IMPROVE SAFETY AND RELIABILITY WITH INSTANT ARC-FLASH DETECTION OVER 13,000 LITTELFUSE ARC-FLASH RELAYS INSTALLED WORLDWIDE
|
|
|
- Aldous Skinner
- 10 years ago
- Views:
Transcription
1 IMPROVE SAFETY AND RELIABILITY WITH INSTANT ARC-FLASH DETECTION OVER 13,000 LITTELFUSE ARC-FLASH RELAYS INSTALLED WORLDWIDE
2 Littelfuse Arc-Flash Relays Fast Arc-Flash Detection Circuit breakers (CBs) or overcurrent protection devices (OCPDs) alone do not provide optimal protection for your personnel and equipment. The Littelfuse Arc-Flash Relays rapidly detect an arc flash and send a trip sinal to interrupt power. PGR-8800 Arc-Flash Relay Control Power VAC/VDC Control Power VDC or Battery* Diital Inputs Outputs Trip Coil PC Connection PGA-LS10 Point Sensor Inputs PGA-LS20/PGA-LS30 Fiber-Optic Sensor Inputs CT Inputs *Backup battery not included Simp le Plu & Play Installation and Maintenance The PGR-8800 and AF0500 Arc-Flash Relays and sensors are easily retrofitted into existin switchear or pre-installed in new equipment with little or no confiuration. Even elaborate systems only take minutes to confiure usin the relays built-in USB interface software, and the innovative diital inputs/outputs on the AF0500. Improve sustainability and life of electrical equipment Lower the Hazard Risk Cateory (HRC) of the equipment Provide protection aainst equipment damae and potential injury to personnel Easily installed without chanes to existin layout Flexible sensor confiuration for any application No additional software is required Installs up to 8X Faster than Competition! Installin a Littelfuse arc-flash relay can lower your HRC ratin. See the case study at: Littelfuse.com/ArcFlashCaseStudy 2 Littelfuse.com/ArcFlash
3 in Less Than 1 ms to Minimize Damae AF0500 Arc-Flash Relay Control Power VAC/VDC Outputs Diital Inputs/Outputs Trip Coil #1 Diital Inputs/Outputs Trip Coil #2 PC Connection Control Power VDC Modbus TCP Communications Ports PGA-LS10 Point Sensor Inputs PGA-LS20/PGA-LS30 Fiber-Optic Sensor Inputs Arc Enery (I 2 t, ka 2 s) Damae Caused By Arc-Flash Incident Total ClearinTime Cable Fire Copper Fire Steel Fire The Littelfuse Arc-Flash Relays use a 125-µs liht-samplin scheme in combination with an ultra-fast IGBT output to be able to detect a developin arc flash and send a trip sinal to a circuit breaker in less than 1 ms. Relay + CB 1 ms ms Time (ms) 50 ka bolted fault between 480 VAC and round. Littelfuse.com/ArcFlash 3
4 ARC-FLASH RELAY ARC-FLASH RELAY PGR-8800 SERIES PGR-8800 SERIES Littelfuse Arc-Flash Relays Superior and Robust PGA-LS10 Point Liht Sensor Line-of-siht liht sensor detects an arc as small as 3 ka in a 2-meter half-sphere radius. Visual LED indication for Ready or Tripped state to assist with fault location Robust sensor desin can withstand a detected arc-flash event Sensor can be installed up to 50 m (164 ft) away from relay; electrical cable can be cut and easily re-terminated in the field Sensor Desin Up to 50 m cable Connect to Relay meter Half-Sphere Sensor Viewin Anle 2m 2.5m Liht Sensor PGA-LS20/PGA-LS30 Fiber-Optic Liht Sensor The 360 liht sensor detects liht throuhout the entire lenth of the fiber. Ideal to protect bus bars, multiple compartment installations like motor control centers, or areas with many obstructions. Visual LED indication for Ready or Tripped state to assist with fault location Durable resin fiber material allows small bendin radius (>5 cm) and reater flexibility without breakin Ready to install from the factory, no need to terminate in the field or polish as with lass fiber Fiber sensors can be installed in locations up to 50 m (164 ft) away from relay; electrical cable can be cut and easily re-terminated in the field Connect to Relay Black Shield (no liht detection) Receiver Up to 50 m cables Fiber-Optic Sensor 360 Liht Detection PGA-LS20 (8 m/26.2 ft*) PGA-LS30 (18 m/59 ft*) * Distance of liht-detectin fiber Sensor Placement Recommendations Generally, it is recommended to mount 1 or 2 sensors per cubicle to cover all horizontal and vertical bus bars, breaker compartments, drawers, and anywhere that there is potential for an arc fault. Threadin a fiber-optic sensor throuh the cabinets and in areas where point-sensor coverae is uncertain results in complete coverae and an added level of protection. Even if policy is to only work on de-enerized systems, all maintenance areas should be monitored for arc flash to prevent potential damae and additional cost. For more information, download the Installation Guide PF711 from Littelfuse.com/ArcFlash. Transmitter Arc Flash Fiber-Optic Sensor Point Sensors Scenario with point sensor placement on the wall of each compartment. Arc detection area for each sensor is shown in reen shade. In this case, both Point Sensor 1 and the Fiber-Optic Sensor detected the flash as it was within their viewin area (shown in orane). 4 Littelfuse.com/ArcFlash
5 Current Transformers Application Example PGR-8800 Fiber-Optic Sensor Transmitter Fiber-Optic Sensor Receiver Point Sensor Circuit Control Power & Battery Back-up PGA-LS20 and PGA-LS30 Detects liht 360 alon the entire lenth of the exposed fiber. Sensor is pre-wired with 10 m (expandable to 50 m) of electrical cable and a plu-in terminal block. Point Sensor Electrical Cables To Relay Upstream Application Example AF0500 PGA-LS10 Detects liht at 180 anle in line of siht. Sensor is pre-wired with 10 m (expandable to 50 m) of electrical cable and a plu-in terminal block. Connection Trip 1 Trip 2 Tie Trip 2 Trip 1 Sends trip sinal to breaker trip coil (undervoltae or shunt trip) to interrupt power. Ability to trip upstream breaker if local breaker fails. Fiber-Optic Sensor Fiber-Optic Sensor Current Transformers Transmitter Source 1 Point Sensor Receiver Transmitter Source 2 Receiver Optional, PGR-8800 only Measures current to help eliminate nuisance trips. Littelfuse.com/ArcFlash 5
6 Littelfuse Arc-Flash Relays Reliable Operation with When you are entrustin a safety device to protect equipment from catastrophic damae, it is important to know that it will operate as expected. Littelfuse Arc-Flash Relays do this by havin built-in redundancies and health monitors, makin maintenance and installation tasks faster, more efficient and helpin to minimize downtime. Redundant Internal Trip Path Two internal trip paths for added reliability if the microprocessor trip path fails, the backup analo trip path will seamlessly take over, sendin an alarm notification to operators Backup analo trip path initializes very quickly upon power up, ensurin protection is enabled while enerizin the system when hazard risk is hiher Health Monitorin Continuously monitors connection to trip coil to ensure path is intact LED indication of sensors Ready or Tripped status on sensor and relay Sensors are durable enouh to withstand a detected arc-flash event Reliable Liht Detection Two types of liht sensors (point and fiber-optic) for different applications Adjustable liht-level and wide-anle detection add flexibility Durable and flexible sensor desin eliminates breakae and re-work Upstream Trippin Ability to trip upstream device if the local breaker fails to clear the fault Optional Current Detection for Fault Verification Avoid nuisance trippin with current-supervised arc-flash trips Phase Current Transformers for overcurrent detection Two user-defined definite-time overcurrent protection levels and times Tie Trippin Ability to trip both incomin feeder and tie breaker when arc is detected in one section of a switchboard Affected part of the switchboard is isolated from the non-affected part Zone Trippin Ability to trip 2 separate zones with 1 relay Sensor zone assinment throuh simple PC confiuration and/or diital inputs and outputs Built-In Redundancies PGR-8800 AF Littelfuse.com/ArcFlash
7 AF0500 Arc-Flash Relay Technical Specifications PGR-8800 Arc-Flash Relay Relay Part Nos. Sensor Inputs Sensor Part Nos. IEEE Device No. Input Voltae Dimensions Optical Trip Settins Trip Coil Output Relay Outputs Communications System Expansion Sensors Battery Approvals Warranty Mountin PGR PGR CC (conformal coatin) 6 liht sensor inputs for PGA-LS10, PGA-LS20 and PGA-LS30 sensors PGA-LS10 (Point) PGA-LS20 (Fiber-Optic) PGA-LS30 (Fiber-Optic) Overcurrent (50), Arc Flash (AFD) Vac, Vdc, or Vdc H 130 mm (5.2 ) W 200 mm (7.9 ) D 54 mm (2.2 ) 9-25 klux <1 ms; IGBT switch Current Ratin: Voltae Ratin: 750 ma cont. 24 to 300 Vac 20 A for 2 s 24 to 300 Vdc 10 A for 5 s Prorammable Form C Output Contact: 5 A at 250 Vac/30 Vdc Status Output Contact: 3 A at 50 Vac/50 Vdc RS-485, Modbus RTU Link up to 4 units Up to 24 (6 per unit) 24 V lead-acid el cell (not included) CE, UL Listed (UL508), C-Tick, CSA, DNV 5 years DIN, Surface Mount PGA-LS10 Point Sensor Type Detection Radius Trip Status LED Health Status LED Electrical Cable Relay Part Nos. Sensor Inputs Sensor Part Nos. IEEE Device No. Input Voltae: Dimensions Optical Trip Settins Trip Coil Outputs Communications System Expansion Sensors Approvals Warranty Mountin AF AF CC (conformal coatin) 4 liht sensor inputs for PGA-LS10, PGA-LS20 and PGA-LS30 sensors PGA-LS10 (Point) PGA-LS20 (Fiber-Optic) PGA-LS30 (Fiber-Optic) Arc Flash (AFD) 100 to 240 Vac, 110 to 250 Vdc or Vdc H 130 mm (5.1 ) W 200 mm (7.9 ) D 54 mm (2.1 ) klux <1 ms; IGBT switch Current Ratin: Voltae Ratin: 750 ma cont. 24 to 300 Vac 20 A for 2 s 24 to 300 Vdc 10 A for 5 s Ethernet, 2 ports with internal Ethernet switch, Modbus TCP Unlimited 4 per unit CE, UL Listed (UL508), C-Tick 5 years Surface, DIN (with optional D0050 adapter clips) PGA-LS20/LS30 Fiber-Optic Sensors Type Fiber-optic liht sensor Detection Radius 360 Line-of-siht liht sensor Trip Status LED Displays tripped state on each sensor Health Status LED Displays ready state on each sensor Sensor Lenth PGA-LS20: 8 m (26.2 ft) active; 10 m (32.8 ft) total PGA-LS30: 18 m (59 ft) active; 20 m (66 ft) total Electrical Cable 10 m (32.8 ft) included, expandable to 50 m (164 ft) PGA-1100 Diode Loic Unit Point liht sensor 180 Line-of-siht liht sensor Displays tripped state on each sensor Displays ready state on each sensor 10 m (32.8 ft) included, expandable to 50 m (164 ft) Type Diode Loic Unit Diodes 1000V reverse voltae, 3 A continuous, 25 A for 1 second Certification CE Dimensions H 70 mm (2.76 ) W 20 mm (5.9 ) D 80 mm Go to Littelfuse.com/ArcFlashCaseStudy to Download the Case Study relay not been there, Hadtheythiswere lookin at $800,000 to $1 million of cost... Tim Deschamp, Evans Enterprises, USA Littelfuse.com/ArcFlash 7
8 Local Resources for a GLOBAL Market Littelfuse products help protect electrical equipment used in marine, minin, petrochem and eneral industrial applications. We offer a broad and reliable selection of fuses, fuse blocks, protection relays and enerator controls to improve safety and reduce downtime. Bellinham Calary Piedras Neras Muzquiz For decades, we have helped OEMs, electrical installers, desin enineers and end-users select the riht product for their applications. Today, Littelfuse offers a broader rane of products addressin protection and control needs while still providin the same reat service and support that customers have learned to expect. Saskatoon Rapid City Chicao Champain Lake Mills Baldwinsville Boston Matamoros São Paulo Trollhättan Roskilde Swindon Norwich Bremen Kaunas Noida Wuxi Suzhou Donuan Shenzhen Seoul Sinapore Shanhai Taipei Hon Kon Lipa City Yokohama Littelfuse electrical product portfolio includes: Industrial Littelfuse World Headquarters 8755 West Hiins Road, Suite 500 Chicao, IL USA Tel: Fax: [email protected] Littelfuse Startco 3714 Kinnear Place Saskatoon, SK S7P 0A6 Canada Tel: Fax: [email protected] Littelfuse Selco Betonvej 10 DK Roskilde Denmark Tel: Fax: [email protected] Littelfuse SymCom, Inc. 222 Disk Drive Rapid City, SD USA Tel: Fax: [email protected] /ARCFLASH Step-by-Step Instructions For Every Stae of Your Decision Process Visit Our Online Library at Littelfuse.com/ArcFlash Visit Our Online Library at Littelfuse.com/ArcFlash 1. Research TECHNICAL DOCUMENTS White Paper: Key Considerations for Selectin an Arc-Flash Relay (PF765) Technical FAQ VIDEOS Overview of Arc-Flash Relay and Applications Features, Benefits and Installation of the PGR-8800 and the AF Desin & Specification PRODUCT LITERATURE Datasheet Users Manual Guideform Specification LITERATURE APP Literature App is available for Apple devices only. Search for Littelfuse in the App Store. 3. Purchase Decision Use our Workbook to quantify the impact of the PGR-8800 and AF0500 before you buy. The Littelfuse Arc-Flash Incident Enery Reduction Workbook (PF710) helps create a preliminary calculation of the reduction of Incident Enery by applyin the PGR-8800 or AF0500 Arc-Flash Relay. It offers a typical scenario calculation as defined per IEEE Installation & Maintenance PRODUCT LITERATURE Application Guide (PF711) Commissionin Check-list (in Application Guide) 5. Post-Installation Support Technical support from our professional enineers at Littelfuse products are certified to many standards around the world. To check certifications on specific product please refer to the product datasheet on Littelfuse.com Littelfuse, Inc. Printed in USA. Specifications, descriptions and illustrative material in this literature are as accurate as known at the time of publication, but are subject to chanes without notice. Visit Littelfuse.com for the most up-to-date technical information. Form: PF136 Rev:
PGR-8800 & AF0500 ARC-FLASH RELAY
PGR-8800 SOLAR & AF0500 PRODUCTS ARC-FLASH RELAY CATALOG TECHNICAL FAQ TABLE OF CONTENTS General Arc-Flash, PGR-8800, and AF0500 Information How much energy is in a typical arc-flash incident?...4 What
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
How to reduce exposure to arc flash hazards
GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not
misconceptions about arc-flash hazard assessments
misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
LightSweep. Modular Lighting Control System. imagination at work. Description. Specifications
Lihtin Controls LihtSweep Modular Lihtin Control System GE s modular indoor lihtin control solution is scalable and hihly flexible makin it easier to meet specification without havin to over-enineer the
New standardized approach to arc flash protection
New standardized approach to arc flash protection Samuel Dahl Juha Arvola Tero Virtala Arcteq Relays Ltd Arcteq Relays Ltd Arcteq Relays Ltd Wolffintie 36 F 11 Wolffintie 36 F 11 Wolffintie 36 F11 65200
Process Alarm Solutions
Process Alarm Solutions Reliable Supervision and Control www.selco.com SELCO flexible alarm panels for supervision and control SELCO provides efficient and reliable solutions for alarm monitoring of electrical
Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer [email protected]. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer [email protected] Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
ISIO 200. Binary Input/Output (I/O) Terminal with IEC 61850 Interface
ISIO 200 Binary Input/Output (I/O) Terminal with IEC 61850 Interface Compact and Easy ISIO 200 Put your Binary I/Os where you need them ISIO 200 is a simple and versatile binary I/O terminal with IEC 61850
Extend the Life of Existing Switchgear
Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE
SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy
Switchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
Paralleling Switchgear
Paralleling Switchgear By Maurice D Mello, P.Eng. Systems Engineer, GE Consumer & Industrial, Canada What is Paralleling? Paralleling is the operation in which multiple power sources, usually two or more
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
Part 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
Regards from the Team at Rheology Solutions.
Rheology Solutions is the sole Australian distributor of this product range and we welcome the opportunity of discussing your application requirements. We hope the information you are seeking is contained
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Short Form Catalogue. Alarm Systems. Reliable Supervision and Control
Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.
Medium voltage arc flash eliminator units VAM 3ED,
Medium voltage arc flash eliminator units VAM 3ED,, Medium voltage arc flash eliminator units Medium voltage arc flash eliminator units The new innovative arc eliminator VAM 3ED is an extremely fast acting
SWITCHGEAR. EGP Switchgear
SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all
OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B
OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B The OVR-3SP three-phase recloser style guide aids in the proper selection of your OVR-3SP style number. The OVR-3SP
Technical Publication
Technical Publication Advancin Thermal Mass Gas Flow Meters By Gerardo Varas, Sr. Member Technical Staff Fluid Components International (FCI) Visit FCI online at www.fluidcomponents.com FCI is ISO 9001:2000
IMVIB. Online vibration monitoring for Ariel compressors
IMVIB Online vibration monitoring for Ariel compressors The cost-effective way to add spectral vibration measurement & trending on critical machinery Monitoring vibration trends of your industrial equipment
API Marine. BMS Presentation. Ballast Measurement Systems
API Marine BMS Presentation Ballast Measurement Systems BMS4 Typical Configuration BMS4 Typical Configuration BMS4 Extended Configuration BMS4 System (24 tanks) Air regulator Terminal block Drain/Air Filter
Buckeye Detection Systems Fixed Detection Systems Application Survey
Buckeye Detection Systems Fixed Detection Systems Application Survey Channel Partner Representative : Company Name: Representative: BDS Representative: Client Contact Information : Company Name: Company
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,
Arc Flash Energy Mitigation Techniques
Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal
C441 series communication modules Accessories for electronic overload relays and soft starters. Monitoring and control made simple
C441 series communication modules Accessories for electronic overload relays and soft starters Monitoring and control made simple Monitoring and control made simple C441 series communication modules Eaton
JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410
The INTEG is an Ethernet I/O (digital, analog) device that monitors and controls a small set of process signals. functions as both basic I/O for integration with another application or system AND as a
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
Catalog. Arc Guard System TM TVOC-2
Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already
OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F
OVR Three-Phase Recloser and PCD Control Style Guide 1VAL264001-SG October 13, 2009 Revision F The OVR three-phase recloser style guide aids in the proper selection of your OVR three-phase style number.
T1 Backhaul Connectivity Solution All Products :: Application Note
Telect 1 RU Customer Interface Panel (CIP) Enables Demarcation, Remote Circuit Maintenance and Trouble Isolation at the Backhaul Node The Application: T1 Demarcation and Testing in Backhaul Environments
Inverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
Chapter 28B - EMF and Terminal P.D. A PowerPoint Presentation by Paul E. Tippens, Professor of Physics Southern Polytechnic State University
Chapter 28B - EMF and Terminal P.D. A PowerPoint Presentation by Paul E. Tippens, Professor of Physics Southern Polytechnic State University 2007 Objectives: After completin this module, you should be
Enhancing Personnel Safety with Arc Resistant Equipment
Enhancing Personnel Safety with Arc Resistant Equipment Carl Christian Power LV Offer Marketing Nashville, TN Sponsored by the Water Wastewater Competency Center 1 Enhancing Personnel Safety 5-10 Five
Application/Connection Examples
This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
Mission Critical Data Center Systems
Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,
UFES Active protection for switchgear
Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
Choosing the Best Solution for Reducing Arc Energy
CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors
NEW. EVEN MORE data acquisition and test stand automation
NEW EVEN MORE data acquisition and test stand automation the new class of data The plug&play complete package User benefits Expert Series is the latest generation of data acquisition Complete hardware
Self Monitoring Power Supply (BPSM)
LIFETIME REPLACEMENT WARRANTY Self Monitoring Power Supply (BPSM) Application - When interfacing with a fire alarm system where the system s auxiliary relay cannot handle the full current potential of
Tmax MCCBs. Molded case circuit breakers. Tmax
Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high
Applications. Remote Display Mounting Kits
June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge
DREXELBROOK. USonic-R Series. Ultrasonic Level Measurement System. User Friendly
DREXELBROOK A Leader In Level Measurement Solutions USonic-R Series Ultrasonic Level Measurement System User Friendly Set the measurement range directly in inches, feet, millimeters, centimeters, or meters
Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear
Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Index 3 Overview 4 Standard Levels 6 Monitoring & Control 7 Measurements 8 Protection & Logic
Eaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT
Products and solutions for pumping, irrigation and piping
Products and solutions for pumping, irrigation and piping 100% electricity www.lovatoelectric.com Tra dition and Innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric
Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical
Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical Victor Lee Commercial Marketing Manager SEA Eaton Oil & Gas Solution Tech Day 2013 Eaton. All Rights Reserved. Eaton is a leading
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.
Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible
Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION
Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature
User Manual Revision 2.201 English
Document code: MN67117_ENG Revision 2.201 Page 1 of 14 User Manual Revision 2.201 English CANopen Repeater Small (Order Code: HD67117 HD67117M HD67117-M12 HD67117R) HD67117 HD67117M HD67117-M12 HD67117R
Wireless Solutions BROCHURE
Wireless Solutions BROCHURE JUNHO 0 [email protected] www.novusautomation.com REV0 Temperature and RH Wireless Transmitter ISO 900 EMPRESA CERTIFICADA Introduction The is a wireless transmitter
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C
Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C DESCRIPTION FEATURES PRODUCT DATA Very low operating trip points LED status indication Integral DIN rail mounting
Technical Guide. SKM Arc Flash Line Side vs. Load Side
SKM Arc Flash Line vs. Load The option of choosing the line-side or the load-side arc flash incident energy for arc flash labels is an important decision when performing an arc flash hazard analysis. When
4-Port 10/100Mbps with PoE + 1-Port 100FX Industrial Ethernet Switch Wide Temperature
4-Port 10/Mbps with + 1-Port FX Industrial Ethernet Switch Wide Temperature 15 F Fiber Optic Link Capability for Flexible Distance Extension The series equips one Base-FX port that provides more flexibility
Bypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
Safety By Design. Strategies for Electrical Contractors
Safety By Design Strategies for Electrical Contractors Introduction Engineering and system design significantly impact worker safety System design provides opportunity to eliminate/minimize workers exposure
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
Reliability requires consulting engineers and end users to grasp design, maintenance basics. By Reza Tajali, P.E. Square D Power Systems Engineering
LOW VOLTAGE CIRCUIT BREAKER GUIDELINES FOR DATA CENTERS Reliability requires consulting engineers and end users to grasp design, maintenance basics By Reza Tajali, P.E. Square D Power Systems Engineering
Installation Instructions. Wireless Adapter/Repeater. Introduction. 30-3001-887 Rev C
/Repeater Installation Instructions 30-3001-887 Rev C Workstation Ethernet bcx Controller Repeater Repeater Introduction Schneider Electric has designed a device that allows Andover Continuum controllers
Industrial RS-232/ RS-422/ RS-485 over Ethernet Media Converter
ICS-2 S15 Industrial RS-232/ RS-422/ RS-485 over Ethernet Media Converter Cost Effective Solution for RS-232 / RS-422 / RS-485 to Industrial Ethernet Application PLANET ICS-210x series Smart Media Converter
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software Abstract: The nature of explosive equipment failures, and the rate of serious burn injuries in the electrical industry
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application by Reza Tajali, P.E. Square D Company ABSTRACT In modern data centers, Uninterruptible Power Supplies (UPS)
Application Note: Monitoring Branch Circuit Loads in Critical Facilities
Application Note: Monitoring Branch Circuit Loads in Critical Facilities Description of application: The AcquiSuite data acquisition server (DAS) from Obvius is used to monitor the electrical loads and
The Application of Circuit Breakers to Reduce Downtime in Datacentres
The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the
PROCESS AUTOMATION REMOTE I/O SYSTEMS RPI REMOTE PROCESS INTERFACE IN THE SAFE AREA OR IN ZONE 2
PROCESS AUTOMATION REMOTE I/O SYSTEMS RPI REMOTE PROCESS INTERFACE IN THE SAFE AREA OR IN ZONE 2 PEPPERL+FUCHS IN PROCESS AUTOMATION PEPPERL+FUCHS COMPANY OVERVIEW BUSINESS OVERVIEW Pepperl+Fuchs offers
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
2G-1.1.0, 200M-2.0.3, 200M-1.0.1
Unmanaged PoE Switches and Media Converters of LAN-BUS System, 200M-2.0.3, SWITCH* MEDIA CONVERTER* RACK IP65 I Bus/ star topology I MM/SM universal I Overvoltage protections I Working temperature 40 +70
Executive Summary. Technical Description
Executive Summary The Cellwatch system is built using modules. The majority of the system is constructed with Data Collection Modules (DCMs). The DCMs are optically linked to Control Units (CUs) that in
MechoNet TM Network Interface (MNI) Specification Submittal
MechoNet TM Network Interface (MNI) Specification Submittal Models MechoNet Network Interface: MNI RJ (RJ45 Motor Ports): Stock No.: IMNI 0001 TP AS (US version) Stock No.: IMNI 0004 TP AS (UK version)
MTI10 Insertion and MTL10 In-line Thermal Mass Flowmeter and Temperature Transmitter
Thermal Mass meter and Temperature Transmitter Description The MTI10 insertion thermal mass flowmeter and the MTL10 in-line thermal mass flowmeter provide accurate mass flow measurement of clean, dry gases
Content. TITAN VC2 Video Encoder/ Decoder from Page 5 Overview. SDSL Modems from Page 7 for Video transmission over 2 Mbit/s
Content TITAN VC2 Video Encoder/ Decoder from Pae 5 Overview SDSL Modems from Pae 7 for Video transmission over 2 Mbit/s TITAN VC2-2M from Pae 9 for Video transmission over 2-Mbit/s Leased Lines TITAN
Controller board and power supply for vivimat III systems
Controller board and power supply for vivimat III systems Ref: VIVIMAT-3.0 The controller board and power supply vivimat 3.0, is the central core of the vivimat III home automation system. The vivimat
Reference Design. conference rooms
Reference Design conference rooms Tomaro Design Group conference rooms The modern commercial conference room embraces communication and multi-media technology from projectors and video conferencing, to
SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE
Series Circuit Breaker Monitors CONSOLIDATED Electronics, Inc. MONITORING THE FUTURE Why SF Gas Density Monitors? 6 Cut Maintenance Costs Your capital investment may be recovered with the elimination of
Arc Flash Mitigation & Selective Co-ordination
Arc Flash Mitigation & Selective Co-ordination Michael Hodder March 2015 Overview This seminar will provide information on: Mitigating arc flash hazards Selective Coordination What can we do to make these
BIS Automation Engine
BIS Automation Engine Installation manual en English BIS Automation Engine en Table of Contents Legal 5. Trademarks 5. Software License Agreement 5.. Limited Warranty 5.. Remedy 6 Introduction 7. About
SMART SENSOR COLLECTION
TEMPERATURE SENSOR This sensor measures temperature in degrees Celsius or Fahrenheit. It works with all SensorHawk base units (SensorHawk-2, SensorHawk-8 and SensorHawk8/20) as well as the SecurityHawk-8
PLA 44. Power quality analyzer. User and service manual. BMR trading
PLA 44 Power quality analyzer User and service manual version 1.2 BMR Lipovka 17 516 01 Rychnov n. Kn. 1 Tel: +420 774 415 703 Fax: +420 494 533 602 Content 1. Front panel...3 5.6.1. List of events...8
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
How To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection
Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection L. Kumpulainen, S. Dahl J. Ma Vamp Ltd, Finland Vamp Ltd, China 1 ABSTRACT This paper describes causes and characteristics