Colorado State University. Durrell Center Roof Repair
|
|
- Alfred Ramsey
- 8 years ago
- Views:
Transcription
1 Colorado State University Durrell Center Roof Repair SPECIFICATION: POLYURETHANE FOAM ROOFING l.0 GENERAL REQUIREMENTS The successful application of a polyurethane foam roofing system is dependent upon the experience, technology and common sense of the designer and contractor. This guide specification is intended as a starting point for development of more complete specifications of roofing assemblies. The successful application of a polyurethane foam roofing system hinges on the experience, integrity and ability of the applicator/contractor. 1.1 Terms and Conditions The roofing contractor is the prime contractor. All subcontractors shall be identified and approved at the time the proposal is submitted Bidders shall be prequalified as follows: a. All bidders shall be contractors specifically engaged in the application of these systems for not less than 10 years. Each bidder shall have performed at least 5 applications of similar size and type. b. Bidders shall submit a copy of the proposed 10 year standard coating labor and material warranty from the manufacturer along with his proposal. c. The contractor shall carry a minimum of $1,000,000 in general liability insurance on a continuing basis. Verification of insurance shall be submitted at the time of the bid Qualifications of Manufacturer: The coating shall have a minimum of 1,000,000 square feet of successful roofing installed over polyurethane foam. 1.2 Submittals Manufacturer's Literature: Submit two copies of the manufacturer's data sheets regarding specifications, application information and safety information and safety instructions on each product proposed for use Samples: Submit two samples of the proposed coating system applied to urethane foam. Samples shall be two inches by four inches in size.
2 1.2.3 Certification of the Manufacturer: Submit on corporate letterhead, a letter from the manufacturer of the foam and a letter from the manufacturer of the coating stating that the applicator of these products is qualified under the manufacturer's warranty program Similar jobs: The applicator shall submit a list of five similar projects which the contractor has completed over the past five years Submit a copy of the manufacturer's 10 year labor and material warranty Submit a copy of the current UL approval for the system over non-combustible decks Materials other than those specified shall be submitted and approved in writing by the owner seven days prior to the opening of the bid. 2.0 MATERIALS AND EQUIPMENT 2.1 Primer: Primer shall be a single component primer specifically designed to improve adhesion of foam to rolled roofing The primer shall be Bayblock 004 or prior approved equal. 2.2 Polyurethane Foam: Shall be a two component polyurethane foam system formulated for use through airless equipment. The product shall be Bayseal 27 as manufactured by Bay Systems NA, Spring Texas, Premiseal 280 as manufactured by Premium Spray Products, Marietta Georgia, or prior approved equal. The product shall exhibit the following typical physical properties: Density (sprayed-in-place): 2.7 pcf min. Compressive Strength: 42 psi min. Tensile Strength: 80 psi min. Shear Strength: 45 psi min. Closed Cell Content: 90% min. K Factor initial: Flame Spread (ASTM E-84): 75 max.* Roof deck Classification: UL 790 (ASTM E-108 Noncombustible deck Class A *This numerical flame spread rating is not intended to reflect hazards presented by this or any other material under actual fire conditions. 2.3 Fluid Applied Elastomeric Coating Acrylic rubber roof coating: The elastomeric coating shall be an acrylic
3 elastomer coating based on the Rohm and Haas EC resins. The product shall be Bayblock HT as manufactured by Bay Systems NA, Spring Texas, Premicote 1500 as manufactured by Premium Spray Products, Marietta Georgia Diathon HT as manufactured by United Coatings, Charleston, SC or prior approved equal with the following physical properties: Solids Content 55% min. Elongation 912% min. Tensile Strength 430 psi min. Ultra Violet Exposure No cracking, checking 8000 hours in Atlas weatherometer or significant discoloration Roof Deck Classification UL 790 (ASTM E-108) Noncombustible deck Class A Combustible deck Class B Lower tensile strength acrylic coatings shall not be allowed. The minimum dry mil thickness of the acrylic coating shall be 44 dry mils. Materials such as silicone, single component urethanes and catalyzed Urethanes, plasticized acrylics, vinyls, asphaltics, reground rubber, EVAs and PVA coatings shall not be considered. 2.4 Equipment Equipment for spraying foam shall be manufactured specifically for the application of polyurethane foam. The equipment shall be airless, capable of maintaining a 1:1 volume ratio and have primary and hose heaters. Coating equipment shall be an airless type as recommended by the coating manufacturer. 3.0 SURFACE PREPARATION 3.1 Surface condition: The surface shall be free from solvent, grease, dust, sediment, and dirt and sticky mastic. All extraneous equipment and equipment supports shall be removed from the deck. 3.2 Around each drain, remove all roofing materials to the deck 12 feet in each direction from the drain. Remove all roofing materials from the sides of each penetration. 3.3 Prime all surfaces with 0.5 gal per square Premicoat primer or prior approved equal.
4 3.4 Install aluminum vents every 200 square feet. Slit the cap sheet under the vent. 3.5 All surfaces not to receive foam such as walls, air conditioners and other roof mounted equipment are to be carefully masked with tape and paper to avoid over spraying of these surfaces with foam or coating. All coating is to be terminated in clean straight lines. 4.0 APPLICATION OF URETHANE FOAM 4.1 Environmental Conditions Wind velocity shall not exceed 12 miles per hour Application of spray foam shall not proceed if ambient temperature is less than 40 degrees F or if the substrate temperature is less than 50 degrees F Spray foam is not to be applied over moist substrates or where rain or inclement weather is eminent. 4.2 Spray Application The polyurethane foam shall be applied in minimum one half inch passes. The foam shall applied at a thickness of 1.5 inch and tapered uniformly to one inch at the drains. Encapsulate flashing on the parapet walls with foam Only as much area as can be brought to final thickness should be attempted in a day. Phasing of the foam is strictly forbidden. (Phasing is foam application on one day and coming back the next day or hereafter and a applying another layer of foam over the old foam. This procedure often leads to the development of blisters down the road.) If additional foam must be added after the 24 hour period, the existing foam must be primed with Futura 502 or equal and a minimum of one half inch of foam applied in a single pass The foam shall be free from bumps, pinholes and ridges. The surface shall exhibit a smooth or orange peel texture. Popcorn or tree bark surfaces shall be deemed unacceptable The foam thickness shall be checked every 500 square feet prior to coating application.
5 5.0 APPLICATION OF FLUID APPLIED PROTECTIVE COATING 5.1 General Sprayed polyurethane foam must be protected from ultraviolet light in order to avoid degradation of the polymer. Coating also protects the foam from liquid water and adverse weather conditions. Coatings must be specifically formulated for use over urethane foams. 5.2 Spray application Coating and Granules The coating is to be applied to the surface of the urethane foam in three uniform passes. The base coat, intermediate and top coat shall be of contrasting colors to assure uniformity of coverage. A total of 44 dry mils shall be applied to the foam as determined by an optical comparator. The coating shall be applied in the following sequence: a. Spray apply 1.5 gallons per 100 square feet of high tensile acrylic, Ivory to achieve a dry mil thickness of 12 dry mils. b. Spray apply 1.5 gallons per 100 square feet of high tensile acrylic white to achieve a dry mil thickness of 12 dry mils. While the top coat is still wet, broadcast white sand granules into the wet top coat at a rate of 25 lbs per square. c. After the intermediate coat has cured, spray apply 2.5 gallons per 100 square feet of high tensile acrylic white to achieve a dry mil thickness of 20 dry mils. While the coating is still wet, broadcast white sand granules into the wet top coat at a rate of 45 lbs per square. d. The total dry film thickness of the coating shall be 44 dry mils. Exception: The parapet walls shall receive 26 mils of Bayblock HT and shall not be granulated. The granule coverage shall be uniform and voids and bald spots (shiners) shall not be allowed. 6.0 WARRANTY AND CERTIFICATION The coating manufacturer shall issue a 10 year non depreciating manufacturer' warranty covering leakage. The coating manufacturer is to supply coating and labor for all repairs covered under the warranty. 7.0 INSPECTION
6 A representative from the coating manufacturer shall inspect the roof after completion to assure that the detail work at the protrusions, drains, parapets and edges have been completed in conformance with good practice. The inspector shall also check the thickness of the coating with an optical comparator. End
RECOATING AND RENEWING SPF ROOFING SYSTEMS
RECOATING AND RENEWING SPF ROOFING SYSTEMS Procedures, Regional Differences and type of coating systems Bruce Schenke Premium Spray Products REASONS TO RECOAT/RENEW Add a new coating layer to renew the
More informationALPHA 15-Year Permathane II FR w/granules
ALPHA 15-Year Permathane II FR w/granules Section 07 57 13 Sprayed Polyurethane Foam Roofing Guide Specification PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Furnish all labor, materials, tools and
More informationHow to repair your existing low slope flat roof.
How to repair your existing low slope flat roof. Recycled Rubber Roofing is not a "Roof Coating." It is a liquid emulsion used as the underlayment of a new or retrofit, built-up roofing system. One of
More informationSECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)
SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) PART 1 GENERAL 1.1 DESCRIPTION 1. Fluid applied flexible acrylic waterproofing system over concrete. This work shall include the
More informationSECTION 07 57 16 CEMENTITIOUS COATED FOAMED ROOFING
SECTION 07 57 16 CEMENTITIOUS COATED FOAMED ROOFING PART 1 GENERAL 1.01 SUBMITTALS A. Product Data: Submit manufacturer's literature and technical data (specifications, installation instructions and evidence
More informationThe Renewal of Spray Polyurethane Foam and Coating Roof Systems
The Renewal of Spray Polyurethane Foam and Coating Roof Systems RECOMMENDED DESIGN CONSIDERATIONS AND GUIDE SPECIFICATIONS Spray Polyurethane Foam Alliance Copyright 1994 - Revised September, 2000 To order
More informationSWD URETHANE COATED FOAM ROOFING SYSTEM MASTER ROOF SPECIFICATION SECTION 075700
SWD URETHANE COATED FOAM ROOFING SYSTEM MASTER ROOF SPECIFICATION SECTION 075700 Part 1 GENERAL SUMMARY Section Includes: Coated foam roofing system and acceptable alternative applications as specified
More informationSECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.
SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied
More informationMETAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES
METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES REFLECTICLEAN ACRYLIC/URETHANE Elastomeric Roofing Systems, Inc 6900 Bleck Dr. Rockford, MN 55373 800.403.7747 -or- 763.565.6900 fax: 763.565.6901 email:
More informationWESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC
More information07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying
More informationBUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION
07560 BUR BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION PART 1: GENERAL 1.01 SCOPE: To extend the useful service life of the aged or new asphalt built-up roof system and to reduce cooling
More informationA. This Section includes rubberized asphalt sheet membrane waterproofing systems.
SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
More informationTHERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER
THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER DESCRIPTION TORCH OVER (15,17,19 YR) TH/BS-TH/CS 2 1 0 No 0. SUBSTRATE 1. THERMOTEK USA 2.0 FV TORCH SMOOTH 2. THERMOTEK USA PRO FP TORCH GRANULE COMPONENTS
More informationTHERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS
OPTIONAL TITLE 24 CRITICAL POINTS POLYISO THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE DESCRIPTION TORCH OVER POLYISO (5,7,9 YR) TH/BS-TH/CS 2 No 0. SUBSTRATE. THERMOTEK USA PRO 2.0 FV
More informationTHERMOTEK SELF ADHESIVE MEMBRANE +G2 OVER WOOD SYSTEM DESCRIPTION SELF ADHESIVE OVER WOOD (8YR) BS-SA/CS
THERMOTEK SELF ADHESIVE MEMBRANE +G OVER DESCRIPTION SELF ADHESIVE OVER (8YR) BS-SA/CS 1 0 No 0. SUBSTRATE 1. BASE SHEET G FIBER GLASS BASE. THERMOTEK SELF ADHESIVE 3.0 FP GRANULE COMPONENTS AND WEIGHTS
More informationSECTION 623 CONCRETE BONDING COMPOUND, EPOXY MORTAR AND EPOXY POLYMER CONCRETE OVERLAY SECTION 623.10 CONCRETE BONDING COMPOUND.
SECTION 623 CONCRETE BONDING COMPOUND, EPOXY MORTAR AND EPOXY POLYMER CONCRETE OVERLAY SECTION 623.10 CONCRETE BONDING COMPOUND. 623.10.1 Description. This work shall consist of preparing the surface,
More informationREROOFING - SCOPE OF WORK
REROOFING - SCOPE OF WORK 1.0 GENERAL A. Summary of work: 1. Information herein is provided as a general overview of the project scope, and as such, does not grant authority for deviation from the manufacturers
More informationDivision 9. SignaFlor Pad and Pour Flooring System
Division 9 SignaFlor Pad and Pour Flooring System SPECIFICATIONS Page 1. General... 2 1.1 Description 2 1.2 Quality Assurance 2 1.3 Submittals 2 1.4 Delivery and Storage 3 1.5 Warranty 3 1.6 Working Conditions
More informationNEOGARD. Preventive Maintenance Manual
NEOGARD Preventive Maintenance Manual Fluid-Applied Roof Coating Systems December 2014 Notes NEOGARD luid-applied roof coating systems are designed to be long lasting, monolithic membranes which provide
More informationDocument Library TS Data Sheet 46012 46013 46014
Document Library TS Data Sheet 46012 46013 46014 Rev:2 Effective: 01/11/2002 3M Marine High Strength Repair Filler Data Sheet Status: Active 3M Part No.(s) 46012 46013 46014 3M Part Descriptor(s) Pint
More informationEXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
More information1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
More informationTECHNICAL DATA RS-6100. European Clear EZ. 5751 N. Webster Street Dayton, OH 45414-0802 Phone 937-890-6547 Toll Free 800-257-6547 Fax 937-890-6320
RS-6100 TECHNICAL DATA European Clear EZ DESCRIPTION: RS-6100 European Clear EZ is formulated with premium European resins. It is ideal for excellent color matching on white, light colors and metallics
More information738-B-297 POLYMERIC CONCRETE BRIDGE DECK OVERLAY. (Adopted 02-20-14)
POLYMERIC CONCRETE BRIDGE DECK OVERLAY (Adopted 02-20-14) Description The polymeric concrete bridge deck overlay shall consist of an epoxy polymer that acts together with special aggregate to form an overlay
More informationRead and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS
AC TOPSEAL SELF-ADHERED, GRANULAR SURFACED, SINGLE PLY, LOW SLOPE ROLLED ROOFING 3 X 33.3 = 100 SQ. FT. 10 YEAR MATERIAL LIMITED WARRANTY For Use on Porches / Sheds / Utility Buildings / Accessory Buildings
More informationRoof Systems Overview
Roof Systems Overview Cold Applied Built-Up Roofing Systems BURmastic Tremco s line of cold applied built-up roofing systems. BURmastic 200 Combines Tremco s expertise in asphalt blending technology with
More informationNRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
More informationPlease read the entire document before purchasing and installing any of these products
Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection
More informationHEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System
More informationCHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
More informationSECTION 32 1816 PLAYGROUND SURFACING TILES
SECTION 32 1816 PLAYGROUND SURFACING TILES PART 1 GENERAL 1.01 SECTION INCLUDES A. Resilient playground safety surfacing tiles. B. Coordinate with work shown in other sections so the work is installed
More informationSECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
More informationTHIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 SECTION ONE A. Objective The objective of this guide is to provide Owners and General Contractors/Construction
More informationRe-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
More informationBITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES
BITUMINOUS ROOF COATINGS, CEMENTS, PRIMERS AND ADHESIVES ABOUT POLYGLASS U.S.A., INC. MODIFIED CEMENTS & ADHESIVES MASTICS ALUMINUM COATINGS EMULSIONS & PRIMERS PROTECTIVE COATINGS Polyglass manufactures
More informationNEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
More information09990 MOLD REMEDIATION, LEAD-BASED PAINT ABATEMENT AND ENCASEMENT OF ASBESTOS
09990 MOLD REMEDIATION, LEAD-BASED PAINT ABATEMENT AND ENCASEMENT OF ASBESTOS PDS SE-160 01-2006 1. PRODUCT NAME SE-160 Clear Surface Coating (water-based copolymer) Specialty Elastomeric Topcoat 2. MANUFACTURER
More informationSecondary Containment Comparison ATI Ultra COAT vs HDPE
When choosing a secondary containment system it must be chosen based on its ability to withstand long term contact with the natural elements (weather), whatever the tanks hold (unrefined oil, fuels, acids,
More informationCITY OF BELL PROFESSIONAL CONSULTING SERVICES FOR ROOF REPAIRS TO CITY OWNED FACILITIES
CITY OF BELL 6330 PINE AVENUE BELL, CA 90201 PH: (323) 588-6211 FAX: (323) 771-9473 CITY OF BELL PROFESSIONAL CONSULTING SERVICES FOR ROOF REPAIRS TO CITY OWNED FACILITIES I. INTRODUCTION City of Bell
More informationSCENIC VIEW SV 10 SECTION 08 87 13 SOLAR CONTROL FILMS
PART 1 GENERAL SCENIC VIEW SV 10 SECTION 08 87 13 SOLAR CONTROL FILMS 1.1 SUMMARY A. Optically clear dual reflective, neutral sputtered and aluminum metallized polyester film for solar control. 1.2 RELATED
More informationPeel & Seal Self-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
More informationDouble Coated Urethane Foam Tapes
3 Double Coated Urethane Foam Tapes 4004 4008 4016 4026 4032 4052 4056 4085 Technical Data April, 2009 Product Description 3M Double Coated Urethane Foam Tapes are conformable foams that offer high shear
More informationSC2000 CEMENT BONDING PROCEDURES
Pg.1 SC2000 CEMENT BONDING PROCEDURES Widely recognized as the world s finest cold vulcanizing cement REMA SC2000 is the solution to your industrial bonding problems. By using REMA UTR20 hardener with
More informationCREEK Technical Services, LLC
EVALUATION REPORT 2010 FLORIDA BUILDING CODE Manufacturer: Henry Company Report Issued February 20, 2013 999 North Sepulveda Blvd., Suite 800 El Segundo, CA 90245 (800) 486-1278 Manufacturing Plants: Quality
More informationATLAS Roofing Products
ATLAS Roll Roofing Products World s Largest producer of roofing s Preferred by roofing professionals. Atlas has you covered on every part of the job, even what goes under your roofing. We are proud to
More informationSection 07540 BUILT UP ROOF (BUR) SPECIFICATION. 3 Coat Protocol. Material Only_10 yr Warranty
1480 Englewood Ave. www.elastikote.com Akron, Ohio 44305 330-669-2552 800-992-1053 Section 07540 3 Coat Protocol Page 2 of 16 Page 3 of 16 Environmentally Responsible LIQUID MEMBRANE SYSTEM Roof restoration
More informationPOLYURETHANE LINING AND COATING ON PIPE RAW WATER
POLYURETHANE LINING AND COATING ON PIPE RAW WATER PART 1 -- GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide pipe coating, complete and in place, in accordance with the Contract Documents. 1.2
More informationProduct Guide Specification
Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail ri@reefindustries.com Product Guide
More information3 Scotch-Weld TM. Urethane Adhesives 3532 B/A 3535 B/A 3549 B/A. Technical Data January, 2010
3 Scotch-Weld TM Technical Data January, 2010 Product Description 3M Scotch-Weld 3532 B/A, 3535 B/A and 3549 B/A are two-component, polyurethane adhesives which cure at room temperature or with heat to
More informationCOMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
More informationCarpet Tile Installation Guidelines
NOTICE FAILURE TO FOLLOW THESE GUIDELINES CAN RESULT IN VOIDING THE CARPET WARRANTY. Installation Guidelines The following instructions should be reviewed prior to installation. Shaw Industries will not
More informationClear Fork Valley Local School District. Roofing Repairs Spring/Summer 2015
Clear Fork Valley Local School District Roofing Repairs Spring/Summer 2015 Instructions to Bidders: Public Notice To Bidders (ORC 3313.46) Notice is hereby given that sealed bids will be received at the
More informationRoof Condition Report. Academy International School 8550 Charity Drive. Colorado Springs, Colorado
Roof Condition Report Academy International School 8550 Charity Drive Colorado Springs, Colorado FOR Mr. Robert Thompson Academy School District 20 10221 Lexington Drive Colorado Springs, Colorado July
More informationHIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS
BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side
More informationSelf-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
More informationSECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.
SECTION 07530 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section includes the flowing: 1. Removal of existing roofing membrane. Existing bur roof has one overlay and penetration mastic is asbestos containing.
More informationCOMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE
www.epdmroofs.org COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE By Ric Vitiello President Forensic Roof Consulting and Hail Damage Assessment Training www.benchmark-services.com
More informationRoofing Repairs 07511-1
SECTION 07511 ROOF AND FLASHING RESTORATION WITH TITLE 24 / COOL ROOF SURFACING PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including General and Supplementary
More information3 Scotch-Weld TM. Urethane Adhesives 3532 B/A 3535 B/A 3549 B/A. Technical Data March, 2002
3 Scotch-Weld TM Technical Data March, 2002 Product Description 3M TM Scotch-Weld TM 3532 B/A, 3535 B/A and 3549 B/A are two-component, polyurethane adhesives which cure at room temperature or with heat
More informationGUIDELINE SPECIFICATIONS
GUIDELINE SPECIFICATIONS GORDON SOFFIT-SHIELD - An Exterior Metal Soffit System DIVISION 05 5800 or DIVISION 07 7700 Note To Specifier: SOFFIT-SHIELD should be installed by tradesmen that are experienced
More informationSpecifying SPF Roofing Systems
Specifying SPF Roofing Systems Spray polyurethane foam (SPF) roofing systems have been marketed for years primarily on their documented energy saving characteristics. Consequently much of the SPF roofing
More informationFEFPA 2015 SUMMER CONFERENCE. Energy Effectiveness through Roof Coatings and Solar
FEFPA 2015 SUMMER CONFERENCE Energy Effectiveness through Roof Coatings and Solar Welcome Danny G. Daniel Stokes, CSI, CDT, RCI, CPRC Vice President Advanced Roofing Inc. About Danny Stokes Vide President
More informationWATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced
More informationWATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
More informationSWEPCO HEAVY DUTY POLYMASTER ROOF SYSTEM 201
31 SC: 33 SWEPCO POLYMASTER ROOF SYSTEM 201 APPLICATION SPECIFICATIONS IMPORTANT -- These application specifications are provided for the use of all persons who are to apply SWEPCO Products. Please read
More informationAcrylic Enamel Topcoat
Acrylic Enamel Topcoat ACRYL-GLO TECHNICAL DATA SHEET The ACRYL-GLO single-stage acrylic enamel paint system provides a durable finish that is easy to apply and suitable for both commercial and passenger
More informationRehabilitation of an Aging Concrete Reservoir Adit Tower
Rehabilitation of an Aging Concrete Reservoir Adit Tower Raymond S. Tombaugh, Senior Coatings Consultant KTA-Tator, Inc. and Mongkol Mahavongtrakul, P.E. Corrosion Control Contract Manager San Francisco
More information07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center
PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 5423 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center A. Tear off existing roof system down to wood deck and install new Thermoplastic membrane roofing
More informationA. Work on this project shall consist of, but is not limited to, the following:
PART 1 - GENERAL CLEANING AND RESTORATION OF SECTION 05900-1 1.1 SUMMARY A. Work on this project shall consist of, but is not limited to, the following: 1. Clean and treat all exposed anodized architectural
More informationROOF INSPECTION & MAINTENANCE
Physical Plant Administration Facilities Maintenance Department ROOF INSPECTION & MAINTENANCE All roofs require periodic inspection and maintenance in order to perform as designed and to provide a long
More informationAdditional Information. Paint Application
Additional Information Paint Prepared by: International Paint Ltd. www.international-pc.com The information in this guideline is not intended to be exhaustive; any person using the product for any purpose
More informationMaintenance & repair Solutions
Maintenance & repair Solutions low-slope ROOFING We ve got what you need in the sizes you need them and the options to match the results that building owners want Seal-fast Temporary roof sealer Now you
More informationIf you are a web registered user of ArlingontPermits.com you may also request an inspection at:
TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors
More informationGigaCrete Specification PlasterMax
GigaCrete Inc. 6775 Speedway Blvd. Suite M105 Las Vegas, NV 89115 Ph (702) 643-6363 Fax (702) 643 1453 www.gigacrete.com GigaCrete Specification PlasterMax PlasterMax : Fire Rated Plaster for Direct Application
More information3 Single-Coated Foam Tapes
3 Single-Coated Foam Tapes Technical Data May, 2008 Product Description 3M Single-Coated Foam Tapes will adhere to a variety of substrates, including latex-painted wood, lacquered wood, enameled steel,
More informationStandard Method for Sampling and Analysis of. of Chlorine Containing Bleaches. Soap Products
GUIDE SPECIFICATION FOR GENERAL CLEANING AND REMOVAL OF MOLD AND MILDEW ON EXTERIOR INSULATED AND FINISH SYSTEMS AND STUCCO DIVISION 07240 and DIVISION 09240 8/05 PART I: GENERAL 1.01 DESCRIPTION AND SCOPE
More information!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!
Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing
More informationSECTION 07400 STANDING SEAM METAL ROOF
SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and
More informationEpoxy Floor Coating Problem Solving Guide
Table of Contents: Page: Troubleshooting Issue: 2. Color Differential 3. Fish Eye 4. Milky or Cloudy Coatings 5. Orange Peel 6. Peeling or Delamination 8. Delamination between Coats 9. Pinholes/Bubbling
More informationSECTION 07 42 13 METAL WALL PANELS
Mitsubishi Plastics Composites America, Inc. 401 Volvo Parkway Chesapeake, VA 23320 Phone: (800) 422-7270 Fax: (757) 436-1896 E-mail: info@alpolic.com www.alpolic-northamerica.com This MANU-SPEC utilizes
More informationPHOENIX 370-120 Product Data Sheet (Updated on 14-Jan-2012) www.phoenixasia.com.hk
DESCRIPTION A water borne thin film intumescent coating for the fire protection of structural steelwork. PRODUCT FEATURES AND RECOMMENDED USES Provides up to 120 minutes fire resistance to structural steelwork.
More information3 Scotch-Weld TM. Structural Adhesive Films AF 6 AF 10 AF 13. Technical Data July, 2001
3 Scotch-Weld TM Technical Data July, 2001 Introduction 3M Scotch-Weld AF 6, AF 10, AF 13 are unsupported, thermosetting adhesives in film form developed for the structural bonding of metals. These products
More informationSTERI-SOFT HIGH FOOT TRAFFIC, ULTRAVIOLET RESISTANT, URETHANE RESILIENT FLOORING SYSTEM, 1/8 GREEN BUILDING FEATURES TYPICAL APPLICATIONS
GREEN BUILDING FEATURES * Steri-Soft contributes toward satisfying credit EQ 4.2 under LEED. 100% Resilient Flooring Low emitting material Contains 27% post consumer recycled product Processed and manufactured
More informationSECTION 15190 HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section 15010.
SECTION 15190 HVAC INSULATION PART ONE - GENERAL PART 1 - GENERAL 1.01 DESCRIPTION A. All work specified in this Section is subject to the provisions of Section 15010. B. All insulation products shall
More informationDocument Library TS Data Sheet 08609. 3M Windo-Weld Super Fast Urethane. Data Sheet. Public
Document Library TS Data Sheet 08609 Public Rev:3 Effective: 09/14/2007 Status: Active 3M Windo-Weld Super Fast Urethane Data Sheet 3M Part No.(s) 3M Part Descriptor(s) 08609 3M Windo-Weld Super Fast Urethane
More informationFIRESTOPPING & SMOKE SEALS
SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of
More informationSEAMS SEAMING USING SEAM TAPE
SEAMING USING SEAM TAPE SEAMS The membrane should be positioned so that the width of the seam is 3. Remove excess chalk from a chalk line by snapping the line into the air and then chalk a line one-quarter
More informationROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
More informationTechnical Data Sheet February 2014
Scotch-Weld Technical Data Sheet February 2014 Product Description s are high performance, two-part acrylic adhesives that offer excellent shear, peel, and impact performance. These toughened products
More information1.02 DESCRIPTION A. This Section specifies furnishing and installing Cast in Place Detectable/Tactile Warning Surface tiles where indicated.
CAST IN PLACE DETECTABLE/TACTILE WARNING SURFACE TILE PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Special Conditions and Division 1 Specifications
More informationSPECIAL NOTE FOR ASPHALT WATERPROOFING MIX FOR BRIDGE-DECK OVERLAYS AND ADJACENT APPROACHES
SPECIAL NOTE FOR ASPHALT WATERPROOFING MIX FOR BRIDGE-DECK OVERLAYS AND ADJACENT APPROACHES 1. DESCRIPTION. Asphalt Waterproofing Mix (AWM) is a highly elastomeric, polymermodified, impermeable asphalt
More informationA. The CONTRACTOR shall provide pipe coating, complete and in place, in accordance with the Contract Documents.
POLYURETHANE COATING ON STEEL PIPE PART 1 -- GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide pipe coating, complete and in place, in accordance with the Contract Documents. 1.2 REFERENCE SPECIFICATIONS,
More informationELASTOCEM. Technical features. Applications. Two-component flexible, waterproofing and protective cementitious grout.
Two-component flexible, waterproofing and protective cementitious grout. 1504-2 PI-MC-IR Technical features Two-component grout, based on cements, selected aggregates, special additives and synthetic polymers
More informationThird Party Inspection Guidelines For Inspectors As Part of the dryvitcare EIFS Repair/Restoration
Third Party Inspection Guidelines For Inspectors As Part of the dryvitcare EIFS Repair/Restoration DS497 SECTION ONE A. Objective The objective of this guide is to provide owners and general contractors/construction
More informationFIRESTONE APP ROOFING SYSTEMS APPLICATION GUIDE TABLE OF CONTENTS
FIRESTONE APP ROOFING SYSTEMS APPLICATION GUIDE TABLE OF CONTENTS 2.01.1 GENERAL...2 2.02.1 JOB SITE CONSIDERATIONS (CAUTION AND WARNINGS)...2 2.03.1 ROOF SUBSTRATE PREPARATION...2 2.04.1 WOOD NAILER LOCATION
More informationSeamless Waterproofing. Systems
Seamless Waterproofing Systems Pitched/Corrugated Roofs Liquid Rubber Instant Set is the ideal solution for pitched roof waterproofing providing a seamless fully bonded finish. RapidRoof is suited to smaller
More informationROOFING CONTRACTORS QUESTIONNAIRE
ROOFING CONTRACTORS QUESTIONNAIRE ALL QUESTIONS MUST BE ANSWERED 1. Applicant Name: Website Address: Address: Years in business under the applicant name: Are you an NRCA (National Roofing Contractors Association)
More informationINSTRUCTIONS FOR COORDINATION SECTION 06651 SOLID SURFACE FABRICATIONS
INSTRUCTIONS FOR COORDINATION SECTION 06651 SOLID SURFACE FABRICATIONS 1. Paragraph 1.02 Provide solid surface countertops at sinks locations. Provide solid surface window sills at drywall framing walls.
More information