ROXUL Board Insulation Section Master Guide Specification (CAVITYROCK ) Page 1 April 2016
|
|
|
- Willa York
- 9 years ago
- Views:
Transcription
1 Master Guide Specification (CAVITYROCK ) Page 1 Click on the pilcrow in the MS Word Toolbar to toggle ROXUL GUIDE NOTES on and off. Delete this text before incorporating the section into a Project Manual. 1 GENERAL 1.1 SUMMARY OF WORK A. This Section specifies stone fiber board insulation for cavity wall, curtain wall, sandwich panel systems, and, other board insulation applications. 1.2 RELATED REQUIREMENTS A. Section [ Acoustical Joint Sealants]. 1.3 REFERENCE STANDARDS A. ASTM International (ASTM). 1. ASTM C165 - [2012], Standard Test Method for Measuring Compressive Properties of Thermal Insulations. 2. ASTM C303 - [2012], Standard Test Method for Dimensions and Density of Preformed Block and Board-Type Thermal Insulation. 3. ASTM C518 - [2010], Standard Test Method for Steady-State Thermal Transmission Properties by Means of the Heat Flow Meter Apparatus. 4. ASTM C612 - [2010], Standard Specification for Mineral Fiber Block and Board Thermal Insulation. 5. ASTM C665 - [2011], Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing. 6. ASTM C795 - [2013], Standard Specification for Thermal Insulation for Use in Contact with Austenitic Stainless Steel. 7. ASTM C1104/C1104M - [2013], Standard Test Method for Determining the Water Vapor Sorption of Unfaced Mineral Fiber Insulation. 8. ASTM C [2008], Standard Test Method for Determining Fungi Resistance of Insulation Materials and Facings. 9. ASTM E84 - [2012b], Standard Test Method for Surface Burning Characteristics of Building Materials. 10. ASTM E96/E96M - [2010], Standard Test Methods for Water Vapor Transmission of Materials. 11. ASTM E136 - [2011], Standard Test Method for Behavior of Materials in a Vertical Tube Furnace at 750 degrees C. B. US Green Building Council (USGBC). 1. LEED v4-[2014], LEED (Leadership in Energy and Environmental Design): Green Building Rating System. 1.4 ADMINISTRATIVE REQUIREMENTS A. Co-ordination: Co-ordinate work of this Section with roofing or deck work and with work of other trades for proper time and sequence to avoid construction delays. B. Pre-installation Meeting: Convene pre-installation meeting after Award of Contract and [one week] before starting work of this Section to verify project requirements, substrate conditions and coordination with other building sub-trades, and to review manufacturer s written installation instructions. 1. Comply with Section Project Meetings and co-ordinate with other similar pre-installation meetings. 2. Notify attendees 2 weeks prior to meeting and ensure meeting attendees include as minimum: a. Owner; b. Consultant; c. Board Insulation Installation Subcontractor; d. Manufacturer s Technical Representative.
2 Master Guide Specification (CAVITYROCK ) Page 2 3. Ensure meeting agenda includes review of methods and procedures related to insulation installation including co-ordination with related work. 4. Record meeting proceedings including corrective measures and other actions required to ensure successful completion of work and distribute to each attendee within 1 week of meeting. 1.5 ACTION AND INFORMATIONAL SUBMITTALS A. Make submittals in accordance with Contract Conditions and Section Submittal Procedures. B. Product Data: Submit product data including manufacturer s literature for insulation materials and accessories, indicating compliance with specified requirements and material characteristics. 1. Submit list on insulation manufacturer s letterhead of materials and accessories to be incorporated into Work. 2. MSDS report. 3. Include product name. 4. Include preparation instructions and recommendations, installation methods, and storage and handling requirements. 5. Include contact information for manufacturer and their representative for this Project. C. Samples: 1. Submit [12 x 12] inches minimum sample of insulation in thickness used on Project. D. Test Reports: 1. Submit evaluation service reports or other independent testing agency reports showing compliance with specified performance characteristics and physical properties. E. Field Reports: Submit manufacturer s field reports within 3 days of each manufacturer representative s site visit and inspection. F. Sustainable Design (LEED). 1. LEED Submittals: In accordance with Section [ LEED Requirements] 2. Submit verification for items as follow: a. EA Credit 1: Thermal value of insulation contributing to overall energy performance of building. b. MR Credits 4: Recycled content of insulation indicating percentages by weight of preconsumer and postconsumer recycled content. c. MR Credits 5: Verify location where insulation is extracted, processed and manufactured. G. Insulation Installer Qualifications: 1. Submit letter verifying insulation installer s experience with work similar to work of this Section. 1.6 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: Supply maintenance data for insulation materials for incorporation into manual specified in Section Closeout Submittals. B. Sustainable Design Closeout Documentation (LEED). 1. Provide calculations on end-of-project recycling rates, salvage rates, and landfill rates for work of this Section demonstrating percentage of construction wastes which were recycled. 2. Submit verification from recycling facility showing receipt of materials. C. Record Documentation: In accordance with Section Closeout Submittals. 1. List materials used in insulation work. 2. Warranty: Submit warranty documents specified. 1.7 QUALITY ASSURANCE A. Board Insulation Installer Quality Assurance: Work experience of [5] years minimum with work similar to work of this Section.
3 Master Guide Specification (CAVITYROCK ) Page 3 B. Sustainability Standards Certification (LEED). 1. LEED submittals: In accordance with Section LEED Requirements. 1.8 DELIVERY STORAGE AND HANDLING A. Delivery and Acceptance Requirements: 1. Deliver material in accordance with Section Common Product Requirements. 2. Deliver materials and accessories in insulation manufacture s original packaging with identification labels intact and in sizes to suit project. 3. Ensure insulation materials are not exposed to moisture during delivery. 4. Replace wet or damaged insulation materials. B. Storage and Handling Requirements: Store materials off ground in dry location and protected from exposure to harmful weather conditions and at temperature conditions recommended by manufacturer. 1. Store in original packaging until installed. C. Packaging Waste Management: 1. Separate and recycle waste packaging materials in accordance with Section Construction Waste Management and Disposal. 2. Remove waste packaging materials from site and dispose of packaging materials at appropriate recycling facilities. 3. Collect and separate for disposal paper and plastic material in appropriate on-site storage containers for recycling [in accordance with Waste Management Plan]. 1.9 WARRANTY A. Project Warranty: Refer to Contract Conditions for project warranty provisions. B. Manufacturer s warranty: Submit, for Owner s acceptance, manufacturer s standard warranty document executed by authorized company official. Manufacturer s warranty is in adual Densityition to and not intended to limit other rights Owner may have under Contract Conditions. C. Warranty period: [1] years commencing on Date of Substantial Performance of Work. 2 PRODUCTS 2.1 MANUFACTURER A. Manufacturer: ROXUL INC., 8024 Esquesing Line, Milton, Ontario, L9T 6W3, Phone: , Toll Free: , [email protected], URL: DESCRIPTION A. Non-combustible, lightweight, water repellent, rigid insulation board with rigid upper surface to ASTM C612 Type IVB. 2.3 PERFORMANCE CRITERIA A. Board insulation for exterior cavity wall: To ASTM C612 Type IVB. 1. Fire performance: a. Non-combustibility: To ASTM E136. c. Surface Burning Characteristics: To ASTM E84. 1) Flame spread: 0. 2) Smoke developed: Thermal resistance.1 2 and less R value/1 inch at 75 ºF: 4.2 h ft2 ºF/Btu to ASTM C and greater R value/1 inch at 75 ºF: 4.3 h ft 2 ºF/Btu to ASTM C Water vapor permeance: 27.2 Perm minimum. 4. Moisture sorption: 1 % maximum to ASTM C1104/C1104M.
4 Master Guide Specification (CAVITYROCK ) Page 4 5. Fungi resistance: Zero mould growth to ASTM C Corrosive resistance: a. Steel to ASTM C665: Pass. b. Stainless steel to ASTM C795: Pass. 7. Recycled content: [16] [40] % minimum. 8. Acoustical performance sound absorption co-efficients to ASTM C423. Sound Absorption Co-efficiences at Frequencies Thickness 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz NRC (inches) MATERIALS A. Non-combustible, lightweight, water repellent, rigid insulation board with rigid upper surface to ASTM C612 Type IVB. 1. Size: [16] [24] x 48 inches. 2. Thickness: and weight: [1] [1.5] [2] [2.5] [3] [3.5] [4] [4.5] [5] inches. 3. Thicknesses 2 and below Density 4.4 lb/ft 3 to ASTM C Thicknesses 2.5 and above Density: a. Outer layer: 6.24 lb/ft 3 to ASTM C303. b. Inner layer: 3.75 lb/ft 3 to ASTM C Acceptable Material: ROXUL INC., CAVITYROCK. 2.5 ACCESSORIES A. Mechanical fasteners in accordance with insulation manufacturer s written recommendations. B. Insulation Clips: in accordance with manufacturer s written recommendations. 2.6 SOURCE QUALITY CONTROL A. Ensure insulation components and accessories are supplied or approved in writing by single manufacturer. 2.7 PRODUCT SUBSTITUTIONS A. Substitutions: [In accordance with Section Product Substitution Procedures] [No substitutions permitted]. 3 EXECUTION 3.1 INSTALLERS A. Use only installers with [5] years minimum experience with work similar to work of this Section. 3.2 EXAMINATION A. Verification of Conditions: Verify that conditions of substrate previously installed under other Sections or Contracts are acceptable for insulation installation in accordance with manufacturer s written recommendations. 1. Visually inspect substrate in presence of Consultant. 2. Ensure surfaces are free of snow, ice, frost, grease and other deleterious materials. 3. Proceed with installation only after unacceptable conditions have been remedied and after receipt of written approval to proceed from Consultant. B. Start of insulation installation indicates installer s acceptance of substrate installation conditions.
5 Master Guide Specification (CAVITYROCK ) Page INSTALLATION A. General: 1. Install insulation in accordance with manufacturer s written recommendations. 2. Install insulation to maintain continuity of thermal protection to building elements and spaces. 3. Fit insulation closely around electrical boxes, pipes, ducts, frames and other objects in or passing through insulation. 4. Keep insulation minimum [3] inches from heat emitting devices such as recessed light fixtures, and minimum [2] inches from sidewalls of chimneys and vents. 5. Do not enclose insulation until before inspection and receipt of Consultant s written approval. B. Installation of Insulation Board for Exterior Cavity Wall Installations: 1. Install insulation board in accordance with insulation manufacturer s written recommendations. 2. Seal joints with acoustical joint sealant in accordance with Section [ Acoustical Joint Sealants]. C. Installation of Insulation Board for Foundations: 1. Install insulation board on foundation using all purpose construction adhesive in accordance with insulation manufacturer s written recommendations. 2. Attach insulation board with 1.5 inches concrete nails and seal with bitumen sealing compound.. 3. Seal joints with acoustical joint sealant in accordance with Section [ Acoustical Joint Sealants]. 3.4 FIELD QUALITY CONTROL A. Field Inspection: Coordinate field inspection in accordance with Section [ Quality Control]. B. Manufacturer s Services: 1. Coordinate manufacturer s services with Section [ Quality Control]. a. Arrange for payment for manufacturer s services. b. Have manufacturer review work involved in handling, installation, protection, and cleaning of insulation and accessories, and submit written reports in acceptable format to verify compliance of Work with Contract conditions. 2. Manufacturer s Field Services: Provide manufacturer s field services consisting of product use recommendations and periodic site visits for product installation review in accordance with manufacturer s instructions. a. Report any inconsistencies from manufacturer s recommendations immediately to Consultant. 3. Schedule site visits to review work at stages listed: a. After delivery and storage of drainage sheet and accessories, and when preparatory work on which Work of this Section depends is complete, but before installation begins. b. Twice during progress of work at 25% and 60% complete. c. Upon completion of Work, after cleaning is carried out. d. Obtain reports within three days of review and submit immediately to Consultant. 3.5 CLEANING A. Progress Cleaning: Perform cleanup as work progresses [in accordance with Section Cleaning and Waste Management]. 1. Leave work area clean at end of each day. B. Final Cleaning: Upon completion, remove surplus materials, rubbish, tools, and equipment [in accordance with Section Cleaning and Waste Management]. C. Waste Management: 1. Co-ordinate recycling of waste materials with Construction Waste Management and Disposal. 2. Collect recyclable waste and dispose of or recycle field generated construction waste created during construction or final cleaning related to work of this Section. 3. Remove recycling containers and bins from site and dispose of materials at appropriate facility.
6 Master Guide Specification (CAVITYROCK ) Page PROTECTION A. Protect installed products and accessories from damage during construction. B. Repair damage to adjacent materials caused by insulation installation. END OF SECTION BOARD INSULATION (CAVITYROCK)
Roxul Board Insulation Section 07 21 13 Master Guide Specification (CAVITYROCK DD) Page 1 October 2013
Master Guide Specification (CAVITYROCK DD) Page 1 ROXUL GUIDE NOTE: This master specification section is based on ROXUL INC., CAVITYROCK DD. Standard application: Cavity wall. ROXUL GUIDE NOTE: This master
EcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings
BUILDING ENVELOPE DESIGN BY ROXUL Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB Exterior
Building Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings
Building Envelope Design using ROXUL Building Envelope Design using ROXUL (BEDR ) FIREWALL and ROXUL PLUS MB Fire Rated Board Insulation for Pre-Engineered Metal Buildings ROXUL FIREWALL & ROXUL PLUS MB
Fiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying
fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors
fire & soundproofing Insulation Roxul Safe n Sound Fire and Soundproofing Insulation for Interior Partition Walls and Floors Roxul Safe n Sound Sound Control and Fire Safety From One Batt Insulation Roxul
Fire & Soundproofing Insulation. Roxul SAFE N SOUND. Fire and Soundproofing Insulation for Interior Partition Walls and Floors.
Fire & Soundproofing Insulation Roxul SAFE N SOUND Fire and Soundproofing Insulation for Interior Partition Walls and Floors. Roxul SAFE N SOUND Sound control and fire safety from one batt Insulation.
INSULATION FOR PRE-ENGINEERED METAL BUILDINGS. ROXUL SAFE 55 & 65 and ROXUL PLUS MB. Insulation for Pre-Engineered Metal Buildings
INSULATION FOR PRE-ENGINEERED METAL BUILDINGS ROXUL SAFE 55 & 65 and ROXUL PLUS MB Insulation for Pre-Engineered Metal Buildings ROXUL SAFE AND ROXUL PLUS MB Exterior Wall Insulation for Pre-Engineered
Product Guide Specification
Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail [email protected] Product Guide
FIRESTOPPING & SMOKE SEALS
SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of
THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST
THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST Instruction: Check each test method for which you are requesting accreditation. An asterisk beside the NVLAP Test Method Code indicates that proficiency
Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
SECTION 05 42 16 COLD-FORMED METAL DECK FRAMING Elevations Steel Deck Framing by Trex
(Specifier Note: The purpose of this guide specification is to assist the specifier in correctly specifying cold-formed metal deck framing products and execution. The specifier needs to edit the guide
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
03/05/14 REVISOR RSI/JC RD3945
1.1 Department of Commerce 1.2 Proposed Permanent Rules Relating to Commerce; Thermal Insulation Standards; 1.3 Materials and Installation 1.4 7640.0100 AUTHORITY; PURPOSE; INCORPORATIONS BY REFERENCE.
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
SECTION 07 21 16 - PRE-ENGINEERED BUILDING BLANKET INSULATION
PROJECT ARCHITECT RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
SECTION 072100 FIBERGLASS INSULATION
This Specification Section is provided in CSI format for engineers and architects specifying fiberglass insulation manufactured by Knauf Insulation GmbH. in Shelbyville, Indiana. Delete insulation types
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.
SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied
ROCK WOOL Preformed Pipe Section
ROCK WOOL Preformed Pipe Section Rockwool preformed Pipe section conforming ASTM C 547 and equivalent BS39584 is intended for the thermoacoustic insulation and fire protection of pipe works operating at
Fire Barrier Duct Wrap 15A
3 Fire Barrier Duct Wrap 15A Commerical Kitchen Grease Duct Fire Protection System Product Data and Installation Instructions Compliance 1998 Edition Complies with International Mechanical Code Complies
ROXUL COMMERCIAL ROOFING. Understanding Climate Requirements That Drive Performance. roxul.com
ROXUL COMMERCIAL ROOFING Understanding Climate Requirements That Drive Performance High Performance Roofing Insulation Products ROXUL /ROCKWOOL commercial roofing products have been available globally
ROXUL TOPROCK DD & MONOBOARD. Roofing Insulation for Commercial Construction. ROXUL TOPROCK DD and MONOBOARD
ROXUL TOPROCK DD & MONOBOARD Roofing Insulation for Commercial Construction ROXUL TOPROCK DD and MONOBOARD NEPRW OVED & IM RD OBOA N O M ROXUL TOPROCK DD & MONOBOARD High Performance Roofing Insulation
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
GYPSUM AREA SEPARATION FIREWALLS GA-620-2011
GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GA-620-2011 Copyright 2011 Gypsum Association All rights reserved. Printed in U.S.A. Characteristics, properties, or performance of materials or systems herein
NEW NEW. Pipe Products Catalogue. ProRox NEW NEW. Pipe Insulation for High Temperature Industrial Applications PRODUCT NAMES
INDUSTRIAL PIPE HIGH TEMPERATURE INSULATION AMES 2 PRODUCT S PRODUCT S 2012 PRODUCT S 2012 PRODUCT S 2012 ProRox Pipe Products Catalogue Pipe Insulation for High Temperature Industrial Applications New
Enclosures 1-866-338-0988. DuraSystems Barriers, Inc. www.durasystems.com Email: [email protected]. The Passive Fire Protection Specialists
Enclosures Sturdy single and double wall fire protection construction Impact resistant Fast & easy installation Pre-manufactured and modular Available in galvanized, stainless steel & other specialty metals
Product Guide Specification
Stabilit America, Inc., dba Glasteel June 2005 285 Industrial Drive Moscow, Tennessee 38057 Toll Free (800) 238-5546 Phone (901) 877-3010 Fax (901) 877-1388 Web Site www.glasteel.com Product Guide Specification
Building Envelope Design. ComfortBoard IS. Exterior Insulated Sheathing for High-Performance Residential Wall Systems
Building Envelope Design by Roxul Building Envelope Design by Roxul (BEDR ) ComfortBoard IS Exterior Insulated Sheathing for High-Performance Residential Wall Systems The Shore House North Vancouver, BC,
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
MASTERFORMAT SPECIFICATION
Insulspan, Incorporated 9012 East US 223 Blissfield, MI, USA 49228-0026 Phone: 800.726.3510 Insulspan Division of Plasti-Fab Ltd. 600 Chester Road Deltas, BC, Canada V3M 5Y3 Phone: 866.848.8855 www.insulspan.com
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 31 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES
Product Information. Tel: 905.696.9900 x2426 or x2443 Fax: 905.696.9300 Email: [email protected]
Tel: 905.696.9900 x2426 or x2443 Fax: 905.696.9300 Email: [email protected] Product Information 6320-2 Danville Rd. Mississauga, Ontario Canada L5T 2L7 TABLE OF CONTENTS Sheet Product Alusion Sheet Products.......................................................
SECTION 07 42 13 METAL WALL PANELS
Mitsubishi Plastics Composites America, Inc. 401 Volvo Parkway Chesapeake, VA 23320 Phone: (800) 422-7270 Fax: (757) 436-1896 E-mail: [email protected] www.alpolic-northamerica.com This MANU-SPEC utilizes
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
Architectural Concrete Masonry
1. Adams Profile Split Face Units (PSF). 2. Adams Profile Split Face Single Score Units (PSF-1). 3. Adams Profile Split Face Double Score Units (PSF-2) 4. Adams Profile Wide Split Rib Four Units (PWSR-4).
SECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
09990 MOLD REMEDIATION, LEAD-BASED PAINT ABATEMENT AND ENCASEMENT OF ASBESTOS
09990 MOLD REMEDIATION, LEAD-BASED PAINT ABATEMENT AND ENCASEMENT OF ASBESTOS PDS SE-160 01-2006 1. PRODUCT NAME SE-160 Clear Surface Coating (water-based copolymer) Specialty Elastomeric Topcoat 2. MANUFACTURER
SCENIC VIEW SV 10 SECTION 08 87 13 SOLAR CONTROL FILMS
PART 1 GENERAL SCENIC VIEW SV 10 SECTION 08 87 13 SOLAR CONTROL FILMS 1.1 SUMMARY A. Optically clear dual reflective, neutral sputtered and aluminum metallized polyester film for solar control. 1.2 RELATED
Tremco Fire Protection Systems Group Technical Bulletin
Compartmentalization products and design play a key role in protecting lives and property from fire. Understanding the tools and techniques available for firestopping is of utmost importance to designers,
ASTM Volume 04.06, November 2015 Thermal Insulation; Building and Environmental Acoustics
Thermal ; Building and Environmental Acoustics 1 C163-05(2010) Standard Practice for Mixing Thermal Insulating Cement Samples 2 C165-07(2012) Standard Test Method for Measuring Compressive Properties of
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
A. This Section includes rubberized asphalt sheet membrane waterproofing systems.
SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
Georgia State University. Urban Life Building Roof Replacement
ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT
SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
Avoiding Air Barrier Pitfalls
Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great
SECTION XXXXXX TECHNICAL SPECIFICATIONS FOR INSTALLATION OF PROTECTIVE COATINGS FOR MANHOLES, WETWELLS, AND OTHER SANITARY SEWER STRUCTURES
1.00 PART 1 GENERAL 1.01 SCOPE A. It is the intent of this contract to install a 100% solids epoxy monolithic coating to the walls, benches and inverts of all manholes and the specified surfaces of other
SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK
SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. This section covers the pre-finished, pre-fabricated Architectural standing seam roof system. All metal trim,
SECTION 00 0110 TABLE OF CONTENTS. H. 00 2115.01 - Proposed Material, Product or Equipment Substitution Request
SECTION 00 0110 PROCUREMENT AND CONTRACTING REQUIREMENTS 1.1 DIVISION 00 -- PROCUREMENT AND CONTRACTING REQUIREMENTS A. 00 0101 - Project Title Page B. 00 0105 - Certifications Page C. 00 0110 - Table
GreenGuard Housewrap Installation Guide
000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be
foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.
Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12
VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
Composite Panel Firewall Systems
Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.
H-Stud Area Separation Wall System
12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic
CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
The Case for Cross Laminated Timber: Part 2
Learning Objectives The Case for Cross Laminated Timber: Part 2 Opportunities and Challenges for a New Class of Timber Product 1. Review answers to common questions regarding the design and construction
Roof Insulation Building. Energy. Environment friendly e-library
Roof Insulation Building Codes & Energy Efficiency Environment friendly e-library Building Code Driver Buildings consumer almost 50% of all energy. Experts believe that a 30% increase in building efficiency
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
Product Information Sheet
Distributed by Thermal Products Company, Inc. Product Information Sheet FyreWrap Elite 1.5 Duct Insulation Air Distribution System (ADS Ducts) Introduction Unifrax s FyreWrap Elite 1.5 Duct Insulation
Asbestos Abatement Work Plan for the Carter Carburetor Superfund Site
for the Prepared for: ACF Industries LLC 101 Clark Street St. Charles, Missouri 63301 Prepared by: AMEC Environment & Infrastructure, Inc. 15933 Clayton Road, Suite 215 Ballwin, Missouri 63011 Project
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
Terms and Definitions In Canada
Terms and Definitions In Canada Most of the following terms and definitions are taken directly from the National Building Code and referenced Test Methods. Learning these terms will provide an important
Section 03 35 43 Polished Concrete Finishing. Vexcon
SS 120 1-13 Section 03 35 43 Polished Concrete Finishing Specifier Note: This product guide specification is written according to the Construction Specifications Institute (CSI) 3-part format. This section
Colorado State University. Durrell Center Roof Repair
Colorado State University Durrell Center Roof Repair SPECIFICATION: POLYURETHANE FOAM ROOFING l.0 GENERAL REQUIREMENTS The successful application of a polyurethane foam roofing system is dependent upon
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
SECTION 08 5656 GUARDA SECURITY WINDOW SCREENS
Page 1 of 5 SECTION 08 5656 GUARDA SECURITY WINDOW SCREENS Guarda Security Window Screens in this specification are appropriate for use in windows, storefronts, curtain walls, vents, and any other applications
B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
Edition: Export Published: 09/2010. Product catalogue. Technical and industrial insulation. Lapinus
Edition: Export Published: 09/2010 Product catalogue Technical and industrial insulation by by RTI, excellence in fi resafe solutions Rockwool Technical Insulation (RTI) - an independent organisation within
SECTION 07410 METAL ROOF & WALL PANELS
This document specifies Metal Roofing Systems prefinished factory formed metal roofing marketed as MRS System 2500 steel and aluminum roofing systems and includes MRS flashing and Trim. MRS finish is a
Dubai Municipality Standard DMS 1: Part 5: 2004
Specification for precast concrete blocks Part 5: Normal-weight concrete-polystyrene sandwich masonry blocks Issue Date Revision Revision Description Prepared by Approved by Authorized by 19/12/2004 Issue
) and air spaces (R a
5.3.3 Thermal Resistance (R-value) Common thermal properties of materials and air spaces are based on steady state tests, which measure the heat that passes from the warm side to the cool side of the test
s ation lic app ntial Foamular sideor RE uide F Ily G am ation F sul In
Family GUIDE FOR RESIDENTIAL applications Foamular Where quality and performance make a home The OWENS CORNING FOAMULAR XPS INSULATION FAMILY ALBUM is a critical feature of any home impacting overall comfort
DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION
SECTION 230713- ALUMAGUARD ENGINEER SPECIFICATION DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,
Underwriters Laboratories Testing Information
Underwriters Laboratories Testing Information R-8078 Underwriters Laboratories Inc. R-13173 Classified Spray Fiber Surface burning characteristics applied to inorganic reinforced cement board with a maximum
Division 9. SignaFlor Pad and Pour Flooring System
Division 9 SignaFlor Pad and Pour Flooring System SPECIFICATIONS Page 1. General... 2 1.1 Description 2 1.2 Quality Assurance 2 1.3 Submittals 2 1.4 Delivery and Storage 3 1.5 Warranty 3 1.6 Working Conditions
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
SECTION 15190 HVAC INSULATION. A. All work specified in this Section is subject to the provisions of Section 15010.
SECTION 15190 HVAC INSULATION PART ONE - GENERAL PART 1 - GENERAL 1.01 DESCRIPTION A. All work specified in this Section is subject to the provisions of Section 15010. B. All insulation products shall
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct
Continuous Insulation Using Polyiso Wall Sheathing
PIMA Technical Bulletin #403 Continuous Insulation Using Polyiso Wall Sheathing What it is, what it does, and why you need it About Polyiso Insulation Polyiso is a rigid foam insulation used in over 70%
SPREFIX SPRAY INSULATION _ in the marine market.
SPREFIX SPRAY INSULATION _ in the marine market. A self-adhesive glass or stone wool, sprayed directly onto surface.. Easily applied to wood, steel, plastic or other surfaces without any mechanical fasteners
Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature
Thermal Values Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature relative to changing exterior temperatures. By reducing interior temperature
Low-slope reroofing guidelines
Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August
INNOVATIVE. ADAPTABLE. ENERGY EFFICIENT.
INNOVATIVE. ADAPTABLE. ENERGY EFFICIENT. awipanels.com From freezing, sub-zero temperatures to Contents dry heat or high humidity, Mother Nature continually tests the limits of building envelopes. That's
Chapter 3 Pre-Installation, Foundations and Piers
Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC
0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
Analysis II Façade Redesign: Architectural Precast Panels
Analysis II Façade Redesign: Architectural Precast Panels Analysis II Façade Redesign: Architectural Precast Panels Overview: This analysis covers the comparison of the current EIFS façade and my proposed
SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)
SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) PART 1 GENERAL 1.1 DESCRIPTION 1. Fluid applied flexible acrylic waterproofing system over concrete. This work shall include the
How To Repair A Boat Landing Deck With A Boat Bed
RESIDENTIAL INSULATED SHEATHING INSTALLATION GUIDE Residential Insulated Sheathing Installation Guide ROXUL COMFORTBOARD IS Table of Contents Slab-on-grade-to Above Grade Wall...1 Foundation Wall at Footing
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,