1 PGR-8800 SOLAR & AF0500 PRODUCTS ARC-FLASH RELAY CATALOG TECHNICAL FAQ
2 TABLE OF CONTENTS General Arc-Flash, PGR-8800, and AF0500 Information How much energy is in a typical arc-flash incident?...4 What is the electrical symbol of an arc-flash relay?...4 How long has Littelfuse had an arc-flash relay in service?...4 Do you have a list of references of companies using the PGR-8800 and AF0500?...4 Do you have an example of the PGR-8800 or AF0500 protecting a facility in the event of an arc-flash?...4 What are the key considerations when choosing an arc-flash relay?...4 Does the PGR-8800 or AF0500 nuisance trip?...5 Does thermal imaging trip the PGR-8800 or AF0500 relay?...5 Would a camera-flash trigger the PGR-8800 relay?...5 Does the PGR-8800 or AF0500 relay detect ultra-violet light?...5 Does the PGR-8800 or AF0500 provide zone identification?...5 Can you compare a service-mode instantaneous setting to an arc-flash relay?...5 Do the different modes of the arc-flash relay have different response times?...6 What is the life of the PGR-8800 or AF0500? What maintenance is required and how often?...6 Does the built in software consider the mechanical delay of all devices in the circuit and allow for changes to faster reacting main breakers?...6 How do arc-flash relays compare to Zone Selective Interlocking Protection (ZSIP) and Bus Differential?...6 Electrical Design Software What is SKM software and where can I find more information?...6 How do you enter resistance-grounding or arc-flash relays into the SKM software for calculating arc flash?...6 How do you model your optical devices in SKM and ETAP, since the relay is detecting light?...6 How does power system analysis software, such as SKM, EasyPower, and ETAP, recognize arc-flash relays?...7 Applications and Installations What are the typical applications / system voltages?...8 What is the maximum recommended length from the PGR-8800 or AF0500 to the breaker?...8 Can the PGR-8800 or AF0500 be used in low-voltage systems? Will a low-voltage breaker s closing or opening cause a trip?...8 Is internal arc classification of switchgear enclosures enough to eliminate an arc hazard?...8 When working on an energized transformer, we use instantaneous settings at the feeder breaker relay. Can the arc-flash relay bring any benefit?...8 Is there a specific relay to protect all of a switchgear bus section against arc flash?...9 Are there control systems available that truly eliminate or control arc flash?...9 Littelfuse.com/ArcFlash Littelfuse, Inc.
3 Light s and Current Transformers What are the installation guidelines for the sensors?...9 What is a typical light sensitivity radius for a fiber optic sensor?...10 Is there a maintenance schedule for the sensors?...10 At what intensity of light will the PGR-8800 or AF0500 indicate or trip?...10 How would the fiber-optic sensors be installed in switchgear that is shipped in groups? Do these sensors come in various lengths or with repeaters?...10 How do you test the sensors, are they fail-safe?...11 What is the purpose of the Current Transformers (CTs) and are they required?...11 Resistance Grounding Would a ground fault on the main switchgear act as an arc-flash relay?...11 Can we have more than 5A L-G fault available in HRG in any circumstances?...11 Is there protection (resistance grounding) for delta circuits?...11 The code only allows HRG if you didn t have neutral to ground loads (i.e. 277 V). Would this only be applied on 3-wire systems?...12 How do you address the system-leakage capacitance on HRGs, especially at medium-voltage levels?...12 Is it possible to apply HRG to a distribution transformer in order to minimize the arc-flash hazard when working on the secondary of the transformer?...12 If you have a neutral-grounding resistor, is an arc-flash relay also recommended?...12 Safety Regulations Do arc-flash relays lower Personal Protective Equipment (PPE) required?...12 Can arc-flash relays eliminate the need for HRC 3 or 4 clothing?...12 Can arc-flash relays reduce PPE required if only walking in front of the equipment, or opening the cabinet to read a nameplate?...12 What are the regulatory agencies opinion on arc-flash relays on life safety and critical circuits?...13 Can greater than 75 kva transformers mitigate the arc-flash labels and requirements?...13 When designing a safety protocol, should low-fault current/long clearing-time hazard and a high-fault current/short clearing-time hazard with the same incident energy be treated differently?...13 Is there a recommendation as to how often you need to update the arc-flash label?...13 Our facility completed an arc-flash hazard assessment and have dangerous level categories. Will the PGR-8800 or AF0500 reduce those levels and will that change the amount of PPE required?...13 If using this arc-flash relay as the only method to protect personnel from arc flash, should the arc-flash relay be tested and have a Safety Integrity Level (SIL)?...13 Catalog Pages PGR-8800 Arc-Flash Relay Catalog Page (Datasheet)...14 AF0500 Arc-Flash Relay Catalog Page (Datasheet) Littelfuse, Inc. 3 Littelfuse.com/ArcFlash
4 General Arc-Flash, PGR-8800, and AF0500 Questions How much energy is in a typical arc-flash incident? A phase-to-phase fault on a 480-V system with 20,000 amperes of fault current provides 9,600,000 watts of power. Imagine that there is no arc protection and the fault lasts for 200 milliseconds before the overcurrent protection clears it. The released energy would be 2 MJ, which corresponds roughly to a stick of dynamite. The energy formula is as follows: Energy = voltage x current x time = 480 V x 20,000 A x 0.2 s = 1,920,000 J For a given system voltage, two factors can be adjusted to reduce arc-flash energy: time and current Time can be reduced by using a device such as the PGR-8800 or AF0500 to rapidly detect an arc flash, thus cause the connected circuit breaker to trip at its instantaneous speed, overriding any inverse-time delay. Current can be reduced by using currentlimiting fuses or, in case of phase-to-ground faults, by using high-resistance grounding. What is the electrical symbol of an arc-flash relay? Although there is no formal symbol, Littelfuse is currently using the following: AFR PGA-LS20 or PGA-LS30 Fiber-optic Arc-Flash Relay PGA-LS10 Point How long has Littelfuse had an arc-flash relay in service? Littelfuse acquired Selco which has been manufacturing arc-flash relays for almost 15 years. The product was launched in the USA in August of Selco has had numerous installations throughout the world for many years and an estimated 13,000 arc-flash relays are installed world-wide. Do you have a list of references of companies using the PGR-8800 or AF0500? Yes, please contact your Littelfuse Sales Rep for a list of available references. Do you have an example of the PGR-8800 or AF0500 protecting a facility in the event of an arc-flash? Please view our arc-flash case study at Littelfuse.com/ArcFlash for an installation success story where the PGR-8800 saved a plant from catastrophic damage. What are the key considerations when choosing an arc-flash relay? We have written a white paper on considerations for choosing an arc-flash relay that examines advantages and drawbacks. It is available to download on our website at Littelfuse.com/ArcFlash. Littelfuse.com/ArcFlash Littelfuse, Inc.
5 Is nuisance tripping a problem? Normal in house lighting will not cause the arc flash relays to trip. Flash lights, direct sunlight or strong torch light on short distance however can cause tripping. If there are concerns about that, the best way to avoid nuisance tripping is by using the optical sensors in conjunction with current supervisory. This function is available with PGR In this case, you now are inputting phase CT s to the relay. In this scenario, the relay looks at the optical sensors for a fault and if it is true, then looks at the CT inputs to see if the current is above the nominal setting you configured, and if both conditions are true, then it will trip the relay. This prevents tripping in cases where there is significant light from an outside source (such as a welder, camera flash or direct sunlight). Does thermal imaging trip the PGR-8800 or AF0500 relay? Assuming the thermal imaging device is passively detecting heat in the switchgear by using the infrared light emitted, there will be no interference with the PGR-8800 or AF0500 relay or sensors. Would a camera-flash trigger the PGR-8800 or AF0500 relay? When the PGR-8800 or AF0500 is set to maximum sensitivity and the amount of time light is required to be present on the sensor is set to a minimum, it is possible that a small point-and-shoot camera close to the sensor could be sufficient to trip the relay. Typically, a compact camera s flash does not present enough intensity to cause a trip, except at VERY close proximity to the sensor. More advanced cameras and larger flashes can trip the PGR-8800 or AF0500 from a greater distance. In applications where this is a concern, it is recommended to use the PGR-8800 with optional CTs so that non-arc-flash light with no corresponding increase in current above normal operating conditions does not cause a trip. Where current supervision is used, both high current and intense light are required to have an arc-flash trip. The PGR-8800 relay can also be toggled into service mode to disable the trip-coil while a camera flash is used. It is imperative to restore the relay to normal operation once the flash photography is completed. Does the PGR-8800 or AF0500 relay detect ultra-violet light? The typical spectrum of light from an arc-flash is spread across the visible spectrum and so this is what the PGR-8800 and AF0500 relays are detecting. Ultraviolet light is mostly used to detect corona which can be present before an arc flash but is also present in higher voltage systems where no arc flash is imminent. Using ultraviolet light alone could lead to nuisance trips and the relay would only be looking at a small section of the total light from the arc. The point sensor has been designed to work with a wide spectrum of visible light. This is due to the fact that there are no distinct peaks in the spectrum of an arc; the peak depends on the material involved. An arc will typically peak on the visible spectrum and fade out toward the infrared area. Below is a graph depicting the PGA-LS10 s spectral sensitivity. The fiber sensor spectral sensitivity is nearly identical. The only difference is the lower part of the spectrum, below ~400 nm, will be cut off. Does the PGR-8800 or AF0500 provide fault location identification? Yes, each sensor has an on-board LED as well as a sensor LED on the arc flash relay that provides feedback identifying which sensor caused the trip. Does the PGR-8800 or AF0500 provide zone tripping? AF0500 has two high speed IGBT outputs for tripping of circuit breakers. Each sensor input can be assigned individually to any or both of the trip outputs. Thus AF0500 can trip up to 2 independent zones. Can you compare a service-mode instantaneous setting to an arc-flash relay? You would need to look at an actual application to do a true comparison. There are cases when lowering the instantaneous setting would serve the same benefit as the arc-flash relay in lowering incident energy. There may be some added complexity to making sure the maintenance mode is entered and also set back to operational mode. You do not want to have mis-coordination or tripping during starting of a motor if you start to exceed the instantaneous level. That being said our motor and feeder relays do have this mode of operation so they are useful. There are cases where the bus may be very large and not loaded (during commissioning for example). An arcing fault is high resistance and may not get near the instantaneous operating range of the breaker. That would be the worst case scenario for the instantaneous setting and show the most difference between it and the light detection method Littelfuse, Inc. 5 Littelfuse.com/ArcFlash
6 Do the different modes of the arc-flash relay have different response times? It is possible for the arc-flash relay to send a trip signal within 1 ms of detecting light above the threshold settings or within 1 ms of detecting light AND current. It is also possible to configure the relay to have additional delay as needed. What is the life of the PGR-8800 or AF0500? What maintenance is required and how often? The PGR-8800 and AF0500 relays have a 5 year warranty but depending on the environment it will last much longer than that. Maintenance required will depend on your application and principally focuses on removing dust collection on light sensors. We recommend checking the light sensors periodically (with a period relevant for the amount of dust) with an external light source to verify that the sensors are not obscured by dust build-up and using compressed air to blow dust off the sensors during regularly scheduled maintenance. It is good practice to periodically check that the IGBT trip output is tripping the breaker. Breaker maintenance is also critical to provide reliable and fast clearing time. Does the built in software consider the mechanical delay of all devices in the circuit and allow for changes to faster reacting main breakers? In reference to the coordination programs such as EDSA, ETAP and SKM. They all allow specific information to be entered on the circuit interrupter chosen in their extensive libraries. This can show changes of using faster main breakers fairly easily. Note if the equipment is older Littelfuse recommends testing the actual operating time of the breakers to make sure they are able to interrupt in the time that is allotted. How do arc-flash relays compare to Zone Selective Interlocking Protection (ZSIP) and Bus Differential? These are different technologies that detect and quickly clear faults. ZSIP will detect a fault and block an upstream protective device from operating until the local protective device has a chance to clear the fault. If not, the upstream device attempts to clear it. This takes valuable time (100ms for detection only) and may be difficult to retrofit. Bus Differential measures the difference of current going into and out of a device, such as switchgear. If the current supplied by the source travels through the switchgear to the load, all is well. If a fault occurs within the switchgear, the current going in does not equal the current going to the load. This detection method is much quicker (33ms for detection only) and may be more difficult and/or expensive to retrofit, depending on the number of CTs. Electrical Design Software What is SKM software and where can I find more information? SKM Software ( is one brand of power system analysis software that allows users to define the electrical parameters of their system and model its behavior. It is often used for coordination studies and arc-flash hazard analysis. Other software brands are ETAP, Easy Power and EDSA. How do you enter resistance-grounding or arc-flash relays into the SKM software for calculating arc flash? Resistance grounding presently shows no advantage in power system modeling software. The analysis of arc-flash energy is based on three-phase faults. High resistance grounding does eliminate the potential hazard from a single phase-to-ground fault. Different sources show 80 to 90% of faults in a plant start as a single phase-to-ground fault. Arc-flash relays can be entered as a definite time trip at 1 ms which is then added to the breaker clearing time. The advantage of arc-flash detection is that the breaker is no longer waiting for co-ordination of downstream devices. Another method often used to lower incident energy is to switch the relay or breaker settings to maintenance mode or a second setpoint group. These are lower settings with quicker operating times, often ignoring co-ordination of downstream devices with knowledge that a person is in the area. When the person leaves the area, the settings are returned to normal. How do you model your optical devices in SKM and ETAP, since the relay is detecting light? You must add the 1 ms PGR-8800 arc-flash trip time to the breaker shunt-trip operating or clearing time. The result will be a vertical line (definite-time) that shows the same response time regardless of the current. This demonstrates the advantage of using light for arc-flash detection. Littelfuse.com/ArcFlash Littelfuse, Inc.
7 How does power system analysis software, such as SKM, EasyPower, and ETAP, recognize arc-flash relays? SKM software list the PGR-8800 relay in the library and other companies are currently adding the relay. The figure below shows the PGR-8800 Arc-Flash relay modeled in SKM: The PGR-8800 has two (2) settings for overcurrent protection: Pickup is adjustable from 10 to 1000% of the secondary CT rating (any CT with a 5A secondary can be used) Time delay from 1ms to 2 seconds DISCLAIMER: PLEASE VISIT FOR INSTRUCTIONS ON HOW TO INSTALL THE SKM FILE. For arc-flash protection, the PGR-8800 and AF0500 must see light of sufficient intensity to initiate the tripping sequence. If current inhibit is enabled, the PGR-8800 will not send a trip signal unless there is also sufficient current. Both light and current trip levels can be adjusted. Currently, no power system analysis software package can model the light detection. They only model the overcurrent setting. To avoid the nuisance tripping with standard overcurrent protection, user typically increases the pickup value or time delay. This leads to arcing faults going unnoticed until it is too late. With the PGR-8800 and AF0500, this is not an issue as the light is used to prevent nuisance tripping on electrical noise or momentary overload conditions while still allowing for very fast tripping. Thus, the reaction time is reduced to that of the AF0500 or PGR-8800 (less than 1 ms unless configured otherwise) plus the circuit-breaker operating time, independent of the current Littelfuse, Inc. 7 Littelfuse.com/ArcFlash
8 Bolted Pressure Switches can also be used, but many of these devices have limitations in terms of interrupting and clearing time rating, so the user must check the ratings first. With either a CB or BPS, the opening time or clearing time can be modeled in SKM. The opening time or clearing time must include all devices in the sequence, which includes the shunt trip or undervoltage times as well as circuit breaker times. It is recommended to regularly maintain and test operation of circuit breakers. A qualified testing company could verify and provide the most accurate information on breaker clearing time. On AF0500 applications and PGR-8800 applications where only light detection is utilized, this clearing time value can be used in the software as a user-defined trip time. For the PGR-8800 applications an alternative is to use the PGR-8800 library model with the current set to a low value to reproduce the current-independent characteristic of optical detection. When current and light are both required then the current-inhibit level setting in the PGR-8800 should be used for the model. Applications and Installations What are the typical application / system voltages? The PGR-8800 and AF0500 can be used on electrical systems operating at any voltage (AC or DC) since it does not directly connect to the system. The system is monitored with light sensors and optional current transformers (for AC systems, PGR-8800 only) that can be selected for any current / voltage rating. The small size of the PGR-8800 and AF0500 allows for installation in any switchgear cubicle, transformer compartment, or motor control center bucket. What is the maximum recommended length from the PGR-8800 or AF0500 to the breaker? Application specific data is needed to determine the maximum distance of the relay from the circuit breaker. Please refer to the installation manual or call technical support for assistance. Can the PGR-8800 or AF0500 be used in low-voltage systems and will a low-voltage breaker s closing or opening cause a trip? When a low-voltage breaker is closing there is often a large inrush current that, depending on the configuration of the PGR-8800 or AF0500, could be sufficient to allow a high-intensity light source other than an arc-flash to cause a trip. While low-voltage breakers often produce an arc when they are opening, closing the breaker does not normally produce an arc, so the PGR-8800 or AF0500 should not operate unintentionally. When opening the breaker, an arc is typically present as part of normal operation of the breaker. If light sensors are placed such that the breaker arcing is visible then it is recommended to also use current-supervision. The breaker arcing during normal opening will cause a reduction in current because of the increased impedance and if using the PGR-8800, the current-supervision will not operate. Is internal arc classification of switchgear enclosures enough to eliminate an arc hazard? No, although it minimizes the hazard. The arc-flash relay may help prevent damage to the equipment and provide additional protection in the event that the doors are not properly closed. Depending on the impedance of the arc fault, the arc may persist for a long time in the switchgear and could exceed the rating of the gear. When working on an energized transformer, we use instantaneous settings at the feeder breaker relay. Can the arc-flash relay bring any benefit? According to IEEE 1584, the arcing current can be as low as 38% of the available bolted fault current. If the instantaneous trip setting of the circuit breaker is greater than the arcing current, the breaker could take seconds or minutes to open, thus creating a potentially DANGEROUS arc flash condition. The PGR-8800 or AF0500 can react in less than 1 millisecond regardless of the fault current, and initiate the tripping signal to open the breaker lowering the incident energy to a minimum. Is there a specific relay to protect all of a switchgear bus section against arc flash? The PGR-8800 or the AF0500 is ideal for protecting switchgear bus sections. The PGA-LS20 or PGA-LS30 fibre sensors are often used for those applications, depending on the bus arrangement. Are there control systems available that truly eliminate or control arc flash? If the equipment is energized there is not a single system that does that. Littelfuse.com/ArcFlash Littelfuse, Inc.
9 Light s and Current Transformers What are the installation guidelines for the sensors? The PGR-8800 and AF0500 Arc-Flash Relay and sensors are easily installed in retrofit projects and new switchgear with little or no re-configuration. Even elaborate systems with multiple power sources take minutes to configure using the relay s built-in USB interface software. Generally, it is recommended to mount 1 or 2 sensors per cubicle to cover all horizontal and vertical bus bars, breaker compartments, drawers, and anywhere that there is potential for an arc-fault. Threading a fiber-optic sensor through the cabinets and in areas where point-sensor coverage is uncertain results in complete coverage and an added level of redundancy. Even if policy is to only work on de-energized systems, all maintenance area should be monitored to prevent potential damage and additional cost. At least once sensor should have visibility of an arc fault if a person blocks the other sensor(s). C C C A B C PGA-LS10 Point Line-of-sight light sensor with a built-in LED to indicate sensor health or trip state. Comes standard with a 10 m (32 ft) cable. PGA-LS20, PGA-LS30 Fiber-Optic A 360 fiber-optic sensor detects light along the active length of the cable and has a built-in LED to indicate sensor health or trip state. Recommended installation is along busbars as well as in challenging spaces that have many compartments. Comes standard with two 10 m (32 ft) cables. Phase Current Transformers (Optional PGR-8800 only) Phase Current Transformers (CTs) are required to detect phase currents. When retrofitting systems, existing CTs with a 5 A secondary can be used. Below are some additional guidelines: First determine sensor placements, then consider zones. Ensure sensors and cables are not blocked by objects, either fixed or movable. Do not place sensors or fiber cable on live or energized components. Chose a location that will minimize collection of foreign debris and easy access for maintenance, if needed. Use care when handling, pulling, and securing cables. Avoid sharp bends (< 5cm) and high temperature (>80 C). Consider placements around air-magnetic circuit breakers. Consider movable parts and area accessible to personnel for commissioning, testing, inspecting, etc. Even though the sensors and cables have no exposed live parts are fully insulated, the placement and routing must comply with industry standard requirements on over-surface (creep) and through-air (clearance). What is a typical light sensitivity radius for a fiber optic sensor? This is a difficult metric to provide because the distance an arc can be detected by the fiber-optic sensor is dependent on many variables. However, the PGA-LS20 and PGA-LS30 fiber-optic sensors are factory calibrated so that it will have the same detection 2016 Littelfuse, Inc. 9 Littelfuse.com/ArcFlash
10 range as the PGA-LS10 when 60 cm (a standard section width) is exposed to the arc flash. In other words, a 3 ka arc can be detected from a distance of 2 m from the fiber assuming that the light is incident on 60 cm of fiber. However, the PGA-LS20 and PGA-LS30 also has an adjustment screw that allows the user to calibrate the fiber-optic sensor to be more sensitive (for smaller sections) or less sensitive (for larger ones) so that the characteristic matches that PGA-LS10 point sensors. We recommend a minimum of 20 cm of fiber exposed per section. The sensor is calibrated at the factory for 60 cm of fiber in each monitored compartment. When using the fiber optic sensor in compartments with less than 60 cm of fiber, the sensitivity may have to be adjusted. The sensor is unable to differentiate between 10,000 lux hitting 60 cm of fiber and 30,000 lux hitting 20 cm of fiber the same amount of light is transmitted through the fiber to the receiver. To achieve the desired sensitivity, the receiver (with the black thumb nut) must be adjusted. Is there a maintenance schedule for the sensors? Each sensor has an internal health LED. Its purpose is to verify the continuity of the sensor cabling and the internal sensor circuitry. This health check circuit will not detect dust buildup on the sensor. There are several ways to mitigate dust buildup. A sensor mounted at the top of an enclosure looking down is optimal. This configuration will not collect much dust in most cabinet installations, due to intensity of an arc combined with the reflections off the metal walls (even a dirty sensor will collect a great deal of light). s must be cleaned in order to maintain consistent sensitivity. cleaning should be part of regular maintenance and should be performed via compressed air or dry wipe down. A maintenance routine can be implemented to clean sensors at a set interval that is aligned with industry standard recommendations, such as NFPA 70B, Recommended Practice for Equipment Maintenance. A more proactive approach could also be used by putting the relay into Service Mode and shining a bright light on each sensor. A trip will be indicated if the sensor is able to detect the light but the breaker will not be tripped. If the relay light isn t indicating a trip then cleaning is necessary. At what intensity of light will the PGR-8800 or AF0500 indicate or trip? The PGR-8800 can be configured to trip between 9 klux and 25 klux. The relay s six sensor LEDs can be configured to indicate at various levels below the trip level to warn that light intensity is approaching the trip level. The AF0500 can be configured to trip between 10 klux and 30 klux. The relay s four sensor LEDs can be configured to indicate at various levels below the trip level to warn that light intensity is approaching the trip level. The fiber-optic sensor has an adjustable sensitivity (in addition to the relay sensitivity dial) that could be used to increase the sensitivity for a given length of fiber to levels below and above the relay setpoint. How would the fiber-optic sensors be installed in switchgear that is shipped in groups? Do these sensors come in various lengths or with repeaters? The fiber-optic sensors have two parts, an electrical cable connection to the relay and the light-sensitive fiber-optic cable. Splitting a fiber is a challenge because a bad splice can result in decreased or increased sensitivity and failure to operate or nuisance tripping. Shipping splits should be wired so that the fiber-optic sensor cable does not traverse multiple sections. The electrical part of the sensor, connecting the sensor to the relay, can be up to 50 m long and is much easier to connect at the final installation as well as much more durable than optical fiber. It is important to remember that a light-collecting fiber-optic cable behaves quite differently from a transmission-only shielded fiber-optic cable. The latter case is more frequently used, especially in telecommunications industries and can have very large lengths, but in that case light is fed directly into the tube at a low angle of incidence and losses along the cable are very low. For the PGA-LS20 and PGA-LS30 fiber-optic sensors, the entire fiber-optic cable is designed to absorb light incident on the surface, bend the light to trap it in the cable, and then keep it in the cable. However, light is lost along the length of the cable and the longer the light must travel along the cable, the more light is lost. The active lengths of the PGA-LS20 and PGA-LS30 are 8m and 18m respectively. Repeaters are not available as the cost may be too high compared to installing a second fiber-optic sensor. Repeaters may cause timing issues for the sensor-check signal. How do you test the sensors, are they fail-safe? A sensor-check circuit in the PGR-8800 and AF0500 tests the sensor once per second to verify that the sensor assembly is functioning correctly and that it is connected. The signal is sent from the relay along the cable to the sensor which activates an Littelfuse.com/ArcFlash Littelfuse, Inc.
11 internal LED. A failure in the sensor circuitry or cable would result in a loss of check signal. The PGR-8800 and AF0500 recognize this signal loss as a missing sensor and will indicate an error condition on the sensor, relay faceplate and the online output will change state. The user can decide what to do with this relay output and whether it will trip the system or simply signal an alarm. The fiber-optic sensor works the same way except that the signal travels through the length of the fiber-optic cable so a break or crimp in that cable is also detected. For the PGR-8800, sensors can be tested individually by putting the relay into Service mode and shining a bright light source on the sensor. A trip will be indicated if the sensor is able to detect the light but a trip signal will not be sent to the breaker. A highpower flashlight can serve to verify the sensors are properly detecting light. The power required on the flashlight is difficult to quantify because of the way the light is spread and focused, but a 3 million candela flashlight has proven more than sufficient for use on point sensors. What is the purpose of the Current Transformers (CTs) and are they required? The purpose of the CTs is to validate an arcing condition, although CTs are not required for operation. The PGR-8800 and AF0500 relays can detect light only to send a trip signal. If the CTs are used with the PGR-8800, the relay will only send a trip signal if both light and overcurrent conditions are detected. In applications where high-intensity light is a possible, overcurrent detection can be used to prevent nuisance tripping. Resistance Grounding Would a ground fault on the main switchgear act as an arc-flash relay? HRG systems eliminate arc-flash hazards associated with ground-faults per IEEE Std (Red Book). Even though tests have shown that HRG systems also reduce the arc-flash energy with phase-to-phase arcing faults, it can not be used to reduce PPE. Arc-Flash Relays can be used to identify these arcing conditions and significantly reduce arc-flash hazards. In many applications, both are used to increase uptime and protection. Can we have more than 5A L-G fault available in HRG in any circumstances? The maximum ground-fault current is physically limited to the value of the resistor, assuming no resistance in the fault and return path. For example, on a 480V system, for a ground-fault current of 5A, the resistor value is 277V / 5A = 55.4ohms. The 55.4ohm resistor sets a maximum ground-fault current of 5A. However, it is typically lower due to either fault resistance and/or resistance in return path. In some older facilities where the return path is weak, a lower resistance value is used to allow for a higher groundfault current. Is there protection (resistance grounding) for delta circuits? HRG systems are only used on 3-wire systems, either wye with floating neutral or delta. If used on wye systems, the resistor is simply directly connected to the neutral bushing. If it is a delta system, typically a zig-zag transformer is used to create a neutral point (or three single-phase transformers are used). In any case, a neutral point, which is used to connect the resistor. The code only allows HRG if you didn t have neutral to ground loads (i.e. 277 V). Would this only be applied on 3-wire systems? Correct, the NEC prohibits using HRG systems on systems with line-to-neutral loads. The reason is that the elevated neutral voltage, which occurs during a ground fault, may backfeed a circuit causing a dangerous condition. However, CEC allows HRG systems on these systems if the entire system is tripped offline during a ground fault. How do you address the system-leakage capacitance on HRGs, especially at medium-voltage levels? You are correct that at medium-voltage, the system leakage capacitive current increases, which is a function of voltage. Fortunately, this has been well documented over the years and tables are used to estimate the leakage current. Depending on this value, the ground-fault on a HRG system may not be recommended to remain on system. Is it possible to apply HRG to a distribution transformer in order to minimize the arc-flash hazard when working on the secondary of the transformer? 2016 Littelfuse, Inc. 11 Littelfuse.com/ArcFlash
12 High-Resistance Grounding (HRG) has some limitations. For example, it cannot be used on systems with line-to-neutral loads. Another limitation is the amount of current flow during a ground-fault. HRG limits the current to typically 10A or less, which may not be enough to detect on your distribution system. If these are not issues, consider using HRG systems. However, perform a detailed engineering study to ensure other limitations (such as voltage shift) are acceptable. If you have a neutral-grounding resistor, is an arc-flash relay also recommended? Yes, because the NGR only reduces or eliminates arcing ground faults. For the other type of arcing faults, phase faults, the PGR-8800 or AF0500 arc-flash relay can be used to provide maximum protection. Typically 95% of all faults are ground faults, so the NGR reduces or eliminates most of the risk and the PGR-8800 or AF0500 provides the 5% protection in the switchgear. Safety Regulations Do arc-flash relays lower the Personal Protective Equipment (PPE) required? In order to lower the amount of PPE required, the incident energy must be reduced. There are two ways to lower the incident energy of an arc-flash event, reducing the fault current or the clearing time and reducing the available energy. Reducing the available energy can be achieved by using current-limiting fuses and, for single-phase faults, resistance grounding. Reducing the clearing time typically is not possible when using overcurrent protection due to system coordination requirements. Current-based protection must have sufficient delay to prevent unnecessary tripping on momentary overload or current spikes, thus losing valuable reaction time. Arc Flash relays resolve this issue by detecting overcurrent and light,which allows for the quickest reaction time in the industry. The PGR-8800 and AF0500 relays can detect an arcing condition and send a trip signal to the circuit breaker within 1ms. This detection time is much faster than standard protection and circuit breakers, which means using an Arc Flash relay in combination with a circuit breaker (PGR-8800 only) will lower the incident energy or Arc Flash hazards. This results in an increase in worker safety, less fault damage, and improved uptime. Since the arc-flash hazard has decreased, the associated PPE may also be lowered. The exact amount will depend on user setpoints, so it must be modeled in the system to determine the new incident energy and PPE. Can arc-flash relays eliminate the need for HRC 3 or 4 clothing? Please use our reduction workbook to learn more about incident energy reduction at Littelfuse.com/ArcFlash. Can arc-flash relays reduce PPE required if only walking in front of the equipment, or opening the cabinet to read a nameplate? If the worker is within the flash protection boundary of the exposed (line of sight) energized part, then the PPE category on the label must be used. If the door is closed or cover is on, check NFPA 70E Table 130.7(C)(15)(a) or (b) for a reduction in HRC. What are the regulatory agencies opinion on arc-flash relays on life safety and critical circuits? Hospitals and health care facilities are not exempted from OSHA safety requirements. They rely on the experience and reputation of the Professional Engineer s assessment. What are the associated arc flash risks for equipment supplied by a 125kVA transformer? The 2002 edition of IEEE 1584 (often referred to as the 125 kva Exception) permits a study to exclude calculations on circuits with voltages less than 240V and fed by transformers 125 kilovolt-amperes (kva) and smaller. This exception was based on tests that indicated, that if an arc flash occurs at lower voltages and also with a lower magnitude of short-circuit current, it would be difficult to sustain the arc. Therefore, it would result in a lower level of incident energy. When designing a safety protocol, should low-fault current/long clearing-time hazard and a highfault current/short clearing-time hazard with the same incident energy be treated differently? Littelfuse.com/ArcFlash Littelfuse, Inc.
13 If the incident energy is the same, No. However, if the incident energy is more or less, NFPA 70E requires the worker to use arc rated clothing equal to or greater than the possible maximum incident energy. Is there a recommendation as to how often you need to update the arc-flash label? NFPA 70E Article requires the arc flash analysis to be updated when major modifications occur and reviewed every 5 years, whichever occurs first. Our facility completed an arc-flash hazard assessment and have dangerous level categories. Will the PGR-8800 or AF0500 reduce those levels and will that change the amount of PPE required? We recommend you contact the engineer or engineering firm that performed the assessment and request them to re-run the study at that equipment using the PGR-8800 or AF0500 relay to lower the hazards and use our Arc-Flash Energy Reduction Workbook, which can be found on Littelfuse.com/ArcFlash If using this arc-flash relay as the only method to protect personnel from arc flash, should the arc-flash relay be tested and have a Safety Integrity Level? (SIL) We don t recommend that the PGR-8800 or AF0500 be used as the only method to protect personnel from arc-flash. Adequate PPE should be worn based on the results of an arc-flash study. Resistance grounding is highly recommended to eliminate single phase-to-ground arc flashes. Current-limiting fuses and relays with maintenance mode settings or dual set-point groups are also highly recommended Littelfuse, Inc. 13 Littelfuse.com/ArcFlash
14 PGR-8800 SERIES (D1000) Arc-Flash Relay PGR-8800 & AF0500 Arc-Flash Relay Technical FAQ Description The PGR-8800 is a microprocessor-based relay that limits arc-fault damage by detecting the light from an arc flash and rapidly tripping. Phase-current-transformer inputs are provided for current-constrained arc-flash protection and, when so equipped, a programmable definite-time overcurrent function can be enabled. An optical sensor on the PGR-8800 and adjustable trip level reduce the chance of nuisance tripping by setting a threshold for ambient light. s, inputs, and connections are monitored to ensure fail-safe operation. A secondary solid-state trip circuit provides a redundant trip path. A USB port is used for configuration and access to event logs and graphs. Simplified Circuit Diagram 5-A-SECONDARY PHASE CT s (Recommended) A D B Optical s The PGR-8800 accepts both PGA-LS10 and PGA-LS20/PGA- LS25/PGA-LS30 optical sensors, designed to collect light over a wide angle and with high sensitivity. For fast fault location, front-panel and sensor LED s indicate sensor health and which sensor detected an arc fault. C L1 L2 PGR-8800 (Arc-Flash Protection Relay) Trip 24 Vdc Battery PGA-1100 Backup (Diode Logic Unit) (Optional) (Optional) For detailed wiring diagram, see adjacent page. Ordering Information C PGA-LS10 (Point ) A B PGA-LS20/ PGA-LS25/ PGA-LS30 (Fiber-Optic ) Placement The PGR-8800 Arc-Flash Relay and sensors are easily installed in retrofit projects and new switchgear with little or no re-configuration. Even elaborate systems with multiple power sources take minutes to configure using the relay s built-in USB interface software. Generally, it is recommended to mount 1 or 2 sensors per cubicle to cover all horizontal and vertical bus bars, breaker compartments, drawers, and anywhere that there is potential for an arc-fault. Threading a fiber-optic sensor through the cabinets and in areas where point-sensor coverage is uncertain results in complete coverage and an added level of redundancy. Even if policy is to only work on de-energized systems, all maintenance areas should be monitored to prevent potential damage and additional cost. At least one sensor should have visibility of an arc fault if a person blocks the other sensor(s). ORDERING NUMBER PGR (UL, CE, C-tick) PGR CC (UL, CE, C-tick) DESCRIPTION Arc-Flash Relay Arc-Flash Relay, Conformally Coated ACCESSORIES PGA-LS10 (A1000) PGA-LS20 (A2000) PGA-LS25 (A ) PGA-LS30 (A ) PGA-1100 (D1100) REQUIREMENT Required* Required* Optional Local Circuit Breaker Current Transformer Recommended *At least one sensor is required. However, the exact number of sensors for proper coverage depends on the application. D D D Littelfuse.com/ArcFlash Littelfuse, Inc.
15 PGR-8800 SERIES (D1000) Arc-Flash Relay Features & Benefits FEATURES Arc-Flash trip time <1 ms Multiple sensors (up to 24) Fail-safe system Redundant trip circuit Adjustable light sensitivity LED indication (on unit and each sensor) Current detection Optical detection Digital inputs (6) Service mode Trip coil contact Indication contacts USB interface Built-in sensor Universal power supply/battery backup Data logging Modbus Upstream Tripping BENEFITS Limits arc-flash damage and risk of injury Single module can monitor 6 sensors. Up to 4 PGR-8800 units can be linked into one system Continuous monitoring of optical sensors and inputs ensures protection Solid-state backup arc-detection circuit adds a second layer of safety Allows for operation in bright environments and maximum sensitivity in dark environments 18 LEDs provide at-a glance status for module and I/O state Phase-CT inputs provide overcurrent protection and prevent nuisance trips Point and fiber-optic sensors provide wide detection area with sensor health trip indication Two each: remote trip, inhibit, and reset inputs Allows for system test without tripping Solid-state Vdc/ Vac IGBT Form C and status outputs Data logging and configuration software uses a USB interface with no drivers or software installation Can be used in single-sensor systems, as a seventh sensor, and for calibration Vac, Vdc, or Vdc supply accepted. Ability to charge and run off an external, user-supplied 24 Vdc battery. On-board event recorder helps with system diagnostics Remotely view measured values, event records & reset trips Ability to trip upstream device if the local breaker fails to clear the fault Wiring Diagram ARC-FLASH RELAY PGR-8800 (optional) ARC-FLASH RELAY PGR-8800 (optional) ARC-FLASH RELAY PGR-8800 (optional) DIODE LOGIC UNIT PGA-1100 (optional) STATUS STATUS STATUS LINK CONTROL POWER DIGITAL INPUTS and BATTERY ONLINE SERVICE TRIPPED TRIP COIL ARC-FLASH RELAY PGR-8800 SERIES PGA-LS10 PGA-LS20 PGA-LS25 or PGA-LS30 OPTICAL SENSOR PGA-LS10 PGA-LS20 PGA-LS25 or PGA-LS30 OPTICAL SENSOR PGA-LS10 PGA-LS20 PGA-LS25 or PGA-LS30 OPTICAL SENSOR PGA-LS10 PGA-LS20 PGA-LS25 or PGA-LS30 OPTICAL SENSOR PGA-LS10 PGA-LS20 PGA-LS25 or PGA-LS30 OPTICAL SENSOR PGA-LS10 PGA-LS20 PGA-LS25 or PGA-LS30 OPTICAL SENSOR PHASE CT (recommended) PHASE CT (recommended) PHASE CT (recommended) Accessories A B C D PGA-LS10 (A1000) Point Line-of-sight light sensor detects an arc as small as 3 ka within a 2-m half-sphere. health and trip indication. Dimensions: See PGR-8800 Manual PGA-LS20 (A2000)/PGA-LS25 (A )/PGA- LS30(A ) Fiber-Optic 360 light sensor for tricky installations with many shadows or to run along bus bars. health and trip indication. Dimensions: See PGR-8800 Manual PGA-1100 (D1100) Diode Logic Unit This module allows multiple PGR-8800 relays to trip the same breaker, for example an upstream or a tie-breaker. Dimensions: H 80mm (3.15 ) W 20mm(.79 ) D 70mm(2.76 ) Current Transformers Eliminate nuisance arc-flash trips and use for overcurrent protection. Specifications IEEE Device Numbers Overcurrent (50), Arc Flash (AFD) Input Voltage Vac, Vdc, and Vdc Dimensions H 130 mm (5.2 ); W 200 mm (7.9 ); D 54 mm (2.2 ) Optical Trip Settings 9-25 klux, 800 μs-20 s Current Trip Setting (A) Programmable Indication Contact Mode Fail-safe Trip Coil Voltage (1) Vdc, Vac Trip Coil Contact Mode Selectable fail-safe or non-fail-safe Redundant Trip Circuit Standard feature Input Monitoring Standard feature USB Interface Standard feature Trip, Reset, Service Buttons Standard feature Expandable System Link up to 4 PGR-8800 units Conformally Coated Optional Warranty 5 years Mounting DIN (with D0050 adapter clips), Surface NOTE (1) - Contact Littelfuse for trip coil voltages higher than 300 Vdc/Vac. Rev: 4-G Littelfuse reserves the right to make product changes, without notice. Material in this document is as accurate as known at the time of publication. Visit Littelfuse.com for the most up-to-date information Littelfuse, Inc. 15 Littelfuse.com/ArcFlash
16 AF0500 Arc-Flash Relay Description The AF0500 is a microprocessor-based arc-flash relay that limits arc-fault damage by detecting the light from an arc flash and rapidly tripping the feeder breaker. The unit is well suited for switchgear, transformer and power converter applications. s, inputs, and connections are health monitored to ensure fail-safe operation. A secondary solid-state trip circuit provides a redundant trip path. A USB port is used for configuration and access to event logs. AF0500 includes an Ethernet interface and supports Modbus TCP communication. Zone tripping, upstream breaker tripping and tie breaker tripping applications can be easily configured. Features & Benefits FEATURES Ordering Information BENEFITS 4 arc sensor inputs Supports both point and fiber sensors Arc-Flash trip time <1ms 2 IGBT high speed trip outputs Universal Power Supply Fail-safe system LED indication (on unit and each sensor) Discrete wire networking USB interface Data logging Ethernet interface Limits arc-flash damage and risk of injury Supports applications such as upstream breaker tripping or tie breaker tripping Vac, Vdc, or Vdc supply Continuous monitoring of optical sensors and inputs ensures protection Trip and sensor status indicated both on relay and sensors Multiple AF0500 units can be interconnected to form a system Data logging and configuration software uses a USB interface with no drivers or software installation On-board event recorder for system diagnostics (2048 log lines) Modbus TCP communication A number of control inputs allows interconnection of multiple AF0500 units to form a system. Optical s The AF0500 accepts both PGA-LS10 point sensors and PGA-LS20/PGA-LS30 fiber optical sensors. Thus any combination of fiber or point sensors is supported. For fast fault location, front-panel and sensor LEDs indicate sensor health and which sensor detected an arc fault. Placement The AF0500 Arc-Flash Relay and sensors are easily installed in retrofit projects and new switchgear with little or no re-configuration. Simple applications work straight out of the box with no need of PC configuration. More complex systems with multiple power sources are configured using the relay s built-in USB interface software. Generally, it is recommended to mount 1 or 2 sensors per cubicle to cover all horizontal and vertical bus bars, breaker compartments, drawers, and anywhere that there is a risk for an arc fault. Threading a fiber-optic sensor through the cabinets and in areas where point-sensor coverage is uncertain results in complete coverage and an added level of redundancy. Even if policy is to only work on de-energized systems, all maintenance areas should be monitored to prevent potential damage and additional cost. ORDERING NUMBER AF AF CC DESCRIPTION Arc-Flash Relay Arc-Flash Relay, Conformally Coated Arc Flash Fiber-Optic Point s Littelfuse.com/ArcFlash Littelfuse, Inc.
17 AF0500 Arc-Flash Relay Applications Zone Tripping AF0500 can trip 2 separate zones. s can be assigned to the zones individually through PC configuration. Tie Breaker Tripping In case of an arc in one section of the switchboard, the AF0500 can trip both the incoming feeder and the tie breaker simultaneously. Thus the affected part of the switchboard is isolated from the non-affected part. Incoming Feeder Incoming Feeder Zone 1 Zone 2 Bus Tie Upstream Breaker Tripping In case of failure of the local circuit breaker to open, another trip command is sent after a short delay to an upstream breaker to clear the fault. Incoming Feeder Upstream Breaker Local Breaker Accessories Specifications PGA-LS10 (A1000) Point Line-of-sight light sensor detects an arc as small as 3 ka within a 2-m half-sphere. Includes health and trip indication. PGA-LS20/PGA-LS30 Fiber-Optic 360 light sensor to run along bus bars. health and trip indication. PGA-1100 (D1100) Diode Logic Unit This module allows multiple arc-flash relays to trip a common breaker, for example a tie-breaker. Power Supply Universal 100 to 240 Vac (+10%, -15%) 50/60 Hz, 20 VA, 110 to 250 Vdc (+10%, -20%) 8 W Low Voltage 24 to 48 Vdc (+10%, -20%), 4 W Inputs 4 light sensor inputs for PGA-LS10, PGA-LS20 and PGA-LS30 sensors Trip Outputs 2 IGBT switches UL Rating: 120/240 Vac, 1800 VA, 0.75 A maximum continuous, 125/250 Vdc, 138 VA, 0.75 A maximum continuous Supplemental Rating: Make/Carry 30 A for 0.2s Voltage Rating 24 to 300 Vac, 24 to 300 Vdc Current Rating 20 A for 2 s, 10 A for 5 s Communication Ethernet, 2 ports with internal Ethernet switch, Modbus TCP Dimensions H 130 mm (5.1 ); W 200 mm (7.9 ); D 54 mm (2.1 ) Shipping Weight 0.9 kg (2 lbs) Operating Temp. 40 C to +70 C ( 40 F to 158 F) Certification UL Listed (UL508), CE, C-tick, FCC Warranty 5 years Mounting Surface, DIN (with optional D0050 adapter clips) Rev: 1-A Littelfuse reserves the right to make product changes, without notice. Material in this document is as accurate as known at the time of publication. Visit Littelfuse.com for the most up-to-date information Littelfuse, Inc. 17 Littelfuse.com/ArcFlash
18 Experts in Arc-Flash and Electrical Safety For over 85 years, Littelfuse s products have helped protect electrical equipment used in mining, petrochem, marine, alternative energy and general industrial applications. We offer Littelfuse Startco protection relays and custom power centers as well as Littelfuse Selco generator protection, controls and alarm panels. Our product offering includes: Littelfuse product range includes: g Arc-Flash Relays g Neutral-Grounding Resistors g Protection Relays g Fuses and Fuse Holders g Generator Control & Protection g Engine Control & Diagnostics g Alarm Monitors g Custom Power Centers Littelfuse products are certified to many standards around the world. To check certifications on specific product please refer to the product datasheet on Littelfuse.com. Littelfuse World Headquarters 8755 West Higgins Road, Suite 500 Chicago, IL USA Tel: Fax: [email protected] Littelfuse Startco 3714 Kinnear Place Saskatoon, SK S7P 0A6 Canada Tel: Fax: [email protected] Littelfuse SymCom 222 Disk Drive Rapid City, SD USA Tel: Fax: [email protected] Littelfuse Selco Betonvej 10 DK Roskilde Denmark Tel: Fax: [email protected] /ARCFLASH Protection Relays & Controls Catalog The comprehensive line of electronic and microprocessor-based PF130 protection relays safeguard equipment and personnel to prevent expensive damage, downtime or injury due to electrical faults. PGR-8800 Arc-Flash Relay Brochure PF136 Arc-Flash Protection White paper PF765 Arc-Flash Case Study PF350 Littelfuse offers one of the fastest Arc-Flash Protection relays on the market. The PGR-8800 can detect a developing arc flash extremely fast and send a trip signal before any significant damage occurs. Knowing how to choose the right Arc-Flash Relay for the application can be a challenge, but use our white paper to determine the key considerations for selecting an Arc-Flash Relay. The Littelfuse PGR-8800 prevented $1 Million in damage, months of downtime and possible injury to employees at one customer location. Learn how the PGR-8800 lowered the HRC of the equipment and prevented a catastrophic accident. To view all Littelfuse product catalogs, visit our website at Littelfuse.com/Catalogs For the full line of Littelfuse protection relays and generator controls, visit Littelfuse.com/RelaysControls 2016 Littelfuse, Inc. Scan code with your mobile device to download the Protection Relays & Controls Catalog. Specifications, descriptions and illustrative material in this literature are as accurate as known at the time of publication, but are subject to changes without notice. Visit Littelfuse.com for the most up-to-date technical information. Form: PFD712 Rev: 4-G
Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer [email protected]. Electrical Hazards 2/18/2015. Shock.
Arc Flash Hazards Dan Neeser Field Application Engineer [email protected] Electrical Hazards Electrical Hazards Shock Arc Flash Arc Blast 2 1 Arcing Fault Basics 35,000 F Radiant Heat & UV Speed of
Part 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
Arc Flash Energy Mitigation Techniques
Arc Flash Energy Mitigation Techniques When short circuits occur on an electrical distribution system, an arc flash event usually forms. These arc flash events can cause dangerous and potentially fatal
Arc Flash Avoidance and its Application to Overhead Traveling Cranes
Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Catalog. Arc Guard System TM TVOC-2
Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already
How to reduce exposure to arc flash hazards
GE Energy Industrial Solutions How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not
Permissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
White Paper Mervin Savostianik P. Eng. Littelfuse, Inc.
Ground-Fault Protection with VFDs How to use a Sensitive Relay to Find Hard-to-Spot Ground Faults in VFDs on Resistance-Grounded Systems White Paper Mervin Savostianik P. Eng. Littelfuse, Inc. How to Use
misconceptions about arc-flash hazard assessments
misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600
Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents
Sentron Series Circuit Breakers
Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of
Safety By Design. Strategies for Electrical Contractors
Safety By Design Strategies for Electrical Contractors Introduction Engineering and system design significantly impact worker safety System design provides opportunity to eliminate/minimize workers exposure
New standardized approach to arc flash protection
New standardized approach to arc flash protection Samuel Dahl Juha Arvola Tero Virtala Arcteq Relays Ltd Arcteq Relays Ltd Arcteq Relays Ltd Wolffintie 36 F 11 Wolffintie 36 F 11 Wolffintie 36 F11 65200
AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
Arc Flash Mitigation. Executive summary. by Antony Parsons, Ph.D., P.E.
by Antony Parsons, Ph.D., P.E. Executive summary Arc flash events can result in significant injury to workers, including severe burn injuries. The most effective arc flash safety programs are not those
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
ABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
Choosing the Best Solution for Reducing Arc Energy
CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors
Guidelines on the Short Circuit Current Rating for Industrial Control Panels
usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A
ELECTRICAL SAFETY RISK ASSESSMENT
ELECTRICAL SAFETY RISK ASSESSMENT The intent of this procedure is to perform a risk assessment, which includes a review of the electrical hazards, the associated foreseeable tasks, and the protective measures
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers
NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth
Table of Contents. TransformerIQ FAQs 1
[12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
Understanding Arc Flash
Understanding Arc Flash Presented by Eddie F. Jones, PE 1 2 3 4 5 Five to 10 arc flash explosions occur in electric equipment every day in the United States. This number does not include cases in which
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit
Arc Flash Mitigation & Selective Co-ordination
Arc Flash Mitigation & Selective Co-ordination Michael Hodder March 2015 Overview This seminar will provide information on: Mitigating arc flash hazards Selective Coordination What can we do to make these
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? Comparing apples-to-apples bids Plant Services Special Report A shock hazard analysis should be included as part of an arc
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC
Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet
Instruction Bulletin 63230-216-244B1 LaVergne, TN, USA MCS025 Sync-Check Module Installation Sheet Retain for future use. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Only qualified electrical
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1
How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE
Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
Common Electrical Hazards in the Workplace Including Arc Flash. Presented by Ken Cohen, PhD, PE & CIH (Ret.)
Common Electrical Hazards in the Workplace Including Arc Flash Presented by Ken Cohen, PhD, PE & CIH (Ret.) 1 What s New In February 1972, OSHA incorporated the 1971 edition of the National Fire Protection
SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Assessing The Hazards Of High and Low Voltage Single-Phase Arc-Flash By Albert Marroquin One common question
Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.
Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible
Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.
Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections
Generator Differential Relay Electrical Apparatus
Generator Differential Relay Electrical Apparatus MD3G Rotating Machine Differential Relay 150-3 The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor
ARC FLASH HAZARD MITIGATION. Industrial Tests, Inc. [indtests.com]
ARC FLASH HAZARD MITIGATION ARC FLASH HAZARD MITIGATION NWHA TECHNICAL SEMINAR May 17, 2012 Richard D Reese Power Systems Manager Industrial Tests, Inc. Rocklin, California [[email protected]; 916-660-2837]
Fault Characteristics in Electrical Equipment
1. Introduction Proper design and installation of electrical equipment minimizes the chance of electrical faults. Faults occur when the insulation system is compromised and current is allowed to flow through
IMPROVE SAFETY AND RELIABILITY WITH INSTANT ARC-FLASH DETECTION OVER 13,000 LITTELFUSE ARC-FLASH RELAYS INSTALLED WORLDWIDE
IMPROVE SAFETY AND RELIABILITY WITH INSTANT ARC-FLASH DETECTION OVER 13,000 LITTELFUSE ARC-FLASH RELAYS INSTALLED WORLDWIDE Littelfuse Arc-Flash Relays Fast Arc-Flash Detection Circuit breakers (CBs) or
Eaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
ARC FLASH HAZARD OVERVIEW. Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc.
ARC FLASH HAZARD OVERVIEW Presented August 13, 2015 WWOA Lake Michigan District by Mead & Hunt, Inc. ARC FLASH EXPERIENCE Christopher J. DeWaal, MS, MEM, PE, LEED AP, HACCP How did I get involved? A client
A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS
A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS By: Gabriel Arce, ABB, San Luis Potosi, Mexico Casey McCollum, ABB, Houston, TX John
System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems
System Grounding and Ground-Fault Protection Methods for -Supplied Power Systems Bill Brown, P.E., Square D Critical Power Competency Center 1. INTRODUCTION The use of solid grounding for -supplied power
Understanding Emergency Power Off (EPO)
Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single
The Application of Circuit Breakers to Reduce Downtime in Datacentres
The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System
Fortune Oregon Data Center Increases Reliability with a High Resistance Grounding System Cory David Smith, Project Manager, ECOM Engineering Inc., and David Lawrence Smith, Principal, ECOM Engineering
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software
A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software Abstract: The nature of explosive equipment failures, and the rate of serious burn injuries in the electrical industry
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Low Voltage Transformer Through-Fault Protection: A System Approach
Data Bulletin 7400DB1001 Nashville, TN USA Low Voltage Transformer Through-Fault Protection: A System Approach Introduction Low Voltage Transformer Protection Criteria NEC Article 450 Transformers and
1SFC170011M0201 EN, Rev C. Arc Guard System, TVOC-2 Installation and maintenance guide
EN, Rev C Arc Guard System, TVOC-2 Installation and maintenance guide Original instruction This is the Installation and maintenance guide for Arc Guard System Type TVOC-2. Document number: Revision: B
Analyzing Electrical Hazards in the Workplace
Analyzing Electrical Hazards in the Workplace By Dennis K. Neitzel, CPE AVO Training Institute, Inc. The need for analyzing electrical hazards in the workplace has been recognized by a small segment of
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS Claudio S. Mardegan [email protected] www.engepower.com Phone: 55 3579-8777
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Arc Flash Safety in 400V Data Centers
Arc Flash Safety in 400V Data Centers Strategies for protecting employees from underappreciated yet potentially deadly hazards By Dave G. Loucks PCM Solution Manager Eaton Corporation Executive summary
Low Voltage Switchgear
Arc Resistant Switchgear n Insulated and isolated bus n Separation barriers and top venting n Breaker shutters 12 SWITCHGEAR Arc resistant metal-enclosed low voltage switchgear is an optional product offering
Arc Protection Relay REA 101. Operator s Manual
Arc Protection Relay 1MRS751003-MUM Issued: 08.04.1998 Version: F/23.06.2005 Arc Protection Relay 1. About this manual...5 1.1. Copyrights...5 1.2. Trademarks...5 1.3. Guarantee...5 1.4. General...5 1.5.
TC-9102 Series Surface Mount Temperature Controllers
TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may
Contractors Guide Central Inverter System Installation
Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.
GE Protection and Control Business Department. Page 1 Date 5/11/99
GE Protection and Control Business Department Page 1 GE Protection and Control Business Department Proven Overcurrent Protection with Power Management Communication The The Advantages of Microprocessor
Safety Requirements Specification Guideline
Safety Requirements Specification Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:[email protected] -1- Summary Safety Requirement
Executive Summary. Technical Description
Executive Summary The Cellwatch system is built using modules. The majority of the system is constructed with Data Collection Modules (DCMs). The DCMs are optically linked to Control Units (CUs) that in
Mission Critical Data Center Systems
Mission Critical Systems Mission Critical/ Electrical Distribution Systems Data center electrical distribution designs are rapidly evolving, driven by needs such as increasing power densities, energy efficiency,
Applied Electronics. Commercial Dimming System UPDATE NOTICE
REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
CompactLogix Power Supplies Specifications
Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,
National Craft Assessment and Certification Program S P E C I F I C A T I O N S
National Craft Assessment and Certification Program S P E C I F I C A T I O N S INDUSTRIAL ELECTRICIAN V4 ELEC26_O4 Released September 2013 Focus Statement An Industrial Electrician must be able to interpret
AC and DC Drive System Installation Information
Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS
Atlanta Chapter IEEE Industry Applications Society
Atlanta Chapter IEEE Industry Applications Society Electrical Equipment Room Design Considerations presented at the Sheraton Buckhead Hotel Atlanta, Georgia November 20, 2006 Outline 1. Definitions 2.
Current Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
NFPA 70E Updates Affect Your Most Valuable Assets
NFPA 70E Updates Affect Your Most Valuable Assets EXECUTIVE SUMMARY Electrocution is a well-known hazard associated with direct contact with electrical energy. According to the U.S. Department of Labor,
Reverse-feed applications for circuit breakers
Technical Publication PU01200001E Contents Description Page Intoduction.......................................................................... 2 breaker classifications..........................................................
UniStream CPU-for-Panel
UniStream CPU-for-Panel Installation Guide USC-P-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for industrial automation. This guide provides basic
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves
Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves White Paper July 2010 Integrating surge protective devices (SPD) into distribution equipment (i.e. switchgear, switchboards,
Applications. Remote Display Mounting Kits
June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC
Maintenance Report MEDIUM VOLTAGE POWER STATION 500SC / 630SC / 800SC / 900SC / 1000 1SC / 1000 2SC / 1250SC / 1600SC / 1800SC / 2000SC Project name: Customer: Address, location of the system: Serial number
Installation guide H-5500-8554-03-A. HSI hardwired system interface
Installation guide H-5500-8554-03-A HSI hardwired system interface 2008-2011 Renishaw plc. All rights reserved. This document may not be copied or reproduced in whole or in part, or transferred to any
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS
Definition: Zone Selective Interlocking (ZSI) - A method which allows two or more ground fault breakers to communicate with each other so that a short circuit or ground fault will be cleared by the breaker
Proper Application of 415V Systems in North American Data Centers. A White Paper from the Experts in Business-Critical Continuity
Proper Application of 415V Systems in North American Data Centers A White Paper from the Experts in Business-Critical Continuity Introduction Increasing pressure to reduce operating expenses and be more