CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS
|
|
|
- Henry Black
- 10 years ago
- Views:
Transcription
1 TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes the DGS Procedure Manual for Professional Services dated July Please recycle the superseded document. 1 GENERAL 1.1 FOR NEW BUILDING PROJECTS, the selection of either a steep slope or low slope roofing system shall be based on the results of a 60 year life cycle cost analysis. This analysis shall consider the scope impact on building structural, mechanical and electrical systems required to configure the building for a steep slope and a low slope roofing system, as well as the maintenance and replacement intervals and costs for both roofing systems. 1.2 FOR ROOF REPLACEMENT PROJECTS, the selection of the replacement roofing system shall be based on an evaluation of costs associated with factors affecting the proposed system, including span dimension, structural condition, foundation design/capacity, and disposition or accommodation of roof top equipment. 1.3 ROOFS ON NEW CONSTRUCTION shall be pitched to drains or gutters, with the roof slope achieved structurally. 1.4 REFERENCES TO NATIONAL STANDARDS DOCUMENTS such as the American Society for Testing Materials (ASTM), American National Standards Institute (ANSI), Factory Mutual System (FM), Underwriters' Laboratories (UL), International Building Code (IBC), American Institute of Steel Construction Manual (AISC), Sheet Metal and Air Conditioning Contractors National Association, Inc. (SMACNA), National Roofing Contractors Association (NRCA), National Institute of Standards and Technology (NIST), Asphalt Roofing Manufacturers= Association (ARMA), etc., shall be interpreted to refer to the most current edition or revision in effect at the time a design is in progress as this takes precedence. 1.5 ALL MATERIALS used for roofing systems shall be asbestos free. 1.6 A SITE VISIT to verify existing conditions will be made for all roof replacement and roof repair projects to verify existing conditions and dimensions even though as-built drawings are VII-1
2 provided. Where composition, thickness or make up of the existing roof system or any of its components cannot be determined by visual means alone, an exploratory investigation shall be conducted to include dismantling or opening up a representative portion of the roof system. Patch and make watertight all areas disturbed during investigation. 2 STEEP SLOPE ROOFS 2.1 STEEP SLOPE ROOFS with a minimum slope of 2-1/2 inches per foot, may be finished with a standing seam metal or sheet metal system or a fiberglass shingle system surfaced with ceramic coated mineral aggregate. All steep slope roofs must have a full width (36") of modified bitumen ice dam protection membrane installed at all eaves and valleys. 2.2 STANDING SEAM METAL ROOFING SYSTEMS shall be fabricated metal panel systems from nominal 22 gauge G-90 galvanized steel conforming to ASTM A446 Grade A and ASTM A525. Alternative panel thickness of 24 gauge or 20 gauge may be considered based on an evaluation of roof framing and purlin spacing. All standing seams shall be double locked with a seam height no greater than 12 inches. The system shall conform to the requirements of ANSI Publication A 58.1, the IBC Chapter 15, and the American Institute of Steel Construction Manual. The panels shall have a UL Class 120 rating and the structural uniform uplift load capacity shall be in accordance with ASTM E330. The finish shall be equal to at least 70% Kynar and shall be tested in accordance with ASTM procedures. The system shall have a 20 year manufacturer's weatherproof warranty. The Kynar color finish shall also be covered by a 20 year manufacturer's warranty. 2.3 ASPHALT SHINGLES shall be reinforced with fiberglass wind resistant type, UL Class A, and comply with ASTM D3462 and ICBO ES AC 127. Shingle manufacturer shall provide a 40 (+) year warranty (minimum) covering repair or replacement of defective shingles as necessary to eliminate leaks. Ventilation must be accounted for, per shingle manufacturers recommendations. Metal drip edges must be installed on all eave and rake edges. VII-2
3 2.4 SPECIAL ROOFS: Under special conditions relating to aesthetic compatibility with surrounding buildings or historical consideration, the use of clay tiles, slate tiles, or cedar shakes may be deemed appropriate. In these cases specifications and details shall be developed in strict accordance with applicable national standards. The roofing tile or slate manufacturer/quarrier shall provide material defects warranty coverage of 20 years minimum to 50 years or more based on the specific roof material and facility under consideration. 2.5 STEEP SLOPE ROOFS shall be provided with adequate means for interior ventilation through eave or soffit louvers, ridge vents, ventilation boards and thermostatically controlled power fans to prevent moisture condensation and excessive heat under roofing or sheathing. Insulation shall be provided in the attic space above the ceiling and shall achieve an insulation value of R LOW SLOPE ROOFS 3.1 LOW SLOPE ROOFS shall be required to have a minimum slope of 1/4 inch per foot. New buildings shall be designed to achieve the minimum slope of 1/4 inch per foot structurally. Existing buildings may have to be provided with tapered insulation to achieve the minimum slope. Lightweight concrete shall not be used to create slope. 3.2 PRIOR TO PLACEMENT OF INSULATION and the roofing system, all low slope roof decks shall have: A. Steel Deck: 1" perlite insulation mechanically fastened and 2 plies of fiberglass felts. B. Concrete Deck: Asphaltic primer and 2 plies of fiberglass felts. C. Nailable Decks: (other than Wood, Lightweight Concrete, Gypsum, and Tectum) Rosin-sized sheathing paper, 75 lb. ventilated base sheet, mechanical fasteners dictated by deck type, and 2 plies of fiberglass felts. D. Wood Decks: Mechanically fasten 1" thick perlite insulation to deck and install 2 plies of fiberglass felts with hot asphalt. VII-3
4 (1) If wood deck is less than 3/4" thick, nail base sheet to deck and install 2 plies of fiberglass felt over base sheet. 3.3 ON LOW SLOPE ROOFS from 1/4 inch per foot to 2-1/2 inches per foot all felt plies shall be back-nailed on slopes greater than 2 inches per foot and the following roofing system shall be used: A. Four Ply Built-up System: The system consists of four plies of roofing felts alternately placed, overlapped and saturated with hot asphalt bitumen. Gravel surfacing to be set in hot asphalt. Roofing felts shall be glass fiber and meet the requirements of Tables 1 and 2 ASTM D-2178 Type VI (Asphalt Impregnated). Steep roofing asphalt shall conform to ASTM D-312, Type III. B. Single-Ply Membranes: Thermoplastic Polyolefin (TPO) membrane roof assemblies are acceptable, as long as long as all warranty requirements listed in 3.3C are met. All other single-ply membranes, as well as vegetative ( green ) roof assemblies, will be considered in some circumstances. C. Warranty: The roofing system shall be covered by a 20 year Total System, No Dollar Limit (NDL) Warranty and must include all flashings and sheet-metal work. All materials and workmanship are to be fully guaranteed by the roofing manufacturer issuing the warranty. All materials must be manufactured by the manufacturer who is to supply the warranty. Any materials that are not made by the Roofing Materials Manufacturer but submitted for approval must be accompanied by a letter from the Roofing Materials Manufacturer issuing the 20 year NDL warranty, stating that this material is suitable for use with their system and fully covered under their 20 year NDL warranty. 4 INSULATION 4.1 ALL LOW SLOPE ROOFING SYSTEMS shall include insulation. The majority of insulating value shall be accomplished with the necessary thickness of flat poly-isocyanurate boards. Where necessary, roof slope shall be developed with tapered perlite or tapered poly-isocyanurate board. Organic insulation material shall VII-4
5 not be used under built-up roofs. Light weight concrete insulating fill is not acceptable. In all cases a minimum 1/2" cover board must be installed over the Isocyanurate insulation. Perlite and Densdeck are acceptable cover board materials. 4.2 HEAT TRANSMISSION: Insulation heat transmission values shall be established in accordance with the Energy Conservation Guidelines, Chapter V and Code Update of 2015 DGS Procedure Manual. For new buildings the suggested insulation value of the roof area envelope is R-30CI(Cont.Insul) for low slope roofs. For roof replacements/renovations on older buildings, a lower "R" value will be considered. 4.3 STRUCTURAL: The first ply of insulation systems over metal decks and wood decks shall be mechanically fastened using steel fasteners acceptable to the manufacturer furnishing guarantee of roofing system. Insulation shall also be installed in accordance with Factory Mutual System Class 120 wind uplift guidelines. 4.4 INSULATION shall be applied in several layers, with the joints staggered, in accordance with the manufacturer's recommendation. 4.5 COMPATIBILITY: Insulation material installed between the roof deck and the roof ply shall be compatible with the roof ply material and asphalt bitumen binder or other adhesive used in the roofing system. 4.6 WARRANTY: Insulation materials shall be considered an integral component of the roofing system, and shall be furnished or approved by the roofing system manufacturer, and shall be covered fully by the roofing system warranty. 5 FLASHING 5.1 BASE FLASHING is part of the roofing system and shall meet requirements of manufacturer furnishing roofing system. Where roof meets a parapet or adjacent building wall, the base flashing shall extend up the wall at least 8 inches, but generally not more than 14 inches unless necessary to be consistent with existing conditions or design requirements. If flashing height is greater than 14 inches, a 2 piece flashing system may be required. 5.2 OTHER FLASHING: Other than base flashing - metal flashing, including expansion joint flashing, shall be in accordance with Roofs. VII-5
6 SMACNA Standards and the NRCA Roofing and Waterproofing Manual and fully covered under the 20 year NDL warranty. 5.3 PITCH POCKETS SHALL BE AVOIDED. Where that is not possible, pitch pockets shall be filled with a pourable urethane sealer. Roof penetrations will be flashed with preformed flexible flashing, using clamps and tents, unless the penetration is such a complex shape that a pitch pocket is required. 5.4 ALL PARAPET WALLS must be covered with a metal coping cap over a peel and stick type modified bitumen membrane and any necessary wood blocking/nailers, etc. 6 ROOF DRAINS 6.1 ROOF DRAINS shall be provided with shallow sumps, gravel stops, and minimum 4.0 pound lead flashing in accordance with the NRCA Roofing and Waterproofing Manual and the International Plumbing Code. 6.2 ROOF DRAINS shall be located wherever possible at the low points, and crickets must be provided between drains in structurally formed valleys and around any structure impeding the flow of water in the drain field to assure positive water flow to the drains. 6.3 ROOF DRAINAGE PATTERNS should be designed to locate roof drains at the mid-points between columns and beams. Overflow scuppers should be provided through perimeter parapet walls, or overflow relief drains should be provided at roof drain locations, to relieve storm water build-up caused by clogged roof drains. 6.4 ROOF DRAINAGE that is directed to exterior downspouts, splash blocks shall be provided at all ground discharge points. Where possible, downspouts may discharge directly into a storm drainage system. 7 ROOF ACCESS 7.1 PERMANENT ACCESS to all roof areas from the inside of the building shall be provided (with a roof hatch and a ship type ladder)for all buildings over two stories high with low slope roofs. VII-6
7 7.2 ROOF ACCESS for one and two story buildings with low slope roofs and for buildings with steep slope roofs will be evaluated based on building and roof configuration and roof type. 7.3 EXTERIOR ACCESS must be provided for all multi-level roofs from the second story up. 8 ROOF MOUNTED EQUIPMENT 8.1 ROOF MOUNTED EQUIPMENT shall be minimized; penthouse enclosures of equipment are preferred. 8.2 ROOF MOUNTED EQUIPMENT shall be installed on curbs and provided with suitable vibration isolation devices and proper flashing. 8.3 IF IT IS NECESSARY TO MOUNT EQUIPMENT ABOVE THE ROOF, without using a curb, sufficient clearance shall be provided under the equipment to permit maintenance of the roofing system, as well as adequate clearance for future roof replacement. 8.3 EQUIPMENT SCREENS must be provided to conceal all roof top equipment. 8.4 INORGANIC WALKING PADS shall be provided from roof access to roof mounted equipment. Modified bitumen membrane is acceptable. 9 CONTRACTOR S GUARANTEE 9.1 THE CONTRACTOR must have at least 5 years experience installing the type of roofing they are bidding on. 9.2 THE CONTRACTOR must be a NDL certified roofing system installer for at least 5 years continuously (currently), and must provide to the State a current letter from a roofing materials manufacturer stating this and that their workmanship, including flashings and sheet-metal work, will be fully covered by the Manufacturers= 20 year >NDL= warranty without exception. 9.3 THE CONTRACTOR must also provide the State with a minimum 2 year workmanship guarantee. VII-7
8 10 GREEN ROOFING SYSTEMS (see section 3.3B) 10.1 GREEN ROOFING SYSTEMS shall comply with the requirements of 2015 International Building Code (IBC), Chapters 15 and 16, and High Performance Green Building Program of 2015 DGS Procedure Manual. All systems must comply with ANSI/SPRI VF-1 and current ANSI wind design guidelines INTENSIVE GREEN ROOFS shall be designed for uniform design live load in the landscaped area as indicated in section of IBC The weight of the landscaping materials shall be considered as dead load and shall be computed on the basis of saturation of the soil EXTENSIVE GREEN ROOFS shall be designed for a minimum uniform live load of 100 psf as per Table of IBC THERMO PLASTIC SINGLE PLY ROOFING shall comply with Chapter 15 of the IBC and shall have a minimum slope of 1/4" + 1'-0" (2%). The roof covering shall comply with ASTM D6878. VII-8
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
TARRANT COUNTY DETAIL STANDARDS
TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design
Basis of Design This section applies to roofing membranes, flashing and accessories. Design Criteria Adhere to the standards and details of the latest editions of the National Contractors Association (NRCA)
APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET
Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
NRCA s steep-slope manual is thoroughly revised for 2013
Photo courtesy of Boone Brothers Roofing, Omaha, Neb. NRCA s steep-slope manual is thoroughly revised for 2013 by Maciek Rupar 38 www.professionalroofing.net MARCH 2013 P ublished in January, The NRCA
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)
ROOF ASSEMBLIES CHAPTER 9
CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION
Smooth cap sheet - 0-10 SQ $ 139.00. Smooth cap sheet - 11-50 SQ $ 63.00. Smooth cap sheet - 51-100 SQ $ 36.00 Smooth cap sheet - 101-200 SQ $ 36.
Demolition/Removal of Work 4-ply built up roofing to the insulation (smooth cap sheet) Smooth cap sheet - 0-10 SQ $ 63.00 Smooth cap sheet - 11-50 SQ $ 63.00 Smooth cap sheet - 51-100 SQ $ 35.00 Smooth
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS
Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
SECTION 07400 STANDING SEAM METAL ROOF
SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and
SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.
SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied
THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING
DIVISION 7 THERMAL AND MOISTURE PROTECTION 07100. WATERPROOFING 07110. MEMBRANE WATERPROOFING: The following are minimum requirements to assure adequately designed waterproofed floors for machine and equipment
Please read the entire document before purchasing and installing any of these products
Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection
ROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof
ROOF CONSTRUCTION The overall appearance of a building is greatly affected by the roof lines and the roofing materials. The designer has many standard designs to choose from and should be able to find
Low-slope reroofing guidelines
Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August
!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!
Table of Contents Section 1: Most Common Types of Flat Roofing Section 2: Better Understand Your Flat Roof Section 3: Flat Roofing Cost in 2015: Four Factors that Dictate Section 4: Planning A Flat Roofing
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
If you are a web registered user of ArlingontPermits.com you may also request an inspection at:
TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors
SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.
SECTION 07530 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section includes the flowing: 1. Removal of existing roofing membrane. Existing bur roof has one overlay and penetration mastic is asbestos containing.
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and
metal Duil~ing manufacturers Association
metal Duil~ing manufacturers Association ApplicatiDns metal Building Systems Conventional Buildings Retrofit Roofing Projects l~e Perfect Cover.One of the most important technological advances in building
16 2 10.3 Materials and Colors
16 2 10.3 Materials and Colors To create a harmonious and coherent image for each development, building designs shall pay close attention to choice of materials and colors. Building construction shall
COMMERCIAL ROOFING. Learning Objectives. Commercial Roofing Fundamentals May 2, 2012
COMMERCIAL ROOFING The Fundamentals Firestone Building Products is a Registered Provider with the American Institute of Architects Continuing Education Systems. Credit earned on completion of this program
DIVISION 7 - THERMAL AND MOISTURE PROTECTION
DIVISION 7 - THERMAL AND MOISTURE PROTECTION Note: This is a guide for Designers only. Contents shall not be used in lieu of specifications as part of the Designer s Contract Documents. SECTION 07 1000
TABLE OF CONTENTS" SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE 7"
2 TABLE OF CONTENTS SECTION 1: What is a Standing Seam Metal Roof PAGE 3 SECTION 2: Common Types of Standing Seam Metal Roofs..PAGE 5 SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and
SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING
SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING PART ONE GENERAL DESCRIPTION This section includes pre-formed standing seam metal roofing and related flashings, closures, trim and accessories including,
Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
Roof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, 2014. RBA Project No. 2014007.00.
Report Fairbank Complex 40 Fairbank Road RBA Project No. 2014007.00 Prepared by: 33 Center Street, 2 nd Floor Burlington, MA Tel: 781-273-1537 Fax: 781-273-1695 TABLE OF CONTENTS Roof Repair Project Report...
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and
Standing Seam Roof Systems
Standing Seam Roof Systems REAL PEOPLE. REAL PRODUCTS. REAL SOLUTIONS. www.a-s.com Building Benefits You Can Expect From A&S Materials Standing Seam roof panels weigh a relatively modest 11/2 pounds per
Durapax Coal Tar BUR Application Guide
400 Old Reading Pike, Suite 304 Pottstown, PA 19464 Tel: 610-579-9075 Fax: 610-323-0115 www.durapax.com Durapax Coal Tar BUR Application Guide DESIGN CONSIDERATIONS The proper specifications of any roof
Detached accessory structures that contain no conditioned floor area are exempt.
RESIDENTIAL ROOFING PERMITS: A roofing permit is required for roofing of residential dwellings and garages in accordance with Section R105 of the International Residential Code. Updated 11/2013 City of
Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010
Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010 Custom bid generated for: Job site address: Lake Villas Condominium Attention:
Roofing Systems. New Applications / Re-Roofing / Maintenance
Roofing Systems New Applications / Re-Roofing / Maintenance New Roof Installation In terms of the design and installation of an original roofing system (in conjunction with the construction of a new building),
SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK
SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. This section covers the pre-finished, pre-fabricated Architectural standing seam roof system. All metal trim,
780 CMR 15.00 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
780 CMR 15.00 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES 780 CMR 1501.0 GENERAL 1501.1 Scope. The provisions of 780 CMR 15.00 shall govern the design, materials, construction and quality of roof assemblies,
HERITAGE WOODGATE LAMINATED ASPHALT SHINGLES Dallas, TX
Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING
FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association
FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING Roofing Manufacturers Association Why is a built-up roof considered a multi-ply roof? ARMA defines a built-up roofing system as a roof where multiple
PETERSONS WATERFRONT CONDOMINIUMS
CONSULT DESIGN CONSTRUCT PETERSONS WATERFRONT CONDOMINIUMS 103 Park Street Chelan, Washington Findings Summary Report Prepared for: Petersons Waterfront Condominium Association March 21, 2014 J2 Project
Dollars & Sense of Compliance!
CRCA s 29 th Annual Trade Show Oakbrook k Terrace, IL January 19 20, 2012 Dollars & Sense of Compliance! Mark S. Graham Associate ExecutiveDirector Director, Technical Services National Roofing Contractors
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM
WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC
Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood
Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Section 07411 Metal Roof Panels Part 1 General 1.1 Summary A. This section includes the following: a. Factory-formed
RB271 06/07 R807.1 RB272 06/07 R807.1. Public Hearing: Committee: AS AM D Assembly: ASF AMF DF. Proponent: Rick Davidson, City of Hopkins, MN
3. The use of asphalt shingles and other roof coverings has been successful over these composite insulation panels, so the extra details about vapor retarders, etc. can be eliminated. RB271 06/07 R807.1
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS
ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the
CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL 33034 305-247-8222 ROOFING PERMIT APPLICATION
IF SUBSIDIARY, PROVIDE MASTER PERMIT NUMBER HERE: CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL 33034 305-247-8222 ROOFING PERMIT APPLICATION Location of Improvements
ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction...2. 2.0 Methodology...2
Standard Practice f Table of Contents 1.0 Introduction...2 2.0 Methodology...2 Appendix A...7 Insulation Board Fastening Patterns 4 feet 4 feet Boards Adhered Membranes...8 Insulation Board Fastening Patterns
GENERAL REQUIREMENTS HENRY WARRANTED COMMERCIAL ROOFING SYSTEMS
GENERAL REQUIREMENTS HENRY WARRANTED COMMERCIAL ROOFING SYSTEMS 1.0 STATEMENT OF POLICY The overall performance of a roofing system can be affected by factors other than the roof system installation. Henry
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and
ROOFS - Guidance for Repair, Maintenance and Replacement
ROOFS - Guidance for Repair, Maintenance and Replacement Guilford Association Architectural Committee ROOFING Slate and tile roofs are a critical design feature of Guilford homes. The homes were designed
07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center
PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 5423 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center A. Tear off existing roof system down to wood deck and install new Thermoplastic membrane roofing
POST AND FRAME STRUCTURES (Pole Barns)
POST AND FRAME STRUCTURES (Pole Barns) Post and frame structures. The following requirements serve as minimum standards for post and frame structures within all of the following structural limitations:
SECTION 07 61 13 STANDING SEAM METAL ROOFING
SECTION 07 61 13 STANDING SEAM METAL ROOFING PART 1 GENERAL 1.01 SCOPE OF WORK A. The Work shall include all labor, materials, equipment and supervision required to complete the work of the above referenced
Delaney-Vogel School
Wrentham Public Schools Delaney-Vogel School Schematic Design 1. INTRODUCTION Wrentham Public Schools contracted with Turowski2 Architecture, Inc. on November 11, 2015 to assess necessary roof repairs
CertainTeed. Protecting Your Home From Ice Dams Homeowner s Guide
CertainTeed Protecting Your Home From Ice Dams Homeowner s Guide What Are Ice Dams? Ice dams are formed when heat from the inside of a home escapes into the attic and warms the roof decking during the
Preventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
ROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof
ROOF CONSTRUCTION The overall appearance of a building is greatly affected by the roof lines and the roofing materials. The designer has many standard designs to choose from and should be able to find
ISO Types 1-6: Construction Code Descriptions
ISO 1 Frame (combustible walls and/or roof) Class 1B Buildings where the exterior walls are wood or other combustible materials, including construction where the combustible materials are combined with
SECTION 07320 ROOFING TILE
SECTION 07320 ROOFING TILE PART 1 - GENERAL 1.1 SUMMARY: A. Section Includes: 1. Vitrified clay roofing tiles. 2. Tile accessories. 3. Felt underlayment. 4. Self-adhering sheet underlayment. 5. Snow guards.
Maintaining Your Roof
Maintaining Your Roof Roofs play a key role in protecting building occupants and interiors from outside weather conditions, primarily moisture. The roof, insulation and ventilation must all work together
Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..
Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
Chapter 6 ROOF-CEILING SYSTEMS
Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;
Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.
Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that
Shingle Installation Guide
Shingle Installation Guide Getting Started Dedicated to improving the environment, NewTech manufactures roofing tiles that are composed of up to 90% recycled post-industrial plastic. The manufacture of
HCD DSA OSHPD 1 2 1/AC AC SS 1 2 3 4
CALIFORNIA RESIDENTIAL CODE MATRIX ADOPTION TABLE CHAPTER 9 ROOF ASSEMBLIES (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority and
BITUMEN-POLYMER WATERPROOFING MEMBRANE, MADE FROM SELECT APP AND DISTILLED BITUMEN, REINFORCED WITH SPUNBOND POLYESTER FABRIC.
93-106 Revised March 2007 BITUMEN-POLYMER WATERPROOFING MEMBRANE, MADE FROM SELECT APP AND DISTILLED BITUMEN, REINFORCED WITH SPUNBOND POLYESTER FABRIC. BITEC APM-4.5T is a torch applied, mineral surfaced,
CHAPTER 6 ASPHALT ROLL ROOFING
CHAPTER 6 ASPHALT ROLL ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 6.1.1 General 6.1.3 Mineral-Surfaced Asphalt roll roofing is roofing in sheet form Mineral-surfaced roll roofing is composed
CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
Indefinite Quantity Unit Price Schedule
Indefinite Quantity Unit Price Schedule DCS # 08002 THIS SET OF BID FORMS IS FOR AREA 4 WORK DESCRIPTION Unit Unit Price Specification Number 2.1 WATERPROOFING & DAMPPROOFING 2.1 10 100 Pressure cleaning.
Holiday Inn Express & Suites Covington (Newton County) 1. Standing-seam metal roofing, custom fabricated.
PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Standing-seam metal roofing, custom fabricated. 1.2 SUBMITTALS A. Product Data: For each type of product indicated. B. Shop Drawings: Show installation
Proper roof slope and drainage are important to prevent excessive water accumulation
Proper roof slope and drainage are important to prevent excessive water accumulation by Jason P. Wilen, AIA, CDT, RRO P onding water sometimes occurs on membrane roof systems as a result of snow, rainfall
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and
A. Roofing Terminology: Definitions in ASTM D 1079 and glossary in NRCA's "The NRCA Roofing and Waterproofing Manual" apply to work of this Section.
SECTION 075419 POLYVINYL CHLORIDE (PVC) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
CHAPTER 5 ASPHALT-SHINGLE ROOFING
CHAPTER 5 ASPHALT-SHINGLE ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 5.1.1 References double-coverage shingles provide two layers over Specifications for shingles and allied materials are most
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
REPLACE ROOFING DENVER CENTRAL LIBRARY PHASE I CITY & COUNTY OF DENVER DENVER, COLORADO
PUBLIC LIBRARY PHASE I 4828 W. 6TH Avenue, Unit B-8 Golden, Colorado 8040 Phone: (303) 233-092 VICINITY MAP SHEET INDEX GT /26/2009 SHEET DESCRIPTION G.0 COVER SHEET R.0 COMPOSITE ROOF PLAN R. NEW ROOF
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
How To Compare Roofing Material
Roofing Material Comparisons Housing Fact Sheets One of the great strengths of our market economy is the number of product choices we are provided with. So when it comes time to replace the roof on your
Retrofitting an Insulated Cold Roof
Retrofitting an Insulated Cold Roof As a metal-roofing contractor in the Upper Peninsula of Michigan, I am frequently asked to fix roof leaks that have less to do with roofing than with the way poorly
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
Roof Condition Analysis
Roof Condition Analysis Prepared for: J.W. Nelson John Evans Middle School - Gym Dome 2900 15th Avenue Greeley, Colorado Prepared by: Gregory Ham Coastal Specified Products 5252 Sherman Street Denver,
Preformed Metal Roofing and Siding
Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision
Crescent Valley High School Roof Investigation
Crescent Valley High School Roof Investigation Project: Corvallis School District Crescent Valley High School Roof Date: July 26, 2011 Report By: Rowell Brokaw Architects: Mark Young, AIA, Chris Andrejko