SECTION 22 LIGHTNING PROTECTION SYSTEM
|
|
|
- Hugo Shelton
- 9 years ago
- Views:
Transcription
1 SECTION 22 LIGHTNING PROTECTION SYSTEM SCOPE: A. These Specifications shall form a part of the Contract Documents and shall govern construction work for all buildings to be built or modified for the Board of Water and Sewer Commissioners of the City of Mobile, Alabama. The work covered by this section includes the furnishings of all parts, labor, equipment, appliances and materials and performing all operations in connection with the installation of lightning protection hardware. This shall include lightning rods that are bonded to ground rods. B. All new construction of buildings or revisions to existing building shall include lightning protection. This shall apply to the following types of architecture: 1. Brick with Composition roof 2. Brick with Metal roof 3. Metal Clad 4. Metal frame with fiberglass siding 5. Concrete with metal framing 6. Steel Structures 7. Flat roofs 8. Sloped roofs C. The Contractor for the installation of lightning protection equipment shall follow these Specifications, the Underwriters Laboratories UL 96 Standards for Safety, Lightning Protection Components, UL 96A and the National Fire Protection Agency 780 Standards for the Installation of Lightning Protection Systems. D. There shall be one common ground established for each building at or near the power source entering the building. The lightning protection system air terminals, electrical system, telephone, antennas, computers, remote telemetry, and radios shall have their grounds bonded together at this common ground SUMMARY: A. The scope of work is to provide and install an effective, aesthetically acceptable lightning protection system employing the latest technology. Page 1 of 7
2 B. The purpose of the system shall be to provide a Faraday cage of protection around the structure, and a path to ground for all lightning protection hardware. This shall include: 1. Air terminals to intercept the lightning strikes. 2. Down conductors to carry lightning from the air terminals to the ground. 3. Ground rods to pass the lightning current into earth ground. C. The system shall require no external power, shall not contain radioactive components, and shall require no scheduled maintenance. D. The installation of equipment shall all be done as per NFPA 780, and UL96A DESCRIPTION OF WORK: A. All new construction or revisions to buildings for the Board of Water and Sewer Commissioners of the City of Mobile, Alabama shall include lightning protection. Contractor shall provide equipment that is UL approved, and install lightning protection equipment on all buildings and structures. This shall include bonding, grounding, and the installation of lightning rods as described in Section 22 of the Specification. Contractor shall also include the installation of surge suppressors as specified in Section 23 entitled Transient Voltage Surge Suppressors B. All construction for lightning protection shall conform to Section 24 entitled Electrical Materials and Methods SUBMITTALS: A. Shop Drawings: Submit the type, size, and location of all equipment, grounds, and conductor routing to be furnished by the system supplier. B. Manufacturer s catalog data sheets for all components. C. Any departure from the submittal drawings as deemed necessary by the Contractor shall have all details of such departures and reasons therefore submitted as soon as practicable to the Owner for approval. No such departures shall be used in construction without the prior approval of the Engineer MANUFACTURER REQUIREMENTS: A. The manufacturer of the products employed in the system shall be regularly engaged and experienced in the design and manufacture of lightning protection products and systems, and have proof of successfully installed lightning protection system performance. B. Product and technical support shall be provided by the manufacturer or its authorized representative. Page 2 of 7
3 22.06 INSTALLER REQUIREMENTS: A. All installations must be performed by an experienced Underwriters Laboratories Master Label Installer. B. The installer shall carry appropriate liability and vehicle insurance in the minimum amount of one million dollars and worker s compensation insurance in at least the minimum amount required by law. Certificates of insurance shall be provided as requested to the Owner or his representative before work is begun. C. The installer shall be responsible for accompanying the Owner or his representative on a walk through each structure as the installation on that structure is completed, and on a walk through of each facility after completion of the project. D. The installation shall be done in a manner that will allow the Owner to obtain an Underwriters Laboratories Master Label for each site upon completion of the installation of the system GENERAL: A. The system shall be designed for installation to provide a Faraday Cage to delay or dissipate the formation of lightning strikes. B. The system shall be designed in such a manner that it affords protection to the structure upon which it is installed in the event a direct lightning strike to the structure does occur. C. The system shall require no external power and shall require no extraordinary maintenance. D. The system shall not be mounted in such a manner as to impose limitations which may interfere with utility use of structure space or otherwise preclude or limit the intended use of the structure or equipment within the structure, around the perimeter, or on top of the structure. E. The system shall be designed to impose minimum weight and low wind loading burden on the structure upon which it is installed. F. The lightning protection system shall be grounded at intervals not to exceed one hundred feet, and at no less than two points, around the perimeter of each structure. In the event a separate grounding system is provided on the structure, the lightning protection system shall be additionally bonded to that grounding system. This ground shall qualify as a lightning protection system ground. All connections for wires at the ground rod shall be CAD welded as per 4014 of NFPA 780. G. If installed on a metallic or otherwise electrically conductive structure, the system shall be electrically bonded to structure upon which it is installed through its mounting clamps and brackets, with additional bonding jumpers to grounded objects or structural members, as required. Page 3 of 7
4 H. Individual air terminals shall be mounted on all outside corners of each structure, around the perimeter of each structure at intervals not to exceed twenty feet, and on the interior of each structure in such a manner that no two air terminals are separated by a distance of more than fifty feet. In the event this is not practical, such as on a large open tank, air terminal spacing around the perimeter shall be decreased to not more than fifty feet, with a total number around the perimeter not less than the total of the normally required perimeter air terminals, plus the additional number of air terminals normally required on the interior of the structure. I. Each air terminal shall be provided with two contiguous, electrically conductive paths to ground. A short, single path jumper between the air terminal and the main conductor system may be employed. J. All equipment that protrudes above the roof line of a building must have its own air terminals that are properly bonded to the ground rods for that building. This shall include air conditioners, air handlers, vents, air conditioning ducts, aerators mixer motors, relief valves and control houses such as for filter galleries. Air terminals shall extend into the air and be at least 18 higher than the equipment. K. On structures with handrails, exposed structural members, or other conductors exposed or hidden, it is permissible to employ those conductors as part of the lightning protection system, provided they meet the minimum requirements for conductors listed in Underwriters Laboratories UL 96 or 96A. L. In the case of a structure or a portion of the structure where the structure itself is electrically conductive, such as a light pole, tower, steel superstructure, etc., that structure or portion of the structure itself may be employed as part of the lightning protection system, provided it meets the minimum requirements of UL 96 or UL 96A, and dedicated conductors are specifically not required on such structures. In such cases contractor shall ensure complete continuity exists between all metal parts that will be used as a pathway to ground. On steel towers that are subject to corrode or rust, such as those used to support radio antennas, a separate wire shall be installed from the lightning rod to the ground rod. M. Use of metal downspouts for conductors between the air terminals and ground rods shall not be allowed. N. On buildings with painted metal roofs, the roofing material itself may be used as a conductor, if it is at least 3/16 thick, but air terminals shall still be required. Installer shall confirm that there is continuous continuity between metal roofing panels or install individual wiring to bond panels together. O. All equipment shall be installed in accordance with Underwriters Laboratories UL 96A and NFPA 780 to the maximum extent practicable. Page 4 of 7
5 P. All equipment shall be installed in a neat, workmanlike manner in the most inconspicuous manner possible. Q. Dissimilar metals shall not be allowed to be in contact, except lightning rods. Aluminum fittings shall be mounted on aluminum where necessary, and bonded to the main system using bi metal connectors. Lead coating shall not be acceptable as a bi metal transition. R. Contractor shall adhere to minimum bending radiuses when routing wiring from the roof line to ground level. On buildings with an eave greater than 6, Contractor shall not bend wire around eaves. Contractor shall instead drill holes in the roof of the building eave and route wire down the side wall. Contractor shall be responsible for sealing all holes in the roof to be water tight upon completion of wiring. Vertical wires down side walls shall be installed in grey colored plastic conduit. S. The installer shall coordinate the lightning protection work to ensure a correct, neat, and unobtrusive installation. Care shall be taken to ensure that equipment to be protected is not obstructed or made inaccessible by the installation of the lightning protection equipment. T. Buildings with fiberglass or other non metallic material on the roof and sides are typically supported by steel. All pieces of steel must be bonded together with metal strapping or electrical wire as per NFPA 780 Standards. U. The installer shall coordinate his work in such a manner as to not interfere with the normal operation of the structure or facility upon which the installation is performed. V. All services to each structure upon which air terminals are installed shall be provided, to the maximum extent practicable, with a common connection (single point) at which they are grounded. Any metallic water or other service piping to the structure shall be electrically bonded to the lightning protection system. W. Upon completion of the installation, the Contractor shall furnish the Owner a certificate for each building stating the work and equipment meets U.L. standards, and that site is ready for the Owner to obtain an Underwriters Laboratories Master Label. X. Contractor is advised that there are power lines, water lines, sewer pipes, fiber optics, telephone lines, conduit, and instrument signal lines underground. Contractor shall contact the management before doing any trenching or digging to bury ground rods or cabling, or wiring. Site management shall have the option of telling Contractor that certain areas must be dug by hand only to protect the wiring and piping and thereby keep the equipment in operation. Y. Contractor must repair and/or replace any piping, power lines, fiber optics, or anything else that is damaged during the trenching, digging, or installation of any equipment or materials. Z. Locations with buildings for sewer lift stations and water booster pumps will typically have a radio for transmitting data back to a central location. These sites will include a pole mounted Page 5 of 7
6 antenna for the radios. Streamer delaying air terminal rods shall be installed on all poles or towers used for radio antennas. The lightning rod shall be installed in a manner that does not place it in the path of radio waves between that radio, and the radio it is sending data to. The lightning rod must be mounted with its elevation at least 2 taller than the antenna. The lightning rod should be mounted on a 2 Galvanized pipe, and then strapped to the pole. AA. AB. A lightning rod installed on a pole or tower to protect a radio antenna provides a zone of protection that extends outward and down at a 45 o angle from the top of the lightning rod. If there is a building adjacent to the antenna pole that is completely within the zone of protection provided by the antenna pole lightning rod, it is not necessary to install lightning rods on the building. This is typically true only where the antenna poles are very tall, and the adjacent structures are relatively small. An example of this would be a 50 pole adjacent to a one story building that was 12 wide and 12 long, and 10 high. Lightning protection for special structures shall be designed as per the NFPA 780 Standard for the installation of Lightning Protection Systems. This includes: 1. Floating Roof Tanks 2. Metallic 3. Fixed Roof Tanks AC. AD. Lightning protection for water towers shall include the installation of a ground rod at each leg of the tower. There shall be a number 4 wire buried 1 6 deep in a ring around the base of the tower. All ground rods shall be bonded together by cad welding this wire to each rod. Lightning protection for pump motors that are mounted outside shall be installed as follows: 1. Install a 2 pipe vertically beside the pump motor that will allow the mounting of an air terminal. Final height of lightning rod shall be 18 higher than pump motor, or piping attached to motor. Final location of pipe shall be approved by building supervisor. 2. Attach #4 base copper wire to motor casing. Bury wire 18 deep, and connect wire from lightning rod and motor casing to common ground for motor control center COMPONENTS: A. All equipment and components shall be of a design and of construction to suit the application for which it is used, in accordance with accepted industry standards. B. Each component which may be so listed shall be listed under Underwriters Laboratories UL 96, and have the appropriate UL label affixed thereto. C. All lightning rods shall be long enough to provide a height of 18 above the item it is to protect. Page 6 of 7
7 22.09 LIGHTNING RODS (AIR TERMINALS) FOR BUILDINGS: A. Buildings or Metal Structures 1. All air terminals for pump stations, water booster stations, and administration buildings, water plants, or sewer plants shall be streamer delaying dissipaters with 500 dissipation electrode wires of.0080 diameter 300 series stainless steel as manufactured by Lightning Master or equal. 2. Air terminal Electrode shall be high quality 316 stainless steel, ½ diameter. Air terminals shall be shipped to the installer ready to install, with no assembly or other setup required. 3. Air terminals over 24 inches high shall be supported at a point not less than one half of the height of the terminal. 4. All other components such as bonding clamps shall be U.L. labeled and approved. Clamps shall be bolted type. B. Acceptable Brands 1. Streamer delaying air terminals shall be manufactured by Lightning Master Corporation, 1920 Sherwood Street, Clearwater, FL USA Tel. (813) Fax (813) END OF SECTION Page 7 of 7
Specifications for Lightning Protection. ASAE Engineering Practice
Chapter 8: Lightning Specifications for Lightning Protection ASAE safety standards are not laws. They are recommended voluntary standards used by designers, engineers, manufacturers and users of the equipment,
HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE: 10.17.12
SECTION 27 05 26 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes grounding and bonding products, design requirements and installation for communications
Canopy Surge. User Manual
Canopy Surge Suppressor User Manual SS00-UM-en Issue 2 May 2003 2003 Motorola, Inc. All rights reserved. Printed in the U.S.A Notices Safety Precautions: Before beginning your installation, please read
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
Mobile Home Pre-Inspection Checklist
Mobile Home Pre-Inspection Checklist TWO (2) STEP INSPECTION PROCESS STEP ONE: CALL FOR THE FIRST INSPECTION WHEN THESE ITEMS ARE COMPLETE. 1. Septic tank installed and plumbing complete. (SEE PLUMBING
Video Camera Installation Guide
Video Camera Installation Guide The intent of this guide is to provide the information needed to complete or modify a video camera installation to avoid lightning and induced power surge damage. This guide
E-Version SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT
SECTION 15318 - CHLORINATION SYSTEM PART 1 - GENERAL 1.1. SCOPE OF WORK A. Under this item the Contractor shall furnish and install a sodium hypochlorite solution metering system complete with all accessories
800 Communications Circuits
ARTICLE 800 Communications Circuits INTRODUCTION TO ARTICLE 800 COMMUNICATIONS CIRCUITS This article has its roots in telephone technology. Consequently, it addresses telephone and related systems that
Requirements for the Attachment of Communication Cable Facilities on PPL Poles
Page 99 of 137 Requirements for the Attachment of Communication Cable Facilities on Replaces: URS-3002 URS-3004 URS-101C-304 A-157649 Page 100 of 137 Reference Notes for Drawings: General 1. The term communication
270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer
DEHN + SÖHNE. DEHNconductor System No Problems with Proximities
DEHN + SÖHNE DEHNconductor System No Problems with Proximities DEHNconductor System - New Possibilities for controling Proximities. For preventing dangerous flashovers among parts of external lightning
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements
16600 Underground Electrical Duct Bank This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications
IRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
Installation Guide (Typical) For Micro-Comm Radio Telemetry And Control Systems
Installation Guide (Typical) For Micro-Comm Radio Telemetry And Control Systems Project: Location: Micro-Comm Project Manager: NOTE: This Installation Guide is intended to be a Typical Installation reference
SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 27 05 36 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 GENERAL 1.01 DESCRIPTION A. The work covered by this section of the Specifications includes all labor necessary to perform and complete such
SECTION 15410 GROUND WATER STORAGE TANKS
SECTION 15410 GROUND WATER STORAGE TANKS PART 1 GENERAL.01 SCOPE A. Section Includes Requirements for designing, fabricating, and erecting a welded steel ground storage tank..02 SYSTEM DESCRIPTION A. Design
Grounding & Bonding Why it is done And How to Install Properly
Grounding & Bonding Why it is done And How to Install Properly The technical information provided herein is to assist qualifi ed persons in planning and installing electric service to farms and residences.
This mount uses concrete parking bumpers and a Davis tripod to create a mounting solution for nonpenetrable
NON-PENETRATING FLAT ROOF MOUNT Application Note 18 For Any Davis Weather Station Installed on a Mounting Tripod Introduction This application note describes various mounting solutions for non-penetrable
SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.
SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION 27 05 26 GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS
SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS RELATED SECTIONS: Section 27 00 00 General Requirements Section 27 02 00 Communication General Requirements Section 27 05 28 Pathways for Communications
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
SECTION 807 PUMP STATION REHABILITATION
SECTION 807 PUMP STATION REHABILITATION 807-1 DESCRIPTION: Rehabilitation of pump stations shall be defined as the cleaning, removal, repair and/or replacement of any and/or all components including but
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
SECTION 28 05 00 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY
SECTION 28 05 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specifications Sections, apply
SECTION 15140 - PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).
DIVISION 27 COMMUNICATIONS 27 00 00 COMMUNICATIONS A. System design shall be completed by a Registered Communications Distribution Designer (RCDD). B. Comply with American National Standards Institute
Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?
A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered
TS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING
TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET
ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS
Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document
GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables
Engineering Department SEPTEMBER, 2007 GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables General Requirements This section applies to all public and private utilities,
Consultants Handbook
Consultants Handbook CONSULTANTS HANDBOOK Welcome to our Wallis Designers Lightning Protection Handbook. This handbook offers a guide for any designers of the structural Lightning protection system to
Grounding Practice at Data and Communications Centers. David Brender, P.E., CPQ National Program Manager Copper Development Association Inc.
Grounding Practice at Data and Communications Centers David Brender, P.E., CPQ National Program Manager Copper Development Association Inc. Overview of This Presentation Elements of building wiring and
3. Contractor shall ensure that all permits are obtained prior to any construction. Contractor shall be responsible for all utility fees.
The following shall serve as the minimum requirements for contractors performing work in relation to the Authority s potable water and sanitary sewer system(s), appurtenances and service connections. General:
SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
4 Installation Requirements
4 Installation Requirements 9 4.1 Code Reference The authority having jurisdiction should be referenced to determine what law, ordinance or code shall apply in the use of flexible duct. Ducts conforming
Optical Cable Pre-Construction Survey. Keywords Stationary Reel Method, empty innerducts, sub-ducts, microducts, Intermediate-feed manholes
Optical Cable Pre-Construction Survey Author John Peters Issued December 2012 Abstract Pre-construction site survey is one of the most important steps in the engineering and placement of a new optical
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
Chapter 9. Bonding and Grounding
Chapter 9 Bonding and Grounding Objectives Describe why the cable should be bonded Describe bonding and grounding procedures Define Bonding and Grounding Explain Safety Benefits and intent of bonding and
Installation Guide. System Release 1.0
Installation Guide System Release 1.0 Safety and Installation Considerations Installing a Connectorized Radio Installing an Integrated Radio Antenna Installation Device LEDs Site Diagrams 2B Accuracy While
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers
9229 Waterford Centre Dr. Bldg C, Suite 110 Austin, Tx 78758 Application Bulletin 103 - NEC Reference Guide for SolarBridge-Enabled AC Module Installers Current Version: 13 AC Modules are a new product
16 2 10.3 Materials and Colors
16 2 10.3 Materials and Colors To create a harmonious and coherent image for each development, building designs shall pay close attention to choice of materials and colors. Building construction shall
UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-27 05 14.00 10 (April 2006) -------------------------------- Preparing Activity: USACE Superseding UFGS-27 05 14.00 10 (April 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS
LOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete.
LOADING DOCK EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Loading dock equipment of the following types: 1. Dock lifts. 2. Control stations. 1.2 RELATED SECTIONS A. Section 03100 - Concrete Forms and
SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
2. What building projects are exempted? (permit not required)
BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and
ELECTRICAL SAFETY Information Bulletin
ELECTRICAL SAFETY Information Bulletin January 2016 CEC-10 [rev-9] Page 1 of 8 CANADIAN ELECTRICAL CODE SUBJECT: Section 10 Grounding and Bonding Rule 10-204 Grounding Connections for Alternating-Current
Please check with your local inspection authority for any additional requirements before installation.
Specifications for Residential Overhead Electric Service Installation This brochure addresses most typical residential overhead service installations. Variances for the following specifications must be
Installation Instructions Hustler 6-BTV Trap Vertical
Installation Instructions Hustler 6-BTV Trap Vertical ASSEMBLY 1. Check the package contents against the parts list on page 2. 2. WARNING. Installation of this product near power lines is dangerous. For
METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D
12 - ELECTRIC SERVICE HANDBOOK SECTION D METER REQUIREMENTS This chapter gives you information on Central Lincoln s metering requirements. It's divided into three sections: General requirements This section
ELECTRIC METERING COMMERCIAL & INDUSTRIAL
ELECTRIC METERING COMMERCIAL & 1.0 INDEX 1.0 INDEX 2.0 SCOPE 3.0 GENERAL REQUIREMENTS 4.0 METER LOCATIONS 5.0 UNDERGROUND TERMINATIONS 6.0 METERING TRANSFORMER ENCLOSURES 7.0 SINGLE CUSTOMER METER INSTALLATIONS
Solar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual
Solar Power Systems Models: PVS220W-24 and PVS220W-48 Installation Manual 255379 Rev. D0 1015 Printed in U.S.A. Copyright 2015 Federal Signal Corporation Limited Warranty The Alerting and Notification
Transformer Deluge Systems
Transformer Deluge Systems How Do Transformer Fires Ignite? Common causes of transformer failure: Weather-related events such as lightning Short circuits in electrical equipment The most common cause is
SECTION 25110 TELECOMMUNICATION ROOMS
PART 1 - GENERAL 1.1 SUMMARY A. SCOPE SECTION 25110 TELECOMMUNICATION ROOMS 1. This section includes the minimum installation requirements for equipment and cabling infrastructure in Telecommunication
INTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 62305-3 Edition 2.0 2010-12 colour inside Protection against lightning Part 3: Physical damage to structures and life hazard INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE
Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1
Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader
BLADDER SURGE CONTROL SYSTEM
PART I GENERAL 1.01 Description BLADDER SURGE CONTROL SYSTEM This specification describes the requirements for a Bladder Surge Control System. The purpose of the system is to minimize transient pressures
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT. YOU COULD PUT YOUR FAMILY AND WORLDLY POSSESSIONS IN DANGER!!!
INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS
INSTALLATION INSTRUCTIONS HUSTLER 4-BTV, 5-BTV TRAP VERTICAL WARNING INSTALLATION OF THIS PRODUCT NEAR POWER LINES IS DANGEROUS FOR YOUR SAFETY, FOLLOW THE INSTALLATION DIRECTIONS GENERAL DESCRIPTION:
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
CATHODIC PROTECTION SYSTEM DESIGN
CATHODIC PROTECTION SYSTEM DESIGN Presented By DENIS L ROSSI P.E. CORROSION ENGINEER New England C P Inc. Corrosion Fundamentals What is corrosion? It is defined as the degradation or deterioration of
-1- SPECIFICATIONS 002085 CONE SETTER PLATFORM ATTACHMENT INDEX
-1-002085 CONE SETTER PLATFORM ATTACHMENT INDEX I. GENERAL EQUIPMENT : A. Intent Statement B. Cone Setter Platform II. III. 1. Understructure Frame 2. Mounting Components 3. Paint 4. Basket 5. Labels 6.
The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables
The National Armored Cable Manufacturers Association Presents Installation Standard for Types AC and MC Cables An ANSI Standard Original document jointly produced by NECA and NACMA as Standard for Installing
During severe flood events, such as those
Recommended Practice for Home Heating Oil Tank Flood Resistance During severe flood events, such as those occurring from Hurricane Irene and Super- Storm Sandy, many coastal and low elevation inland areas
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
Installation/Operators Guide
BOLTEK CORPORATION Lightning Detection StormTracker Lightning Detector with PCI style receiver card Installation/Operators Guide SEE NOTICES ON REVERSE B O L T E K L I G H T N I N G D E T E C T I O N StormTracker
Grounding of Electrical Systems NEW CODE: Grounding and Bonding
Grounding of Electrical Systems NEW CODE: Grounding and Bonding Presented By Scott Peele PE Grounding of Electrical Systems Outline Defining the Terms Why should I Ground? Types of Grounding Systems Separately
EZ-48-3AB-125-35 Weather Station Mounting Tripod and Mast
EZ-48-3AB-125-35 Weather Station Mounting Tripod and Mast EZ-125-35M 35 Mast Extension (Optional) EZ-125-SK Stake Kit (Optional) EZ-46-3 Tar Pad Kit (Optional) EZ-GWA Guy Wire Kit (Optional) Ambient Weather
COLORADO MODEL. 35 x 65 SPECIFICATIONS
COLORADO MODEL 35 x 65 SPECIFICATIONS Dimensions: Roof Dimensions 35-0 x 65-0 Column Dimensions (center to center) 31-0 x 30-6 Minimum Clearance 14-0 Roof Height @ Peak ±18-8 Curved Roof ±42-6 radius Square
STREETLIGHT SYSTEM GROUNDING AND BONDING
Page: 1 of 8 STREETLIGHT SYSTEM GROUNDING AND BONDING 1. Scope This Construction Standard covers the grounding and bonding requirements for single phase streetlight systems served by the Looped Radial
Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes
CANTEX INC. 301 Commerce Ste 2700 Fort Worth, Texas 76102 817-215-7000 Fax: 817-215-7001 Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes YOUR FULL
Bryant Woods Condominium Association. Antenna and Satellite Dish Installation Rules
Antenna and Satellite Dish Installation Rules Dear Residents: Enclosed please find the Antenna Rules that have been adopted by the Board. If you have any questions, comments or concerns relating to the
Lightning Protection Introduction
Lightning Protection Introduction Structural lightning protection design considerations BS 6651 (Protection of structures against lightning) clearly advises strict adherence to the provision of a conventional
NEGRP TEST SUMMARY. Joseph A. Lanzoni, November 2005
NEGRP TEST SUMMARY Joseph A. Lanzoni, November 2005 The National Electrical Grounding Research Project (NEGRP) was a project managed and sponsored by the National Fire Protection Association (NFPA) Research
MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS
Los Angeles, CA Project Manual and Specification DIVISION 1 GENERAL CONDITIONS 01 01 10 STATEMENT OF WORK 01 11 00 SUMMARY OF THE WORK 01 14 05 METRO (OWNER) - DIRECTED STOPPAGES 01 20 00 PRICE AND PAYMENT
Cellular Wireless Antennas
Cellular Wireless Antennas A Technical Brief GarrettCom Inc., November 2010 Overview The Cellular Wireless Antenna Technical brief is provided to assist with the design and deployment of the DX940 Cellular
Security Cameras, CATV, GPS & Satellite Protection. White Paper
Security Cameras, CATV, GPS & Satellite Protection White Paper Security Cameras, CATV, GPS & Satellite Protection Surge Protection Solutions for PTC 1 Security Cameras, CATV, GPS & Satellite Protection
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
METHOD STATEMENT FOR INSTALLATION OF CABLE TRAY/TRUNKING/LADDER
Page 1 of 6 FOR INSTALLATION OF CABLE TRAY/TRUNKING/LADDER 0 Issued for Review & Comments Rev. Date Description Eng. A.H Prepared by Checked by Approved by Page 2 of 6 REVISION CONTROL SHEET REV. NO. DATE
David Brender Copper Development Association Inc. [email protected]. Miramar, March 8, 2013
Grounding and Bonding in Communications Systems David Brender Copper Development Association Inc. [email protected] Ennes Workshop Miramar, March 8, 2013 MMXIII This talk concentrates on:
EARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property
2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property A brief summary of the most used code references for residential wiring State of Idaho Division of Building Safety Electrical
Preformed Metal Roofing and Siding
Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision
AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding
AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding A Guide for California Developers of Com m ercial Property This guide consists of
Whitepaper. Modular Substation Cable Termination Design. Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada
Whitepaper Modular Substation Cable Termination Design Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada Abstract The methods for cable penetrations into modular industrial substations are
Wildland Fire Remote Monitor
K A N S A S F O R E S T S E R V I C E KANSAS STATE UNIVERSITY Wildland Fire Remote Monitor For years, fire department administrators have struggled to find an alternative to having firefighters ride on
Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS
Electric Engineering Division FIBER CONDUIT RULES AND REGULATIONS TABLE OF CONTENTS I. RULES AND REGULATIONS A. TABLE OF CONTENTS... 2 B. TERMS AND DEFINITIONS... 3 C. DEVELOPER S/CONTRACTOR S RESPONSIBILITIES...
Multiple Meter Installation - 200 Amperes Per Position -Single Phase, Self-contained
Overhead Meters TABLE OF CONTENTS D D Consumer Service Pole for Mobile Home Park Temporary Service -wire Single Phase D. Overhead Meter Installation - Single Phase D. Connection Diagram - Single Phase
ReachFree ID Installation Instructions For Portal TI, Sentinel and C-Start. Unitec www.startwithunitec.com
ReachFree ID Installation Instructions For Portal TI, Sentinel and C-Start Unitec www.startwithunitec.com Proprietary Information and Materials of Unitec, Inc. Such proprietary information and materials
Underground Storage Tanks
Underground Storage Tanks An Informational and Guidance Document for the University Community. Please contact Yale Environmental Health and Safety for latest Regulatory Requirements. A typical UST installation
DENVER MODEL 30 X 30 SPECIFICATIONS
DENVER MODEL 30 X 30 SPECIFICATIONS Dimensions: Roof Dimensions 30-0 x 30-0 (4) Columns (Center to Center) 25-6½ x 25-6½ Minimum Clearance 8-0 Roof Height @ Peak Dependent on Col. Ht. Hip Roof 4:12 pitch
CCU Engineering Specifications. Section 003300 PRECAST CONCRETE PRODUCTS
CCU Engineering Specifications Section 003300 Effective Date: Nov. 1st, 2011 Page 1 of 5 PRECAST CONCRETE PRODUCTS PART 1 - GENERAL The following specification is intended for use for the design, selection
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
TCTC Cabling Specifications
TCTC Cabling Specifications Purpose: To provide a standard specification that will be used for all Tri County Technical College (TCTC) facilities requiring structured cabling installation. Product specifications,