in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

Size: px
Start display at page:

Download "in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus."

Transcription

1 DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure that has evolved over time and that makes use of available space and systems. Structural concerns aside, the Data Center is located on the 2nd floor of the facility and is fairly exposed via large windows. Its location makes maintenance and access difficult given its primary entrance is within a working classroom. A seismic event that causes the local building official to prevent re-entry or occupancy has the potential to cause University IT operations to come to a stop. A severe windstorm or rainstorm could cause water and other physical damage given the Data Center s windows and IT equipment proximity to the exterior of the building. The Data Center does have local, rack-mounted uninterpretable power systems (UPS) providing power conditioning and battery-back-up allowing graceful & orderly shutdown of servers within a 30 minute period. However, the Data Center lacks a back-up generator to support the UPS systems and HVAC for the Data Center during extended outages. During a localized power outage at the Founders Hall, the IT systems supported by the data center are unavailable locally in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus. Mechanical Systems serving the Data Center appear to be partially redundant allowing concurrent maintenance of mechanical cooling systems components. Electrical Systems serving the Data Center appear to be nonredundant and do not allow concurrent maintenance of electrical systems components without a data center shutdown. The importance of having access to data center services all the time will become a necessity in the future. As distance learning and collaborative/hybrid teaching models evolve, reliance on the network and servers will become absolute. Suffering a data outage will become more impactful to the University s main educational mission. The current high risk of a data center service outage coupled with a growing dependency on those services should cause the University to strongly consider construction of a new Data Center on or off campus. Less typical of data center that have evolved over the long period, the IT Server, SAN and Network topologies and strategies are fairly robust with a reliance on visualization and redundant communication links to outlying facilities and remote campuses. The current IT infrastructure and telecommunications cabling topology simplifies locating a new Data Center in a new Campus building 146

2 CURRENT Current campus technology infrastructure consists largely of a central data center that provides a variety of services to on-campus and remote buildings through both local area networks and wide area networks. These networks carry both voice and data services utilizing a combination of fiber optic network (oncampus) and leased telecommunications connectivity (remote campuses). The current data center server infrastructure is nearly fully virtualized which creates scalability, flexibility and adaptability. New services can be added quickly and easily. The facility that houses the data center is one of the original campus buildings. As such, there are severe limitations with regard to data center growth, data center redundancy, maintainability, and survivability. The current on-campus telecommunications pathways are generally adequate for current needs with the exception of connections across Arrow Highway which are of very limited capacity. The current campus does make use of Wi-Fi, but will need to plan for cabling and network upgrades to support higher bandwidth width wi-fi technologies. Current classroom technology ranges from use of white boards, over head projectors, and short throw overhead projectors coupled to instructor station computers. Existing classroom layouts have been modified to support use of limited technology, often in ways that are less than optimal. Effective collaboration enhancement is not currently achieved by these limited classroom technology installations. SCALABILITY The campus has a good starting point with its adoption of Air-Blown Fiber Optic Cabling (ABF) which provides a scalable approach for both adding bandwidth and buildings. Use of Single-Mode Fiber optic cable provides higher bandwidth capability over longer distances. This should be the media of choice for intra-campus design. FLEXIBILITY AND ADAPTABILITY The existing Air-blown Fiber network should be expanded. ABF technology allows fiber strands to be removed and replaced without access to pullboxes or other intermediate points along a fiber run. Spare tubes will allow fiber to be upgraded without downtime. Intermediate Tube Distribution Units (TDUs) enable a direct point to point pathways to be configured between individual buildings. RELIABILITY Telecommunications Cabling The system should be expanded to allow for loop or ring diversity as University operations become more dependent on the network at the main campus and the remote campus locations. Dual disparate pathways should be created from each building to the data center to increase service reliability. 147

3 MASTER PLAN RECOMMENDATIONS Campus Infrastructure With voice over Internet Protocol (VOIP) the need for multi-pair copper cabling has been greatly reduced. Future Campus Infrastructure will be designed around mostly fiber optic cable with only a small contingent of copper (50-pairs per building) for analog phone lines referred to as (POTS) or Plain Old Telephone Service. Certain building services such as elevator phone and fire alarm dialers require these copper pairs. To remain flexible the Fiber Optic cable Infrastructure should have the ability to change the number of strands and type of fiber cable as needed. This will be achieved with the use of air blown fiber (ABF), which is already deployed in a limited capacity on the main campus. The ABF is essentially a network of small tubes and tube distribution units (TDU) that can be plugged and unplugged to create a dedicated air and water tight path between any (2) points on Campus. Fiber strands are installed or extracted with the use of compressed inert gas. To achieve reliability the physical campus infrastructure should be configured such that any one building will have (2) physically redundant connections to the Campus Data Center. These physical connections will ideally take (2) disparate paths to the Data Center. Additional redundancy can be achieved by having an additional Data Center. Within new buildings a structured cabling approach should be considered. A 4-pair Category 6 cable provides transmission bandwidth up to 1000Mb/second and is suitable for most student or faculty workstation applications. A 4-pair Category 6A cable provides up to 10Gbit/second bandwidth and is suitable for extremely high capacity workstation applications and audio video transmission. WiFi throughout interior and exterior spaces will permit laptops, tablet devices, and smart phones to communicate at bandwidths up to 60 Mb/second. 148

4 MAIN CAMPUS The importance of having access to data center services all the time will become a necessity in the future. As distance learning and collaborative/hybrid teaching models evolve, reliance on the network and servers will become absolute. Suffering a data outage will become more impactful to the University s main educational mission. A new Campus Data Center is recommended in order to support the increasing importance of connectivity and the data-centric world that already exists today. The future data center will be located in a new campus building, purposefully-built with the ability to expand or contract based on modular building blocks (space, airconditioning, and power). Data center cabinets will be standardized to a universal configuration. Accessible overhead pathways will allow easy patching between cabinets. Spare multi-strand and multi-cable assemblies will accommodate quick reconfiguration in between cabinets to facilitate adding bandwidth or services in near real time. MAINTAINABILITY The new data center shall be concurrently maintainable where possible allowing maintenance of mechanical or electrical system without taking the data center off-line. The new Data Center should be purposefully-built to house critical telecommunications equipment. There will be a need for reliable environmental control to maintain strict operating temperature and humidity margins. Multiple Computer Room Air Conditioners (CRACs) will be used in an N +1 configuration such that design capacity is still maintained while any one component is turned off (or failed). An intelligent HVAC control panel will insure that all CRACs are run periodically on a rotation basis. Server cabinets should be arranged in a hot aisle / cold aisle alternating pattern per current best practices to maximized air flow efficiency. A hot aisle containment system will be installed around each hot aisle to prevent supply/ return air mixing further increasing HVAC efficiency and to comply with 2013 California Energy Code (CEC). Additional CEC requirements will include an air side of water side economizer to utilize outside air for Data Center air conditioning when environmental conditions permit. Power system should be equally robust and redundant to support the telecommunications equipment as well as the HVAC equipment. The new data center should be supported by a fuel cell or diesel generator capable of providing power to IT equipment, HVAC systems, lighting, and support systems for the Data Center. An automatic transfer switch (ATS) will automatically start the generator and switch over from utility power during a power outage. The Data Center should be equipped with N+1 UPS system to provide ride-over power during transition from utility power to generator power. Modern servers and switching equipment are equipped with dual redundant power supplies with (2) or more cords and plugs. The Data Center power should be routed from redundant power sources within the Data Center. If dual (redundant) UPSs are not specified then redundant power should be sourced from a non-ups circuit to mitigate the impact of a UPS failure. The Data Center should not be located below drains or pipes containing liquid. A dry sprinkler system should be installed so that water is not expelled if a sprinkler head is accidentally knocked off. A dry agent fire suppression system should be considered as well as an emergency power off system (EPO) to allow IT equipment to be shut off prior to release of any fire suppression agent or potential sprinkler activation. The Data Center will not require a raised floor for power distribution or air circulation. An acoustical t-grid drop tile ceiling configuration with ducted supply will provide the most efficient method of air distribution. Power outlets should be located above the server cabinets mounted on telecommunications style ladder tray. In lieu of conventional power distribution an overhead busway system such as Starline, which allows easy snap in and out of various receptacle types, should be considered. 149

5 DATA CENTER RELIABILITY The existing data center will remain the single active data center until the future redundant data center is built and dual pathways have been established to each building. The future data center will be designed with N+1 reliability standard in mind. While not completely fault tolerant, elements of certain infrastructure systems should be made fault tolerant. Examples include use of on-site generation (fuel cell or diesel generator), two electrical systems feeding each data center cabinet. Dual disparate pathways should be created from the data center to both the University s service providers and the campus telecommunications infrastructure to increase service reliability. REMOTE CAMPUS Each remote campus, generally leased facility of up to 15 classrooms, should be equipped with redundant telecommunications service providers to ensure uninterrupted connectivity. Each remote campus network node/it room should be located in a dedicated space and equipped with a minimum of two telecommunications cabinets ( 1 for Audio Visual equipment, 1-for network equipment & voice/data cabling). The node/it room will service all classrooms, offices, and WiFi antennae in the building. The existing Data Center located in Founder s Hall could be decommissioned or maintained as a fail-over Data Center until such time as an off-site redundant Data Center or Co Location Facility can be established. 150

Academic and Technology Resources

Academic and Technology Resources Academic and Technology Resources 140 VISION INTRODUCTION Technology should effectively support pedagogy and multiple learning modalitites to facilitate the teaching and learning process. technology resources

More information

TECHNOLOGY. The seamless integration of technology resources into every space on all campuses is the goal through new construction and renovation

TECHNOLOGY. The seamless integration of technology resources into every space on all campuses is the goal through new construction and renovation VISION FLEXIBLE The design must allow for degrees of flexibility. This may mean more diverse types of spaces, such as small work areas adjacent to lecture rooms or groupings of educational programs into

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center

More information

Data Center Management

Data Center Management Data Center Management How Cisco IT Operates, Manages, and Protects Its Data Center A Cisco on Cisco Case Study: Inside Cisco IT 1 Overview The Cisco IT Operations Data Center on the San Jose, California

More information

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier

More information

Data Centers, Information Technology and Low Current Services

Data Centers, Information Technology and Low Current Services Data Centers, Information Technology and Low Current Services 1 Data Centers and Low Current Services SDT offers a wide-ranging variety of professional services to Data Centres and Low Current operators.

More information

Data Center Infrastructure & Managed Services Outline

Data Center Infrastructure & Managed Services Outline Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists

More information

Data Center Design Considerations. Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc.

Data Center Design Considerations. Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc. Data Center Design Considerations Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc. Data Center Design: Overall Expectations Need: Prime vs. Redundant vs. Mirrored

More information

DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE

DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE Molex Premise Networks EXECUTIVE SUMMARY The term data centre usually conjures up an image of a high-tech IT environment, about the size of a football

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Build for Tomorrow. Today.

Build for Tomorrow. Today. Commercial Building Systems Build for Tomorrow. Today. 2010 Legrand. All Rights Reserved. LG1621 0610 designed to be better. Cablofil On-Q Ortronics Pass & Seymour Vantage WattStopper Wiremold Legrand,

More information

OPERATOR - FACILITY ADDRESS - DATE

OPERATOR - FACILITY ADDRESS - DATE . Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.

More information

Building a Tier 4 Data Center on a Tier 1 Budget

Building a Tier 4 Data Center on a Tier 1 Budget Building a Tier 4 Data Center on a Tier 1 Budget A Walk Through of TIA-942 Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc. March 27, 2008 BICSI South Central Region Meeting Denver, CO TIA-942

More information

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. 1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking

More information

Data Centers and Mission Critical Facilities Operations Procedures

Data Centers and Mission Critical Facilities Operations Procedures Planning & Facilities Data Centers and Mission Critical Facilities Operations Procedures Attachment A (Referenced in UW Information Technology Data Centers and Mission Critical Facilities Operations Policy)

More information

Data Center Presentation

Data Center Presentation Data Center Presentation The NetSource Datacenter. Agenda General Layout of Data Center Policies and Procedures Designed to Latest Standards High Performance High Reliability High Security Design Details

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical

More information

by Metagyre, Inc. September 27, 2010

by Metagyre, Inc. September 27, 2010 NewCo Data Center Assessment by September 27, 2010 Metagyre Account Manager Contact Paul Thompson 1249 NW Arcadia Ct. Suite 300 Poulsbo, WA 98370 voice - 360 697-3386 fax 360 697-6676 pthompson@metagyre.com

More information

OPERATIONS MANUAL DATA CENTER COLOCATION

OPERATIONS MANUAL DATA CENTER COLOCATION Section I: Introduction and Service Description. OPERATIONS MANUAL DATA CENTER COLOCATION Company means MCI Communications Services, Inc., d/b/a Verizon Business Services, or any affiliated entity designated

More information

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009 Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of

More information

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features

More information

Data Center Cabling Design Trends

Data Center Cabling Design Trends Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:

More information

san francisco//usa data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence

san francisco//usa data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in San Francisco, USA. We can colocate standard rack-mountable servers

More information

ASX Australian Liquidity Centre. ASXCoLo

ASX Australian Liquidity Centre. ASXCoLo ASX Australian Liquidity Centre ASXCoLo Australian Liquidity Centre Location The ASX Australian Liquidity Centre is located at: Gore Hill Business Park 219-247 Pacific Highway Artarmon. NSW, 2064 The location

More information

Perceptive Software Platform Services

Perceptive Software Platform Services Perceptive Software Platform Services CLOUD SOLUTIONS process and content management Perceptive Software Platform Services Perceptive Software process and content management systems have been deployed

More information

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G 100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the

More information

TELECOMMUNICATION SYSTEM HAZARD MITIGATION STRATEGIC PLANNING

TELECOMMUNICATION SYSTEM HAZARD MITIGATION STRATEGIC PLANNING TELECOMMUNICATION SYSTEM HAZARD MITIGATION STRATEGIC PLANNING A.K. Tang 1 1 President, L&T Engineering and Project Management Consultant, Mississauga. Canada Email: alexktang@mac.com ABSTRACT: Telecommunication

More information

POWERING A CONNECTED ASIA. Pacnet Hong Kong CloudSpace1 Technical Specifications. Asia s Pioneering Facility with Direct Subsea Cable Access

POWERING A CONNECTED ASIA. Pacnet Hong Kong CloudSpace1 Technical Specifications. Asia s Pioneering Facility with Direct Subsea Cable Access POWERING A CONNECTED ASIA Pacnet Hong Kong CloudSpace1 Technical Specifications Asia s Pioneering Facility with Direct Subsea Cable Access Our purpose-built, 300 m 2 Pacnet Hong Kong CloudSpace1 (HKCS1)

More information

World-Class Data Centers, Colocation, Cloud & Management Services. Central and Southern Oregon Locations East and West of the Cascade Divide

World-Class Data Centers, Colocation, Cloud & Management Services. Central and Southern Oregon Locations East and West of the Cascade Divide World-Class Data Centers, Colocation, Cloud & Management Services Central and Southern Oregon Locations East and West of the Cascade Divide Data Center facilities located East and West of the Cascade Divide.

More information

Colt Colocation Services. 2010 Colt Technology Services Group Limited. All rights reserved.

Colt Colocation Services. 2010 Colt Technology Services Group Limited. All rights reserved. Colt Colocation Services 2010 Colt Technology Services Group Limited. All rights reserved. Award winning Colt Data Centre Solutions 2012: Modular Data Centre Solution of the year winner at 5 th Datacentre

More information

South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime

South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in

More information

SolveXia Business Continuity Planning

SolveXia Business Continuity Planning Business continuity planning is the term we use to describe all the steps we take at SolveXia to ensure that our service is up and running when you need it. As a 'Software as a Service' provider, our aim

More information

Using Industrial Ethernet Switches to Assure Maximum Uptime White Paper

Using Industrial Ethernet Switches to Assure Maximum Uptime White Paper Six Best Practices for Effective Wind Farm Operation Using Industrial Ethernet Switches to Assure Maximum Uptime White Paper Six Best Practices for Effective Wind Farm Operation Using Industrial Ethernet

More information

Network Design. Yiannos Mylonas

Network Design. Yiannos Mylonas Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which

More information

hong kong//china data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence

hong kong//china data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in Hong Kong, China. We can colocate standard rack-mountable servers or

More information

Keyword: TIA 942, Tier level, Nuclear Data Center. Introduction

Keyword: TIA 942, Tier level, Nuclear Data Center. Introduction Nuclear Data Center International Standard Towards TSO Initiative Raja Murzaferi Raja Moktar, Mohd Fauzi Haris, Siti Nurbahyah Hamdan, Saaidi Ismail,Radhiah Jamaluddin, Nursuliza Samsudin. IT Center, Technical

More information

19 Site Location, Design and Attributes. Site Location, Design and Attributes

19 Site Location, Design and Attributes. Site Location, Design and Attributes 1 Site Location, Design and Attributes The Primary Data Center shall be physically located on Oahu, Hawaii. 2 Site Location, Design and Attributes The Primary Data Center shall be located at least 1 mile

More information

CommScope Intelligent Building Infrastructure Solutions (IBIS)

CommScope Intelligent Building Infrastructure Solutions (IBIS) SYSTIMAX Solutions CommScope Intelligent Building Infrastructure Solutions (IBIS) Questions & Answers Q. What is an Intelligent Building? A. An intelligent building can be defined as one which provides

More information

NY-1 DATACENTER AT A GLANCE. NY-1 is a Tier III-rated, SAS SSAE16 and HIPAA-certified data center

NY-1 DATACENTER AT A GLANCE. NY-1 is a Tier III-rated, SAS SSAE16 and HIPAA-certified data center NY-1 1.866.WEBAIR.1 WWW.NY1.WEBAIR.COM NY-1 LONG ISLAND S MOST SECURE, FULLY-REDUNDANT DATA CENTER ENTERPRISE COLOCATION, PRIVATE AND HYBRID CLOUD SOLUTIONS, AND MANAGED SERVICES. DATACENTER Enjoy the

More information

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design.

Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Data Centre Stockholm II, Sweden Flexible, advanced and efficient by design. Equinix Telecity Kvastvägen 25-29 128 62 Sköndal Stockholm Sweden Tel: +46 (0) 8 799 3800 se.info@telecity.com www.telecitygroup.se

More information

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA

More information

Data Center Overview Document

Data Center Overview Document Overview NetSource is a Chicago area (Naperville) hosting company that owns and operates its own world class datacenter. The initial datacenter buildout was put into operation in 2007 and expanded in 2013.

More information

UW MEDICINE SITE CONFIGURATION STANDARDS Overview

UW MEDICINE SITE CONFIGURATION STANDARDS Overview UW MEDICINE SITE CONFIGURATION STANDARDS Overview UW-IT is deploying Voice over IP (VoIP) phone service to improve and expand existing voice services, leveraging state-of-the-art capabilities that allow

More information

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging

More information

IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com. 2011 IBM Corporation

IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com. 2011 IBM Corporation IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com Overview Profile IBM owned facility 6447 m² IT-Space Infrastructure concurrent maintainable (Tier Level 3) Feed-ins of Power

More information

Pacnet Hong Kong CloudSpace2 Technical Specifications. Upholding the Principles of Efficiency and Sustainability in Data Center Design

Pacnet Hong Kong CloudSpace2 Technical Specifications. Upholding the Principles of Efficiency and Sustainability in Data Center Design POWERING A CONNECTED ASIA Pacnet Hong Kong CloudSpace2 Technical Specifications Upholding the Principles of Efficiency and Sustainability in Data Center Design Our purpose-built, 5,000 m 2 Pacnet Hong

More information

DISASTER RECOVERY AND NETWORK REDUNDANCY WHITE PAPER

DISASTER RECOVERY AND NETWORK REDUNDANCY WHITE PAPER DISASTER RECOVERY AND NETWORK REDUNDANCY WHITE PAPER Disasters or accidents would cause great harm on network infrastructure. It is unavoidable and the operation of network would be hampered for a long

More information

Introduction to Datacenters & the Cloud

Introduction to Datacenters & the Cloud Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview

More information

Introducing UNSW s R1 Data Centre

Introducing UNSW s R1 Data Centre Introducing UNSW s R1 Data Centre R1-DC Our New High Density Data Centre Right here Right now - Welcome to our newest UNSW Data Centre R1-DC R1 Location on UNSW Randwick campus. Keeping it in the family

More information

NeuStar Ultra Services Physical Security Overview

NeuStar Ultra Services Physical Security Overview NeuStar Ultra Services Physical Security Overview Mission-critical network operations must have the highest standards of quality, security and reliability. NeuStar Ultra Services currently locates its

More information

Colocation Service Definition. SD008 v1.3 Issue Date 19 Feb 09

Colocation Service Definition. SD008 v1.3 Issue Date 19 Feb 09 Colocation Service Definition SD008 v1.3 Issue Date 19 Feb 09 Colocation Service Definition Service Overview InTechnology offers secure data centre environments for your business critical systems, applications

More information

The Three Principles of Data Center Infrastructure Design WHITE PAPER

The Three Principles of Data Center Infrastructure Design WHITE PAPER The Three Principles of Data Center Infrastructure Design WHITE PAPER The Three Principles of Data Center Infrastructure Design Understand These Three Principles and You ll: Lower your total cost of ownership

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation Data Center Pre-terminated Patch Panel System Patch Panels Plug & Play Installation 10G + Gigabit Patch Cords Bundled + Labeled Cabling Systems Simplified Our Mission At Cablesys, our mission is to simplify

More information

Data Center Commissioning: What you need to know

Data Center Commissioning: What you need to know Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,

More information

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.

More information

Scalable. Affordable. Flexible. Fast.

Scalable. Affordable. Flexible. Fast. Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations

More information

How To Move Your Data Center

How To Move Your Data Center The IT Management Guide to Business Relocation Relocating your business is a major project that entails careful planning. You want to minimize the disruption to your business, provide a new space that

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA)

AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA) AT&T Internet Data Center Site Specification Washington-DC Area (Ashburn, VA) Site Biography Market Area: Washington, DC Area Location: Ashburn, VA 20147-6011 Address: All deliveries should be sent to

More information

Zone Distribution in the Data Center

Zone Distribution in the Data Center Zone Distribution in the Data Center By Jennifer Cline, RCDD As data centers face the continued need to expand and grow, the fundamental concerns and needs remain constant. Key concerns of the data cabling

More information

www.quicknetworksolutions.net RC: 960240

www.quicknetworksolutions.net RC: 960240 QSL is a growing business that s offering IT Solutions and services to SME and Established Organizations with a high level of understanding and fully qualified, friendly and knowledgeable consultants.

More information

LEVEL 3 DATA CENTER ASSESSMENT

LEVEL 3 DATA CENTER ASSESSMENT Nationwide Services Corporate Headquarters 410 Forest Street Marlborough, MA 01752 USA Tel: 800-342-5332 Fax: 508-303-0579 www.eecnet.com LEVEL 3 DATA CENTER ASSESSMENT Submitted by: Electronic Environments

More information

OCTOBER 2010. Layer Zero, the Infrastructure Layer, and High-Performance Data Centers

OCTOBER 2010. Layer Zero, the Infrastructure Layer, and High-Performance Data Centers Layer Zero, the Infrastructure Layer, and The demands on data centers and networks today are growing dramatically, with no end in sight. Virtualization is increasing the load on servers. Connection speeds

More information

How To Visit An Internet Data Center

How To Visit An Internet Data Center AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina

More information

Evaluating Datacenter Colocation

Evaluating Datacenter Colocation 1/14 Evaluating Datacenter Colocation Flexibility and Security for Business Growth 2/14 The Advantages of Colocation Colocation is a service that allows customers to install and operate computer server

More information

UW CAMPUS SITE CONFIGURATION STANDARDS

UW CAMPUS SITE CONFIGURATION STANDARDS Overview Networks, Data Centers & Telecommunications UW CAMPUS SITE CONFIGURATION STANDARDS UW-IT is deploying a converged voice and data network. This service will improve and expand existing voice services

More information

IBM Portable Modular Data Center Overview for Critical Facilities Round Table

IBM Portable Modular Data Center Overview for Critical Facilities Round Table Brian Canney Global Services Executive, IBM GTS Site and Facilities Services April 2011 IBM Portable Modular Data Center Overview for Critical Facilities Round Table 2009 IBM Corporation Key messages Containers

More information

Multi-protocol Label Switching

Multi-protocol Label Switching An INS White Paper Multi-protocol Label Switching An economic way to deliver integrated voice, video and data traffic March 2013 Run your business on one network Multi-protocol Label Switching (MPLS) is

More information

Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport

Location. Central Business District. Ataturk Airport IFC. Sabiha Gökçen Airport Welcome Zenium Istanbul One provides 12,000 square metres of high specification technical space across three purpose-built data centers. It is Turkey s first wholesale data center offering; the data halls

More information

How To Write An Infrastructural Standard For Data Center Infrastructure

How To Write An Infrastructural Standard For Data Center Infrastructure Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers

More information

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0. Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M

More information

The College of Southern Maryland respectfully submits the following responses regarding the project cited above:

The College of Southern Maryland respectfully submits the following responses regarding the project cited above: The College of Southern Maryland respectfully submits the following responses regarding the project cited above: 1. Will this room be treated as a data center required to meet all NFPA, and International

More information

Availability and Disaster Recovery: Basic Principles

Availability and Disaster Recovery: Basic Principles Availability and Disaster Recovery: Basic Principles by Chuck Petch, WVS Senior Technical Writer At first glance availability and recovery may seem like opposites. Availability involves designing computer

More information

Fiscal Year 2015-16 Information Technology Request

Fiscal Year 2015-16 Information Technology Request PROGRAM PLAN STATUS and OIT BEST PRACTICES 2016-016 Approved Program Plan? N/A Date Approved: The university says that the project design follows best practices set forth by the datacenter equipment manufacturers

More information

Technical specifications. Containerized data centre NTR CDC 40f+

Technical specifications. Containerized data centre NTR CDC 40f+ Technical specifications Containerized data centre NTR CDC 40f+ CONTENT 1 THE PURPOSE OF CDC... 3 2 BASIC PROPERTIES... 4 2.1 EXTERNAL DIMENSIONS... 4 2.2 INSTALLATION REQIREMENTS... 4 2.3 ELECTRICAL CONNECTION

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Managed Colocation Service Definition. SD008 v1.5 Issue Date 20 July 11

Managed Colocation Service Definition. SD008 v1.5 Issue Date 20 July 11 Managed Colocation Service Definition SD008 v1.5 Issue Date 20 July 11 10 Service Overview InTechnology offers secure data centre environments for your business critical systems, applications and data

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions

AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 CABLING

More information

MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS

MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS MISSION CRITICAL FACILITIES DESIGN UPS BATTERY ROOM ENVIRONMENT CRITICAL DESIGN CONSIDERATIONS Allen Wood Vice President Data Center Division Engineering Design Group INTRODUCTION It can be very effectively

More information

Data Center Solutions

Data Center Solutions Data Center Solutions One Enterprise One Infrastructure One Partner R Professional Hosting and Domains ICN.Bg data center is a part of the best Bulgarian Neutral Co-location point Telepoint-a Tier 3 N+1

More information

Data Center Trend: Distributed Power in the White Space

Data Center Trend: Distributed Power in the White Space Data Center Trend: Distributed Power in the White Space By Jason Anderson Product Line Manager Eaton Executive summary Cloud computing vendors and colocation data centers make every effort to maximize

More information

Electrical. This section applies to the design and installation of building power distribution systems.

Electrical. This section applies to the design and installation of building power distribution systems. Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions

More information

Co-location service from Bell. Version 1.0 April 10, 2007. Updated as of 4/10/2007 1

Co-location service from Bell. Version 1.0 April 10, 2007. Updated as of 4/10/2007 1 Co-location service from Bell Version 1.0 April 10, 2007 Updated as of 4/10/2007 1 Contents 1. Introduction... 3 2. Service features... 3 3. Installation guidelines... 4 3a. Equipment installation in racks...

More information

The number LEON COUNTY NG9-1-1, RFP # BC-01-11-12-25 Addendum #3

The number LEON COUNTY NG9-1-1, RFP # BC-01-11-12-25 Addendum #3 Date: December 30, 2011 The number LEON COUNTY NG9-1-1, RFP # BC-01-11-12-25 Addendum #3 The following is an addendum to the Leon County NG9-1-1 System Request for Proposal (#BC-01-11-12-25). This and

More information

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture

A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture A Scalable, Reconfigurable, and Efficient Data Center Power Distribution Architecture White Paper 129 Revision 1 by Neil Rasmussen > Executive summary Significant improvements in efficiency, power density,

More information

Data center upgrade proposal. (phase one)

Data center upgrade proposal. (phase one) Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The

More information

Data Operations Center Renovation

Data Operations Center Renovation Data Operations Center Renovation Frederick County s main Data Center is located at Winchester Hall and was originally designed to house five HP3000 computer systems and the support hardware needed for

More information

Best Practices for Wire-free Environmental Monitoring in the Data Center

Best Practices for Wire-free Environmental Monitoring in the Data Center White Paper Best Practices for Wire-free Environmental Monitoring in the Data Center April 2012 Introduction Monitoring for environmental threats in the data center is not a new concept. Since the beginning

More information

Engineers Edge, LLC PDH & Professional Training

Engineers Edge, LLC PDH & Professional Training 510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Communication

More information

Power over Ethernet technology for industrial Ethernet networks

Power over Ethernet technology for industrial Ethernet networks Power over Ethernet technology for industrial Ethernet networks Introduction Ethernet networking has grown beyond office and home usage to become a very successful protocol suite used in many industrial

More information

Data Centre Design ready for your future

Data Centre Design ready for your future Data Centre Design ready for your future Introduction to Data Centres What is a Data Centre? The definition of a Data Centre according to TIA-942 is a building or portion of a building whose primary function

More information

COLOCATION PROVIDERS:

COLOCATION PROVIDERS: COLOCATION PROVIDERS: INTRO The benefits of colocation are well documented, and making the business case for going that route is often quite easy for many organizations. Once the decision has been made

More information

AUDIO VISUAL SYSTEMS. Conference Room A/V Presentation Systems. Video Conference Rooms. Video Conference Room. Theater Room A/V System

AUDIO VISUAL SYSTEMS. Conference Room A/V Presentation Systems. Video Conference Rooms. Video Conference Room. Theater Room A/V System California State University, Northridge Student Recreation Center Northridge, California Audiovisual systems design included Child Care Center, Conference Room, Exercise Studio, Paging System and Sports

More information

Disaster Recovery: Protect Your Business & Prepare Your Digital Prepress Operations

Disaster Recovery: Protect Your Business & Prepare Your Digital Prepress Operations Eastman Kodak Company 343 State Street Rochester, NY 14650-0238 USA Revision date: March 2014 White Paper Contact Name Robyn Lundstrom PSSG Specialist, KODAK Unified Workflow Solutions robyn.lundstrom@kodak.com

More information

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,

More information