1 Tier Classification of Data Centres Eric Maddison Senior Consultant, The Uptime Institute

2 Uptime Institute Unbiased and vendor neutral Global thought leadership for the data center industry Founded 1993 Standards and Training > Created the global data center Tier Classifications System > Certification of Designs, Facilities, Operations > Training of data center engineers and operators > Data Center Due Diligence Assessment > Management & Operations Stamp of Approval > Facilities Management Program Development Uptime Institute Network > North America, EMEA, APAC and LATAM Symposium Annual industry event 2

3 Uptime Institute EMEA Team Established 2012 Based in London and Dubai Commercial and service delivery capabilities Part of global Uptime Institute organisation > Global standards > Local execution 3

4 Uptime Institute Tier Standards 4

5 Why does Tier Certification matter? Quality and reliability of the data center > Independent third party review by Uptime Institute > Globally understood standard (Tier I, II, III and IV) > Protects against loss of weakness in infrastructure > Ensures consistent solution Enterprise Recognizes organizational accomplishment > Demonstrate to senior management that performance capability is there Positioning and differentiation > An Uptime Institute certified data center has an expected level of resilience corresponding to business requirements > Service Level Agreements can be quantified 5

6 Tier Certifications Worldwide 6

7 Uptime Institute Tier Standard Owners Advisory Committee Members Owner Advisory Committee (OAC) is a consortium of data center owners/operators having received Uptime Institute Tier Certifications > OAC is a formally organized group created to validate and endorse the contents and direction of the Tier Standards OAC represents global leaders in the Financial, Healthcare, Insurance, Manufacturing, Retail, and Government industries OAC members are worldwide: Australia, Brazil, Canada, Costa Rica, India, Kingdom of Saudi Arabia, Luxembourg, Russia, South Africa, Spain, Switzerland, Taiwan, UAE, UK, and the U.S. 7

8 Tier Classification Genesis An Owner s Request Data Center Performance and Investment Criteria An Industry Solution Tier Classifications Define Site Infrastructure Performance An International Standard Data Center Site Infrastructure Tier Standard Annually Adjudicated Standard Owners Advisory Committee (OAC) 8

9 Evolution of Tier Documentation 2008 and previous > White paper: Industry Standard Tier Classifications Define Site Infrastructure Performance Included attributes at request of operations teams Provided illustrations at request of engineering community 9

10 Illustrations Removed 10

11 Attributes Table Eliminated TIER I TIER II TIER III TIER IV Building Type Tenant Tenant Standalone Standalone Staffing None 1 Shift 1+ Shifts 24 by Forever Usable for critical load 100%N 100%N 90%N 90%N Initial build-out UPS output watts/ft² (typical) Ultimate UPS output watts/ft² (typical) Class A uninterruptible cooling No No Maybe Yes Support space to raised floor ratio 20% 30% % 100+% Raised floor height (typical) Floor loading lbs/ft² (typical) Utility voltage (typical) 208, , kv kv Single points-of-failure Many + human error Many + human error Some + human error Fire+ EPO + human error Annual site caused IT downtime (actual field data) 28.8 hours 22.0 hours 1.6 hours 0.8 hours Representative site availability 99.67% 99.75% 99.98% 99.99% Months to implement 3 3 to 6 15 to to 20 Year first deployed

12 Tier Standards Tier Standard: Topology > Defines Tier Classification System > Performance Requirements for each functionality objective Tier Standard: Operational Sustainability > Defines Expected Operational Behaviors > Aligned by Tier Both Are Owner Standards 12

13 Tier Standards The Current Versions 13

14 Tier Standard Topology 14

15 Definitions N R = Required number of units (components) necessary to meet need = Capacity of system when discussing the design load or demand (Excludes IT-level architecture redundancy) = Number of redundant components Outage = A loss of IT equipment Loss of utility power, water, gas, or a hot day are expected events 15

16 Tier Classification Objectives Provide a common understanding and language of data center infrastructure concepts Identify expected data center performance by differences in topology > Recognize that all data centers are not alike nor need to be > Refers to a single operations site Tier concepts are simple; application requires extreme diligence 16

17 Tier Topology Concepts Tier Classifications represent broad topology concepts > Redundant capacity components > Redundant (diverse) distribution paths > Classification based on Maintenance opportunity and Failure response Fractional concepts are not recognized > No Standard for Tier III.6 > Tier III + is undefined > Tier rating tied to lowest system 17

18 Tiers Pertain to Design Topology Configuration of the site infrastructure equipment > Maintenance opportunities > Fault response Driven by owner s tolerance for an outage > Planned or unplanned downtime Do not address operation or location of the facility 18

19 Key Tier Topology Principles Begin and end at the IT Critical Environment > Owner decides what is critical or not Build upon the previous Tier Provide facility operation and maintenance opportunities Considers only the built environment > Temporary, roll-up, emergency, truck-mounted equipment not factored 19

20 Tier Classifications Tier I Basic Capacity Tier II Redundant Components Tier III Concurrently Maintainable > Applies to Each and Every component and path Tier IV Fault Tolerant > Considers a Single event, but Consequential impact 20

21 Tier I Basic Capacity Summary > Non-redundant capacity components ( N only) Critical Environment power and cooling systems > Single distribution path Operations and Maintenance Considerations > Site infrastructure and Critical Environments must be shut down for annual maintenance and repair work > Installation or construction of capacity may disrupt the Critical Environment 21

22 Tier I Operational Risks Any capacity component or distribution path element failure will disrupt the Critical Environment All or portions of the Critical Environment are susceptible to disruption due to planned and unplanned activities Operations (Human) errors have high likelihood of site disruption Deferred maintenance to avoid downtime increases the risk and severity of disruptions in the Critical Environment 22

23 Tier II Redundant Components Summary > Redundant capacity components (N+R) Engine generators, UPS modules, IT and UPS cooling > Single distribution path Operations and Maintenance Considerations > Some capacity components can be maintained or repaired with limited impact to the Critical Environment > Site infrastructure and Critical Environments must be shut down for annual maintenance and repair work > Installation or replacement of capacity components may disrupt the Critical Environment 23

24 Tier II Operational Risks A capacity component failure may disrupt the Critical Environment A distribution path element failure will disrupt the Critical Environment All or portions of the Critical Environment are susceptible to disruption due to planned and unplanned activities Operations (Human) errors have high likelihood of site disruption Deferred maintenance to avoid downtime increases the risk and severity of disruptions in the Critical Environment 24

25 Tier III Concurrently Maintainable Summary > Redundant capacity components and independent distribution paths (transformers and transfer switches are path elements) > Elements of a distribution path may be inactive > Predicated on dual-cord IT equipment > No runtime limits on engine-generator capacity at design load Operations and Maintenance Considerations > Each and Every capacity component and distribution path element can be taken out of service for maintenance, repair, or replacement without impacting the Critical Environment or IT processes 25

26 Tier III Practical Insight Each and Every extends to: > Valves and fittings > Switchgear and panels Maintenance focus requires: > Dead lugs for safety during electrical activities > Dry pipes to avoid liquid spills Single Points-of-Failure are not eliminated 26

27 Tier III Operational Risks All or portions of the Critical Environment are susceptible to disruption due to failures or unplanned activities Scheduled maintenance activities occur on redundant components, distribution paths, and systems which will reduce redundancy and may elevate risk of disruption Operations (Human) errors may lead to site disruption Single-cord IT equipment or incorrect installation may defeat Tier III infrastructure 27

28 Tier IV Fault Tolerant Summary > Redundant capacity components > Redundant active distribution paths > Compartmentalization of both capacity components and distribution paths > N after any failure > Continuous Cooling for critical IT and UPS systems > No runtime limits on engine-generator capacity at design load Operations and Maintenance Considerations > Each and Every capacity component and distribution path element can sustain a failure, error, planned, or unplanned event without impacting the Critical Environment or IT processes 28

29 Tier IV Practical Insight Single event with consequential impact > Loss of a switchboard impacts everything downstream powered by that switchboard > Replacing a valve requires a dry pipe on both sides Continuous Cooling must be consistent with UPS for IT equipment power Most human errors are considered failure events > Exceptions: Emergency Power Off (EPO) Activations Fire Suppression Activations Failure to properly connect IT loads 29

30 Tier IV Operational Risks The Critical Environment is not susceptible to disruption due to failure of any single capacity component, distribution element, site infrastructure system, or single human error Scheduled maintenance activities occur on redundant components, elements, and systems which may create a risk of disruption Operation of the EPO system, activation of the fire protection system, or malicious human interaction may lead to site disruption Single-cord IT equipment or incorrect installation may defeat Tier IV infrastructure 30

31 Tier IV Autonomous Response Operator intervention shall not be required to respond to single system failure Control system failure shall not disrupt Critical Environment > Critical Environment must remain stable with failed control system Tier IV data center facility infrastructure control systems > Detect system failure > Isolate and contain failure > Sustain N capacity after failure of any component or path 31

32 Tier Standard Topology Application to Mechanical and Electrical Systems 32

33 N Either kw or number of capacity components > Capacity of system to meet the load > Required number of units to meet the load 33

34 Nominal Capacity: 300 kw Example Components: N = 1 Capacity: N = 300 kw Components: N = 2 Capacity: N = 300 kw 34

35 N+1 Components N= 300 kw 600kW Installed N + 1= Component Count 450 kw Installed Stranded capacity is underutilized investment but running all pumps at reduced speed saves energy 35

36 2N Capacity N= 300 kw 600 kw Installed 36

37 N and Tiers No direct relationship between N and Tiers N+R or 2N does not guarantee functionality If N is one piece of equipment, N+1 = 2N = S+S > What Tier? 2N does not speak to Concurrent Maintainability or Fault Tolerant criteria N is often applied to capacity components, but not distributions paths > Common shortfall 37

38 Component Count Does Not Determine Tier Level The Uptime Institute: > N+1, N+2, N+N or 2(N+1) does not determine Tier level > It is possible to achieve Tier IV with just N+1 components for some systems 38

39 Tier I Chilled Water Distribution Components: N = 2 Basic Capacity Chilled Water Supply Chilled Water Return 39

40 Tier II Chilled Water Distribution Components: N = 2 Redundant Components Chilled Water Supply Chilled Water Return 40

41 Tier III Chilled Water Distribution Components: N = 2 Concurrently Maintainable Chilled Water Supply Chilled Water Return 41

42 Tier III Chilled Water Distribution Components: N = 2 Concurrently Maintainable Chilled Water Supply Chilled Water Return 42

43 Tier III Chilled Water Distribution Components: N = 2 Concurrently Maintainable Chilled Water Supply A and B Chilled Water Return A and B 43

44 Tier IV Chilled Water Distribution Components: N = 2 Chilled Water Supply A and B Concurrently Maintainable Fault Tolerant Chilled Water Return A and B 44

45 Tier I Chilled Water System Basic Capacity 45

46 Tier II Chilled Water System Redundant Components 46

47 Tier III Chilled Water System Concurrently Maintainable 47

48 Tier IV Chilled Water System Components N = 2 Fault Tolerant Concurrently Maintainable 48

49 2.4.1.d) Continuous Cooling Continuous Cooling is the capability to maintain steady state in the Critical Environments during a UPS discharge when neither utility nor enginegenerator power is available > Computer rooms, Network rooms, UPS rooms Corollary to uninterrupted power for IT devices Continuous Cooling is required to meet Tier IV criteria > Part of the Tier Standard: Topology 49

50 Tier I Power Backbone Basic Capacity 50

51 Tier II Power Backbone Redundant Components 51

52 Tier III Power Backbone Concurrently Maintainable 52

53 Tier IV Power Backbone Concurrently Maintainable Fault Tolerant 53

54 Tier III Engine-Generator Concept (2N) N = 2 Concurrently Maintainable 54

55 Tier III Engine-Generator Concept (N+1) N = 2 Concurrently Maintainable 55

56 Tier IV Engine-Generator Concept (N+1) N = 2 Concurrently Maintainable Fault Tolerant 56

57 Utility Power For Tier III and IV, engine-generator systems are considered the source of reliable power for the data center Utility power is an economic alternative The utility power system does not have to be Concurrently Maintainable Multiple utility feeds for redundancy are NOT required for any Tier > Multiple utility feeds may be required for capacity 57

58 Engine-Generator Ratings International Standards Organization (ISO) is the governing document Rating classifications > Emergency Standby > Prime > Continuous Major differences in operating hours and power output capacities 58

59 Standby Rating Definition > The maximum power available during a variable electrical power sequence, under the stated operating conditions, for which a generating set is capable of delivering in the event of a utility power outage or under test conditions for up to 200 hours of operation per year ISO But > The permissible average power output over 24 hours of operation cannot exceed 70% of the standby rating unless otherwise agreed by the manufacturer ISO

60 Prime Rating Definition But > The maximum power which a generating set is capable of delivering continuously while supplying a variable electrical load when operated for an unlimited number of hours per year ISO > The permissible average power output over 24 hours of operation cannot exceed 70% of the Prime rating unless otherwise agreed by the manufacturer ISO

61 Continuous Rating Definition > The maximum power which the generating set is capable of delivering continuously while supplying a constant electrical load when operated for an unlimited number of hours per year ISO

62 Rating Examples (Same Frame) 62

63 Tier Standard Topology Additional Considerations 63

64 2.4.1.c) Compartmentalization Applies to complementary systems and distribution paths in Tier IV topology Tier IV requires physical isolation to prevent a single event from simultaneously impacting more than the number of redundant components or systems Each compartment shall contain no more than the number of redundant components > Where there are N+R components, no more than R components inside a single room 64

65 Equipment Compartmentalization Not Compliant with Tier IV Requirements 65

66 Effective Compartmentalization Secondary Chilled Water Pumps N=3 (R=1) Tier IV Compliant Chilled Water Machines and Primary Pumps N=4 (R=2) 66

67 Electrical Compartmentalization Not Compliant with Tier IV Requirements 67

68 Electrical Compartmentalization Tier IV Compliant 68

69 Electrical Compartmentalization Not Compliant with Tier IV Requirements 69

70 Electrical Compartmentalization Tier IV Compliant 70

71 Distribution Path Not Compliant with Tier IV Requirements 71

72 Distribution Path Tier IV Compliant 72

73 Site Communications Path POP A POP B Not Compliant with Tier IV requirements Concurrently Maintainable paths required for Tier III Common vault is not Fault Tolerant Compartmentalized path required for Tier IV 73

74 2.6 Ambient Temperature Design Points For all Tiers, equipment to be selected and sized per ASHRAE Handbook Fundamentals extreme maximums > Dry Bulb: N=20 value > Wet Bulb: Extreme Maximum Value Ambient temperatures impact the capacity of cooling equipment and engine-generator radiators Equipment must be sized to meet the extreme maximum temperatures Altitude over 3,000 feet may also impact capacity 74

75 ASHRAE Design Conditions Reference: 2009 ASHRAE Handbook Fundamentals (Updated and Published every 4 years) DALLAS, TEXAS, USA Monthly Design Dry Bulb Temperature Profiles (July) Required for all Tiers Extreme Annual Design Conditions 2% 1% 0.4% N=20 years 35.7 C 36.8 C 38.0 C 43.3 C 96.3 F 98.2 F F F (Probable) Hours Exceeded 15 hours 7.5 hours 3 hours Unlikely (20-year period) 75

76 Manufacturing Tolerances This means that a nominal 100kW unit could actually deliver only 92kW The performances are obtained through calculations and they are therefore subject to the consequent variations. Declared performances according to EN14511:

77 Fuel System Tier Progression Tier I Fuel storage to support engine generator Tier II Redundant tanks and pumps Tier III Redundant fuel supply paths to N engine generators Tier IV Autonomous control response to component or path failure 77

78 Fuel System Tier Criteria Tanks, piping, and pumps > Minimum of 12 hours of on-site fuel storage for all Tiers > Concurrently Maintainable for Tier III > Fault Tolerant for Tier IV while engines are in operation! Tier III fuel system must provide fuel from N tanks to N engines during scheduled maintenance on any fuel system component Tier IV fuel system controls must respond to system failures autonomously > Fuel system must provide fuel to N engines after any failure > Isolate and contain a leak or other failure 78

79 Fire Detection and Suppression Systems Application of Tiers focuses on the connection between the fire detection/suppression system and the HVAC and electronic systems supporting the critical environment Does not include the physical suppression system > e.g., sprinkler piping, sprinkler valves, etc. Tier III requires that the Critical Environment must not be impacted by any fire detection/suppression component taken out of service for calibration, repair, or replacement on a scheduled basis Principal Tier IV consideration > Tier IV requires autonomous response to failure 79

80 Building Automation Includes > Supervisory Control and Data Acquisition (SCADA) > Plant Controls (BAS or BMS) > Emergency Power Off (EPO) Tier III requires that the Critical Environment must not be impacted by any control element taken out of service for calibration, repair, or replacement on a scheduled basis Principal Tier IV consideration > Tier IV requires autonomous response to failure 80

81 Other Ancillary Systems No Tier-level specific or Certification criteria > Building Pressurization (Makeup Air Systems) > Battery Room Ventilation > Water Treatment Systems > Free-cooling or Economizer Systems > Lightning Protection > Grounding > Fuel Polishing Integrate carefully! 81

82 Component Labeling All Tier levels require that each and every critical component is uniquely labeled > e.g., CH-1 (chiller #1), UPS-1A, etc. > Includes breakers and valves Required to develop commissioning plans, preventive maintenance program, and operational procedures 82

83 Tier Standard Operational Sustainability 83

84 Operational Sustainability The behaviors and risks beyond Design Topology that impact the ability of a data center to meet its Business Objectives over the long term 84

85 Indicators of Operational Sustainability Shortfalls Computer room or storage space? Accident or poor planning? 85

86 Indicators of Operational Sustainability Shortfalls Office space in the computer room Mercedes in a data center support space 86

87 Genesis of Operational Sustainability Uptime Institute over the years has observed management issues posing the largest risk to uptime then physical infrastructure > Inadequate staffing > Ineffective or non-existing maintenance and training programs > Lacking processes and procedures > Resulting in the majority of outages being caused by human error No standard existed to help owners/operators determine > Common language/vocabulary of data center operations > Focus of data center management > Resource allocation > Justification of additional resources 87

88 Genesis of Operational Sustainability Failures Caused by human error 73% (and thus avoidable) Uptime Institute Abnormal Incident Reports through 1 January

89 Purpose of the Standard Addresses behaviors and risks to: > Reduce failures due to human error (cause of 70% of failures) > Achieve maximum potential from the facility infrastructure Provides a tool to measure a data center s Operational Sustainability using these behaviors and risks Retains focus on those items that will most improve the performance of a data center Encourages doing it your way results oriented > Behaviors, not requirements 89

90 An Owner s Standard Developed by Uptime Institute team with hands-on site operations experience Tier Standard: Operational Sustainability (1 July 2010) > Measures effectiveness of data center management > Assists owners to maximize the investment in infrastructure > Gives owners an indication of where the data center stands operationally in relation to others > Supports efforts to maximize uptime and minimize risk Adjudicated by the Owner s Advisory Committee 90

91 Elements of Operational Sustainability 91

92 Operational Sustainability Rating System 92

93 Relationship Between Tiers and Operational Sustainability Based on Business Objectives Increased rigor with increased uptime requirement > Greater management rigor required to achieve the design potential of Tier III and IV infrastructure > Change opportunities become more complex and require more planning to achieve Both Tier Classification System and Operational Sustainability required to meet business/uptime objectives 93

94 Tiers Summary 94

95 Mapping Business Objective to Tiers Can your organization afford to take the computer room down to perform infrastructure maintenance (planned downtime)? > If yes, Tier I or II > If no, Tier III or IV Can your organization afford unplanned downtime taking your computer room down? > If yes, Tier III > If no, Tier IV 95

96 Tiers Certification Process 96

97 Tier Certification Process Tier Certification Of Design Documents Tier Certification of Constructed Facility Tier Certification of Operational Sustainability Design Documents Meet the Tier Objective Data Center Meets Functionality for the Tier Objective Data Center Is Being Managed/Operated to Meet the Tier Objective For more information: 97

98 Tier Gap Analysis Before starting the formal Tier Certification process of existing data centers > Single in-office review of select design documents to identify common significant design shortfalls > Memo documents major gaps to the Tier objective > Conference call with owner team to discuss findings 98

99 Tier Certification of Design Documents Review of 100% design document package in Uptime Institute offices Deliverable of Tier deficiencies and Operational Sustainability enhancements Conference call with owner and design team to discuss report Compliance review of revised drawings Award letter and foil 99

100 Tier Certification of Constructed Facility On-site visit by team of consultants Identify discrepancies between design drawings and installed equipment Observe tests and demonstrations to prove Tier compliance Deliverable of Tier deficiencies and Operational Sustainability enhancements Conference call with owner team Award letter, foil, and plaque 100

101 Tier Certification of Operational Sustainability Site visit to review the facilities management Evaluate presence and effectiveness of staffing, training, maintenance program, processes, and procedures Scorecard and Gold, Silver, Bronze rating Certification becomes suffix to Tier > Tier III Gold 101

102 Global Tier Certifications Tier II 20 Tier III 224 Tier IV 50 Tier II 4 Tier III 76 Tier IV 14 Tier III Gold 4 Tier IV Gold 2 Certifications Underway Worldwide

103 Unbiased and vendor neutral thought leadership, research, and publications Thank you! Eric Maddison Uptime Institute Professional Services, LLC 103

Tier Standards. Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI. Consultant EMEA

Tier Standards. Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI. Consultant EMEA Tier Standards Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI Consultant EMEA Uptime Institute Unbiased and vendor neutral Global thought leadership for the data center industry Founded 1993 Standards and

More information

IKS Data Centres Conference Moscow 6 th September 2011 Mark Acton

IKS Data Centres Conference Moscow 6 th September 2011 Mark Acton IKS Data Centres Conference Moscow 6 th September 2011 Mark Acton data center management and engineering consultants professionalservices.uptimeinstitute.com 2011 Uptime Institute Professional Services,

More information

Uptime Institute Tier Standard for Data Centers Facts vs. Myths and Misconceptions

Uptime Institute Tier Standard for Data Centers Facts vs. Myths and Misconceptions Uptime Institute Tier Standard for Data Centers Facts vs. Myths and Misconceptions Presented by Kenneth ( Ken ) Brill, Founder Uptime Institute kgb@uptimeinstitute.com Agenda Introduction to Tiers Benefits

More information

Uptime Institute Tier Classification System & Operational Sustainability

Uptime Institute Tier Classification System & Operational Sustainability Uptime Institute Tier Classification System & Operational Sustainability April 17, 2012 Dana L. Smith data center management and engineering consultants http://uptimeinstitute.com/professional-services

More information

Data Center Site Infrastructure Tier Standard: Topology

Data Center Site Infrastructure Tier Standard: Topology U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2009-2012 by Uptime Institute, LLC 20 West

More information

Data Center Site Infrastructure Tier Standard: Topology

Data Center Site Infrastructure Tier Standard: Topology U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2010 by Uptime Institute, LLC 20 West 37th

More information

Data Center Commissioning: What you need to know

Data Center Commissioning: What you need to know Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, P.E., John H. Seader, P.E., and Kenneth G. Brill Widely accepted within the uninterruptible industry, The Uptime Institute s Tier Performance Standards are an objective basis for

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, P.E., John H. Seader, P.E., and Kenneth G. Brill Widely accepted within the uninterruptible industry, The Uptime Institute s Tier Performance Standards are an objective basis for

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance W h i t e P a p e r Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, PE, John H. Seader, PE, Vince Renaud, PE, and Kenneth G. Brill Table of Contents Executive Summary...

More information

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier

More information

Redundancy and Reliability for an HPC Data Centre

Redundancy and Reliability for an HPC Data Centre Available online at www.prace-ri.eu Partnership for Advanced Computing in Europe Redundancy and Reliability for an HPC Data Centre Erhan Yılmaz* 1 Ladina Gilly** 2 * National High Performance Computing

More information

Data Center Infrastructure & Managed Services Outline

Data Center Infrastructure & Managed Services Outline Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists

More information

Building a Tier 4 Data Center on a Tier 1 Budget

Building a Tier 4 Data Center on a Tier 1 Budget Building a Tier 4 Data Center on a Tier 1 Budget A Walk Through of TIA-942 Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc. March 27, 2008 BICSI South Central Region Meeting Denver, CO TIA-942

More information

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center

More information

Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM

Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM Data Center Management Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM A physical place that houses a computer network's most critical systems, including back-up power supplies, air conditioning, and

More information

BICSI 002 / TIA 942 / Uptime

BICSI 002 / TIA 942 / Uptime BICSI 002 / TIA 942 / Uptime Which Data Center Standard Should I Follow Phil Isaak, PE, P.Eng., RCDD, DCDC President, Master Instructor Isaak Technologies Inc. Standards Who are these People Standards

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle

More information

A Quick Primer on Data Center Tier Classifications

A Quick Primer on Data Center Tier Classifications A Quick Primer on Data Center Tier Classifications What You Should Know Before Starting a Data Center Project White Paper Abstract Data center facility projects are often driven by the Uptime Institute

More information

PAYGO for Data Center -- Modular Infrastructure

PAYGO for Data Center -- Modular Infrastructure PAYGO for Data Center -- Modular Infrastructure Introduction The infrastructure costs for Data Centers are increasing at a significant pace. Construction costs and their environmental impact are also soaring.

More information

MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS

MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively

More information

Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport

Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport Welcome Zenium Istanbul One provides 12,000 square metres of high specification technical space across three purpose-built data centers. It is Turkey s first wholesale data center offering; the data halls

More information

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is

More information

Increased power protection with parallel UPS configurations

Increased power protection with parallel UPS configurations Increased power protection with parallel UPS configurations Making the selection between Centralized Bypass and Distributed Bypass systems Janne Paananen Application Engineer, Large Systems Group Eaton

More information

plantemoran.com {Data center. } Design standards

plantemoran.com {Data center. } Design standards plantemoran.com {Data center. } Design standards IT systems have become critical for the day-to-day operations of today s organizations. {Data center.} Design standards IT systems are critical for the

More information

DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE

DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE Molex Premise Networks EXECUTIVE SUMMARY The term data centre usually conjures up an image of a high-tech IT environment, about the size of a football

More information

Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group

Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group The data center industry has experienced several evolutions over the past 20 years. One principal change has been the development of the

More information

Statement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

Statement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary Statement Of Work Professional Services Data Center Thermography Assessment Data Center Thermography Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits

More information

How To Write An Infrastructural Standard For Data Center Infrastructure

How To Write An Infrastructural Standard For Data Center Infrastructure Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers

More information

OPERATOR - FACILITY ADDRESS - DATE

OPERATOR - FACILITY ADDRESS - DATE . Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.

More information

The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements

The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements Edward P Rafter, P.E. CxAP Tier IV Consulting Group Synopsis The data center industry has experienced

More information

Modern Data Centers: Creating a New Value Proposition

Modern Data Centers: Creating a New Value Proposition Modern Data Centers: Creating a New Value Proposition América Latina 2008 Inter-secretarial Commission for the Development of Electronic Government Mexico City 24 May 2013 Data Center Consolidation Consolidating

More information

Designed for uptime. Defining data center availability via a tier classification system

Designed for uptime. Defining data center availability via a tier classification system Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center

More information

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center

More information

Assessment of Existing Data Centers for Critical Facilities Round Table Group

Assessment of Existing Data Centers for Critical Facilities Round Table Group Assessment of Existing Data Centers for Critical Facilities Round Table Group Chuck Shalley, P.E. Consulting Electrical Engineers BACKGROUND INFORMATION ASSIGNMENT Data Center Criteria Type Raised Floor

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information

How to Meet 24 by Forever Cooling Demands of your Data Center

How to Meet 24 by Forever Cooling Demands of your Data Center W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the

More information

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0. Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

Introduction to Datacenters & the Cloud

Introduction to Datacenters & the Cloud Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview

More information

EBRC Tier IV Certification of Constructed Facility: a premiere in Luxembourg

EBRC Tier IV Certification of Constructed Facility: a premiere in Luxembourg Press Release Luxembourg, 3 December 2013 EBRC Tier IV Certification of Constructed Facility: a premiere in Luxembourg The Uptime Institute recently awarded EBRC Resilience Centre South with the Tier IV

More information

Applications for Infrared Thermography at Computer Centers

Applications for Infrared Thermography at Computer Centers Applications for Infrared Thermography at Computer Centers By Eric Stockton CompuSCANIR, a division of Stockton Infrared Thermographic Services, Inc. 8472 Adams Farm Road Randleman, NC 27317 http://www.compuscanir.com/

More information

COMMODITIZING THE DATA CENTER MARKET

COMMODITIZING THE DATA CENTER MARKET COMMODITIZING THE DATA CENTER MARKET Site Summary The building at 1360 Kifer Road has approximately 94,500 SF of server and support space and is currently divided into two independent data center areas.

More information

Agility Logistics Datacenter Trends in Enterprises. Ben N. Hasnai VP IT Infrastructure and Operations

Agility Logistics Datacenter Trends in Enterprises. Ben N. Hasnai VP IT Infrastructure and Operations Agility Logistics Datacenter Trends in Enterprises Ben N. Hasnai VP IT Infrastructure and Operations Agility Business Globally Head office Revenue Market position Lines of business Operations Employees

More information

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G 100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the

More information

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features

More information

David Sandars Sales Director EMEA

David Sandars Sales Director EMEA David Sandars Sales Director EMEA Data Centre Introduction and Future Trends Datatapahtuma, Design Factory at Aalto University 9 th October 2014 Agenda What is a Data Centre? Key Characteristics Why are

More information

Dodging Data Center Operations Disasters

Dodging Data Center Operations Disasters Dodging Data Center Operations Disasters Philip Hu Managing Director - North Asia, Uptime Institute Thomas Baehr Sr. Director Management Services - APAC, Uptime Institute Data Centre World Hong Kong, May

More information

Strategic Data Centre Site Profiles Data Centre Co-Location London North

Strategic Data Centre Site Profiles Data Centre Co-Location London North Strategic Data Centre Site Profiles Data Centre Co-Location London North Document details Version: 1 Last Updated: 12/07/2013 Version 1.0 Page 1 of 6 Contents 1. LONDON NORTH...3 1.1 LOCATION...3 1.2 TECHNICAL

More information

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.

More information

Subject: County of Los Angeles Data Center Space Requirement

Subject: County of Los Angeles Data Center Space Requirement Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,

More information

Hosting Infrastructure. Overview and Benefits of Hosting Infrastructure

Hosting Infrastructure. Overview and Benefits of Hosting Infrastructure Hosting Infrastructure Overview and Benefits of Hosting Infrastructure Data Centre definition In it's simplest form, a data centre is a facility that houses IT equipment Servers, and networking kit. The

More information

AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)

AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:

More information

Data Centres A complete solution to noise control and acoustic packages

Data Centres A complete solution to noise control and acoustic packages Data Centres A complete solution to noise control and acoustic packages Introduction World class noise control. Expertise you can trust. IAC Acoustics is world-renowned for providing cost effective solutions

More information

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA

More information

A Framework for Developing and Evaluating Data Center Maintenance Programs

A Framework for Developing and Evaluating Data Center Maintenance Programs A Framework for Developing and Evaluating Data Center Maintenance Programs White Paper 178 Revision 0 by Bob Woolley > Executive summary Inadequate maintenance and risk mitigation processes can quickly

More information

DATA CENTRE DATA CENTRE MAY 2015

DATA CENTRE DATA CENTRE MAY 2015 DATA CENTRE DATA CENTRE MAY 2015 CONCERTHOUSE MUSIC Concerthouse Music Data Centre services are located in the Equinix Internet Business Exchange (IBX ) Centre at Mascot. This IBX offers the highest level

More information

Battery Monitoring Systems

Battery Monitoring Systems Cellwatch is a state of the art family of battery monitoring solutions that help prevent unplanned outages on critical power backup systems. Cellwatch was a pioneer in its ability to monitor batteries

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Sovereign. The made to measure data centre

Sovereign. The made to measure data centre Sovereign D ATA C O N N E C T The made to measure data centre Prime Location Within touching distance of everything that s important. 2 Your Customer-Centric Data Centre For the vast majority of organisations

More information

IBM Portable Modular Data Center Overview for Critical Facilities Round Table

IBM Portable Modular Data Center Overview for Critical Facilities Round Table Brian Canney Global Services Executive, IBM GTS Site and Facilities Services April 2011 IBM Portable Modular Data Center Overview for Critical Facilities Round Table 2009 IBM Corporation Key messages Containers

More information

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H. POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,

More information

SolveXia Business Continuity Planning

SolveXia Business Continuity Planning Business continuity planning is the term we use to describe all the steps we take at SolveXia to ensure that our service is up and running when you need it. As a 'Software as a Service' provider, our aim

More information

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that

More information

Data Center Solutions - The Containerized Evolution

Data Center Solutions - The Containerized Evolution Data Center Solutions - The Containerized Evolution Power IT Cooling 7 th Green Connected World Tsikogias Thanassis Data Centers Solutions Architect, IT Business Athens 2015 1 We are the global specialist

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical

More information

How To Visit An Internet Data Center

How To Visit An Internet Data Center AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina

More information

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...

More information

EXAMPLE OF A DATA CENTRE BUILD

EXAMPLE OF A DATA CENTRE BUILD EXAMPLE OF A DATA CENTRE BUILD BT Harmondsworth Data Centre Hall 2 Upgrade Temperature Control have been involved in providing specialist to data centres for over 20 years, starting from providing specialist

More information

PHP/MySQL APPLicAtion HoSting

PHP/MySQL APPLicAtion HoSting PHP/MySQL Application Hosting Connectivity DMD PHP/MySQL Hosting is partnered with a Kansas City, USA based Data Center connected to the internet through multiple backbones to ensure that the data is transmitted

More information

Data Center Site Infrastructure Tier Standard: Operational Sustainability

Data Center Site Infrastructure Tier Standard: Operational Sustainability U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Operational Sustainability Prepared by Uptime Institute Professional Services, LLC Copyright 2010 by Uptime Institute,

More information

Automated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview

Automated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview Automated Commissioning for Energy (ACE) Platform for Large Retail Property $62,900 dollars of energy savings identified during the first 6 weeks Overview The ability to pull large amounts of complex data

More information

Server Monitoring & Management Services

Server Monitoring & Management Services Server Monitoring & Management Services Monitor and manage your applications and servers under enterprise-class monitoring solutions, and protect your business from planned and unplanned downtime. ITI

More information

PROJECT REQUEST REPORT UNIVERSITY OF WASHINGTON DATA CENTER

PROJECT REQUEST REPORT UNIVERSITY OF WASHINGTON DATA CENTER UNIVERSITY OF WASHINGTON OFFICE OF THE VICE PROVOST PLANNING AND BUDGETING Capital and Space Planning PROJECT REQUEST REPORT UNIVERSITY OF WASHINGTON DATA CENTER JULY 31, 2006 University of Washington

More information

Data Center Colocation Build vs. Buy

Data Center Colocation Build vs. Buy Data Center Colocation Build vs. Buy Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for

More information

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus. DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure

More information

Data Center Combined Heat and Power Benefits and Implementation. Justin Grau, Google Inc. Sam Brewer, GEM Energy

Data Center Combined Heat and Power Benefits and Implementation. Justin Grau, Google Inc. Sam Brewer, GEM Energy Data Center Combined Heat and Power Benefits and Implementation Justin Grau, Google Inc. Sam Brewer, GEM Energy Data Center Challenges Electric Load Densification Thermal Dissipation Requires constant

More information

Dedicated Hosting Services

Dedicated Hosting Services Dedicated Hosting Services Protect and manage your Servers/ Routers/ Switches/ storage devices/ security devices under a highly secure hosting space and get the finest performances out of them. SERVICE

More information

GENERATOR RATINGS AND THE IMPLICATIONS FOR DATA CENTERS

GENERATOR RATINGS AND THE IMPLICATIONS FOR DATA CENTERS Systems POWER SYSTEMS TOPICS 109 GENERATOR RATINGS AND THE IMPLICATIONS FOR DATA CENTERS By Todd Matte Manager - Corporate Accounts Project Management Group KOHLER Systems Understanding how generator ratings

More information

COLOCATION A BUYERS GUIDE

COLOCATION A BUYERS GUIDE COLOCATION A BUYERS GUIDE INTRODUCTION Colocation in a data centre offers organisations a place to securely house their IT equipment, as opposed to storing and running it on-site, which can be both expensive

More information

Increasing safety, reliability and efficiency for today s data centers

Increasing safety, reliability and efficiency for today s data centers Increasing safety, reliability and efficiency for today s data centers Products and expertise for data center success Drawing upon vast experience in complex industries where uptime is critical, ABB provides

More information

The Pros and Cons of Modular Systems

The Pros and Cons of Modular Systems The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated

More information

Commissioning of Mission Critical Facilities

Commissioning of Mission Critical Facilities Commissioning of Mission Critical Facilities Terry L. Rodgers, CPE, CPMP VP of Sustainable Operations Primary Integration Solutions Paul Liesman SVP of FM & Commissioning Syska Hennessy Group AIA Quality

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

NO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM

NO-BREAK KS 7e. Concentrated Energy. 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM NO-BREAK KS 7e Concentrated Energy e 2750 kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM Data Centre owners, operators and designers are required to meet ever increasing and

More information

A risky business. Why you can t afford to gamble on the resilience of business-critical infrastructure

A risky business. Why you can t afford to gamble on the resilience of business-critical infrastructure A risky business Why you can t afford to gamble on the resilience of business-critical infrastructure Banking on a computer system that never fails? Recent failures in the retail banking system show how

More information

INSPECTION AND TESTING OF EMERGENCY GENERATORS

INSPECTION AND TESTING OF EMERGENCY GENERATORS INSPECTION AND TESTING OF EMERGENCY GENERATORS Certification requirements NFPA 101(00), Sec. 7.9.2.3 requires that emergency generators be installed, tested and maintained in accordance with NFPA 110,

More information

Capgemini UK Infrastructure Outsourcing

Capgemini UK Infrastructure Outsourcing Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,

More information

The Application of Circuit Breakers to Reduce Downtime in Datacentres

The Application of Circuit Breakers to Reduce Downtime in Datacentres The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the

More information

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM

Power Management Strategies for High-Density IT Facilities and Systems. A White Paper from the Experts in Business-Critical Continuity TM Power Management Strategies for High-Density IT Facilities and Systems A White Paper from the Experts in Business-Critical Continuity TM Executive Summary Increases in data center density and diversity

More information

Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+)

Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+) Design Consultant (Electrical Services) Design Deliverables and Responsibilities Allocation (Stage E+) 1. In addition to the information scheduled below, the pre-tender designer is responsible for: (i)

More information

Comparing UPS System Design Configurations

Comparing UPS System Design Configurations Comparing UPS System Design Configurations By Kevin McCarthy White Paper #75 Revision 1 Executive Summary There are five main UPS system design configurations that distribute power from the utility source

More information

Scalable. Affordable. Flexible. Fast.

Scalable. Affordable. Flexible. Fast. Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations

More information

Designing Fault-Tolerant Power Infrastructure

Designing Fault-Tolerant Power Infrastructure Designing Fault-Tolerant Power Infrastructure System Analysis and New Standards Enable Maximization of Operating Dependability for Data Centers & Other Mission Critical Facilities J.F. Christin (Author)

More information

Colt Colocation Services. 2010 Colt Technology Services Group Limited. All rights reserved.

Colt Colocation Services. 2010 Colt Technology Services Group Limited. All rights reserved. Colt Colocation Services 2010 Colt Technology Services Group Limited. All rights reserved. Award winning Colt Data Centre Solutions 2012: Modular Data Centre Solution of the year winner at 5 th Datacentre

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information