Manual for Fire Suppression & Methane Detection System
|
|
|
- Linette Lawrence
- 10 years ago
- Views:
Transcription
1 Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA Delivery address: 150 Gordon Dr Exton, PA Tel: Fax: Page Rev. L
2 Methane Fume Detector/Fire Detection System Installation and Operation Manual MADE IN THE USA READ THIS MANUAL CAREFULLY AND SAVE FOR FUTURE REFERENCE. KEEP THIS MANUAL WITH THE FM-US Introduction The FM-US vapor-monitoring system utilizes advanced technology for detection of methane fumes. The FM-US allows the connection of (2-6) sensors and has both visual and audible alarms that trigger at 20% and 50% LEL of methane respectively. Test switches are provided for full testing of all operations. System operation and correct sensor operation are continually monitored and indicators are provided for fault detection. The FM-US has an internal relay for automatic control of an external device up to 1 amp. The FM-US also has a fire detection system built in. It has the ability to monitor pressure switches/ir-thermal switches/ and other contact type inputs. These inputs will control the indicators on the display to alert a user of service needed or in case of a fire. They also control the engine shutdown relay and one input has its own separate output. This output switches system voltage or ground out if a condition occurs. Read this owner s manual completely before installation. Failure to read and follow these instructions can result in damage to the unit voiding the warranty. DANGER! NO POWER ON/OFF SWITCH IS PROVIDED FOR THIS UNIT. TO FUNCTION AS INTENDED, THE FM-US MUST BE CONNECTED TO A SUITABLE POWER SOURCE AND BE POWERED CONTINUOUSLY. DANGER! UNLIKE CNG, LNG HAS NO IDENTIFIABLE ODOR. IF AN LNG LEAK IS DETECTED BY THE METHANE SYSTEM TAKE EXTREME CAUTION! CAUTION: IF POWER IS ON AND LEFT UNATTENDED FOR AN EXTENDED PERIOD OF TIME, BATTERY POWER MAY BE DIMINISHED. Manual Display Controls / Indicator Fire Detection OK - Green when there is no fire detected or service required Service Required Orange when pressure has dropped in detector bottle or piston accumulator. Fire Red when pressure lost or fire detected/occurred. Methane Detection OK Green when there is no service required and no gas detected Service Required Orange when sensor is disconnected or malfunction detected Trace Gas Orange when methane is detected between 20% and 50% LEL Significant Gas Red when methane is detected over 50% LEL Display Installation The FM-US should be mounted in a convenient location, preferably where the visual indicators may be readily seen. To install the display, you must first cut a rectangular opening 4 1/8 x 2 1/4. Secure the display at the four corners with #6 screws. Sensor Installation The sensor can be mounted horizontally or vertically on a flat surface. It is important for the surface to be flat to prevent bowing of the housing. Page Rev. L
3 CNG (Compressed Natural Gas) is lighter than air and will rise. Therefore, it is important that a location be selected that is within nine (9 ) inches (22.86cm) of the ceiling height. Do not locate sensor directly in the path of any kind of constant external air flow or sources of contamination. Keep sensor dry. Once the location has been selected peel the backing paper off of the sensor and stick in its desired location. Place a #8 washer on a #8 pan head screw and insert through the hole in the sensor ear to secure. Repeat on the other ear. Do not use Loctite as it can cause the sensor housing to crack. Use a lock washer or locknut instead. Tighten the screws to 20 in-lbs, do not over tighten. Wiring the FM-US The display has five connectors for external connections and one pink wire for battery back-up. See diagram below for connections. See the table for connector pin outs. FM-US has an in line fuse on the positive cable. Optional Equipment FM-US Methane Sensor FM-US Allows for additional MS-3 or MS-4 sensor to be connected to a system FM-US Methane Sensor with built in LED FM-US Methane Sensor 90 degree mounting bracket FM-US Rechargeable battery backup unit for Vdc FM-US Aluminum Methane Sensor with built in LED FMWH XX Extension Cable for MS-3/MS-4 Sensor (0XX = length in 5 increments) Page Rev. L
4 Connector Pin Function Color Gauge Primary Fire Connector A Gnd from display W 18 B 50 Bar in switch (if 50 Bar is open & 14 Bar is closed then service lights. If 50 Bar & 14 Bar are open then fire lights, siren sounds, relay activation) Y 18 C 5 Bar in switch (if 5 Bar is open & 14 Bar is closed then service lights. If 5 Bar & 14 Bar are open then fire lights, siren sounds, relay activation) Blk 18 D Relay Option (if disconnected no relay delay, if connected to system voltage 15 second delay on relay) Grn 18 E 14 Bar in switch (if 14 Bar is open & 50 or 5 Bar is closed then service lights. If 14 Bar & 50 or 5 Bar are open then fire lights, siren sounds, relay activation) Br 18 F NC output for Engine relay O 18 G NO output for Engine relay R 18 H Common input for the Engine relay. Relay is triggered by 50Bar, 5Bar, IR Thermal or Methane in Danger. Bl 18 IR Thermal Connector A B IR Thermal switch input. (if closed fire lights, siren sounds, 15sec delayed relay activation) Switched system voltage on closed IR Thermal switch Bl R Power Connector Sensor 1 Sensor 2 A Power (10V 54V) R 18 B Ground input for display Blk V to sensor (regulated by display do not by pass) R 22 2 Methane signal out from sensor Grn 22 3 Ground to sensor (can be by passed and grounded remotely) Blk V to sensor (regulated by display do not by pass) R 22 2 Methane signal out from sensor Grn 22 3 Ground to sensor (can be by passed and grounded remotely) Blk 22 Testing Display Mode If no alarm conditions are present, holding either SILNCE/RESET button down for 4 seconds will initiate a self test sequence. During this sequence all LED s will cycle along with the engine relay and siren. Sensor Fault Detection Should the unit determine that either of the methane sensors are faulty or disconnected, the Service Required LED will illuminate. In the case of service required, the vehicle should be stopped and pulled from service until the sensor / system is serviced and the Service Required LED is cleared. FM-US and FM-US sensors are also equipped with an LED to indicate each state of operation. Solid On - Everything is ok no methane present LED off - Sensor is in fault or is not plugged in Slow Flash - Sensor is detecting trace gas (20% LEL) Fast Flash - Sensor is detecting significant gas (50% LEL) Page Rev. L
5 Engine Relay The engine relay is controlled by both the fire and methane detection systems and has (C, NO, NC) dry contacts for multiple wiring options. If the Fire or Significant Gas lights come on the relay will turn on immediately. If the green wire is connected to system voltage the relay will turn on after 15 seconds. (See connector table.) IR-Thermal Relay This relay has the common tied to system voltage and is normally open. When a ground is present at the IR- Thermal input the relay closes sending out system voltage. Button Operation Either SILENCE/RESET button can be used for each system. When there are no alarm conditions holding either button for 4 seconds will initiate a self test sequence. If the siren is sounding, holding either button in for 1 second will mute the siren for 15 seconds. Engine Relay If the engine relay is activated holding either SILENCE/RESET button will reset the relay for 250mS to signal the bus s monitoring system. If the green wire is connected to system voltage and the engine relay is activated, holding either button for 5 seconds will cause the relay to reset for 15 seconds allowing the vehicle to start. (See connector table.) DANGER! UNLIKE CNG, LNG HAS NO IDENTIFIABLE ODOR. IF AN LNG LEAK IS DETECTED BY THE METHANE SYSTEM TAKE EXTREME CAUTION! DANGER! CHOOSING TO OVERRIDE THE METHANE SYSTEM DURING A 50% LEL ALARM CAN RESULT IN AN EXPLOSION. EXTREME CAUTION SHOULD BE TAKEN BEFORE OVERRIDING THE SYSTEM. Nuisance Alarms The sensors used for the FM-US are sensitive to hydrocarbons but an alarm may be triggered by the use of other chemicals such as cleaners, paint, polish, etc The sensors will also detect hydrogen fumes from an overcharged battery. If no hydrocarbon fumes are present, check for recent use of cleaners, fiberglass repairs, strong adhesives, etc If none of these are present, the sensor may have been damaged and will need replacement. WARNING: The FM-US has been designed to alarm visually at 20% of the LEL (Lower Explosive Limit) of Methane and alarm visually and audibly at 50% of the LEL. Implement immediately the following procedures in the event of an alarm. Manually shut off the source of Methane if possible. Turn off all electrical circuits EXCEPT circuits, which operate blowers and/or exhaust fans. Remove all personnel from the area. Ventilate the area. Carefully check all fuel lines, tanks and fittings to locate the leak. Have the problem repaired by qualified personnel. Page Rev. L
6 Panel Logic: Testing the operation of the fire suppression system: 1. Connect all wires and arm the fire suppression system. Turn on the bus. After the automatic system test runs if everything is connected and the bottles charged to the correct pressure the green SYSTEM OK light should be illuminated. 2. Disconnect the connection between the 50 bar pressure switch and the wire harness. This is labeled EXT PR SW. The SERVICE REQUIRED light will be illuminated. Reconnect after this is verified. 3. Disconnect the connection between the 14 bar pressure switch and the wire harness. This is labeled DET CYL PR SW. The SERVICE REQUIRED light will be illuminated. Reconnect after this is verified. 4. Disconnect the connections between the 14 bar pressure switch and the 50 bar pressure switch. The FIRE light will be illuminated. The siren will sound. The relay will activate (unless the green wire is connected to system voltage. See connector table.). Press Silence reset button for 1 second to silence the alarm. To restart the bus hold the Silence reset button for 4 seconds to reset the 15 second timer. If system is equipped with the optional 5 bar pressure switch: 1. Disconnect the connection between the 5 bar pressure switch and the wire harness. This is labeled 5 BAR SW. The SERVICE REQUIRED light will be illuminated. Reconnect after this is verified. 2. Disconnect the connections between the 5 bar pressure switch and the 14 bar switch. The FIRE light will be illuminated. The siren will sound. The relay will activate (unless the green wire is connected to system voltage. See connector table.). 3. Disconnect the connections between the 14 bar pressure switch, the 50 bar pressure switch and the 5 bar pressure switch. The FIRE light will be illuminated. The siren will sound. The relay will activate (unless the green wire is connected to system voltage. See connector table.). Maintenance The FM-US requires very little maintenance. Periodically examine the sensors for contamination or damage. Check that sensor wires are not frayed, pinched, or cut. Test the operation of both sensors and display frequently. Do NOT expose sensors to liquids or chemicals. When cleaning, seal off the sensor(s) with a plastic covering. Harsh chemicals may damage the sensor. Keep sensor(s) sealed until the compartment has been completely ventilated. Page Rev. L
7 Specifications 3A Fuse Voltage +12VDC Nominal (10VDC to 48VDC) Temperature. -40F to 158F operating (-40F to 170F storage) Alarm 20% of LEL 50% of LEL Relay... 1 amp max Display Current.. 50 ma Sensor Current 75 ma Splitter01 current. 40 ma WARNING The FM-US is Fire & Methane. This device is meant to serve as a supplement warning only. It is NOT intended to replace standard safety practices which should be carried out around explosive gases (i.e. inspect all compartments, check all gas fittings and connections, smell for methane gas fumes, etc ) To function properly the FM-US must be powered at all times. Before installing in applications which may appear different than those outlined in this manual, contact the manufacturer. This device is not intended for use in aircraft. There are no user or field serviceable parts in this product. The FM-US must be returned to the manufacturer for any repair or trouble shooting beyond what is recommended in this manual. Installation shall be done by qualified personnel authorized to do so by the authorities having jurisdiction for the particular application in which the product is being used. Electrical wiring shall be in accordance with applicable codes. Improper wiring, including all wire connections, may render the unit inoperable, damage components, or cause a fire, and will void all warranties Page Rev. L
600-GD & 600-GDL 600 SERIES GAS DETECTOR
600-GD & 600-GDL 600 SERIES GAS DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS This page has been deliberately left blank. Page 1 Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING
BEP FD-2 CONTOUR MATRIX FUME DETECTOR
BEP FD-2 CONTOUR MATRIX FUME DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING GAS SENSORS...3 4 FEATURES...4 5 SPECIFICATION...4 6
Mobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
INSTALLATION MANUAL 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS
3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS INSTALLATION MANUAL Before you begin the installation Read the INSTRUCTIONS! Always use a multi-meter when verifying vehicle wiring. Before mounting the
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
tidesmarine Smart Seal Temperature Alarm System Generation II Installation Instructions Starboard side cable
tidesmarine Smart Seal Temperature Alarm System Generation II Installation Instructions Starboard side cable Port side cable (with black cable tie attached) Power cable Preparing for Installation 1 Overall
1R / 4-BUTTON SERIES
Button 1 1R / 4-BUTTON SERIES VEHICLE SECURITY SYSTEM Standard Features: Two 4-Button Remote Transmitters Status indicator (LED) Valet / override switch Multi-tone siren Dual stage impact detector Remote
Residential Gateway (RG) Battery Backup
Residential Gateway (RG) Battery Backup BU3DC000-12V User Manual Table of Contents Page Introduction... 3 Safety Information... 3 System Requirements... 3 Package Contents... 4 Recycling... 4 Product Layout
EPSOLAR LS0512R / LS0524R. Solar Light Controller INSTRUCTION MANUAL. Please read this manual carefully before using the product!
EPSOLAR LS0512R / LS0524R Solar Light Controller INSTRUCTION MANUAL Please read this manual carefully before using the product! LandStar LS0512R / LS0524R Solar Light Controller Nominal system voltage
site monitoring Kit Site Monitoring Kit User Manual we prove it.
site monitoring Kit 1 User Manual Site Monitoring Kit User Manual we prove it. 2 site monitoring Kit Content 1. Introduction 3 2. Content of the Site Monitoring Kit 4 3. Preparation 6 1. Positioning of
How To Program An Autodialer
GJD HYL005 GSM Autodialer Instruction Manual Please read these instructions before you start the installation Features: LCD display. Programmable 9 x 32 digit phone numbers for each trigger. 10 second
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
GSM AD05 Slave GSM Auto Dialer- Instruction Manual
GSM AD05 Slave GSM Auto Dialer- Instruction Manual Please read these instructions before you start the installation Features LCD display Programmable 9 x 32 digit phone numbers for each trigger. 10 second
Fire suppression system for engine compartments USER MANUAL
Fire suppression system for engine compartments USER MANUAL Contractor s machinery/vehicles, tooling machines and special machines Edition 2011-3 Hydro pneumatic activation Mechanical activation Electrical
LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual
CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: 01825 733600 LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual Contents 1) Operation 2)
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
AC-115 Compact Networked Single Door Controller. Installation and User Manual
AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors
D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH
Business/ Home GSM Alarm System
Business/ Home GSM Alarm System BUSINESS/HOME GSM ALARM SYSTEM POWER STATUS RECORD SIGNAL User Manual Profile For a better understanding of this product, please read this user manual thoroughly before
i ChatterBox! Motorcycle Security
i Before you Start the Installation * Please read this manual to become familiar with the requirements necessary to complete the installation. * Use a high quality multi-meter to test all wires before
HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS
ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS USER MANUAL USER MANUAL ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS INTRODUCTION The (HA-841K) is a complete
USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018
USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and
Co-location Interconnect Power Panel (CIPP) Installation Guide
Co-location Interconnect Power Panel (CIPP) Installation Guide Document INS-97xxxxxxx This guide covers the following part numbers- Trimm 97xxxxxxx Series Table of Contents Section 1 - General Information...
PRO PLM Installation Instructions
PRO PLM Installation Instructions PROFESSIONAL INSTALLATION STRONGLY RECOMMENDED Installation Precautions: Roll down window to avoid locking keys in vehicle during installation Avoid mounting components
How To Control A Car Alarm On A Car With A Remote Control System
MODEL CA100 REMOTE CONTROL AUTO ALARM SYSTEM INSTALLATION & OPERATION INSTRUCTIONS WIRING DIAGRAM Black Antenna Wire 6 Pin 6 Pin Mini Connector Valet Switch Blue LED Indicator Blue Wire: (-) 200mA Unlock
Multi Function, User Configurable Remote Vehicle Security System with 4 Button Replaceable Membrane Remote Transmitter
MODEL PRO-9744 INSTALLATION MANUAL Multi Function, User Configurable Remote Vehicle Security System with 4 Button Replaceable Membrane Remote Transmitter This System Allows The Transmitter Buttons To Be
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
Fire Alarm Control Panel. Family. Operating Manual
Fire Alarm Control Panel Family Operating Manual CONTENTS System Description AH-03312 System Characteristics... Fire Signal Receiving Board Description-4L... Fire Signal Receiving Board Description-8L...
Y7230A CO 2 Alarm System
Y7230A CO 2 Alarm System FOR CO 2 GAS DETECTION PRODUCT DATA FEATURES APPLICATION Y7230A CO 2 alarm system is used to detect gas leaking from CO 2 beverage dispensing systems and posts an alarm to occupants
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
CAD-05 Kit GSM Auto Dialer. Owner s Manual
CAD-05 Kit GSM Auto Dialer Owner s Manual CAD-05 Kit Manual.indd 1 Warnings: This device complies with Part 15 of the FCC rules, Operation of this device is subject to the following conditions: 1. This
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems
CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way
IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White
IMPORTANT INSTRUCTIONS & OPERATING MANUAL Houston 50 Inch Electric Wall Mounted Fireplace Black / White Model Number:MFE5050BK Model Number:MFE5050WH Read these instructions carefully before attempting
Installation and Operating Instructions (for chargers shown below)
Installation and Operating Instructions (for chargers shown below) For additional information please call our Technical Support Group 800.742.2740 PRO CHARGING SYSTEMS, LLC 1551 Heil Quaker Boulevard,
DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0
Form No. 74-00-4001 S168-195-001 Revision E DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0 INTRODUCTION Allied Healthcare Products, Inc. s Digital Alarm
Recommended Practice for Installation of Transit Vehicle Fire Protection Systems
Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Approved October 25, 2007 APTA Fire Safety Working Group Approved May 3, 2008 APTA Bus Safety Committee Approved October
DC400 Dispensing Cutoff System
DC400 Dispensing Cutoff System DC404 and DC406 Installation Instructions Franklin Fueling Systems 3760 Marsh Rd. Madison, WI 53718 USA Tel: +1 608 838 8786 800 225 9787 Fax: +1 608 838 6433 www.franklinfueling.com
Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems
Vehicle Fire Protection An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems 002792 Off-road vehicles do have fires Statistics show that off-road vehicles burn with alarming frequency. These
Using your LED Plus keypad
Using your LED Plus keypad System 238 System 2316 System 238i System 2316i Part Number 5-051-372-00 Rev B Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced
Installation and Operating Instructions (for chargers shown below)
Installation and Operating Instructions (for chargers shown below) For additional information please call our Technical Support Group 800.742.2740 PRO CHARGING SYSTEMS, LLC 1551 Heil Quaker Boulevard,
WIRING HARNESS FOR AS635P4. BLUE PLUG RED, BLUE, BLACK, WHITE - Plug in dual stage sensor harness
WIRING HARNESS FOR AS635P4 ANTENNA NOT USED 5 PIN WHITE PLUG 2 PIN WHITE PLUG GREEN - PARKING BRAKE INPUT (-) BLUE - NOT USED 3 PIN BLUE PLUG RED, BLUE, BLACK, WHITE - Plug in dual stage sensor harness
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY
SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL
Water Leak Detection System
Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:[email protected] 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright
Online UPS. PowerWalker VFI 1000R/1U
Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.
MOBILE CALL GSM Alarm System User s Manual
MOBILE CALL GSM Alarm System User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. Contents Function Introduction Alarm Host Diagram
SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P
SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P 2 Alarm Levels Bargraph + LED Indication of Gas Concentration Visual and Audible Signalization of Activated Alarm Levels 2 SPDT 5A/250V Output Relays Shock-Proof
DC-8706K Auto Dial Alarm System
DC-8706K Auto Dial Alarm System User Guide Basic Contents: 1x the host unit; 1x wireless door (window) magnet; 1x wireless infrared detector; 2x remote control; 1x siren; 1x phone core; 1x AC to DC power
Thermo Top - Troubleshooting Tree
Thermo Top - Troubleshooting Tree 07-15-2002 CAUTION Troubleshooting requires comprehensive knowledge about the structure and theory of operation of the Thermo Top heater. Troubleshooting and repairs may
Conventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
SR-i900 Series. www.scorpioalarms.com [email protected]. Phone (480)951-1109
www.scorpioalarms.com [email protected] SR-i900 Series Phone (480)951-1109 Aritronix Ltd 16055 N. Dial Blvd. Suite B-10 Scottsdale, AZ 85260 V9.3 Important Information Save this information for future
EzFlex Combustible Gas Leak Detector Model EZ40
User's Guide EzFlex Combustible Gas Leak Detector Model EZ40 Introduction Congratulations on your purchase of the Extech EZ40 Combustible Gas Leak Detector. The EZ40 detects the presence of combustible
USER GUIDE TURBOCORD TM PORTABLE CHARGER 120V/240V: DUAL VOLTAGE. AeroVironment EV Solutions
USER GUIDE TURBOCORD TM PORTABLE CHARGER 120V/240V: DUAL VOLTAGE AeroVironment EV Solutions 2013 AeroVironment, Inc. All rights reserved. AeroVironment, EV Solutions, and the AeroVironment logo are trademarks
Vertical Display and Storage B1350-2. SKOPE Gen2: Three Door Chiller
Vertical Display and Storage User Manual MAN1227 Rev. 3.0 March 2008 edition CONTACT ADDRESSES Designed and Manufactured by New Zealand SKOPE INDUSTRIES LIMITED PO Box 1091, Christchurch New Zealand Freephone:
FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
SECURITY SYSTEM ADP-CAN
INSTALLATION INSTRUCTION SECURITY SYSTEM ADP-CAN Introduction Motorcar security system ADP-CAN is for motorcars provided with CAN net. It is for the work with the motorcar factory security systems or remote
ABLOY DA60 SWING DOOR OPERATOR Installation and commissioning manual Abloy Oy An ASSA ABLOY Group company APPROVALS / STANDARDS Low Voltage directive 7//EEC as amended by the directive 9/68/EEC EMC directive
AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810
AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810 This Manual and the information contained therein is the property of AMI Marine (UK) Ltd. It must not be reproduced
WD-AMX Water Detection Controllers
Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation
INSTALLATION GUIDE OWNER S GUIDE
INSTALLATION GUIDE OWNER S GUIDE SECURITY SYSTEM PRO-SERIES 5002 CONTENTS System Features... 1-2 System Components... 2 Technical Assistance... 2 Before You Begin... 2 Precautions... 2-3 Making Connections...
Streaming Potential System (SPT1000, SPD1000)
Streaming Potential System (SPT1000, SPD1000) User's Manual Sentrol Systems, Inc. 3949 Cotswold Dr. SW, Lilburn, GA 30047-2371 Tel: 770-564-1541, Fax: 770-564-8605 www.sentrolsystems.com Since the streaming
Automatic Telephone Dialer TD-101(W)
Automatic Telephone Dialer TD-101(W) The TD-101 is an automatic dialing device which can transmit prerecorded information via the telephone line. The dialer can send two different 10 second voice messages
WIRELESS HOME ALARM SYSTEM (WHA1)
WIRELESS HOME ALARM SYSTEM (WHA1) IMPORTANT : PLEASE READ THIS MANUAL CAREFULLY BEFORE ATTEMPTING TO INSTALL AND OPERATE THIS ALARM SYSTEM. SAFETY Please note: Before you start to install this alarm, we
Combustible Gas Transmitter 65-2400RK-05
Combustible Gas Transmitter 65-2400RK-05 Overview This detection insert describes the combustible gas transmitter. This insert also describes how to install, start up, maintain, and calibrate the transmitter.
AUTODIALLER / QUICKDIALLER - SA132
AUTODIALLER / QUICKDIALLER - SA132 INSTRUCTION LEAFLET ENGLISH www.thermomax-group.com CONTENTS 1 SETUP AT A GLANCE... 2 2 FOREWORD....... 3 3 INSTALLATION...... 4 4 KEYPAD AND INDICATORS...... 5 SETTING
K9 Heat Alarm Owners Manual HA-1520
K9 Heat Alarm Owners Manual HA-1520 Your K9 Heat Alarm is a state of the art product designed and developed by ACEK9.COM a division of Radiotronics, Inc. It is a unique blend of positive features taken
WALL MOUNTED SPLIT TYPE AIR CONDITIONER
WALL MOUNTED SPLIT TYPE AIR CONDITIONER MANUAL 8 OM-G12-ACSON CONTENTS - Operating Guide page 1 - G12 Remote Controller Indication page 2 - Indicator Lights page 4 - Installation of Aroma page 5 - Auto
Wespot. SecNurse A NEW GENERATION TECHNICAL AIDS USER S GUIDE
Wespot SecNurse A NEW GENERATION TECHNICAL AIDS USER S GUIDE EN This manual is published by OPTEX, without any warranty. Improvements and changes to this manual necessitated by typographical errors, inaccuracies
ANTI-THEFT SYSTEM. 1995 Volvo 850 DESCRIPTION & OPERATION BASIC ALARM. 1995-96 ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems
ANTI-THEFT SYSTEM 1995 Volvo 850 1995-96 ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems 850 DESCRIPTION & OPERATION WARNING: Deactivate air bag system before performing any service operation. For 1995
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
Electric Panel Pump Control System. Operation, Maintenance and Installation Manual
Manual No. 5EP-OM1-1 Electric Panel Pump Control System Operation, Maintenance and Installation Manual INTRODUCTION... 1 RECEIVING AND STORAGE... 1 DESCRIPTION OF OPERATION... 1 INSTALLATION... 2 SEQUENCE
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
TMS TANK MANAGEMENT SYSTEM
TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS
VEHICLE THEFT/SECURITY SYSTEMS
DN VEHICLE THEFT/SECURITY SYSTEMS 8Q - 1 VEHICLE THEFT/SECURITY SYSTEMS TABLE OF CONTENTS page GENERAL INFORMATION INTRODUCTION...1 VEHICLE THEFT SECURITY SYSTEM....1 ENABLING...1 ARMING...1 DISARMING...2
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
INSTALLATION GUIDE. www.security.soundstream.com FCC ID NOTICE
AL.1 AUTO SECURITY SYSTEM INSTALLATION GUIDE www.security.soundstream.com FCC ID NOTICE This device complies with Part 15 of the FCC rules. Operation is subject to the following conditions: 1. This device
Service Guide 12/27/03 TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models)
TESTING, SERVICE & REPAIR GUIDE (For SH Space Heating Models & RA Water Heating Models) WARNING - HIGH VOLTAGE AC electrical circuits are connected to this heater. Do not attempt any service work on the
MS4000/MS4000U Mini-Siren
MAN MS4000 INSTALL REV: 1/26/01 255331B INSTALLATION AND OPERATING INSTRUCTIONS MS4000/MS4000U Mini-Siren i Section Title Page I General Description...... 1 II Specifications... 2 III Safety Message To
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
Now Available With. Technical Support. Temperature Monitor & Alert Unit For K9 Police Vehicles M852-15 and M852-20 with Alpha
Now Available With Temperature Monitor & Alert Unit For K9 Police Vehicles M2-15 and M2-20 with Alpha Alpha Check will remind you to check the safety of your K9 partner. CoolGuard Temp Probe Technical
Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868
Instruction Sheet 10-2004 Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868 PowerCommand is a registered trademark of Cummins Inc. InPower
Part Number: 250-1859
General Applicability 2010 Honda Insight 07- Kia Optima / Forte / Rondo/ 10- Sedona / 12 Soul 10- Hyundai Tucson / Elantra Touring ETC 2012 Accent / Elantra/ Genesis Recommended Tools Safety Tools Gloves,
WIND ALARM. Wind Speed Alarm. Wind Speed. Set Point 2. Set Point 1 NEW BEDFORD, MA 02745 USA
Thank you for purchasing the Maximum wind speed alarm. The Maximum wind speed alarm is a dual set point wind speed indicator with a two digit LED display. It contains a yellow light to display one set
BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS
BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS WG2 Dimensions: LxHXW: 26 x 14.5 x 29.5 cm INTERNAL Alarm Terminals EXTERNAL Alarm Terminals WG2 Control Unit WaterGuard
SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE
SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE Cable Processor Module overview WARNING! When tipping the Cable Processor Module back, (after removing the toggle arm pin), use extreme caution not to drop
SLIM LINE FUME HOOD MONITOR
SLIM LINE FUME HOOD MONITOR Phoenix Controls FHM420 Fume Hood Monitor is sized to fit any fume hood and includes icons for simple and universal operation. The FHM420 slim line monitor works in conjunction
User s Manual AURORA 1.2K/2.2K
User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable
VLT Series 300 Watt True Sine Wave Inverter
VLT Series 300 Watt True Sine Wave Inverter PURE SINE WAVE INVERTER I ON 0 OFF REMOTE CONTROL AC OUTPUT POWER STATUS Vout Vin Models VLT12-300 VLT24-300 300 Watt VLT Series Inverter - 1 - TABLE OF CONTENTS
ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL
ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL INTRODUCTION... 2.. TECHNICAL DATA... 3 ACCESSORIES... 5. INSTALLATION... 7 OPERATION... 12. TECHNICAL INFORMATION... 13 MAINTENANCE... 14. CONFIGURATIONS...
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions
TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TRACETEK TraceTek TTDM Replacement Parts General Information These instructions detail the steps to
The Child Reminder System Installation Manual
The Child Reminder System Installation Manual Revised June, 2006 Detailed installation information can be found at www.childreminder.com. Get through your installation quickly and easily by calling 1-888-330-6786
FT-100 Fire Training Fog Machine User Manual English
FT-100 Fire Training Fog Machine User Manual English 2015 Antari Lighting and Effects Ltd. User Manual - English Safety Information Please read the following safety information carefully before operating