Earth Ground Resistance
|
|
|
- Nora McKenzie
- 9 years ago
- Views:
Transcription
1 Principles, testing methods and applications Diagnose intermittent electrical problems Avoid unnecessary downtime Learn earth ground safety principles Earth Ground Resistance
2 Why Ground, Why Test? Why ground? Poor grounding not only contributes to unnecessary downtime, but a lack of good grounding is also dangerous and increases the risk of equipment failure. Without an effective grounding system, we could be exposed to the risk of electric shock, not to mention instrumentation errors, harmonic distortion issues, power factor problems and a host of possible intermittent dilemmas. If fault currents have no path to the ground through a properly designed and maintained grounding system, they will find unintended paths that could include people. The following organizations have recommendations and/or standards for grounding to ensure safety: OSHA (Occupational Safety Health Administration) NFPA (National Fire Protection Association) ANSI/ISA (American National Standards Institute and Instrument Society of America) TIA (Telecommunications Industry Association) IEC (International Electrotechnical Commission) CENELEC (European Committee for Electrotechnical Standardization) IEEE (Institute of Electrical and Electronics Engineers) However, good grounding isn t only for safety; it is also used to prevent damage to industrial plants and equipment. A good grounding system will improve the reliability of equipment and reduce the likelihood of damage due to lightning or fault currents. Billions are lost each year in the workplace due to electrical fires. This does not account for related litigation costs and loss of personal and corporate productivity. Why test grounding systems? Over time, corrosive soils with high moisture content, high salt content, and high temperatures can degrade ground rods and their connections. So although the ground system when initially installed, had low earth ground resistance values, the resistance of the grounding system can increase if the ground rods are eaten away. Grounding testers, like the Fluke 163 and 165, are indispensable troubleshooting tools to help you maintain uptime. With frustrating, intermittent electrical problems, the problem could be related to poor grounding or poor power quality. That is why it is highly recommended that all grounds and ground connections are checked at least annually as a part of your normal Predictive Maintenance plan. During these periodic checks, if an increase in resistance of more than 0 % is measured, the technician should investigate the source of the problem, and make the correction to lower the resistance, by replacing or adding ground rods to the ground system. What is a ground and what does it do? The NEC, National Electrical Code, Article 100 defines a ground as: a conducting connection, whether intentional or accidental between an electrical circuit or equipment and the earth, or to some conducting body that serves in place of the earth. When talking about grounding, it is actually two different subjects: earth grounding and equipment grounding. Earth grounding is an intentional connection from a circuit conductor, usually the neutral, to a ground electrode placed in the earth. Equipment grounding ensures that operating equipment within a
3 structure is properly grounded. These two grounding systems are required to be kept separate except for a connection between the two systems. This prevents differences in voltage potential from a possible flashover from lightning strikes. The purpose of a ground besides the protection of people, plants and equipment is to provide a safe path for the dissipation of fault currents, lightning strikes, static discharges, EMI and RFI signals and interference. What is a good ground resistance value? There is a good deal of confusion as to what constitutes a good ground and what the ground resistance value needs to be. Ideally a ground should be of zero ohms resistance. There is not one standard ground resistance threshold that is recognized by all agencies. However, the NFPA and IEEE have recommended a ground resistance value of 5.0 ohms or less. The NEC has stated to Make sure that system impedance to ground is less than 5 ohms specified in NEC In facilities with sensitive equipment it should be 5.0 ohms or less. The Telecommunications industry has often used 5.0 ohms or less as their value for grounding and bonding. The goal in ground resistance is to achieve the lowest ground resistance value possible that makes sense economically and physically. Why Test? Corrosive soils. Why Ground? Lightning strikes. Table of contents Why Ground? Why Test? 4 Grounding basics 6 Methods of earth ground testing 1 Measuring ground resistance Use the Fluke 165 to determine the health of your earth ground systems. 3
4 Grounding Basics Components of a ground electrode Ground conductor Connection between the ground conductor and the ground electrode Ground electrode Locations of resistances (a) The ground electrode and its connection The resistance of the ground electrode and its connection is generally very low. Ground rods are generally made of highly conductive/low resistance material such as steel or copper. (b) The contact resistance of the surrounding earth to the electrode The National Institute of Standards (a governmental agency within the US Dept. of Commerce) has shown this resistance to be almost negligible provided that the ground electrode is free of paint, grease, etc. and that the ground electrode is in firm contact with the earth. (c) The resistance of the surrounding body of earth The ground electrode is surrounded by earth which conceptually is made up of concentric shells all having the same thickness. Those shells closest to the ground electrode have the smallest amount of area resulting in the greatest degree of resistance. Each subsequent shell incorporates a greater area resulting in lower resistance. This finally reaches a point where the additional shells offer little resistance to the ground surrounding the ground electrode. What affects the grounding resistance? First, the NEC code (1987, ) requires a minimum ground electrode length of.5 meters (8.0 feet) to be in contact with soil. But, there are four variables that affect the ground resistance of a ground system: 1. Length/depth of the ground electrode. Diameter of the ground electrode 3. Number of ground electrodes 4. Ground system design Length/depth of the ground electrode One very effective way of lowering ground resistance is to drive ground electrodes deeper. Soil is not consistent in its resistivity and can be highly unpredictable. It is critical when installing the ground electrode, that it is below the frost line. This is done so that the resistance to ground will not be greatly influenced by the freezing of the surrounding soil. Generally, by doubling the length of the ground electrode you can reduce the resistance level by an additional 40 %. There are occasions where it is physically impossible to drive ground rods deeper areas that are composed of rock, granite, etc. In these instances, alternative methods including grounding cement are viable. Diameter of the ground electrode Increasing the diameter of the ground electrode has very little effect in lowering the resistance. For example, you could double the diameter of a ground electrode and your resistance would only decrease by 10 %. So based on this information, we should focus on ways to reduce the ground resistance when installing grounding systems.
5 Number of ground electrodes Another way to lower ground resistance is to use multiple ground electrodes. In this design, more than one electrode is driven into the ground and connected in parallel to lower the resistance. For additional electrodes to be effective, the spacing of additional rods need to be at least equal to the depth of the driven rod. Without proper spacing of the ground electrodes, their spheres of influence will intersect and the resistance will not be lowered. To assist you in installing a ground rod that will meet your specific resistance requirements, you can use the table of ground resistances, below. Remember, this is to only be used as a rule of thumb, because soil is in layers and is rarely homogenous. The resistance values will vary greatly. Ground system design Simple grounding systems consist of a single ground electrode driven into the ground. The use of a single ground electrode is the most common form of grounding and can be found outside your home or place of business. Complex grounding systems consist of multiple ground rods, connected, mesh or grid networks, ground plates, and ground loops. These systems are typically installed at power generating substations, central offices, and cell tower sites. Complex networks dramatically increase the amount of contact with the surrounding earth and lower ground resistances. Each ground electrode has its own sphere of influence. Ground systems Single ground electrode. Multiple ground electrodes connected. Type of soil Very moist soil, swamplike Farming soil loamy and clay soils Soil resistivity R E Ground electrode depth (meters) Earthing resistance Earthing strip (meters) ΩM Sandy clay soil Moist sandy soil Concrete 1: Moist gravel Dry sandy soil Dry gravel Stoney soil 30, Rock Mesh network. Ground plate. 5
6 What are the Methods of Earth Ground Testing? There are four types of earth ground testing methods available: Soil Resistivity (using stakes) Fall-of-Potential (using stakes) Selective (using 1 clamp and stakes) Stakeless (using clamps only) Soil resistivity measurement Why determine the soil resistivity? Soil Resistivity is most necessary when determining the design of the grounding system for new installations (green field applications) to meet your ground resistance requirements. Ideally, you would find a location with the lowest possible resistance. But as we discussed before, poor soil conditions can be overcome with more elaborate grounding systems. The soil composition, moisture content, and temperature all impact the soil resistivity. Soil is rarely homogenous and the resistivity of the soil will vary geographically and at different soil depths. Moisture content changes seasonally, varies according to the nature of the sub layers of earth, and the depth of the permanent water table. Since soil and water are generally more stable at deeper strata, it is recommended that the ground rods be placed as deep as possible into the earth, at the water table if possible. Also, ground rods should be installed where there is a stable temperature, i.e. below the frost line. For a grounding system to be effective, it should be designed to withstand the worst possible conditions. How do I calculate soil resistivity? The measuring procedure described below uses the universally accepted Wenner method developed by Dr. Frank Wenner of the US Bureau of Standards in (F. Wenner, A Method of Measuring Earth Resistivity; Bull, National Bureau of Standards, Bull 1(4) 58, p ; 1915/16.) The formula is as follows: ρ = p A R (ρ = the average soil resistivity to depth A in ohm cm) p = A = the distance between the electrodes in cm R = the measured resistance value in ohms from the test instrument Note: Divide ohm centimeters by 100 to convert to ohm meters. Just watch your units. Example: You have decided to install three meter long ground rods as part of your grounding system. To measure the soil resistivity at a depth of three meters, we discussed a spacing between the test electrodes of three meters. To measure the soil resistivity start the Fluke 165 and read the resistance value in ohms. In this case assume the resistance reading is 100 ohms. So, in this case we know: A = 3 meters, and R = 100 ohms Then the soil resistivity would equal: ρ = x p x A x R ρ = x x 3 meters x 100 ohms ρ = 1885 Ωm 6
7 How do I measure soil resistance? To test soil resistivity, connect the ground tester as shown below. As you can see, four earth ground stakes are positioned in the soil in a straight line, equidistant from one another. The distance between earth ground stakes should be at least three times greater than the stake depth. So if the depth of each ground stake is one foot (.30 meters), make sure the distance between stakes is greater than three feet (.91 meters). The Fluke 165 generates a known current through the two outer ground stakes and the drop in voltage potential is measured between the two inner ground stakes. Using Ohm s Law (V=IR), the Fluke tester automatically calculates the soil resistance. Because measurement results are often distorted and invalidated by underground pieces of metal, underground aquifers, etc. additional measurements where the stake s axis are turned 90 degrees is always recommended. By changing the depth and distance several times, a profile is produced that can determine a suitable ground resistance system. Soil resistivity measurements are often corrupted by the existence of ground currents and their harmonics. To prevent this from occurring, the Fluke 165 uses an Automatic Frequency Control (AFC) System. This automatically selects the testing frequency with the least amount of noise enabling you to get a clear reading. START 165 ADVANCED EARTH / GROUND ER GEO Earth/Ground Resistance 300 kω 300 kω E ES S H DC Low Resistance 3 kω H/C S/P Setup for soil resistivity testing using the Fluke 163 or /3 a a a a 7
8 START 165 ADVANCED EARTH / GROUND ER GEO Earth/Ground Resistance 300 kω 300 kω E S H DC Low Resistance 3 kω H/C S/P What are the Methods of Earth Ground Testing? Earth electrode Inner stake >0 m (65 ft) >0 m (65 ft) Fall-of-Potential measurement Outer stake The Fall-of-Potential test method is used to measure the ability of an earth ground system or an individual electrode to dissipate energy from a site. How does the Fall-of-Potential test work? First, the earth electrode of interest must be disconnected from its connection to the site. Second, the tester is connected to the earth electrode. Then, for the 3-pole Fall-of-Potential test, two earth stakes are placed in the soil in a direct line away from the earth electrode. Normally, spacing of 0 meters (65 feet) is sufficient. For more detail on placing the stakes, see the next section. A known current is generated by the Fluke 165 between the outer stake (auxiliary earth stake) and the earth electrode, while the drop in voltage potential is measured between the inner earth stake and the earth electrode. Using Ohm s Law (V = IR), the tester automatically calculates the resistance of the earth electrode. Connect the ground tester as shown in the picture. Press START and read out the R E (resistance) value. This is the actual value of the ground electrode under test. If this ground electrode is in parallel or series with other ground rods, the R E value is the total value of all resistances. How do you place the stakes? To achieve the highest degree of accuracy when performing a 3 pole ground resistance test, it is essential that the probe is placed outside the sphere of influence of the ground electrode under test and the auxiliary earth. If you do not get outside the sphere of influence, the effective areas of resistance will overlap and invalidate any measurements that you are taking. The table is a guide for appropriately setting the probe (inner stake) and auxiliary ground (outer stake). To test the accuracy of the results and to ensure that the ground stakes are outside the spheres of influence, reposition the inner stake (probe) 1 meter (3 feet) in either direction and take a fresh measurement. If there is a significant change in the reading (30 %), you need to increase the distance between the ground rod under test, the inner stake (probe) and the outer stake (auxiliary ground) until the measured values remain fairly constant when repositioning the inner stake (probe). Depth of the ground electrode Distance to the inner stake Distance to the outer stake m 15 m 5 m 3 m 0 m 30 m 6 m 5 m 40 m 10 m 30 m 50 m 8
9 START Earth/Ground Resistance 300 kω 300 kω E S H DC Low Resistance 3 kω Selective measurement Selective testing is very similar to the Fallof-Potential testing, providing all the same measurements, but in a much safer and easier way. This is because with Selective testing, the earth electrode of interest does not need to be disconnected from its connection to the site! The technician does not have to endanger himself by disconnecting ground, nor endanger other personnel or electrical equipment inside a nongrounded structure. Just as with the fall-of-potential test, two earth stakes are placed in the soil in a direct line, away from the earth electrode. Normally, spacing of 0 meters (65 feet) is sufficient. The tester is then connected to the earth electrode of interest, with the advantage that the connection to the site doesn t need to be disconnected. Instead, a special clamp is placed around the earth electrode, which eliminates the effects of parallel resistances in a grounded system, so only the earth electrode of interest is measured. Just as before, a known current is generated by the Fluke 165 between the outer stake (auxiliary earth stake) and the earth electrode, while the drop in voltage potential is measured between the inner earth stake and the earth electrode. Only the current flowing through the earth electrode of interest is measured using the clamp. The generated current will also flow through other parallel resistances, but only the current through the clamp (i.e. the current through the earth electrode of interest) is used to calculate resistance (V=IR). If the total resistance of the ground system should be measured, then each earth electrode resistance must be measured by placing the clamp around each individual earth electrode. Then the total resistance of the ground system can be determined by calculation. Testing individual ground electrode resistances of high voltage transmission towers with overhead ground or static wire, requires that these wires be disconnected. If a tower has more than one ground at its base, these must also be disconnected one by one and tested. However, the Fluke 165 has an optional accessory, a 30 mm (1.7 in) diameter clamp-on current transformer, which can measure the individual resistances of each leg, without disconnecting any ground leads or overhead static/ground wires. Connect the ground tester as shown. Press START and read out the R E value. This is the actual resistance value of the ground electrode under test. 165 ADVANCED EARTH / GROUND ER GEO H/C S/P EI-16X 9
10 START 165 ADVANCED EARTH / GROUND ER GEO START E S H Earth/Ground Resistance 300 kω 300 kω DC Low Resistance 3 kω H/C S/P Earth/Ground Resistance 300 kω 300 kω INDUCING CURRENT EI-16 E S H DC Low Resistance 3 kω EI-16X H/C What are the Methods of Earth Ground Testing? Stakeless measurement 165 ADVANCED EARTH / GROUND ER GEO Source Measure Test current paths in the stakeless method. S/P INDUCING CURRENT EI-16 The Fluke 165 earth ground tester is able to measure earth ground loop resistances for multigrounded systems using only current clamps. This test technique eliminates the dangerous, and time consuming activity of disconnecting parallel grounds, as well as the process of finding suitable locations for auxiliary ground stakes. You can also perform earth ground tests in places you have not considered before: inside buildings, on power pylons or anywhere you don t have access to soil. With this test method, two clamps are placed around the earth ground rod or the connecting cable and each are connected to the tester. Earth ground stakes are not used at all. A known voltage is induced by one clamp, and the current is measured using the second clamp. The tester automatically determines the ground loop resistance at this ground rod. If there is only one path to ground, like at many residential situations, the Stakeless method will not provide an acceptable value and the Fall-of- Potential test method must be used. The Fluke 165 works on the principle that in parallel/multi-grounded systems, the net resistance of all ground paths will be extremely low as compared to any single path (the one under test). So, the net resistance of all the parallel return path resistances is effectively zero. Stakeless measurement only measures individual ground rod resistances in parallel to earth grounding systems. If the ground system is not parallel to earth then you will either have an open circuit, or be measuring ground loop resistance. EI-16X Setup for the stakeless method using the 165. >10 cm (4 in) 10
11 START Earth/Ground Resistance 300 kω 300 kω ES S DC Low Resistance 3 kω Ground impedance measurements When attempting to calculate possible short circuit currents in power plants and other high voltage/current situations, determining the complex grounding impedance is important since the impedance will be made up of inductive and capacitive elements. Because inductivity and resistivity are known in most cases, actual impedance can be determined using a complex computation. Since impedance is frequency dependent, the Fluke 165 uses a 55 Hz signal for this calculation to be as close to voltage operating frequency as possible. This ensures that the measurement is close to the value at the true operating frequency. Using this feature of the Fluke 165, accurate direct measurement of grounding impedance is possible. Power utilities technicians, testing high voltage transmission lines, are interested in two things. The ground resistance in case of a lightning strike, and the impedance of the entire system in case of a short circuit on a specific point in the line. Short circuit in this case, means an active wire breaks loose and touches the metal grid of a tower. Two-pole ground resistance In situations where the driving of ground stakes is neither practical nor possible, the Fluke 163 and 165 testers give you the ability to do two-pole ground resistance/ continuity measurements, as shown below. To perform this test, the technician must have access to a good, known ground such as an all metal water pipe. The water pipe should be extensive enough and be metallic throughout without any insulating couplings or flanges. Unlike many testers, the Fluke 163 and 165 perform the test with a relatively high current (short circuit current > 50 ma) ensuring stable results. 165 ADVANCED EARTH / GROUND ER GEO ST H/C S/P Equivalent circuit for two-point measurement. 11
12 Measuring Ground Resistance MGN Building steel The layout of a typical central office. MGB At central offices Ground field Water pipe When conducting a grounding audit of a central office there are three different measurements required. Before testing, locate the MGB (Master Ground Bar) within the central office to determine the type of grounding system that exists. As shown on this page, the MGB will have ground leads connecting to the: MGN (Multi-Grounded Neutral) or incoming service, ground field, water pipe, and structural or building steel First, perform the Stakeless test on all the individual grounds coming off of the MGB. The purpose is to ensure that all the grounds are connected, especially the MGN. It is important to note that you are not measuring the individual resistance, rather the loop resistance of what you are clamped around. As shown in Figure 1, connect the Fluke 165 or 163 and both the inducing and sensing clamps, which are placed around each connection to measure the loop resistance of the MGN, the ground field, the water pipe, and the building steel. Second, perform the 3-pole fall-of-potential test of the entire ground system, connecting to the MGB as illustrated on in Figure. To get to remote earth, many phone companies utilize unused cable pairs going out as much as a mile. Record the measurement and repeat this test at least annually. Third, measure the individual resistances of the ground system using the Selective test of the Fluke 165 or 163. Connect the Fluke tester, as shown in Figure 3. Measure the resistance of the MGN; the value is the resistance of that particular leg of the MGB. Then measure the ground field. This reading is the actual resistance value of the central office ground field. Now move on to the water pipe, and then repeat for the resistance of the building steel. You can easily verify the accuracy of these measurements through Ohm s Law. The resistance of the individual legs, when calculated, should equal the resistance of the entire system given (allow for reasonable error since all ground elements may not be measured). These test methods provide the most accurate measure of a central office, because it gives you the individual resistances and their actual behavior in a ground system. Although accurate, the measurements would not show how the system behaves as a network, because in the event of a lightning strike or fault current, everything is connected. 1
13 EI-16X EI-16X EI-16X START 165 ADVANCED EARTH / GROUND ER GEO E S H Earth/Ground Resistance 300 kω 300 kω DC Low Resistance 3 kω START H/C S/P 165 ADVANCED EARTH / GROUND ER GEO E S H Earth/Ground Resistance 300 kω 300 kω DC Low Resistance 3 kω START 165 ADVANCED EARTH / GROUND ER GEO E S H Earth/Ground Resistance 300 kω 300 kω DC Low Resistance 3 kω INDUCING CURRENT EI-16 H/C S/P H/C S/P EI-16X INDUCING CURRENT To prove this, you need to perform a few additional tests on individual resistances. First, perform the 3-pole fall-of-potential test on each leg off the MGB and record each measurement. Using Ohm s Law again, these measurements should be equal to the resistance of the entire system. From the calculations you will see that you are from 0 % to 30 % off the total R E value. Finally, measure the resistances of the various legs of the MGB using the selective stakeless method. It works like the stakeless method, but it differs in the way we use the two separate clamps. We place the inducing voltage clamp around the cable going to the MGB, and since the MGB is connected to the incoming power, which is parallel to the earth system, we have achieved that requirement. Take the sensing clamp and place it around the ground cable leading out to the ground field. When we measure the resistance, this is the actual resistance of the ground field, plus the parallel path of the MGB. And because it should be very low ohmically, it should have no real effect on the measured reading. This process can be repeated for the other legs of the ground bar i.e. water pipe and structural steel. To measure the MGB via the stakeless selective method, place the inducing voltage clamp around the line to the water pipe (since the copper water pipe should have very low resistance) and your reading will be the resistance for only the MGN. MGN Figure 1: Stakeless testing of a central office. MGB MGN EI-16 MGB Figure : Perform the 3-Pole Fall-of-Potential test of the entire ground system. Figure 3: Measure the individual resistances of the ground system using the Selective test. MGB MGN 13
14 More Ground Resistance Applications A typical setup at a cellular tower installation. MGN Application sites There are four other particular applications where you can use the Fluke 165 to measure the capability of the earth ground system. Cellular sites/microwave and radio towers MGB At most locations there is a 4-legged tower with each leg individually grounded. These grounds are then connected with a copper cable. Next to the tower is the Cell site building, housing all the transmission equipment. Inside the building there is a halo ground and a MGB, with the halo ground connected to the MGB. The cell site building is grounded at all 4 corners connected to the MGB via a copper cable and the 4 corners are also interconnected via copper wire. There is also a connection between the building ground ring and the tower ground ring. Electrical substations A substation is a subsidiary station on a transmission and distribution system where voltage is normally transformed from a high value to low value. A typical substation will contain line termination structures, high-voltage switchgear, one or more power transformers, low-voltage switchgear, surge protection, controls, and metering. Remote switching sites Remote switching sites also known as slick sites, where digital line concentrators and other telecommunications equipment is operating. The remote site is typically grounded at either end of the cabinet and then will have a series of ground stakes around the cabinet connected by copper wire. Lightning protection at commercial/ industrial sites Most lightning fault current protection systems follow the design of having all four corners of the building grounded and these are usually connected via a copper cable. Depending on the size of the building and the resistance value that it was designed to achieve, the number of ground rods will vary. Recommended tests End users are required to perform the same three tests at each application: stakeless measurement, 3-pole fall-of-potential measurement and selective measurement. Stakeless measurement First, perform a Stakeless measurement on: The individual legs of the tower and the four corners of the building (cell sites/towers) All grounding connections (electrical substations) The lines running to the remote site (remote switching) The ground stakes of the building (lightning protection) 14
15 EI-16X START EI-16 START 165 ADVANCED EARTH / GROUND ER GEO EI-16X E S H Earth/Ground Resistance 300 kω 300 kω DC Low Resistance 3 kω 165 ADVANCED EARTH / GROUND ER GEO Earth/Ground Resistance 300 kω 300 kω E ES S H DC Low Resistance 3 kω H/C S/P H/C S/P EI-16X For all applications, this is not a true ground resistance measurement because of the network ground. This is mainly a continuity test to verify that the site is grounded, that we have an electrical connection, and that the system can pass current. 3-pole fall-of-potential measurement Second, we measure the resistance of the entire system via the 3-pole Fall-of-Potential method. Keep in mind the rules for stake setting. This measurement should be recorded and measurements should take place at least twice per year. This measurement is the resistance value for the entire site. Selective measurement Lastly, we measure the individual grounds with the Selective test. This will verify the integrity of the individual grounds, their connections, and determine whether the grounding potential is fairly uniform throughout. If any of the measurements show a greater degree of variability than the other ones, the reason for this should be determined. The resistances should be measured on: Each leg of the tower and all four corners of the building (cell sites/towers) Individual ground rods and their connections (electrical substations) Both ends of the remote site (remote switching) All four corners of the building (lightning protection) INDUCING CURRENT A typical setup at an electrical substation. Using Stakeless testing at a remote switching site. Using Selective testing on a lightning protection system. 15
16 Earth Ground Products Fluke 165 Advanced GEO Earth Ground Tester Fluke 163 Basic GEO Earth Ground Tester The most complete tester The Fluke 163 and 165 are distinctive earth ground testers that can perform all four types of earth ground measurement: 3-and 4-pole fall-of-potential (using stakes) 4-pole soil resistivity testing (using stakes) Selective testing (using 1 clamp and stakes) Stakeless testing (using clamps only) The complete model kit comes with the Fluke 163 or 165 tester, a set of two leads, 4 earth ground stakes, 3 cable reels with wire, clamps, batteries and manual all inside a rugged Fluke carrying case. Fluke 165 advanced features Advanced features of the Fluke 165 include: Automatic Frequency Control (AFC) identifies existing interference and chooses a measurement frequency to minimize its effect, providing more accurate earth ground values R* Measurement calculates earth ground impedance with 55 Hz to more accurately reflect the earth ground resistance that a fault-to-earth ground would see Adjustable Limits for quicker testing Optional Accessories 30 mm (1.7 in) Split Core Transformer for performing Selective testing on individual legs of towers. For more information go to The complete kit Fluke. Keeping your world up and running. Fluke Corporation PO Box 9090, Everett, WA USA 9806 Fluke Europe B.V. PO Box 1186, 560 BD Eindhoven, The Netherlands For more information call: In the U.S.A. (800) or Fax (45) In Europe/M-East/Africa +31 (0) or Fax +31 (0) In Canada (800)-36-FLUKE or Fax (905) From other countries +1 (45) or Fax +1 (45) Web access: Fluke Corporation. All rights reserved. Printed in U.S.A. 6/ B-EN-N Rev A
12 Appendix 12 Earth Electrodes And Earth Electrode
12 Appendix 12 Earth Electrodes And Earth Electrode Testing 12.1 Introduction This appendix provides guidance and background information an earth electrode testing and some limited information on earth
Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria
Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria Abstract Gabriel A. Adegboyega and Kehinde O. Odeyemi Department of Electrical and Electronic
Video Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
GroundRod AC Substation Earthing Tutorial
1 GroundRod AC Substation Earthing Tutorial 1. Functions of an earthing system The two primary functions of a safe earthing system are: To ensure that a person who is in the vicinity of earthed facilities
Grounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
DET3 Contractor Series 3-Terminal Earth/Ground Resistance Testers
99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com DET3 Contractor Series 3-Terminal DET3 Contractor Series 2 and 3 point testing
UNDERSTANDING GROUND RESISTANCE TESTING. Soil Resistivity. Ground Resistance. 3-Point Measurements. 4-Point Measurements. Clamp-on Measurements E I
UNDERSTANDING GROUND RESISTANCE TESTING Current supply E I Ammeter (I) Voltimeter (E) X Auxiliary potential electrode Y Auxiliary current electrode Z Rx R1 R2 Rn-1 Rn Ground rod and clamp Contact resistance
Multi-Function Ground
Multi-Function Ground Resistance SOIL RESISTIVITY TEster Model 6470-B Now measure ground resistance, soil resistivity and bonding resistance with one instrument! 2- and 4-Wire Bond Resistance/Continuity
Understanding Soil Resistivity Testing
Technical Hotline: (00) -9 Technical Hotline: (00) -9 www.aemc.com www.aemc.com Understanding Testing Effects of on Ground Electrode Resistance Factors Affecting APPLICATION NOTES JULY rev.0 Understanding
Substation Grounding Study Specification
Substation Grounding Study Specification Introduction A grounding study is required for name of station, a / / kv substation located in name of location and connected to the following circuits: number
EARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
SOIL RESISTIVITY MEASUREMENTS
SOIL RESISTIVITY MEASUREMENTS APPENDIX B B Soil resistivity directly affects the design of a grounding (earthing) electrode system and is the prime factor that determines the resistance to earth of a grounding
Grounding & Bonding Why it is done And How to Install Properly
Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.
Digital Ground Resistance Tester. Models 4620 & 4630. Digital Ground Resistance Tester
Digital Ground Resistance Tester Models 4620 & 4630 Digital Ground Resistance Tester Models 4620 and 4630 perform both ground resistance and soil resistivity tests. These testers measure from 0 to 2000Ω,
Chapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
DET3 and 4 Contractor Series Earth/Ground Resistance Testers
DET3 and 4 Contractor Series 2, 3 and 4 point testing ART (Attached Rod Technique) testing capability and stakeless testing technique Choice of digital or analog display Warning indicators prevent test
1587/1577. Insulation Multimeters. Technical Data. Two powerful tools in one.
1587/1577 Insulation Multimeters Technical Data Two powerful tools in one. The Fluke 1587 and 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true-rms digital multimeter
DET3 Contractor Series
DET3 Contractor Series 3-Terminal 2 and 3 point testing ART (Attached Rod Technique) testing capability User selectable test voltage (25/50 V) Choice of digital or analog display Warning indicators prevent
CONSTRUCTION STANDARD ELECTRIC OPERATIONS ORGANIZATION
Page 1 of 11 ****This Standard Supercedes BECo CS2.13-2.3 & ComElectric OH Construction Manual, System Grounding Section, drawings CGND, GRDSUM, and C2**** 1.0 Bill of Materials GROUNDING AND BONDING POLE-MOUNTED
A practical guide to earth resistance testing WWW.MEGGER.COM
A practical guide to earth resistance testing WWW.MEGGER.COM The word Megger is a registered trademark Introduction Nothing is quite so common or abundantly available throughout the world as the earth
Multimeter measurements on variable frequency drives using the new Fluke 289 DMM
Multimeter measurements on variable frequency drives using the new Fluke 289 DMM Application Note Editor s note: For similar instructions using the Fluke 87V DMM, reference Fluke article 12345. In the
Best Methods for Safe Hipot Testing
Best Methods for Safe Hipot Testing When working with electrical safety test equipment, instruments that output potentially dangerous voltages and currents, it is always important to regular review and
EARTHING SYSTEM CALCULATION
BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references
Electrical Fundamentals Module 3: Parallel Circuits
Electrical Fundamentals Module 3: Parallel Circuits PREPARED BY IAT Curriculum Unit August 2008 Institute of Applied Technology, 2008 ATE310- Electrical Fundamentals 2 Module 3 Parallel Circuits Module
6/14/02 Chapter 14: Use of Electrical Test Equipment 1/20
USE OF ELECTRICAL TEST EQUIPMENT Test equipment is necessary for determining proper set-up, adjustment, operation, and maintenance of electrical systems and control panels. The following is a general procedure
13 common causes of motor failure
13 common causes of motor failure Application Note What to look for and how to improve asset uptime Motors are used everywhere in industrial environments and they are becoming increasingly complex and
David Brender Copper Development Association Inc. [email protected]. Miramar, March 8, 2013
Grounding and Bonding in Communications Systems David Brender Copper Development Association Inc. [email protected] Ennes Workshop Miramar, March 8, 2013 MMXIII This talk concentrates on:
LocoNet, the Digitrax Difference
LocoNet, the Digitrax Difference LocoNet is Digitrax's method of communication between LocoNet compatible devices on a model railroad layout. LocoNet Compatible devices are designed to work together on
Coupling Effect in Substation Ground Measurements
SERBIAN JOURNAL OF ELECTRICAL ENGINEERING Vol. 9, No. 3, October 2012, 315-324 UDK: 621.316.13.011.2 DOI: 10.2298/SJEE1203315F Coupling Effect in Substation Ground Measurements Alex Farber 1, Boris Katz
Introduction to Data Centre Design
Introduction to Data Centre Design Barry Elliott BSc RCDD MBA CEng Earthing, grounding and bonding November 09 Earthing what s the point Safety from electrical hazards Reliable signal reference within
Strength and Durability for Life CORROSION CONTROL. The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines
Strength and Durability for Life CORROSION CONTROL The Effect of Overhead AC Power Lines Paralleling Ductile Iron Pipelines Last Revised: May 2016 Sharing of rights-of-way by AC power lines and buried
Insulation resistance testing. A complete solution for every person.
Insulation resistance testing. A complete solution for every person. Insulation resistance. The latest test tools from the testing experts. You asked. We responded. Now you have more insulation testing
270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer
CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE
CHAPTER VIII LINE PLANT SYSTEM COMMUNICATION THROUGH RE CABLE 8.1 SYSTEM 8.1.1 Armoured, screened underground cables are used for control communication in electrified areas to limit induction effect. 8.2
Lightning Protection Introduction
Lightning Protection Introduction Structural lightning protection design considerations BS 6651 (Protection of structures against lightning) clearly advises strict adherence to the provision of a conventional
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
10 Multimeter. Users Manual
10 Multimeter Users Manual 1991-2001 Fluke Corporation, All rights reserved. Printed in USA All product names are trademarks of their respective companies. 10 MULTIMETER m m Mk SELECT RANGE OFF VDC VAC
The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.
i800 AC Current Clamp Instruction Sheet Introduction The i800 AC Current Clamp, the Clamp, has been designed for use with multimeters, recorders, power analyzers, safety testers, etc., for accurate non-intrusive
Section B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13
Interfacing electrification and system reliability Roger White Professional Head of Electrification and Plant Rail Abstract Integration is the term given to ensuring that the different elements of an electrified
Who sets the rules for electrical testing and safety?
Who sets the rules for electrical testing and safety? Application Note Alphabet soup There s no question that electrical safety is a key concern for electricians and engineers, their employers, unions
Specifications for Lightning Protection. ASAE Engineering Practice
Chapter 8: Lightning Specifications for Lightning Protection ASAE safety standards are not laws. They are recommended voluntary standards used by designers, engineers, manufacturers and users of the equipment,
INTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 62305-3 Edition 2.0 2010-12 colour inside Protection against lightning Part 3: Physical damage to structures and life hazard INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE
The Do s and Don ts of Pressure Transducers
The Do s and Don ts of Pressure Transducers ABSTRACT When specifying a pressure transducer for a process measurement, a number of items have to be considered. Some of the more important ones are discussed
Electrical Safety Tester Verification
Ensuring Validity of Regulatory Tests Verification of electrical safety testing equipment is a procedure that is often overlooked by manufacturers. Running test verification is crucial to ensuring that
i410/i1010 AC/DC Current Clamp
/i1010 AC/DC Current Clamp Instruction Sheet Safety Information XW Read First: Safety Information To ensure safe operation and service of the current clamp, follow these instructions: Read all operating
Are you aware. Outline
Electrical Safety of Medical Equipment Hasan Al-Nashash School of Engineering American University of Sharjah (AUS) 1 Are you aware Electrocutions are the 5th leading cause of accidental death in the U.S.
MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.
MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question. 1) If the voltage at a point in space is zero, then the electric field must be A) zero. B) positive.
How Much Voltage Drop Is Acceptable?
How Much Voltage Drop Is Acceptable? Article supplied by Ideal The National Electrical Code (NEC) recommends that the combined voltage drop of the electrical system (branch circuit and feeders) not exceed
Fluke 1650B Series Multifunction Installation Testers
Fluke 1650B Series Multifunction Installation Testers Extended Specifications The installation testing solution for demanding environments The Fluke 1650B Series testers, with new advanced features, are
Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc.
Grounding Practice at Data and Communications Centers David Brender, P.E., CPQ National Program Manager Copper Development Association Inc. Overview of This Presentation Elements of building wiring and
User Guide. www.burntec.com. 4 wire Earth Resistance Tester Model GRT300
User Guide 4 wire Earth Resistance Tester Model GRT300 Introduction Congratulations on your purchase of Extech s 4 Wire Earth Resistance Tester. The Model GRT300 has been designed and tested according
K Standard Grade Ni-Cr vs Ni-Al (Chromel vs Alumel)
SureGrip TM 80PK-24 Air Temperature Probe Instruction Sheet XWWarning To avoid electrical shock, do not use this probe when voltages exceeding 24 V ac rms or 60 V dc are present. The probe tip is electronically
Ground Resistance Clamp On Tester
USER MANUAL Ground Resistance Clamp On Tester MODEL 382357 Introduction Congratulations on your purchase of Extech s 382357 Ground Resistance Tester. This Clamp on device allows the user to measure ground
Lab E1: Introduction to Circuits
E1.1 Lab E1: Introduction to Circuits The purpose of the this lab is to introduce you to some basic instrumentation used in electrical circuits. You will learn to use a DC power supply, a digital multimeter
Designing For A Low Resistance Earth Interface (Grounding) Roy B. Carpenter, Jr. Joseph A. Lanzoni
Designing For A Low Resistance Earth Interface (Grounding) Roy B. Carpenter, Jr. Joseph A. Lanzoni An LEC Publication Revised 2007 TM DESIGNING FOR A LOW RESISTANCE EARTH INTERFACE (GROUNDING) Roy B. Carpenter,
Operating Instructions
VMD202 Vehicle Motion Detector Operating Instructions CAUTIONS AND WARNINGS Never use the VMD202 as a safety reversing or presence detection system. The VMD202 requires that a vehicle be moving for detection.
Grounding Demystified
Grounding Demystified 3-1 Importance Of Grounding Techniques 45 40 35 30 25 20 15 10 5 0 Grounding 42% Case 22% Cable 18% Percent Used Filter 12% PCB 6% Grounding 42% Case Shield 22% Cable Shielding 18%
Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW
Complete One Stop Solution for OPGW Cable and Fittings for OPGW 53, Justice Chandra Madhav Road, Kolkata - 700020. India. Phone: 91-33-24748575 / 7565 Fax: 91-33-2476-1955 Email: [email protected] Website:
Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12
Table of Contents The Basics of Electricity 2 Using a Digital Multimeter 4 IDEAL Digital Multimeters An Introduction The Basics of Digital Multimeters is designed to give you a fundamental knowledge of
ACL 395 Resistivity Meter
ACL 395 Resistivity Meter OPERATION MANUAL Meter is warranted for one year from the date of purchase on parts and labor. Calibration is recommended every 12 months. 840 W. 49 th Place Page 1 of 13 [email protected]
CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS
CUSTOMER REQUIREMENTS AT POWER SUBSTATIONS Customer Handout Date Aug 2, 2010 Version 1.0 File Name Customer Requirements At Power Substations Document Id Outside Plant Engineering 1 Table Of Contents 1.0
Essential Electrical Concepts
Essential Electrical Concepts Introduction Modern vehicles incorporate many electrical and electronic components and systems: Audio Lights Navigation Engine control Transmission control Braking and traction
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
AC-DC Converter Application Guidelines
AC-DC Converter Application Guidelines 1. Foreword The following guidelines should be carefully read prior to converter use. Improper use may result in the risk of electric shock, damaging the converter,
Electrical safety requirements in DC distribution systems
Electrical safety requirements in DC distribution systems PAUL J.L.AN TICHELEN, DOMINIQUE WEYEN ITO Boeretang 200, 2400 Mol BELGIUM Abstract: This paper focuses on the safety requirements for the DC bus
White Paper: Electrical Ground Rules
Acromag, Incorporated 30765 S Wixom Rd, Wixom, MI 48393 USA Tel: 248-295-0880 Fax: 248-624-9234 www.acromag.com White Paper: Electrical Ground Rules Best Practices for Grounding Your Electrical Equipment
Dielectric Withstand Testing in a Production Environment
Dielectric Withstand Testing in a Production Environment Performing a routine product safety test should not in itself represent a shock hazard to the operator who is conducting the test, yet anytime you
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
MYTHBUSTING Takes on Shielded Cabling
MYTHBUSTING Takes on Shielded Cabling Herb Congdon Brian Davis Objectives Take on myths of shielded cabling and use modern-day science to show what's real and what's fiction - through trial and error actually
CCTV System Troubleshooting Guide
Wouldn t be nice to start and finish a CCTV System Project without running into any problems before, during and after the installation is completed. Well, in this article we will try and explain why we
800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
V=5 L 3 GROUNDING ELECTRODES EXPLAINED
GROUNDING ELECTRODES EXPLAINED In the last few decades, much has been ascertained about the interaction between the grounding electrode and the earth, which is a three-dimensional electrical circuit. Ultimately,
Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers
9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product
Insulation Resistance Testing of Low Voltage Cables in the Field
Insulation Resistance Testing of Low Voltage Cables in the Field Table of Contents 1. Background...3 1.1. Before Making Measurements...3 1.2. How to Apply the Temperature Correction Factor...4 1.2.1. Calculation...4
Security Cameras, CATV, GPS & Satellite Protection. White Paper
Security Cameras, CATV, GPS & Satellite Protection White Paper Security Cameras, CATV, GPS & Satellite Protection Surge Protection Solutions for PTC 1 Security Cameras, CATV, GPS & Satellite Protection
Complete Solar Photovoltaics Steven Magee. Health and Safety
Health and Safety Health and safety around solar photovoltaic systems is very important. In the DC circuit you will find up to 600 volts in residential and commercial systems. In utility systems you may
A Practical Guide to Dielectric Testing
Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Stand Alone POTS Fiber Optic System. P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit. Description & Installation
Stand Alone POTS Fiber Optic System P31372 Station (Subscriber) Unit P31379 Remote (Exchanger) Unit Description & Installation Printed in USA 09/11 TO466 Rev. A Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC
Manual Ranging MultiMeter
Owner s Manual Manual Ranging MultiMeter Model 82345 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product.! Safety! Operation! Maintenance!
Single-Phase AC Synchronous Generator
ST Series Single-Phase AC Synchronous Generator Instructions for Operation and Maintenance English to English translation by R.G. Keen, May 2004. ST Series of Single-Phase AC Synchronous Generators Description
Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards
Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry
Interference in the ECG and its elimination
Interference in the ECG and its elimination General points The signal voltages in ECG recording are known to be very small and are in the millivolt range, i.e. they have amplitudes of only a few thousands
AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
CODE OF PRACTICE FOR EARTHING AND BONDING SYSTEM FOR SIGNALLING EQUIPMENTS SPECIFICATION NO. RDSO/SPN/197/2008 SIGNAL DIRECTORATE
CODE OF PRACTICE FOR EARTHING AND BONDING SYSTEM FOR SIGNALLING EQUIPMENTS SPECIFICATION NO. RDSO/SPN/197/2008 SIGNAL DIRECTORATE RESEARCH, DESIGNS & STANDARDS ORGANISATION LUCKNOW - 226011 1 CODE OF PRACTICE
SECTION 22 LIGHTNING PROTECTION SYSTEM
SECTION 22 LIGHTNING PROTECTION SYSTEM 22.01 SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for
This presentation to be used in conjunction with:
1 This presentation to be used in conjunction with: Spec Sheets: SA-GRSP10, SA-GRSP09, SA-GRSP11 Samples in DC-GROUND-KIT 8/16/2012 2 Network Bonding and Grounding: TIA-607-B Generic Telecommunications
STREETLIGHT SYSTEM GROUNDING AND BONDING
Page: 1 of 8 STREETLIGHT SYSTEM GROUNDING AND BONDING 1. Scope This Construction Standard covers the grounding and bonding requirements for single phase streetlight systems served by the Looped Radial
PS-6.2 Explain the factors that determine potential and kinetic energy and the transformation of one to the other.
PS-6.1 Explain how the law of conservation of energy applies to the transformation of various forms of energy (including mechanical energy, electrical energy, chemical energy, light energy, sound energy,
1. The diagram below represents magnetic lines of force within a region of space.
1. The diagram below represents magnetic lines of force within a region of space. 4. In which diagram below is the magnetic flux density at point P greatest? (1) (3) (2) (4) The magnetic field is strongest
Ground Resistance Clamp-On Tester
User s Manual Ground Resistance Clamp-On Tester MODEL 382357 Warranty EXTECH INSTRUMENTS CORPORATION (a FLIR company) warrants the basic instrument to be free of defects in parts and workmanship for one
STUDY GUIDE: ELECTRICITY AND MAGNETISM
319 S. Naperville Road Wheaton, IL 60187 www.questionsgalore.net Phone: (630) 580-5735 E-Mail: [email protected] Fax: (630) 580-5765 STUDY GUIDE: ELECTRICITY AND MAGNETISM An atom is made of three
Loop Calibration and Maintenance
Loop Calibration and Maintenance Application Note Introduction Process instrumentation requires periodic calibration and maintenance to ensure that it is operating correctly. This application note contains
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1
ABCs of DMMs Multimeter features and functions explained Application Note
ABCs of DMMs Multimeter features and functions explained Application Note Digital multimeters offer a wide selection of features. Choosing the right meter for the job can be challenging unless you know
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
November 2014. Stray Voltage Test Procedure for Electrical Contractors
Stray Voltage Test Procedure for Electrical Contractors 1 LIMITATION OF LIABILITY AND DISCLAIMER Any person who uses, relies on, or otherwise deals with this document and the information herein, does so