Electrical Service Guidelines

Size: px
Start display at page:

Download "Electrical Service Guidelines"

Transcription

1 Electrical Service Guidelines Middle Tennessee Electric Membership Corporation Revised: May 23, 2013

2 MTEMC's Electrical Guidelines TABLE OF CONTENTS Right-of-Way Clearance Guide 3 MTEMC Requirements 4 General Metering Requirements 5 Metering Room Specifications 6 ESG-400: 400 Amp Residential Metering 7 LBL-MDMB: Labeling for Multi-Metered Installations 8 ESG-1: Overhead Residential Service 9 ESG-2: Underground Residential Service 10 ESG-3: Underground Residential Service, Pad-Mount Transformer 11 ESG-4: Additional Meter on House 12 ESG-5: Member Pole Service, Standard Underground 13 FSMC-2: Free Standing Meter Center 14 ESG-6: Overhead Temporary Service 15 ESG-7: Underground Temporary Service 16 COM-6: Non Residential Metering with Multiple Customers and Service Laterals from a Single Transformer 17 ESG-8: Security Lighting 18 1S: Secondary Ditch Detail 19 2S: Secondary Ditch Detail 20 CTE-1: Current Transformer Enclosure Specifications 21 ESG-9: Double Throw Switch Configuration of MTEMC Service and Standby Generator 22 ESG-10: Generlink Meter Collar 23 MTEMC Offices Listed 24

3 Right-of-Way Clearance Guide

4 MTEMC Requirements Installation In addition to the National Electrical Code, National Electrical Safety Code, and state and local building codes, MTEMC has installation requirements which must be followed. Please check with an MTEMC engineer or representative before locating the meter base or if you have questions about requirements or specifications. General Specifications A. Overhead Services: 1. Where a MTEMC engineering representative specifies an eyebolt for service attachment, install the eyebolt at a point lower than the weatherhead and no more than 18 horizontally from the weatherhead. 2. Where a MTEMC engineering representative specifies a service mast for service attachments, install 2 1/2 inch rigid metal or IMC conduit fastened with a minimum of 2 mast clamps bolted through the wall on all residential services. 3. All services must comply with Codes requirements for clearance. A minimum 18 ft. clearance is required on all non-residential services. In no case shall a point of attachment be less than 12 ft. or more than 30 ft. above final grade. 4. See ESG-1 for additional specification details. B. Underground Services: See ESG-2 or ESG-3 for specification details. See drawings 1S and 2S for the secondary ditch details. C. Manufactured and Modular Home Services: 1. A red HUD label identifies manufactured or mobile homes. Meters may not be installed on manufactured or mobile homes. See ESG-4 or ESG-5 for specification details. 2. Modular homes are identified by a green State of Tennessee label. Services for modular homes may be identical to overhead or underground residential services. See ESG-1, ESG-2, or ESG-3 for specification details. D. Temporary Services: 1. Overhead - Temporary service pole must be within 125 ft. of MTEMC pole. See ESG-6 for specification details 2. Underground - Temporary service pole must be located behind right corner of pad mount transformer or underground secondary box. See ESG-7 for specification details. E. Meter on MTEMC s Pole: MTEMC no longer allows meter installations on MTEMC poles. When a MTEMC pole is changed out, any meters on MTEMC s poles shall be removed if possible. Meters on poles for communication companies may be transferred to new poles as necessary. GENERAL SERVICE CONDUCTOR Service conductors installed near other utility lines, structures, or obstructions require: A. Conductors run parallel to water or gas lines must have a minimum 3 ft. separation. B. Telephone and TV cable may run in the same ditch with a minimum 36 in. horizontal separation between service conductor and cable; or 12 in. vertical separation AND 18 in. horizontal separation. C. All foreign utility perpendicular crossings must have 12 in. minimum separation from MTEMC ducts.

5 GENERAL METERING REQUIREMENTS Non Residential- anything other than a single family dwelling 1. All meter sockets used in MTEMC s service area must be one of the MTEMC approved meter sockets (bases). All sockets and hubs shall be furnished and installed by the member. 2. All meter sockets must be mounted between 4 and 6 feet above final grade. 3. All meter sockets shall be mounted outdoors in a location that is easily accessible for MTEMC personnel. Any variation must be approved in writing by a MTEMC engineering representative. 4. The maximum allowable service wire to connect to MTEMC padmount transformer is 750MCM. The maximum allowable service wire to connect in UG pull box is 500 MCM. For single phase services of 800 amps or less, MTEMC will pull the service wire from the transformer/pull box to the metering point. 5. For multiple services feeding from the same transformer a non-fused safety switch with provisions for an MTEMC padlock shall be installed on the source side each 277/480V self contained (400 Amps and smaller) meter and each instrument metering installation (larger than 400 Amps). 120/208V and 120/240V self contained (400 Amps and smaller) metering shall require a disconnect adjacent to the meter on the exterior of the building. 6. If more than one metering installation is fed from the same transformer, a disconnect shall be installed on the source side of all troughs and ganged metering installations. 7. If a service conductor feeds several meters (gang meter socket, metering trough, etc.), each meter and disconnect shall be labeled with identification numbers (address). These numbers shall be on a stamped or engraved brass or stainless steel label and attached with 2 or more rivets. They should be in a readily visible location on both the meter and disconnect. Labels shall be furnished and installed by the customer. Residential- single family dwelling 1. All meter sockets used in MTEMC s service area must be one of the MTEMC approved meter sockets (bases). All sockets and hubs shall be furnished and installed by the member. 2. All meter sockets must be mounted between 4 and 6 feet above final grade. 3. All meter sockets shall be mounted outdoors in a location that is easily accessible for MTEMC personnel. Any variation must be approved in writing by a MTEMC engineering representative. 4. The maximum allowable service wire to connect to MTEMC padmount transformer is 750MCM. The maximum allowable service wire to connect in UG pull box is 500 MCM. For single phase services of 800 amps or less, MTEMC will pull the service wire from the transformer/pull box to the metering point. 5. Meter base will not be located on or under porches, decks or carports. The meter base shall be located as close to MTEMC s transformer/pull box as possible. If the distribution panel is not located in immediate vicinity of meter, a weatherproof disconnect may be required; refer to National Electric Code. 6. A grounding electrode conductor (ground wire) of a minimum of No. 4 copper or larger shall be run unspliced from a lug in the meter base to a driven grounding electrode (ground rod). An 8 ft. driven grounding electrode (ground rod) bonded to grounding electrode conductor (ground wire) with clamp suitable for direct soil burial will be installed below final grade.

6 METERING ROOMS NO ELECTRICAL METER ROOM WILL BE ALLOWED WITHOUT PRIOR MTEMC APPROVAL. City or County approval of meter room locations is not sufficient and will not be considered if a meter room is installed without prior MTEMC consultation. A drawing showing the physical arrangement of all meters must be provided to MTEMC prior to obtaining approval. If physical space available requires that meter bases be installed in a vertical arrangement, the highest meter shall be not more than seven (7) feet above the floor to the center of the glass cover, and the lowest meter shall not be less than three (3) feet from the floor to the center of the glass cover. When indoor meter locations are necessary and approved by MTEMC, the meters shall be located where they will be readily accessible at ALL times for emergencies, meter reading, testing and other maintenance purposes. All meter locations shall meet all NEC requirements regarding but not limited to access, egress and clear space around the meter. There shall be a minimum of three and one half (3.5) feet working space between the front of the meter socket and any walls or other obstructions. In the event that the meter room is located inside of the building, all secondary conductors under the building shall be encased in RED concrete and be installed 12 inches below all indoor facilities (water, gas, sewer). Raceway under the building shall be responsibility of owner to maintain or repair in the event of failure, therefore installing a spare conduit(s) at time of construction may be advantageous. The concrete encasement shall extend a minimum of three (3) feet from the edge of the building foundation. If the meter bases are located on an exterior wall then no encasement is required. It is preferable that meter rooms be accessible without requiring entry into the building itself. Situations will be evaluated on a case-by-case basis, with MTEMC having the final decision making authority as to the acceptability of the proposed location. Further, it is preferable that meter rooms NOT have a door or gate, locking or otherwise. However, when a locked gate or door is required and approved by MTEMC, the customer shall either: Provide and install a NEMA 3R key box adjacent to the meter room door or gate with provisions for an MTEMC padlock. (7/16 th inch shank) Customer shall provide a key to the door or gate which will remain in the key box at all times. Or In the case of a gate, the use of a chain and lock for securing the entrance into the meter room is acceptable. MTEMC shall place its padlock in the chain in such a way that only the MTEMC key will be required to gain entry into the meter room. Access is a critical issue for MTEMC related to its facilities. If access to the meter room is not possible due to key or lock issues, MTEMC reserves the right to remove the door or gate and is not responsible for any damages to those or for reinstalling them in the future. Meter rooms shall not be used for other purposes such as storage closets, maintenance areas, etc. Meter bases shall be surface mounted. Flush mounted or recessed meter installations are not acceptable. If the acceptance of a meter room by MTEMC requires additional communication infrastructure related to the reading of the meters by the MTEMC AMI system, the additional costs will be the responsibility of the customer.

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24 MTEMC Office Locations FRANKLIN 2156 Curd Lane Franklin, Tennessee LEBANON 201 Maddox-Simpson Parkway Lebanon, Tennessee Mt JULIET 1475 North Mt. Juliet Road Mt. Juliet, Tennessee WOODBURY 911 West Main Woodbury, Tennessee SMYRNA 317 S. Lowry Street Smyrna, Tennessee MURFREESBORO 326 St. Andrews Drive Murfreesboro, Tennessee CORPORATE 555 New Salem Road Murfreesboro, Tennessee Customer Service:

BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE

BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE Toll Free Telephone Numbers Residential Services 800.454.3853 Commercial Services 800.653.5307 Utility Locating Company N.C. 800.632.4949 S.C. 888.721.7877

More information

Please check with your local inspection authority for any additional requirements before installation.

Please check with your local inspection authority for any additional requirements before installation. Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be

More information

NEW SERVICE INSTALLATION STEPS. Common Slow Downs. Other Necessary Steps

NEW SERVICE INSTALLATION STEPS. Common Slow Downs. Other Necessary Steps NEW SERVICE INSTALLATION STEPS Here is the step-by-step process required to fulfill your service installation request. Please take a few minutes to review the steps, become familiar with key milestones

More information

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property 2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical

More information

TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE

TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE A. GENERAL NOTES: Service entrance line and load conductors, conduit straps, weatherhead, lock nuts, bushings, connectors, and

More information

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document

More information

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,

More information

Policy and Guidelines for Electric Service

Policy and Guidelines for Electric Service Policy and Guidelines for Electric Service FRANKLIN MUNICIPAL POWER & LIGHT 1050 Pretlow Street Franklin, VA 23851 757-562-8568 757-562-7883 Fax January 2008 Franklin Power & Light HELPFUL TELEPHONE NUMBERS

More information

MOBILE HOME SERVICE REQUIREMENTS GAS

MOBILE HOME SERVICE REQUIREMENTS GAS ELECTRIC AND GAS 1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 GENERAL 4.0 REFERENCE MATERIAL 5.0 TYPICAL UNDERGROUND UTILITY LAYOUT 6.0 METER PAD DETAILS 7.0 GENERAL INSTALLATION PROCEDURES 8.0 PEDESTAL SPECIFICATIONS

More information

Electrical Code Regulation

Electrical Code Regulation Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county

More information

Electric Service Manual

Electric Service Manual Table of Contents SECTION 1... 5 INTRODUCTION... 5 SECTION 2... 7 DEFINITIONS... 7 COMPANY... 7 CUSTOMER... 7 OVERHEAD SERVICE DROP... 7 UNDERGROUND SERVICE DROP... 7 SERVICE ENTRANCE... 7 SERVICE EQUIPMENT...

More information

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

ELECTRIC METERING COMMERCIAL & INDUSTRIAL ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS

More information

SERVICE ENTRANCE REQUIREMENTS MANUAL

SERVICE ENTRANCE REQUIREMENTS MANUAL SERVICE ENTRANCE REQUIREMENTS MANUAL 7th Edition 2012 TABLE OF CONTENTS BTU General Policies and Procedures... 3 SECTION 1: Temporary Construction Meter Poles... 5 Temporary Overhead Fed Meter Pole...

More information

SWIMMING POOL, SPA, & HOT TUB GUIDELINES

SWIMMING POOL, SPA, & HOT TUB GUIDELINES SWIMMING POOL, SPA, & HOT TUB GUIDELINES Pool permit cost is based on the total value of the project. See Permit Fee Schedule Table 1A. A. Adopted construction codes and installation requirements 1. 2015

More information

ELECTRIC SERVICE HANDBOOK

ELECTRIC SERVICE HANDBOOK ELECTRIC SERVICE HANDBOOK Revised July 2006 Table of Contents Electric Construction Title: Electric Service Handbook Page No. TOC Rev. July-06 Section 1: Introduction...1-010 Section 2: DP&L Offices...2-010

More information

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264 BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

Step 1: Application Instructions

Step 1: Application Instructions Step 1: Application Instructions CONTENTS Introduction Customer and Electrician Instructions Completing Section 1 or Section 2 Definitions INTRODUCTION Every effort has been made to provide clear instruction

More information

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1

INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

OVERHEAD SERVICE. Table of Contents - Section 400

OVERHEAD SERVICE. Table of Contents - Section 400 OVERHEAD SERVICE Table of Contents - Section 400 PARAGRAPH 400.0 OVERHEAD SERVICES (0-600 VOLTS)... 1 400.1 GENERAL... 1 400.2 IDENTIFICATION OF CONDUCTORS... 1 400.3 MAXIMUM SERVICE ENTRANCE CONDUCTOR

More information

PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property.

PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property. INTRODUCTION These rules are issued for use by Customers, builders, electrical contractors, architects, engineers, etc. The rules require the installation of safe and adequate wiring and electrical equipment,

More information

2012 Edition Redbook 11.0 GENERAL DRAWINGS AND STANDARDS

2012 Edition Redbook 11.0 GENERAL DRAWINGS AND STANDARDS 2012 Edition Redbook 11.0 GENERAL DRAWINGS AND STANDARDS Minimum Vertical Clearances Above Ground and Roofs D1 Minimum Pool Clearances D2 Minimum Clearances of Wires Adjacent to Buildings and Other Structures

More information

IRRIGATION PUMPING Table of Contents - Section 900

IRRIGATION PUMPING Table of Contents - Section 900 IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS

More information

Underground Commercial Electric Service

Underground Commercial Electric Service Underground Commercial Electric Service SCANA Corporation 2013 Revised: June 2013 Table of Contents SECTION PAGE I. Specification and Requirements 2 A. General B. Definition of Terms C. Company and Developer

More information

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to

More information

CARROLL COUNTY ELECTRICAL DEPARTMENT SERVICE POLICIES. EFFECTIVE MARCH 1, 1995 Revised 1/01/2013

CARROLL COUNTY ELECTRICAL DEPARTMENT SERVICE POLICIES. EFFECTIVE MARCH 1, 1995 Revised 1/01/2013 CARROLL COUNTY ELECTRICAL DEPARTMENT SERVICE POLICIES EFFECTIVE MARCH 1, 1995 Revised 1/01/2013 CARROLL COUNTY ELECTRICAL DEPARTMENT 103 WEST PARIS ST. P. O. BOX 527 HUNTINGDON, TENNESSEE 38344 Telephone

More information

METERING INSTALLATION REQUIREMENTS

METERING INSTALLATION REQUIREMENTS METERING INSTALLATION REQUIREMENTS Table of Contents Section 300 PARAGRAPH 300.0 METERING AND SERVICE ENTRANCE EQUIPMENT... 1 300.1 GENERAL... 1 300.2 METERED AND UNMETERED CONDUCTORS... 1 300.3 SEALING

More information

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope 3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service

More information

Electric Service Standards

Electric Service Standards IV: 1 of 24 IV. SERVICE and METER CONNECTIONS A. Service Equipment 1. General The Customer should consult FPL at an early stage to verify availability of service (section II.C) and to determine the FPL

More information

800 Communications Circuits

800 Communications Circuits ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that

More information

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained

Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase

More information

208.652.7431 Report power outage after hours: 866.887.8442. 1150 N. 3400 E. Ashton, ID 83420 www.frr ec.com. Ashton, Idaho Headquarters Building

208.652.7431 Report power outage after hours: 866.887.8442. 1150 N. 3400 E. Ashton, ID 83420 www.frr ec.com. Ashton, Idaho Headquarters Building The aim of Fall River Rural Electric Cooperative, Inc. is to make electric energy available to its members at the lowest cost consistent with sound economy and good management. Ashton, Idaho Headquarters

More information

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D 12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section

More information

Electric Service Requirement Handbook

Electric Service Requirement Handbook INLAND POWER 10110 W. HALLETT RD. SPOKANE, WA 99224-7435 inlandpower.com Electric Service Requirement Handbook Table of Contents Contact Information... 1 1. Introduction... 2 2. Line Extension Policy...

More information

COMMERCIAL CONDUIT RULES AND REGULATION

COMMERCIAL CONDUIT RULES AND REGULATION Electric Engineering Division COMMERCIAL CONDUIT RULES AND REGULATION S:\COO_ACM_US_Electric_Telecommunications\COO_ET_Engineering\Conduit Policies\Residential 1805 NE 30th Ave., Bldg. 400 Ocala, FL 34470-4875

More information

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions

More information

Electric Service Requirements & Guidelines

Electric Service Requirements & Guidelines Electric Service Requirements & Guidelines Montana Service Area September 2011 NORTHWESTERN ENERGY Montana Service Area ELECTRIC SERVICE REQUIREMENTS AND GUIDELINES CONTENTS I. GENERAL INFORMATION 1.01

More information

ELECTRIC SERVICE HANDBOOK General Information Residential Service Portable/Standby Generators Temporary Service Commercial Service Metering

ELECTRIC SERVICE HANDBOOK General Information Residential Service Portable/Standby Generators Temporary Service Commercial Service Metering ELECTRIC SERVICE HANDBOOK General Information Residential Service Portable/Standby Generators Temporary Service Commercial Service Metering Requirements Clearance Requirements August 2015 A current version

More information

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS

Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS TABLE OF CONTENTS I. RULES AND REGULATIONS A. TABLE OF CONTENTS... 2 B. TERMS AND DEFINITIONS... 3 C. DEVELOPER S/CONTRACTOR S RESPONSIBILITIES...

More information

County of Riverside Building and Safety Department

County of Riverside Building and Safety Department County of Riverside Building and Safety Department Mike Lara Director Photovoltaic Permitting Guidelines The information provided in this document is general and is intended only as a guide. Each project

More information

Customer Metering and Services Guide

Customer Metering and Services Guide This document is an uncontrolled copy and may not be the most current copy. The most current copy is available at www.atcoelectric.com. This document is the property of ATCO Electric and may be updated

More information

INSPECTION GUDELINES

INSPECTION GUDELINES GENERAL REQUIREMENTS Building permit and approved set of plans Building permit on the card is the same as on the route "If this is not the first inspection, read inspection records and notes on permit

More information

AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding

AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding A Guide for California Developers of Com m ercial Property This guide consists of

More information

Mobile Home Pre-Inspection Checklist

Mobile Home Pre-Inspection Checklist Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING

More information

Electric Service Standards

Electric Service Standards VI - 1 of 17 VI. METERING EQUIPMENT A. Equipment Furnished and Installed by FPL FPL provides and installs, at its expense, adequate metering instruments to measure the electric service used by the Customer.

More information

Electric Service and Meter Installations Manual SCANA Corporation 2013

Electric Service and Meter Installations Manual SCANA Corporation 2013 Electric Service and Meter Installations Manual SCANA Corporation 2013 Revised: June 2013 On file with South Carolina Public Service Commission Table of Contents Section 1: Introduction 1 Customer Call

More information

Hyperlinks are Inactive

Hyperlinks are Inactive Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)

More information

0095.05 June 30. 2011 July 18, 2014 1 of 7

0095.05 June 30. 2011 July 18, 2014 1 of 7 Standard Number: Superseding: Effective Date: Page: 0095.05 June 30. 2011 July 18, 2014 1 of 7 Pole Attachments, Automated Meter Reading and Cellular Phone Antennas 1. Scope 2. Application This standard

More information

Underground Service Requirements and Instructions

Underground Service Requirements and Instructions This packet includes all FKEC underground service requirements, instructions, procedures and drawings. If you are considering underground power service please review this document in its entirety (3 page

More information

Call the Experts at REA Energy Services for all of Your Electrical and HVAC Needs.

Call the Experts at REA Energy Services for all of Your Electrical and HVAC Needs. Call the Experts at REA Energy Services for all of Your Electrical and HVAC Needs. REA Energy Services Sells and Installs: Heating and Air Conditioning Electrical Contracting Geothermal Heat Pumps Back-Up

More information

Approved Meter Sockets and Cabinets

Approved Meter Sockets and Cabinets Single Unit Residential Guide 1 PHASE, 120/240 VOLT S METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to center of meter ± 100 mm ( 4

More information

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov

City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a

More information

Residential Electrical Inspection. Checklist

Residential Electrical Inspection. Checklist 443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us Residential Electrical Inspection (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5743 TTY: (651) 297-4198 Checklist Generally, Minnesota

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Requirements for the Attachment of Communication Cable Facilities on PPL Poles Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication

More information

Guide for Electric Service and Meter Installations

Guide for Electric Service and Meter Installations Guide for Electric Service and Meter Installations April 28, 2009 Preface This booklet is not intended to conflict with the National Electrical Safety Code, the National Electrical Code, or such state

More information

Top Commercial / Residential Electrical Requirements *

Top Commercial / Residential Electrical Requirements * Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial

More information

New Residential Service Requiring Construction

New Residential Service Requiring Construction New Residential Service Requiring Construction What you should know about having service connected to your new home visit us at www.flintenergies.com FEMC 593 R2/12 All references from NEC 2011 New Residential

More information

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage: Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial

More information

ELECTRIC SERVICE GUIDELINES (For Indiana)

ELECTRIC SERVICE GUIDELINES (For Indiana) ELECTRIC SERVICE GUIDELINES (For Indiana) FOR COMMERCIAL / INDUSTRIAL DEVELOPMENTS ELECTRIC SERVICE GUIDELINES FOR COMMERCIAL/INDUSTRIAL DEVELOPMENTS INTRODUCTION... 2 WHAT YOU NEED TO OBTAIN ELECTRIC

More information

Electric Service Rules

Electric Service Rules 2016 Electric Service Rules GENERAL INFORMATION TEMPORARY SERVICES OVERHEAD SERVICES UNDERGROUND SERVICES DISTRIBUTED GENERATION METERING HUD MANUFACTURED HOMES FARM SERVICES UTILITY/CATV SERVICES PRIMARY

More information

Gas Meter Clearances and Service Installation Requirements

Gas Meter Clearances and Service Installation Requirements March 2015 Gas Meter Clearances and Service Installation Requirements Builder/Owner/Developer Requirements Call PSE s Customer Construction Services 1-888-321-7779 or visit PSE.com/CustomerConstruction

More information

Requirements for the installation of. Electric Services. September 8, 2003. Specifications for Electric Installations

Requirements for the installation of. Electric Services. September 8, 2003. Specifications for Electric Installations Requirements for the installation of Electric Services & Meters September 8, 2003 Specifications for Electric Installations TABLE OF CONTENT Section I - Introduction... 1 Section II - Definitions... 3

More information

Solar Panel Installations

Solar Panel Installations Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.

More information

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING

TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET

More information

TABLE OF CONTENTS. PUD SERVICE TERRITORY & CONTACTS... Page 1. NEW SERVICE QUESTIONNAIRE... Page 2. GENERAL... Page 3

TABLE OF CONTENTS. PUD SERVICE TERRITORY & CONTACTS... Page 1. NEW SERVICE QUESTIONNAIRE... Page 2. GENERAL... Page 3 UNDERGROUND TABLE OF CONTENTS PUD SERVICE TERRITORY & CONTACTS... Page 1 NEW SERVICE QUESTIONNAIRE... Page 2 GENERAL... Page 3 TRENCHING SECONDARY (120/240 volts)... Page 3 CONDUITS FOR PUD-INSTALLED CONDUCTORS...

More information

REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING

REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING REQUIREMENTS AND SPECIFICATIONS FOR HIGH VOLTAGE CUSTOMER BUILT FACILITIES PEPCO ENGINEERING Revised October, 2013 TABLE OF CONTENTS 1.0 INTRODUCTION... 3 2.0 REQUIRED DRAWINGS... 3 2.1 Site Plan... 3

More information

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,

More information

Duke Energy Carolinas. Inverter Based Generation Interconnection

Duke Energy Carolinas. Inverter Based Generation Interconnection Duke Energy Carolinas Inverter Based Generation Interconnection Options for Non-Residential Service Customers Table of Contents Rider NM and Rider SCG: Net Metering Single Phase PV System Typical 120/240V

More information

Section 5 Meters and Service Entrance Equipment

Section 5 Meters and Service Entrance Equipment Table of Contents Section 5 Meters and Service Entrance Equipment A. GENERAL... 5-3 B. METER TOTALIZING... 5-4 C. SEQUENCE OF SERVICE ENTRANCE EQUIPMENT... 5-4 D. METER LOCATIONS... 5-11 E. METER ROOMS...

More information

SPECIAL GUIDELINES FOR ELECTRICAL INSTALLATION

SPECIAL GUIDELINES FOR ELECTRICAL INSTALLATION SPECIAL GUIDELINES FOR ELECTRICAL INSTALLATION **** New Contact and Fax Telephone Numbers, Page 3 **** Effective October 1, 2011 CITY OF BRENTWOOD PLANNING AND CODES DEPARTMENT BRENTWOOD, TENNESSEE Updated

More information

Gas Meter Clearances and Service Installation Requirements

Gas Meter Clearances and Service Installation Requirements March 2016 Gas Meter Clearances and Service Installation Requirements Builder/Owner/Developer Requirements Call PSE's Customer Construction Services 1 888 321 7779 or visit PSE.com/CustomerConstruction

More information

Section 10 Electric Switchboards: 0 Through 600 Volts

Section 10 Electric Switchboards: 0 Through 600 Volts Section 10 Electric Switchboards: 0 Through 600 Volts 10.1. Scope This section provides specific dimensions and details for service and meter equipment that is assembled by the manufacturer in freestanding,

More information

GENERAL ELECTRICAL REQUIREMENTS

GENERAL ELECTRICAL REQUIREMENTS GENERAL ELECTRICAL REQUIREMENTS RECEPTACLE SPACING Within 6-feet of the edge of any door HABITABLE Not more than 12-feet apart along wall ROOMS: At all wall spaces 24 or more wide Within 24 of edge of

More information

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)

ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity

More information

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS

MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

Residential Electrical Inspection Checklist

Residential Electrical Inspection Checklist Residential Electrical Inspection Checklist Based on the 2008 National Electrical Code Generally, Minnesota law requires all electrical work to be performed by licensed, bonded and insured electrical contractors

More information

UNDERGROUND ELECTRIC TEMPORARY SERVICE PANEL

UNDERGROUND ELECTRIC TEMPORARY SERVICE PANEL S 1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 CUSTOMER RESPONSIBILITY FOR TOTAL TEMPORARY SERVICE 4.0 CUSTOMER RESPONSIBILITY FOR TEMPORARY SERVICE IN PERMANENT LOCATION 5.0 NVE RESPONSIBILITIES 6.0 GROUNDING

More information

Customer Substation Manual 08/05/02

Customer Substation Manual 08/05/02 Customer Substation Manual Table of Contents Section Page 2 of 85 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation

More information

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12 SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications

More information

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS

GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical

More information

Section 2 General Requirements

Section 2 General Requirements Table of Contents Section 2. General Requirements Section 2 General Requirements A. SCOPE... 2-3 B. AVAILABILITY OF SERVICE... 2-3 C. APPLICATION FOR SERVICE... 2-4 D. SERVICE ENTRANCE LOCATION / METER

More information

SPECIFICATIONS FOR ELECTRIC SERVICE GARLAND POWER & LIGHT

SPECIFICATIONS FOR ELECTRIC SERVICE GARLAND POWER & LIGHT FOREWORD This booklet is issued by the Electric Department of the City of Garland, herein after referred to Garland Power & Light or GP & L, to acquaint electric customers of Garland Power & Light, or

More information

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the

More information

Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10

Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10 Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10 This document was developed by the Orange County Fire Chiefs Association, Orange County Fire Marshal Committee.

More information

NTUA GUIDELINES FOR DESIGNING AN ELECTRICAL POWER DISTRIBUTION SYSTEM FOR NEW DEVELOPMENTS

NTUA GUIDELINES FOR DESIGNING AN ELECTRICAL POWER DISTRIBUTION SYSTEM FOR NEW DEVELOPMENTS NTUA GUIDELINES FOR DESIGNING AN ELECTRICAL POWER DISTRIBUTION SYSTEM FOR NEW DEVELOPMENTS These guidelines are intended to familiarize Developers regarding some issues that are important to get electric

More information

Doe Residence - 5.64 kw DC Roof Mounted Photovoltaic System

Doe Residence - 5.64 kw DC Roof Mounted Photovoltaic System EQUIPMENT SUMMARY 20 LG 300W solar panels 1 SMA SE6000AUS Inverter Everest Solar Systems Cross Rail Racking System QuickMount PV Quick Hook Curved Tile Mount QMCTH SHEET INDEX T01 COVER PV01 SITE MAP &

More information

Generator DoCKInG StatIonS

Generator DoCKInG StatIonS Generator DOCKING STATIONS TRYSTAR Portable Power Cable Cam to cam cable extensions 2000V, 100A-400A rated to NEC table 400.5 (B) All portable power cable sold is highly flexible and UL & C-UL or CSA Listed

More information

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC ELECTRICAL SERVICE REQUIREMENTS ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC TABLE OF CONTENTS TITLE SECTION NO. List of Approved Electric Utility Service Equipment Requirements Committee

More information

How To Get A Power Line Extension

How To Get A Power Line Extension GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs

More information

Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM

Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM Los Angeles Fire Department Requirement No. 96 SOLAR PHOTOVOLTAIC SYSTEM The following is the Los Angeles Fire Department s minimum requirement for Solar Photovoltaic System Installations. The City of

More information

TCTC Cabling Specifications

TCTC Cabling Specifications TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,

More information

Residential Decks. Planning and Development Services Department

Residential Decks. Planning and Development Services Department Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: [email protected] Planning and Development Services Department Residential Decks

More information

Application for. Commercial New Service

Application for. Commercial New Service Application for Commercial New Service Welcome to Lake Country Power! In order to make your new service installation easy, we provide individualized help to process and install a new service. In order

More information

Considering UNDERGROUND. tampaelectric.com

Considering UNDERGROUND. tampaelectric.com Considering UNDERGROUND Electric Service? tampaelectric.com INTRODUCTION The majority of Tampa Electric s customers receive their electric service through overhead construction, which is the standard type

More information

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp

SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp SERVICE ENTRANCE - UNDERGROUND 07-01-15 PAGE 1 OF 6 USE: Arrangement of service equipment to supply electric energy to an underground, outdoor self contained meter installation. LATEST REVISION: PREVIOUS

More information

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers

ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers ELECTRICAL REQUIREMENTS Specific Information for Electrical Work Installers This handout is intended to be a general overview of residential electrical requirements as noted in the 2014 National Electrical

More information