other analog devices. The analog outputs may be programmed to reflect any of the following: Phases A, B, C, average, N, G L-L, L-N, N-G Power: Real (watts) Reactive (vars) Apparent (VA) Phases A, B, C and system % THD: Current (Phases A, B, C, N) Voltage (L-L, L-N) Frequency: System Power Factor: System displacement PF System apparent PF
6 Page 6 Effective: November 2001 Input/Output Capabilities Power Module Connection Separate Source Power Suppl Relay #1 Relay #2 Relay #3 Relay #4 System Voltage Connections Line Control Power L3 L2 A L1 Open Delta Fuse n Note s Optional Under 600V B Fuse A B C Vac/dc Connections) C Input/Output Capabilities Neutral Term. H1G H2G H1N H2N H1C H2C H1B H2B Current Transformer Connections H1A H2A 3CT 2CT 1CT Load IQ Analyzer Earth Ground Analog Input Common Analog Outputs Remote Inputs Field Replaceable Fuse Communication Connection 3-Phase 3-Wire (Above 600 Volts) External Potential Transformers and Current Transformers Relay No. 1 Relay No. 2 Relay No. 3 Relay No Discrete Contact Inputs Analog I/O Outputs (+) (-) (+) (-) (+) (-) GND Definition of Power Quality Terms Displacement Power Factor = W W 2 + Var 2 = Fundamental (60 Hz) watts to (60 Hz) VA. A ratio of fundamental (60 Hz) real power to apparent power. Apparent Power Factor = W VA = Total rms watts to VA. A ratio of total real power (including harmonic component) to apparent power. K-Factor = 2 I Sh n n è æ -- I ø ö S I n è æ -- ø ö 2 I 1 A derating factor which is related to the sum of the squares of harmonic currents times the squares of their harmonic numbers (multiples of the fundamental). CBEMA Factor = 2 2I RMS ---- = CF IPeak A transformer harmonic derating factor (THDF) defined as a pure sine wave s crest factor (1.4141) divided by the measured crest factor. Crest Factor = I Peak I RMS Ratio of peak current to rms current. Figure 1. Field Wiring Connections Separate Source Power Supply Shown Here (For 3-Phase Power Supply, No Separate Control Power is Required)
7 Effective: November 2001 Page 7 Figure 2. Dimensions and Cutout 8.90 Figure 3. Drilling Pattern Figure 4. Drilling Pattern for Flange Mounting CL RAD 4 Places CL Typ. for DIA 10 Places Specifications Fuses Self-powered units with IQMSSPM have 3/4 ampere, 600 volts bus type KTK-R-3/4 fuses (3 required). Separate source dual voltage units with IQMSSPM have a single 5 x 20 mm 1/4 ampere fuse. Separate source DC units with IQMDCPM do not have user replaceable fuses. Environmental Conditions Operating Temperature: -20 to 70 C Storage Temperature: -30 to 85 C Operating Humidity: 5% to 95% relative humidity Device Weight: 5.8 Lbs (2.6 kg) Current Inputs (Each Channel) Conversion: True rms, 32 sample/cycle (all samples used in all rms calculations) CT Input: 5 ampere secondary any integer 5:5 to 10,000:5) Burden: 0.05 VA Power Supply PONI Overload Withstand: 40 amperes AC continuous, 300 amperes AC 1 second Range: 8X CT continuous Accuracy: 0.1% of CT primary rating, 0.2% of reading above 150% of rating, sinusoidal (see accuracy below for non-sinusoidal specifications) Input Impedance: ohm Voltage Inputs (Each Channel) Conversion: True rms, 32 samples/cycle (all samples used in all rms calculations) PT Input: Direct or any integer 120:120 to 500,000:120 Range: 30 to 660V AC separate source and DC source) Nominal Full Scale: V AC Burden: 21 VA (self-powered only) Overload Withstand: 635V AC, continuous 700V AC, 1 second Input Impedance: 1 megohm Frequency Range Hz fundamental (up to 50th harmonic) Harmonic Response (Voltages, Currents) 50th harmonic Accuracy (in percent full scale) Accuracy from 3 300% of full scale and from to 1.00 to 0.5 power factor. Current and Voltage: ± 0.20% Power, Energy, and Demand: ± 0.40% Frequency: ± 0.04% Power Factor: ± 0.80% % THD: ± 1.00% Specific Current Accuracies: ±0.20% of full scale to 200% of full scale and 150% crest factor
8 Page 8 Effective: November 2001 Specifications (Continued) ±0.20% of full scale to 150% of full scale and 200% crest factor ±0.20% of full scale to 100% of full scale and 300% crest factor ±0.40% of reading for currents to 800% of full scale Power and Energy: Start recording with an average of 3 ma secondary current Discrete Inputs (Dry Contact) +30V DC differential across each discrete input pair of terminals. Minimum Pulse Width: 1.6 msec Optically isolated inputs to protect IQ Analyzer circuitry. Analog Outputs (4) 0 to 20 ma/4 to 20 ma into maximum 750 ohm load. Accuracy: 1% Analog Input (1) 0 to 20 ma/4 to 20 ma into 200 ohm load. Accuracy: 1% Relay Output Contacts (4) Form C Dry Contact: 10 amperes at 120/240V AC (Resistive) 10 amperes at 30V DC (Resistive) 30 amperes make (50 ms) at 240V AC/240V DC Minimum Pulse Width: 4 cycles (68 ms) Withstand Rating: 1000V AC, 1 minute across contacts 5000V AC (contacts to coil, 1 minute) 10,000V AC (contacts to coil, surge voltage) Relay Response Time (excluding programmed time delays): 2 line cycles for discrete Input, Cutler-Hammer PowerNet command (communications port). 4 5 line cycles for voltage disturbance, voltage unbalance line cycles for all others. Table 1. Control Power Input Description Separate Source Self Powered DC Source Input Range, AC V AC ±10% V AC ±10% N/A Frequency Range Hz Hz N/A Input Range, DC V AC ±10% N/A 24 48V DC ±20% Burden 21 VA 21 VA 21 VA When directly wired to 480V AC, IQ Analyzer can ride through a continuous sag that is 20% of rated voltage. Ordering Information Table 2. Ordering Information Description IQ Analyzer, Separate Source Power Module IQ Analyzer, 24 to 48V DC Power Module IQ Analyzer, 3-Phase Power Module IQ Analyzer, Separate Source Power Module with Waveform Display and Sub-Cycle Voltage Disturbance Capture IQ Analyzer, 24 to 48V DC Power Module with Waveform Display and Sub-Cycle Voltage Disturbance Capture IQ Analyzer, 3-Phase Power Module with Waveform Display and Sub-Cycle Voltage Disturbance Capture IQ Flange, to Provide Extra Clearance When Mounting 36-inch (914.4 mm) Extension Cable for Remote Mounting of Power Module 45-inch ( mm) Extension Cable for Remote Mounting of Power Module PowerNet Waveform Display Software 24 to 48V DC Separate Source Power Module V AC and V DC Separate Source Power Module 3-Phase, Self Powered Power Module INCOM Communication Module Ethernet Communications Module (10Base-T) Ethernet Communications Module with Fiber Optic Port (10Base-T and 10Base FL) Web-Enabled Communications Module IQ Analyzer/IQ DP-4000 Auxiliary Power Supply Portable IQ Analyzer with IPONI Catalog Number IQA6410 IQA6420 IQA6430 IQA6610 IQA6620 IQA6630 IQFLANGE IQACABLE IQA45CABLE NPWAVEFORM IQMDCPM IQMSSPM IQM3PPM IPONI EPONI EPONIF WEBPONI IQDPAUXPS IQA6600PORTI Eaton Corporation Cutler-Hammer business unit 1000 Cherrington Parkway Moon Township, PA USA tel: Eaton Corporation All Rights Reserved Printed in USA Publication No. November 2001
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D
7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values
Model 8220. POWER QUALITY ANALYZERS, METERS & LOGGERS Power Quality Meter
Special product features '''' ENERGY METER ''' MEASURES RPM POWER QUALITY ANALYZERS, METERS & LOGGERS Power Quality Meter Model A measurement tool for electrical parameters and distribution network disturbances
Power Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
Energy Management Energy Meter Type EM23 DIN
Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy
ATC-300 Automatic Transfer Switch Controller
ATC-300 Technical Data New Information Technical Data Page 2 Effective: May 2004 ATC-300 Introduction The Cutler-Hammer ATC-300 from Eaton s Electrical business is a comprehensive, multi-function, microprocessor-based
Applications. diris_826_a_1_gb_cat
Measurement units NEW diris_824_a_1_cat Energy monitoring and management of low voltage/ high voltage electrical installations Function are measurement units which can provide all the functions offered
Power quality monitoring and analysis with reliability
Power quality monitoring and analysis with reliability PowerLogic CM4000 series circuit monitors Buildings Industry Data Center Intelligent metering and control devices Whether in offices, classrooms,
POWERLOGIC Circuit Monitor Series 2000
Class POWERLOGIC Circuit Monitor Series 2000 Features True rms metering Certified ANSI C2.6 revenue accuracy High accuracy 0.2% current and voltage Power quality readings THD, k-factor, crest factor Over
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
Pow-R-Con Multi Function Control
37264 Pow-R-Con Multi Function Control Product Specification Product Specification 37264 Product Information DYNA Power Controls Pow-R-Con TM GENERAL The Barber-Colman Pow-R-Con TM represents an integrated
A project to optimise quality and energy efficiency must include metering
EMDX 3 : Energy Metering A project to optimise quality and energy efficiency must include metering Metering upstream identifies the critical points and ensures optimum targeting of the actions to be taken,
T 3000. Substation Maintenance and Commissioning Test Equipment
T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy
Eaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
User Manual V1.0 2014 SDM220MODBUS. Single-Phase Two Module DIN rail Meters
SDM220MODBUS Single-Phase Two Module DIN rail Meters Measures kwh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc. Di-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting 36mm
Quick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
Transient Recorder and Power Meter With Advanced Power Quality and Communication
www.electroind.com Transient Recorder and Power Meter With Advanced Power Quality and Communication Communication and User Interface Standard 10/100BaseT Ethernet Port Expandable Serial Ports (Dual RS485
Power System Harmonics
Pacific Gas and Electric Company Power System Harmonics What are power system harmonics? Ideally, voltage and current waveforms are perfect sinusoids. However, because of the increased popularity of electronic
DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters
The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual
FP-4000 Feeder Protection
FP-4000 Feeder Protection Technical Data TD02602007E Effective September 2007 Supersedes TD02602003E Pages 1 8, Dated March 2006 FP-4000 FP-4000 Product Description........................... 2 Application
Titelgrau belassen! Leere Vorlage
Titelgrau belassen! Leere Vorlage MAVOWATT 20 Energy Platform Energy and Power Analyzer MAVOWATT 20 The new Energy and Power Analyzer 2 Klaus-Peter Richter Product Management 10.3.2010 Page 2 Applications
How Do You Reduce Energy Costs And Prolong The Life Of Your Equipment?
How Do You Reduce Energy Costs And Prolong The Life Of Your Equipment? PowerLogic PM800 series power meters Buildings Industry Data Center Compact power, energy and power quality meters The Square D PowerLogic
Electronic Control Devices The European Product Catalogue 2007
FX07 Field Controller (1/4) FX07 Field Controller Display Model Dimensions in mm (inches) The FX07 is a terminal unit controller in the Facility Explorer range of products. The controller is designed specifically
PowerLogic power-monitoring units. PM5350 power meter. Technical data sheet
PowerLogic power-monitoring units PM5350 power meter Technical data sheet Mid-range metering PM5350 Functions and characteristics PE86278 The PowerLogic PM5350 power meter offers all the measurement capailities
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES
SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a
RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
Panel Meters and Controllers Modular Panel Meter Type EDM 35
Panel Meters and Controllers Modular Panel Meter Type EDM 35 Modular digital panel meter, 3 1/2-digit Indicating or controlling current, voltage, resistance, temperature, tacho or frequency. Easy programming
3U 4V 4A L1 L2 L3 V2 = 314 V3 = -84 N = -14 > ensuring high performance C.A 8332B C.A 8334B C.A 8335 POWER AND ENERGY QUALITY ANALYSERS
v 3 9. v C.A 833B C.A 8334B C.A 8335 9.3 v The experience of the Qualistar ensuring high performance POWER AD EERGY QUALITY AALYSERS 3U 4V 4A L1 L L3 Measure all the necessary voltage, current and power
Energy Management Power Analyzer Type WM14-96 Basic Version
Energy Management Power Analyzer Type WM-96 Basic Version Optional dual pulse output Alarms (visual only) V, An Optional galvanically insulated measuring inputs Product Description 3-phase power analyzer
CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410
The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
Power Monitoring and Control Systems Catalog. Class 3000
Power Monitoring and Control Systems Catalog Class 3000 Table of Contents Power Monitoring and Control Systems Introduction... Page 4 Power Meters... Page 8 Circuit Monitors... Page 12 System Manager
Power Quality Standards for Electric Service
Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as
Power Meter Series 800
PowerLogic power-monitoring units Power Meter Series 800 Technical data sheet 2007 Functions and characteristics E90463 PB101813-51 PB101823-50 DB111799 Front view of Power Meter Series 800 meter with
Bulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor
LogicLab s.r.l Via della valle 67 20048 Carate Brianza (MI) Tel. +39 0362 805287 Fax. +39 0362 1914102 www.logiclab.it
Test system DV1512A2NCI Single Current Generator Maximum current 15 Arms in continuity and 30 Arms per 1 s Single Voltage generator 150 Vrms Programmable phase between Current and Voltage Programmable
PLA 44. Power quality analyzer. User and service manual. BMR trading
PLA 44 Power quality analyzer User and service manual version 1.2 BMR Lipovka 17 516 01 Rychnov n. Kn. 1 Tel: +420 774 415 703 Fax: +420 494 533 602 Content 1. Front panel...3 5.6.1. List of events...8
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
SECTION 16911 WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM
WEB-BASED POWER MONITORING COMMUNICATIONS SYSTEM PART 1 GENERAL 01 02 03 04 SCOPE This section describes the metering, communications, and visualization requirements for a modular, scalable Web-based Power
EARTH LEAKAGE PROTECTION: CONTENTS
EARTH LEAKAGE PROTECTION: CONTENTS Earth Leakage Relays 128-130 Trip Circuit Supervision Relays 128-130 TEMPROTECT Protection and Distribution 1A to 6300A page 127 EARTH LEAKAGE PROTECTION ELR-1E The ELR-1E
MAJORSINE Power Inverter
MAJORSINE Power Inverter Product Features: 24, 48, 130 V 1 KVA/800 Watts Output 2 KVA/1600 Watts Output 100-120 VAC Range 208-240 VAC Range Standard 19 /23, Pure Sine Wave Output High Low EMI/RFI Emissions
The Basics of Digital Multimeters
IDEAL INDUSTRIES INC. The Basics of Digital Multimeters A guide to help you understand the basic Features and Functions of a Digital Multimeter. Author: Patrick C Elliott Field Sales Engineer IDEAL Industries,
GTEC transfer switch open transition
GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility
LOXONE 12 Channel Amplifier
LOXONE 12 Channel Amplifier Item no.: 200110 Thank you for purchasing the Loxone Twelve Channel Amplifier. The versatility of the Amplifier makes it the perfect choice for almost every type of custom multi-room
Three phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
Uninterruptible Power Supply
96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features
For a complete explanation of all the functions and configurations available please refer to the SC6006: Manual of operation.
PRELIMINARY TECHNICAL INFORMATION Three-phase Digital SCR Firing Board HIGHLIGHTS - Up to 480 V AC input supply voltage - Up to 700 V AC sync input - DSP controlled - Digital or analog input signaling
Applications. Remote Display Mounting Kits
June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge
CruzPro VAF110. AC Volts, Amps, Frequency, kw Monitor
CruzPro VAF110 AC Volts, Amps, Frequency, kw Monitor Table of Contents Introduction............................ 3 Specifications........................... 4 Installation..............................5
Table of Contents. TransformerIQ FAQs 1
[12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is
1.44 kw Programmable DC Power Supplies XLN Series
Data sheet 1.44 kw Programmable DC Power Supplies XLN Series New Family of High Density System Power Supplies The B&K Precision XLN series are compact, programmable, single-output DC power supplies, suitable
Application/Connection Examples
This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.
Multilin EPM 6000. GE Grid Solutions. High Accuracy Power & Energy Measurement. Monitoring & Metering. Advanced Communications.
GE Grid Solutions Multilin EPM 6000 High Accuracy Power & Energy Measurement The Multilin EPM 6000 is one of the industry s highest performance revenue grade panel meters with superior cost to performance
3500/22M Transient Data Interface
3500/22M Transient Data Interface Bently Nevada* Asset Condition Monitoring Description The 3500 Transient Data Interface (TDI) is the interface between the 3500 monitoring system and GE s System 1* machinery
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage
NETWORK ENABLED EQUIPMENT MONITOR
NETWORK ENABLED EQUIPMENT MONITOR Remotely Monitor Sensors over the Internet Connect Sensors to the Web to Remotely Monitor Equipment, Processes or Other Applications A Complete, Easy to Deploy, Stand-Alone
THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit 55-77-03-62, March 2012
Technical Information THYRISTORS T1-1PH from 850A to 2700A Specifications Universal 1 Phase Thyristor Unit 55-77-03-62, March 2012 GENERAL DESCRIPTION THYRISTORS T1-1PH is a full digital and universal
Power Electronics Testings
Power Electronics Testings PV Inverter Test Solution www.chromaate.com Turnkey Test & Automation Solution Provider w w w.chromaate.com A PV system is an energy system which directly converts energy from
APSYN420A/B Specification 1.24. 0.65-20.0 GHz Low Phase Noise Synthesizer
APSYN420A/B Specification 1.24 0.65-20.0 GHz Low Phase Noise Synthesizer 1 Introduction The APSYN420 is a wideband low phase-noise synthesizer operating from 0.65 to 20 GHz. The nominal output power is
H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.
Application : The transducer RISH CON - CA/CV (Fig.1) converts a sinusoidal AC Current or AC Voltage into a load independent DC Current or a load independent DC Voltage proportional to the measured value.
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
Polyphase kwh Electricity Meter
Polyphase kwh Electricity Meter Model Type: 5192B USER MANUAL Issue 1.0 E & O E AMPY Automation Ltd. July 2003 doc. ref. CSD 093 Contents 1 Introduction 2 1.1 Purpose 2 2 Definitions 2 2.1 References 2
M2M The measure of efficiency
M2M The measure of efficiency The importance of control Measurement and advanced analysis of electrical parameters To make equipment as efficient as possible, it is essential to know the details of its
NC-12 Modbus Application
NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1
SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General
SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General A. Electrical usage on the Brown campus is presently monitored by a Siemens-brand, web-based central metering system, which includes
CPS 100 480Y S K CPS 100 480Y S C
Ref. No. 1299 Visor Series Ordering Guidelines Table.1-4. Retrofit Surge Protection Products TVSS General Description Clipper Power System Visor Series CPS 100 480Y S K.1-9 Surge Ratings 100 = /phase 120
Test & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
Relion 605 series. Self-powered feeder protection REJ603 Product Guide
Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection Product Guide Product version: 3.0 Contents 1.... 3 2. Relay functions... 3 3. Protection functions... 4 4. Application...
Automation System TROVIS 6400 TROVIS 6493 Compact Controller
Automation System TROVIS 6400 TROVIS 6493 Compact Controller For panel mounting (front frame 48 x 96 mm/1.89 x 3.78 inch) Application Digital controller to automate industrial and process plants for general
TDMS Test & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
Electrical Monitoring and Control System Solution. Guideform Specification
Electrical Monitoring and Control System Solution Guideform Specification 1 SYSTEM... 2 1.1 Overview... 2 1.2 System Solution Functional... 2 1.2.1 Monitoring... 2 1.2.2 Power Quality... 4 1.2.3 Cost Allocation
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
Electrical Measuring Instruments
Electrical Measuring Instruments Index Contents: Page Measuring Centres MC 320 Energy meter, MC 330 Multimeter 3 MC 760/UMC 760 Network Analyzer, MC 750/UMC 750 - Network Recorder 5 MC 740 Multifunction
TECHNICAL SPECIFICATIONS FOR 1.5 KVA ONLINE UPS
Capacity Technology Inverter Technology Noise Level Operating Temperature Humidity Harmonic Distortion Total DC bus voltage Battery recharge time (After Complete discharge) to 100% charge Crest Factor
Always On UPS Systems Inc., #100-150 Campion Road, Kelowna, BC Canada V1X 7S8
Door Mount UPS (Patent Pending) Shelf Mount UPS (Patent Pending) DESCRIPTION: The Always On NDM (door mount) and NSM (shelf mount) Series UPS s are dual conversion online UPS systems provided in slim,
Safety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
FREJA 300 Relay Testing System
Relay Testing System A Megger Group Company FREJA 300 Relay testing system The FREJA 300 relay testing system is a computer-aided relay testing and simulation system. The weight of FREJA 300 is only 15
Galleon 6-10K Online UPS. Voltronic Power Technology Corporation
Galleon 6-10K Online UPS Voltronic Power Technology Corporation Features Galleon online UPS series delivers optimal power quality, provides superior power management, resolves utility power protection
DCS Series 1 kw, 1.2 kw, & 3 kw
DCS Series 1 kw, 1.2 kw, & 3 kw AVAILABLE WITH LXI STANDARD COMPLIANT ETHERNET Applications Automotive Electronics Rackmount ATE System Battery Charging DCS Series DCS Series: 1 kw, 1.2 kw, & 3 kw DCS
Figure 1 - Crydom 3RHP Three-phase Hybrid Solid State Contactor. Crydom Inc.
Crydom RHP Series 3 Phase Hybrid Solid State Contactor By Paul Bachman Fellow Engineer, Crydom, Inc. ABSTRACT Solid State Relays and Contactors (SSRs) have been available in one form or the other for over
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
E-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port
OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port MODEL NUMBER: OMNIVS1500 Highlights 1500VA / 1.5kVA tower 120V line-interactive UPS Corrects brownouts and overvoltages from 75 to 147V
PRO370D 65A Mbus MID DIN rail three phase four wire energy meter. User manual Version 1.03
PRO370D 65A Mbus MID DIN rail three phase four wire energy meter User manual Version 1.03 1 Safety instructions... 3 2 Foreword... 4 3 CE certificates... 5 4 MID certificate... 7 5 Performance criteria...
Overview. 1. GPS data tracking via GSM SMS / GPRS. 2. GPS data logging in internal memory. 3. Alarm alert via GSM SMS / Dialing / GPRS
Vehicle or Personal Position Tracking Vehicle Status and Speed Tracking Auto Accident Report Global Position System (GPS) Navigation System Anti theft Alarm System Overview 1. GPS data tracking via GSM
Maximum Demand Control
Maximum Demand Control There are three terms that appear on the majority of electric company bills: Active energy consumption (kwh) Reactive energy consumption (kvarh) Maximum Demand Traditionally, utility
1587/1577. Insulation Multimeters. Technical Data. Two powerful tools in one.
1587/1577 Insulation Multimeters Technical Data Two powerful tools in one. The Fluke 1587 and 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true-rms digital multimeter
MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)
MILLENIUM Table of contents 1. INTRODUCTION 1 2. HARDWARE DESCRIPTION 2 3. INSTALLATION 5 4. CONNECTION 6 5. USER SAFETY AND PROTECTION OF EQUIPMENT 8 1. Introduction The MILLENIUM series has been designed
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE
Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,