INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS
|
|
|
- Shannon Boone
- 9 years ago
- Views:
Transcription
1 INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS Introduction This inspection guide is organized to follow the EIF System's Installation Guide. It should be used in conjunction with the system Installation Guide and the Product Data Sheet for each of the system components. These publications contain the specific requirements for the use of the EIFS components and their incorporation into the system. In addition, reference should be made to the specification and detail drawings for the system. These publications are available on the Parex USA branded websites. Users of this guide should be thoroughly familiar with EIFS and general construction and be able to read and understand construction plans and specifications. This Inspection Guide is divided into in three parts. The parts follow the order of the construction. The first part of the guide covers some items of construction that are installed prior to the EIFS. For those items of construction, though, the guide is limited to inspecting the features that are specific requirements for the EIFS. The second part covers inspection of the EIFS at each of the major steps of its installation. The third part covers some items of construction that are installed after the EIFS. But also, for those items of construction, the guide is limited to inspecting the features that are specific requirements for the EIFS. Each of the three parts contains a series of checklists that can be copied for use. EIFS installation progresses by layers, with each layer covering the previous work. Therefore, inspecting different stages of the work requires schedule coordination. The inspections addressed by this guide are those that do not require testing or demolition or other destructive measures. The checklists are not intended to prevent inspectors from using their own alternative methods of recording or reporting their findings nor is it intended to limit the scope of inspections agreed to between the inspector and the party engaging the inspector s services. This guide is not intended to define the scope of the EIFS installer s work. The user of this guide assumes all responsibility for its use. Please direct any questions about this guide to: Technical Services Parex USA, Inc Installation Inspection Guide Page 1 of 8
2 Third Party Inspector Qualifications 1. The third party inspector should be knowledgeable in the construction industry. 2. The third party inspector should be knowledgeable in the installation of exterior insulation and finish systems (EIFS). 3. The third party inspector should have attended a training session provided by AWCI and should possess an AWCI/EIFS Inspector Training Certificate. 4. The third party inspector should be capable of reading and understanding design and construction drawings as well as EIF System details. He/she should be able to identify and report discrepancies between project conditions and the project EIFS design requirements in a timely manner so as not to delay the construction schedule. The third party inspector should report all discrepancies and nonconforming work to the Owner, Architect, General Contractor/Construction Manager and EIFS Applicator or as agreed with the party engaging the third party inspector s services. All deviations should be corrected by the EIFS Applicator or other appropriate subcontractor prior to proceeding with the next stage of installation. The Third Party Inspector should confirm that the deviation was corrected and conforms with the contract documents. The final section of this Guide provides for a record of corrections. Inspection A final inspection of the project should be conducted jointly by the Owner, Third Party Inspector, General Contractor/Construction Manager, and EIFS Applicator for the purpose of final review and acceptance of the work by the Owner. Applicable Products for each EIF System are shown in the table below. Substrate, Flashing, and Sealant Checklists are applicable for all systems. Water Resistive Barriers (Sheet) Water Resistive Barriers Coatings Mechanical Fasteners Adhesive Parex Standard and Optimum System Parex Standard Extra System Parex Standard & Optimum Water Master LCR Parex Waster Master DB Parex Standard & Optimum Water Master Flex Airtight Permadry Permadrain Weathertight/VNT El Rey Insul-Flex Adhered Standard EIFS El Rey Insul-Flex Mechanically Optional Fastened Standard EIFS El Rey Insul-Flex VR Drainage El Rey Insul-Flex with StuccoWrap or Housewrap LaHabra Insul-Flex LaHabra Insul-Flex Water Master LaHabra Insul-Flex Water Master LCR Installation Inspection Guide Page 2 of 8
3 FINAL INSPECTION REPORT SUMMARY Inspections Made: Project Name & Address: Applicator Name: The following Inspections were made and noted on the attached checklists: During Installation Installed Notes: Material Storage Substrate Water-Resistive Barrier Drainage Medium Insulation Board Installation Base Coat & Reinforcing Mesh Finish Coat Sealants Flashings The following applications are outside the scope of this inspection guide: 1. Inspection of the building design and construction to determine the structural adequacy of the substrate wall in regard to the design negative wind loads imposed on it. 2. Expansion joints location and design other than those over expansion joints in the substrate or shown on the project drawings. 3. Expansion joint design other than as shown on the project drawings or as given in the project specifications. To the best of my knowledge, work inspected was in accordance with the project specifications and product specifications. (In case of a discrepancy between the two, the third-party inspector shall have the design professional confirm in writing which documents apply.) Name: Signature: Date: Installation Inspection Guide Page 3 of 8
4 INSPECTION CHECKLIST Substrate Sheathing attached to framing Concrete and masonry Metal siding Metal lath ** Substates Specified: Thickness: Frame spacing: 1. Correct orientation 2. Joints offset from corners of openings 3. Edges supported by framing members 4. Fastener type/ spacing per contract documents 5. Fasteners overdriven 6. Sound, plumb, true, in-plane, and free from all but minor irregularities 7. Flat within ¼ inch in 4-0 radius 8. Clean, dry surface free from contaminants Gypsum Sheathing 10. Paper facing laps to the inside 11. Paper attached firmly to core 12. Glass-mat types coating outward Wood Based 13. Properly gapped at edges and ends ** lath must be installed per ASTM C1063 and be backed by a solid continuous surface, either masonry or sheathing. Flashings Installed Prior to the EIFS & Prior to the Water Resistive Barrier Membranes Flashings are supplied and installed by others. They are NOT a part of this inspection other than regarding the integration of the products. Inspection of flashing is limited to determination that it has been installed and that it has no readily observable discontinuities. Water Resistive Barrier Membrane Manufacturer & Product Name: Water Resistive Barrier Installation Locations: Metal Flashing Material: 14. Flashings that will be counter-flashed by the EIFS are to be installed prior to the EIFS Flashing Installation Locations 15. Flashing over window heads 16. Flashing between the bottom edge of the EIFS and a dissimiliar wall covering material immediately below it. 17. Flashing under the sills of windows where the windows are installed prior to the EIFS 18. Roof/wall flashings where the wall is above the roof and the lower edge of the EIFS terminates near the roof 19. Flashing at openings installed per contact documents 20. Roof wall intersection diverters are installed Installation Inspection Guide Page 4 of 8
5 Water Resistive Barrier Coating Product Used: Approximate coverage per 5 gallon pail: 21. Delivered to the job site in original, unopened containers. Stored in a cool, dry location, out of sunlight, protected from weather and damage. 22. Minimum temp. 40 F 23. Joint reinforced with applicable product at sheathing joints, inside and outside corners, exposed edges at terminations 24. Reinforcement material embedded in accordance with installation instructions 25. Applied to the entire surface of the substrate to a uniform nominal thickness 26. Coverage Rate or thickness: 27. Laps onto all tracks/flashing: 28. If flashing not installed during inspection, application of Water Resistive Barrier Coating and/or compatible materials must be used to create positive drainage. Joint Tape Used: Water Resistive Barrier (Sheet Membrane) Product Used: 29. Water Resistive barrier installed and lapped horizontally in a weatherboard fashion 30. Horizontal Overlap per Manufacturers Instructions: 31. Vertical Overlap per Manufacturers Instructions: Drainage Medium Drainage Mat Tyvek Stuccowrap Metal/Plastic Lath ( only) Parex Water Master EPS 32. Installed according to contract documents Drainboard Channelboard El Rey Grooved Board Backwrap Mesh 33. Backwrap installed to the substrate at all system terminations except at foundation terminations that have a vented track. Installation Inspection Guide Page 5 of 8
6 Insulation Board Flat EPS Drainboard Thickness: EPS Supplier: Channelboard Parex Water Master Drainboard Channelboard El Rey Grooved Board Name of Adhesive: Fastener Manufacturer: Notched trowel dimensions: Fastener Type/Length: Adhesive Attachment Mechanical Attachment Expanded polystyrene Polyisocyanurate Extruded polystyrene (XPS) 34. Delivered to the job site in original, unopened containers. Stored in a cool, dry location, out of sunlight, protected from weather and damage 35. Boards installed with long edges oriented horizontally (EPS only) 36. Boards installed in a running bond with vertical joints staggered 37. Board joints tightly butted 38. Board joints offset from sheathing board joints 39. Board joints at all inside and outside corners are staggered and interlocked 40. Board terminates a minimum of above finished horizontal surfaces as indicated on drawings 41. Expansion Joints backwrapped 42. Minimum thickness of FLAT insulation board at base of aesthetic reveals is 3/4 inch 43. Minimum slope on horizontal areas % of insulation board (EPS) sanded flat 45. Slivers of insulation board/foam spray installed in insulation board gaps where required ADHESIVE ATTACHMENT 46. Adhesive suitable for substrate type 47. Mixed according to mixing proportions 48. Lump free Type I and/or II portland cement 49. Clean potable water 50. Notched trowel dimensions 51. Notched trowel or ribbon and dab 52. Drainage systems run in vertical ribbons MECHANICAL ATTACHMENT 53. Fasteners installed into framing members or nailable substrate 54. Proper type and length for framing/sheathing 55. Corrosion resistant 56. Washer plates flush with surface of insulation board 57. Fasteners overdriven Installation Inspection Guide Page 6 of 8
7 Base Coat and Reinforcing Mesh Name of Base Coat: Amount of water added to each pail: 58. Products delivered to the job site in original, unopened containers. Stored in a cool, dry location, out of sunlight, protected from weather and damage 59. Surface of insulation board is clean, dry, flat and all sanding debris is removed 60. There is no yellowing of insulation board (EPS) from extended exposure 61. Damaged insulation board replaced 62. Lump free Type I and/or II portland cement used 63. Clean potable water used 64. Corners of all openings have butterfly pieces of reinforcing mesh 65. High Impact Mesh installed where specified 66. Mesh patches over abutting ends of vented track at foundations 67. Edges of High Impact Mesh butted tightly 68. High Impact Mesh totally embedded in base coat 69. Reinforcing mesh overlapped a minimum of 2-1/2" at all edges 70. Reinforcing mesh not lapped within 8" of any corner 71. Reinforcing mesh continuous through aesthetic reveals 72. Reinforcing mesh is totally embedded with no mesh color visible Finish Coat Name of Finish: Amount of water added to each pail: Approximate coverage per 5 gallon pail: 73. Base coat free of irregularities 74. Base coat clean, dry, free of dust, dirt efflorescence or other contaminants 75. Base coat has no reinforcing mesh color showing 76. Finished mixed in accordance with Instructions 77. Finish applied to proper thickness 78. Finish not installed on surfaces to receive sealant (joints at terminations, expansion, etc.) 79. Texture and color consistent 80. Cold joints apparent Name of Reinforcing Mesh: Mixing Proportions: Primer (if applicable): Spray or trowel applied: Installation Inspection Guide Page 7 of 8
8 Sealants (not a part of the EIF System) Type of sealant: Coverage per 5 gallon pail: 81. Joint width per contract documents 82. Joint width is uniform 83. Closed cell backer rod installed 84. Bond breaker tape installed 85. Sealant mixed and applied per manufacturer s instructions 86. Proper width to depth ratio 87. Sealant properly tooled Sealant Primer: Flashing Installed after EIFS 88. Cap flashing installed after installation of EIFS 89. Roof counter flashing 90. Gravel stops 91. Balcony deck edge flashing 92. Sill flashing 93. Other: Non-Conformance and Discrepancy Corrections Item # Correction Date: Installation Inspection Guide Page 8 of 8
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 SECTION ONE A. Objective The objective of this guide is to provide Owners and General Contractors/Construction
Third Party Inspection Guidelines For Inspectors As Part of the dryvitcare EIFS Repair/Restoration
Third Party Inspection Guidelines For Inspectors As Part of the dryvitcare EIFS Repair/Restoration DS497 SECTION ONE A. Objective The objective of this guide is to provide owners and general contractors/construction
Window Installation Instructions
Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for
2015 DuROCK Alfacing International Limited
SEPTEMBER 2015 DuROCK DEFS Direct-Applied Exterior Finish System MANUFACTURER S IFICATION 09 25 15 Part 1 GENERAL 1.1 RELATED SECTIONS.1 Specification 03 30 00 Cast-in-Place Concrete.2 Specification 04
Tundra Series Windows January 2016
Tundra Series Windows January 2016 New Construction Installation Instructions Nail Fin, J-Fin and Brickmold Aplications product. ATTENTION! Read and understand all installation instructions before installing
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
K2 STONE NATURAL VENEER
INTRODUCTION WHAT IS K2 NATURAL THINSTONE VENEER? Natural K2 Stone veneer is real stone, cut 1 inch thick, making it light enough to be installed as a veneer. Sometimes referred to as thin veneer, thin
LEGACY REPORT. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council RETAINED ON U.S.
ICC-ES Legacy Report ER-5043* Reissued March 2004 www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council Legacy report on the 1997 Uniform Building Code DIVISION: 09
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
Clad Direct Glaze Window Installation Instructions
Clad Direct Glaze Window Installation Instructions Sill flashing and sealing: 2. An overview of the proper flashing sequence is shown in figure 1. Please read entire installation instructions carefully
GigaCrete Specification PlasterMax
GigaCrete Inc. 6775 Speedway Blvd. Suite M105 Las Vegas, NV 89115 Ph (702) 643-6363 Fax (702) 643 1453 www.gigacrete.com GigaCrete Specification PlasterMax PlasterMax : Fire Rated Plaster for Direct Application
GreenGuard Housewrap Installation Guide
000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
WELCOME. Recommended Window Installation. 1.5 credits Minnesota Department of Labor and Industry
WELCOME Recommended Window 1.5 credits Minnesota Department of Labor and Industry In accordance with the Department of Labor and Industry s statute 326.0981, Subd. 11, This educational offering is recognized
CertainTeed. Self-Adhering Roof Systems for Low Slope Residential Roofs
CertainTeed Self-Adhering Roof Systems for Low Slope Residential Roofs Goes down fast. Stays on strong. Flintlastic SA performs in all the right ways. What s more important to you? Speed of installation,
Exterior Insulation and Finish System. Application Guide
Exterior Insulation and Finish System Application Guide Always use the latest version of the Parex USA Application Guide. This guide focuses on the application techniques for Parex USA Exterior Insulation
Sun Windows General Information Sun New Construction Window Installation Instructions
Sun Windows General Information Section 1 G F H H H A. Apply Weather Resistive Barrier B. Apply Sill Flashing Tape C. Place Waterproof Sill Shims D. Caulk Back of Nail Fin Sides & Top, Set Window, Fasten
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
Standard Method for Sampling and Analysis of. of Chlorine Containing Bleaches. Soap Products
GUIDE SPECIFICATION FOR GENERAL CLEANING AND REMOVAL OF MOLD AND MILDEW ON EXTERIOR INSULATED AND FINISH SYSTEMS AND STUCCO DIVISION 07240 and DIVISION 09240 8/05 PART I: GENERAL 1.01 DESCRIPTION AND SCOPE
dryvitcare EIFS Repair Procedures
dryvitcare EIFS Repair Procedures DS498 Index of Documents DC001 DC002 DC003 DC004 DC005 DC006 DC007 DC008 DC009 DC009A DC010 DC011 DC012 DC013 DC014 DC015 Recommendations for Periodic Cleaning of Dryvit
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
Georgia State University. Urban Life Building Roof Replacement
ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
The Minnesota Lath and Plaster Bureau Repairing Cracks in Stucco
The Minnesota Lath and Plaster Bureau Repairing Cracks in Stucco Disclaimer: This guide contains general information on stucco installation and related materials. It is provided as a guide only and is
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
Finegan Inspection Services, Inc.
Finegan Inspection Services, Inc. Report Prepared For: Phone 513-683-0733 Fa 513-697-0163 Owners Property Address City, State, ZIP Phone FAX Owners Realtor Realty Company Phone FAX OWNER INFORMATION PROPERTY
INSTALLATION RECOMMENDATIONS. Outdoor Rubber Tiles
INSTALLATION RECOMMENDATIONS Outdoor Rubber Tiles Prior to Installation: The Outdoor Rubber Tiles and accessory transition pieces intended for this installation have been shipped to you via a freight carrier
application instructions
application instructions ARCHITECTURAL COLLECTION PRIMED BOLD PROFILE 120 SERIES LAP SIDING (D5, T4, D8, T5, Q4) General At the time of manufacture, siding meets or exceeds the performance standards set
Manufactured Stone Veneer Installation Instructions
Manufactured Stone Veneer Installation Instructions Published: 8/14/2008 Revised: 6/25/2010 Table of Contents PART 1 -- INTRODUCTION PART 2 -- MATERIAL REQUIREMENTS PART 3 EXECUTION REQUIREMENTS PART 4
ARDEX GUIDE SPECIFICATION ARDEX Exterior Concrete Repair & Resurfacing Polymer-Modified, Cement-Based, Patch & Horizontal Overlay Materials
ARDEX GUIDE SPECIFICATION ARDEX Exterior Concrete Repair & Resurfacing Polymer-Modified, Cement-Based, Patch & Horizontal Overlay Materials SECTION 03 92 50 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings,
GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
CHAPTER 25 GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER User note: Code change proposals to this chapter will be considered by the IBC Structural Code Development Committee during the 2016 (Group B)
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
RESIDENTIAL MASONRY A BEST PRACTICES GUIDE
RESIDENTIAL MASONRY A BEST PRACTICES GUIDE Build With Brick Build With Boral CONTENTS BRICK :01 MASONRY CEMENT :03 MASONRY SAND :04 WALL TIES :05 STEEL LINTELS :07 DRAINAGE WALL SYSTEM :09 FLASHING :11
G VYCOR DECK PROTECTOR
G VYCOR DECK PROTECTOR Self-Adhered Flashing Contractor s Guide DECKS AND DETAIL AREAS For longer lasting decks, install Grace Vycor Deck Protector. FROM THE MAKERS OF G Ice & Water Shield What Self-Adhered
Composite Stone Veneer
Composite Stone Veneer Installation Guide Ver 1 Jun 2015 www.compstone.com Composite Stone Veneer Installation Guide Contents Introduction & Overview 3 Required Tools 4 Optional Tools 4 Attachment Guidelines:
3.1 Water Intrusion Problems Related to Unsealed Stucco Penetrations
3.1 Water Intrusion Problems Related to Unsealed Stucco Penetrations Any penetration through the stucco that is left unsealed will allow entry of moisture. Even an average size home can have an extreme
The existing roof angle change terminations and flashings when sound and intact can be reused.
January 2, 2015 Summary Specification Re-Skinning an Existing Roof Maintenance and Repair Warranty Upgrade for Up to 30 Years Re-Skinning Over an Existing Roof with a New C-EPDM Membrane Using The Existing
Chapter 9: INSTALLING ROOFING
9.1 LEAK BARRIER (ICE AND WATER SHIELD) 9.2 SHINGLE UNDERLAYMENT 9.3 INSTALLING GUTTER APRON AND GABLE D-EDGE 9.4 INSTALLING SHINGLES 9.5 RIDGE VENT AND CAP Tools needed by each volunteer: Hammer (16 oz.
The better way to build TM. Installation Manual. EXTERIOR WALL SIPs
The better way to build TM Installation Manual EXTERIOR WALL SIPs July 2015 EXTERIOR WALL SIPs Installation Manual Table of Contents Topics General Requirements................................... 3 Materials..............................................
Dark colors will increase the surface temperature of the EIFS wall.
CSI SECTION 07 24 00 Insulation & Finish System (EIFS) - Class PB SYSTEM OVERVIEW The Standard System is a Class PB EIF System qualified for use on noncombustible construction, combustible non-residential
Although we do a fair amount of residential roofing, my family s breadand-butter. Installing a. Sealants aren t universal
Installing a Low-Slope Exposed EPDM for roof transition Exposed EPDM for resistance to ice damming Sidewall flashing Done with care, a flat roof can provide 0 years or more of leak-free service Gravel
2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS
2.18 INTERIOR & EXTERIOR FINISHES 2.18.1 VAPOR & AIR BARRIERS The LOGIX wall assembly has no need for an additional vapor barrier, the solid concrete core covered with the low permeance EPS (Type II) foam
LAYING BLOCK AND BRICK
LAYING BLOCK AND BRICK Products highlighted in this section: SAKRETE Type N Mortar Mix SAKRETE Type S Mortar Mix Brick And Block Laying Basics The first step in building a brick or block wall is to construct
INSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001)
Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for Vinyl windows with an integral nailing fin. While the use of these installation instructions
SEAMS SEAMING USING SEAM TAPE
SEAMING USING SEAM TAPE SEAMS The membrane should be positioned so that the width of the seam is 3. Remove excess chalk from a chalk line by snapping the line into the air and then chalk a line one-quarter
INSTALLATION INSTRUCTIONS for Vinyl Windows without Nailing Fin (JII011) ImPOrTANT INFOrmATION & GlOssAry. rough OPeNINGs
Thank you for selecting JELD-WEN products. Attached are JELD-WEN s recommended installation instructions for vinyl windows without a nailing fin (including finless, flush fin and flange). Read these instructions
Superform Products Ltd.
TYPICAL CORNER REINFORCING NOTE : SEE ENGINEERED REBAR SCHEDULES SUPPLIED BY THE MANUFACTURER STEEL REINFORCEMENT WALL CORNER 90 Copyright 2012 Sept. 2012 5.1.1 Rebar Spacing 6" 12" Max. Load LB./FT. 2000
OLD BRICK ORIGINALS KILN-FIRED THIN BRICK VENEER Installation Guide. GeneralShale.com
OLD BRICK ORIGINALS KILN-FIRED THIN BRICK VENEER Installation Guide GeneralShale.com OLD BRICK ORIGINALS THIN BRICK VENEER Page 2 INTRODUCTION Check local building codes for proper installation guidelines
Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide
Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
H-Stud Area Separation Wall System
12 TH EDITION 09 21 16.33/NGC H-Stud Area Separation Wall System 09 21 16.33 139 H-STUD AREA SEPARATION WALL SYSTEM The fire-protection of gypsum-based Area Separation Walls is demonstrated in dramatic
Sikaflex Sealant Installation. Sika Corporation
Sikaflex Sealant Installation 1 Critical Success Factors Substrate preparation If done properly would probably eliminate 95% of all call backs Most common mode of sealant failure Must remove all weak material
Dryvit Finish System For Exterior Soffits
Dryvit Finish System For Exterior Soffits 100% Acrylic Architectural Coatings For Use on Exterior Soffits Dryvit Finish System For Exterior Soffits Specifications DRYVIT SYSTEMS CANADA MANUFACTURER SPECIFICATION
Storage Store the siding in a dry and ventilated area. Do not place it directly on the ground. Always cover the siding after a day s work.
Installation Guide Before you begin, take the time to read this entire guide to clearly understand the requirements and steps to follow for proper installation. Warning Do not install defective material.
Brick Veneer Construction
Brick Veneer Construction Check list of suggested tools & support items Claw hammer Tape measure 3/4" [19 or 20] Wood chisel Wood or plastic shims Pry bar Utility knife Caulking and caulking gun Power
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
Avoiding Air Barrier Pitfalls
Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great
CONTENTS. General conditions 2. Material requirements 3. Terms 4. Estimating shingle requirements 4. Roof preparation 6. Shingle application 9 - 1 -
CONTENTS General conditions Material requirements 3 Terms 4 Estimating shingle requirements 4 Roof preparation 6 Shingle application 9 Shingle Shingle application application guide guide - - b a 3a 3b
ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
Renovating Your Basement
building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Renovating Your Building America Report - 0309 2003 (revised 2007) Building Science Corporation Abstract:
PART 1 GENERAL 1.1 SECTION INCLUDES
J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including
Backstop NT. Backstop NT Specifications DS180. A High Performance, Polymer-Based, Noncementitious Water-Resistive Membrane and Air Barrier
Backstop NT A High Performance, Polymer-Based, Noncementitious Water-Resistive Membrane and Air Barrier Backstop NT Specifications DRYVIT SYSTEMS, INC. MANUFACTURER S SPECIFICATION CSI MASTERFORMAT SECTIONS
Linea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1
Top plate Stud Soffit lining 45mm min nog Fix scotia bead Building underlay/james Hardie rigid air barrier Soffit Detail Building underlay/james Hardie rigid air barrier Bottom plate 25mm wide cant strip.
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS
Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING
The WANZ Guide to Window Installation
The WANZ Guide to Window Installation as described in E2/AS1 Amendment 5 Ver. 1.1 Page 2 of 74 Contents Overview Page 5 Objective Page 5 Scope Page 5 Opening Preparation Page 7 Step P1 Preliminary Check
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES
HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES 101 Retrofits Required. Pursuant to Section 553.844 553.884, Florida Statutes, strengthening of existing site-built,
Figure 1 The GENERAL CONTRACTOR blames the applicator (if available) for improper installation and
BACKGROUND History The Exterior Insulation and Finish System (EIFS) was originally developed in West Germany in the 1960s. The original market for EIFS was providing an insulation layer to existing masonry
Section 04810 EXTERIOR STONE VENEER Full Mortar
Full Mortar PART 1 GENERAL 1.1 SUMMARY A. Section includes: 1. Portland cement mortar bed 2. Stone Veneer 3. Expansion and control joints. 4. Portland cement and hydraulic mortar and grout. 5. Sealer and
Directions For Applying Malarkey Laminate Shingles
S Laminate Shingle Instructions 1 Directions For Applying Malarkey Laminate Shingles GENERAL INSTRUCTIONS Install Malarkey laminate shingles according to building code and local amendments. To qualify
Natural Thin Stone Veneer
Natural Thin Stone Veneer Until recently, if a project called for the natural look of stone but could not support its weight or thickness, the options were limited to manufactured imitation stone. More
COMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section
SPECIAL INSPECTION AND TESTING AGREEMENT INTERNATIONAL BUILDING CODE
Community Development Permit Services SPECIAL INSPECTION AND TESTING AGREEMENT INTERNATIONAL BUILDING CODE PROJECT NAME PROJECT ADDRESS PERMIT NUMBER CITY RECEIVED STAMP AND INITIALS Instructions: BEFORE
Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing
Substrate, structural panel, bonded waterproofing The universal substrate for tiles Perfect covering No matter whether you work with mosaics or large format tiles, an absolutely level substrate with straight
Durapax Coal Tar BUR Application Guide
400 Old Reading Pike, Suite 304 Pottstown, PA 19464 Tel: 610-579-9075 Fax: 610-323-0115 www.durapax.com Durapax Coal Tar BUR Application Guide DESIGN CONSIDERATIONS The proper specifications of any roof
Schluter -KERDI-BOARD Substrate, building panel, bonded waterproofing
Schluter -KERDI-BOARD Substrate, building panel, bonded waterproofing Schluter -KERDI-BOARD The universal substrate for tiles Flat. Level. Plumb. Square. No matter the quality, cost, or extravagance of
DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H
DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H Soil Drainage Mat with Built-In Protection Layer POLYGUARD DRAINAGE MATS are three-part prefabricated geocomposite drain consisting of a
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS
AC TOPSEAL SELF-ADHERED, GRANULAR SURFACED, SINGLE PLY, LOW SLOPE ROLLED ROOFING 3 X 33.3 = 100 SQ. FT. 10 YEAR MATERIAL LIMITED WARRANTY For Use on Porches / Sheds / Utility Buildings / Accessory Buildings
SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.
SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
Introduction...COMB-2 Design Considerations and Examples...COMB-3
SECTION DIRECTORY General Information Introduction...COMB-2 Design Considerations and Examples...COMB-3 Combination Assembly Recommendations and Limitations Composite Configurations...COMB-4 Typical Sealant
The Prefab Package. Modular EIFS construction offers benefits to today s busy jobsites. Building Envelope. Roland Serino, P.E., of Dryvit Systems Inc.
26 D+D MARCH 2015 Building Envelope Roland Serino, P.E., Dryvit Systems Inc. here has always been a need for a more efficient way to build in large cities like Chicago, New York, Los Angeles or other central
Sto Specification R100. Guideline Specification for Repair of Exterior Insulation and Finish (EIFS) Wall Assemblies
Sto Specification R100 Sto Corp. 3800 Camp Creek Parkway Building 1400, Suite 120 Atlanta, GA 30331 Tel: 404-346-3666 Toll Free: 1-800-221-2397 Fax: 404-346-3119 www.stocorp.com Guideline Specification
Please read the entire document before purchasing and installing any of these products
Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection
SLIDING PATIO DOOR INSTALLATION INSTRUCTIONS USING FRAME SCREWS
Vinyl Windows and Doors Manufactured by Pella Corporation Part Number: V984528 2012 Pella Corporation SLIDING PATIO DOOR INSTALLATION INSTRUCTIONS USING FRAME SCREWS Installation Instructions for Typical
Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows
Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows americancraftsmanwindows.com Project Requirements: Read
SHINGLE APPLICATION GUIDE
SHINGLE APPLICATION GUIDE CONTENTS 01. General conditions 01. Material requirements 02. Terms 07. Estimating shingle requirements 08. Roof preparation 10.Shingle application E version 2006 GENERAL CONDITIONS
Housewrap Errors. By Steve Easley
Housewrap Errors By Steve Easley There Are Seven Common Mistakes Contractors Make When Installing Housewraps Green building and remodeling programs, the U.S. Environmental Protection Agency s IAQ Plus
When dealing with a potential moisture problem, time is of the essence. Taking a proactive approach will save you money and headaches down the road.
If you own a house clad in something known as exterior insulated finish systems (EIFS), also known as synthetic stucco, you are probably trying to cope with a small but growing feeling of anxiety. You
VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD
SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation
We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.
Important Information for New Construction Installations Attention Installer! We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden
STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS
ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the
GYPSUM BOARD AND PLASTER
CHAPTER 25 GYPSUM BOARD AND PLASTER SECTION 2501 GENERAL 2501.1 Scope. 2501.1.1 General. Provisions of this chapter shall govern the materials, design, construction and quality of gypsum board, lath, gypsum
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
A. This Section includes rubberized asphalt sheet membrane waterproofing systems.
SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
AUTHORIZATION TO MARK
AUTHORIZATION TO MARK This authorizes the application of the Certification Mark(s) shown below to the models described in the Product(s) Covered section when made in accordance with the conditions set