RECOATING AND RENEWING SPF ROOFING SYSTEMS
|
|
|
- Grant Haynes
- 10 years ago
- Views:
Transcription
1 RECOATING AND RENEWING SPF ROOFING SYSTEMS Procedures, Regional Differences and type of coating systems Bruce Schenke Premium Spray Products
2 REASONS TO RECOAT/RENEW Add a new coating layer to renew the weathering surface of the SPF system. Allow for maintenance and repair Hail or storm damage repairs Provide for additional durability and longevity Improve the surface reflectivity and aesthetics Obtain new or renewed warranty protection Change the color or aesthetics
3 ECONOMIC ADVANTAGES The owner sustains the their exist SPF system The owner in most cases eliminate the cost of tear off and disposal. The cost of the renewal process is less than a new SPF systems in most cases A recoat of the existing SPF system should yield a new warranty and stronger system than the original system.
4 HISTORY OF RENEWED SPF ROOFING SPF roofing systems were first applied in the early to mid 1960 s The first recoat applications began in the mid to late 1970 s or about years later. There are some SPF roofing systems in place that are now about years old that have been renewed 2-4 times and performing very well and under a manufacturers warranty. There are also some roofs that are years old that have not been recoated and are still performing with no leaks.
5 HISTORY OF RENEWED SPF ROOFING 24 year old SPF System with No Maintenance, No Complaints No Leaks Perfect for Renewal
6 ACCESSING THE EXISTING SPF ROOF SYSTEM SPF Roofs may have some damage and erosion of the coating system due to weathering, storms or mechanical damages
7 ACCESSING THE EXISTING SPF ROOF SYSTEM Good Roofing Practices are applicable to renewing or recoating SPF roofs Clean Dry Sound Meets current code
8 ACCESSING THE EXISTING SPF ROOF SYSTEM AY-121 Spray Polyurethane Foam Estimating Reference Guide AY-102 A Guide for Selection of Elastomeric Protective Coatings Over Sprayed Polyurethane Foam AY-107 Spray Polyurethane Foam Blisters AY-122 The Renewal of Spray Polyurethane Foam and Coating Roof Systems AY-138 Guideline for Roof Assembly Evaluation for Spray Polyurethane Foam Roof System AY-139 Recommendations for Repair of Spray Polyurethane Foam Roof Systems due to Hail and Wind Driven Damage SPFA has developed several technical standards and documents to aid in the renewal or recoating of SPF systems. m.org/technical/spfatechnical-documents
9 ACCESSING THE EXISTING SPF ROOF SYSTEM The existing system must be dry On the surface No leaks No wet insulation, either the SPF or any insulation system under the SPF system.
10 ACCESSING THE EXISTING SPF ROOF SYSTEM The existing system must be dry Infrared or Nuclear Moisture Scans can be done by outside professionals Or done with FLIR cameras by the contractor.
11 ACCESSING THE EXISTING SPF ROOF SYSTEM The existing system must be dry Mark areas verified as wet (over 15% on Tramex or capacitance moisture meters) so that they can be total prior to your bid and torn out and replaced during the renewal process.
12 ACCESSING THE EXISTING SPF ROOF SYSTEM The existing system must be dry Look closely for damages and pinholes that show evidence of water exuding.
13 ACCESSING THE EXISTING SPF ROOF SYSTEM Inspect the roof for surface and coating defects Eroded coatings Exposed degraded SPF
14 ACCESSING THE EXISTING SPF ROOF SYSTEM Inspect the roof for surface and coating defects Mechanical Damages
15 ACCESSING THE EXISTING SPF ROOF SYSTEM Inspect the roof for surface and coating defects Ponding HVAC Condensate leakage
16 ACCESSING THE EXISTING SPF ROOF SYSTEM Inspect the roof for surface and coating defects Hail or wind damage
17 ACCESSING THE EXISTING SPF ROOF SYSTEM Inspect the roof for surface and coating defects Debris Units that can be removed
18 ACCESSING THE EXISTING SPF ROOF SYSTEM Inspect the flashings, expansion joints and drains for damage or need for replacement
19 WHAT TYPE OF COATING OR COVERING IS ON THE EXISTING ROOF? How do you Determine what Coating System is on an existing SPF Roofing System?
20 WHAT TYPE OF COATING OR COVERING IS ON THE EXISTING ROOF? Coating Types Acrylic Silicone Urethane Polyurea Other 1. Does it Chalk? Not to confused with dirt. 2. Does water bead up on it? 3. Is it softer or harder shore hardness? 4. What color is it? Base and Top coats? 5. Resistance to solvents? 6. Owner s records? 7. Slit or core sample cross section? 8. Adhesion? 9. Tensile and elongation? 10.How does it feel? 11.Experience is also a factor.
21 WHAT TYPE OF COATING OR COVERING IS ON THE EXISTING ROOF?
22 WHAT TYPE OF COATING OR COVERING IS ON THE EXISTING ROOF?
23 WHAT TYPE OF COATING OR COVERING IS ON THE EXISTING ROOF?
24 WHAT TYPE OF COATING OR COVERING IS ON THE EXISTING ROOF?
25 A SOUND ROOF SYSTEM Identify any delaminations in the existing roofing system Including a underlying roof system and its attachment to the deck. Document areas to be repaired.
26 A SOUND ROOF SYSTEM Investigate the reasons for the delaminations to help determine the best long term and economic means of repair.
27 A SOUND ROOF SYSTEM Take cores to: Examine how many roofs are in place The adhesion to the deck Interlaminar adhesion Insulation value Coating membrane thickness
28 A CLEAN AND SUITABLE SUBSTRATE For a somewhat worn SPF roof renewal the first step is to pressure wash the surface with clean tap water. This should remove dirt, most contaminants and loose granules. About psi is fine.
29 A CLEAN AND SUITABLE SUBSTRATE Soft mastics used in repairs should be removed. Reverted or poorly cured or peeling coatings must be removed.
30 A CLEAN AND SUITABLE SUBSTRATE Detergents can be used for challenging cases if a thorough rinse is done. Greases and oils by be removed by steam cleaning or scarifying the surface.
31 OTHER POINTS TO EXAMINE Unused Units or Equipment that can be removed Need for additional insulation Chemical Resistance Aesthetics and the Owners color preferences Reflectivity, rebates Term and Warranty Requirements
32 RECOATING/RENEWAL AND CODE System should be tested per ASTM E108 and weathered for 2000 hours. Some indicate minimum reflectivity or SRI ¼ in 12 slope and positive drainage. Comply where applicable, to ASTM coating product standards Roof Coating is not considered an additional roof system.
33 SCARIFYING OPTIONS Some systems may need to be renewed by removing the top layer of coating and SPF and reapplying SPF and a new coating system in whole or in part. Scarify areas or the roof when: The surface is eroded or damaged by storms Much of the surface of the SPF insulation is wet. The coating is reverted or incompatible The SPF is poorly adhered or blistered.
34 SCARIFYING OPTIONS Scarify at least ½ of the existing coating and SPF. Remove any wet insulation. Vacuum and sweep all debris.
35 SCARIFYING OPTIONS Prime the SPF surface per manufacturer s recommendations Spray apply 1 + of new SPF when primer is cured.
36 The first pass over the scarified SPF surface should be about ½ to reduce the exotherm and seal the rough surface. SCARIFYING OPTIONS
37 SCARIFYING OPTIONS
38 SELECTING THE COATING SYSTEM In recoating the new coating should be compatible with the existing or A primer is used to ensure good adhesion.
39 SELECTING THE COATING SYSTEM Acrylic over Acrylic Silicone only over Silicone Acrylic/Silicone over Urethane Urethane over Urethane Coating over Polyurea Others
40 CONSIDERATIONS WHEN SELECTING A COATING The coating systems performance matches The regional climate and weathering The owners aesthetic and performance requirements Your application equipment and experience Special project requirements
41 REPAIRS PRIOR TO COATING Repair of Blisters and Delaminations Ensure that all poor adhesion is addressed.
42 REPAIRS PRIOR TO COATING Remove the delamination to the sound substrate Taper the edges Prime if needed Spray new SPF to near or slightly higher level of the existing roof system
43 REPAIRS PRIOR TO COATING Repairs should be neat and secure Should not apply SPF over silicone coatings Repairs should hinder drainage
44 REPAIRS PRIOR TO COATING Some repairs may need to be ground or shaped prior to the coating application Repairs must have the coating applied the same day as the SPF application
45 REPAIRS PRIOR TO COATING Eroded coating or exposed SPF and rough or pinholed areas can be repaired with a compatible sealant
46 REPAIRS PRIOR TO COATING Small holes, blisters and damages can be repaired with sealant Ensure that the sealant is cured prior to over coating.
47 THE NEW COATING APPLICATION New coating systems can be spray, roller and or brush applied. Rougher surfaces will require more coating to achieve the specified thickness
48 THE NEW COATING APPLICATION Two coats or just one? Coating over granules? Adding granules? Neatness counts
49 THE NEW COATING APPLICATION
50 THE SUSTAINABLE SPF ROOF
51 QUESTIONS
Colorado State University. Durrell Center Roof Repair
Colorado State University Durrell Center Roof Repair SPECIFICATION: POLYURETHANE FOAM ROOFING l.0 GENERAL REQUIREMENTS The successful application of a polyurethane foam roofing system is dependent upon
ALPHA 15-Year Permathane II FR w/granules
ALPHA 15-Year Permathane II FR w/granules Section 07 57 13 Sprayed Polyurethane Foam Roofing Guide Specification PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Furnish all labor, materials, tools and
The Renewal of Spray Polyurethane Foam and Coating Roof Systems
The Renewal of Spray Polyurethane Foam and Coating Roof Systems RECOMMENDED DESIGN CONSIDERATIONS AND GUIDE SPECIFICATIONS Spray Polyurethane Foam Alliance Copyright 1994 - Revised September, 2000 To order
BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION
07560 BUR BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION PART 1: GENERAL 1.01 SCOPE: To extend the useful service life of the aged or new asphalt built-up roof system and to reduce cooling
RECOMMENDATIONS FOR REPAIR OF SPRAY POLYURETHANE FOAM (SPF) ROOF SYSTEMS DUE TO HAIL AND WIND DRIVEN DAMAGE
RECOMMENDATIONS FOR REPAIR OF SPRAY POLYURETHANE FOAM (SPF) ROOF SYSTEMS DUE TO HAIL AND WIND DRIVEN DAMAGE RECOMMENDED DESIGN CONSIDERATIONS AND GUIDE SPECIFICATIONS Spray Polyurethane Foam Alliance Copyright
NEOGARD. Preventive Maintenance Manual
NEOGARD Preventive Maintenance Manual Fluid-Applied Roof Coating Systems December 2014 Notes NEOGARD luid-applied roof coating systems are designed to be long lasting, monolithic membranes which provide
How to repair your existing low slope flat roof.
How to repair your existing low slope flat roof. Recycled Rubber Roofing is not a "Roof Coating." It is a liquid emulsion used as the underlayment of a new or retrofit, built-up roofing system. One of
METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES
METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES REFLECTICLEAN ACRYLIC/URETHANE Elastomeric Roofing Systems, Inc 6900 Bleck Dr. Rockford, MN 55373 800.403.7747 -or- 763.565.6900 fax: 763.565.6901 email:
Crescent Valley High School Roof Investigation
Crescent Valley High School Roof Investigation Project: Corvallis School District Crescent Valley High School Roof Date: July 26, 2011 Report By: Rowell Brokaw Architects: Mark Young, AIA, Chris Andrejko
SWD URETHANE COATED FOAM ROOFING SYSTEM MASTER ROOF SPECIFICATION SECTION 075700
SWD URETHANE COATED FOAM ROOFING SYSTEM MASTER ROOF SPECIFICATION SECTION 075700 Part 1 GENERAL SUMMARY Section Includes: Coated foam roofing system and acceptable alternative applications as specified
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
A. This Section includes rubberized asphalt sheet membrane waterproofing systems.
SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
Specifying SPF Roofing Systems
Specifying SPF Roofing Systems Spray polyurethane foam (SPF) roofing systems have been marketed for years primarily on their documented energy saving characteristics. Consequently much of the SPF roofing
SECTION 07 57 16 CEMENTITIOUS COATED FOAMED ROOFING
SECTION 07 57 16 CEMENTITIOUS COATED FOAMED ROOFING PART 1 GENERAL 1.01 SUBMITTALS A. Product Data: Submit manufacturer's literature and technical data (specifications, installation instructions and evidence
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC
FEFPA 2015 SUMMER CONFERENCE. Energy Effectiveness through Roof Coatings and Solar
FEFPA 2015 SUMMER CONFERENCE Energy Effectiveness through Roof Coatings and Solar Welcome Danny G. Daniel Stokes, CSI, CDT, RCI, CPRC Vice President Advanced Roofing Inc. About Danny Stokes Vide President
WATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
Commercial Roof Inspection Form
Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building
SECTION 623 CONCRETE BONDING COMPOUND, EPOXY MORTAR AND EPOXY POLYMER CONCRETE OVERLAY SECTION 623.10 CONCRETE BONDING COMPOUND.
SECTION 623 CONCRETE BONDING COMPOUND, EPOXY MORTAR AND EPOXY POLYMER CONCRETE OVERLAY SECTION 623.10 CONCRETE BONDING COMPOUND. 623.10.1 Description. This work shall consist of preparing the surface,
Reroof or Restore? The right decision can save weeks of time and thousands of dollars
APOC A DIVISION OF GARDNER - GIBSON 5903 Paramount Boulevard Long Beach, California 90805 Telephone (800) 562-5669 Fax (562) 423-9597 www.apoc.com THE FOLLOWING TECHNICAL ARTICLE WAS PUBLISHED IN A MAJOR
SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.
SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied
Low-slope reroofing guidelines
Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August
Building Owners Guide to a Duro-Last System!
Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof
METHOD STATEMENT 006 TORCH APPLIED MEMBRANE TO BASEMENT WALLS
This Document is designed to cover best practice installation procedures for a one layer torch applied sheet membrane system to basement walls. PRELIMINARY WORK Ensure that all surface preparation work,
BLACK JACK ALL WEATHER ROOF COATING
PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.
ROOF INSPECTION & MAINTENANCE
Physical Plant Administration Facilities Maintenance Department ROOF INSPECTION & MAINTENANCE All roofs require periodic inspection and maintenance in order to perform as designed and to provide a long
REROOFING - SCOPE OF WORK
REROOFING - SCOPE OF WORK 1.0 GENERAL A. Summary of work: 1. Information herein is provided as a general overview of the project scope, and as such, does not grant authority for deviation from the manufacturers
Commercial Roof Management
Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading
Super Roof. Coating Gives Superdome a Bright New Look. february 2015. By Jon Henson and Kim Bistromowitz Quest Construction Products
february 2015 The Premier Magazine for Commercial and Residential Roofing & Insulation As Also Seen In Building Envelope Magazine! Super Roof Coating Gives Superdome a Bright New Look By Jon Henson and
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Introduction Wastewater of petrochemical industries and refineries contains high amounts of emulsified aliphatic or
SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)
SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) PART 1 GENERAL 1.1 DESCRIPTION 1. Fluid applied flexible acrylic waterproofing system over concrete. This work shall include the
Bituminous Sheet Flat Roofs: Their repair and maintenance
Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and
3M Scotchkote Urethane Coating 165HB
3M Scotchkote Urethane Coating 165HB Product Description 3M Scotchkote Urethane Coating 165HB is a two component 100% solids urethane coating used for the internal and external protection of steel and
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center
PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 5423 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center A. Tear off existing roof system down to wood deck and install new Thermoplastic membrane roofing
INDUSTRIAL FLOORING INSTALLATION CHALLENGES. James C. Ziegler, ArmorSeal Product Manager Sherwin Williams Cincinnati, Ohio, USA
INDUSTRIAL FLOORING INSTALLATION CHALLENGES James C. Ziegler, ArmorSeal Product Manager Sherwin Williams Cincinnati, Ohio, USA Abstract: Specifier's and contractors not only need to properly evaluate the
SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.
SECTION 07530 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section includes the flowing: 1. Removal of existing roofing membrane. Existing bur roof has one overlay and penetration mastic is asbestos containing.
MODULAR EPDM ROOFING SYSTEMS
MODULAR EPDM ROOFING SYSTEMS INSPECTION, REPAIR & MAINTENANCE HANDBOOK Now that you ve selected one of the best roofing systems available today, please take the time to read through this handbook carefully
THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS
OPTIONAL TITLE 24 CRITICAL POINTS POLYISO THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE DESCRIPTION TORCH OVER POLYISO (5,7,9 YR) TH/BS-TH/CS 2 No 0. SUBSTRATE. THERMOTEK USA PRO 2.0 FV
Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS
AC TOPSEAL SELF-ADHERED, GRANULAR SURFACED, SINGLE PLY, LOW SLOPE ROLLED ROOFING 3 X 33.3 = 100 SQ. FT. 10 YEAR MATERIAL LIMITED WARRANTY For Use on Porches / Sheds / Utility Buildings / Accessory Buildings
Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.
Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that
COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE
www.epdmroofs.org COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE By Ric Vitiello President Forensic Roof Consulting and Hail Damage Assessment Training www.benchmark-services.com
Maintenance & repair Solutions
Maintenance & repair Solutions low-slope ROOFING We ve got what you need in the sizes you need them and the options to match the results that building owners want Seal-fast Temporary roof sealer Now you
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
CARLISLE OWNER S MANUAL
Investing in Solutions for Over 45 Years For over 45 years Carlisle Construction Materials Incorporated (CCM) has been creating solutions for the construction industry. Beginning with single-ply roofing
Aerial Infrared Roof Moisture Surveys
Aerial Infrared Roof Moisture Surveys INTRODUCTION IR P/PM (infrared predictive/preventive maintenance) is not limited to annual infrared surveys of electrical switchgear. For instance, infrared thermography
Roof Systems Overview
Roof Systems Overview Cold Applied Built-Up Roofing Systems BURmastic Tremco s line of cold applied built-up roofing systems. BURmastic 200 Combines Tremco s expertise in asphalt blending technology with
CREEK Technical Services, LLC
EVALUATION REPORT 2010 FLORIDA BUILDING CODE Manufacturer: Henry Company Report Issued February 20, 2013 999 North Sepulveda Blvd., Suite 800 El Segundo, CA 90245 (800) 486-1278 Manufacturing Plants: Quality
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!
Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing
Maintaining YOUR TILE ROOF
Maintaining YOUR TILE ROOF TABLE OF CONTENTS Maintaining Your Tile Roof 2 Walking on Your Tile Roof 2 Replacing Broken Tiles 3 Mildew, Algae and Moss 4 Cleaning, Re-Coating & Painting 4 Efflorescence 5
THERMOTEK SELF ADHESIVE MEMBRANE +G2 OVER WOOD SYSTEM DESCRIPTION SELF ADHESIVE OVER WOOD (8YR) BS-SA/CS
THERMOTEK SELF ADHESIVE MEMBRANE +G OVER DESCRIPTION SELF ADHESIVE OVER (8YR) BS-SA/CS 1 0 No 0. SUBSTRATE 1. BASE SHEET G FIBER GLASS BASE. THERMOTEK SELF ADHESIVE 3.0 FP GRANULE COMPONENTS AND WEIGHTS
Avoiding Air Barrier Pitfalls
Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great
THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER
THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER DESCRIPTION TORCH OVER (15,17,19 YR) TH/BS-TH/CS 2 1 0 No 0. SUBSTRATE 1. THERMOTEK USA 2.0 FV TORCH SMOOTH 2. THERMOTEK USA PRO FP TORCH GRANULE COMPONENTS
PAINTING OVER HOT DIP GALVANIZED STEEL
PAINTING OVER HOT DIP GALVANIZED STEEL Thomas J. Langill, Ph.D., Technical Director American Galvanizers Association 12200 E. Iliff Ave. Suite 204 Aurora, CO 80014 Abstract: Duplex systems, also known
Please read the entire document before purchasing and installing any of these products
Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection
TARRANT COUNTY DETAIL STANDARDS
TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout
GUIDELINE SPECIFICATIONS
GUIDELINE SPECIFICATIONS GORDON SOFFIT-SHIELD - An Exterior Metal Soffit System DIVISION 05 5800 or DIVISION 07 7700 Note To Specifier: SOFFIT-SHIELD should be installed by tradesmen that are experienced
Roofing Repairs 07511-1
SECTION 07511 ROOF AND FLASHING RESTORATION WITH TITLE 24 / COOL ROOF SURFACING PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including General and Supplementary
Solicitation DTFACN-11-R-00079 Attachment #9
These specs are only a general overview of the typical VOR Roof construction. These are for reference only. Each individual project will have its own specifications. 1 VOR Roof Projects IDIQ Solicitation
The Perfect Fit For Metal Retrofit
D u r o - S h i e l d M e t a l R e t r o f i t R o o f i n g S y s t e m The Perfect Fit For Metal Retrofit Lock out leaks. Lock in your investment. Has time caught up with your metal roof? There are
FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS
FLAT ROOF REPAIR CUT COST WITHOUT CUTTING CORNERS Table of Contents Chapter 1: FLAT ROOF REPAIR - CUT COST WITHOUT CUTTING CORNERS Chapter 2: PVC RECOVER SYSTEM HOW IT WORKS Chapter 3: 8 STRATEGIES TO
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
Roof Condition Report. Academy International School 8550 Charity Drive. Colorado Springs, Colorado
Roof Condition Report Academy International School 8550 Charity Drive Colorado Springs, Colorado FOR Mr. Robert Thompson Academy School District 20 10221 Lexington Drive Colorado Springs, Colorado July
HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS
BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side
SEAMS SEAMING USING SEAM TAPE
SEAMING USING SEAM TAPE SEAMS The membrane should be positioned so that the width of the seam is 3. Remove excess chalk from a chalk line by snapping the line into the air and then chalk a line one-quarter
738-B-297 POLYMERIC CONCRETE BRIDGE DECK OVERLAY. (Adopted 02-20-14)
POLYMERIC CONCRETE BRIDGE DECK OVERLAY (Adopted 02-20-14) Description The polymeric concrete bridge deck overlay shall consist of an epoxy polymer that acts together with special aggregate to form an overlay
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System
EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES
Building and Construction Industry A joint industry initiative produced by BSA Supershow logo.indd 1 30/01/2008 9:43:29 AM EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES FAILING WATERPROOFING
SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING
SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING PART ONE GENERAL DESCRIPTION This section includes pre-formed standing seam metal roofing and related flashings, closures, trim and accessories including,
Rehabilitation of an Aging Concrete Reservoir Adit Tower
Rehabilitation of an Aging Concrete Reservoir Adit Tower Raymond S. Tombaugh, Senior Coatings Consultant KTA-Tator, Inc. and Mongkol Mahavongtrakul, P.E. Corrosion Control Contract Manager San Francisco
Get Rid of Roof Problems for Good. How spray foam roofing can protect your building and make you money
Get Rid of Roof Problems for Good How spray foam roofing can protect your building and make you money What is a Spray Foam Roofing System? 300 MILLION Board feet of roofing spray foam installed annually
Note: Minor color change may occur in exposed service, but corrosion protection will not be compromised
DESCRIPTION One component, high-build heat-resistant inert multipolymeric matrix coating to prevent corrosion under insulation (CUI) of carbon and stainless steel to temperatures ranging up to 650 C (1200
WATERPROOFING OF WET ROOMS
WATERPROOFING OF WET ROOMS Waterproofing under tiles For longterm enjoyment of a wetroom area a complete and resistant waterproofing system is an important precondition. Most tiles are by themselves waterproof
IS800 Series. Technical Data Sheet IS802, IS803, IS808, IS800.09. Description. Key Features and Benefits. Typical Physical Properties
1810.html Technical Data Sheet IS800 Series IS802, IS803, IS808, IS800.09 Description IS802, IS803, IS808 and IS800.09 one-component, ready-to-use silicone adhesive sealants have a paste-like consistency
Finegan Inspection Services, Inc.
Finegan Inspection Services, Inc. Report Prepared For: Phone 513-683-0733 Fa 513-697-0163 Owners Property Address City, State, ZIP Phone FAX Owners Realtor Realty Company Phone FAX OWNER INFORMATION PROPERTY
SECTION 32 1816 PLAYGROUND SURFACING TILES
SECTION 32 1816 PLAYGROUND SURFACING TILES PART 1 GENERAL 1.01 SECTION INCLUDES A. Resilient playground safety surfacing tiles. B. Coordinate with work shown in other sections so the work is installed
SECTION 03 35 43 POLISHED CONCRETE FINISHING
SECTION 03 35 43 POLISHED CONCRETE FINISHING PART 1 - GENERAL 1.01 SUMMARY A. Provide polished concrete finishing system where indicated on drawings, complete. This section includes the following: 1. Concrete
A. Work on this project shall consist of, but is not limited to, the following:
PART 1 - GENERAL CLEANING AND RESTORATION OF SECTION 05900-1 1.1 SUMMARY A. Work on this project shall consist of, but is not limited to, the following: 1. Clean and treat all exposed anodized architectural
FIRESTOPPING & SMOKE SEALS
SPECIFICATION SECTION 07 84 00 FIRESTOPPING & SMOKE SEALS 1 GENERAL 1.1 SECTION INCLUDES 1.1.1 Comply with Division 1, General Requirements and Documents referred to therein. 1.1.2 It is the intent of
Maintenance & Inspection Guide
ADDRESSING THE NEEDS OF OUR CUSTOMERS AND THE ENVIRONMENT ONE high Performance roofing SOLUTION AT A TIME. Maintenance & Inspection Guide TABLE OF CONTENTS Topic: Page: I. Introduction 1 II. Maintenance
Construction. Sikalastic -560 Economical and eco-friendly liquid applied roof waterproofing solution. Product Description.
Product Data Sheet Edition 02, 2015 Version no. 12.2014 Sikalastic -560 Economical and eco-friendly liquid applied roof waterproofing solution Product Description Sikalastic -560 is a cold-applied, one-component
CHAPTER 6 ASPHALT ROLL ROOFING
CHAPTER 6 ASPHALT ROLL ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 6.1.1 General 6.1.3 Mineral-Surfaced Asphalt roll roofing is roofing in sheet form Mineral-surfaced roll roofing is composed
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
A. Roofing Terminology: Definitions in ASTM D 1079 and glossary in NRCA's "The NRCA Roofing and Waterproofing Manual" apply to work of this Section.
SECTION 075419 POLYVINYL CHLORIDE (PVC) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION
SECTION 230713- ALUMAGUARD ENGINEER SPECIFICATION DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,
EPDM System Repair and Cleaning
EPDM single-ply roof systems have represented a third of the volume of the low-sloped commercial market for close to twenty years. The majority of these roofs were installed to receive the manufacturer
Division 9. SignaFlor Pad and Pour Flooring System
Division 9 SignaFlor Pad and Pour Flooring System SPECIFICATIONS Page 1. General... 2 1.1 Description 2 1.2 Quality Assurance 2 1.3 Submittals 2 1.4 Delivery and Storage 3 1.5 Warranty 3 1.6 Working Conditions
Roofing 101 - Signs that Your Roof Needs Repair/Replacement
By: Cherie Martel Roofing 101 - Signs that Your Roof Needs Repair/Replacement 1. Tell us a little bit about your company and its foundation. In 1963, Samuel T. Martel began a small family run roofing company,
Peel & Seal Self-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
ARDEX GUIDE SPECIFICATION ARDEX Exterior Concrete Repair & Resurfacing Polymer-Modified, Cement-Based, Patch & Horizontal Overlay Materials
ARDEX GUIDE SPECIFICATION ARDEX Exterior Concrete Repair & Resurfacing Polymer-Modified, Cement-Based, Patch & Horizontal Overlay Materials SECTION 03 92 50 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings,
RTV159. RTV157 and RTV159 High Strength Silicone Adhesive Sealants
RTV159 RTV157 and RTV159 High Strength Silicone Adhesive Sealants Product Description RTV157 and RTV159 are one-component, ready-to-use, high strength silicone rubber adhesive sealants. They cure to tough
Winterizing Your Building
Winterizing Your Building DEC Author: Steven J. Susca This article was originally published in the Hoffmann Architects Journal in Issue 3, 2009. As spring thaws uncover the ravages winter weather has wreaked
Epoxy Floor Coating Problem Solving Guide
Table of Contents: Page: Troubleshooting Issue: 2. Color Differential 3. Fish Eye 4. Milky or Cloudy Coatings 5. Orange Peel 6. Peeling or Delamination 8. Delamination between Coats 9. Pinholes/Bubbling
Stucco Repair and Maintenance No. 1.01
Tel: 404 346-3666 Toll Free: 800 221-2397 Fax: 404 346-3119 Stucco Repair and Maintenance No. 1.01 These stucco repair and maintenance techniques are intended as a partial guide to repair of stucco walls.