Electrical safety rules

Size: px
Start display at page:

Download "Electrical safety rules"

Transcription

1 Electrical safety rules 2015

2

3 DISCLAIMER The material contained in this publication has been developed for the use of ActewAGL, its contractors and all others working on or near ActewAGL s electricity network. It should be read in conjunction with any applicable Laws, Regulations, Technical Guidelines, Australian Standards and Internal Procedures. ActewAGL believes that to the best of its knowledge, the information contained herein is correct and current as at the date of its publication. However, ActewAGL gives no warranty as to the completeness, accuracy or suitability of the information contained herein. No party outside ActewAGL should act based on the information contained in this publication without first considering his or her own circumstances and if necessary, obtaining professional advice as to his or her legal obligations. Note however, that the Safe Approach Distances tabled within, are to be considered a minimum standard for all work near ActewAGL assets. Except for any liability that cannot be excluded or limited by law, ActewAGL excludes all liability for any loss or damage of any kind arising from or relating in any way to reliance on the information contained in this publication. ACKNOWLEDGEMENT OF COPYRIGHT The development of these Electrical Safety Rules was based on the Code of Practice on Electrical Safety for the Distribution Businesses in the Victorian Electricity Supply Industry (The Green Book). Copyright of The Green Book is jointly owned by the Victorian Major Electricity Companies. CitiPower Pty Ltd SP AusNet Powercor Australia Ltd Jemena United Energy These Victorian Major Electricity Companies, known as the Victorian Electricity Supply Industry (VESI) collectively, are members of the Distribution Sub-Committee of the Electrical Safety Committee in Victoria. The Distribution Sub-Committee has given its written permission to ActewAGL for The Green Book to be used as the basis for the development of ActewAGL s Electrical Safety Rules. ActewAGL thanks the VESI for its cooperation in this regard. BLUE BOOK ISSUES REGISTER For all queries or issues identified please the Work Practices Group at bluebook@actewagl.com.au ActewAGL Distribution ABN a partnership of Jemena Networks (ACT) Pty Ltd ABN and Icon Distribution Investments Limited ABN SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

4 ActewAGL s Life Saving Rules The ActewAGL Life Saving Rules are important rules that must never be broken. Breaking one of these rules could result in a serious injury or a fatality. They are non-negotiable rules that require constant reinforcement by managers, supervisors, team leaders and workers. Breaking a Life Saving Rule will result in consequences for the rule breaker/s. For those that see a Life Saving Rule being broken and choose to ignore it or let it go, they will also face consequences. Depending on the investigation results, consequences can range from education, coaching and counselling up to formal disciplinary action, including the possibility of employment termination. 2 Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

5 The Life Saving Rules are: I will always... actively participate in a site job assessment before commencing every job, every day test and prove de-energised before commencing any non live work check and confirm equipment / apparatus is safe to energise only work on or near the electricity network when trained and authorised to do so implement required controls to manage site hazards have current training and authorisation for the plant and equipment that is to be operated check and wear PPE that is appropriate for the job abide by drug and alcohol rules Report incidents and near misses SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

6 PURPOSE The purpose of these Electrical Safety Rules (The Blue Book) is to specify the safe working requirements and minimum standards for workers working on, near or in the vicinity of ActewAGL s electrical apparatus within the Australian Capital Territory and the surrounding region into which ActewAGL s electricity networks may extend. These rules do not apply to customer installations beyond the network boundary with the exception of equipment for the purpose of metering. These Electrical Safety Rules are to be read in conjunction with associated documents detailing work practices and procedures. The rules and associated documents are intended to thoroughly specify the safe working requirements and minimum standards that will permit the ActewAGL electricity distribution network to be operated and maintained safely at a high standard. Safety incidents that occur in the electricity industry drive home the need for workers at all levels to understand and implement the requirements set out in these Electrical Safety Rules. These rules were created with recognition that they will need periodic revision. They shall be reviewed annually, with amendments to be communicated and issued. 4 Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

7 SCOPE These Electrical Safety Rules (The Blue Book) define principles and are the basis for additional development of electrical safety procedures. Work shall be carried out in accordance with these rules and relevant approved procedures and/or approved practices. Acts, Regulations and Utility Services Licence Technical Codes, Standards and Guidelines Electrical Safety Rules (The Blue Book) ActewAGL Policies and Procedures Hierarchy of documentation for electrical safety ActewAGL s compliance with these Electrical Safety Rules assists in meeting obligations imposed by the Work Health and Safety Act, the Utilities Act and the electricity distribution licence issued to ActewAGL by the Independent Competition and Regulatory Commission. It is not expected that there would be any conflict between these Electrical Safety Rules and an Act or Regulation. If anyone identifies such a conflict, they are asked to immediately notify Work Practices or the General Manager Energy Networks, ActewAGL. In order to comply with the requirements of these Electrical Safety Rules, ActewAGL workers and its contractors shall either: a. apply the rules and procedures contained within these Electrical Safety Rules; or b. vary the procedures by: completing a hazard identification and risk assessment to ensure that workers are not exposed to any increase in risk; and ensuring that community and business standards for managing risk are met; and documenting the procedure through SWMS or other means; and ensuring any variations are endorsed by the General Manager Energy Networks and that the Safety Committee is informed in writing. SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

8 Contents Acknowledgement of copyright 1 Blue book issues register 1 Purpose 4 Scope 5 1. Definitions 11 2 Safe approach distances to electrical apparatus General Safe approach distances persons Safe approach distances mobile plant Emergency situations Contact with live high voltage (HV) conductors by means of appliances Approach to live high voltage (HV) insulated cables Work in the vicinity of electrical apparatus Handling objects/loads Erection or dismantling of overhead conductors Possibility of leakage currents on poles Work by instructed persons 30 3 Training and authorisation General Ordinary persons signing onto electrical access permits Instructed persons signing onto electrical access authorities Authority to receive an electrical access authority Authority to receive a sanction for testing Authority to operate low voltage (LV) and/or high voltage (HV) electrical apparatus and issue access authorities Authority to operate the network Authority to work on live high voltage (HV) overhead lines using glove and barrier or stick procedures Authority to work on live low voltage (LV) electrical apparatus Authority to enter confined spaces Withdrawal and/or restriction of an authorisation First aid Perform rescue 35 6 Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

9 3.14 Work safely at heights prevention of falls Work on poles 35 4 General safety requirements Hazard identification, risk assessment and control Personal protective equipment (PPE) First aid kits Fire extinguishers Emergency rescue kits Communications Labelling of electrical apparatus Ladders Use of safety observers Working alone or without a safety observer Fit for work Danger of materials which can conduct electricity Storage of materials Work in the vicinity of electric and magnetic fields Portable electric tools and equipment Design, construction and commissioning Danger tags 42 5 Operation of electrical apparatus Workers authorised to operate high voltage (HV) electrical apparatus Operator protection 45 6 Earthing of high voltage electrical apparatus Earthing hierarchy General Earthing for access to high voltage (HV) electrical apparatus Removal of earth when working under an electrical access authority Earthing of overhead lines High voltage (HV) metal-clad switch units Precautions prior to work near aerial communication cables Equipotential bonding 51 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

10 7 Issue of access authorities General Electrical access permit Sanction for testing Permit to work Electrical apparatus out of commission High voltage (HV) operating sticks Barriers and signs Working on insulated network, service or supervisory cables (SCADA) 69 8 Access for work on or near high voltage electrical apparatus General Live work high voltage (HV) Use and testing of operating and live-line equipment Insulated sticks Work on or near de-energised high voltage (HV) electrical apparatus Preparing high voltage (HV) electrical apparatus for access Suppression of auto-reclose on HV overhead feeders 84 9 Access to low voltage electrical apparatus General Temporary supply of electricity Work on or near live low voltage (LV) conductors Notification of work on de-energised low voltage (LV) electrical apparatus Work on de-energised low voltage (LV) electrical apparatus Testing, commissioning and decommissioning electrical apparatus Correct supply, polarity, and rotation Use of testing devices Clearance for service Connections to electrical apparatus Work on pilot cables Prior to making apparatus live for service Work in electrical stations Entry of electrical stations General working practices Hazards within electrical stations Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

11 12 Metering General Metering new installations Metering changes to existing installations Metering work on live equipment Metering work on transformer operated equipment Public lighting General Precautions to be taken Testing conductive objects Changing tubes or lamps from an elevating work platform Work by other personnel not under the supervision of ActewAGL General Work on abandoned cables Permit to work issued to non-actewagl personnel Work by tree surgeons requiring the isolation of overhead conductors Work by electrical contractors requiring the isolation of electrical apparatus Statement of condition of apparatus and plant (SCAP) 110 Appendix A ActewAGL policy and procedure list 115 Appendix B Reference documents 117 B1 Legislation and regulations 117 B2 Industry guidelines 117 B3 Australian standards 118 Version register 119 List of tables Table 2.1 Safe approach distance (mm) to live conductors for ordinary, instructed persons and authorised workers 21 Table 2.2 Safe approach distance (mm) to live conductors for vehicles and mobile plant 25 Table 3.1 Frequency of assessment training and authorisations 36 Table 5.1 Protection for electrical operations 46 Table 8.1 Safe approach distance (mm) to live conductors for authorised glove and barrier workers 79 Table 10.1 Insulation Resistance Values 98 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

12 List of figures Figure 2.1 Safe approach distance persons and workers 20 Figure 2.2 Safe approach distance mobile plant 24 Figure 3.1 Hierarchy of access authorities 31 Figure 4.1 Typical PPE requirements 37 Figure 4.2 Example of Danger Do Not Operate tag 43 Figure 5.1 Example of HV operating Gloves 45 Figure 6.1 Earthing hierarchy 47 Figure 6.2 Typical overhead earthing 50 Figure 7.1 Examples and diagram illustrating correct entry to a safe work area 66 Figure 7.2 Examples of various HV apparatus which is taped and/or danger tagged to control access to various parts of the apparatus 67 Figure 7.3 Isolation and restoration process 70 Figure 7.4 Blank Access Authority form as an Electrical Access Permit or Sanction for Testing or Permit to Work 72 Figure 9.1 Low voltage (LV) network topography and permit requirements 91 Figure 9.2 Examples of LV earthing or bonding 94 Figure 11.1 Example of operational earths in zone substation 100 Figure 11.2 Example of vehicle earthing in a zone substation 103 Figure 14.1 Example of a SCAP form 113 List of flowcharts Chart 7.1 Access authority sign-on checklist 71 Chart 8.1 General workflow for high voltage (HV) access 76 Chart 9.1 General workflow for low voltage (LV) access 86 Chart 9.2 General workflow for service access 92 Chart 14.1 Process for the issue of a SCAP Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

13 DEFINITIONS 1. DEFINITIONS 1 Access Authority means any form of authorisation which allows an authorised or instructed worker access to test or work on or near electrical apparatus. Access Authorities used in these rules are: Electrical Access Permit means a form of authorisation that allows persons and workers access to, and to work upon, electrical apparatus. Permit to Work means a form of authorisation providing permission to approved persons and workers, working near or up to safe approach distances of electricity apparatus. Sanction for Testing means a form of authorisation to allow energisation of electrical apparatus for testing purposes. ActewAGL means ActewAGL Distribution ABN Appliance means any instrument or device designed for use near or in direct contact with live conductors and/or electrical apparatus. Approved means having appropriate organisation endorsement in writing for a specified function (see Written or in Writing). Approved Examiner means a person who has the permission of ActewAGL as appropriate for the duty concerned, to act on its behalf. Authorised Worker means a worker with technical knowledge or relevant trade experience who has been approved, or has the delegated authority to act on behalf of ActewAGL, to perform the duty concerned. (Sign on, work and receive an Access Authority). Barrier means a rope, tape, barricade or alternative erected barrier in accordance with approved procedures for the purpose of issuing an access authority. Bonded means connected together in such a manner as to ensure that all bonded parts are maintained at the same electrical potential. Cable means an insulated conductor, or two or more such conductors, laid together, whether with or without fillings, reinforcements or protective coverings. Note: Cable, in these rules, also means low voltage and high voltage aerial bundled cable (ABC), covered conductor thick (CCT) and covered conductor (CC). Competent means the ability to perform particular tasks and duties to the standard of performance expected in the workplace. Competency requires the application of specified skills, knowledge and attitudes relevant to effective participation for completing a task. Conductor means a wire, cable, bar, tube or form of metal designed for carrying electric current. Confined Space means an enclosed or partially enclosed space that: a. is not designed or intended primarily to be occupied by a person; and b. is, or is designed or intended to be, at normal atmospheric pressure while any person is in the space; and c. is or is likely to be a risk to health and safety from: i. an atmosphere that does not have a safe oxygen level; or ii. contaminants, including airborne gases, vapours and dusts, that may cause injury from fire or explosion; or SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

14 DEFINITIONS 1 iii. iv. harmful concentrations of any airborne contaminants; or engulfment. Contractor means a Company and its employees or an individual, engaged by ActewAGL but not on a basis of employment, to carry out work, or provide services, for ActewAGL. Danger Do Not Operate Tag means a tag attached to the controls of an electrical apparatus to warn and prevent workers from inadvertent or unauthorised operation. De-energised means not connected to any source of electrical supply but not necessarily isolated, earthed, discharged or out of commission. Discharged means having been connected to the general mass of earth in such a manner as to remove any residual electrical energy in a conductor or conducting object. Earthed means the electrical connection of conductors and/or electrical apparatus connected directly to the general mass of earth to ensure and maintain the effective dissipation of electrical energy. Earthing Device means an approved device used for the earthing of conductors and/or electrical apparatus. Earths Operational Earth means approved earthing and short circuiting equipment applied to apparatus, as a requirement for the issue of an electrical access authority, for the purpose of proving the electrical apparatus to be de-energised and earthed. Note: All earths applied in a Zone Substation and on the underground network between a point of supply and the work site shall be regarded as Operational Earths. Working Earth means approved earthing and short circuiting equipment applied to apparatus that is under an electrical access authority. System Earth means a permanent electrical connection which would be anticipated to have standing fault or earth return currents in it during normal service. Electrical Apparatus means any HV or LV electrical equipment, including overhead lines and underground cables, the conductors of which are live or can be made live. Electricity Network means an interconnected system or transmission and/or distribution conductors and electrical apparatus (see Mains). Electrical Operator means a worker tested and deemed competent against an approved training standard who has written authorisation to carry out electrical operating work on HV and/or LV electrical apparatus. Electrical Operating Work means work: a. involving the operation of switching devices, links or fuses other than on a service; and b. providing access to the Electricity Network; and c. proving electrical conductors and/or electrical apparatus is de-energised; and d. where earthing and bonding, locking and/or tagging of electrical apparatus and erection of barriers and/or signs will be required. Electrical Operator s Authority means written authorisation issued by System Control to allow an electrical operator to carry out electrical operating work. 12 Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

15 DEFINITIONS Electrical Station means any location, in which HV supply is switched, converted, controlled or transformed, or in which any similar electrical apparatus or plant is installed. 1 Stations more commonly referred to include: Bulk Supply Station means the station at which a HV customer purchases their electricity. Electricity can be purchased at any voltage. The electricity is metered and controlled within the station but not necessarily transformed. The electrical network and electrical apparatus beyond the bulk supply station may or may not be owned and/or operated by ActewAGL. Distribution Substation means a station in which electricity is controlled and transformed. The highest voltage in the station does not exceed 22,000V. Distribution Switching Station means a station in which electricity is controlled and possibly metered. The highest voltage in the station does not exceed 22,000V. For the purposes of these rules the requirements of a substation apply to a switching station. Zone Substation means a station in which electricity is controlled metered and transformed. The highest voltage in the station exceeds 22,000V. Zone Switching Station means a station in which electricity is controlled and metered. The highest voltage in the station exceeds 22,000V. For the purposes of these rules the requirements of a zone substation apply to a zone switching station. Electrical Worker means a worker who is qualified to work on or near live electrical apparatus for specific work to which the qualification pertains. Embedded Generating Unit means a generating unit that is connected directly to and/or operating in parallel with the distribution network that is, or can be, connected directly to the electricity network by means of an operating switch or switching device. The generating unit may include photovoltaic (PV) systems via inverters, rotating machines, solar, thermal and other renewable generation, such as wind power generation or fuel cells. Micro PV Generator means a Class 1 PV Generator which is up to 10kW single phase or 30kW three phase. Energised means connected to a source of electrical supply, or subject to hazardous induced or capacitive voltages. Equipotential Bonding means electrical connections intended to bring exposed conductive parts or extraneous conductive parts to the same or approximately the same potential, but not intended to carry current in normal service. Exposed Conductor means an electrical conductor, approach to which is not prevented by a barrier of rigid material or by insulation which is adequate under a relevant Australian Standard specification for the voltage concerned. Extra Low Voltage (ELV) means a nominal voltage not exceeding 50 volts alternating current or 120 volts ripple-free direct current. Fallen means dropped or come down from a higher place. Gas Insulated Switchgear (GIS) means a switch which relies on Sulphur Hexafluoride Gas (SF 6 ) as the insulating medium. SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

16 DEFINITIONS 1 Glove and Barrier (Live HV Line) Worker means a worker tested against an approved training standard who has written authorisation to carry out live line work using Glove and Barrier or Stick techniques on HV electrical apparatus. Hazard means a situation or thing that has the potential to harm a person. High Voltage (HV) means a nominal voltage exceeding 1,000 volts alternating current or 1,500 volts direct current. Immediately Available means the item is located within a few metres of the work and is available without any delay such as the time taken to open doors and/or remove securing straps etc. Instructed Person means a person with technical knowledge or relevant trade experience to perform the task concerned under direct supervision of an authorised worker to enable them to avoid the dangers which electricity may create. (Sign on, work but not receive an Access Authority) Insulated means separated from adjoining conducting material by a non-conducting substance which provides resistance to the passage of current, or to disruptive discharges through or over the surface of the substance at the operating voltage, and to mitigate the danger of shock or injurious leakage of current. Insulated Stick means a stick of insulating material specifically designed, approved and tested for use in physically bridging the distance between the Glove and Barrier Worker and energised apparatus, between the energised apparatus and earth, between adjacent phases and to enable physical loads to be taken or tools to be applied to the stick (see Operating Stick). Isolated means disconnected from all possible sources of electricity supply by means which will prevent unintentional re-energisation of the electrical apparatus and which is assessed as a suitable step in the process of making safe for access to the electricity network. Isolator means a device which, for reasons of safety, provides in the open position, breaks to the circuit of a length appropriate to the voltage and the insulating medium. This device is not intended to make or break load currents. Live means energised or subject to hazardous induced or capacitive voltages. Live Work means all work performed on apparatus energised or capable of becoming energised without implementing the full protective practice of isolating, proving de-energised and earthing at the worksite. Low Voltage (LV) means a nominal voltage exceeding 50 volts alternating current or 120 volts ripplefree direct current, but not exceeding 1000 volts alternating current or 1500 volts direct current. Mains means a cable or conductor which has more than one service connected to it, excluding fused underground Tee d Service Cables (see Electricity Network). Main Switchboard means a switchboard from which the supply to the whole electrical installation can be controlled. Mobile Plant means cranes, elevating work platforms, trucks (tipping) or similar plant, any equipment fitted with a jib or boom and any device capable of raising or lowering a load. Note: Mobile plant can only be considered as a vehicle when in the normal travelling mode and not in the working mode when determining safe approach distances. Near means a situation where there is a reasonable possibility of a person, either directly or through any conducting medium (for example via mobile plant), coming within the relevant safe approach distances. 14 Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

17 DEFINITIONS Network Boundary means the boundary between ActewAGL s Electricity Network and a customer s premises: a. at the point of attachment of an overhead service line to the customer s building or structure; or b. at the point of entry of an underground service cable to the customer s building or structure; or c. as otherwise agreed in accordance with the Electricity Network Boundary Code if neither (a) nor (b) apply. 1 Not Electrically Connected means disconnected from all sources of supply by the removal or absence of conductors appropriate to the voltage and insulating medium and not able to be made live by normal operating means, or bridging. Operating Stick means a stick specifically designed, approved and tested for carrying out operations on live electrical apparatus (see Insulated Stick). Ordinary Person means a person without sufficient training or experience to enable them to avoid the dangers which electrical apparatus may create. (Sign on to an Access Authority but not work) Out of Commission means electrical apparatus that is unserviceable and not fit for its intended use/ purpose/service in its current condition. A commissioning process is required before it can be reenergised. Out of Service Tag means a tag fitted to unserviceable or faulty tools, plant and equipment to warn against inadvertent operation. Overhead line means any aerial conductor or conductors with associated supports, insulators and other apparatus erected, or in the course of erection, for the purpose of the conveyance of electrical energy, excluding poles or supporting structures or anything in an Electrical Station. Person in Control (PIC) means a person who is nominated, responsible for and in control of a work site. This person shall remain at the site for the duration of the work to ensure: a. the work is completed as per the safe work method statement and procedures; and b. all hazards are identified, specific controls are implemented and that these controls remain effective for the duration of the work. Personal Protective Equipment (PPE) means approved clothing, equipment and/or substances, which when worn or correctly used, protect parts or all of the body from foreseeable risk of injury or disease at work or in the workplace. Plant means machinery, equipment, appliances, containers, implements and tools and includes all components or anything fitted or connected to any of those items (see also mobile plant). Potential (electrical) means a difference of electrical charge or a difference in voltage between two points. Practicable means capable of being done, or put into practice successfully; feasible. Procedure means the documentation of a systematic series of actions (or activities) directed to achieve a desired result. Recipient means an authorised worker to whom an access authority has been issued and is the worker responsible for compliance with the requirements of the access authority. Representative means a licensed electrician or a person who has been granted permission by ActewAGL to accept a SCAP, other than employees or contractors of ActewAGL. Risk means the possibility that harm (death, injury or illness) might occur when exposed to a hazard. SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

18 DEFINITIONS 1 Safe Approach Distance means the minimum distance that shall be maintained by a person, worker, vehicle or mobile plant (including its load, controlling ropes and any other accessories) when approaching electrical apparatus other than for work in accordance with an access authority. Safety Observer means a worker with sufficient knowledge and experience of the task being performed and assessed as competent for the duty of observing and warning against unsafe approach to electrical apparatus or other unsafe conditions. Supervisory Control and Data Acquisition (SCADA) means a system providing remote control of apparatus. Service means a dedicated radial electrical apparatus running from the point of connection from ActewAGL s LV electricity network to the customer s network boundary (see Network boundary). Shall, shall not or must is to be interpreted as mandatory. Should is to be interpreted as advisory or discretionary. Statement of Condition of Apparatus and Plant (SCAP) means a declaration regarding the status of particular plant and/or apparatus connected to a private network, issued by an ActewAGL authorised worker to a representative, other than employees or contractors of ActewAGL. Supply means supply of electricity. Switch means a device capable of making, carrying and breaking currents under normal circuit conditions. It is also capable, in the open position, of satisfying the isolating requirement for an isolator. System Control means the functional area within ActewAGL that is responsible for the operation and security of the electrical systems, and controls access to the HV and LV electrical networks and apparatus (includes both Control and Dispatch). Tester in Charge means an authorised worker to whom a sanction for testing has been issued and is the worker responsible for compliance with the requirements of the sanction for testing. Testing Device means an approved device to be used for testing on the Electricity Network. Vehicle means a truck (non-tipping), car, utility, or other general purpose conveyance used for the carriage of persons or goods (see also mobile plant). Vicinity means a situation where it is unlikely that a person or worker will, either directly or through any conducting medium (for example via mobile plant), come within the relevant safe approach distances. Within Reach means at such a distance that can be touched by any part of the body or clothing or with any conducting object or non-approved object held in the hand. Work Site means a place where work is carried out for a business or undertaking and includes any place where a worker goes, or is likely to be, while at work. Worker means a person who carries out work in any capacity for a person conducting a business or undertaking, including work as: a. an employee; or b. a contractor or subcontractor; or c. an employee of a contractor or subcontractor; or d. employees of a labour hire company who has been assigned to work in the person s business or undertaking. 16 Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

19 DEFINITIONS Working Alone means any worker working or travelling for work purposes on their own and without regular interaction with other people because of time, location and/or the nature of their work. A person is considered to be alone when they are: 1 a. on their own; or b. cannot be seen or heard by another person; or c. do not expect a visit from another person for some time; or d. in circumstances where emergency assistance is not immediately available if needed. Written (or in Writing) means recorded on paper or in an electronic form that is capable of being represented, reproduced or converted to writing. SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

20 DEFINITIONS 1 This page left intentionally blank 18 Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

21 2Section Safe approach distances to electrical apparatus PRINCIPLE Workers shall observe an appropriate safe approach distance when working, or operating vehicles or mobile plant, near electrical apparatus. Work in the vicinity of live electrical apparatus shall be carried out in a safe manner and control measures taken shall be consistent with the risk and work performed.

22

23 SECTION 2 Safe approach distances to electrical apparatus 2.1 General The safe approach distances in these Electrical Safety Rules are based on an exclusion zone principle. This defines an area around the electrical apparatus into which no part of the worker, mobile plant or object (other than approved insulated objects) may encroach unless in accordance with Sections 8 and 9. 2 When working at these distances work practices shall be established to ensure workers, mobile plant and unapproved objects do not encroach on the safe approach distances. Refer to Table 2.1 Safe approach distance (mm) to exposed live conductors for ordinary persons, instructed persons and authorised workers. Unnecessary approach to electrical apparatus shall be avoided. Necessary approach to electrical apparatus shall be kept to a minimum and shall be restricted to the period required to perform the work. SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

24 SECTION 2 Safe approach distances to electrical apparatus 2 SAFE APPROACH DISTANCE means the minimum distance that shall be maintained by a person, vehicle or mobile plant when approaching conductors or electrical apparatus other than for work in accordance with an access authority. IN THE VICINITY Where a person is unlikely (either directly or through any conducting medium) to come within the Safe Approach Distances CONDUCTOR When working on live conductors or electrical apparatus, workers must be trained and authorised ACCESS AUTHORITY DANGER ZONE SAFE APPROACH DISTANCE WORKING ON Working within the Safe Approach Distances in accordance with an Access Authority WORKING NEAR Where there is a reasonable possibility of a person (either directly or through any conducting medium) coming within the Safe Approach Distances Authorised worker or instructed person Ordinary person Movement Figure 2.1 Safe approach distance persons and workers 20 Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

25 SECTION 2 Safe approach distances to electrical apparatus Table 2.1 Safe approach distance (mm) to live conductors for ordinary, instructed persons and authorised workers Voltage Nominal phase to phase AC (kv) Ordinary person 1-4 Instructed person 1-3 Authorised worker LV including communications. catenaries connected to LV neutrals 1500 No contact Insulated contact Insulated LV 100 No contact Insulated contact Earthed metallic screened HV insulated conductor Unscreened HV insulated conductor up to and including Insulated contact HV up to and including Notes: 1. Deliberately avoid movements that could result in distances being infringed. 2. The distances specified are based on conductors not protected by a barrier of rigid material. For electrical apparatus protected by a barrier of rigid material the safe approach distance is the barrier itself (for example substation shell). Safe to touch tests and procedures shall be applied at all times. 3. The distances specified are based on work from a stable surface. Appropriate allowance shall be made for conductor sag and sway. 4. These figures are the minimum safe approach distance that shall be used by ordinary persons. For approach closer than these distances an ordinary person would need to become an instructed person. 5. When operating electrical apparatus with approved tools (for example Magnefix MD4 Operating Handle) the safe approach distance may be reduced to 300mm in conjunction with the requirements of Table 5.1 Protection for electrical operations. SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

26 SECTION 2 Safe approach distances to electrical apparatus 2.2 Safe approach distances persons Safe approach distance ordinary persons The safe approach distances for an ordinary person approaching insulated, covered or exposed live conductors are shown in Table 2.1 Safe approach distance (mm) to live conductors for ordinary, instructed persons and authorised workers. These are the distances beyond the reach of any part of the ordinary person's body or any conducting or unapproved object touching any part of the ordinary person's body. To maintain these minimum distances from overhead conductors, appropriate allowance shall be made for sag and sway under a variety of conditions Safe approach distance instructed persons and authorised workers Instructed person safe approach distances apply whilst undertaking duties under supervision or instruction by an authorised worker. Where continuous direct supervision is not provided to instructed persons, consideration shall be given to applying greater safe approach distances than those given in Table 2.1 Safe approach distance (mm) to live conductors for ordinary, instructed persons and authorised workers, and if practicable, greater clearances should be maintained. The safe approach distances for an authorised worker approaching insulated, covered or exposed live conductors are shown in Table 2.1 Safe approach distance (mm) to live conductors for ordinary, instructed persons and authorised workers. These are the distances beyond the reach of any part of the instructed person or authorised worker's body or any conducting or unapproved or uninsulated object touching any part of the instructed person or authorised worker's body. To maintain these minimum distances from overhead conductors, appropriate allowance shall be made for sag and sway under a variety of conditions Safe approach distance glove and barrier electrical workers Refer to Clause 8.2 Live work high voltage (HV) Safe approach distance vegetation clearing general Vegetation limbs shall be considered as conductive objects when within the safe approach distances of HV conductors. Before undertaking vegetation clearing activities, a risk assessment shall be conducted to assist in the identification and control of hazards to ensure that the work can be performed safely. Issues that shall be considered prior to commencing work: a. the suppression of auto-reclose; and b. positioning any mobile plant in use such that the safe approach distance can be maintained in all circumstances; and c. the use of safety observers and barriers and signs; and d. consideration of weather and environmental conditions (for example rain, wind, light, sag or sway of conductors); and 22 Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

27 SECTION 2 Safe approach distances to electrical apparatus e. movement of trees or other vegetation when cut; and f. the use of insulated barriers, protective covers and insulated equipment; and g. de-energising the electrical apparatus; and h. isolating and earthing the electrical apparatus. Subject to the outcome of a risk assessment, vegetation below, but not contacting HV conductors, may be cut. Additional means of controlling the movement of limbs being cut should be assessed and action taken as appropriate. At no time shall personal safe approach distances be reduced. 2 Vegetation above, adjacent and/or contacting HV conductors shall only be cut by authorised workers in accordance with Clauses and below. Vegetation contacting bare live LV conductors may be cut only after a risk assessment has been performed. Vegetation overhanging LV conductors can be cut while the conductors remain live provided the movement of limbs being cut can be controlled Safe approach distance vegetation clearing by instructed person or authorised workers Workers performing vegetation clearing activities shall apply safe approach distances as identified in Table 2.1 Safe approach distance (mm) to live conductors for ordinary, instructed persons and authorised workers and Table 2.2 Safe approach distance (mm) to live conductors for vehicles and mobile plant, applicable to their level of training and authorisation and the type of plant and equipment being used. Those same workers when not contracted in vegetation cutting activities for ActewAGL are to refer to Section 14 Work by other personnel not under the supervision of ActewAGL, for guidance. Instructed person or authorised workers: a. are not to clear tree limbs overhanging HV conductors with the conductors energised, unless complying with Clause below; and b. are not permitted to clear vegetation from an elevating work platform positioned over the top of live HV conductors Safe approach distance vegetation clearing by workers not contracted to ActewAGL Instructed persons or authorised workers not contracted to ActewAGL are to refer to Section 14 for guidance before performing vegetation cutting activities in the vicinity of ActewAGL electrical apparatus Safe approach distance vegetation clearing by authorised live HV workers Only authorised HV glove and barrier or stick line workers are permitted to clear vegetation from an elevating work platform positioned over the top of live HV conductors (refer to Clause 2.3 Safe approach distances mobile plant). SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

28 SECTION 2 Safe approach distances to electrical apparatus 2 SAFE APPROACH DISTANCE means the minimum distance that shall be maintained by a person, vehicle or mobile plant when approaching conductors or electrical apparatus other than for work in accordance with an access authority. IN THE VICINITY Where a person is unlikely (either directly or through any conducting medium) to come within the Safe Approach Distances CONDUCTOR When working on live conductors or electrical apparatus, workers must be trained and authorised DANGER ZONE SAFE APPROACH DISTANCE ACCESS AUTHORITY WORKING ON Working within the Safe Approach Distances in accordance with an Access Authority WORKING NEAR Where there is a reasonable possibility of a person (either directly or through any conducting medium) coming within the Safe Approach Distances Mobile plant Movement Safety observer Figure 2.2 Safe approach distance mobile plant 24 Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

29 SECTION 2 Safe approach distances to electrical apparatus Table 2.2 Safe approach distance (mm) to live conductors for vehicles and mobile plant 1 Voltage Vehicles Mobile plant Nominal phase to phase AC (kv) Ordinary person Instructed person or authorised worker 2-4 Ordinary person Instructed person or authorised worker 2-4 Uninsulated Insulated 2 LV Contact HV up to and including Notes: 1. The distances specified are based on work from a stable surface. Appropriate allowance shall be made for conductor sag and sway and for uncontrolled movement of vehicle or plant due to any reason. 2. A safety observer is required. 3. Any part of the covered pole shall remain at least 300mm clear of any live, covered HV conductor/s, allowing for sag and sway of the conductors, as the pole is being erected. 4. An appropriate risk assessment shall be undertaken before work is performed. SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

30 SECTION 2 Safe approach distances to electrical apparatus Ordinary persons in vehicles An ordinary person in control of any vehicle, excepting mobile plant when in working mode, shall ensure that no part of the vehicle or its load is placed or moved within the distances shown in Table 2.2 Safe approach distance (mm) to live conductors for vehicles and mobile plant Instructed persons or authorised workers in vehicles Instructed persons or authorised workers in control of any vehicle, excepting mobile plant when in working mode, shall ensure that no part of the vehicle or its load is placed or moved within the distances shown in Table 2.2 Safe approach distance (mm) to live conductors for vehicles and mobile plant. 2.3 Safe approach distances mobile plant Because of the physical capabilities of, and potential hazard to mobile plant working adjacent to live conductors and/or electrical apparatus, specific consideration (including earthing) shall be given to the use of mobile plant during the planning of the work. For safe approach distances to exposed live conductors for mobile plant refer to Table 2.2 Safe approach distance (mm) to live conductors for vehicles and mobile plant Use of mobile plant Mobile plant shall only be used in the vicinity of live conductors and/or electrical apparatus after precautions appropriate to the particular circumstances have been considered and action taken to control the associated hazards and risks. When mobile plant is operated in working mode in the vicinity of live electrical apparatus, the possibility of inadvertent contact with live conductors shall be taken into account during the planning and execution of the work. The control measures to be considered within a risk assessment shall include: a. isolating and earthing electrical apparatus; and b. positioning the mobile plant such that the safe approach distance can be maintained in all circumstances; and c. the use of safety observers, barriers and signs; and d. the use of other precautions such as physical restrictions or control devices in conjunction with barriers; and e. the suppression of auto-reclose; and f. de-energising the conductors and/or electrical apparatus. When mobile plant may come near live electrical apparatus, the mobile plant shall be earthed. This shall be achieved by an approved earthing conductor directly connected to a station earth or other approved earthing system refer Clause 6.1 Earthing hierarchy. Mobile plant and where appropriate, vehicles, shall be earthed by a trailing earthing conductor to protect against the hazards presented by induced voltages refer Clause 11.2 d. Work in electrical stations general working practices. When mobile plant is operated from outside the mobile plant, precautions shall be taken to protect the operator from hazardous step and touch potentials. No worker other than the mobile plant operator shall touch the mobile plant whilst in operation. 26 Blue Book 2015 SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED

31 SECTION 2 Safe approach distances to electrical apparatus Suspended loads shall be controlled by means of dry fibre rope (tag line) or other approved insulating medium. Neither the mobile plant nor conductive winch rope/load shall be touched by any worker while the mobile plant or any conducting object attached is in motion. During operation of the mobile plant only those workers at ground level actually involved in the work associated with the mobile plant shall be near the plant; all other workers shall remain clear Testing of mobile plant Mobile plant shall be used in accordance with procedures (refer Appendix A). Each elevating work platform vehicle used in the vicinity of overhead lines shall be subjected to approved HV electrical test on its insulated boom section/s at intervals not exceeding six months or more frequently depending on usage and work environment. The vehicle shall not be accepted as suitable for use in the vicinity of live overhead conductors unless it is within its test date. Lifting or pushing live HV conductors out of the way, in order to pass mobile plant below them is prohibited except in the following circumstances: a. where no other route is available and the mobile plant cannot be arranged to provide the required clearance to exposed live apparatus of voltage up to 132kV, arrangements shall be made for glove and barrier procedures to allow the conductors to be contacted and lifted or pushed out of the way; or b. live LV conductors fitted with approved insulating covers may be lifted or pushed out of the way to provide clearance over mobile plants or its load, but this shall only be done by a suitably trained electrical worker using approved equipment. The person in control of the work shall, through all workers engaged in the work, ensure that the mobile plant, its gear and load shall not approach live conductors and/or electrical apparatus within the distances as shown in Table 2.2 Safe approach distance (mm) to live conductors for vehicles and mobile plant Special approach mobile plant When working under glove and barrier procedures, special safe approach distance may be applied where a safety observer is used. Where the conductors and load are suitably insulated, the load should remain a minimum of 300mm from the conductor (allowing for sag and sway of the conductor). Every effort should be made for the load to avoid inadvertent contact with the conductors. The person in control of the work shall, through all workers engaged in the work, ensure compliance with the special approach distances for mobile plant/lifting equipment and the following general requirements for all the work situations covered in these rules, including: a. pole structures carrying live circuits shall be checked to ensure that they are in a safe condition prior to the commencement of any work; and b. suppression of auto-reclose; and c. a safety observer shall be appointed; and d. for all work, either specific work instructions shall be issued or alternatively, ActewAGL s procedures shall apply; and e. contractors shall be issued with authorisation, in accordance with these Electrical Safety Rules; and f. an appropriate risk assessment shall be undertaken before work is performed. Pole structures may be lifted into exposed live LV conductors under direct supervision of the person in control. SM4605 REVISION 1 UNCONTROLLED WHEN PRINTED Blue Book

CoDe of PRACtICe on electrical safety for work on or near high voltage electrical apparatus. the blue book

CoDe of PRACtICe on electrical safety for work on or near high voltage electrical apparatus. the blue book CoDe of PRACtICe on electrical safety for work on or near high voltage electrical apparatus the blue book VICtoRIA 2012 ISSUE SHEET Copy Number... CONTROLLED COPY UNCONTROLLED COPY Note: Uncontrolled copies

More information

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance

High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety

More information

The Electrical Safety Regulation (pre and post 1 January 2014)

The Electrical Safety Regulation (pre and post 1 January 2014) The Electrical Safety Regulation (pre and post 1 January 2014) The following table provides an overview comparison between the Electrical Safety Regulation 2002 (the ESR 2002) current as at 1 July 2013

More information

SITE CONTRACTOR PROCEDURES

SITE CONTRACTOR PROCEDURES SITE CONTRACTOR PROCEDURES Asset Collection Type B Assets are considered High risk ; the site activities must be in accordance with Graysonline contractor procedures and are to be collected by appointment

More information

Work in Substations - General

Work in Substations - General Work in Substations - General Summary: This document supports the Power System Safety Rules and its requirements assembled under Work in Substations General Category 3 and apply to all persons working

More information

Code of Practice Electricity transmission and distribution asset management. February 2009

Code of Practice Electricity transmission and distribution asset management. February 2009 Code of Practice Electricity transmission and distribution asset management February 2009 CONTENTS 1 PREFACE...4 2 APPLICATION AND OBJECTIVES...5 3 SCOPE...6 4 DEFINITIONS...7 5 DESIGN AND CONSTRUCTION...11

More information

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV 1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled

More information

WORKING IN CONFINED SPACES GUIDELINES

WORKING IN CONFINED SPACES GUIDELINES WORKING IN CONFINED SPACES GUIDELINES Contents 1 Introduction... 2 2 Scope... 2 3 Definitions... 2 4 Responsibilities... 3 4.1 Permit Authoriser... 3 4.2 Permit Receiver... 3 4.3 Responsible UOW Officer...

More information

Circuit Electrical Testing

Circuit Electrical Testing Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved

More information

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

CHECKING AND TESTING ELECTRICAL INSTALLING WORK CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical

More information

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

EARTHING AND BONDING AT SECONDARY SUBSTATIONS DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the

More information

Electrical Safety Tips. Help us keep you safe

Electrical Safety Tips. Help us keep you safe Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural

More information

Electrical Practices for Construction Work

Electrical Practices for Construction Work 1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in

More information

Handbook 16. Handbook 16. AC electrified lines. GE/RT8000/HB16 Rule Book

Handbook 16. Handbook 16. AC electrified lines. GE/RT8000/HB16 Rule Book GE/RT8000/HB16 Rule Book Uncontrolled When Printed Handbook 16 AC electrified lines Handbook 16 Issue 3 September 2015 Comes into force 05 December 2015 This handbook is for those personnel who need to

More information

WORKING IN THE ELECTRIFIED AREA

WORKING IN THE ELECTRIFIED AREA Network Safety Management System SPECIFICATION SAF/SPC/5178/ELE/NET WORKING IN THE ELECTRIFIED AREA Version 1.0 Effective Date: 12 October 2014 AURIZON COMMERCIAL-IN-CONFIDENCE SAF/SPC/5178/ELE/NET Working

More information

Electrical safety code of practice 2013. Managing electrical risks in the workplace

Electrical safety code of practice 2013. Managing electrical risks in the workplace Electrical safety code of practice 2013 Managing electrical risks in the workplace This Queensland code of practice has been approved by the Attorney-General and Minister for Justice and commences on 1

More information

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting 12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.

More information

Excavation & Trenching Procedure

Excavation & Trenching Procedure Excavation & Trenching 1. Overview The will ensure, as far as is reasonably practicable, that the conduct of work relating to excavation and trenching will not be harmful to the health and safety of employees

More information

AVOIDANCE OF ELECTRICAL HAZARDS WHEN WORKING NEAR OVERHEAD ELECTRIC LINES

AVOIDANCE OF ELECTRICAL HAZARDS WHEN WORKING NEAR OVERHEAD ELECTRIC LINES overhead 23/11/04 2:28 PM Page 1 AVOIDANCE OF ELECTRICAL HAZARDS WHEN WORKING NEAR OVERHEAD ELECTRIC LINES ESB Code 9803203 overhead 23/11/04 2:28 PM Page 2 overhead 23/11/04 2:28 PM Page 3 Page 1 of 20

More information

Tremline Pty Ltd trading as The Hills Bark Blower

Tremline Pty Ltd trading as The Hills Bark Blower JSA No: Rev: 10011 Date: 10010 ABN 1 07 880 6 Website: wwwbarkblowercomau Job Number Start Time: Vehicle : Max Length Hose Date: Company Name: Product: Quantities Depth Job site address: Description of

More information

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time

Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to

More information

Customer Installation Safety Plan. March 2015

Customer Installation Safety Plan. March 2015 Customer Installation Safety Plan March 2015 Document History Issue No. Date Approved By Summary of Changes 1 June 2014 Chief Engineer Updated and revised in line with requirement for biennial review under

More information

Contractor Connect Scheme Electrical Contractor and Worker Handbook

Contractor Connect Scheme Electrical Contractor and Worker Handbook Contractor Connect Scheme Electrical Contractor and Worker Handbook January 2016 Document release information Document number 13553681 Document title Revision status Contractor Connect Scheme handbook

More information

The Electrical Contractor Safety Program Guide

The Electrical Contractor Safety Program Guide The Electrical Contractor Safety Program Guide September 2013 Electrical Hazard Warning Sign Disclaimer Whilst this guide endeavors to provide general information on work health and safety issues relating

More information

11. Assessment of service 12. S-phase supply 13. Water heaters NORTHERN TERRITORY OF AUSTRALIA ELECTRICITY BY-LAWS T ABLE OF PROVISIONS

11. Assessment of service 12. S-phase supply 13. Water heaters NORTHERN TERRITORY OF AUSTRALIA ELECTRICITY BY-LAWS T ABLE OF PROVISIONS NORTHERN TERRITORY OF AUSTRALIA ELECTRICITY BY-LAWS T ABLE OF PROVISIONS By-law PART I - PRELIMINARY 1. Citation 2. Repeal 3. Interpretation 4. Qualifications of inspector PART II - INSPECTORS PART III

More information

Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au

Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks

More information

Hazard Identification, Risk Assessment And Control Procedure

Hazard Identification, Risk Assessment And Control Procedure Hazard Identification, Risk Assessment And Control Procedure 1. Purpose 1.1 To ensure that there is a formal process for hazard identification, risk assessment and control to effectively manage hazards

More information

ELECTRICAL PRACTICES FOR CONSTRUCTION WORK

ELECTRICAL PRACTICES FOR CONSTRUCTION WORK CONTRACTOR S CHECKLIST ELECTRICAL PRACTICES FOR CONSTRUCTION WORK 2007 WorkCover. Watching out for you. New South Wales Government Disclaimer This publication contains information regarding occupational

More information

Contractor s Safe Working Agreement

Contractor s Safe Working Agreement Contractor s Safe Working Agreement This statement provides details on how I/we, the Trade Contractor will manage the health and safety hazards associated with my/our work. ASSESSING WORKPLACE HEALTH AND

More information

Service & Installation Rules 2014

Service & Installation Rules 2014 Victorian Electricity Distributors Service & Installation Rules 2014 These Service & Installation Rules form the following Distributors Reasonable Technical Requirements for the connection of electrical

More information

Transmission Business Electrical Incident & Safety Performance Reporting Guide

Transmission Business Electrical Incident & Safety Performance Reporting Guide Transmission Business Electrical Incident & Safety Performance Reporting Guide December 2011 Version 1.0 Energy Safe Victoria PO Box 262 Collins Street West MELBOURNE VIC 8007 AUSTRALIA Telephone (03)

More information

FIREFIGHTER SAFETY. Stay safe during substation fires

FIREFIGHTER SAFETY. Stay safe during substation fires FIREFIGHTER SAFETY Stay safe during substation fires FIREFIGHTERS AND SUBSTATIONS Electrical substations reduce the high voltages used to move electricity over long distances to the lower voltages that

More information

Earthing Guidance Notes

Earthing Guidance Notes Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head

More information

Working at Height. Procedure

Working at Height. Procedure Procedure *All Forth Valley College Health, Safety and Welfare Procedures are covered under the overarching Health, Safety and Welfare Policy. Status: Date of version: Reviewed by: Author/Contact Person;

More information

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices

Union County Public Schools. Facilities Department. Electrical. Safe Work Practices 1 Union County Public Schools Facilities Department Electrical Safe Work Practices 2 Purpose In accordance with OSHA Standards 1910.331-335, safety-related work practices shall be used by Union County

More information

mit to Original Authorised Issue number Prepared Review date March 2014 copies up Electrified Interim Page 1 Manager National Standards

mit to Original Authorised Issue number Prepared Review date March 2014 copies up Electrified Interim Page 1 Manager National Standards Interim Guide to Electrical Perm mit to Work ( EF201) in the Auckland Electrified Area Issue number Prepared (P) Reviewed (R) Amended (A) Approved by Authorised for release by Review date Original 22 November

More information

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE

GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by

More information

RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016

RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016 RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 3 Related Documents 3.1 Occupational Health and Safety Act, R.S.O. 1990 3.2 Regulations for Industrial Establishments, R.R.O.

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

32-421 Eskom Life Saving Rules 39-47 Implementation of the Eskom Life Saving Rules

32-421 Eskom Life Saving Rules 39-47 Implementation of the Eskom Life Saving Rules 32-421 Eskom Life Saving Rules 39-47 Implementation of the Eskom Life Saving Rules LIFE SAVING RULES WHY DO WE HAVE THEM? Life Saving Rules are Non-negotiable Rules All Eskom Employees, Agents, Consultants,

More information

THE ELECTRICAL CONTRACTOR SAFETY PROGRAM GUIDE

THE ELECTRICAL CONTRACTOR SAFETY PROGRAM GUIDE THE ELECTRICAL CONTRACTOR SAFETY PROGRAM GUIDE December 2013 Electrical Hazard Warning Sign Disclaimer Whilst this guide endeavours to provide general information on work health and safety issues relating

More information

CONFINED SPACE PROCEDURE

CONFINED SPACE PROCEDURE Document uncontrolled when printed Procedure ID no 0460/05 CONFINED SPACE PROCEDURE This procedure is applicable to: All Department of Education and Children's Services employees. DOCUMENT CONTROL Managed

More information

THE UNIVERSITY OF SHEFFIELD WORK AT HEIGHT POLICY

THE UNIVERSITY OF SHEFFIELD WORK AT HEIGHT POLICY THE UNIVERSITY OF SHEFFIELD WORK AT HEIGHT POLICY CONTENTS Page No 1 INTRODUCTION 2 2 LEGISLATION 2 3 HIERARCHY OF CONTROL 2 4 WORK AT HEIGHT POLICY 3 5 ROLES AND RESPONSIBILITIES 3 6 RISK ASSESSMENTS

More information

2002 No. 2665 ELECTRICITY. The Electricity Safety, Quality and Continuity Regulations 2002

2002 No. 2665 ELECTRICITY. The Electricity Safety, Quality and Continuity Regulations 2002 STATUTORY INSTRUMENTS 2002 No. 2665 ELECTRICITY The Electricity Safety, Quality and Continuity Regulations 2002 Made - - - - - 24th October 2002 Laid before Parliament 28th October 2002 Coming into force

More information

Life Saving Rules. Working Safely at EPCOR

Life Saving Rules. Working Safely at EPCOR Life Saving Rules Working Safely at EPCOR 1 Our Health and Safety Beliefs We believe: All incidents are preventable. HSE is integral to our work and the way we conduct business. HSE is serious and a shared

More information

Release: 2. UEENEEJ194A Solve problems in low voltage refrigeration circuits

Release: 2. UEENEEJ194A Solve problems in low voltage refrigeration circuits Release: 2 UEENEEJ194A Solve problems in low voltage refrigeration circuits UEENEEJ194A Solve problems in low voltage refrigeration circuits Modification History Not Applicable Unit Descriptor Unit Descriptor

More information

GHD EPCM Standard operating procedure Working at height May 2013 v1

GHD EPCM Standard operating procedure Working at height May 2013 v1 GHD EPCM Standard operating procedure Working at height May 2013 v1 Table of contents 1. Purpose 2. Scope 3. Duty of care 4. Lifesaving rules; An overview 5. Roles and responsibilities 4.1 Operating centre

More information

High Voltage. Hazards

High Voltage. Hazards High Voltage Hazards HV Hazards Substations, Overhead Lines, Cables Safety Incidents Requirements for Designers, Constructors Construction Regs 2013 and other Legislation Codes of Practice Other Guidance

More information

Complete Solar Photovoltaics Steven Magee. Health and Safety

Complete Solar Photovoltaics Steven Magee. Health and Safety Health and Safety Health and safety around solar photovoltaic systems is very important. In the DC circuit you will find up to 600 volts in residential and commercial systems. In utility systems you may

More information

TLILIC3003A Licence to operate a bridge and gantry crane

TLILIC3003A Licence to operate a bridge and gantry crane TLILIC3003A Licence to operate a bridge and gantry crane Release: 1 TLILIC3003A Licence to operate a bridge and gantry crane Modification History Not Applicable Unit Descriptor Unit Descriptor This unit

More information

Asbestos Policy ASBESTOS POLICY. Version 2 / Jun 2015 Page 1 of 11 Asbestos Policy

Asbestos Policy ASBESTOS POLICY. Version 2 / Jun 2015 Page 1 of 11 Asbestos Policy ASBESTOS POLICY Version 2 / Jun 2015 Page 1 of 11 Asbestos Policy This is a controlled document. It should not be altered in any way without the express permission of the author or their representative.

More information

SAFETY OF SOLAR PANEL INSTALLATIONS IN VICTORIA REPORT

SAFETY OF SOLAR PANEL INSTALLATIONS IN VICTORIA REPORT SAFETY OF SOLAR PANEL INSTALLATIONS IN VICTORIA REPORT July 2010 Table of Contents Executive Summary... 3 Glossary of Acronyms and Phrases.....4 Introduction...5 Background 6 Electricity safety requirements

More information

WORKING IN ISOLATION PROCEDURE

WORKING IN ISOLATION PROCEDURE Document uncontrolled when printed Procedure ID no 0479/05 WORKING IN ISOLATION PROCEDURE This procedure is applicable to: All Department of Education and Children's Services employees. DOCUMENT CONTROL

More information

TIG INVERTER INSTRUCTION MANUAL

TIG INVERTER INSTRUCTION MANUAL TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4

More information

ENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas

ENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas ENERGY NETWORKS ASSOCIATION Electricity Industry EMF Measurement Protocol for High Field Areas Contents 1 Introduction 1.1 Background 1.2 High Field Areas 2 High Field Area - Generation Businesses 2.1

More information

WHS Policies and Procedures Package

WHS Policies and Procedures Package WHS Policies and Procedures Package The following is an extract to highlight the style and layout of this publication, as well as a snapshot of the content. Some samples may not be included in their entirety

More information

October Safety Subject

October Safety Subject October Safety Subject Electrical Hazards All electrical equipment should be kept in good repair. Replace defective equipment or have it repaired by a qualified person. Watch for wiring on appliances that

More information

This Guidance Notes is prepared by the Occupational Safety and Health Branch, Labour Department. This edition July 2004

This Guidance Notes is prepared by the Occupational Safety and Health Branch, Labour Department. This edition July 2004 This Guidance Notes is prepared by the Occupational Safety and Health Branch, Labour Department This edition July 2004 This Guidance Notes is issued free of charge and can be obtained from offices of the

More information

Life Saving Rules SAFETY BY CHOICE, NOT BY CHANCE

Life Saving Rules SAFETY BY CHOICE, NOT BY CHANCE Life Saving Rules SAFETY BY CHOICE, NOT BY CHANCE Foreword from Kevin Reinhart The 12 Life Saving Rules are a part of Nexen s continued commitment to create a safe work environment for our employees. The

More information

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV

MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects

More information

Installation and safety instructions for AC/DC built-in devices

Installation and safety instructions for AC/DC built-in devices The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further

More information

1. GENERAL STATEMENT OF COMPANY HEALTH, SAFETY AND ENVIRONMENTAL POLICY

1. GENERAL STATEMENT OF COMPANY HEALTH, SAFETY AND ENVIRONMENTAL POLICY 1. GENERAL STATEMENT OF COMPANY HEALTH, SAFETY AND ENVIRONMENTAL POLICY Dumfries Timber Co. Ltd. is committed to comply with our legal duties in order to provide a safe and healthy working environment

More information

Pre-Apprenticeship Training Apprentice Training Post-Trade Training Short Refresher Courses

Pre-Apprenticeship Training Apprentice Training Post-Trade Training Short Refresher Courses The College of Electrical Training (CET) is the major private training provider for the Western Australian electrical & telecommunications industries. Course Delivery Profile Pre-Apprenticeship Training

More information

Release 1. BSBWHS508A Manage WHS hazards associated with plant

Release 1. BSBWHS508A Manage WHS hazards associated with plant Release 1 BSBWHS508A Manage WHS hazards associated with plant BSBWHS508A Manage WHS hazards associated with plant Modification History Release Release 1 Comments This Unit first released with BSB07 Business

More information

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards

Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry

More information

Electrical Safety Policy

Electrical Safety Policy Electrical Safety Policy Version Number: V2 Name of originator/author: Director of Estates and Facilities Name of responsible committee: Estates and Facilities Committee Name of executive lead: Chief Operating

More information

WHS Contractor Management Procedure

WHS Contractor Management Procedure Wudinna District Council 1. Overview Wudinna District Council as part of its commitment under its Policy recognises its obligation to: Ensure, so far as is reasonably practicable, the health and safety

More information

CAPACITOR BANK TESTING SWP

CAPACITOR BANK TESTING SWP 1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.

More information

Networks. Code of Practice for Avoiding Danger from Overhead Electricity Lines

Networks. Code of Practice for Avoiding Danger from Overhead Electricity Lines Networks Code of Practice for Avoiding Danger from Overhead Electricity Lines CODE OF PRACTICE FOR AVOIDING DANGER FROM OVERHEAD ELECTRICITY LINES (FIRST EDITION SEPTEMBER 2008) Approved by the Health

More information

SPECIFIC SAFETY OBLIGATIONS FOR CONTRACTORS ENGAGED WITH THE CITY OF BUNBURY.

SPECIFIC SAFETY OBLIGATIONS FOR CONTRACTORS ENGAGED WITH THE CITY OF BUNBURY. SPECIFIC SAFETY OBLIGATIONS FOR CONTRACTORS ENGAGED WITH THE CITY OF BUNBURY. The City of Bunbury acknowledges that it has a Duty of Care obligation under the Occupational Safety and Health Act 1984 (Section

More information

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers

NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers NFPA 70E 2012 Rolls Out New Electrical Safety Requirements Affecting Data Centers A market position paper from the experts in Business-Critical Continuity TM Executive Summary Electrocutions are the fourth

More information

No. Name of Legislation Applicable Issues and Requirements Demonstration of Compliance 1. Health and Safety at Work Act 1974

No. Name of Legislation Applicable Issues and Requirements Demonstration of Compliance 1. Health and Safety at Work Act 1974 The Police Treatment Centres Health and Safety Legal Compliance Register No. Name of Legislation Applicable Issues and Requirements Demonstration of Compliance 1. Health and Safety at Work Act 1974 2.

More information

NEW ZEALAND ELECTRICAL CODE OF PRACTICE. for ELECTRICAL SAFE DISTANCES

NEW ZEALAND ELECTRICAL CODE OF PRACTICE. for ELECTRICAL SAFE DISTANCES NZECP 34:2001 ISSN 0114-0663 NEW ZEALAND ELECTRICAL CODE OF PRACTICE for ELECTRICAL SAFE DISTANCES NZECP 34:2001 NEW ZEALAND ELECTRICAL CODE OF PRACTICE for ELECTRICAL SAFE DISTANCES Issued by: Manager,

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.147 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) SECTION: 2400

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.147 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) SECTION: 2400 OSHA REGULATION: 29 CFR 90.7 THE CONTROL OF HAZARDOUS ENERGY (LOCKOUT / TAGOUT) DATE: 0/5/2008 DATE: /2/202 A. POLICY. This procedure follows requirements set forth in 29 CFR 90.7. 2. It is the policy

More information

Trees, powerlines and your property

Trees, powerlines and your property Your safety and responsibility Trees, powerlines and your property Tree clearing Victoria has well earned the reputation as the Garden State. It s in everyone s interest to help manage the growth and health

More information

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)

DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation

More information

OPTIONAL INFORMATION ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST

OPTIONAL INFORMATION ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL SAFETY WORK PRACTICES SELF INSPECTION CHECKLIST Instructions: This checklist

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS

More information

Operational Control of the UKPN Low Voltage Distribution Network for EPN and LPN Regions

Operational Control of the UKPN Low Voltage Distribution Network for EPN and LPN Regions Operational Control of the UKPN Low Voltage Distribution Network for EPN and LPN Regions Owner Name Title Signature Steve White Head of Network Control and Operations Date 16 February 2016 Authoriser Name

More information

Pollution Incident Response Management Plan

Pollution Incident Response Management Plan Pollution Incident Response Management Plan POLLUTION INCIDENT RESPONSE MANAGEMENT PLAN 1. Introduction This Pollution Incident Response Management Plan (PIRMP) has been prepared to describe the processes

More information

FIXED CHARGE: This is a cost that goes towards making the service available, including

FIXED CHARGE: This is a cost that goes towards making the service available, including ELECTRICITY BILL COMPONENTS FIXED CHARGE: This is a cost that goes towards making the service available, including installation and maintenance of poles, power lines and equipment, and 24-hour customer

More information

MANAGING ELECTRICAL RISKS IN THE WORKPLACE

MANAGING ELECTRICAL RISKS IN THE WORKPLACE MANAGING ELECTRICAL RISKS IN THE WORKPLACE Code of Practice MARCH 2015 Safe Work Australia is an Australian Government statutory agency established in 2009. Safe Work Australia consists of representatives

More information

Policy for the Management of Asbestos in the Workplace

Policy for the Management of Asbestos in the Workplace Southwark Council Management of Asbestos in the Workplace November 2011 Page 1 of 15 CONTENTS 1. INTRODUCTION... 3 2. POLICY STATEMENT... 3 3. ASBESTOS RISK CLASSIFICATION SCHEME... 5 4. SAMPLING OF ASBESTOS

More information

Distribution Substation Manual (DSM) Section I - Introduction

Distribution Substation Manual (DSM) Section I - Introduction (DSM) Section I - Introduction March 2007 Document release information Client Project name Western Power Distribution Substation Manual Document number 3463019 Document title Revision status Introduction

More information

How To Keep An Eye On Electric Safety

How To Keep An Eye On Electric Safety Table of Contents Keep an Eye on Electric Safety................ 1 Safety in an Emergency...................... 1 Downed Power Lines...................... 1 Keep an Eye on Electric Safety Electricity is

More information

PowlVac Vacuum Integrity Tester

PowlVac Vacuum Integrity Tester Instructions IB-60025B PowlVac Vacuum Integrity Tester POWELL ELECTRICAL MANUFACTURING COMPANY 8550 MOSLEY DRIVE HOUSTON, TEXAS 77075 USA PHONE (713) 944-6900 FAX (713) 947-4453 www.powellelectric.com

More information

Work Permits. A Health and Safety Guideline for Your Workplace. When is a Work Permit Needed? What is a Work Permit? Why use a Work Permit?

Work Permits. A Health and Safety Guideline for Your Workplace. When is a Work Permit Needed? What is a Work Permit? Why use a Work Permit? A Health and Safety Guideline for Your Workplace What is a Work Permit? A work permit is a written form used to authorize jobs that expose workers to serious hazards. It identifies the work to be done,

More information

LOCK-OUT/TAG-OUT PROGRAM I. Purpose

LOCK-OUT/TAG-OUT PROGRAM I. Purpose LOCK-OUT/TAG-OUT PROGRAM I. Purpose This procedure establishes requirements for the lockout of energy isolating devices. It should be used to ensure that the machine or piece of equipment is isolated from

More information

Release: 1. PRSTS303A Test installed security equipment/system

Release: 1. PRSTS303A Test installed security equipment/system Release: 1 PRSTS303A Test installed security equipment/system PRSTS303A Test installed security equipment/system Modification History Not applicable. Unit Descriptor This competency standard covers the

More information

Electrical engineering control plan For public comment

Electrical engineering control plan For public comment DRAFT NSW CODE OF PRACTICE WHS (MINES) LEGISLATION Electrical engineering control plan This code applies to all mines other than underground small gemstone mines, opal mines and tourist mines. www.resourcesandenergy.nsw.gov.au/safety

More information

WHS CONTRACTOR MANAGEMENT PROCEDURE

WHS CONTRACTOR MANAGEMENT PROCEDURE 1. Overview The Port Augusta City Council as part of its commitment under its WHS Contractor Management policy, recognises its obligation to: Ensure, so far as is reasonably practicable, the health and

More information

Installation Instructions for Alarm Module Kit A043F059

Installation Instructions for Alarm Module Kit A043F059 Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line

More information

RISK PROFILING AND RISK REDUCING ACTIONS FOR WORK PLACEMENT

RISK PROFILING AND RISK REDUCING ACTIONS FOR WORK PLACEMENT RISK PROFILING AND RISK REDUCING ACTIONS FOR WORK PLACEMENT Factors Risk Profile Indications Possible specific actions to reduce risk Work Work with hazards that have potential to cause permanent injury

More information

Corporate Standard. Contractor Management

Corporate Standard. Contractor Management Corporate Standard Contents Purpose... 2 Scope... 2 Definitions... 2 Background... 3 Specific Requirements... 4 Responsibilities... 11 Review Date... 11 References... 11 Date Issued July 2010 Management

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

Guide Document for Development of WHS Management Plans

Guide Document for Development of WHS Management Plans DISCLAIMER: THIS DOCUMENT IS PROVIDED AS GUIDANCE TO ASSIST CONTRACTORS IN MEETING THEIR OBLIGATIONS UNDER THE WHS LAW AND NTG CONTRACTS. NTG DOES NOT ACCEPT ANY RESPONSIBILITY FOR THE CONTENTS OF CONTRACTORS

More information

ELECTRICAL SAFETY. The standard unit for measuring electrical current.

ELECTRICAL SAFETY. The standard unit for measuring electrical current. ELECTRICAL SAFETY Introduction The following sections provide general safety guidelines and procedures for electrical safety. This chapter covers the following topics: TOPIC PAGE General Electrical Safety

More information

CONTRACTOR INDUCTION HANDBOOK

CONTRACTOR INDUCTION HANDBOOK CONTRACTOR INDUCTION HANDBOOK POLICY The health and safety of all school employees and contractor employees is a vital concern at the school. Contract personnel will be treated in a manner consistent with

More information

Release: 1. ICTWOR3093A Manage spare parts

Release: 1. ICTWOR3093A Manage spare parts Release: 1 ICTWOR3093A Manage spare parts ICTWOR3093A Manage spare parts Modification History Not Applicable Unit Descriptor Unit descriptor This unit describes the performance outcomes, skills and knowledge

More information

Tech Talk. Smart metering update Successful rollout. Connection Standards newsletter December 2013. Contents. To all Registered Electrical Contractors

Tech Talk. Smart metering update Successful rollout. Connection Standards newsletter December 2013. Contents. To all Registered Electrical Contractors BLEED BLEED Connection Standards newsletter December 2013 Contents Smart metering update Successful rollout Flexible pricing A major benefit of the smart meter program Business flexible pricing New residential

More information