Please check with your local inspection authority for any additional requirements before installation.
|
|
|
- Claude Norton
- 9 years ago
- Views:
Transcription
1 Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be approved in advance by Ameren Illinois. If you have any questions, please contact your Ameren Illinois Representative at the number listed on the back of this brochure, or call or visit us at or for more detailed information. BEFORE DIGGING CALL JULIE or 811 To insure your new overhead electric service is installed in a safe, reliable and timely manner, the following specifications must be met. Failure to meet any of the requirements may cause a delay in receiving service and/or require the relocation of facilities. Please check with your local inspection authority for any additional requirements before installation. Location for Point of Delivery on Buildings NOTES: (Service Manual Figure 200-1C) Meter Location 1. These guidelines apply to Ameren Illinois only. 2. An approved location for the point of delivery to a customer s premises will normally be between the midpoints of building from the corner nearest the company s distribution system. A and C are the midpoints of the building. The service may be located anywhere between A and B or B and C observing clearance requirements from windows, chimneys, driveways, trees, etc. outlined in Figure 600-6A and Section Location of Service Manual. 3. Distribution point from Ameren System may be overhead or underground. Refer questions to an Ameren representative if recommended location is not feasible. 4. Applicable charges are governed by state regulatory tariffs. Contact your local Ameren representative for an explanation of charges that may apply. 5 Meter socket shall be securely attached to home 3 to 5 6 above finished grade from center of the meter. A minimum of 3-1/2 of clear working space shall be provided and maintained in front of all meter and instrument transformer enclosures and 6 above, below, and to each side of the meter equipment, and 6-6 standing headroom. See meter location for additional details AMEREN ILLINOIS SPECIFICATIONS FOR RESIDENTIAL OVERHEAD ELECTRIC INSTALLATION DATE: Revised &Amended Page 1
2 Grounding (Service Manual Figure 500-1A) Notes: (The notes included as below are part of notes from Service Manual, Section 500) 1. The grounding method drawing is schematic in nature. Actual wiring details will vary between equipment and manufacturer. 2. The details shown in these drawings are not a substitute for an understanding of the grounding and bonding requirements of the National Electrical Code (NEC) and the requirements of the Jurisdiction Having Authority in the area the work is taking place. 3. For meters mounted outdoors, Ameren requires an external ground rod at the meter socket location that is connected to the meter socket. It is essential that Ameren can verify that there is a grounded meter socket for safety of Ameren personnel; installation of an external ground rod will provide this assurance. Installation and material used for this Ameren required external ground rod must meet all NEC requirements for size, material and installation requirements. If an external ground rod connected to the meter socket is provided by the customer to meet NEC grounding requirements this ground rod will also meet Ameren s requirement for an external ground rod. Where the customer has a main service disconnect mounted within 10 and in sight of the Ameren meter socket, connection of an external ground rod to the main service disconnect is acceptable in lieu of landing in the meter socket. In cases where Ameren has approved meter mounted indoor, an external ground requirement rod is not required. Grounding should be provided to meet requirements of the NEC or the Jurisdiction Having Authority. 10. The grounding electrode system may be connected to the meter socket (or CT/PT enclosure) neutral, or the service equipment neutral, but not both when it would create a parallel path for neutral current. 11. The equipment cabinet must be bonded to neutral and ground in this application. 14. Bonding of metallic conduit systems is not shown in any of the drawings. 15. Grounding of communication systems should not be made at the meter socket or the meter socket cover. If it is desired to ground the communication system to the premise grounding system the ground should be made with a NEC/UL approved grounding connector that bonds the communication system ground to the premise ground. This connector should be solidly affixed to the premise wall or other substantial premise structure. AMEREN ILLINOIS SPECIFICATIONS FOR RESIDENTIAL OVERHEAD ELECTRIC INSTALLATION DATE: Revised &Amended Page 2
3 Service Specifications Overhead Services Attached to buildings (Service Manual Figure 600-7A) AMEREN ILLINOIS SPECIFICATIONS FOR RESIDENTIAL OVERHEAD ELECTRIC INSTALLATION DATE: Revised &Amended Page 3
4 SINGLE PHASE INSTALLATION, AMP RESIDENTIAL RISER ON CUSTOMER OWNED POLE (Service Manual Figure 600-5A) Notes: 1. Service drop conductors, grips and connectors are provided, installed, and owned by Ameren. 2. See Figure 600-2A of Service Manual for maximum length of residential service drop. For all other services contact Ameren for maximum service lengths. Reduced distance or higher attachment point may be required for large service or to maintain minimum clearances. 3. Customer installs service drop attachment of adequate strength for attachment of Ameren s service drop conductors. See Section 800 of Service Manual for clearance information. 4. Service entrance conductors can be connected to meter socket terminals by Customer. Service entrance conductors can extend a minimum of 36 or longer if required by local inspector, outside the service head for connection to service drop. 5. Service raceway and service entrance conductors to be owned, maintained, and installed by Customer. 6. Customer s installation to meet the requirements of all applicable local codes as well as the NEC. 7. Grounding shall meet the requirements of the latest edition of the National Electrical Code (NEC) or the requirements of the Authority having Jurisdiction. 8. Insulated conduit bushings are required for raceways terminating in the meter socket. 9. The use of flexible metallic conduit, liquid tight flexible metallic conduit, and liquid tight flexible non-metallic conduit for service entrance raceway is prohibited, unless approved by the local inspecting authority. 10. Clearance required between low point of service cable and finished ground grade; refer to Section 800 of Service Manual. 11. The use of electrical grade schedule 40 or 80 PVC for service mast not supporting service drop is allowed unless prohibited by the local inspecting authority. 12. Customer to provide and install support for service attachment and meter socket. 13. Refer to Section 800 of Service Manual for required clearances. 14. Guy and anchor installed by customer to be used when required holding any unbalanced conductor load which pole cannot sustain. 15. If customer install as a yard light on this pole, such yard light shall maintain a clearance to Ameren Service wires by not less than 24. AMEREN ILLINOIS SPECIFICATIONS FOR RESIDENTIAL OVERHEAD ELECTRIC INSTALLATION DATE: Revised &Amended Page 4
5 SINGLE PHASE INSTALLATION 120/240 VOLT RESIDENTIAL OVERHEAD SERVICE AMP RISER/NON-RISER TYPE (Service Manual 600-2A) 1. Before installing electrical facilities, check for compliance with local codes as well as NEC. 2. The screw of the knob shall be imbedded at least 2 into a vertical stud or masonry of the house. Another acceptable attachment such as clevis, bolt and backing plate may be substituted. 3. Approximately 36 or longer of conductor will extend from weatherhead. 4. #2 triplex cable shall not be used where the span length exceeds 140 and 1/0 and 4/0 triplex and quadruplex shall not exceed 100 ft minimum permitted within 6 feet of service mast, providing voltage between conductors does not exceed 600V, the service mast is no more than 4 from the edge of the roof, and the service is terminated at the service mast. 6. Refer to Section 800 of Service Manual for required clearances. 7. Heights greater than shown in Table 1 are possible provided that adequate guying and support are provided and approved by Ameren. 8. The conduit size specified are the minimum required for either conduit fill or strength required to support the overhead service, whichever is greater. 9. Ranch Style homes or buildings with flat roofs may require service masts to provide proper clearance. When through the roof service masts are installed, the customer assumes all responsibility for roof leaks. Service masts must be of adequate strength or be supported by brackets or guy wires to safely withstand the strain imposed by the service drop. The attachment point must have sufficient height to meet clearance requirements. 10. The roof support plate provides the main means of support for the mast. It shall be securely lagged to roof rafters. The following Manufacturers roof support plates are acceptable for use on the Ameren system. Manufacturers 2 Conduit 2-1/2 Conduit PPC Insulators Alternate attachment is to use roof bracket furnished and installed by the customer or contractor. Bracket bolts to be furnished by the customer with minimum ⅜ inches lag bolts or ⅜ inch bolts through the rafter. AMEREN ILLINOIS SPECIFICATIONS FOR RESIDENTIAL OVERHEAD ELECTRIC INSTALLATION DATE: Revised &Amended Page 5
6 OVERHEAD SERVICE SPECIFICATIONS ATTACHMENT TO BUILDINGS 0 TO 600 VOLTS (Service Manual Figure 600-6A) NOTES: (Ameren Service Manual Figure 600-6A) 1. The first point of attachment for service wires shall be in the shaded spaces or higher. The minimum height of attachment shall be adjusted so that the lowest point of the service conductor meets the clearances. A service mast may be used if necessary to obtain the minimum clearances. The point of attachment should be approved by Ameren and should not be located as to limit ladder access, i.e. above a deck, hot tub, spa, stairwell, or swimming pool. 2. The customer s service weatherhead shall not be located above 18, but it may be necessary to attach services higher than 18 to meet the minimum ground clearances. 3. Triplex cable or separate open wire service busses on buildings shall be placed in the shaded spaces shown. 4. Service conductors passing by doors, porches, fire escapes or similar locations, shall have a clearance of not less than 36 inches. Service conductors passing by windows shall have a clearance of not less than 36 inches. 5. Service conductors shall not be installed beneath openings through which materials may be moved, such as openings in farm and commercial buildings. Overhead wires shall not be run such that they obstruct entrance to these building openings. 6. For minimum required clearance of services over sheds, garages, swimming pools, hot tubs, spas, etc., please refer to the latest NEC and NESC. AMEREN ILLINOIS SPECIFICATIONS FOR RESIDENTIAL OVERHEAD ELECTRIC INSTALLATION DATE: Revised &Amended Page 6
7 MATERIALS TO BE FURNISHED & INSTALLED BY CUSTOMER Meter Socket Less than or equal to 320 amp service continuous rating: Clamp jaw lever bypass. To get the latest catalog number information for the meter sockets, please use the website as indicated below. (Note: Ameren Illinois only accepts meter mounting devices from the list, and if failure to comply the requirements may delay service until requirement is met.) CUSTOMER CHECKLIST Correct type & size meter socket installed? (see material list for details) Meter socket properly installed? (securely fastened to wall, at an approved location for the point of delivery to a customer s premises which is between the midpoints of building form the corner nearest the company s distribution system, 3.0 to 5 6 above finished grade) Permanent unobstructed work space left in front of meter socket? (minimum 3 1/2 of clear working space in front of meter and 6 above, below, and to each side of the meter equipment, 6 6 standing headroom) Clear work area required around the Ameren Illinois pole and or secondary where the overhead service will attach. Customer wiring completed and inspected as necessary? Cost arrangements made and easements provided? (as required) Ameren Illinois Work Request No: Engineering Contact: Phone: Construction Contact: Phone: Thank you for letting Ameren Illinois serve your energy needs. Construction and Engineering Services Contact Us Via [email protected] Phone: Monday Friday 7:30-5:00 Visit us at: At Ameren Illinois, we strive to meet our customer's expectations on every job. We measure our customer satisfaction by conducting phone surveys with a sampling of our customers after we complete our work. Our goal is for customers to be fully satisfied with every aspect of their interaction with Ameren Illinois. If for any reason you feel the quality of service you have received throughout this process would not deserve a rating of a 9 or 10, please let us know so we can address your concern at or via at [email protected]. Dig Safely: Call JULIE First Digging responsibly is the only way to dig -- the alternative could lead to personal injury or damage to underground lines, property or the environment. Regardless of the depth of the project, Illinois law requires anyone planning to dig to call JULIE at or 811 at least 48 hours (two working days) prior to the start of excavation and to begin that excavation project within 28 calendar days after calling JULIE. Make the call before you dig and protect yourself and those around you. AMEREN ILLINOIS SPECIFICATIONS FOR RESIDENTIAL OVERHEAD ELECTRIC INSTALLATION DATE: Revised &Amended Page 7
Electrical Code Regulation
Electrical Code Regulation St. Clair County has adopted the 2005 National Electrical Code in its entirety for the unincorporated areas of the county and all communities that have contracted with the county
PRIMARY SERVICE LINE: The Company's conductors which connect the supply line with a transformer located on private property.
INTRODUCTION These rules are issued for use by Customers, builders, electrical contractors, architects, engineers, etc. The rules require the installation of safe and adequate wiring and electrical equipment,
ELECTRIC SERVICE HANDBOOK
ELECTRIC SERVICE HANDBOOK Revised July 2006 Table of Contents Electric Construction Title: Electric Service Handbook Page No. TOC Rev. July-06 Section 1: Introduction...1-010 Section 2: DP&L Offices...2-010
Electrical Service Guidelines
Electrical Service Guidelines Middle Tennessee Electric Membership Corporation Revised: May 23, 2013 MTEMC's Electrical Guidelines TABLE OF CONTENTS Right-of-Way Clearance Guide 3 MTEMC Requirements 4
BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE
BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE Toll Free Telephone Numbers Residential Services 800.454.3853 Commercial Services 800.653.5307 Utility Locating Company N.C. 800.632.4949 S.C. 888.721.7877
TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE
TYPICAL WIRING OF METER SOCKET FOR SINGLE PHASE, THREE WIRE OVERHEAD SERVICE A. GENERAL NOTES: Service entrance line and load conductors, conduit straps, weatherhead, lock nuts, bushings, connectors, and
NEW SERVICE INSTALLATION STEPS. Common Slow Downs. Other Necessary Steps
NEW SERVICE INSTALLATION STEPS Here is the step-by-step process required to fulfill your service installation request. Please take a few minutes to review the steps, become familiar with key milestones
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
Requirements for the Attachment of Communication Cable Facilities on PPL Poles
Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication
4. REQUEST FOR ELECTRIC SERVICE. 4.1 General Service Information
4. REQUEST FOR ELECTRIC SERVICE To establish an electric service, temporary or permanent, contact UI s Customer Care Center by calling: 1-800-722-5584 (7:00 a.m. 7:00 p.m., Monday Friday and 7:00 AM to
ELECTRIC SERVICE HANDBOOK General Information Residential Service Portable/Standby Generators Temporary Service Commercial Service Metering
ELECTRIC SERVICE HANDBOOK General Information Residential Service Portable/Standby Generators Temporary Service Commercial Service Metering Requirements Clearance Requirements August 2015 A current version
Electric Service Manual
Table of Contents SECTION 1... 5 INTRODUCTION... 5 SECTION 2... 7 DEFINITIONS... 7 COMPANY... 7 CUSTOMER... 7 OVERHEAD SERVICE DROP... 7 UNDERGROUND SERVICE DROP... 7 SERVICE ENTRANCE... 7 SERVICE EQUIPMENT...
Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained
Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase
OVERHEAD SERVICE. Table of Contents - Section 400
OVERHEAD SERVICE Table of Contents - Section 400 PARAGRAPH 400.0 OVERHEAD SERVICES (0-600 VOLTS)... 1 400.1 GENERAL... 1 400.2 IDENTIFICATION OF CONDUCTORS... 1 400.3 MAXIMUM SERVICE ENTRANCE CONDUCTOR
2012 Edition Redbook 11.0 GENERAL DRAWINGS AND STANDARDS
2012 Edition Redbook 11.0 GENERAL DRAWINGS AND STANDARDS Minimum Vertical Clearances Above Ground and Roofs D1 Minimum Pool Clearances D2 Minimum Clearances of Wires Adjacent to Buildings and Other Structures
Electric Service Guide for Residential Construction
Electric Service Guide for Residential Construction Table of Contents Contacting KCP&L... 2 Existing Home Remodeling or Additions... 2 Changing your electric service... 2 What you need to know before you
PLEASE NOTE. For more information concerning the history of these regulations, please see the Table of Regulations.
PLEASE NOTE This document, prepared by the Legislative Counsel Office, is an office consolidation of this regulation, current to August 1, 2013. It is intended for information and reference purposes only.
ELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
Policy and Guidelines for Electric Service
Policy and Guidelines for Electric Service FRANKLIN MUNICIPAL POWER & LIGHT 1050 Pretlow Street Franklin, VA 23851 757-562-8568 757-562-7883 Fax January 2008 Franklin Power & Light HELPFUL TELEPHONE NUMBERS
Homeowner Information Guide Electrical Safety. British Columbia Safety Authority
Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in
Approved Meter Sockets and Cabinets
Single Unit Residential Guide 1 PHASE, 120/240 VOLT S METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to center of meter ± 100 mm ( 4
IRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
Electric Service Requirement Handbook
INLAND POWER 10110 W. HALLETT RD. SPOKANE, WA 99224-7435 inlandpower.com Electric Service Requirement Handbook Table of Contents Contact Information... 1 1. Introduction... 2 2. Line Extension Policy...
METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
Electric Service Standards
IV: 1 of 24 IV. SERVICE and METER CONNECTIONS A. Service Equipment 1. General The Customer should consult FPL at an early stage to verify availability of service (section II.C) and to determine the FPL
Electric Service Conversion Overhead-to-Underground. Minnesota
Electric Service Conversion Overhead-to-Underground Xcel Energy Electric Connections Minnesota Process Please fill out these forms and complete this checklist to begin your application process: 1) Overhead-to-Underground
Electric Service and Meter Installations Manual SCANA Corporation 2013
Electric Service and Meter Installations Manual SCANA Corporation 2013 Revised: June 2013 On file with South Carolina Public Service Commission Table of Contents Section 1: Introduction 1 Customer Call
Electric Service Guide for Commercial Construction
Electric Service Guide for Commercial Construction Contents Contacting KCP&L... 2 Voltages... 2 Temporary Service... 2 Customer-Provided Temporary Service... 2 KCP&L-Provided Temporary Service.... 2 Current
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
Call the Experts at REA Energy Services for all of Your Electrical and HVAC Needs.
Call the Experts at REA Energy Services for all of Your Electrical and HVAC Needs. REA Energy Services Sells and Installs: Heating and Air Conditioning Electrical Contracting Geothermal Heat Pumps Back-Up
ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS
Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document
Section 4 Electric Service: Overhead CAUTION
Section 4 Electric Service: Overhead 4.1. Scope This section provides instructions and minimum clearance requirements for attaching permanent, overhead services to residential and nonresidential properties.
SERVICE - GENERAL Residential, Commercial, Industrial
PAGE 1 OF 9 USE: Rules and procedures for overhead or underground services. PREVIOUS REVISION 10-01-01 ORIGINATED 03-94 PREVIOUS NUMBER ER 1-290-B, 07-15-93 LATEST REVISION: Remove details of Facility
CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION
Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED
INSPECTION GUDELINES
GENERAL REQUIREMENTS Building permit and approved set of plans Building permit on the card is the same as on the route "If this is not the first inspection, read inspection records and notes on permit
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS
GUIDELINES FOR WIRING SINGLE FAMILY DWELLING UNITS This guideline has been prepared to assist the owner/occupant of a single family dwelling with compliance to the requirements of the National Electrical
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:
RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS: Signed completed Electrical Permit application form. Minnesota law requires all electrical work is to be performed by licensed,
Charter Township of Shelby Harry Reese Building Director
Charter Township of Shelby Harry Reese Building Director Phone: (586) 731-5969 52700 Van Dyke Fax: (586) 803-2099 Shelby Township, MI 48316-3572 E-mail: [email protected] OUTLINE PROCEDURES FOR PRIVATE
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
Electric Service Guide for Residential Construction
Electric Service Guide for Residential Construction TABLE OF CONTENTS Contacting KCP&L... 2 Existing Home Remodeling or Additions... 2 Building a New Home... 3 KCP&L Services at a Glance... 4 Current Transformers...
WINDOW AND DOOR REPLACEMENT REQUIREMENTS
WINDOW AND DOOR REPLACEMENT REQUIREMENTS Should you have any questions after reading the following information, please call the Building Inspection Department at 651-439-4439 to discuss the topics of concern.
CARROLL COUNTY ELECTRICAL DEPARTMENT SERVICE POLICIES. EFFECTIVE MARCH 1, 1995 Revised 1/01/2013
CARROLL COUNTY ELECTRICAL DEPARTMENT SERVICE POLICIES EFFECTIVE MARCH 1, 1995 Revised 1/01/2013 CARROLL COUNTY ELECTRICAL DEPARTMENT 103 WEST PARIS ST. P. O. BOX 527 HUNTINGDON, TENNESSEE 38344 Telephone
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
SERVICE ENTRANCE - UNDERGROUND Single & Three Phase 200, & 320/400 Amp
SERVICE ENTRANCE - UNDERGROUND 07-01-15 PAGE 1 OF 6 USE: Arrangement of service equipment to supply electric energy to an underground, outdoor self contained meter installation. LATEST REVISION: PREVIOUS
Solar Panel Installations
Solar Panel Installations Page 1 of 6 SINGLE-FAMILY RESIDENTIAL CHECKLIST City of Hayward Development Services Department Revised: 7-09-15 PERMIT REQUIREMENTS Permits are required for all solar panel installations.
800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
City of San Diego Residential Photovoltaic Systems Inspection Guidelines
City of San Diego Residential Photovoltaic Systems Inspection Guidelines The purpose of inspections by DSD staff is to ensure compliance with the California Electrical Code (CEC), other applicable codes
0095.05 June 30. 2011 July 18, 2014 1 of 7
Standard Number: Superseding: Effective Date: Page: 0095.05 June 30. 2011 July 18, 2014 1 of 7 Pole Attachments, Automated Meter Reading and Cellular Phone Antennas 1. Scope 2. Application This standard
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
Underground Commercial Electric Service
Underground Commercial Electric Service SCANA Corporation 2013 Revised: June 2013 Table of Contents SECTION PAGE I. Specification and Requirements 2 A. General B. Definition of Terms C. Company and Developer
REQUEST FOR ELECTRIC SERVICE Commercial
This form should be completed if you are applying to have new electric facilities installed on your property for the purpose of providing electric service to a commercial entity. PROJECT CHECKLIST Below
MOBILE HOME SERVICE REQUIREMENTS GAS
ELECTRIC AND GAS 1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 GENERAL 4.0 REFERENCE MATERIAL 5.0 TYPICAL UNDERGROUND UTILITY LAYOUT 6.0 METER PAD DETAILS 7.0 GENERAL INSTALLATION PROCEDURES 8.0 PEDESTAL SPECIFICATIONS
Electric Service Requirements & Guidelines
Electric Service Requirements & Guidelines Montana Service Area September 2011 NORTHWESTERN ENERGY Montana Service Area ELECTRIC SERVICE REQUIREMENTS AND GUIDELINES CONTENTS I. GENERAL INFORMATION 1.01
SERVICE ENTRANCE REQUIREMENTS MANUAL
SERVICE ENTRANCE REQUIREMENTS MANUAL 7th Edition 2012 TABLE OF CONTENTS BTU General Policies and Procedures... 3 SECTION 1: Temporary Construction Meter Poles... 5 Temporary Overhead Fed Meter Pole...
Step 1: Application Instructions
Step 1: Application Instructions CONTENTS Introduction Customer and Electrician Instructions Completing Section 1 or Section 2 Definitions INTRODUCTION Every effort has been made to provide clear instruction
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
3. TYPES OF SERVICE AVAILABLE. 3.1 Scope
3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service
Changes in the 10/2/2013 Revision of the CNP Service Standards Book
0 Changes in the 10/2/2013 Revision of the CNP Service Standards Book 1. Article 303 - Three Phase (Page 19). Revised 240/120V Delta, Added Max Load to Overhead and Underground 2. Article 408 - Service
BUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
SWIMMING POOL, SPA, & HOT TUB GUIDELINES
SWIMMING POOL, SPA, & HOT TUB GUIDELINES Pool permit cost is based on the total value of the project. See Permit Fee Schedule Table 1A. A. Adopted construction codes and installation requirements 1. 2015
4/1/2016 Revision of the CNP Service Standards Book (Effective Date 5-1-2016)
0 4/1/2016 Revision of the CNP Service Standards Book (Effective Date 5-1-2016) 1. Article 422.1 Meter Pole Installations - Requirements (Page 59). Revised paragraph - Steel poles shall be truck accessible.
208.652.7431 Report power outage after hours: 866.887.8442. 1150 N. 3400 E. Ashton, ID 83420 www.frr ec.com. Ashton, Idaho Headquarters Building
The aim of Fall River Rural Electric Cooperative, Inc. is to make electric energy available to its members at the lowest cost consistent with sound economy and good management. Ashton, Idaho Headquarters
The City of Basehor, Kansas
The City of Basehor, Kansas Residential and Miscellaneous Permits This list provides general information regarding permit requirements for various residential construction and maintenance activities. The
Chapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
Mobile Home Pre-Inspection Checklist
Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING
Electric Service Rules
2016 Electric Service Rules GENERAL INFORMATION TEMPORARY SERVICES OVERHEAD SERVICES UNDERGROUND SERVICES DISTRIBUTED GENERATION METERING HUD MANUFACTURED HOMES FARM SERVICES UTILITY/CATV SERVICES PRIMARY
Residential Electrical Inspection. Checklist
443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us Residential Electrical Inspection (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5743 TTY: (651) 297-4198 Checklist Generally, Minnesota
How To Get A Power Line Extension
GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
Residential Plan Routing Information
Residential Plan Routing Information BUILDING INSPECTIONS 800 4th AVENUE EAST WEST FARGO, ND 58078 PHONE: 701-433-5480 The building Inspection s Department receives and issues all applications for building
The replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
Gas Meter Clearances and Service Installation Requirements
March 2015 Gas Meter Clearances and Service Installation Requirements Builder/Owner/Developer Requirements Call PSE s Customer Construction Services 1-888-321-7779 or visit PSE.com/CustomerConstruction
Requirements for Electric Service and Meter Installations
Requirements for Electric Service and Meter Installations Florida service area Revised 2012 Amended 7/2013 2014 Duke Energy Corporation 140165 01/14 Section TABLE OF CONTENTS Page Number Committee Member
Requirements for Electrical Installations
ARTICLE 110 Requirements for Electrical Installations INTRODUCTION TO ARTICLE 110 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS Article 110 sets the stage for how you ll implement the rest of the NEC. This
TABLE OF CONTENTS. PUD SERVICE TERRITORY & CONTACTS... Page 1. NEW SERVICE QUESTIONNAIRE... Page 2. GENERAL... Page 3
UNDERGROUND TABLE OF CONTENTS PUD SERVICE TERRITORY & CONTACTS... Page 1 NEW SERVICE QUESTIONNAIRE... Page 2 GENERAL... Page 3 TRENCHING SECONDARY (120/240 volts)... Page 3 CONDUITS FOR PUD-INSTALLED CONDUCTORS...
Wellesley Municipal Light Plant. Standard Requirements for Electric Service
Wellesley Municipal Light Plant Standard Requirements for Electric Service Index Section 1... General Information Section 2..General Requirements for Service Section 3. Types of Available Service Section
Electric Service Standards
VI - 1 of 17 VI. METERING EQUIPMENT A. Equipment Furnished and Installed by FPL FPL provides and installs, at its expense, adequate metering instruments to measure the electric service used by the Customer.
GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
Uncovered Decks & Porches
Uncovered Decks & Porches Building Guides for Homeowners Why Do I need a Permit? D I D Y O U K N O W? As owner-builder you are the responsible party of record on such a permit. If your work is being performed
Residential Electric Service Handbook
Residential Electric Service Handbook INTRODUCTION This booklet was developed to help you acquire electrical power to your property. It presents information and general specification about the supply and
How To Plan Out An Array Of Solar Panels
CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013
Applying For New or Revised Electric Service
Applying For New or Revised Electric Service Dear Customer: ComEd is happy to assist you in initiating new or revised electric service to your location. Please complete, sign and return the attached service
Zoning Department DECK PERMITS. Checklist
MANOR BOROUGH Zoning Department DECK PERMITS Checklist Complete Building and Electrical Permit Form. Complete Zoning Permit Form. Obtain a Plot Plan/Survey showing locaion of ALL streets, alleys, property
New Residential Service Requiring Construction
New Residential Service Requiring Construction What you should know about having service connected to your new home visit us at www.flintenergies.com FEMC 593 R2/12 All references from NEC 2011 New Residential
NTUA GUIDELINES FOR DESIGNING AN ELECTRICAL POWER DISTRIBUTION SYSTEM FOR NEW DEVELOPMENTS
NTUA GUIDELINES FOR DESIGNING AN ELECTRICAL POWER DISTRIBUTION SYSTEM FOR NEW DEVELOPMENTS These guidelines are intended to familiarize Developers regarding some issues that are important to get electric
Requirements for the installation of. Electric Services. September 8, 2003. Specifications for Electric Installations
Requirements for the installation of Electric Services & Meters September 8, 2003 Specifications for Electric Installations TABLE OF CONTENT Section I - Introduction... 1 Section II - Definitions... 3
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01)
ELECTRICAL INSPECTION BULLETIN (Effective 2000-03-01) Rule 28-900 Standby Generator Installations Due to the increasing number of standby generator installations being established to maintain continuity
PERMIT APPLICATION REQUIREMENTS FOR RESIDENTIAL ROOF MOUNTED PHOTOVOLTAIC SYSTEMS
Butte County Department of Development Services PERMIT CENTER 7 County Center Drive, Oroville, CA 95965 Main Phone (530)538-7601 Permit Center Phone (530)538-6861 Fax (530)538-7785 FORM NO DBP-71 PERMIT
Residential Electrical Inspection Checklist
Residential Electrical Inspection Checklist Based on the 2008 National Electrical Code Generally, Minnesota law requires all electrical work to be performed by licensed, bonded and insured electrical contractors
How To Protect A Swimming Pool
County of Gloucester Codes Compliance Building Department Building Three P. O. Box 329 Gloucester, Virginia 23061 Building Code Guidelines Residential Swimming Pools & Spas KEEP YOUR POOL SAFE CODE REQUIREMENTS
UNDERGROUND ELECTRIC TEMPORARY SERVICE PANEL
S 1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 CUSTOMER RESPONSIBILITY FOR TOTAL TEMPORARY SERVICE 4.0 CUSTOMER RESPONSIBILITY FOR TEMPORARY SERVICE IN PERMANENT LOCATION 5.0 NVE RESPONSIBILITIES 6.0 GROUNDING
Walking and Working Surface Checklist:
Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!
READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY! The main power to any existing system must be disconnected prior to the
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
new construction departments...
New Service GUIDE NEW SERVICE GUIDE new construction departments... If you re building a new home or performing any construction that requires a change to your existing electric or gas service, it s important
County of Riverside Building and Safety Department
County of Riverside Building and Safety Department Mike Lara Director Photovoltaic Permitting Guidelines The information provided in this document is general and is intended only as a guide. Each project
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a
STREETLIGHT SYSTEM GROUNDING AND BONDING
Page: 1 of 8 STREETLIGHT SYSTEM GROUNDING AND BONDING 1. Scope This Construction Standard covers the grounding and bonding requirements for single phase streetlight systems served by the Looped Radial
