SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.

Size: px
Start display at page:

Download "SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck."

Transcription

1 SECTION PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied roofing and penetration flashings. E. Fluid applied base flashing REFERENCES A. ASTM D41--Asphalt primer used in roofing, damp proofing, and waterproofing. B. ASTM D312--Asphalt used in roofing. C. ASTM D2178--Asphalt impregnated glass mat used in roofing and waterproofing. D. Plastic cement: ASTM D 4586, Type II E. Manufacturer's reference manual, most current edition. F. NRCA roofing and waterproofing manual SYSTEM DESCRIPTIONS A. New roof system over a structural concrete roof deck ply modified roof membrane, surfaced 2. Insulation cover board 3. Polyisocyanurate roof insulation 4. Vapor barrier (modified roof membrane) B. New roof system over existing gypsum roof deck ply modified roof membrane, surfaced 2. Cover board adhered to existing roof deck C. New roof system over existing gypsum roof deck. 1. Fluid applied reinforced roof membrane 2. Insulation cover board 3. Tapered polyisocyanurate roof insulation 08/30/11 ISSUE FOR PRICING (ADDENDUM 1)

2 1.04 SUBMITTALS A. Submit certificates showing that the products delivered to the site comply with the standards set forth in the specifications. Include a certificate for bulk materials. B. Submit manufacturer s certification of compliance to the specified performance criteria in the form of a system description letter that includes: 1. Descriptions of the roof systems to be installed. 2. Confirmation that the roofing contractor is approved by the roof manufacturer to install the roof system and furnish the specified manufacturer s warranty. 3. Wind uplift pressures for all three zones on all roof levels and a roof plan denoting the location and widths of the corner, perimeter and field wind uplift zones. Refer to Structural Drawing Sheet S0.0, General Notes, Design Criteria, for design wind uplift pressures. 4. Plan view of insulation / cover board showing attachment requirements per board for each of the wind uplift zones on all roof levels. 5. A schedule of inspections to be performed by a technical representative of the roof system manufacturer during the installation of the roofing. C. Submit the manufacturer's cut sheet on all products. D. Submit the manufacturer's latest installation instructions for all materials QUALITY ASSURANCE A. The installer of the roof system must have a minimum of five years experience installing this type of roofing on projects of this type and size. B. The installer must be approved by the manufacturer of the roofing materials. C. It is the intent to install all materials in accordance with the manufacturer's latest printed specifications. If there is a conflict between manufacturer's instructions and these specifications, notify the owner and the consultant. If there is a question of quantity in materials or application method, the more rigid specification shall apply. D. A pre-installation conference shall be convened prior to the beginning of this work. The conference should be used to clear up any questions or ambiguities about materials and methods of installation. E. The roof system and the component parts must be designed and installed to meet, at minimum, wind uplift pressures in accordance with local building codes and must withstand at least 120 mph wind velocity. F. The roofing and sheet metal must be installed and warranted by the roofing contractor. If the sheet metal work is installed by a sub-contractor, that contractor must be employed by the roofing contractor. 08/30/11 ISSUE FOR PRICING (ADDENDUM 1)

3 1.06 DELIVERING, STORAGE, AND HANDLING OF MATERIALS A. Deliver materials to the site bearing manufacturers' labels, production dates, or product codes. B. Deliver material on pallets. Roll goods shall be stacked on end. Handle all goods to prevent damage. C. Store materials in dry protected areas. Use enclosed trailers when possible. Do not store roll goods or insulation materials in the PVC shipping wrappers. Use a waterproof tarpaulin to completely cover the materials. Protect materials from freezing. D. Keep lids on plastic cement, adhesive, primers, and other materials which are sensitive to evaporation. E. Do not thin primers, adhesives, or similar materials unless specified by the manufacturer. F. Remove any material from the job site which becomes wet or damaged. G. Comply with local fire codes and ordinances when flammable materials are to be stored. H. Do not load the roof deck or structure beyond its capacity PROJECT SITE AND CONDITIONS A. Do not install roofing products when moisture in any form is present (eg. rain, dew, frost, ice, or snow). B. Care must be taken when the mean temperature falls below 40 degrees F. Follow the manufacturer's instructions for cold weather application. C. Test surfaces for moisture by pouring or mopping hot bitumen over a section of the area in question. Do not proceed with roofing operations if: 1. There is any foaming or bubbling of the bitumen on the unprimed concrete deck. 2. If the bitumen can be readily stripped from the primed substrate after it cools WARRANTY A. Before final payment, submit to the owner a warranty for a period of 2 years. The warranty shall cover all roofing, sheet metal, and related work called out in these documents. It shall cover defects in material and workmanship, as well as agreeing to make prompt repairs if notified of a leak. Provide a warranty inspection 3 months prior to the expiration. Repair defects in materials or labor discovered at this time. These defects shall include, but not be limited to, bitumen drips, voids, blisters, vapor ridges, or fish mouths. B. Provide a maintenance schedule and maintenance information for the roof system installed. 08/30/11 ISSUE FOR PRICING (ADDENDUM 1)

4 C. Provide a manufacturer's warranty on the full system installed for a period of twenty years with all available options, flashing endorsement and including roof membrane, vapor barrier, roof insulation, fluid applied roofing and flashings, and roofing manufacturer s accessories, and signed by roofing system manufacturer agreeing to promptly repair leaks resulting from defects in materials or workmanship for a 20-Year Full Systems (NDL) Warranty after date Substantial Completion. The warranty shall also include a 120 mph wind warranty. Include in pricing, all materials and labor upgrades required by Derbigum for the specified warranty. PART 2 PRODUCTS 2.01 GENERAL A. Performance: The entire roof assembly must be FM listed. Identify materials with FM markings. The roofing system shall be designed by the roof system manufacturer and installed to meet at minimum wind uplift pressures in accordance with local building codes and must withstand at least 120 mph wind velocity. B. Compatibility: Provide products which are recommended by manufacturers to be fully compatible with indicated substrates, or provide separation materials as required eliminating contact between incompatible materials ACCEPTABLE MANUFACTURER A. Performance Roof systems, Kansas City, Mo. (No substitutions) 2.03 VAPOR BARRIER (BASE PLY) A. Derbibase 1. Smooth surfaced APP modified base sheet 2. Thickness: 80 mils 3. Tensile strength: ASTM D Machine Direction / 150 Cross Direction 2.04 INSULATION AND COVER BOARD A. Roof Insulation: Derbiboard polyisocyanurate 1. Roof insulation thickness: 3.2 (minimum R 19.8) 2. Compressive strength: 20 psi per ASTM D Density: Nominal 2.0 pcf per ASTM D Insulation shall comply with FM Standard Crickets: Derbiboard polyisocyanurate tapered insulation board. Provide crickets where indicated on plans or required for positive roof drainage, slope shall be ½ per foot. 6. Tapered Insulation: Derbiboard polyisocyanurate, slope shall be 1/8 per foot where shown on plans. 08/30/11 ISSUE FOR PRICING (ADDENDUM 1)

5 B. Roof Insulation Cover Board and behind base flashings and waterproofing on vertical walls: USG Securock Gypsum Fiber Roof Board 1. 4 x 4 sheets 2. ½ inch thick (minimum R 0.5) 3. Water Absorbtion: 10 % maximum per ASTM C Surface Water Absorbtion: 1.6 grams per ASTM C BASE SHEET A. Derbigum GP 1. Smooth surfaced dual reinforced APP modified bitumen 2. Thickness: 160 mils 3. Tensile strength: ASTM D Machine Direction/170 Cross Direction at 0 deg. F CAP MEMBRANE A. Derbibrite 1. Acrylic surfaced fiberglass/polyester composite reinforcement 2. Thickness: 140 mils 3. Tensile strength: ASTM D5147, 170 Machine Direction / 170 Cross Direction at 0 degrees F 4. Fire resistance: ASTM E-108 and UL790, Class A rated 5. Initial Reflectivity: ASTM C-1549, Initial Emissivity: ASTM E-408, Solar Reflective Index: ASTM E-1980 (E-408), Fungus Resistance: ASTM G21, 0 (No growth of fungus) 2.07 MEMBRANE ADHESIVES A. Derbigum Permastic asphaltic based cold process adhesive (vapor barrier) 1. Weight: 9.5 lbs/gallon 2. VOC: 180 grams/l B. Derbigum Permastic IA asphaltic based cold process adhesive (base sheet and cap membrane) 1. Weight: 9.5 lbs/gallon 2. VOC: 245 grams/l 2.08 INSULATION ADHESIVE A. Olympic Olybond 500 two-component polyurethane adhesive 1. Density: 3.2 lb./cf per ASTM D Tensile Strength: 35 psi per ASTM D Water Absorption: 5.1% per ASTM D Closed Cell Content: 90% minimum per ASTM D BASE FLASHING A. Deleted, refer to Paragraph 2.11 of this Specification 08/30/11 ISSUE FOR PRICING (ADDENDUM 1)

6 2.10 PRIMER A. Derbigum Primer, as recommended by the roof system manufacturer 1. Application Rate: per 1.2 gallons 2.11 FLUID APPLIED ROOFING AND FLASHING A. Derbiflash 1. Derbigum EF Resin, cold fluid applied polyester reinforced membrane 2. Derbigum HP Fleece, polyester reinforced fleece 3. Derbigum Liquid Surfacing & Mixing Sand, topcoat bonding/sealing agent on roofing. 4. Derbigum Permacool, reflective elastomeric roof coating on both roofing and flashings. Color to match cap sheet on roofing and flashings except under Alucobond wall panels; color of Permacool to match color of Alucobond wall panels. PART 3 EXECUTION 3.01 EXAMINATION A. Examine surfaces to receive the new roof assembly, base flashing, and sheet metal. Report any conditions which may lead to defective installation or failure in workmanship or products. The products used should be suitable for the conditions present to produce a functional, leak free installation PREPARATION A. Clean and prepare the deck to receive the new roof system including primers as required by the roof system manufacturer. B. At re-roof areas, tear off existing roofing and prepare the roof deck to receive the new roof system. Do not remove more roofing than can be installed in the same day. C. Install a two-ply water cut off at the end of work each day; remove it when work resumes. D. Protect new roofing and the building from water entry at all times INSTALLATION A. Install all materials in strict compliance with the manufacturer s recommendations. Provide all materials and installation upgrades required by the manufacturer for the specified manufacturer s warranty including wind speed resistance warranty. B. Over the new structural concrete roof deck and over existing structural concrete roof deck, install the vapor barrier (base ply) using the torch method. Follow the manufacturer s instructions for installation. 1. Exert sufficient pressure on the roll to prevent voids. 2. Install the roof membrane from the low edge of the roof in shingle fashion. 08/30/11 ISSUE FOR PRICING (ADDENDUM 1)

7 3. Cut out and repair wrinkles, voids and fish mouths. 4. Follow the manufacturer's latest printed specifications for installation of the roofing material. C. Install insulation and cover board over the vapor barrier on the new structural concrete roof deck and existing structural concrete roof deck in cold adhesive (Permastic IA) at a rate of 1.5 to 2 gallons per square. Follow the manufacturer's instructions for installation. 1. Fill all voids over ¼ with additional insulation. 2. Stagger joints between insulation layers. 3. Follow the manufacturer s latest printed specifications for installation of the insulation and cover board. D. Install cover board over existing gypsum roof deck with insulation adhesive. Application rate of adhesive shall be determined by roof system manufacturer to withstand wind uplift pressures. E. Install roof insulation / tapered roof insulation over cover board on existing gypsum deck where indicated on plans with insulation adhesive. Install cover board over roof insulation with insulation adhesive; install urethane sealant in board joints as recommended by Derbigum. Application rate of adhesive shall be determined by roof system manufacturer to withstand wind uplift pressures. F. Install roof insulation to match existing gypsum board roof deck thickness at existing steel roof deck, secure insulation to steel deck with mechanical fasteners and plates, and cover board with insulation adhesive Number and type of fasteners and plates, and the application rate of the insulation adhesive shall be determined by roof system manufacturer to withstand wind uplift pressures. G. Install base sheet over cover board with cold adhesive (Permastic) at a rate of 1.5 to 1.8 gallons per square. Follow the manufacturer's instructions for installation. 1. Exert sufficient pressure on the roll to prevent voids. 2. Install the roof membrane from the low edge of the roof in shingle fashion. 3. Cut out and repair wrinkles, voids and fish mouths. 4. Heat fuse laps. 5. Follow the manufacturer's latest printed specifications for installation of the roofing material. H. Install cap membrane over base sheet with cold adhesive (Permastic) at a rate of 1.5 to 1.8 gallons per square. Follow the manufacturer s instructions for installation. 1. Exert sufficient pressure on the roll to prevent voids. 2. Install the roof membrane from the low edge of the roof in shingle fashion. 3. Cut out and repair wrinkles, voids and fish mouths. 4. Heat fuse laps. 5. Follow the manufacturer's latest printed specifications for installation of the roofing material. 08/30/11 ISSUE FOR PRICING (ADDENDUM 1)

8 I. Prime substrates and install reinforced fluid applied roofing system with surfacing at area denoted on the plans in accordance with the manufacturer s latest printed installation instructions. Countersink screws used to attach cover board to walls at base flashings and install urethane sealant in board joints and over screws as recommended by Derbigum. All base flashings including new curbed flashing at new roof top unit shall be reinforced fluid applied flashing QUALITY CONTROL A. The owner may employ inspection services during the course of this project. Provide safe and adequate access to all parts of the work. B. Test cuts may be taken to determine quantities and quality. Provide labor and material to repair these cuts. Test cuts will not exceed one per 10,000 sq. ft. of area. Testing will be paid for by the owner. If problems are indicated, further cuts and tests may be done, pay for any additional testing costs due to defective work PROTECTION A. Protect the roof membrane from damage until acceptance by the owner. Repair or replace damaged sections. B. Place temporary plywood panels or other protection over heavily trafficked areas. END OF SECTION 08/30/11 ISSUE FOR PRICING (ADDENDUM 1)

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance

More information

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and

More information

ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING

ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings

More information

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.

More information

Colorado State University. Durrell Center Roof Repair

Colorado State University. Durrell Center Roof Repair Colorado State University Durrell Center Roof Repair SPECIFICATION: POLYURETHANE FOAM ROOFING l.0 GENERAL REQUIREMENTS The successful application of a polyurethane foam roofing system is dependent upon

More information

SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)

SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) PART 1 GENERAL 1.1 DESCRIPTION 1. Fluid applied flexible acrylic waterproofing system over concrete. This work shall include the

More information

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within

More information

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC

More information

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded

More information

TARRANT COUNTY DETAIL STANDARDS

TARRANT COUNTY DETAIL STANDARDS TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout

More information

How to repair your existing low slope flat roof.

How to repair your existing low slope flat roof. How to repair your existing low slope flat roof. Recycled Rubber Roofing is not a "Roof Coating." It is a liquid emulsion used as the underlayment of a new or retrofit, built-up roofing system. One of

More information

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry

More information

SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING

SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Please read the entire document before purchasing and installing any of these products

Please read the entire document before purchasing and installing any of these products Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

A. Roofing Terminology: Definitions in ASTM D 1079 and glossary in NRCA's "The NRCA Roofing and Waterproofing Manual" apply to work of this Section.

A. Roofing Terminology: Definitions in ASTM D 1079 and glossary in NRCA's The NRCA Roofing and Waterproofing Manual apply to work of this Section. SECTION 075419 POLYVINYL CHLORIDE (PVC) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS

Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS AC TOPSEAL SELF-ADHERED, GRANULAR SURFACED, SINGLE PLY, LOW SLOPE ROLLED ROOFING 3 X 33.3 = 100 SQ. FT. 10 YEAR MATERIAL LIMITED WARRANTY For Use on Porches / Sheds / Utility Buildings / Accessory Buildings

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

Roofing Repairs 07511-1

Roofing Repairs 07511-1 SECTION 07511 ROOF AND FLASHING RESTORATION WITH TITLE 24 / COOL ROOF SURFACING PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including General and Supplementary

More information

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS OPTIONAL TITLE 24 CRITICAL POINTS POLYISO THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE DESCRIPTION TORCH OVER POLYISO (5,7,9 YR) TH/BS-TH/CS 2 No 0. SUBSTRATE. THERMOTEK USA PRO 2.0 FV

More information

07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center

07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 5423 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center A. Tear off existing roof system down to wood deck and install new Thermoplastic membrane roofing

More information

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes

More information

Durapax Coal Tar BUR Application Guide

Durapax Coal Tar BUR Application Guide 400 Old Reading Pike, Suite 304 Pottstown, PA 19464 Tel: 610-579-9075 Fax: 610-323-0115 www.durapax.com Durapax Coal Tar BUR Application Guide DESIGN CONSIDERATIONS The proper specifications of any roof

More information

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the

More information

SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING

SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING PART ONE GENERAL DESCRIPTION This section includes pre-formed standing seam metal roofing and related flashings, closures, trim and accessories including,

More information

SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.

SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings. SECTION 07530 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section includes the flowing: 1. Removal of existing roofing membrane. Existing bur roof has one overlay and penetration mastic is asbestos containing.

More information

Low-slope reroofing guidelines

Low-slope reroofing guidelines Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August

More information

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER DESCRIPTION TORCH OVER (15,17,19 YR) TH/BS-TH/CS 2 1 0 No 0. SUBSTRATE 1. THERMOTEK USA 2.0 FV TORCH SMOOTH 2. THERMOTEK USA PRO FP TORCH GRANULE COMPONENTS

More information

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 SECTION ONE A. Objective The objective of this guide is to provide Owners and General Contractors/Construction

More information

RECOATING AND RENEWING SPF ROOFING SYSTEMS

RECOATING AND RENEWING SPF ROOFING SYSTEMS RECOATING AND RENEWING SPF ROOFING SYSTEMS Procedures, Regional Differences and type of coating systems Bruce Schenke Premium Spray Products REASONS TO RECOAT/RENEW Add a new coating layer to renew the

More information

ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016

ROXUL Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK ) Page 1 April 2016 Master Guide Specification (CAVITYROCK ) Page 1 Click on the pilcrow in the MS Word Toolbar to toggle ROXUL GUIDE NOTES on and off. Delete this text before incorporating the section into a Project Manual.

More information

Georgia State University. Urban Life Building Roof Replacement

Georgia State University. Urban Life Building Roof Replacement ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT

More information

SECTION 07 61 13 STANDING SEAM METAL ROOFING

SECTION 07 61 13 STANDING SEAM METAL ROOFING SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced

More information

07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying

More information

The existing roof angle change terminations and flashings when sound and intact can be reused.

The existing roof angle change terminations and flashings when sound and intact can be reused. January 2, 2015 Summary Specification Re-Skinning an Existing Roof Maintenance and Repair Warranty Upgrade for Up to 30 Years Re-Skinning Over an Existing Roof with a New C-EPDM Membrane Using The Existing

More information

PSU WHP ROOF REPLACEMENT

PSU WHP ROOF REPLACEMENT SECTION 075216 - MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION

BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION 07560 BUR BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION PART 1: GENERAL 1.01 SCOPE: To extend the useful service life of the aged or new asphalt built-up roof system and to reduce cooling

More information

THERMOTEK SELF ADHESIVE MEMBRANE +G2 OVER WOOD SYSTEM DESCRIPTION SELF ADHESIVE OVER WOOD (8YR) BS-SA/CS

THERMOTEK SELF ADHESIVE MEMBRANE +G2 OVER WOOD SYSTEM DESCRIPTION SELF ADHESIVE OVER WOOD (8YR) BS-SA/CS THERMOTEK SELF ADHESIVE MEMBRANE +G OVER DESCRIPTION SELF ADHESIVE OVER (8YR) BS-SA/CS 1 0 No 0. SUBSTRATE 1. BASE SHEET G FIBER GLASS BASE. THERMOTEK SELF ADHESIVE 3.0 FP GRANULE COMPONENTS AND WEIGHTS

More information

Avoiding Air Barrier Pitfalls

Avoiding Air Barrier Pitfalls Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great

More information

SECTION 07 57 16 CEMENTITIOUS COATED FOAMED ROOFING

SECTION 07 57 16 CEMENTITIOUS COATED FOAMED ROOFING SECTION 07 57 16 CEMENTITIOUS COATED FOAMED ROOFING PART 1 GENERAL 1.01 SUBMITTALS A. Product Data: Submit manufacturer's literature and technical data (specifications, installation instructions and evidence

More information

COMMERCIAL BUILDING APPLICATIONS

COMMERCIAL BUILDING APPLICATIONS EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that

More information

A. This Section includes rubberized asphalt sheet membrane waterproofing systems.

A. This Section includes rubberized asphalt sheet membrane waterproofing systems. SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Solicitation DTFACN-11-R-00079 Attachment #9

Solicitation DTFACN-11-R-00079 Attachment #9 These specs are only a general overview of the typical VOR Roof construction. These are for reference only. Each individual project will have its own specifications. 1 VOR Roof Projects IDIQ Solicitation

More information

Roof Systems Overview

Roof Systems Overview Roof Systems Overview Cold Applied Built-Up Roofing Systems BURmastic Tremco s line of cold applied built-up roofing systems. BURmastic 200 Combines Tremco s expertise in asphalt blending technology with

More information

Residential Roofing Guide

Residential Roofing Guide Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design Basis of Design This section applies to roofing membranes, flashing and accessories. Design Criteria Adhere to the standards and details of the latest editions of the National Contractors Association (NRCA)

More information

ALPHA 15-Year Permathane II FR w/granules

ALPHA 15-Year Permathane II FR w/granules ALPHA 15-Year Permathane II FR w/granules Section 07 57 13 Sprayed Polyurethane Foam Roofing Guide Specification PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Furnish all labor, materials, tools and

More information

METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES

METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES REFLECTICLEAN ACRYLIC/URETHANE Elastomeric Roofing Systems, Inc 6900 Bleck Dr. Rockford, MN 55373 800.403.7747 -or- 763.565.6900 fax: 763.565.6901 email:

More information

Building Owners Guide to a Duro-Last System!

Building Owners Guide to a Duro-Last System! Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof

More information

Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood

Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Section 07411 Metal Roof Panels Part 1 General 1.1 Summary A. This section includes the following: a. Factory-formed

More information

HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION

HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System

More information

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced

More information

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)

More information

SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK

SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. This section covers the pre-finished, pre-fabricated Architectural standing seam roof system. All metal trim,

More information

CREEK Technical Services, LLC

CREEK Technical Services, LLC EVALUATION REPORT 2010 FLORIDA BUILDING CODE Manufacturer: Henry Company Report Issued February 20, 2013 999 North Sepulveda Blvd., Suite 800 El Segundo, CA 90245 (800) 486-1278 Manufacturing Plants: Quality

More information

ROOF ASSEMBLIES CHAPTER 9

ROOF ASSEMBLIES CHAPTER 9 CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION

More information

CHICAGO ROOFING CONTRACTORS ASSOCIATION

CHICAGO ROOFING CONTRACTORS ASSOCIATION CHICAGO ROOFING CONTRACTORS ASSOCIATION JANUARY 22, 2016 Roofing Claims & Lawsuits Stephen M. Phillips Hendrick, Phillips, Salzman & Flatt, P.C. 230 Peachtree Street, Suite 2500 Atlanta, GA 30303 (404)

More information

How To Install A Membrane Roofing System

How To Install A Membrane Roofing System SECTION 075400 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION 07400 STANDING SEAM METAL ROOF

SECTION 07400 STANDING SEAM METAL ROOF SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and

More information

SWD URETHANE COATED FOAM ROOFING SYSTEM MASTER ROOF SPECIFICATION SECTION 075700

SWD URETHANE COATED FOAM ROOFING SYSTEM MASTER ROOF SPECIFICATION SECTION 075700 SWD URETHANE COATED FOAM ROOFING SYSTEM MASTER ROOF SPECIFICATION SECTION 075700 Part 1 GENERAL SUMMARY Section Includes: Coated foam roofing system and acceptable alternative applications as specified

More information

BITUMEN-POLYMER WATERPROOFING MEMBRANE, MADE FROM SELECT APP AND DISTILLED BITUMEN, REINFORCED WITH SPUNBOND POLYESTER FABRIC.

BITUMEN-POLYMER WATERPROOFING MEMBRANE, MADE FROM SELECT APP AND DISTILLED BITUMEN, REINFORCED WITH SPUNBOND POLYESTER FABRIC. 93-106 Revised March 2007 BITUMEN-POLYMER WATERPROOFING MEMBRANE, MADE FROM SELECT APP AND DISTILLED BITUMEN, REINFORCED WITH SPUNBOND POLYESTER FABRIC. BITEC APM-4.5T is a torch applied, mineral surfaced,

More information

SECTION 07411 STANDING SEAM METAL ROOFING

SECTION 07411 STANDING SEAM METAL ROOFING PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following: 1. Standing-seam metal roof. 2. Metal gutters. 1.2 DEFINITIONS A. Metal Roof Panel Assembly: Metal roof panels, waterproofing membrane (underlayment),

More information

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing

More information

ATLAS Roofing Products

ATLAS Roofing Products ATLAS Roll Roofing Products World s Largest producer of roofing s Preferred by roofing professionals. Atlas has you covered on every part of the job, even what goes under your roofing. We are proud to

More information

ROOF CONSTRUCTION SCIENCE (METCT092)

ROOF CONSTRUCTION SCIENCE (METCT092) ROOF CONSTRUCTION SCIENCE (METCT092) This training program is intended for applicators that are interested in gaining an understanding of the various technologies incorporated in roof systems, including

More information

HHS J.W. Peavy Center Exterior Walls Waterproofing and Roof Replacement Project WBS # H-000018-0006-4 SECTION 07610 STANDING SEAM METAL ROOFING

HHS J.W. Peavy Center Exterior Walls Waterproofing and Roof Replacement Project WBS # H-000018-0006-4 SECTION 07610 STANDING SEAM METAL ROOFING PART 1 - GENERAL 1.01 DESCRIPTION SECTION 07610 A. Furnish and install a weather and watertight prefabricated standing seam roof system complete, in place, as shown on the drawings and as specified herein.

More information

238T Standing Seam Metal Roof System (SSMRS)

238T Standing Seam Metal Roof System (SSMRS) 238T Standing Seam Metal Roof System (SSMRS) Text in red are instructions to the specifier and should be deleted. Text in blue are choices that need to be made, with those not selected, deleted. McElroy

More information

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side

More information

EPDM. Roofing systems

EPDM. Roofing systems Roofing systems Our Promise Through ongoing interchange of experiences with contractors, Mule-Hide keeps on top of the latest roofing requirements and solutions Trusted in roofing since 1906, Mule-Hide

More information

EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS

EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use

More information

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof! Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing

More information

APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE

APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT NCE Table Application Type Description Page 1A-1 Wood New, Reroof (Tear-Off), Recover C-1 Mechanically Attached Insulation, Bonded Roof Cover 4 1A-2

More information

075216 SBS MODIFIED BITUMINOUS MEMBRANE ROOFING

075216 SBS MODIFIED BITUMINOUS MEMBRANE ROOFING SECTION 075216 - SBS-MODIFIED BITUMINOUS MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

GENERAL REQUIREMENTS HENRY WARRANTED COMMERCIAL ROOFING SYSTEMS

GENERAL REQUIREMENTS HENRY WARRANTED COMMERCIAL ROOFING SYSTEMS GENERAL REQUIREMENTS HENRY WARRANTED COMMERCIAL ROOFING SYSTEMS 1.0 STATEMENT OF POLICY The overall performance of a roofing system can be affected by factors other than the roof system installation. Henry

More information

Firestone SBS Modified Bitumen Roofing System Design and Application Guide

Firestone SBS Modified Bitumen Roofing System Design and Application Guide SBS Modified Bitumen Roofing System Design and Application Guide October, 2013 Table of Contents 1.01 Introduction... 1 1.01.1.1 General Considerations... 1 1.01.1.2 Warranty... 3 1.01.1.3 QUALITY ASSURANCE...

More information

STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS

STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the

More information

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 Commercial rooftops represent the most available, sustainable and secure real estate for new

More information

SCENIC VIEW SV 10 SECTION 08 87 13 SOLAR CONTROL FILMS

SCENIC VIEW SV 10 SECTION 08 87 13 SOLAR CONTROL FILMS PART 1 GENERAL SCENIC VIEW SV 10 SECTION 08 87 13 SOLAR CONTROL FILMS 1.1 SUMMARY A. Optically clear dual reflective, neutral sputtered and aluminum metallized polyester film for solar control. 1.2 RELATED

More information

Specifying SPF Roofing Systems

Specifying SPF Roofing Systems Specifying SPF Roofing Systems Spray polyurethane foam (SPF) roofing systems have been marketed for years primarily on their documented energy saving characteristics. Consequently much of the SPF roofing

More information

Proper roof slope and drainage are important to prevent excessive water accumulation

Proper roof slope and drainage are important to prevent excessive water accumulation Proper roof slope and drainage are important to prevent excessive water accumulation by Jason P. Wilen, AIA, CDT, RRO P onding water sometimes occurs on membrane roof systems as a result of snow, rainfall

More information

INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS

INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS Introduction This inspection guide is organized to follow the EIF System's Installation Guide.

More information

SEAMS SEAMING USING SEAM TAPE

SEAMS SEAMING USING SEAM TAPE SEAMING USING SEAM TAPE SEAMS The membrane should be positioned so that the width of the seam is 3. Remove excess chalk from a chalk line by snapping the line into the air and then chalk a line one-quarter

More information

Preformed Metal Roofing and Siding

Preformed Metal Roofing and Siding Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision

More information

Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer

Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer Leak Buster Repair & Maintenance Products Quality You Can Trust Since 1886...From North America s Largest Roofing Manufacturer

More information

Detached accessory structures that contain no conditioned floor area are exempt.

Detached accessory structures that contain no conditioned floor area are exempt. RESIDENTIAL ROOFING PERMITS: A roofing permit is required for roofing of residential dwellings and garages in accordance with Section R105 of the International Residential Code. Updated 11/2013 City of

More information

Firestone Modified Bitumen Roofing Systems DURABLE. RELIABLE. SUSTAINABLE

Firestone Modified Bitumen Roofing Systems DURABLE. RELIABLE. SUSTAINABLE Firestone Modified Bitumen Roofing Systems DURABLE. RELIABLE. SUSTAINABLE I n t r o d u c t i o n t o M o d i Acres of Roofing. Decades of Performance. Over the past 20 years, Firestone Building Products

More information

NRCA s steep-slope manual is thoroughly revised for 2013

NRCA s steep-slope manual is thoroughly revised for 2013 Photo courtesy of Boone Brothers Roofing, Omaha, Neb. NRCA s steep-slope manual is thoroughly revised for 2013 by Maciek Rupar 38 www.professionalroofing.net MARCH 2013 P ublished in January, The NRCA

More information

The Perfect Fit For Metal Retrofit

The Perfect Fit For Metal Retrofit D u r o - S h i e l d M e t a l R e t r o f i t R o o f i n g S y s t e m The Perfect Fit For Metal Retrofit Lock out leaks. Lock in your investment. Has time caught up with your metal roof? There are

More information

SECTION 07320 ROOFING TILE

SECTION 07320 ROOFING TILE SECTION 07320 ROOFING TILE PART 1 - GENERAL 1.1 SUMMARY: A. Section Includes: 1. Vitrified clay roofing tiles. 2. Tile accessories. 3. Felt underlayment. 4. Self-adhering sheet underlayment. 5. Snow guards.

More information

GUIDE SPECIFICATION. Manufacturer: DECRA Roofing Systems, Inc.

GUIDE SPECIFICATION. Manufacturer: DECRA Roofing Systems, Inc. GUIDE SPECIFICATION Manufacturer: DECRA Roofing Systems A Fletcher Building Company 1230 Railroad Street Corona, CA 92882 951-272-8180 phone 951-272-4476 facsimile www.decra.com SECTION 07314 [07 31 14]

More information

BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES

BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES ABOUT POLYGLASS U.S.A., INC. MODIFIED CEMENTS & ADHESIVES MASTICS ALUMINUM COATINGS EMULSIONS & PRIMERS PROTECTIVE COATINGS Polyglass manufactures

More information

FEFPA 2015 SUMMER CONFERENCE. Energy Effectiveness through Roof Coatings and Solar

FEFPA 2015 SUMMER CONFERENCE. Energy Effectiveness through Roof Coatings and Solar FEFPA 2015 SUMMER CONFERENCE Energy Effectiveness through Roof Coatings and Solar Welcome Danny G. Daniel Stokes, CSI, CDT, RCI, CPRC Vice President Advanced Roofing Inc. About Danny Stokes Vide President

More information

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that

More information

GigaCrete Specification PlasterMax

GigaCrete Specification PlasterMax GigaCrete Inc. 6775 Speedway Blvd. Suite M105 Las Vegas, NV 89115 Ph (702) 643-6363 Fax (702) 643 1453 www.gigacrete.com GigaCrete Specification PlasterMax PlasterMax : Fire Rated Plaster for Direct Application

More information

SECTION 32 1816 PLAYGROUND SURFACING TILES

SECTION 32 1816 PLAYGROUND SURFACING TILES SECTION 32 1816 PLAYGROUND SURFACING TILES PART 1 GENERAL 1.01 SECTION INCLUDES A. Resilient playground safety surfacing tiles. B. Coordinate with work shown in other sections so the work is installed

More information

Product Guide Specification

Product Guide Specification Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail ri@reefindustries.com Product Guide

More information

CONTINENTAL MATERIALS, INC. ALL-WEATHER APP INSTALLATION GUIDELINES

CONTINENTAL MATERIALS, INC. ALL-WEATHER APP INSTALLATION GUIDELINES CONTINENTAL MATERIALS, INC. ALL-WEATHER APP INSTALLATION GUIDELINES Page 1 APP INSTALLATION GUIDELINES This guide provides instructions for the installation of CMI All Weather APP roofing materials. Any

More information

How To Replace A Roofing System In Florida

How To Replace A Roofing System In Florida Florida Consumer Considerations in Replacing their Roofing System The Florida Roofing, Sheet Metal and Air Conditioning Contractors Association provides the following general information to help Florida

More information