Technical Guide. SKM Arc Flash Line Side vs. Load Side

Size: px
Start display at page:

Download "Technical Guide. SKM Arc Flash Line Side vs. Load Side"

Transcription

1 SKM Arc Flash Line vs. Load The option of choosing the line-side or the load-side arc flash incident energy for arc flash labels is an important decision when performing an arc flash hazard analysis. When an engineer performs an arc flash hazard analysis for any electrical equipment that includes a main overcurrent protection device (OCPD), there is a possibility of choosing between two distinct values of incident energies. They are referred to as the Line- or the Load- values. See Figures 1 and 2. Figure 1 Figure 2 This choice could greatly affect the maintenance procedures of the electrical equipment. If the line-side incident energy - which is normally higher than the load-side incident energy - is chosen for the complete panel, the personal protective equipment (PPE) requirements would be more stringent than that required if the load-side incident energy was chosen. When working on the incoming section of the enclosure (where the main OCPD is located), there could be an arc flash event on the line-side of this main OCPD. In this case, the electrician will be normally exposed to the higher incident energy value and he should be wearing higher rated PPE. When working on the feeder sections (on the load-side of the main OCPD), the electrician will normally be exposed to the lower incident energy value and could be wearing lower rated PPE. Nevertheless, you have to consider what would occur if the electrician is working on a feeder section adjacent to the incoming section. Normally, the arc flash is initiated by human error, but an arc flash event on the line-side could also occur while working on a feeder section (adjacent to the incoming section and without any human influence) due to insulation failure, lack of maintenance, overvoltages, animals, etc. Many switchboards and switchgears do not have strong and reliable barriers or isolation between the incoming section and the adjacent feeder sections. See Figure 3. Therefore, if this arc flash event would occur on the line-side, the electrician working on the adjacent feeder section (protected only for lower load-side incident energy), he will probably be exposed to a higher incident energy than he is protected for. Therefore, which value of incident energy should be shown in the equipment arc flash label? There are many options for solving this issue. Three of them are the most common:

2 Figure 3 1. Label the electrical equipment with only one incident energy value, the higher line side value. This will require the electrician to wear the highest rated PPE even while working on feeder sections at the load-side of the main OCPD. 2. Label the equipment with a dual-value incident energy. One higher incident energy that applies only while working on the line-side of the main OCPD (the incoming section) an another lower value of incident energy while working on the load-side of the main OCPD (feeder sections). If the electrician is working on a feeder section adjacent to the incoming section of an open-framed switchboard, additional analysis should be performed to insure that the worker will be protected by the higher incident energy from the line-side that could migrate to the adjacent feeder section. Note: The fact that an electrical equipment, where the main OCPD is installed, has a barrier that seems strong enough between the incoming section and the adjacent sections is not an acceptable condition to consider using dual-value incident energy arc flash labels. The engineer can t assume that an arc flash event on the line-side of the main OCPD will be totally contained (will not migrate to the adjacent sections). Therefore, under this circumstance, it is not acceptable to have an arc flash label with dual values, one for the incoming section and one for the rest of the switchgear. Note: Only arc-resistant with Suffix C switchgears (applicable to low or medium voltage switchgears) built in compliance with ANSI/IEEE C standard can insure that the dangerous power of the higher line-side incident energy from the incoming section will not migrate to the adjacent feeder section. Therefore, under this circumstance, it is acceptable to have an arc flash label with dual values, one for the incoming section and one for the rest of the switchgear. 3. Label the electrical equipment with only one incident energy value, the lower load-side value. This will require the electrician to wear the lower rated PPE even while working on the incoming section. According to the previous discussion, it is hard to understand why and engineer would choose to

3 show the load-side value of incident energy on the label associated with the entire electrical equipment. Why is the Line- and Load- Incident Energy Different? The line-side incident energy value is normally higher than the load-side value because at the line-side the main OCPD is not involved in the clearing of the largest component of the arcing fault current. The main OCPD will only see the motor and generator contribution to the fault on the load-side of the main OCPD, which is normally much lower than the utility contribution to this fault and contributes the least amount of incident energy at that location. The OCPD that will interrupt the higher arcing current from the utility is upstream from this main OCPD and is normally is much larger. Higher ampere rated OCPD normally will result in longer interrupting time and therefore higher incident energies. When is the Load- Incident Energy Higher than Line- Incident Energy? There are, nevertheless, some few instances where the load-side incident energy is higher than the line-side incident energy. This might occur when there is a large motor contribution on the load-side bus. An example of this situation is shown on Figure 4, where we have several small motors (less than 50 HP) totaling 765 HP modeled as a single equivalent motor connected directly to the bus of a motor control center (MCC). Under these conditions, the load-side incident energy is more than twice as large as the lineside incident energy. Figure 4

4 Modeling the Line- vs. Load- option in the Arc-Flash module of SKM Power*Tools for Windows software One possible option to model the load-side vs. line-side incident energy is shown in Figure 4. Place a bus immediately upstream from the main OCPD. You could rename this bus with the name of the electrical equipment and add some indication that shows that this bus is the line-side bus. In Figure 4 the line-side bus is designated as MCC-1 (LINE SIDE). We want the load-side of this main OCPD to be connected directly to the bus of the electrical equipment. In Figure 4 that bus would be MCC-1. But in the Power*Tools software we can t have an OCPD connected directly between two buses without an impedance. To solve this challenge, we can insert a non-existing impedance (cable) between the load-side of the main OCPD and the equipment bus. This cable does not exist, so it should be modeled with very low impedance and it s symbol should be changed to show just a line (See Figure 4). Now you can calculate the line-side incident energy and the load-side incident energy by using the Arc Flash software module and use the options as shown in Figure 5. Figure 5 After the Arc-Flash module finishes the calculations, the results table will show the load-side incident energy at bus MCC-1 (2.2 cal/cm^2) and the line-side incident energy (0.99 cal/cm^2). See Figure 6. Figure 6 In this particular case the label attached to the equipment should show the higher incident energy calculated for the load-side bus. Conclusions 1. When any electrical equipment has a main OCPD, there are two levels of incident energy, one at the line-side of the main OCPD and one at the load-side. 2. Normally, the line-side incident energy is equal or larger than the load-side incident energy. There are few instances where the load-side incident energy is higher than the line-side incident energy. 3. The majority of the electrical equipment are not Arc-Rated tested to accepted standards.

5 4. If electrical equipment is not Arc Rated according to recognize standards (that insures the containment of the arc flash energy in the faulted section without any migration of energy to the adjacent sections) we do not have any guarantee that this migration will not happen, even when barriers exist between adjacent sections. 5. Every electrical equipment that has a main OCPD could be modeled in Power*Tools for Windows as having a line-side bus and a load-side bus and perform the arc flash calculation in both locations. 6. Under normal circumstances, the consultant performing the arc flash hazard analysis should print the label for this equipment with the higher incident energy. 7. There are some exceptions to this general rule, but these exceptions should be analyzed with care, considering maintenance procedures that would justify that decision.

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE

More information

RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA

RISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA RISK MITIGATION for ELECTRICAL WORK Feb 2013 San Diego CA Agenda I. RISK Define the Risks Arc Flash Review II. MITIGATION 3 Easy Steps New Designs Vs. Existing Systems III. DUKE UNIVERSITY EXAMPLE I. Risk

More information

misconceptions about arc-flash hazard assessments

misconceptions about arc-flash hazard assessments misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.

More information

Safety By Design. Strategies for Electrical Contractors

Safety By Design. Strategies for Electrical Contractors Safety By Design Strategies for Electrical Contractors Introduction Engineering and system design significantly impact worker safety System design provides opportunity to eliminate/minimize workers exposure

More information

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock.

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer DanRNeeser@Eaton.com. Electrical Hazards 2/18/2015. Shock. Arc Flash Hazards Dan Neeser Field Application Engineer DanRNeeser@Eaton.com Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of

More information

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety

More information

Engineering Series Ratings: Is It Practical?

Engineering Series Ratings: Is It Practical? Engineering Series Ratings: Is It Practical? By the National Electrical Manufacturers Association The 2005 National Electrical Code (NEC) introduces a change regarding series ratings for circuit breakers

More information

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible

More information

Part 1 System Modeling & Studies for Existing Systems

Part 1 System Modeling & Studies for Existing Systems Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures

More information

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce

More information

Understanding Arc Flash

Understanding Arc Flash Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which

More information

2013WWOA Conference Technical Conference Program

2013WWOA Conference Technical Conference Program 2013WWOA Conference Technical Conference Program Understanding Arc-Flash Hazards, Its Implications on Operations and Solutions that Mitigate Such Exposure Presented by Jerry Baskin Senior Product Manager

More information

Choosing the Best Solution for Reducing Arc Energy

Choosing the Best Solution for Reducing Arc Energy CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors

More information

Arc Flash Energy Mitigation Techniques

Arc Flash Energy Mitigation Techniques Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal

More information

NFPA 70E Updates Affect Your Most Valuable Assets

NFPA 70E Updates Affect Your Most Valuable Assets NFPA 70E Updates Affect Your Most Valuable Assets EXECUTIVE SUMMARY Electrocution is a well-known hazard associated with direct contact with electrical energy. According to the U.S. Department of Labor,

More information

A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software

A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software Abstract: The nature of explosive equipment failures, and the rate of serious burn injuries in the electrical industry

More information

Analyzing Electrical Hazards in the Workplace

Analyzing Electrical Hazards in the Workplace Analyzing Electrical Hazards in the Workplace By Dennis K. Neitzel, CPE AVO Training Institute, Inc. The need for analyzing electrical hazards in the workplace has been recognized by a small segment of

More information

! WARNING Arc Flash and Shock Hazard Appropriate PPE Required

! WARNING Arc Flash and Shock Hazard Appropriate PPE Required Arc Flash Hazard Labeling Do s and Don ts! WARNING Arc Flash and Shock Hazard Appropriate PPE Required 11' - 3" Flash Hazard Boundary 9 cal/cm2 Flash Hazard at 18 inches #3 PPE Level Cotton underwear plus

More information

The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS

The Other Hazard of Electricity. Larren Elliott Ph.D. Lindsay Polic, CSP, REHS The Other Hazard of Electricity Larren Elliott Ph.D. Lindsay Polic, CSP, REHS Presenters Larren Elliott Ph.D. EORM Electrical Safety Service Partner 45 years practical and hands-on industrial experience

More information

2008 Eaton Corporation. All rights reserved.

2008 Eaton Corporation. All rights reserved. FlashGard TM Motor Control Center Electrical Safety Hazards Design Philosophy The Product 2008 Eaton Corporation. All rights reserved. Research studies say. Five to 10 arc flash explosions occur in electrical

More information

Mission Critical Data Center Systems

Mission Critical Data Center Systems Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,

More information

Low Voltage Switchgear

Low Voltage Switchgear Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering

More information

How to reduce exposure to arc flash hazards

How to reduce exposure to arc flash hazards GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not

More information

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth

More information

What s up with Arc Flash?

What s up with Arc Flash? What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition

More information

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009 A Comparison of Contemporary Electrical Distribution Equipment Standards San Francisco IEEE Industry Applications Society May 26, 2009 What are Standards? Clearly defined performance characteristics Based

More information

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.

ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH HAZARD OVERVIEW Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH EXPERIENCE Christopher J. DeWaal, MS, MEM, PE, LEED AP, HACCP How did I get involved? A client

More information

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,

More information

New standardized approach to arc flash protection

New standardized approach to arc flash protection New standardized approach to arc flash protection Samuel Dahl Juha Arvola Tero Virtala Arcteq Relays Ltd Arcteq Relays Ltd Arcteq Relays Ltd Wolffintie 36 F 11 Wolffintie 36 F 11 Wolffintie 36 F11 65200

More information

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY 2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

Implementation of arc flash mitigating solutions at industrial manufacturing facilities

Implementation of arc flash mitigating solutions at industrial manufacturing facilities Thought leadership White paper Implementation of arc flash mitigating solutions at industrial manufacturing facilities David B. Durocher Senior Member, IEEE Global Industry Manager Eaton 26850 SW Kinsman

More information

Arc Flash Standards - Australian Developments

Arc Flash Standards - Australian Developments Session 12 Arc Flash Standards - Australian Developments Peter Willis Principal Engineer, DIgSILENT Pacific ABSTRACT Across the world, Arc Flash Hazard studies have emerged as a engineering service centred

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short

More information

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS By: Gabriel Arce, ABB, San Luis Potosi, Mexico Casey McCollum, ABB, Houston, TX John

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont Test Before Touch Easier Said Than Done Ken Crawford, DuPont Kent Haggerty, Dupont Overview Test Before Touch (TBT) Principles Key Learnings by One Company One Method for Performing a TBT Induced Voltages

More information

Arc Flash Mitigation. Executive summary. by Antony Parsons, Ph.D., P.E.

Arc Flash Mitigation. Executive summary. by Antony Parsons, Ph.D., P.E. by Antony Parsons, Ph.D., P.E. Executive summary Arc flash events can result in significant injury to workers, including severe burn injuries. The most effective arc flash safety programs are not those

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

2012 NFPA 70E. Ten Most Important Changes. John A. DeDad

2012 NFPA 70E. Ten Most Important Changes. John A. DeDad 2012 NFPA 70E Ten Most Important Changes John A. DeDad GE Energy Management 41 Woodford Avenue Plainville, CT 06062 USA 860-747-7344 John.dedad@ge.com Abstract The 2012 Edition of NFPA 70E, Standard for

More information

Who sets the rules for electrical testing and safety?

Who sets the rules for electrical testing and safety? Who sets the rules for electrical testing and safety? Application Note Alphabet soup There s no question that electrical safety is a key concern for electricians and engineers, their employers, unions

More information

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for commercial and industrial facilities Executive Summary

More information

4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS

4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS 4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED MEDIUM VOLTAGE

More information

Understanding the Standards Surrounding Arc Flash Hazards and Arc Resistant Equipment

Understanding the Standards Surrounding Arc Flash Hazards and Arc Resistant Equipment Understanding the Standards Surrounding Arc Flash Hazards and Arc Resistant Equipment 1 Rev 5058-CO900E This presentation contains many hidden slides that are provided for the presenters information and/or

More information

ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com]

ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com] ARC FLASH HAZARD MITIGATION ARC FLASH HAZARD MITIGATION NWHA TECHNICAL SEMINAR May 17, 2012 Richard D Reese Power Systems Manager Industrial Tests, Inc. Rocklin, California [Dick@indtests.com; 916-660-2837]

More information

Fault Characteristics in Electrical Equipment

Fault Characteristics in Electrical Equipment 1. Introduction Proper design and installation of electrical equipment minimizes the chance of electrical faults. Faults occur when the insulation system is compromised and current is allowed to flow through

More information

Roadmap to Compliance with NFPA 70E Arc Flash Requirements

Roadmap to Compliance with NFPA 70E Arc Flash Requirements Roadmap to Compliance with NFPA 70E Arc Flash Requirements TAHFM Interlink 2015 March 30, 2015 Antony Parsons, Ph.D., P.E. Schneider Electric Engineering Services 1 2 How do we get to Reliable Power? >

More information

PRESENTED AT THE 2011 IEEE IAS PULP & PAPER INDUSTRY TECHNICAL CONFERENCE, NASHVILLE, TN: IEEE 2011 - PERSONAL USE OF THIS MATERIAL IS PERMITTED.

PRESENTED AT THE 2011 IEEE IAS PULP & PAPER INDUSTRY TECHNICAL CONFERENCE, NASHVILLE, TN: IEEE 2011 - PERSONAL USE OF THIS MATERIAL IS PERMITTED. Arc Flash Energy Reduction Techniques Zone Selective Interlocking & Energy-Reducing Maintenance Switching Christopher G. Walker Senior Member, IEEE Eaton Corporation Moon Township, PA 15108 chrisgwalker@eaton.com

More information

MEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED

MEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED CCG Facilities Integration Incorporated

More information

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for

Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for Understanding 2015 Changes to NFPA 70E Safety-related work practices and maintenance requirements mandate more robust electrical safety programs for data centers Executive Summary Every three years, the

More information

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System

Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Cory David Smith, Project Manager, ECOM Engineering Inc., and David Lawrence Smith, Principal, ECOM Engineering

More information

UL Validated Testing of Arc-Resistant Motor Control Centers

UL Validated Testing of Arc-Resistant Motor Control Centers UL Validated Testing of Arc-Resistant Motor Control Centers Ensure Protective Features Perform as Designed Larry Sifers Account Manager Littleton, CO Siemens Industry June 1st - 3rd, 2011 Western Mining

More information

Procedure Number 1022. Arc Flash Hazard Calculation and Required Protection Revision 5. TVA Safety Procedure Page 1 of 25. 1.

Procedure Number 1022. Arc Flash Hazard Calculation and Required Protection Revision 5. TVA Safety Procedure Page 1 of 25. 1. TVA Safety Procedure Page 1 of 25 Arc Flash Hazard Calculation and 1. Purpose April 30, 2007 1.1. This procedure defines TVA s method for calculating the electric arc flash incident energy at various distances,

More information

A Comparison of Circuit Breakers and Fuses for Low-Voltage Applications

A Comparison of Circuit Breakers and Fuses for Low-Voltage Applications Data Bulletin 0600DB0601 2/2007 Cedar Rapids, IA, USA A Comparison of Circuit Breakers and Fuses for Low-Voltage Applications Tony Parsons, PhD, P.E., Square D / Schneider Electric Power Systems Engineering

More information

Andre Gretler, LPLS BU Function Operation and Sales Low Voltage Systems ANSI vs IEC. BU 3101 Low Voltage Systems June 27, 2013 Slide 1

Andre Gretler, LPLS BU Function Operation and Sales Low Voltage Systems ANSI vs IEC. BU 3101 Low Voltage Systems June 27, 2013 Slide 1 Andre Gretler, LPLS BU Function Operation and Sales Low Voltage Systems ANSI vs IEC June 27, 2013 Slide 1 Business card André Gretler BU Function Operation and Sales Business Unit Low Voltage Systems ABB

More information

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B SURGE PROTECTIVE DEVICES (SPDs) EXTERNAL SIDEMOUNT UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective

More information

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?

What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? Comparing apples-to-apples bids Plant Services Special Report A shock hazard analysis should be included as part of an arc

More information

Sample - No Commercial Use

Sample - No Commercial Use COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort

More information

ETAP Arc Flash Analysis

ETAP Arc Flash Analysis ETAP Arc Flash Analysis The purpose of this tutorial is to introduce the Arc Flash Analysis module of ETAP and provide instructions on how to setup Arc Flash (AF) calculations. For this section of the

More information

ELECTRICAL & ARC FLASH SAFETY PROGRAM

ELECTRICAL & ARC FLASH SAFETY PROGRAM ELECTRICAL & ARC FLASH SAFETY PROGRAM ADOPTED VERSIO 2, SEPTEMBER 26, 2012 Supercedes all prior versions A. COMMITTEE OVERSIGHT OF PROGRAM The University of Montana ( University ) recognizes the importance

More information

Demystifying arc flash hazard management

Demystifying arc flash hazard management Demystifying arc flash hazard management Presented by Matt Brazier Senior Electrical Engineer Gove Operations November 2013 Standard NFPA 70E IEEE 1584 AS/NZS 4836 TERMINOLOGY Arc arc flash hazard analysis

More information

Introduction to Arc Flash

Introduction to Arc Flash Introduction to Arc Flash Worker Training of Electrical Hazards Including Arc Flash SH-16614-7 This material was produced under grant number SH-16614-7 from the Occupational Safety and Health Administration,

More information

INFRARED WINDOWS APPLIED IN SWITCHGEAR ASSEMBLIES: TAKING ANOTHER LOOK

INFRARED WINDOWS APPLIED IN SWITCHGEAR ASSEMBLIES: TAKING ANOTHER LOOK INFRARED WINDOWS APPLIED IN SWITCHGEAR ASSEMBLIES: TAKING ANOTHER LOOK David B. Durocher Senior Member, IEEE Eaton Corporation 26850 SW Kinsman Road Wilsonville, OR 97070 USA davidbdurocher@eaton.com David

More information

Siemens tiastar TM Motor Control Center (MCC) Siemens 2011. All rights reserved.

Siemens tiastar TM Motor Control Center (MCC) Siemens 2011. All rights reserved. Siemens tiastar TM Motor Control Center (MCC) Siemens 2011. All rights reserved. tiastar Arc Resistant MCCs UL Validated Testing of Arc-Resistant Motor Control Centers page 2 tiastar Arc Resistant MCCs

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects

More information

Common Sense and Knowledge Approach to Electrical Safety

Common Sense and Knowledge Approach to Electrical Safety Common Sense and Knowledge Approach to Electrical Safety L. Bruce McClung Distinguished Lecturer on Electrical Safety Issues for IEEE-IAS/PES 2002-03 3/30/2004 1 For IEEE-Brazil Section in Guararema -

More information

Worldwide Thermography Headquarters

Worldwide Thermography Headquarters Arc-flash brochure B 18/9/07 09:22 Page 1 Copyright 2007, Hawk IR International Ltd. All other brand and product names are trademarks of Hawk IR International Ltd.. Hawk IR International Ltd. reserve the

More information

The Three A s of Arc Flash

The Three A s of Arc Flash The Three A s of Arc Flash Gary H. Fox, PE Senior Specification Engineer In 2007 GE conducted a survey of industry professionals working in facilities related to the oil and gas industry, pulp and paper

More information

Protection Considerations to Mitigate Arc-Flash Hazards

Protection Considerations to Mitigate Arc-Flash Hazards 1 Protection Considerations to Mitigate Arc-Flash Hazards echnical Report to the Substation Subcommittee of the Power Systems Relaying Committee Working Group: Chair: K. Zimmerman, Vice Chair: R.A. Hedding,

More information

Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection

Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection Mitigation of Arc-Flash Hazards and Reduction of Costs by Selective Arc-Flash Protection L. Kumpulainen, S. Dahl J. Ma Vamp Ltd, Finland Vamp Ltd, China 1 ABSTRACT This paper describes causes and characteristics

More information

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

Risk Mitigation of Aging Electrical Infrastructure

Risk Mitigation of Aging Electrical Infrastructure Risk Mitigation of Aging Electrical Infrastructure 2015 MWEA Annual Conference 2pm Monday June 22 nd, 2015 Presented by Tim Murphy Authored by Jeff M. Miller, PE, ENV SP About the Presenter 5 Jeff M. Miller,

More information

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,

More information

IMPROVING SELECTIVITY & ARC-FLASH PROTECTION THROUGH OPTIMIZED INSTANTANEOUS PROTECTION SETTINGS Copyright Material IEEE Paper No.

IMPROVING SELECTIVITY & ARC-FLASH PROTECTION THROUGH OPTIMIZED INSTANTANEOUS PROTECTION SETTINGS Copyright Material IEEE Paper No. MPROVNG SELECTVTY & ARC-FLASH PROTECTON THROUGH OPTMZED NSTANTANEOUS PROTECTON SETTNGS Copyright Material EEE Paper No. ESW 2012 EEE. Reprinted, with permission, from authors, Marcelo E. Valdes, Steve

More information

Written Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards

Written Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards Written Program ELECTRICAL SAFETY Based on OSHA Subpart S and NFPA 70E Standards Revised November 2012 Disclaimer The presentations and program provided by Workplace Safety Solutions, Inc. are based on

More information

Arc Flash Mitigation & Selective Co-ordination

Arc Flash Mitigation & Selective Co-ordination Arc Flash Mitigation & Selective Co-ordination Michael Hodder March 2015 Overview This seminar will provide information on: Mitigating arc flash hazards Selective Coordination What can we do to make these

More information

Arc Flash Safety in 400V Data Centers

Arc Flash Safety in 400V Data Centers Arc Flash Safety in 400V Data Centers Strategies for protecting employees from underappreciated yet potentially deadly hazards By Dave G. Loucks PCM Solution Manager Eaton Corporation Executive summary

More information

INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010

INTRODUCTION ARC FLASH PROTECTION AND SAFETY MEASURES. September 2010 ARC FLASH PROTECTION AND SAFETY MEASURES September 2010 Introduction Hazards of Electrical Energy Electrical Safety Program Safety-Related Work Practices Electrical Safety Procedures Presented By: Ken

More information

Evaluating Water-Damaged Electrical Equipment

Evaluating Water-Damaged Electrical Equipment Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire

More information

Power-Zone 4 Arc Resistant Low Voltage Switchgear

Power-Zone 4 Arc Resistant Low Voltage Switchgear Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions

More information

ELECTRICAL SAFETY RISK ASSESSMENT

ELECTRICAL SAFETY RISK ASSESSMENT ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures

More information

PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT

PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT Human Resources Support Services Health, Wellness and Safety PROCEDURES FOR SAFE WORKING AND TESTING OF ENERGIZED ELECTRICAL EQUIPMENT 1 SCOPE The electrical safety procedure shall be part of the Peel

More information

ELECTRICAL SAFETY PROGRAM

ELECTRICAL SAFETY PROGRAM ELECTRICAL SAFETY PROGRAM Adopted January 2014 Table of Contents Chapter 1: Introduction... 1 1.1 Purpose... 1 1.2 Scope... 1 1.3 Definitions... 1 1.4 Responsibilities... 8 1.5 Basic Electrical Safety

More information

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E

SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E SAFE ELECTRICAL WORK PRACTICES & 2015 NFPA 70E This easy-to-use Leader s Guide is provided to assist in conducting a successful presentation. Featured are: INTRODUCTION: A brief description of the program

More information

Contents. Description. Product Selection Guide

Contents. Description. Product Selection Guide .1 Medium Voltage Switchgear Introduction Indoor Type VCP-W Metal-Clad Switchgear Assembly (5/15 kv shown) Product Selection Guide Product Offering Chart Metal-Enclosed Contents Description Notes Additional

More information

CHAPTER 2 EXAMPLES AND TABLES

CHAPTER 2 EXAMPLES AND TABLES CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of

More information

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)

Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.) Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection

More information

NZECP 14: 1995 ISSN 0114-0663 COVER PAGE

NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14:1995 NEW ZEALAND ELECTRICAL CODE OF PRACTICE FOR CONTROL PROTECTION AND SWITCHBOARDS Issued by the Office of The Chief Electrical Engineer, Energy and

More information

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY

More information

100% Rule Alternate Method Arc Blast Arc Flash Approved Approved Equipment Authority Having Jurisdiction (AHJ) Authorized Work Bare Hand Work

100% Rule Alternate Method Arc Blast Arc Flash Approved Approved Equipment Authority Having Jurisdiction (AHJ) Authorized Work Bare Hand Work Definitions 100% Rule Work on or near energized parts must be performed only after all participating qualified electrical workers are in 100% agreement on the work to be completed, on the sequence in which

More information

OSHA & ARC FLASH HAZARD ANALYSIS

OSHA & ARC FLASH HAZARD ANALYSIS OSHA & ARC FLASH HAZARD ANALYSIS Impact of Revisions to the OSHA Electrical Safety Regulations Presented by: John J. Kolak, MS, CSP Introduction Important Definitions Understanding OSHA Applicable standards

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

UL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training. 2002 Eaton Corporation. All rights reserved.

UL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training. 2002 Eaton Corporation. All rights reserved. UL 508A Industrial Control Panels Power Distribution and Control Lunch & Learn Training 2002 Eaton Corporation. All rights reserved. Agenda Who is UL and what role do they play? What is the UL 508A Standard?

More information

I Viewing Windows and Arc Ratings Dispelling the myth of Arc-Resistant IR Viewing Windows

I Viewing Windows and Arc Ratings Dispelling the myth of Arc-Resistant IR Viewing Windows I Viewing Windows and Arc Ratings Dispelling the myth of Arc-Resistant IR Viewing Windows Abstract There exists a dangerous misconception regarding the Arc Rating of viewing windows or viewing panes. Many

More information

Why Construction Workers are Getting Electrocuted

Why Construction Workers are Getting Electrocuted Why Construction Workers are Getting Electrocuted Michael McCann, PhD, CIH Director of Safety and Ergonomics The Center to Protect Workers Rights mmccann@cpwr.com Causes of Death in Construction, 1992-98

More information

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

What are the basic electrical safety issues and remedies in solar photovoltaic installations? What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic

More information