RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012

Size: px
Start display at page:

Download "RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012"

Transcription

1 RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 Commercial rooftops represent the most available, sustainable and secure real estate for new solar energy Approximately 3 billion square feet of new roofs are installed on existing and new buildings in the United States each year. At a 50 percent utilization rate, the solar energy industry could leverage this rooftop space to add 5 gigawatts of photovoltaic capacity annually. In order to accelerate the deployment of properly installed, well- maintained solar energy roofing systems, the Center for Environmental Innovation in Roofing (Center) launched the Center PV Taskforce in October The Center PV Taskforce works to bridge the gap and increase communication between the roofing and solar industries. The Center PV Taskforce is publishing the first public version of PV Racking and Attachment Criteria for Effective Membrane Roof System Integration to address the critical interaction between the solar racking system and roofing system. The criteria document identifies five fundamental principles of effective roof system integration: A. External Forces B. System Integration C. Roof Drainage D. Roof and PV System Maintenance E. Roof Safety Each fundamental principle is parceled into specific examples and recommended action items. The Center PV Taskforce intends PV Racking and Attachment Criteria for Effective Membrane Roof System Integration to provide a guide to the practitioner for the design, installation and long- term maintenance of rooftop solar racking Questions/Comments Please send questions or comments regarding the document to the Center PV Taskforce by at PVTaskforce@RoofingCenter.org, or by telephone at

2 Table of Contents A. External Forces...3 B. System Integration...5 C. Roof Drainage...8 D. Roof and PV System Management...9 E. Roof Safety...11 Page 2 of 11 Center PV Taskforce

3 Fundamental Principle A: External Forces FUNDAMENTAL PRINCIPLE EXAMPLE RECOMMENDED CRITERION APPLIES TO A.1. Base mounts of ballasted and self- ballasting racks may puncture, cut or abrade the roof waterproofing surface through vibration, creep or expansion / contraction. A.1.a. Include durable protection layer(s) of compatible materials between all ballasting materials and the roofing surface. Protection layer(s) shall be designed to prevent damage to the roofing membrane over the service life of the PV / roofing system. If approved by the roof system manufacturer, protection layer(s) may be directly integrated into the ballasted racking system. A. EXTERNAL FORCES. The racking and attachment system shall be designed so that external forces acting on the rack do not compromise roof waterproofing integrity. All vertical and horizontal forces should be transferred to the building structure without overloading or damaging the roofing system. Loads to be considered include wind loads, wind uplift loads, dead loads, snow loads, seismic loads as well as thermal expansion / contraction and non- specific vibratory loads from external forces or building equipment. A.2. Base mounts of mechanically attached racking systems may move laterally under load due to external forces or internal expansion / contraction, causing distortion and failure of flashing and sealing materials. A.1.b. Include expansion / contraction joints in the racking system and/or racking mounts to minimize differential movement between the roofing and racking system. A.2.a. Whenever possible, anchor the racking system directly to the building structure or structural blocking. When anchoring to the roof deck, the roof deck shall be capable of accommodating the imposed loads or reinforced with adequate blocking. In all cases, the attachment method shall provide adequate uplift/pullout resistance and resistance to lateral loads. A.2.b. Racking mounts and roof flashing details shall be designed so that lateral racking movement is accommodated without damaging the integrity of roof flashings. This may be accomplished through the use of flexible roof flashing details and materials that accommodate lateral movement of the racking mounts as well as minimization of movement of the racking mounts. Calculation of loads and sizing of base mount surface area shall be in accordance with the most recent edition of ASCE 7 and in consideration of the physical properties of the flashing materials. Ballasted and other non- mechanically attached PV racking Mechanically attached PV racking Mechanically attached PV racking systems and ballasted racking anchors. Page 3 of 11 Center PV Taskforce

4 FUNDAMENTAL PRINCIPLE EXAMPLE RECOMMENDED CRITERION APPLIES TO A.3.a. Use integrated PV and roofing systems documented for compatibility by the respective PV and roofing system manufacturers. A.3. PV systems that are fully adhered to a mechanically attached roof surface may exert stresses within the adhesives that could disbond the PV modules or alter the uplift resistance of the mechanically attached roof system. A.4. Base mounts of ballasted and other non- mechanically attached racks may overload the underlying roof surface area, causing puncture or permanent compression of the roofing system. A.5. Large arrays of sloped PV modules and racking systems may cause drifting snow build- up and possibly overload portions of the roof. A.3.b. Use integrated PV / roofing systems that have been certified for code- compliant wind uplift resistance, either through recognized third- party testing (UL, FM or equal) or an engineering analysis prepared by a licensed Professional Engineer. A.4.a. Use base mounts of sufficient surface area to distribute vertical loads without cutting or compressing the underlying roofing system. Calculation of loads and sizing of base mount surface area shall be in accordance with the most recent edition of ASCE 7 and in consideration of the compressive strength and puncture resistance of the underlying roof system components. A.4.b. Install high- density cover board beneath roofing membrane and above thermal insulation to reduce the likelihood of compression of underlying insulation. A.5.a. In areas where snow occurs, a structural analysis shall be performed by a licensed Professional Engineer to account for possible snow drift build- up in accordance with the most recent edition of ASCE- 7. In addition, consideration shall be given for large horizontal racking components, such as covered wireways and wind deflectors. PV systems directly adhered to mechanically attached roofing Ballasted and other non- mechanically attached PV racking Page 4 of 11 Center PV Taskforce

5 Fundamental Principle B: System Integration FUNDAMENTAL PRINCIPLE EXAMPLE RECOMMENDED CRITERION APPLIES TO B.1. Ballasting materials such as concrete pavers may deteriorate, causing increased racking movement and puncture of the roof surface. B.1.a. Use ballast pavers or other ballasting materials that have been documented for long- term durability. B. SYSTEM INTEGRATION. The components of the racking system and roofing system shall be designed for compatibility and documented to prevent or mitigate premature failure that could compromise roof waterproofing integrity. B.2. Ballasting materials installed directly over roofing systems with mechanical fasteners located directly beneath the roofing membrane may cut or puncture the roofing membrane. B.3. Ballasting materials installed directly over mechanically attached racking anchors may cut or puncture the roofing membrane. B.4. Racking and roofing system components with a service life less than either the PV system or underlying roofing system may deteriorate and compromise overall system performance and service life. B.1.b. Use racking trays / holders designed to contain deteriorated and cracked pavers. B.2.a. Avoid installing ballasted and self- ballasting racking systems over roofing systems containing mechanical fasteners directly beneath the roofing membrane. Examples of such roofing systems include mechanically attached membrane systems and fully adhered membrane systems with insulation fasteners directly beneath the roofing membrane. Alternatives to installing ballasted and self- ballasting racking systems over such roofing systems include the use of mechanically attached PV racking systems and / or the use of fully adhered roofing systems using one or more layers of adhered insulation or cover board directly beneath the roofing membrane. B.3.a. Avoid installing any ballasting materials directly over mechanically attached racking anchors. B.4.a. Use racking and roofing system components fabricated from materials that will provide an expected service life equal to or greater than the service life of the combined PV / roofing system. Execute PV racking and roof system maintenance programs recommended by the respective manufacturers to achieve the expected length of service B.4.b. Whenever there is a reasonable expectation that the racking system or roofing system may need to be replaced prior to Ballasted and self- ballasting PV racking Ballasted and other non- mechanically attached PV racking systems installed over fully adhered or mechanically attached roofing Ballasted and other non- mechanically attached racking systems with supplementary mechanical anchors. Page 5 of 11 Center PV Taskforce

6 FUNDAMENTAL PRINCIPLE EXAMPLE RECOMMENDED CRITERION APPLIES TO the end of the useful service life of the PV system, a decommissioning / recommissioning plan shall be established. At a minimum, this plan shall include a logistical plan for removal and replacement of the racking / roofing / pv system components, a projected budget for the replacement, and a financial analysis of the effect of the replacement on project return on investment B.5. PV modules adhered directly to the roofing surface will increase the heat load on the roof membrane and adhesives which may compromise roof system performance and service life. B.6. Thin- film PV adhered directly to mechanically- attached roofing systems may billow or flutter, causing additional stresses on critical components and connections and may compromise both PV and roof system performance and service life. B.7. Flashing details not reviewed and approved by the roof system manufacturer / roof warranty issuer or not in conformance with NRCA guidelines may compromise roof system performance and service life. B.8. Base mounts with complex cross- sections may be difficult to flash and subject to premature failure and moisture penetration. B.9. The roofing system may be damaged during staging and installation of the PV system. B.5.a. Use roofing membranes and adhesives that are designed and certified by the roof system manufacturer to be compatible with the additional heat loads from PV laminates and provide a projected service life equal to or greater than the PV system. B.6.a. Consider use of a fully adhered roof system in lieu of a mechanically attached system, or restrict billowing by installing a continuous air barrier. Note: The application of thin- film PV directly adhered to existing mechanically attached roofing systems is not recommended without approval and acceptance of the roof system manufacturer. B.7.a. Use flashing details that have been reviewed and approved by the roof system manufacturer / roof warranty issuer and installed by an approved applicator. B.7.b. Use flashing details in conformance with most recent edition of NRCA guidelines. B.8.a. Whenever possible, use round or tubular base mount materials which can be flashed securely and do not require penetration pockets. B.9.a. Load and store PV system components in designated staging areas. Do not overload the roofing system or the building PV systems directly adhered to the roofing surface. (Both fully adhered and mechanically attached roofing ) PV systems directly adhered to mechanically attached roofing All PV systems installed over a new or existing roof system warranted by a roof system manufacturer or other warranty issuer. All PV systems installed over a new or existing roof system NOT warranted by a roof system manufacturer or other warranty issuer. Mechanically attached PV racking Page 6 of 11 Center PV Taskforce

7 FUNDAMENTAL PRINCIPLE EXAMPLE RECOMMENDED CRITERION APPLIES TO structure. Install protection materials between the PV system components and the roofing surface to prevent compression, abrasion, cutting or puncture. Store PV system components on raised pallets to allow roof drainage. B.9.b. Whenever possible, confine installation traffic to designated walkways covered with protection materials to prevent compression, abrasion, cutting and puncture of the roofing system. Cover the roofing system with protective materials whenever field installation may require or produce sharp objects that could cut or puncture the roofing system. Bag and remove debris from the roof on a regular basis. Page 7 of 11 Center PV Taskforce

8 Fundamental Principle C: Roof Drainage FUNDAMENTAL PRINCIPLE EXAMPLE RECOMMENDED CRITERION APPLIES TO C. ROOF DRAINAGE. The racking and attachment system shall be designed so that water drainage on the roof is not compromised. C.1. Racking systems with horizontal elements (either structural elements or wireways) that block the roof drainage plane may cause water to pond on the roof and allow for debris accumulation. C.1.a. Maintain a minimum clearance between the roof surface and any horizontal element of the racking system sufficient to allow effective roof drainage. As an alternative, the racking system shall contain drainage openings or gaps that allow adequate water flow. In all cases the drainage design of the combined PV / roof shall be based on calculations derived from the most recent edition of the International Plumbing Code. Assure that all areas where debris may accumulate are accessible for cleaning C.1.b. Whenever possible, orient the racking system so that horizontal elements blocking roof drainage are parallel to roof drainage flow. Design ballast mounts to provide drainage in both directions of the mount or to redirect water around the mount. C.2. Placement of racking systems may impede access to roof drains for periodic maintenance. C.2.a. Provide access to roof drains suitable for periodic maintenance. C.3. Roof curbs greater than 30 inches wide* supporting PV equipment such as inverter and combiner hardware may block drainage and cause water to pond on the roof. (* as measured perpendicular to the slope per most recent edition of the International Building Code.) C.3.a. Whenever possible, orient roof curbs greater than 30 inches wide* supporting PV equipment so that they provide drainage in both directions or redirect water around the curb." (* as measured perpendicular to the slope per most recent edition of the International Building Code.) Page 8 of 11 Center PV Taskforce

9 Fundamental Principle D: Roof and PV System Maintenance FUNDAMENTAL PRINCIPLE EXAMPLE RECOMMENDED CRITERION APPLIES TO D.1. The PV system may obstruct safe and effective access to rooftop equipment and other openings requiring periodic inspection and maintenance. D. ROOF and PV SYSTEM MAINTENANCE. The racking and attachment system shall be designed to allow effective roof and PV system inspection, leak detection, maintenance and repair. D.2. PV racking system components may obstruct effective observation and maintenance of underlying roof surfaces by roofing workers. D.3. In the event that major roof system repairs are needed, the PV racking system may need to be temporarily disassembled and stored to allow for roof repairs. D.4. Roof maintenance may be performed by personnel with inadequate training to service roofs with PV systems or insufficient information regarding the specific rooftop PV installation. D.1.a. Provide designated walkway areas for roof inspection and maintenance. At a minimum, roof walkways should include an unobstructed pathway along the perimeter of the roof as well as unobstructed pathways leading from all roof access points to and around all rooftop equipment and other openings that may require periodic maintenance. Walkways shall be constructed of durable and compatible materials suitable for protecting the roof surface, as approved by the roof system manufacturer or roofing contractor. In all cases, design and layout of walkways shall conform to the requirements of the most recent edition of the International Fire Code. D.2.a. Whenever possible, provide clearances between the racking system and the roof surface sufficient for effective inspection and maintenance. When sufficient clearances cannot be achieved, use racking system components that can be disassembled for inspection and maintenance. D.3.a. Staging areas for PV system disassembly and removal shall be identified and provided. (See also B.7.a.) D.4.a. Assure that roof maintenance in close proximity to the PV system is conducted by roofing personnel trained to work safely and effectively around PV components. D.4.b. Whenever possible provide the building owner with maintenance manuals covering all major elements of the roofing and PV system, including a roof system manual provided by the roof system manufacturer or roofing contractor, a PV system Page 9 of 11 Center PV Taskforce

10 FUNDAMENTAL PRINCIPLE EXAMPLE RECOMMENDED CRITERION APPLIES TO maintenance manual provided by the PV manufacturer or installer, and a racking system maintenance manual provided by the racking system manufacturer or installer. D.5. PV cleaning materials may cause premature deterioration of roof membrane. D.6. Lack of electricity and water supply on rooftop increases costs for maintaining roof and PV D.5.a. Coordinate PV maintenance guidelines to ensure compatibility between PV maintenance and roof system, especially the use cleaning chemicals that are compatible with the roof system membrane. D.6.a. Provide water and electrical utilities to roof for operation and maintenance of roof and PV system. Page 10 of 11 Center PV Taskforce

11 Fundamental Principle E: Roof Safety FUNDAMENTAL PRINCIPLE EXAMPLE RECOMMENDED CRITERION APPLIES TO E.1. Racking system components may impinge on designated maintenance and service walkways. E. ROOF SAFETY. The racking and attachment system shall be designed to assure worker safety during roof inspection, maintenance and repair. E.2. Racking system layout may create an unnecessary fall exposure. E.1. Whenever possible, design racking systems to allow unimpeded access along all designated walkways. In all cases, design and layout of walkways shall conform to the requirements of the most recent edition of the International Fire Code. E.2. Develop and implement a long- term fall protection plan to allow safe access to the PV system both during system installation and ongoing system maintenance. (End of Document) Page 11 of 11 Center PV Taskforce

Maximizing the Benefits of Roof-Mounted Solar Arrays for Commercial Buildings

Maximizing the Benefits of Roof-Mounted Solar Arrays for Commercial Buildings 1 Maximizing the Benefits of Roof-Mounted Solar Arrays for Commercial Buildings Featuring the Eco-Top System by DCE Solar Elevating the Future for Solar 2 The Smart Business of Solar Even though the solar

More information

Commercial Roof Management

Commercial Roof Management Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading

More information

ROOF INSPECTION & MAINTENANCE

ROOF INSPECTION & MAINTENANCE Physical Plant Administration Facilities Maintenance Department ROOF INSPECTION & MAINTENANCE All roofs require periodic inspection and maintenance in order to perform as designed and to provide a long

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

Building Owners Guide to a Duro-Last System!

Building Owners Guide to a Duro-Last System! Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof

More information

GUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS

GUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS INFORMATION BULLETIN / PUBLIC GENERAL INFORMATION REFERENCE NO.: LAMC 91.1301, 93.690 Effective: 01-01-2014 DOCUMENT NO.: P/GI 2014-027 Revised: 12-16-2015 Previously Issued As: P/GI 2011-027 GUIDELINES

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design Basis of Design This section applies to roofing membranes, flashing and accessories. Design Criteria Adhere to the standards and details of the latest editions of the National Contractors Association (NRCA)

More information

Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2

Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building

More information

Roof Insulation Building. Energy. Environment friendly e-library

Roof Insulation Building. Energy. Environment friendly e-library Roof Insulation Building Codes & Energy Efficiency Environment friendly e-library Building Code Driver Buildings consumer almost 50% of all energy. Experts believe that a 30% increase in building efficiency

More information

RESIDENTIAL PHOTOVOLTAIC SUBMITTAL REQUIREMENTS

RESIDENTIAL PHOTOVOLTAIC SUBMITTAL REQUIREMENTS DEVELOPMENT AND RESOURCE MANAGEMENT DEPARTMENT BUILDING AND SAFETY SERVICES 2600 Fresno Street, Third Floor Fresno, California 93721-3604 (559) 621-8082 FAX (559) 498-4357 RESIDENTIAL PHOTOVOLTAIC SUBMITTAL

More information

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry

More information

TARRANT COUNTY DETAIL STANDARDS

TARRANT COUNTY DETAIL STANDARDS TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout

More information

Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building

Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, 66046 Sauer-Danfoss Building Prepared For: Ms Marilyn Bittenbender Colliers International 805 New Hampshire St Lawrence Kansas, 66046 Prepared

More information

Asphalt Shingle Application Requirements

Asphalt Shingle Application Requirements Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt

More information

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded

More information

Saving Energy and Money On Your Commercial Roof

Saving Energy and Money On Your Commercial Roof Saving Energy and Money On Your Commercial Roof John Geary Vice President of Marketing, Firestone Building Products Chairman of the Board, Center for Environmental Innovation in Roofing gearyjohn@firestonebp.com

More information

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12

WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced

More information

Low-slope reroofing guidelines

Low-slope reroofing guidelines Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

Roof Condition Analysis

Roof Condition Analysis Roof Condition Analysis Prepared for: J.W. Nelson John Evans Middle School - Gym Dome 2900 15th Avenue Greeley, Colorado Prepared by: Gregory Ham Coastal Specified Products 5252 Sherman Street Denver,

More information

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It

More information

ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction...2. 2.0 Methodology...2

ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction...2. 2.0 Methodology...2 Standard Practice f Table of Contents 1.0 Introduction...2 2.0 Methodology...2 Appendix A...7 Insulation Board Fastening Patterns 4 feet 4 feet Boards Adhered Membranes...8 Insulation Board Fastening Patterns

More information

ABOVE ALL, IT S A ROOF SERVICED BY THE JAMES MYERS COMPANY

ABOVE ALL, IT S A ROOF SERVICED BY THE JAMES MYERS COMPANY ABOVE ALL, IT S A ROOF SERVICED BY THE JAMES MYERS COMPANY BEAM A Premiere Roof Asset Management Program WITH BEAM WE CAN HELP YOU MAINTAIN AND PROTECT THE ROOF THAT PROTECTS YOU. A FRAGILE BARRIER Consider

More information

Owner s Care & Maintenance Guide For Viridian Systems Roof Membranes

Owner s Care & Maintenance Guide For Viridian Systems Roof Membranes Owner s Guide For Viridian Systems Roof Membranes VIRIDIAN SYSTEMS ROOF MEMBRANE SYSTEM CARE & MAINTENANCE GUIDE TABLE OF CONTENTS A. INTRODUCTION... 2 B. PREVENTIVE MAINTENANCE... 2 C. LEAK INVESTIGATION...

More information

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

Georgia State University. Urban Life Building Roof Replacement

Georgia State University. Urban Life Building Roof Replacement ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT

More information

Commercial Roof Inspection Form

Commercial Roof Inspection Form Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building

More information

SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING

SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

The existing roof angle change terminations and flashings when sound and intact can be reused.

The existing roof angle change terminations and flashings when sound and intact can be reused. January 2, 2015 Summary Specification Re-Skinning an Existing Roof Maintenance and Repair Warranty Upgrade for Up to 30 Years Re-Skinning Over an Existing Roof with a New C-EPDM Membrane Using The Existing

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within

More information

SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide

SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide Inspection Questions? Call Bloom At 800-483-9932 www.bloomroofing.com DISCLAIMER

More information

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs. Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12

More information

GUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS

GUIDELINES FOR PLAN CHECK AND PERMIT REQUIREMENTS FOR SOLAR ENERGY SYSTEMS INFORMATION BULLETIN / PUBLIC GENERAL INFORMATION REFERENCE NO.: LAMC 91.1301, 93.690 Effective: 01-01-2014 DOCUMENT NO.: P/GI 2014-027 Revised: 11-07-2014 Previously Issued As: P/GI 2011-027 GUIDELINES

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association

FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING Roofing Manufacturers Association Why is a built-up roof considered a multi-ply roof? ARMA defines a built-up roofing system as a roof where multiple

More information

Exterior Elevated Elements Inspection Guidelines

Exterior Elevated Elements Inspection Guidelines Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code

More information

Get Rid of Roof Problems for Good. How spray foam roofing can protect your building and make you money

Get Rid of Roof Problems for Good. How spray foam roofing can protect your building and make you money Get Rid of Roof Problems for Good How spray foam roofing can protect your building and make you money What is a Spray Foam Roofing System? 300 MILLION Board feet of roofing spray foam installed annually

More information

SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.

SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck. SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied

More information

Rooftop Matters. 2 0 1 2 Benchmark Report. Executive Summary

Rooftop Matters. 2 0 1 2 Benchmark Report. Executive Summary The 2012 Benchmark Report is our initial survey covering results from roof inspections and service calls over a six-month period. Our intention is to update these results annually in order to provide meaningful

More information

Proper roof slope and drainage are important to prevent excessive water accumulation

Proper roof slope and drainage are important to prevent excessive water accumulation Proper roof slope and drainage are important to prevent excessive water accumulation by Jason P. Wilen, AIA, CDT, RRO P onding water sometimes occurs on membrane roof systems as a result of snow, rainfall

More information

The Perfect Fit For Metal Retrofit

The Perfect Fit For Metal Retrofit D u r o - S h i e l d M e t a l R e t r o f i t R o o f i n g S y s t e m The Perfect Fit For Metal Retrofit Lock out leaks. Lock in your investment. Has time caught up with your metal roof? There are

More information

Peel & Seal Self-Stick Roofing Solutions

Peel & Seal Self-Stick Roofing Solutions Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,

More information

Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5. 1. Purpose

Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5. 1. Purpose Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5 1. Purpose The purpose of this practice note is to address the incidence of deck and roof membrane

More information

How To Design A Sustainable Roofing

How To Design A Sustainable Roofing Benchmark, Inc. Perspectives Webinar Series Sustainable Roofing: A Practical Strategy for Roof Replacement Commitment from the ground up. Presenters Dr. James Hoff, DBA Center for Environmental Innovation

More information

Fall Protection System: A system put in place to protect workers from falling. (i.e. installation of guardrails, fall arrest, fall restraint, etc.

Fall Protection System: A system put in place to protect workers from falling. (i.e. installation of guardrails, fall arrest, fall restraint, etc. SWP (6) FALL PROTECTION PROGRAM The following information on Fall Protection has been based around the BC OHS Regulations, standards, policies and guidelines. Prior to starting work outside of BC, the

More information

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam

More information

Roof Restoration System. For building owners, property management firms and facility managers. seamless possibilities

Roof Restoration System. For building owners, property management firms and facility managers. seamless possibilities Roof Restoration System For building owners, property management firms and facility managers seamless possibilities Extending your roof life Think of your existing older roof custom fit with a seamless,

More information

NEOGARD. Preventive Maintenance Manual

NEOGARD. Preventive Maintenance Manual NEOGARD Preventive Maintenance Manual Fluid-Applied Roof Coating Systems December 2014 Notes NEOGARD luid-applied roof coating systems are designed to be long lasting, monolithic membranes which provide

More information

SECTION 07400 STANDING SEAM METAL ROOF

SECTION 07400 STANDING SEAM METAL ROOF SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and

More information

PIMA Technical Bulletin #115. The High R Roof: Guidelines for Energy-Efficient Roofing and Re-Roofing. What is a High R Roof?

PIMA Technical Bulletin #115. The High R Roof: Guidelines for Energy-Efficient Roofing and Re-Roofing. What is a High R Roof? PIMA Technical Bulletin #115 The High R Roof: Guidelines for Energy-Efficient Roofing and Re-Roofing About Polysio Insulation Polyiso is a rigid foam insulation used in over 70% of commercial roof construction,

More information

LEED PRESENTATION OUTLINE

LEED PRESENTATION OUTLINE 16902 BOLSA CHICA STREET, SUITE 101 HUNTINGTON BEACH, CA 92649 TELEPHONE (714) 840-8230 FACSIMILE (714) 840-2490 LEED PRESENTATION OUTLINE I. Overview of Green Building and Risks Involved with Sustainability

More information

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that

More information

Roof Inspection. Summary Report

Roof Inspection. Summary Report www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,

More information

Waterproofing Problems: A Simple Explanation, A Simple Solution

Waterproofing Problems: A Simple Explanation, A Simple Solution Waterproofing Problems: A Simple Explanation, A Simple Solution The purpose of this paper is to point out the underlying causes of waterproofing problems and simple means of preventing them. Such problems

More information

REQUEST FOR PROPOSALS

REQUEST FOR PROPOSALS Page 1 of 6 REQUEST FOR PROPOSALS Issue Date: 2/19/2013 RFP# WHS-2013-001 Title: Services for roofing improvements and annual roof assessments, Windsor School Complex, State Street, Windsor, Vermont Issuer

More information

CARLISLE OWNER S MANUAL

CARLISLE OWNER S MANUAL Investing in Solutions for Over 45 Years For over 45 years Carlisle Construction Materials Incorporated (CCM) has been creating solutions for the construction industry. Beginning with single-ply roofing

More information

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance

More information

metal Duil~ing manufacturers Association

metal Duil~ing manufacturers Association metal Duil~ing manufacturers Association ApplicatiDns metal Building Systems Conventional Buildings Retrofit Roofing Projects l~e Perfect Cover.One of the most important technological advances in building

More information

COMMERCIAL BUILDING APPLICATIONS

COMMERCIAL BUILDING APPLICATIONS EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that

More information

Regional and Site Assumptions This document is based on the following regional and site assumptions:

Regional and Site Assumptions This document is based on the following regional and site assumptions: Structural Criteria for Residential Rooftop Solar Energy Installations Use of this document This toolkit document includes a one-page list of structural criteria for over-the-counter or online approval,

More information

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS

CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes

More information

A. This Section includes rubberized asphalt sheet membrane waterproofing systems.

A. This Section includes rubberized asphalt sheet membrane waterproofing systems. SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Rehabilitation Strategies for Bonded Concrete Overlays of Asphalt Pavements

Rehabilitation Strategies for Bonded Concrete Overlays of Asphalt Pavements University of Pittsburgh Rehabilitation Strategies for Bonded Concrete Overlays of Asphalt Pavements Authors: J. M Vandenbossche S. Sachs August 2013 1. Introduction Bonded concrete overlays of asphalt

More information

Winterizing Your Building

Winterizing Your Building Winterizing Your Building DEC Author: Steven J. Susca This article was originally published in the Hoffmann Architects Journal in Issue 3, 2009. As spring thaws uncover the ravages winter weather has wreaked

More information

Impact of Solar Photovoltaic Laminate Membrane Systems on Roofs

Impact of Solar Photovoltaic Laminate Membrane Systems on Roofs T E C H N I C A L M E M O R A N D U M Impact of Solar Photovoltaic Laminate Membrane Systems on Roofs PREPARED FOR: PREPARED BY: REVIEWED BY: COPIES: Jessie Denver, City of San José Solar America Showcase

More information

SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)

SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) PART 1 GENERAL 1.1 DESCRIPTION 1. Fluid applied flexible acrylic waterproofing system over concrete. This work shall include the

More information

ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING

ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings

More information

Dollars & Sense of Compliance!

Dollars & Sense of Compliance! CRCA s 29 th Annual Trade Show Oakbrook k Terrace, IL January 19 20, 2012 Dollars & Sense of Compliance! Mark S. Graham Associate ExecutiveDirector Director, Technical Services National Roofing Contractors

More information

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01. Section 5.0 Basements Wall insulated externally Product: Polyfoam ECO Ba01 Wall insulated internally Product: Polyfoam ECO Ba02 Basements Basements Basement design Waterproofing BS 8102: 2009 Code of practice

More information

Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM

Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM The following is the Los Angeles Fire Department s minimum requirement for Solar Photovoltaic System Installations. The City of

More information

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.

More information

Solar America Board for Codes and Standards

Solar America Board for Codes and Standards Impacts on Photovoltaic Installations of Changes to the 2012 International Codes A Solar ABCs White Paper May 2011 Solar America Board for Codes and Standards www.solarabcs.org Solar America Board for

More information

0845 0098 980 www.nicholsonsts.com

0845 0098 980 www.nicholsonsts.com 0845 0098 980 www.nicholsonsts.com ROOFTRAK The IFP is revolutionising the way we fix things to roofs. Technical Director of a leading UK roofing system manufacturer The ROOFTRAK-IFP A revolutionary solution

More information

Solar Panel Installations

Solar Panel Installations Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.

More information

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

Final inspections are completed by site visit only. Access to fenced yards shall be planned. ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,

More information

07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center

07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 5423 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center A. Tear off existing roof system down to wood deck and install new Thermoplastic membrane roofing

More information

Maintenance & Inspection Guide

Maintenance & Inspection Guide ADDRESSING THE NEEDS OF OUR CUSTOMERS AND THE ENVIRONMENT ONE high Performance roofing SOLUTION AT A TIME. Maintenance & Inspection Guide TABLE OF CONTENTS Topic: Page: I. Introduction 1 II. Maintenance

More information

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM

WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM WESTERN COOL ROOF SYSTEMS Sustainable - Energy Efficient FLUID APPLIED REINFORCED ROOF SYSTEM SPECIFICATION NO. SMAA-2P-8xE UPGRADE SMOOTH SURFACE / CAP SHEET / SINGLE PLY 2 PLY POLYESTER REINFORCED ACRYLIC

More information

A. Roofing Terminology: Definitions in ASTM D 1079 and glossary in NRCA's "The NRCA Roofing and Waterproofing Manual" apply to work of this Section.

A. Roofing Terminology: Definitions in ASTM D 1079 and glossary in NRCA's The NRCA Roofing and Waterproofing Manual apply to work of this Section. SECTION 075419 POLYVINYL CHLORIDE (PVC) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS OPTIONAL TITLE 24 CRITICAL POINTS POLYISO THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE DESCRIPTION TORCH OVER POLYISO (5,7,9 YR) TH/BS-TH/CS 2 No 0. SUBSTRATE. THERMOTEK USA PRO 2.0 FV

More information

Site Inspection Report

Site Inspection Report Site Inspection Report Project Title: 1 Canada Square Location: 1 Canada Square, Canary Wharf, London Date of Inspection: 16/05/12 System / Products: TBA (suggested flame free application) Attendees: G

More information

The Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems

The Butler MR-24 Standing Seam Roof Difference. A comparison between metal roof systems The Butler MR-24 Standing Seam Roof Difference A comparison between metal roof systems Roof Systems Necessities Weathertight (don t leak!) Low maintenance Weathertightness Roof clips, seams, panel alignment

More information

RESIDENTIAL ROOF PERMITTING - 101. A REFRESHER WORKSHOP September 11, 2014

RESIDENTIAL ROOF PERMITTING - 101. A REFRESHER WORKSHOP September 11, 2014 RESIDENTIAL ROOF PERMITTING - 101 A REFRESHER WORKSHOP September 11, 2014 Agenda Basics of Permit Application Use of Charlotte County GIS system Florida Product Approvals Top Application Mistakes Standard

More information

A Guide to Green Roofs on Existing School Buildings

A Guide to Green Roofs on Existing School Buildings A Guide to Green Roofs on Existing School Buildings What is a Green Roof? What does it do? Green Roofs can mean different things. It can include vegetative plantings, solar thermal installations, solar

More information

High Performance PSA in Sheet Membrane in Water Protection

High Performance PSA in Sheet Membrane in Water Protection High Performance PSA in Sheet Membrane in Water Protection Xia Cao, Senior R&D Chemist, W. R. Grace, Cambridge MA 02140 Jyoti Seth, Strategic Program Leader, W. R. Grace, Cambridge MA 02140 Concrete is

More information

How To Replace A Roofing System In Florida

How To Replace A Roofing System In Florida Florida Consumer Considerations in Replacing their Roofing System The Florida Roofing, Sheet Metal and Air Conditioning Contractors Association provides the following general information to help Florida

More information

Specifying SPF Roofing Systems

Specifying SPF Roofing Systems Specifying SPF Roofing Systems Spray polyurethane foam (SPF) roofing systems have been marketed for years primarily on their documented energy saving characteristics. Consequently much of the SPF roofing

More information

How To Improve Roof Drainage

How To Improve Roof Drainage The Roof Drainage Epidemic Stewart M. Verhulst, M.S., P.E., M.ASCE 1 Marco A. Deleon, M.E., P.E., M.ASCE 2 Bradley L. East, M.S., M.ASCE 3 1 Nelson Architectural Engineers, Inc., 9701 Brodie Lane, Suite

More information

Durapax Coal Tar BUR Application Guide

Durapax Coal Tar BUR Application Guide 400 Old Reading Pike, Suite 304 Pottstown, PA 19464 Tel: 610-579-9075 Fax: 610-323-0115 www.durapax.com Durapax Coal Tar BUR Application Guide DESIGN CONSIDERATIONS The proper specifications of any roof

More information

TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe

TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe TN 5.14 February 2010 Introduction It may be at times necessary, in an aging infrastructure, to rehabilitate drainage and sanitary lines

More information

Fixed Access Ladders. Table of Contents. 1. Legislative Requirements

Fixed Access Ladders. Table of Contents. 1. Legislative Requirements Fixed Access Ladders Engineering Data Sheet 2-04 Revised: January 1997 Table of Contents 1. Legislative Requirements 2. General 3. Rungs 4. Side Rails 5. Safety Cages 6. Attachment & Anchoring 7. Platforms

More information

Proven roofing SyStemS

Proven roofing SyStemS Proven Roofing Systems Above all. Roofing challenges are never over our heads At GenFlex, we live to tackle and solve the toughest challenges in roofing. The result is a full line of proven, durable roofing

More information

RECOATING AND RENEWING SPF ROOFING SYSTEMS

RECOATING AND RENEWING SPF ROOFING SYSTEMS RECOATING AND RENEWING SPF ROOFING SYSTEMS Procedures, Regional Differences and type of coating systems Bruce Schenke Premium Spray Products REASONS TO RECOAT/RENEW Add a new coating layer to renew the

More information

Crescent Valley High School Roof Investigation

Crescent Valley High School Roof Investigation Crescent Valley High School Roof Investigation Project: Corvallis School District Crescent Valley High School Roof Date: July 26, 2011 Report By: Rowell Brokaw Architects: Mark Young, AIA, Chris Andrejko

More information

FireSmart IRS Insulating Roof Screed

FireSmart IRS Insulating Roof Screed Insulating Roof Screed CI/SfB January 2004 CI/SfB January 2004 M2 P M2 P Icopal Ltd Barton Dock Road Stretford, Manchester M32 0YL Telephone: 0161 865 4444 Fax: 0161 866 9859 Technical Fax: 0161 865 8433

More information

Bituminous Sheet Flat Roofs: Their repair and maintenance

Bituminous Sheet Flat Roofs: Their repair and maintenance Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and

More information

COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE

COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE www.epdmroofs.org COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE By Ric Vitiello President Forensic Roof Consulting and Hail Damage Assessment Training www.benchmark-services.com

More information

PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT

PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT PREVENTING GROUNDWATER POLLUTION IS EVERYONE S JOB! Even if our drinking water comes from rivers, lakes, or reservoirs, we need to be mindful of

More information

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com

HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,

More information