EARTHING AND BONDING AT SECONDARY SUBSTATIONS



Similar documents
Earthing Guidance Notes

ScottishPower Distribution Cables & Equipment. Metal Theft

Circuit Electrical Testing

GroundRod AC Substation Earthing Tutorial

EDS LV NETWORK EARTHING DESIGN

Lightning Protection Introduction

Fault location on power cables. Fault location on power cables

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance

Chapter 9. Bonding and Grounding

STREETLIGHT SYSTEM GROUNDING AND BONDING

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

Network Standard Advice No. 1420C 9/6/2011

Consultants Handbook

CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION

TS 813 GROUNDING AND BONDING TTD TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD CONTROLLER CABINET GROUNDING

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1

Work in Substations - General

12 Appendix 12 Earth Electrodes And Earth Electrode

Cables, Cable Laying & Accessories Manual

Session 14 Cable Support Systems

Hyperlinks are Inactive

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

TABLE OF CONTENT

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

INTERNATIONAL STANDARD

Video Camera Installation Guide

Electrical Grounding. Appendix C

Voltage Detection and Indication by Electric Field Measurement

How To Safely Dig For Natural Gas

Lightning Arresters P KVA P KVA. Description & Installation

environment briefing02

Please check with your local inspection authority for any additional requirements before installation.

Code of Practice Electricity transmission and distribution asset management. February 2009

Screened cable and data cable segregation

Gulf Cable & Electrical Ind. Co.

Grounding & Bonding Why it is done And How to Install Properly

AVOIDANCE OF ELECTRICAL HAZARDS WHEN WORKING NEAR OVERHEAD ELECTRIC LINES

FREQUENTLY ASKED QUESTIONS

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria

METHOD STATEMENT INSTALLATION OF INSULATING FLANGE KITS

Specifications for Lightning Protection. ASAE Engineering Practice

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Application Guide for Equipotential Earth Mat Installation on Substation Structure Mounted Switches

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

Strength and Durability for Life CORROSION CONTROL. The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

800 Communications Circuits

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

Electrical Code Regulation

Electrical Service Guidelines

Homeowner Information Guide Electrical Safety. British Columbia Safety Authority

TC Grounding and Bonding for Telecommunications Systems

Electrical safety rules

Undergrounding high voltage electricity transmission. The technical issues

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

NEW SERVICE INSTALLATION STEPS. Common Slow Downs. Other Necessary Steps

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

FAQs-Main switchboard design criteria

PROCEDURES PREVENTION OF ACCIDENTAL IGNITION

Lead & Magnet Wire Connection Methods Using the Tin Fusing Method Joyal A Division of AWE, Inc.

2002 No ELECTRICITY. The Electricity Safety, Quality and Continuity Regulations 2002

COMMISSIONING TESTS FOR HV UNDERGROUND CABLES (UP TO 33KV) SWP

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM

UGVCL/SP/591/11KV HT AB CABLE

CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE

EDS CUSTOMER LV INSTALLATION EARTHING DESIGN

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

CAPACITOR BANK TESTING SWP

Douglas J. Reinemann, Ph.D. University of Wisconsin-Madison, Department of Agricultural Engineering Madison, Wisconsin. and

IRRIGATION PUMPING Table of Contents - Section 900

Unified requirements for systems with voltages above 1 kv up to 15 kv

ELECTRICAL SAFETY Information Bulletin

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

Comparative study for cables and busbars

SECTION 22 LIGHTNING PROTECTION SYSTEM

Electrical Safety Products

Electrical Practices for Construction Work

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Standards. 5 ANSI/TIA/EIA-569-A (CSA T530)

Distribution Substation Manual (DSM) Section I - Introduction

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

FIREFIGHTER SAFETY. Stay safe during substation fires

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Airdac CNE and SNE, 600/1000V, Polyethylene Sheath, SANS 1507, NRS 063 & NRS 017

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

SECTION SIGNAL WIRE AND CABLE

Earth Ground Resistance

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection

Current Transformers

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.

Transcription:

DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the standard for earthing and bonding of plant and apparatus at secondary substations to comply with Regulations. 2 GENERAL Earth is defined as the general mass of earth. Earthed means connected to the general mass of earth in such a manner as shall ensure at all times, an immediate discharge of the electrical energy without danger. An Earth Electrode comprises a metal rod or system of rods or other conducting objects, such as copper tape, providing an effective connection with the general mass of earth. Earth Electrode Systems At every secondary substation two earth electrode systems are necessary i.e. Equipment Earthing (HV Earth) and System Neutral Earthing (LV Earth). The two systems shall be installed with suitable segregation and can only be connected together when the combined value of the systems in less than 1 ohm. Equipment Earthing and Bonding of all the metalwork associated with the electrical equipment (other than parts which are normally current carrying) ensures effective operation of the HV fuse or switchgear controlling the circuit, where the potential of such metalwork, with respect to the general mass of earth or other adjacent metalwork could rise to a value which could cause danger to life or risk of fire. System Neutral Earthing is necessary to preserve security of systems, to ensure that the voltage on each live conductor is restricted to such a value with respect to the potential of the general mass of earth as is consistent with the insulation level of the system. DCM 4.4.4 ISSUE B SEPTEMBER 1996 PAGE 1 OF 8

3 HV STEELWORK EARTH 3.1 The HV steelwork in the substation shall be connected with earth by bonding an un-insulated copper conductor (in accordance with Table 1) from the earth terminal on the transformer tank or switchgear to an earth electrode system, Reference Section 6, with an ohmic resistance value as low as economically practicable, and of such a value that when contact is made between a line conductor and earthed metalwork, the resulting leakage current shall be not less than twice the current required to operate the device which will make the line dead. The earth electrode system resistance value, measured independently shall not exceed 40 ohms. The sheaths of any metallic sheathed cables shall subsequently be bonded to that established system. 3.2 The routing and position of the earth electrode system should be such as to form an equi-potential mat beneath the operating position of any of the apparatus so that the operator is protected, so far as reasonably possible, from any voltage gradient arising from an HV fault. 3.3 Where secondary substations are surrounded by metallic structures e.g. palisade fencing, all separate sections of the surround shall be bonded to the HV earth electrode system. Care should be taken to keep the earth electrode and their bonding leads as far as possible from nearby non-related metal fences, metal buildings etc., so as to avoid these becoming charged during a fault on the HV system. A distance of 3 metres is recommended if this is possible. 4 LV NEUTRAL EARTH 4.1 The LV neutral shall be connected to an earth electrode system separate from the HV earth electrode system, reference Section 6, by running a PVC insulated cable (in accordance with Table 1), from the neutral busbar in the LV pillar or fuse cabinet to an earth electrode system. The resistance of the LV neutral earth electrode system at the substation measured independently shall not exceed 40 ohms. The combined resistance of all the LV neutral electrodes, including any contribution from any metallic sheathed cables, shall not exceed 20 ohms. 4.2 Care shall be exercised to place the neutral earth electrode system outside the influence of the HV steelwork earthing system. A distance of not less than 3 metres is recommended from the nearest steelwork earth electrode or earth mat but this distance may require to be increased in cases of abnormally high resistances. 5 COMBINED HV STEELWORK AND LV NEUTRAL EARTHS 5.1 Where the earth resistance of the combined earths (HV steelwork + neutral earth + connections with earth associated with the cables connected to the substations via their sheaths) is 1 ohm or less, then the separate HV and LV earth electrode systems shall be bonded together. This is the preferred state and when this condition prevails the link provided in the LV pillar between the neutral earth bar and the pillar shell shall be closed. DCM 4.4.4 ISSUE B SEPTEMBER 1996 PAGE 2 OF 8

5.2 Where it is not technically and economically justified to reduce the combined earth resistance value to 1 ohm or less, the HV steelwork earth electrode system shall remain segregated from the neutral earth electrode system. In this condition, where a link is provided between the neutral earth and the LV metalwork, it shall be left in the open position. A notice shall be installed in a conspicuous position within the pillar showing that this condition prevails. 6 EARTH ELECTRODE SYSTEMS 6.1 Earth electrode systems shall normally be comprised of conductors as detailed in Table 1 and earth rods complying with EA Technical Specification 43-94 Issue 3 and ScottishPower Procurement Specification No. 4389/10,000 which includes non extensible galvanised steel tubes 20 mm dia., non extensible copper clad 9 mm dia. rods and extensible copper clad 15 mm dia. rods. The rods shall be driven into the ground vertically until their tops are at least 600 mm below the surface. This depth is necessary to prevent appreciable voltage gradient on the surface of the ground in the vicinity of the electrode. The HV earth electrode system can be installed within the substation and shall cross the area on which an operator will be required to stand while operating the switchgear. The LV earth electrode system can be installed along an LV cable trench but shall not make contact with a cable or come within 3m of an HV cable. Paper insulated metallic sheath, jute or hessian served cables laid direct in the ground shall not be used as the main HV steelwork or LV neutral earth electrode system but shall be bonded to the relative systems. 6.2 Where more than one rod is necessary, then a number of rods may be installed at a distance of approximately, but not less than, 3 metres from each other. The resistance of N rods at 3 metre spacing, connected in parallel, is approximately 1.5 x R/N where R is the resistance in ohms of one rod. The connections between earth rods, where more than one are installed shall always be made using copper conductor in accordance with Table 1. The connections from the neutral/earth bar to the neutral earth electrode system shall be insulated until they are outwith the sphere of influence of HV steelwork earth system (not less than 3 metres separation). 6.3 All connections between the earth rods and the earth leads must be carefully made up, using approved clamps, adequately protected by wrapping with denso or other approved tape or cast in bitumen compound. Where connections are made using lugs and bolts then two bolt fixings shall be used. 6.4 Means must be provided for disconnecting the earth electrode system at substations for testing, and this can normally be achieved by having a bolted connection where the earth electrode system is connected on to the equipment or neutral busbar which can be undone and the lead disconnected. These disconnections must always be at copper to copper or copper to brass joints. Aluminium joints shall not be disconnected for testing. DCM 4.4.4 ISSUE B SEPTEMBER 1996 PAGE 3 OF 8

6.5 In areas of high soil resistivity, low electrode resistances are difficult to achieve and dangerous potential gradients could occur over and around the site unless adequate steps are taken to prevent this. These potential gradients may also be imposed on the entire LV distribution system. Increasing the number of electrodes will reduce the overall earth resistance value but may result in extending the earth system outwith the confines of the substation and produce potential gradients between nearby metallic objects, e.g. metal framed buildings or fences. A lower resistance value may often be achieved by driving extensible earth electrodes deep into the ground without extending the earth system outside the substation. In rocky soil, copper tape in accordance with Table 1 may be installed. 6.6 Great care should be exercised when installing the earth electrode system particularly when hammering rods into the ground, to avoid accidents due to piercing cables or other utilities services already laid in the ground, e.g. gas, water, telephone, sewage, etc. Before commencing installation of electrodes an up-to-date plan of the site should be prepared showing the exact position of all cables and other services including cables recently laid in conjunction with the project under construction and the cables in question should be positively located, if necessary by excavating trial holes, before driving the earth rods. So far as possible, persons should avoid direct contact with earth rods being driven into the ground by using an insulated tool to steady the rod or by the use of rubber gloves. 7 BONDING 7.1 The size and type of bonding conductors to be used are set down in Table 1. 7.2 All steelwork within touching distance (2 metres) shall be bonded together, so that no potential difference can arise between units. This includes the transformer, HV switchgear, HV cables, LV feeder pillar shells, fences, exposed total enclosure metalwork and any other apparatus installed. The bond shall be made using conductors shown in Table 1. Where theft of copper is likely, aluminium conductors are recommended for above ground with terminations similar to those in Section 4.3.3 Appendix 2 of this manual. 8 SUBSTATION EARTH POTENTIAL RISE (HOT EARTHS) 8.1 Under system earth fault conditions the neutral or earth potential near a substation rises above the true earth potential and can adversely affect telecommunications equipment in that zone. Engineering Recommendation ER G60 recommends that where the rise of potential exceeds 430 volts at Distribution substations, the substation is deemed "HOT" and additional protection is required for telecommunications equipment in the vicinity of the substation. DCM 4.4.4 ISSUE B SEPTEMBER 1996 PAGE 4 OF 8

8.2 For all new substations, or when requested to do so, it is incumbent upon ScottishPower to calculate the 430 volt contour radius using Engineering Recommendation S34, "A Guide for Assessing the Rise of Earth Potential at Substation Sites" and advise BT or other companies involved. Additional precautions for telecommunications equipment will only be needed in the calculated "HOT" zone. This will normally be done at the design stage, reference Section 13.8 of the Distribution Design Manual, but must be confirmed at the construction stage. 9 LV SYSTEM EARTHING 9.1 At network pillars and link boxes remote from substations or at other disconnecting points on the LV system, the cable neutral and earth shall be securely bonded together using 35 mm 2 or 70 mm 2 conductor depending on the cable size. The framework of the pillar shall be bonded to the cable neutral/earth and shall be connected with a 35 mm 2 conductor to an earth electrode. 10 INSTALLATION EARTHING The earthing of installations shall comply with the Code of Practice "Earthing of LV Distribution Networks". Where a new installation is being connected to a separate neutral and earth (SNE) network, preference should be given to adopting protective multiple earthing (PME). In certain circumstances, however, it may be technically and economically justified to extend the existing SNE earthing system. 11 TECHNICAL NOTES 11.1 In situations of high earth resistivity, there may be difficulty in obtaining the required earth electrode system resistance. This would cause high potential gradients to occur in and around the substation, which could be impressed on the whole of the LV distribution system supplied from the substation or on telecommunications equipment. The earth resistance can be reduced by inserting more electrodes, until a low enough total resistance is achieved. This may, however, result in extending the earth system beyond the confines of the substation, and may produce dangerous proximities between the earth leads and external metal objects. It may be better in certain locations to use extensible deep driving earth electrodes, within or near the substation to obtain the same results. The LV neutral earth electrode system should always have an insulated lead, and be at least 3 metres separate from the HV steelwork earth electrode system or any metalwork bonded thereto. This is particularly important in high resistivity areas. Special care must be taken to ensure that all metalwork, including the fence and LV pillars, is bonded, and connected to the HV steelwork earth electrode system to avoid potential differences between items of apparatus, when within touching distance, i.e. within 2 metres proximity. With the increased use of plastic covered cables it is essential to achieve sufficiently low DCM 4.4.4 ISSUE B SEPTEMBER 1996 PAGE 5 OF 8

earth electrode system resistance values. The requirement for the electrode systems to dissipate fault current must be achieved by installing a minimum of five earth rods in every system even if a lesser number could achieve the required ohmic value of resistance. 11.2 LV Neutral/HV Metalwork Earth System Should a potential gradient exist in the vicinity of a substation during an HV fault there is a risk of this being impressed on the LV system if the neutral and HV steelwork earths are connected together, and the earth system resistance is high. It is considered safe to join the two earth systems together when their combined resistance is 1 ohm or less. Where it is impracticable to achieve this resistance, care should be taken to ensure that the LV neutral is connected by an insulated lead to the electrode system which is well clear of the estimated potential gradient of the HV earth system. This may require a greater distance than the stipulated minimum of 3 metres. 11.3 PVC Over Sheathed Cables In the past, advantage has been taken of the effectiveness of the sheaths of lead-covered hessian protected cables as an earth. It should be noted that PVC over sheathed cables do not contribute to the earth electrode system in this way. 11.4 Substations Supplied by HV Overhead Lines Only Where substations are supplied from a metallic sheathed underground cable system, the major part of the earth fault current returns to the source (the primary substation) via the sheath, whereas in the case of an overhead line fed substation there is no metallic return path and all of the fault current must return via the earth electrode system and the general mass of earth. In these circumstances, it is most important to make sure that the earth electrode system and the earth leads have a low enough resistance and an adequate current-carrying capacity to dissipate the whole of the fault current. 11.5 Metal Objects Adjacent to Substations Where there are metal structures or fences adjacent to a substation, potential differences may occur between them and the metal parts of the substation or the fences, which may be within touching distance. On the other hand, if such structures are bonded, or in contact with the substation steelwork, then the potential may be carried a considerable distance from the substation, e.g. along the wires of a fence with wooden posts and create a danger elsewhere. Substations must be designed and sited so as to avoid these situations. 11.6 Gates on Steel Fences or Total Enclosure Steel Doors DCM 4.4.4 ISSUE B SEPTEMBER 1996 PAGE 6 OF 8

Where gates exist in steel fences or the doors of a total enclosure are of sheet steel, particularly if the fence or door is discontinuous, they shall be bonded on both sides of the gate or door to avoid the possibility of a potential developing across the gate or door. DCM 4.4.4 ISSUE B SEPTEMBER 1996 PAGE 7 OF 8

TABLE 1 - EARTHING AND BONDING CONDUCTORS TO BE USED AT SECONDARY SUBSTATIONS Type of Conductor Bonding of S/Stn. Apparatus HV Steelwork Earth Leads LV Neutral Earth Leads Solid Alum. PVC insulated cable to BS 6791: 1969 600 1000 V Grade 120 mm 2 - - Copper Strip to BS 1432: 1970 20 mm x 4 mm 20 mm x 4 mm - Alum. Strip to BS 2898: 1970 (EIE.M) Bare Copper Conductor Solid or Stranded 30 mm x 4 mm - - Not less than Not less than 70 mm 2 70 mm 2 - Insulated Copper Wire Not less than 70 mm 2 - Not less than 70 mm 2 DCM 4.4.4 ISSUE B SEPTEMBER 1996 PAGE 8 OF 8