LV power air circuit breakers and switch-disconnectors Catalogue NT and NW Merlin Gerin We do more with electricity
Industries SA 5, rue Nadar 92506 Rueil-Malmaison Cedex France Tel : +33 (0)1 41 29 82 00 Fax : +33 (0)1 47 51 80 20 http://www.schneiderelectric.com As standards, specifications and designs change from time to time, please ask for confirmation of the information given iin this publication This ce document document a été has imprimé been printed on ecological paper sur du papier écologique. 000000000 yyyy - All right reserved Design: - AMEG Photos: Printed: BTP207E mm-yy
E58856 Things never will be same the E58880 The original has set a new standard for power circuit breakers around the world. Over the years, other major manufacturers have tried to keep up by developing products incorporating s most innovative features, including the breaking principle, modular design and the use of composite materials. Today, continues to innovate with the new Merlin Gerin NT and NW ranges. In addition to the traditional features of power circuit breakers (withdrawability, discrimination and low maintenance), now offers built-in communications and metering functions, all in optimised frame sizes. NT and NW incorporate the latest technology to enhance both performance and safety. Easy to install, with user-friendly, intuitive operation and environment-friendly design, they are, quite simply, circuit breakers of their time. 1
E58873 The ultimate power in power distribution New, new levels of performance Five performance levels 029693 N1 - for standard applications with low short-circuit levels. H1 - for industrial sites with high short-circuit levels or installations with two parallel-connected transformers. H2 - high-performance for heavy industry where very high short-circuits can occur. H3 - for incoming devices supplying critical applications requiring both high performance and a high level of discrimination. L1 - for high current-limiting capability and a discrimination level (37 ka) as yet unequalled by any other circuit breaker of its type; intended for the protection of cable-type feeders or to raise the performance level of a switchboard when the transformer power rating is increased. 025855 E58868 Integration in a communications network can be integrated in a general supervision system to optimise installation operation and maintenance. The communication architecture is open, and may be upgraded for interfacing with any protocol. Switch-disconnector versions The switch-disconnectors are derived directly from the circuit breakers and offer the same features and performance levels. They are available in HA, NA and HF versions, depending on the models. The HF version includes instantaneous protection to prevent closing on a short-circuit. Once closed, the switch-disconnectors are unprotected and behave like ordinary switches. They are often used for busbar coupling. E58865 1000 V and 400 Hz distribution systems The range can be used on 1000 V installations (mining industry) and 400 Hz systems (aeronautics, computer centres). 2
Thing will be never the same 3 frame sizes, 2 families NT 800 to 1600 A The new range of power circuit breakers includes two families: c NT, the world s smallest true power circuit breaker, with ratings from 800 to 1600 A; c NW, in two frame sizes, one from 800 to 4000 A and the other from 4000 A to 6300 A. NW 800 to 4000 A De 4000 à 6300 A 056473 056472 056477 E58892 E58893 E58891 E58882 3
E58869 No other offer can put us in the shade Optimised volumes E58879 The smallest circuit breaker in the world NT innovates by offering all the performance of a power circuit breaker in an extremely small volume. The 70 mm pole pitch means a three-pole drawout circuit breaker can be installed in a switchboard section 400 mm wide and 400 mm deep. Practical installation solutions E58880 E58881 The new range improves upon all the installation solutions which have already made a success. It has been designed to standardise switchboards, optimise volumes and simplify installation: c incoming connection to top or bottom terminals; c no safety clearance required; c connection: v horizontal or vertical rear connection; v front connection with minimum extra space; v mixed front and rear connections; c 115 mm pole pitch on all versions; c no derating up to 55 C and 4000A. Optimised volumes Up to 4000 A, NW circuit breakers are all the same size, the same as the old M08 to 32 range. From 4000 A to 6300 A, there is just one size, much smaller than before. Retrofit solutions Special connections are available to replace a fixed or drawout M08 to 32 with a NW, without modifying the busbars or the door cut-out. 4
E58867 A perfect fit Ease of installation E58871 Vertical front connection of a fixed NW. E58879 With optimised sizes, the NT and NW ranges simplify the design of switchboards and standardise the installation of devices: c a single connection layout for NT; c three connection layouts for NW: v one from 800 to 3200 A; v one for 4000 A; v one up to 6300 A; c identical connection terminals from 800 to 6300 A ( NW); c front connection requires little space because the connectors to not increase the depth of the device; c rear connection to vertical or horizontal busbars simply by turning the connectors 90. E58870 E58872 Vertical and horizontal rear connection of a fixed NW. Connection to busbars. 5
E58878 The shortest distance between two points Innovation E58875 Greater dependability Filtered breaking The patented new design of the arc chutes includes stainless-steel filters. The chutes absorb the energy released during breaking, thus limiting the stresses exerted on the installation. They filter and cool the gases produced, reducing effects perceptible from the outside. Filtered breaking Automatic unlatching The automatic unlatching of the circuit breaker operating mechanism for high short-circuits extends performance up to 150kA. It produces ultrafast tripping for all short-circuits higher than 37 ka (L1) and 65 ka (H3). For lower short-circuits, the system does not react so that the control unit can provide total discrimination with downstream devices. More intelligent trip units E58874 Today, with the high speed of calculation, the small size of memories and advances in miniaturisation, trip units have become circuit breaker control units offering increasingly powerful functions. They accurately measure system parameters, instantly calculate values, store data, log events, signal alarms, communicate, take action, etc. The new ranges, equipped with Micrologic control units, constitute both an extremely reliable protective device and an accurate measurement instrument. User friendly Intuitive use Micrologic control units are equipped with a digital LCD display used in conjunction with simple navigation buttons. Users can directly access parameters and settings. Navigation between screens is intuitive and the immediate display of values greatly simplifies settings. Text is displayed in the desired language. Navigation buttons on a Micrologic P control unit. backed by incomparable security Protection functions are separate from the measurement functions and are managed by an ASIC electronic component. This independence guarantees immunity from conducted or radiated disturbances and ensures a high degree of reliability. A patented double setting system for protection functions establishes: * a maximum threshold set using the control-unit dials; * fine adjustments via the keypad or remotely. The fine adjustments for thresholds (to within one ampere) and tripping delays (to within a fraction of a second) are displayed directly on the screen. The control unit cover can be lead-sealed to prevent uncontrolled access to the dials and protect the settings. 6
E58876 How many green circuit breakers do you know? Ready for the future Compliance with environmental requirements fully takes into account environmental requirements, starting right from the design phase of every product through to the end of its service life: c the materials used for are not potentially dangerous to the environment; c the production facilities are non-polluting in compliance with the ISO 14001 standard; c filtered breaking eliminates pollution in the switchboard; c the energy dissipated per pole is low, making energy losses insignificant; c the materials are marked to facilitate sorting for recycling at the end of product service life. Simple upgrading of installations Installations change, power levels increase, new equipment is required and switchboards must be extended. is designed to adapt to these changes: c all control units are interchangeable; c communication with a supervision system is an option that may be added at any time; c a reserve chassis can be pre-addressed so that system parameters do not have to be modified when a drawout device is installed at a later date; c any future changes to the products will be designed to ensure continuity with the current ranges, thus simplifying installation upgrades. 7
NT and NW 10 years already The original has set a new standard for power circuit breakers around the world. Over the years, other major manufacturers have tried to keep up by developing products incorporating s most innovative features, including the breaking principle, modular design and the use of composite materials. Today, continues to innovate with the new Merlin Gerin NT and NW ranges. In addition to the traditional features of power circuit breakers (withdrawability, discrimination and low maintenance), now offers built-in communications and metering functions, all in optimised frame sizes. NT and NW incorporate the latest technology to enhance both performance and safety. Easy to install, with user-friendly, intuitive operation and environment-friendly design, they are, quite simply, circuit breakers of their time. 056409 Setting the standard, once again 1
Loup The ultimate power in power distribution 2
5 levels of performance NT and NW offer 5 levels of performance to cover a wide range of applications. 044587 026160 053598 N1 - for standard applications with low short-circuit levels. H1 - for industrial sites with high short-circuit levels or installations with two parallel-connected transformers. H2 - high-performance for heavy industry where very high short-circuits can occur. H3 - for incoming devices supplying critical applications requiring both high performance and a high level of discrimination. L1 - for high current-limiting capability and a discrimination level (37 ka) as yet unequalled by any other circuit breaker of its type; intended for the protection of cable-type feeders or to raise the performance level of a switchboard when the transformer power rating is increased. Special applications 1000 V and 400 Hz distribution systems The range can be used on 1000 V installations (mining industry) and 400 Hz systems (aeronautics, computer centres). E58868 Switch-disconnectors The switch-disconnectors are derived directly from the circuit breakers. They are available in a number of versions: c for NT: HA (equivalent to H1). c for NW: v NA and HA (equivalent to N1 and H1) v HF, a high-performance switch-disconnector including instantaneous protection to prevent closing on a shortcircuit. Once closed, the switch-disconnector is unprotected and behaves like an ordinary switch. It is often used for busbar coupling. 029693 3
Tournesol Things never will be same the 4
3 frame sizes, 2 families NT 800 to 1600 A E58891 The new range of power circuit breakers includes two families: c NT, the world s smallest true power circuit breaker, with ratings from 800 to 1600 A; c NW, in two frame sizes, one from 800 to 4000 A and the other from 4000 A to 6300 A. 056477 056472 NW 800 to 4000 A E58892 4000 to 6300 A 056473 E58893 5
Cypres No other offer can put us shade in the 6
Optimised volumes E58879 The smallest circuit breaker in the world NT innovates by offering all the performance of a power circuit breaker in an extremely small volume. The 70 mm pole pitch means a three-pole drawout circuit breaker can be installed in a switchboard section 400 mm wide and 400 mm deep. Practical installation solutions: E58880 The new range improves upon all the installation solutions which have already made a success. It has been designed to standardise switchboards, optimise volumes and simplify installation: c incoming connection to top or bottom terminals c no safety clearance required c connection: v horizontal or vertical rear connection v front connection with minimum extra space v mixed front and rear connections c 115 mm pole pitch on all versions c no derating up to 55 C and 4000A. E58881 Optimised volumes Up to 4000 A, NW circuit breakers are all the same size, the same as the old M08 to 32 range. The dimensions of a 3-pole NW40 drawout circuit breaker are therefore 440 mm x 440 mm x 400 mm (H x W x D). From 4000 A to 6300 A, there is just one size, much smaller than before. The dimensions of a 3-pole NW63 drawout circuit breaker are therefore 480 mm x 730 mm x 440 mm (H x W x D). Retrofit solutions Special connections are available to replace a fixed or drawout M08 to 32 with a NW, without modifying the busbars or the door cut-out. 7
Abeilles A perfect fit 8
Ease of installation With optimised sizes, the NT and NW ranges simplify the design of switchboards and standardise the installation of devices: c a single connection layout for NT c three connection layouts for NW: v one from 800 to 3200 A v one for 4000 A v one up to 6300 A c identical connection terminals from 800 to 6300 A ( NW) c front connection requires little space because the connectors to not increase the depth of the device c rear connection to vertical or horizontal busbars simply by turning the connectors 90. E58871 Vertical front connection of a fixed NW E58870 E58872 Connection to busbars. Vertical and horizontal rear connection of a fixed NW. 9
Girafe The shortest distance between two points Giraffe You can replace the Giraffe photo by the Micrologic photo. Micrologic 10
Innovation E58875 Greater dependability Filtered breaking The patented new design of the arc chutes includes stainless-steel filters. The chutes absorb the energy released during breaking, thus limiting the stresses exerted on the installation. They filter and cool the gases produced, reducing effects perceptible from the outside. E58874 Filtered breaking. Navigation buttons on a Micrologic P control unit. Automatic unlatching The automatic unlatching of the circuit breaker operating mechanism for high short-circuits extends performance up to 150kA. It produces ultrafast tripping for all short-circuits higher than 37 ka (L1) and 65 ka (H3). For lower short-circuits, the system does not react so that the control unit can provide total discrimination with downstream devices. Greater intelligence Today, with the high speed of calculation, the small size of memories and advances in miniaturisation, trip units have become circuit breaker control units offering increasingly powerful functions. They accurately measure system parameters, instantly calculate values, store data, log events, signal alarms, communicate, take action, etc. The new ranges, equipped with Micrologic control units, constitute both an extremely reliable protective device and an accurate measurement instrument. User friendly Intuitive use Micrologic control units are equipped with a digital LCD display used in conjunction with simple navigation buttons. Users can directly access parameters and settings. Navigation between screens is intuitive and the immediate display of values greatly simplifies settings. Text is displayed in the desired language. backed by incomparable security Protection functions are separate from the measurement functions. They are managed by an ASIC electronic component common to all the control units to guarantee immunity from conducted or radiated disturbances and ensure a high degree of reliability. A patented «double setting» system for protection functions establishes a maximum threshold set using the control-unit dials and fine adjustments via the keypad or remotely. The fine adjustments for thresholds (to within one ampere) and tripping delays (to within a fraction of a second) are displayed directly on the screen. The control unit cover can be lead-sealed to prevent uncontrolled access to the dials and protect the settings. 11
Oiseaux How many green circuit breakers know? do you 12
Ready for the future Compliance with environmental requirements fully takes into account environmental requirements, starting right from the design phase of every product through to the end of its service life: c the materials used for are not potentially dangerous to the environment c the production facilities are non-polluting in compliance with the ISO 14001 standard c filtered breaking eliminates pollution in the switchboard and the energy dissipated per pole is low, making energy losses insignificant c the materials are marked to facilitate sorting for recycling at the end of product service life. Integration in a communications network can be integrated in a general supervision system to optimise installation operation and maintenance. The communication architecture is open, and may be upgraded for interfacing with any protocol. Simple upgrading of installations Installations change, power levels increase, new equipment is required and switchboards must be extended. is designed to adapt to these changes: c all control units are interchangeable c communication with a supervision system is an option that may be added at any time c a reserve chassis can be pre-addressed so that system parameters do not have to be modified when a drawout device is installed at a later date c any future changes to the products will be designed to ensure continuity with the current ranges, thus simplifying installation upgrades. 13
8
Functions and characteristics Presentation 1 General overview Detailed contents 10 Circuit breakers and switch-disconnectors NT06 to NT16 12 NW08 to NW63 14 Micrologic control units Overview of functions 16 Micrologic A «ammeter» 18 Micrologic P «power meter» 20 Micrologic H «harmonic meter» 24 Accessories and test equipment 26 Communication COM option in 28 Overview of functions 29 in a communication network 30 Connections Overview of solutions 32 Optional accessories 33 Locking On the device 36 On the chassis 37 Indication contacts 38 Remote operation Remote ON/OFF 40 Remote tripping 43 Accessories 44 Source-changeover systems Presentation 46 Mechanical interlocking 47 Electrical interlocking 48 Associated automatic controllers 49 Display modules 50 Dimensions and connection 53 Electrical diagrams 81 Installation recommendations 91 Additional characteristics 115 References 121 9
menu Functions and characteristics General overview Detailed contents 056402 056403 This chapter describes all the functions offered by NT and NW devices. The two product families have identical functions implemented using the same or different components depending on the case. Circuit breakers and switch-disconnectors page 12 c ratings: v NT 630 to 1600 A v NW 800 to 6300 A c circuit breakers type N1, H1, H2, H3, L1 c switch-disconnectors type NA, HA, HF c 3 or 4 poles c fixed or drawout versions c option with neutral on the right c protection derating Micrologic control units page 16 Ammeter A 2.0 basic protection 5.0 selective protection 6.0 selective + earth-fault protection 100 % 7.0 selective + earth-leakage protection 40 % Power meter P 5.0 selective protection 6.0 selective + earth-fault protection 7.0 selective + earth-leakage protection Harmonic meter H 5.0 selective protection 6.0 selective + earth-fault protection 7.0 selective + earth-leakage protection c external sensor for earth-fault protection c rectangular sensor for earth-leakage protection c setting options (long-time rating plug): v low setting 0.4 to 0.8 x Ir v high setting 0.8 to 1 x Ir v without long-time protection c external power-supply module c battery module Communication page 28 c COM option in c in a communication network Connections page 32 c rear connection (horizontal or vertical) c front connection c mixed connections c optional accessories v bare-cable connectors and connector shields v terminal shields v vertical-connection adapters v cable-lug adapters v interphase barriers v spreaders v disconnectable front-connection adapter v safety shutters, shutter locking blocks, shutter position indication and locking E46431 E46428 E46427 E46426 E46253 E46256 10
056405 Locking page 36 c pushbutton locking by padlockable transparent cover c OFF-position locking by padlock or keylock c chassis locking in disconnected position by keylock c chassis locking in connected, disconnected and test positions c door interlock (inhibits door opening with breaker in connected position) c racking interlock (inhibits racking with door open) c racking interlock between crank and OFF pushbutton c automatic spring discharge before breaker removal c mismatch protection E47482 E47481 056428 Indication contacts page 38 c standard or low-level contacts: v ON/OFF indication (OF) v «fault trip» indication (SDE) v carriage switches for connected (CE), disconnected (CD) and test (CT) positions c programmable contacts: v 2 contacts (M2C) v 6 contacts (M6C). E47302 E47301 056407 M2C contact Remote operation page 40 c remote ON/OFF: v gear motor v XF closing or MX opening voltage releases v PF ready-to-close contact v options: RAR automatic or Res electrical remote reset - BPFE electrical closing pushbutton c remote tripping function: v MN voltage release - standard - adjustable or non-adjustable delay v or second MX voltage release E47303 OF contact Gear motor E47304 MX, XF and MN voltage releases Accessories page 44 c auxiliary terminal shield c operation counter c escutcheon c transparent cover for escutcheon c escutcheon blanking plate E47483 00399 11
Functions and characteristics Circuit breakers and switch-disconnectors NT06 to NT16 056408 common characteristics number of poles 3 / 4 rated insulation voltage (V) Ui 1000/1250 impulse withstand voltage (kv) Uimp 12 rated operational voltage (V AC 50/60 Hz) Ue 690 / 1000V suitability for isolation IEC 60947-2 degree of pollution IEC 60664-1 3 circuit-breaker characteristics as per IEC 60947-2 rated current (A) In at 40 C / 50 C** rating of 4th pole (A) sensor ratings (A) type of circuit breaker ultimate breaking capacity (ka rms) Icu 220/415 V V AC 50/60 Hz 440 V 525 V 690 V 1000 V rated service breaking capacity (ka rms) Ics % Icu rated short-time withstand current (ka rms) Icw 0.5 s V AC 50/60 Hz 3 s integrated instantaneous protection (ka peak ±10%) rated making capacity (ka peak) Icm 220/415 V V AC 50/60 H 440 V 525 V 690 V 1000 V break time (ms) closing time (ms) circuit-breaker characteristics as per NEMA AB1 breaking capacity (ka) V AC 50/60 Hz 240 V 480 V 600 V switch-disconnector characteristics as per IEC 60947-3 type of switch-disconnector rated making capacity (ka peak) Icm 220/415 V V AC 50/60 Hz 440 V 500/690 V 1000 V rated short-time withstand current (ka rms) Icw 0.5 s V AC 50/60 Hz 3 s ultimate breaking capacity (Icu) with external protection relay, maximum delay 350 ms installation, connection and maintenance service life mechanical with maintenance C/O cycles x 1000 without maintenance electrical without maintenance 440 V 690 V 1000 V motor control (AC3-947-4) 690 V connection drawout FC RC fixed FC RC dimensions (mm) drawout 3P H x W x D 4P fixed 3P 4P weight (kg) drawout 3P/4P (approximate) fixed 3P/4P * see the current-limiting curve in the «additional characteristics» section ** 50 C: rear vertical connected. Refer to temperature derating tables for other connection types. (1) SELLIM system 12
NT06 NT08 NT10 NT12 NT16 630 800 1000 1250 1600 630 800 1000 1250 1600 400 400 400 630 800 to 630 to 800 to 1000 to 1250 to 1600 H1 L1* H10 H1 H10 42 150-42 - 42 130-42 - 42 100-42 - 42 25-42 - - - 20-20 100 % 100 % 42 10 20 42 20 20 - - 20 - - 1 (1) - - - 88 330-88 - 88 286-88 - 88 220-88 - 88 52-88 - - - 42-42 25 9 25 25 25 < 50 < 50 42 150-42 - 42 100-42 - 42 25-42 - HA HA10 HA HA10 75-75 - 75-75 - 75-75 - - 42-42 42 20 42 20 20-20 - 42 20 42 20 25 25 25 25 25 12.5 12.5 12.5 12.5 12.5 6 3-6 (NT16: 3) - 3 2-2 (NT16: 1) - - - 0.5-0.5 3 2-2 (NT16: 1) - c c c c c c c c c c c c - c - c c - c - 322 x 288 x 280 322 x 358 x 280 301 x 274 x 211 301 x 344 x 211 30/39 14/18 sensor selection sensor rating (A) 400 630 800 1000 1250 1600 Ir threshold setting (A) 160 to 400 250 to 630 320 to 800 400 to 1000 500 to 1250 640 to 1600 13
Functions and characteristics Circuit breakers and switch-disconnectors NW08 to NW63 056409 common characteristics number of poles 3 / 4 rated insulation voltage (V) Ui 1000/1250 impulse withstand voltage (kv) Uimp 12 rated operational voltage (V AC 50/60 Hz) Ue 690/1150 suitability for isolation IEC 60947-2 degree of pollution IEC 60664-1 4 circuit-breaker characteristics as per IEC 60947-2 rated current (A) In at 40 C / 50 C** rating of 4th pole (A) sensor ratings (A) 056410 type of circuit breaker ultimate breaking capacity (ka rms) Icu 220/415 V V AC 50/60 Hz 440 V 525 V 690 V 1150 V rated service breaking capacity (ka rms) Ics % Icu rated short-time withstand current (ka rms) Icw 1s V AC 50/60 Hz 3s integrated instantaneous protection (ka peak ± 10%) rated making capacity (ka peak) Icm 220/415 V V AC 50/60 Hz 440 V 525 V 690 V 1150 V break time (ms) closing time (ms) circuit-breaker characteristics as per NEMA AB1 breaking capacity (ka) V AC 50/60 Hz 240 V 480 V 600 V switch-disconnector characteristics as per IEC 60947-3 type of switch-disconnector rated making capacity (ka peak) Icm 220/415 V V AC 50/60 Hz 440 V 500/690 V 1150 V rated short-time withstand current (ka rms) Icw 1 s V AC 50/60 Hz 3 s ultimate breaking capacity (Icu) with external protection relay, maximum delay 350 ms installation, connection and maintenance service life mechanical with maintenance C/O cycles x 1000 without maintenance electrical without maintenance 440 V 690 V 1150 V motor control (AC3-947-4) 690 V connection drawout FC RC fixed FC RC dimensions (mm) drawout 3P H x W x D 4P fixed 3P 4P weight (kg) drawout 3P/4P (approximate) fixed 3P/4P * see the current-limiting curve in the «additional characteristics» section ** 50 C: rear vertical connected. Refer to temperature derating tables for other connection types. (1) except 4000 A 14
NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40b NW50 NW63 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300 400 400 630 800 1000 1250 1600 2000 2000 2500 3200 to 800 to 1000 to 1250 to 1600 to 2000 to 2500 to 3200 to 4000 to 4000 to 5000 to 6300 N1 H1 H2 L1* H10 H1 H2 H3 L1* H10 H1 H2 H3 H10 H1 H2 42 65 100 150-65 100 150 150-65 100 150-100 150 42 65 100 150-65 100 150 150-65 100 150-100 150 42 65 85 130-65 85 130 130-65 85 130-100 130 42 65 85 100-65 85 100 100-65 85 100-100 100 - - - - 50 - - - - 50 - - - 50 - - 100 % 100 % 100 % 100 % 42 65 85 30 50 65 85 65 30 50 65 85 65 50 100 100 22 36 50 30 50 36 75 65 30 50 65 75 65 50 100 100 without without 190 80 without without 190 150 80 without without 190 150 without without270 88 143 220 330-143 220 330 330-143 220 330-220 330 88 143 220 330-143 220 330 330-143 220 330-220 330 88 143 187 286-143 187 286 286-143 187 286-220 286 88 143 187 220-143 187 220 220-143 187 220-220 220 - - - - 105 - - - - 105 - - - 105 - - 25 25 25 10 25 25 25 25 10 25 25 25 25 25 25 25 < 70 < 70 < 70 < 80 42 65 100 150-65 100 150 150-65 100 150-100 150 42 65 100 150-65 100 150 150-65 100 150-100 150 42 65 85 100-65 85 100 100-65 85 100-100 100 NA HA HF HA10 HA HF HA10 HA HF HA10 HA 88 105 187-105 187-121 187-187 88 105 187-105 187-121 187-187 88 105 187-105 187-121 187-187 - - - 105 - - 105 - - 105-42 50 85 50 50 85 50 55 85 50 85-36 75 50 36 75 50 55 75 50 85 42 50 85 50 50 85 50 55 85 50 85 25 20 20 10 12.5 10 10 5 10 10 10 3-8 8 2 3-5 5 1.25-1.5 1.5 10 10 10 3-6 6 2 3-2.5 2.5 1.25-1.5 1.5 - - - - 0.5 - - - - 0.5 - - - 0.5 - - 10 10 10 - - 6 6 6 - - 2.5 2.5 2.5 - - - c c c c c c c c c c c c c c - - c c c c c c c c c c c c c c c c c c c - - c c - - - c (1) c (1) - - - - c c c - - c c - - - c c - - c c 439 x 441 x 395 479 x 786 x 395 439 x 556 x 395 479 x 1016 x 395 352 x 422x 297 352 x 767x 297 352 x 537x 297 352 x 997x 297 90/120 225/300 60/80 120/160 sensor selection sensor rating (A) 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300 Ir threshold 160 250 320 400 500 630 800 1000 1250 1600 2000 2500 setting (A) to 400 to 630 to 800 to 1000 to 1250 to 1600 to 2000 to 2500 to 3200 to 4000 to 5000 to 6300 15
Functions and characteristics Micrologic control units Overview of functions All circuit breakers are equipped with a Micrologic control unit that can be changed on site. Control units are designed to protect Power circuits and loads. Alarms may be programmed for remote indications. Measurements of current, voltage, frequency, power and power quality optimise continuity of service and energy management. Dependability Integration of protection functions in an ASIC electronic component used in all Micrologic control units guarantees a high degree of reliability and immunity to conducted or radiated disturbances. On Micrologic A, P and H control units, advanced functions are managed by an independent microprocessor. Micrologic name codes 2.0 A X Y Z E46019 Current protection Micrologic 2: basic protection t X: type of protection c 2 for basic protection c 5 for selective protection c 6 for selective + earth-fault protection c 7 for selective + earth-leakage protection Y: control-unit generation Identification of the control-unit generation. 0 signifies the first generation. Z: type of measurement c A for ammeter c P for power meter c H for harmonic meter. E46020 0 Ir Isd I t Micrologic 5: selective protection Protection: long time + instantaneous 0 Ir Isd Ii I Protection: long time + short time + instantaneous 056411 Micrologic 6: selective + earth-fault protection E46020 t E46033 t 0 Ir Isd Ii I 0 Ig I Protection: long time + short time + instantaneous + earth fault Micrologic 7: selective + earth-leakage protection E46020 t E46034 t 0 Ir Isd Ii I 0 I n I Protection: long time + short time + instantaneous + earth leakage 16
menu menu menu menu Measurements and programmable protection A: ammeter c I1, I2, I3, IN, Iearth-fault, Iearth-leakage and maximeter for these measurements c fault indications c settings in amperes and in seconds P: A + power meter + programmable protection c measurements of V, A, W, VAR, VA, Wh, VARh, VAh, Hz, Vpeak, Apeak, power factor and maximeters and minimeters c IDMTL long-time protection, minimum and maximum voltage and frequency, voltage and current imbalance, phase sequence, reverse power c load shedding and reconnection depending on power or current c measurements of interrupted currents, differentiated fault indications, maintenance indications, event histories and time-stamping, etc. H: P + harmonics c power quality: fundamentals, distortion, amplitude and phase of harmonics up to the 51st order c waveform capture after fault, alarm or on request c enhanced alarm programming: thresholds and actions 2.0 A E46251 100 % 40 % 5.0 A E46252 5.0 P E46255 5.0 H E46255 100 % 40 % 6.0 A E46253 6.0 P E46256 6.0 H E46256 100 % 40 % 7.0 A E46253 7.0 P E46256 7.0 H E46256 100 % 40 % 17
Functions and characteristics Control units Micrologic A ammeter E46028 Micrologic A control units protect power circuits. They also offer measurements, display, communication and current maximeters. Version 6 provides earth-fault protection, version 7 provides earth-leakage protection. 10 1 3 5.6.5.4 100 % Micrologic 6.0 A 40 % menu long time Ir.7.8.9 x In.95.98 1 short time Isd 2.5 3 4 56 2 8 1.5 10 x Ir setting Ig D E F C B A t= I n= tsd= tr= Isd= Ii= Ir= Ig= tg= G H J ground fault tr (s) 2 1.5 tsd (s) 4 8 12 16 20 @ 6 Ir 24.4.4.3.2.3.2.1 on I 2 t delay MAX.1 0 off tg (s).4.4.3.3.2.2.1.1 on I 2 0 t off ka s alarm instantaneous I i 6 8 10 4 12 3 15 2 off x In test 9 11 12 13 2 7 4 6 8 Protection settings... Protection thresholds and delays are set using the adjustment dials. The selected values are momentarily displayed in amperes and in seconds. Setting accuracy may be enhanced by limiting the setting range using a different long-time rating plug. Overload protection True rms long-time protection. Thermal memory: thermal image before and after tripping. Short-circuit protection Short-time (rms) and instantaneous protection. Selection of I 2 t type (ON or OFF) for short-time delay. Earth fault protection Residual or source ground return. Selection of I 2 t type (ON or OFF) for delay. Residual earth-leakage protection (Vigi). Operation without an external power supply. d Protected against nuisance tripping. k DC-component withstand class A up to 10 A. Neutral protection On three-pole circuit breakers, neutral protection is not possible. On four-pole circuit breakers, neutral protection may be set using a three-position switch: neutral unprotected (4P 3t), neutral protection at 0.5 In (4P 3t + N/2), neutral protection at In (4P 4t). Zone selective interlocking (ZSI) A ZSI terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping. menu Ammeter measurements... Micrologic A control units measure the true rms value of currents. A digital LCD screen continuously displays the most heavily loaded phase (Imax) or displays the I1, I2, I3, IN, Ig, I n, stored-current (maximeter) and setting values by successively pressing the navigation button. The optional external power supply makes it possible to display currents < 20% In. Communication option In conjunction with the COM communication option, the control unit transmits the following: c setting values c all ammeter measurements c tripping causes c maximeter reset. 1 long-time current setting and tripping delay 2 overload signal (LED) 3 short-time pick-up and tripping delay 4 instantaneous pick-up 5 earth-leakage or earth-fault pick-up and tripping delay 6 earth-leakage or earth-fault test button 7 long-time rating plug screw 8 test connector 9 lamp test, reset and battery test 10 indication of tripping cause 11 digital display 12 three-phase bargraph and ammeter 13 navigation buttons Note. Micrologic A control units come with a transparent leadseal cover as standard. 18
Protection Micrologic 2.0 A long time current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 tripping between 1.05 and 1.20 x Ir other ranges or disable by changing rating plug time delay (s) accuracy: 0 to -30 % tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600 accuracy: 0 to -20 % tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24 accuracy: 0 to -20 %) tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6 thermal memory 20 minutes before and after tripping instantaneous pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10 accuracy: ±10 % time delay fixed: 20 ms E46022 t Ir tr Isd 0 I Ammeter Micrologic 2.0 A continuous current measurements measurements from 20 to 200 % de In I1 I2 I3 IN accuracy: 1.5% (including sensors) no auxiliary source (where I > 20 % In) maximeters I1 max I2 max I3 max IN max menu Protection Micrologic 5.0 / 6.0 / 7.0 A long time Micrologic 5.0 / 6.0 / 7.0 A current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 tripping between 1.05 and 1.20 x Ir other ranges or disable by changing rating plug time delay (s) accuracy: 0 to -30 % tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600 accuracy: 0 to -20 % tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24 accuracy: 0 to -20 % tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6 thermal memory 20 minutes before and after tripping short time pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10 accuracy: ±10 % time delay (ms) at 10 Ir settings I 2 t Off 0 0.1 0.2 0.3 0.4 I 2 t On 0.1 0.2 0.3 0.4 tsd (max resettable time) 20 80 140 230 350 tsd (max break time) 80 140 200 320 500 instantaneous pick-up (A) Ii = In x 2 3 4 6 8 10 12 15 off accuracy: ±10 % earth fault Micrologic 6.0 A pick up (A) Ig = In x A B C D E F G H J accuracy: ±10 % In i 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 400 A < In i 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 In > 1200 A 500 640 720 800 880 960 1040 1120 1200 time delay (ms) settings I 2 t Off 0 0.1 0.2 0.3 0.4 at In or 1200 A I 2 t On 0.1 0.2 0.3 0.4 tg (max resettable time) 20 80 140 230 350 tg (max break time) 80 140 200 320 500 residual earth leakage (Vigi) Micrologic 7.0 A sensitivity (A) I n 0.5 1 2 3 5 7 10 20 30 accuracy: 0 to -20 % time delay (ms.) settings 60 140 230 350 800 t n (max resettable time) 80 140 230 350 800 t n (max break time) 140 200 320 500 1000 Ammeter Micrologic 5.0 / 6.0 / 7.0 A continuous current measurements measurements from 20 to 200 % of In I1 I2 I3 IN Ig I n accuract: 1.5 % (including sensors) no auxiliary source (where I > 20 % In) maximeters I1 max I2 max I3 max IN max Ig max I n max E46023 E46024 E46243A t t 0 I t Ir Ig tr I n tg Isd Ii 0 I t n tsd I 2 t on I 2 t off 0 I menu Note. All current-based protection functions require no auxiliary source. The test / reset button resets maximeters, clears the tripping indication and tests the battery. 19
Functions and characteristics Control units Micrologic P power E46017 Micrologic P control units include all the functions offered by Micrologic A. In addition, they measure voltages and calculate power and energy values. They also offer new protection functions based on currents, voltages, frequency and power reinforce load protection. 10 11 15 1 3 16 5 long time Ir.7.8.9.6.5.4 x In Micrologic 6.0 P.95.98 1 short time Isd 2.5 3 4 56 2 8 1.5 10 x Ir setting Ig D E F C B A G H J ground fault I(A) Trip 2000A 24s 20 ka 0.4s Off tr (s) 2 1.5 tsd (s) 4 8 12 16 20 @ 6 Ir 24.4.4.3.2.3.2.1 on I 2 t delay.1 0 off tg (s).4.4.3.3.2.2.1.1 on I 2 0 t off alarm instantaneous I i 6 8 10 4 12 3 15 2 off x In test 9 13 12 14 1 long-time current setting and tripping delay 2 overload signal (LED) 3 short-time pick-up and tripping delay 4 instantaneous pick-up 5 earth-leakage or earth-fault pick-up and tripping delay 6 earth-leakage or earth-fault test button 7 long-time rating plug screw 8 test connector 9 lamp + battery test and indications reset 10 indication of tripping cause 11 high-resolution screen 12 measurement display 13 maintenance indicators 14 protection settings 15 navigation buttons 16 hole for settings lockout pin on transparent cover 2 7 4 6 8 Protection settings... + The adjustable protection functions are identical to those of Micrologic A (overloads, short-circuits, earth-fault and earth-leakage protection). Double setting Within the range determined by the adjustment dial, fine adjustment of thresholds (to within one ampere) and time delays (to within one second) is possible on the keypad or remotely using the COM option. IDMTL setting Coordination with fuse-type or medium-voltage protection systems is optimised by adjusting the slope of the overload-protection curve. This setting also ensures better operation of this protection function with certain loads. Neutral protection On three-pole circuit breakers, neutral protection may be set using the keypad or remotely using the COM option, to one of four positions: neutral unprotected (4P 3t), neutral protection at 0.5 In (4P 3t + N/2), neutral protection at In (4P 4t) and neutral protection at 2 In (4P 3t + 2N). Neutral protection at 2 In is used when the neutral conductor is twice the size of the phase conductors (major load imbalance, high level of third order harmonics). On four-pole circuit breakers, neutral protection may be set using a three-position switch or the keypad: neutral unprotected (4P 3t), neutral protection at 0.5 In (4P 3t + N/2), neutral protection at In (4P 4t). Neutral protection produces no effect if the long-time curve is set to one of the IDMTL protection settings. Programmable alarms and other protection... Depending on the thresholds and time delays set using the keypad or remotely using the COM option, the Micrologic P control unit monitors currents and voltage, power, frequency and the phase sequence. Each threshold overrun is signalled remotely via the COM option. Each threshold overrun may be combined with tripping (protection) or an indication carried out by an optional M2C or M6C programmable contact (alarm), or both (protection and alarm). Load shedding and reconnection... Load shedding and reconnection parameters may be set according to the power or the current flowing through the circuit breaker. Load shedding is carried out by a supervisor via the COM option or by an M2C or M6C programmable contact. Measurements... The Micrologic P control unit calculates in real time all the electrical values (V, A, W, VAR, VA, Wh, VARh, VAh, Hz), power factors and crest factors. The Micrologic P control unit also calculates demand current and demand power over an adjustable time period. Each measurement is associated with a minimeter and a maximeter. In the event of tripping on a fault, the interrupted current is stored. The optional external power supply makes it possible to display the value with the circuit breaker open or not supplied. Histories and maintenance indicators... The last ten trips and alarms are recorded in two separate history files. Maintenance indications (contact wear, operation cycles, etc.) are recorded for local access. Indication option via programmable contacts The M2C (two contacts) and M6C (six contacts) auxiliary contacts may be used to signal threshold overruns or status changes. They can be programmed using the keypad on the Micrologic P control unit or remotely using the COM option. Communication option (COM) The communication option may be used to: c remotely read and set parameters for the protection functions c transmit all the calculated indicators and measurements c signal the causes of tripping and alarms c consult the history files and the maintenance-indicator register. An event log and a maintenance register, stored in control-unit memory but not available locally, may be accessed in addition via the COM option. Note. Micrologic P control units come with a non-transparent lead-seal cover as standard. 20
Protection Micrologic 5.0 / 6.0 / 7.0 P + long time (rms) Micrologic 5.0 / 6.0 / 7.0 P current setting (A) Ir = In x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 tripping between 1.05 and 1.20 x Ir other ranges or disable by changing rating plug time delay (s) accuracy: 0 to -30 % tr at 1.5 x Ir 12.5 25 50 100 200 300 400 500 600 accuracy: 0 to -20 % tr at 6 x Ir 0.5 1 2 4 8 12 16 20 24 accuracy: 0 to -20 % tr at 7.2 x Ir 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6 IDMTL setting curve slope SIT VIT EIT HVFuse DT thermal memory 20 minutes before and after tripping short time (rms) pick-up (A) Isd = Ir x 1.5 2 2.5 3 4 5 6 8 10 accuracy: ±10 % time delay (ms.) at 10 x Ir settings I 2 t Off 0 0.1 0.2 0.3 0.4 I 2 t On 0.1 0.2 0.3 0.4 tsd (max resettable time) 20 80 140 230 350 tsd (max break time) 80 140 200 320 500 instantaneous pick-up (A) Ii = In x 2 3 4 6 8 10 12 15 OFF accuracy: ±10 % earth fault Micrologic 6.0 P pick-up (A) Ig = In x A B C D E F G H J accuracy: ±10 % In i 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 400 A < In i 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 In > 1200 A 500 640 720 800 880 960 1040 1120 1200 time delay (ms.) at 10 x Ir settings I 2 t Off 0 0.1 0.2 0.3 0.4 I 2 t On 0.1 0.2 0.3 0.4 tg (max resettable time) 20 80 140 230 350 tg (max break time) 80 140 200 320 500 residual earth leakage (Vigi) Micrologic 7.0 P sensitivity (A) I n 0.5 1 2 3 5 7 10 20 30 accuracy: 0 to -20 % time delay (ms.) settings 60 140 230 350 800 t n (max resettable time) 60 140 230 350 800 t n (max break time) 140 200 320 500 1000 E46021 E46024 E46243 t 0 t 0 I t Ir IDMTL Ig I n tr tg Isd tsd t n I 2 t on I 2 t off 0 I Ii I Alarms and other protection Micrologic 5.0 / 6.0 / 7.0 P current threshold time delay current imbalance Iimbalance 0.05 to 0.6 Imax 1 to 40 s. maximum demand current Imax demand: I1, I2, I3, IN, Ig 0.4 In at short-time pick-up 0 to 1500 s. voltage voltage imbalance Uimbalance 0.02 to 0.3 Uaverage 1 to 40 s. minimum voltage Umin 60 to 690 V between phases 0.2 to 5 s. maximum voltage Umax 100 to 930 V between phases 0.2 to 5 s. power reserve power rp 5 to 500 kw 0.2 to 20 s. frequency minimum frequency Fmin 45 to 400 Hz 0.2 to 5 s. maximum frequency Fmax 45 to 540 Hz 0.2 to 5 s. phase sequence sequence Ø Ø1/2/3 or Ø1/3/2 instantaneous E46015 t threshold threshold delay delay 0 I/U/P/F Load shedding and reconnection Micrologic 5.0 / 6.0 / 7.0 P measured value threshold time delay current I 0.5 to 1 Ir per phases 20% tr to 80% tr. power P 200 kw to 10 MW 10 to 3600 s. E46016 t threshold threshold delay delay 0 I/P Note. All current-based protection functions require no auxiliary source. Voltage-based protection functions are connected to AC power via a voltage measurement input built into the circuit breaker. 21
Functions and characteristics Control units Micrologic P power E46258 E46262 E47305 3850A N 1 2 3 100 50 0 Default display Uinst. U 12 = 400V U 23 = 404V U 31 = 401V U 1N = 230V U 2N = 229V U 3N = 233V Display of a voltage F (Hz) 60.0 Display of a frequency E46261 E46263 E46265 I 1 = 4800A I 2 = 4600A I 3 = 4000A I N = 200A I = 13A P Q S Imax instant. Reset ( + / - ) Display of a maximum current Pinst. (kw) +2180 (kvar) -650 (kva) +2280 Display of a power Pdemand Pdemande PActive P (kw) 2180 kw +2180 Q Réactive (kvar) Q - 650 kvar -650 S (kva) Apparente +2280 S 2280 kva Display of a demand power Navigation from one display to another is intuitive. The six buttons on the keypad provide access to the menus and easy selection of values. When the setting cover is closed, the keypad may no longer be used to access the protection settings, but still provides access to the displays for measurements, histories, indicators, etc. Measurements... Instantaneous values The value displayed on the screen is refreshed every second. Minimum and maximum values of measurements are stored in memory (minimeters and maximeters). currents I rms A 1 2 3 N A e-fault e-leakage I max rms A 1 2 3 N A e-fault différentiel voltages U rms V 12 23 31 V rms V 1N 2N 3N U average rms V (U12 + U23 + U31) / 3 U imbalance % power, energy P active, Q reactive, S apparent W, Var, VA totals E active, E reactive, E apparent Wh, VARh, VAh totals consumed - supplied totals consumed totals supplied power factory PF total frequencies F Hz Demand metering The demand is calculated over a fixed or sliding time window that may be programmed from 5 to 60 minutes. According to the contract signed with the power supplier, an indicator associated with a load shedding function makes it possible to avoid or minimise the costs of overrunning the subscribed power. Maximum demand values are systematically stored and time stamped (maximeter). currents I demand A 1 2 3 N A e-fault e-leakage I max demand A 1 2 3 N A e-fault e-leakage power P, Q, S demand W, Var, VA totals P, Q, S max demand W, Var, VA totals Minimeters and maximeters Only the current and power maximeters may be displayed on the screen. E46259 Trip history Ir 03/08/1999 Isd 27/07/1999 Umax 30/06/1999 Display of a tripping history E46260 Trip 03/08/1999 12:02:36 Ir = I 1 = I 2 = I 3 = I N = 1000A 1200A 1430A 1060A 53A Display after tripping Histories... The last ten trips and alarms are recorded in two separate history files that may be displayed on the screen. c tripping history: v type of fault v date and time v values measured at the time of tripping (interrupted current, etc.). c alarm history: v type of fault v date and time v values measured at the time of the alarm.. Maintenance indicators... A number of maintenance indicators may be called up on the screen: c contact wear c operation counter: v cumulative total v total since last reset 22
E47070 POWERLOGIC System Manager Demo File Edit View Setup Control Display Tools Reports Window Help Time Ready Event Sampling Mode : MANUAL Display of an event log on a supervisor 5 seconds Module 04/21/98 08:49:06 Net Server Shutdown User : master Level : 1 PowerLogic Network 04/21/98 08:49:01 User Log Out User : master User level : 1 SMS-3000 Client 04/21/98 08:48:38 DB Table Change User : master TOD Event Tasks Alarm Setup 04/21/98 08:48:30 DB Table Change User : master Tasks Alarm Setup 04/21/98 08:46:16 DB Table Change User : master TOD Events Alarm Setup 04/21/98 08:39:19 User Log In User : master User level : 1 SMS-3000 Client 04/21/98 08:39:06 Security Check Key Status : Key Found PowerLogic Network 04/21/98 08:39:06 Net Server Started User : master Level : 1 PowerLogic Network 04/21/98 08:38:57 User Log In Event/Alarm/Network 04/21/98 08:30:44 Net Server Shutdown User : master Level : 1 PowerLogic Network 04/21/98 08:24:31 Security Check Key Status : Key Found PowerLogic Network 04/21/98 08:24:30 Net server Started User : master Level : 1 PowerLogic Network 04/21/98 08:24:15 User Log IN Event/Alarm/Network 04/21/98 08:18:07 IPC Error User : NA Err : 109 SMS-3000 Client 04/21/98 07:54:05 DB Table Change User : -1 Logger Template Devices Logger Setup 04/21/98 07:53:55 DB Table Change User : -1 Logger Template Topics Logger Setup 04/21/98 07:53:54 DB Table Change User : -1 Logger Templates Logger Setup 04/21/98 07:51:46 DB Table Change User : master Analog Levels Assigned Alarm Setup 04/21/98 07:51:33 DB Table Change User : master Analog Levels Template Alarm Setup 04/21/98 07:51:29 DB Table Change User : master Functions Alarm Setup 04/21/98 07:50:17 DB Table Change User : master Digital Levels Assigned Alarm Setup 04/21/98 07:50:17 DB Table Change User : master Analog Levels Assigned Alarm Setup 04/21/98 07:49:13 Setup: Device Name Device : MicroLogic User :master Device Setup Change Breaker 04/21/98 07:48:57 Setup: Device Added Device : MicroLogic Breaker User :master Device Setup 04/21/98 07:48:38 Setup: Device Name Change Device : Transformer Temp User : master Device Setup 04/21/98 07:48:22 Setup: Device Added Device : Transformer Temp User :master Device Setup 04/21/98 07:46:54 User Log In User : master User Level : 1 SMS-3000 Client 04/21/98 07:44:59 Security Check Key Status : Key Found PowerLogic Network 04/21/98 07:44:59 Net Server Started User :master Level : 1 PowerLogic Network ONLINE: DEMO No working system 9:30 With the communication option Additional measurements, maximeters and minimeters Certain measured or calculated values are only accessible with the COM communication option: c I peak / r, (I1 + I2 + I3)/3, I imbalance c load level in % Ir c total power factor The maximeters and minimeters are available only via the COM option for use with a supervisor. Event log All events are time stamped. c trips c beginning and end of alarms c modifications to settings and parameters c counter resets c system faults: v fallback position v thermal self-protection c loss of time c overrun of wear indicators c test-kit connections c etc. Maintenance register Used as an aid in troubleshooting and to better plan for device maintenance operations. c highest current measured c operation counter c number of test-kit connections c number of trips in operating mode and in test mode c contact-wear indicator. Additional technical characteristics Setting the display language System messages may be displayed in six different languages. The desired language is selected via the keypad. Protection functions All current-based protection functions require no auxiliary source. Voltage-based protection functions are connected to AC power via a voltage measurement input built into the circuit breaker. Measurement functions Measurement functions are independent of the protection functions. The high-accuracy measurement module operates independently of the protection module, while remaining synchronised with protection events. Measurement-calculation mode c measurement functions implement the new zero blind time concept which consists in continuously measuring signals at a high sampling rate. The traditional blind window used to process samples no longer exists. This method ensures accurate energy calculations even for highly variable loads (welding machines, robots, etc.). c energies are calculated on the basis of the instantaneous power values, in two manners: v the traditional mode where only positive (consumed) energies are considered v the signed mode where the positive (consumed) and negative (supplied) energies are considered separately. Accuracy of measurements (including sensors) cvoltage (V) 1% c current (A) 1.5% c frequency (Hz) 0.1 Hz c power (W) and energy (Wh) 2.5% Stored information The fine setting adjustments, the last 100 events and the maintenance register remain in the control-unit memory even when power is lost. Time-stamping Time-stamping is activated only if an external power supply module is present (max. drift of 1 hour per year). Reset An individual reset, via the keypad or remotely, acts on alarms, minimum and maximum data, peak values, the counters and the indicators. 23
Functions and characteristics Control units Micrologic H harmonics E46257 Micrologic H control units include all the functions offered by Micrologic P. Integrating significantly enhanced calculation and memory functions, the Micrologic H control unit offers in-depth analysis of power quality and detailed event diagnostics. It is intended for operation with a supervisor. long time Ir.7.8.9.6.5.4 I x In Micrologic 7.0 H U P E.95.98 1 tr (s) 4 8 12 16 20 2 1.5 @ 6 Ir 24 (A) (V) (kw) (kwh) Harmonics earth leakage alarm short time instantaneous Isd tsd I i (s).4.4.3 2.5 3 4 6 56 8 10.3.2 4 12 2 8.2.1 3 15 1.5 10.1 on I 2 0 2 off x Ir t off x In setting delay test I n t (A) 3 5 (ms) 7 230 350 2 10 140 1 20.5 30 60 800 In addition to the Micrologic P functions, the Micrologic H control unit offers: c in-depth analysis of power quality including calculation of harmonics and the fundamentals c diagnostics aid and event analysis through waveform capture c enhanced alarm programming to analyse and track down a disturbance on the AC power system Measurements... The Micrologic H control unit offers all the measurements carried out by Micrologic P, with in addition: c phase by phase measurements of: v power, energy v power factors c calculation of: v current and voltage total harmonic distortion (THD) v current, voltage and power fundamentals (50 Hz) v current and voltage harmonics up to the 51st order. Instantaneous values displayed on the screen currents I rms A 1 2 3 N A e-fault e-leakage I max rms A 1 2 3 N A e-fault e-leakage voltages U rms V 12 23 31 V rms V 1N 2N 3N U average rms V (U12 + U23 + U31) / 3 U imbalance % power, energy P active, Q reactive, S apparent W, Var, VA totals 1 2 3 E active, E reactive, E apparent Wh, VARh, VAh totals consumed - supplied totals consumed totals supplied power factor PF total 1 2 3 frequencies F Hz power-quality indicators total fundamentals U I P Q S THD % U I U and I harmonics amplitude 3 5 7 9 11 13 Harmonics 3, 5, 7, 9, 11 and 13, monitored by electrical utilities, are displayed on the screen. Demand measurements Similar to the Micrologic P control unit, the demand values are calculated over a fixed or sliding time window that may be set from 5 to 60 minutes. currents I demand A 1 2 3 N A e-fault e-leakage I max demand A 1 2 3 N A e-fault e-leakage puissances P, Q, S demand W, Var, VA totals P, Q, S max demand W, Var, VA totals Maximeters Only the current maximeters may be displayed on the screen. Histories and maintenance indicators These functions are identical to those of the Micrologic P. Note. Micrologic H control units come with a non-transparent lead-seal cover as standard. 24
E47071 E47072 POWERLOGIC System Manager Demo File Edit View Setup Control Display Tools Reports Window Help Time % Fundamental Ready 1,20 1,00 0,80 0,60 0,40 0,20 0,00 POWERLOGIC System Manager Demo File Edit View Setup Control Display Tools Reports Window Help 167 83 0-83 -167 167 83 0-83 -167 Event Phase A-N Voltage 17 33 50 66 Phase B-N Voltage 17 33 50 Sampling Mode : MANUAL Phase A-N Voltage - Harmonics Analysis Sampling Mode : MANUAL 642 321 0-321 5 seconds Phase A Current 17 33 50 Your Specific Device - Phase A-N Voltage -642 Fundamental: 118.08 RMS: 118.11 RMS-H: 2.38 Peak: 166.86 CF: 1.41 THD: 2.02 OK 5 seconds Module H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 Harmonics Display of harmonics up to 12th order. Fundamental: RMS: RMS-H: Peak: CF: THD: Phase 1-N Harmonics(RMS) H1: 118.09 H2: 0.01 H3: 0.45 H4: 0.03 H5: 0.45 H6: 0.04 H7: 1.27 H8: 0.05 H9: 0.42 H10: 0.01 H11: 1.03 H12: 0.07 ONLINE: DEMO No working system 9:30 OK Harmonics(RMS) H1: 118.09 H2: 0.01 H3: 0.45 H4: 0.03 H5: 0.45 H6: 0.04 H7: 1.27 H8: 0.05 H9: 0.42 H10: 0.01 H11: 1.03 H12: 0.07 66 With the communication option Additional measurements, maximeters and minimeters Certain measured or calculated values are only accessible with the COM communication option: c I peak / r, (I1 + I2 + I3)/3, I imbalance c load level in % Ir c power factor (total and per phase) c voltage and current THD c K factors of currents and average K factor c crest factors of currents and voltages c all the fundamentals per phase c fundamental current and voltage phase displacement c distortion power and distortion factor phase by phase c amplitude and displacement of current and voltage harmonics 3 to 51. The maximeters and minimeters are available only via the COM option for use with a supervisor. Waveform capture The Micrologic H control unit stores the last 12 cycles of each instantaneous current or voltage measurement. On request or automatically on programmed events, the control unit stores the waveforms. The waveforms may be displayed in the form of oscillograms by a supervisor via the COM option. Enhanced alarm programming Each instantaneous value can be compared to user-set high and low thresholds. Overrun of a threshold generates an alarm. An alarm or combinations of alarms can be linked to programmable actions, including circuit-breaker opening, activation of a M2C or M6C contact, selective recording of measurements in a log, waveform capture, etc. Event log and maintenance registers The Micrologic H offers the same event log and maintenance register functions as the Micrologic P. Ready ONLINE: DEMO No working system 9:30 E47070 Waveform capture POWERLOGIC System Manager Demo File Edit View Setup Control Display Tools Reports Window Help Time Ready Log Event Sampling Mode : MANUAL 5 seconds Module 04/21/98 08:49:06 Net Server Shutdown User : master Level : 1 PowerLogic Network 04/21/98 08:49:01 User Log Out User : master User level : 1 SMS-3000 Client 04/21/98 08:48:38 DB Table Change User : master TOD Event Tasks Alarm Setup 04/21/98 08:48:30 DB Table Change User : master Tasks Alarm Setup 04/21/98 08:46:16 DB Table Change User : master TOD Events Alarm Setup 04/21/98 08:39:19 User Log In User : master User level : 1 SMS-3000 Client 04/21/98 08:39:06 Security Check Key Status : Key Found PowerLogic Network 04/21/98 08:39:06 Net Server Started User : master Level : 1 PowerLogic Network 04/21/98 08:38:57 User Log In Event/Alarm/Network 04/21/98 08:30:44 Net Server Shutdown User : master Level : 1 PowerLogic Network 04/21/98 08:24:31 Security Check Key Status : Key Found PowerLogic Network 04/21/98 08:24:30 Net server Started User : master Level : 1 PowerLogic Network 04/21/98 08:24:15 User Log IN Event/Alarm/Network 04/21/98 08:18:07 IPC Error User : NA Err : 109 SMS-3000 Client 04/21/98 07:54:05 DB Table Change User : -1 Logger Template Devices Logger Setup 04/21/98 07:53:55 DB Table Change User : -1 Logger Template Topics Logger Setup 04/21/98 07:53:54 DB Table Change User : -1 Logger Templates Logger Setup 04/21/98 07:51:46 DB Table Change User : master Analog Levels Assigned Alarm Setup 04/21/98 07:51:33 DB Table Change User : master Analog Levels Template Alarm Setup 04/21/98 07:51:29 DB Table Change User : master Functions Alarm Setup 04/21/98 07:50:17 DB Table Change User : master Digital Levels Assigned Alarm Setup 04/21/98 07:50:17 DB Table Change User : master Analog Levels Assigned Alarm Setup 04/21/98 07:49:13 Setup: Device Name Device : MicroLogic User :master Device Setup Change Breaker 04/21/98 07:48:57 Setup: Device Added Device : MicroLogic Breaker User :master Device Setup 04/21/98 07:48:38 Setup: Device Name Change Device : Transformer Temp User : master Device Setup 04/21/98 07:48:22 Setup: Device Added Device : Transformer Temp User :master Device Setup 04/21/98 07:46:54 User Log In User : master User Level : 1 SMS-3000 Client 04/21/98 07:44:59 Security Check Key Status : Key Found PowerLogic Network 04/21/98 07:44:59 Net Server Started User :master Level : 1 PowerLogic Network ONLINE: DEMO No working system 9:30 Additional technical characteristics Setting the display language System messages may be displayed in six different languages. The desired language is selected via the keypad. Protection functions All current-based protection functions require no auxiliary source. Voltage-based protection functions are connected to AC power via a voltage measurement input built into the circuit breaker. Measurement functions Measurement functions are independent of the protection functions. The high-accuracy measurement module operates independently of the protection module, while remaining synchronised with protection events. Measurement-calculation mode An analogue calculation function dedicated to measurements enhances the accuracy of harmonic calculations and the power-quality indicators. The Micrologic H control unit calculates electrical magnitudes using 1.5 x In dynamics (20 x In for Micrologic P). Measurement functions implement the new zero blind time concept Energies are calculated on the basis of the instantaneous power values, in the traditional and signed modes. Harmonic components are calculated using the discrete Fourier transform (DFT). Accuracy of measurements (including sensors) cvoltage (V) 1% c current (A) 1.5% c frequency (Hz) 0.1 Hz c power (W) and energy (Wh) 2.5% c total harmonic distortion 1% Stored information The fine-setting adjustments, the last 100 events and the maintenance register remain in the control-unit memory even when power is lost. Time-stamping Time-stamping is activated only if an external power supply module is present (max. drift of 1 hour per year). Reset An individual reset, via the keypad or remotely, acts on alarms, minimum and maximum data, peak values, the counters and the indicators. 25
Functions and characteristics Micrologic control units Accessories and test equipment 025171 025173 056412 056467 E47477 External sensor (CT) Rectangular sensor for source return protection External sensors External sensor for earth-fault and neutral protection The sensors, used with the 3P circuit breakers, are installed on the neutral conductor for: c neutral protection (with Micrologic P and H) c residual type earth-fault protection (with Micrologic A, P and H).. The rating of the sensor (CT) must be compatible with the rating of the circuit breaker: c NT06 à NT16: TC 400/1600 c NW08 à NW20: TC 400/2000 c NW25 à NW40: TC 1000/4000 c NW40b à NW63: TC 2000/6300. For double neutral protection (2 IN,) the sensor rating must be compatible with the measurement range: 2 x IN. Rectangular sensor for earth-leakage protection The sensor is installed around the busbars (phases + neutral) to detect the zerophase sequence current required for the earth-leakage protection. Rectangular sensors are available in two sizes. Inside dimensions (mm) c 280 x 115 up to 1600 A for NT c 470 x 160 up to 4000 A for NW. External sensor for source ground return protection The sensor is installed around the connection of the transformer neutral point to earth and connects to the Micrologic 6.0 control unit via an MDGF module to provide the source ground return (SGR) protection. Voltage measurement inputs Voltage measurement inputs are required for power measurements and for earthleakage protection. As standard, the control unit is supplied by internal voltage measurement inputs placed downstream of the pole for voltages between 100 and 690 V AC. On request, it is possible to replace the internal voltage measurement inputs by an external connector which enables the control unit to draw power directly from the distribution system upstream of the circuit breaker. Long-time rating plug Four interchangeable plugs may be used to limit the long-time threshold setting range for higher accuracy. As standard, control units are equipped with the 0.4 to 1 plug. Setting ranges standard Ir = In x 0,4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1 Low-setting option Ir = In x 0.4 0.45 0.50 0.55 0.60 0.65 0.70 0.75 0.8 high-setting option Ir = In x 0.80 0.82 0.85 0.88 0.90 0.92 0.95 0.98 1 off plug no long-time protection External power-supply module The external power-supply module makes it possible to use the display even if the circuit breaker is open or not supplied (for the exact conditions of use, see the electrical diagrams part of this catalogue). This module powers both the control unit and the M2C and M6C programmable contacts. With the Micrologic A control unit, this module makes it possible to display currents of less than 20% of In. With the Micrologic P and H, it can be used to display fault currents after tripping and to time-stamp events (alarms and trips). Characteristics c power supply: v 110/130, 200/240, 380/415 V AC (+ 10% - 15%), consumption 10 VA v 24/30, 48/60, 100/125 V DC (+20% -20%), consumption 10 W c output voltage: 24 V DC; power delivered: 5 W / 5 VA c ripple < 5% c class 2 isolation. Battery module The battery module makes it possible to use the display even if the power supply to the Micrologic control unit is interrupted. Characteristics: c battery run-time: 12 hours (approximately) c mounted on vertical backplate or symmetrical rail 26
056429 Lead-seal cover Spare parts Lead-seal covers A lead-seal cover controls access to the adjustment dials. When the cover is closed: c it is impossible to modify settings using the keypad unless the settings lockout pin on the cover is removed. c the test connector remains accessible. c the test button for the earth-fault and earth-leakage protection function remains accessible. Characteristics c transparent cover for basic Micrologic and Micrologic A control units c non-transparent cover for Micrologic P and H control units. Spare battery A battery supplies power to the LEDs identifying the tripping causes. Battery service life is approximately ten years. A test button on the front of the control unit is used to check the battery condition. The battery may be replaced on site when discharged. 056413 M2C 056430 M6C M2C, M6C programmable contacts These contacts are optional equipment for the Micrologic P and H control units. They are described with the indication contacts for the circuit breakers. characteristics M2C/M6C minimum load 10mA/24V breaking V AC 240 5 capacity (A) 380 3 p.f.: 0.7 V DC 24 1.8 48 1.5 125 0.4 250 0.15 M2C: 24 V DC power supplied by control unit (consumption 100 ma). M6C: external 24 V DC power supply required (consumption 100 ma). 056466 Portable test kit Test equipment Mini test kit The autonomous hand-held mini test kit may be used to: c check operation of the control unit and the tripping and pole-opening system by sending a signal simulating a short-circuit c supply power to the control units for settings via the keypad when the circuitbreaker is open (Micrologic P and H control units). Power source: standard LR6-AA battery. Portable test kit The portable test kit is available in two versions: c the autonomous version with built-in keypad and display c the complete version controlled by a PC. The autonomous version may be used to check: c the mechanical operation of the circuit breaker c the electrical continuity of the connection between the circuit breaker and the control unit c operation of the control unit: v display of settings v operating tests on the ASIC electronic component v automatic and manual tests on protection functions v test on the zone-selective interlocking (ZSI) function v inhibition of the earth-fault protection v inhibition of the thermal memory. The complete version controlled by a PC offers in addition: c comparison of the real tripping curve with the catalogue curves available on the PC c reset of the M2C / M6C contacts and indications c reading and modification of settings and counters c reading of histories and logs c waveform capture c analysis of harmonics. 27
CT CD CE Functions and characteristics Communication COM option in 056431 056401 The COM option is required for integration of the circuit breaker or switch-disconnector in a supervision system. uses the Digipact or Modbus communications protocol for full compatibility with the SMS PowerLogic electrical-installation management systems. An external gateway is available for communication on other networks: c Profibus c Ethernet Digipact «device» communication module. Digipact «craddle» communication module E47073 For fixed devices, the COM option is made up of: c a "device" communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SDE,PF and CH micro-contacts) and its kit for connection to XF and MX communicating voltage releases. For drawout devices, the COM option is made up of: c a "device" communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SDE, PF and CH micro-contacts) and its kit for connection to XF and MX communicating voltage releases c a "craddle" communication module supplied separately with its set of sensors (CE, CD and CT contacts). Status indication by the COM option is independent of the device indication contacts. These contacts remain available for conventional uses. Digipact or Modbus «Device» communication module This module is independent of the control unit. It receives and transmits information on the communication network. An infra-red link transmits data between the control unit and the communication module. Consumption: 30 ma, 24 V. Digipact or Modbus «craddle» communication module This module is independent of the control unit. With Modbus "craddle" communication module, this module makes it possible to address the craddle and to maintain the address when the circuit breaker is in the disconnected position. Consumption: 30 ma, 24 V. XF and MX communicating voltage releases The XF and MX communicating voltage releases are equipped for connection to the "device" communication module. The remote-tripping function (second MX or MN) are independent of the communication option. They are not equipped for connection to the "device" communication module. communication Bus 2 CCM modbus + + + E45183 056431 Modbus «device» communication module Modbus «craddle» communication module OF SDE PF CH 1 «Device» communication module 2 «Craddle» communication module 3 OF, SDE, PF and CH «device» sensors 4 CE, CD and CT «craddle» sensors 5 MX and XF release 3 CD CT MX XF CE 4 5 1 : hard wire : communication bus Note: eco COM The eco COM Modbus is intended to fit the circuit breaker with module display (DMB300, DMC300 ). 28
Overview of functions E47071 POWERLOGIC System Manager Demo File Edit View Setup Control Display Tools Reports Window Help Sampling Mode : MANUAL 5 seconds The switch-disconnectors are compatible only with the Digipact COM option. Time 1,20 1,00 0,80 0,60 % Fundamental 0,40 0,20 0,00 Event Module Phase A-N Voltage - Harmonics Analysis Phase 1-N Harmonics(RMS) Fundamental: H1: 118.09 H2: 0.01 RMS: H3: 0.45 H4: 0.03 H5: 0.45 RMS-H: H6: 0.04 H7: 1.27 Peak: H8: 0.05 H9: 0.42 CF: H10: 0.01 H11: 1.03 THD: H12: 0.07 OK H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 Harmonics The circuit breakers are compatible with the Digipact or Modbus COM option. The COM option may be used with all types of control units to: c identify the device c indicate status conditions c control the device. Depending on the different types of Micrologic (A, P, H) control units, the COM option also offers: c setting of the protection and alarms functions c analysis of the AC-power parameters for operating-assistance and maintenance purposes Ready ONLINE: DEMO No working system 9:30 switch-disconnector with circuit breaker with communication bus communication bus Digipact Modbus Digipact Modbus device identification address c - A P H A P H calibre - - A P H A P H type of device - - P H type of control unit - - A P H A P H type of long-time rating plug - - A P H A P H status indications ON/OFF OF c - A P H A P H spring charged CH c - A P H A P H ready to close PF c - A P H A P H fault-trip SDE - - A P H A P H connected/disconnected/test c - A P H A P H position CE/CD/CT commandes opening / closing MX/XF c - A P H A P H spring charging - - reset of the mechanical - - indicator protections and alarms settings reading of protections settings A P H A P H writing of fine settings in the range P H imposed by the adjustment dials reading/writing of alarms (délestage, relestage, M2C ) P H reading/writing of alarms personnalisables H operating and maintenance aids measurement current A P H A P H voltages, frequency, power, etc. P H P H power quality: fundamental, harmonics H programming of demand metering P H fault readings type of fault A P H interrupted current P H waveform capture on faults H on demand or programmed H histories and logs trip history P H alarm history P H event logs P H indicators counter operation A P H A P H contact wear P H maintenance register P H Note. See the description of the Micrologic control units for further details on protection and alarms, measurements, waveform capture, histories, logs and maintenance indicators. 29
CD3 CD2 CD1 CE6 CE5 CE4 CD3 CD2 CD1 834 824 814 832 822 812 831 821 811 M2C/M6C 484/ Q3 E5 E6 Z5 M1 M2 M3 F2 + V3 E3 E4 Z3 Z4 T3 T4 VN V2 E1 E2 Z1 Z2 T1 T2 F1 - V1 184/ K2 474/ Q2 471/ Q1 181/ K1 182 Ir 84 Reset Micrologic 70 Isd I i Ig I n CE3 CE2 CE1 MN/MX2 MX1 334 324 314 D2/ C12 82 332 322 312 / C13 81 331 321 311 D1/ C11 Ap reset 0 1 2 5 3 XF PF MCH 254 252 251 C2 A2 B2 C3 A3 B3 C1 A1 B1 pulsar SV volets shutters Ue Icu 220/440 100 525 100 690 85 cat.b Icw 85kA/1s Ics = 100% Icu IEC 947-2 EN 60947-2 OK error N 1 N 1 Test BBus com 24V OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 OF4 OF3 OF2 OF1 CT3 CT2 CT1 244 234 224 214 144 134 124 114 44 34 24 14 934 924 914 242 232 222 212 142 132 122 112 42 32 22 12 932 922 912 241 231 221 211 141 131 121 111 41 31 21 11 931 921 911 NX 32 H 2 (V) (ka) 50/60Hz UTE VDE BS CEI UNE AS NEMA com error JBus CD3 CD2 CD1 CE6 CE5 CE4 CD3 CD2 CD1 834 824 814 832 822 812 831 821 811 M2C/M6C 484/ Q3 E5 E6 Z5 M1 M2 M3 F2 + V3 E3 E4 Z3 Z4 T3 T4 VN V2 E1 E2 Z1 Z2 T1 T2 F1 - V1 474/ Q2 184/ K2 471/ Q1 Ir Reset Micrologic 70 Isd I i Ig I n Ap reset 0 1 2 5 3 C2 A2 B2 C3 A3 B3 C1 A1 B1 CE3 CE2 CE1 MN/MX2 MX1 XF PF MCH 84 334 324 314 D2/ C12 254 182 82 332 322 312 / C13 252 81 331 321 311 D1/ C11 251 181/ K1 OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 OF4 OF3 OF2 OF1 CT3 CT2 CT1 244 234 224 214 144 134 124 114 44 34 24 14 934 924 914 242 232 222 212 142 132 122 112 42 32 22 12 932 922 912 241 231 221 211 141 131 121 111 41 31 21 11 931 921 911 Test volets shutters NX 32 H 2 Ue Icu 220/440 100 525 100 690 85 cat.b Icw 85kA/1s Ics = 100% Icu IEC 947-2 EN 60947-2 (V) (ka) 50/60Hz UTE VDE BS CEI UNE AS NEMA Functions and characteristics Communication in a communication network E67968 Software Communication interface RS 232C,Ethernet RS 485 Communication Bus MERLIN GERIN 1 3 Data concentrator DC150 Device Com UC1 UC2 UC3 UC4 M2C UC2 SDE2 CE3 CE2 CE1 MN MX1 XF PF MCH OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 OC24 OC23 OC22 OC21 OC14 OC13 OC12 Com UC1 UC2 UC3 UC4 M2C UC2 SDE2 CE3 CE2 CE1 MN MX1 XF PF MCH OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 OC24 OC23 OC22 OC21 OC14 OC13 OC12 Com UC1 UC2 UC3 UC4 SDE1 Com UC1 UC2 UC3 UC4 SDE1 push OFF push ON O OFF discharged push OFF push ON O OFF discharged Digipact Bus ModBUS Bus Devices Circuit breakers equipped with Micrologic control units may be connected to either a Digipact or Modbus communication bus. The information made available depends on the type of Micrologic control unit (A, P or H) and on the type of communication bus (Digipact or Modbus). Switch-disconnectors may be connected exclusively to the Digipact communication bus. Communication bus Digipact The Digipact bus is the internal bus of the low-voltage switchboard in which the Digipact communicating devices are installed ( with Digipact COM, PM150, SC150, UA150, etc.). This bus must be equipped with a DC150 data concentrator (see the Powerlogic System catalogue). Addresses Addressing is carried out by the DC150 data concentrator. Number of devices The maximum number of devices that may be connected to the Digipact bus is calculated in terms of communication points. These points correspond to the amount of traffic the bus can handle. The total number of points for the various devices connected to a single bus must not exceed 100. If the required devices represent more than 100 points, add a second Digipact internal bus. Communicating device Number of points DC150 data concentrator 4 Micrologic + Digipact COM 4 PM150 4 SC150 4 UA150 4 Length of bus The maximum recommended length for the Digipact internal bus is 200 meters. Bus power source Power is supplied by the DC150 data concentrator (24 V).. 30
Modbus The Modbus RS485 (JBus) system is an open bus on which communicating Modbus devices ( with Modbus COM, PM300, Sepam, Vigilohm, etc.) are installed. All types of PLCs and microcomputers may be connected to the bus. Addresses The software layer of the Modbus protocol can manage up to 255 addresses (1 to 255). The device communication module comprises three addresses linked to: b circuit-breaker manager; b measurement manager; b protection manager. The craddle communication module comprises one address linked to: b the craddle manager. The division of the system into four managers secures data exchange with the supervision system and the circuit-breaker actuators. The manager addresses are automatically derived from the circuit-breaker address @xx entered via the Micrologic control unit (the default address is 47). logic addresses @xx Circuit-breaker manager (1 to 47) @xx + 50 Craddle manager (51 to 97) @xx + 200 Measurement managers (201 to 247) @xx + 100 Protection manager (101 to 147) Number of devices The maximum number of devices that may be connected to the Modbus bus depends on the type of device ( with Modbus COM, PM300, Sepam, Vigilohm, etc.), the baud rate (19200 is recommended), the volume of data exchanged and the desired response time. The RS485 physical layer offers up to 32 connection points on the bus (1 master, 31 slaves). A fixed device requires only one connection point (communication module on the device). A drawout device uses two connection points (communication modules on the device and on the craddle). The number must never exceed 31 fixed devices or 15 drawout devices. Length of bus The maximum recommended length for the Modbus bus is 1200 meters. Bus power source A 24 V DC power supply is required (less than 20% ripple, insulation class II). Communication interface The Modbus bus may be connected to the central processing device in any of three manners: b direct link to a PLC. The communication interface is not required if the PLC is equipped with a Modbus port; b direct link to a computer. The Modbus (RS485) / Serial port (RS232) communication interface is required; b connection to a TCP/IP (Ethernet) network. The Modbus (RS485) / TCP/IP (Ethernet) communication interface is required. Software To make use of the information provided by the communicating devices, software with a Modbus driver must be used. Micrologic utilities This is a set of Modbus drivers that may be used with a PC to: b display the variables (I, U, P, E, etc.) with the DDS (Data Display Software) application; b read/write the settings with the RSS (Remote Setting Software) application; b remotely control (ON / OFF) the device with the CSS (Control Command Software) application. These softwares are available upon request. SMS (System Manager Software) SMS is a software to monitor LV and/or MV electrical energy. The SMS family includes a software range depending on the application and function, from single product monitoring to the management of a multiple building: cpower Meter and Circuit Monitor units clv devices csepam units. 31
Functions and characteristics Connections Overview of solutions Three types of connection are available: c vertical or horizontal rear connection c front connection c mixed connection. The solutions presented are similar in principle for all NT and NW fixed and drawout devices.. 056432 Rear connection horizontal 056433 vertical Simply turn a horizontal rear connector 90 to make it a vertical connector. Front connection 056434 Mixed connection 056435 056436 056437 Note. circuit breakers can be connected indifferently with bare-copper, tinnedcopper and tinned-aluminium conductors, requiring no particular treatment. 32
Optional accessories Type of accessory NT06 to NT16 NW08 to NW63 fixed drawout fixed drawout front rear front rear front rear front rear connection connection connection connection connection connection connection connection Bare-cable connectors and connector shield E47064 Vertical connection adapters E46426 E46426 Cable lug adapters E46427 E46427 Interphase barriers E79058 E46428 E46428 E46428 max. 4000 A Spreaders E46431 E46431 Disconnectable front-connection adapter E46889 Safety shutters with padlocking E47066 E47067 Shutter position indication and locking E47068 Arc chute screen E70745 M replacement kit A set of connection parts is available to allow replacement of a M08 to M32 circuit breaker by a NW without modifying the busbars (please consult us). Mounting on a switchboard backplate using special brackets NT and NW fixed front-connected circuit breakers can be installed on a backplate without any additional accessories. NW circuit breakers require a set of special brackets. 33
push OFF I push ON Functions and characteristics Connections Optional accessories 056438 Bare-cable connectors and connector shield The connectors can be mounted on fixed front-connected devices to allow connection using bare cables. They are supplied with a connector shield. They are designed to connect four 240 mm2 cables each. 056440 Vertical-connection adapters Mounted on front-connected devices or craddle, the adapters facilitate connection to a set of vertical busbars. 056441 Cable-lug adapters Cable-lug adapters are used in conjunction with vertical rear connectors or with vertical-connection adapters. They can be used to connect a number of cables fitted with lugs. To ensure adequate mechanical strength, the connectors must be secured together via spacers. 056415 Interphase barriers These barriers are flexible insulated partitions used to reinforce isolation of connection points in installations with busbars, whether insulated or not. For NT/NW devices, they are installed vertically between rear connection terminals. 056442 Spreaders Mounted on the front or rear connectors, spreaders are used to increase the distance between bars in certain installation configurations. E70746 Arc chute screen For NT fixed, front connected and using vertical-connection adapters front oriented, it is mandatory to install arc chute screen in order to comply with the safety perimeter. O O OFF discharged 34
056443 Disconnectable front-connection adapter Mounted on a fixed front-connected device, the adapter simplifies replacement of a fixed device by enabling fast disconnection from the front. 056445 E47476 Safety shutters Mounted on the craddle, the safety shutters automatically block access to the disconnecting contact cluster when the device is in the disconnected or test positions (degree of protection IP 20) When the device is removed from its craddle, no live parts are accessible. The shutter-locking system is made up of a moving block that can be padlocked (padlock not supplied). The block: * prevents connection of the device * locks the shutters in the closed position For NW08 to NW63 A support at the back of the craddle is used to store the blocks when they are not used. * 2 blocks for NW08 to NW40 * 4 blocks for NW40b to NW63. Shutter position indication and locking on front face This option located on the craddle front plate indicates that the shutters are closed. It is possible to independently or separately padlock the two shutters using one to three padlocks (not supplied). 35
Ir Isd I i Ig I n Ap 100 85 Functions and characteristics Locking On the device E47062 1 2 Micrologic 70 reset O push OFF I push ON O OFF discharged NW 1250 H1 Ui 1000V Uimp 12kV Uimp 8kV Ue (V) 220/240 480/690 Ics = 100% Icu IEC 947-2 Icu (ka) UTE VDE BS CEI UNE NEMA 3 4 5 6 7 8 1 reset button for mechanical trip indication 2 OFF pushbutton 3 OFF position lock 4 electrical closing pushbutton 5 ON pushbutton 6 springs charged indication 7 pushbutton locking 8 contact position indication 9 operation counter 0 1 2 5 3 9 056446 056447 056448 056449 Access to pushbuttons protected by transparent cover Pushbutton locking using a padlock OFF position locking using a padlock OFF position locking using a keylock Pushbutton locking The transparent cover blocks access to the pushbuttons used to open and close the device. It is possible to independently lock the opening button and the closing button. The locking device is often combined with a remote operating mechanism. The pushbuttons may be locked using either: c three padlocks (not supplied) c lead seal c two screws. Device locking in the OFF position The circuit breaker is locked in the OFF position by physically maintaining the opening pushbutton pressed down: c using padlocks (one to three padlocks, not supplied) c using keylocks (one or two different keylocks, supplied). Keys may be removed only when locking is effective (Profalux or Ronis type locks). The keylocks are available in any of the following configurations: c one keylock c one keylock mounted on the device + one identical keylock supplied separately for interlocking with another device c two different key locks for double locking. Profalux and Ronis keylocks are compatible with each other. A locking kit (without locks) is available for installation of one or two keylocks (Ronis, Profalux, Kirk or Castell). Accessory-compatibility For NT: 3 padlocks or 1 keylock For NW: 3 padlocks and/or 2 keylocks Cable-type door interlock This option prevents door opening when the circuit breaker is closed and prevents circuit breaker closing when the door is open. For this, a special plate associated with a lock and a cable is mounted on the right side of the circuit breaker. With this interlock installed, the source changeover function cannot be implemented. 36
On the craddle E47063 1 3 4 5 6 7 8 9 1 mismatch protection 2 door interlock 3 racking interlock 4 keylock locking 5 padlock locking 6 position indicator 7 craddle front plate (accessible with cubicle door closed) 8 racking-handle entry 9 reset button 10 racking-handle storage 2 10 056450 056451 «Disconnected» position locking Mounted on the craddle and accessible with the door closed, these devices lock the circuit breaker in the «disconnected» position in two manners: c using padlocks (standard), up to three padlocks (not supplied) c using keylocks (optional), one or two different keylocks are available. Profalux and Ronis keylocks are available in different options: c one keylock c two different keylocks for double locking c one (or two) keylocks mounted on the device + one (or two) identical keylocks supplied separately for interlocking with another device. A locking kit (without locks) is available for installation of one or two keylocks (Ronis, Profalux, Kirk or Castell). 056417 056452 «Disconnected» position locking by padlocks «Disconnected» position locking by keylocks Door interlock Racking interlock «Connected», «disconnected» and «test» position locking The «connected», «disconnected» and «test» positions are shown by an indicator. The exact position is obtained when the racking handle blocks. A release button is used to free it. On request, the «disconnected» position locking system may be modified to lock the circuit breaker in any of the three positions, «connected», «disconnected» and «test». Door interlock catch Mounted on the right or left-hand side of the craddle, this device inhibits opening of the cubicle door when the circuit breaker is in «connected» or «test» position. It the breaker is put in the «connected» position with the door open, the door may be closed without having to disconnect the circuit breaker. Racking interlock This device prevents insertion of the racking handle when the cubicle door is open. Cable-type door interlock This option is identical for fixed and drawout versions. Racking interlock between crank and OFF pushbutton This option makes it necessary to press the OFF pushbutton in order to insert the racking handle and holds the device open until the handle is removed. 056453 Mismatch protection Automatic spring discharge before breaker removal This option discharges the springs before the breaker is removed from the craddle. Mismatch protection Mismatch protection ensures that a circuit breaker is installed only in a craddle with compatible characteristics. It is made up of two parts (one on the craddle and one on the circuit breaker) offering twenty different combinations that the user may select. 37
Functions and characteristics Indication contacts 056418 Indication contacts are available: c in the standard version for relay applications c in a low-level version for control of PLCs and electronic circuits. M2C and M6C contacts may be programmed via the Micrologic P and H control units. ON/OFF indication contacts (OF) (microswitch type) ON/OFF indication contacts (OF) Two types of contacts indicate the ON or OFF position of the circuit breaker: c microswitch type changeover contacts for NT c rotary type changeover contacts directly driven by the mechanism for NW. These contacts trip when the minimum isolation distance between the main circuit-breaker contacts is reached. OF NT NW supplied as standard 4 4 maximum number 4 12 breaking capacity (A) standard minimum load: 100mA/24V p.f.: 0.3 V AC 240/380 6 10/6* AC12/DC12 480 6 10/6* 690 6 6 V DC 24/48 2.5 10/6* 125 0.5 10/6* 250 0.3 3 low-level minimum load: 2mA/15V DC V AC 24/48 5 6 240 5 6 380 5 3 V DC 24/48 5/2.5 6 125 0.5 6 250 0.3 3 * standard contacts: 10 A; optional contacts: 6 A. 056419 056462 056455 ON/OFF indication contacts (OF) (rotary type) Additional «fault-trip» indication contacts (SDE) Combined contacts «Fault-trip» indication contacts (SDE) Circuit-breaker tripping due to a fault is signalled by: c a red mechanical fault indicator (reset) c one changeover contact (SDE). Following tripping, the mechanical indicator must be reset before the circuit breaker may be closed. SDE NT/NW supplied as standard 1 maximum number 2 breaking capacity (A) standard minimum load: 100mA/24V p.f.: 0.3 V AC 240/380 5 AC12/DC12 480 5 690 3 V DC 24/48 3 125 0.3 250 0.15 low-level minimum load: 2mA/15V DC V AC 24/48 3 240 3 380 3 V DC 24/48 3 125 0.3 250 0.15 Combined «connected/closed» contacts (EF) The contact combines the «device connected» and the «device closed» information to produce the «circuit closed» information. Supplied as an option for NW, it is mounted in place of the connector of an additional OF contact. EF NW maximum number 8 breaking capacity (A) standard minimum load: 100mA/24V p.f.: 0.3 V AC 240/380 6 AC12/DC12 480 6 690 6 V DC 24/48 2.5 125 0.8 250 0.3 low-level minimum load: 2mA/15V DC V AC 24/48 5 240 5 380 5 V DC 24/48 2.5 125 0.8 250 0.3 38
056456 056413 056430 CE, CD and CT «connected/ disconnected/test» position carriage switches M2C programmable contacts: circuit-breaker internal relay with two contacts M6C programmable contacts: circuit-breaker external relay with six independent changeover contacts controlled from the circuit breaker via a threewire connection. «Connected», «disconnected» and «test» position carriage switches Three series of optional auxiliary contacts are available for the craddle: c changeover contacts to indicate the «connected» position (CE) c changeover contacts to indicate the «disconnected» position (CD). This position is indicated when the required clearance for isolation of the power and auxiliary circuits is reached. c changeover contacts to indicate the «test» position (CT). In this position, the power circuits are disconnected and the auxiliary circuits are connected. Additional actuators A set of additional actuators may be installed on the craddle to change the functions of the carriage switches. NT NW contacts CE/CD/CT CE/CD/CT maximum number standard 3 2 1 3 3 3 with additional actuators 9 0 0 6 3 0 6 0 3 breaking capacity (A) standard minimum load: 100mA/24V p.f.: 0.3 V AC 240 8 8 AC12/DC12 380 8 8 480 8 8 690 6 6 V DC 24/48 2.5 2.5 125 0.8 0.8 250 0.3 0.3 low-level minimum load: 2mA/15V DC V AC 24/48 5 5 240 5 5 380 5 5 V DC 24/48 2.5 2.5 125 0.8 0.8 250 0.3 0.3 M2C / M6C programmable contacts These contacts, used with the Micrologic P and H control units, may be programmed via the control unit keypad or via a supervisory station with the COM communication option. They require an external power supply module. They indicate: c the type of fault c instantaneous or delayed threshold overruns. They may be programmed: c with instantaneous return to the initial state c without return to the initial state c with return to the initial state following a delay. characteristics M2C/M6C minimum load 100mA/24V breaking V AC 240 5 capacity (A) 380 3 p.f.: 0.7 V DC 24 1.8 48 1.5 125 0.4 250 0.15 E59469 474 484 M2C: 24 V DC power supplied by control unit (consumption 100 ma). M6C: external 24 V DC power supply required (consumption 100 ma). 1 3 7 9 6 4 12 10 18 16 24 22 E59470 S1 S2 S3 S4 S5 S6 S1 471 S2 5 11 2 8 14 20 39
Functions and characteristics Remote operation Remote ON / OFF 056407 Two solutions are available for remote operation of devices: c a point-to-point solution c a bus solution with the COM communication option. The remote ON / OFF function is used to remotely open and close the circuit breaker. It is made up of: c an electric motor (MCH) equipped with a «springs charged» limit switch contact (CH) c two voltage releases: v a closing release (XF) v an opening release (MX). Optionally, other functions may be added: c a «ready to close» contact (PF) c an electrical closing pushbutton (BPFE) c remote reset following a fault. A remote-operation function is generally combined with: c device ON / OFF indication (OF) c «fault-trip» indication (SDE). Wiring diagram of a point-to-point remote ON / OFF function E46041 spring charged opening order closing order ready to close fault open closed B3 B2 C2 A2 252 254 82 84 12 14 CH MCH MX XF PF SDE OF1 B1 C1 A1 251 81 11 Wiring diagram of a bus-type remote ON / OFF function E46042 spring charged B3 opening order B2 C2 closing order C3 A2 A3 MCH CH MXcom XFcom Note: An opening order always takes priority over a closing order. If opening and closing orders occur simultaneously, the mechanism discharges without any movement of the main contacts. The circuit breaker remains in the open position (OFF). In the event of maintained opening and closing orders, the standard mechanism provides an anti-pumping function by blocking the main contacts in open position. Anti-pumping function. After fault tripping or intentional opening using the manual or electrical controls, the closing order must first be discontinued, then reactivated to close the circuit breaker. When the automatic reset after fault trip (RAR) option is installed, to avoid pumping following a fault trip, the automatic control system must take into account the information supplied by the circuit breaker before issuing a new closing order or blocking the circuit breaker in the open position (information on the type of fault, e.g. overload, short-time fault, earth fault, earth leakage, short-circuit, etc.). B1 OF PF SDE CH C1 A1 COM supervisor 40
056468 056420 Electric motor (MCH) The electric motor automatically charges and recharges the spring mechanism when the circuit breaker is closed. Instantaneous reclosing of the breaker is thus possible following opening. The spring-mechanism charging handle is used only as a backup if auxiliary power is absent. The electric motor (MCH) is equipped as standard with a limit switch contact (CH) that signals the charged position of the mechanism (springs charged). characteristics power supplyv AC 50/60 Hz 48/60-100/130-200/240-277- 380/415-400/440-480 V DC 24/30-48/60-100/125-200/250 operating threshold 0.85 to 1.1 Un consumption (VA or W) 180 motor overcurrent 2 to 3 In for 0.1 second charging time maximum 3 seconds for NT maximum 4 seconds for NW operating frequency maximum 3 cycles per minute CH contact 10 A at 240 V 056421 056457 Electric motor (MCH) for NT Electric motor (MCH) for NW XF and MX voltage releases Ready to close contacts (PF) Voltage releases (XF and MX) Closing release (XF) The XF release remotely closes the circuit breaker if the spring mechanism is charged. Opening release (MX) The MX release instantaneously opens the circuit breaker when energised. The supply can be maintained or automatically disconnected. characteristics XF MX power supplyv AC 50/60 Hz 24-48 - 100/130-200/250-277 - 380/480 V DC 12-24/30-48/60-100/130-200/250 operating threshold 0.85 to 1.1 Un 0.7 to 1.1 Un consumption (VA or W) hold: 4.5 hold: 4.5 pick-up: 200 pick-up: 200 circuit-breaker response 55 ms ± 10 ( NT) 50 ms ± 10 time at Un 70 ms ± 10 (NW i 4000A) 80 ms ± 10 (NW > 4000A) Ready to close contact (PF) The ready to close position of the circuit breaker is indicated by a mechanical indicator and a PF changeover contact. This signal indicates that all the following are valid: c the circuit breaker is in the OFF position c the spring mechanism is charged c a maintained opening order is not present: v MX energised v fault trip v remote tripping (second MX or MN) v device not completely racked in v device locked in OFF position v device interlocked with a second device. characteristics NT/NW supplied as standard 1 maximum number 1 breaking capacity standard minimum load: 100mA/24V p.f.: 0.3 V AC 240/380 5 AC12/DC12 480 5 690 3 V DC 24/48 3 125 0.3 250 0.15 low-level minimum load: 2mA/15V DC V AC 24/48 3 240 3 380 3 V DC 24/48 3 125 0.3 250 0.15 41
Functions and characteristics Remote operation Remote ON / OFF (cont.) 056469 Electrical closing pushbutton (BPFE) Located on the front panel, this pushbutton carries out electrical closing of the circuit breaker. It is generally associated with the transparent cover that protects access to the closing pushbutton. Electrical closing via the BPFE pushbutton takes into account all the safety functions that are part of the control/monitoring system of the installation. The BPFE connects to the closing release (XF) in place of the COM module. E46044 remote closing order Electrical closing pushbutton (BPFE). BPFE A2 A3 XF com A1 Remote reset after fault trip Electrical reset after fault trip (Res) Following tripping, this function resets the fault trip indication contacts (SDE) and the mechanical indicator and enables circuit breaker closing. Power supply: 110 / 130 V AC and 200 / 240 V AC E46045 reset order K2 SDE2 K1 Automatic reset after fault trip (RAR) Following tripping, a reset of the mechanical indicator (reset button) is no longer required to enable circuit-breaker closing. The mechanical (reset button) and electrical (SDE) indications remain in fault position until the reset button is pressed. 42
Remote tripping 056458 This function opens the circuit breaker via an electrical order. It is made up of: c a shunt release (second MX) c or an undervoltage release (MN) c or a delayed undervoltage release (MN + delay unit). The delay unit, installed outside the circuit breaker, may be disabled by an emergency OFF button to obtain instantaneous opening of the circuit breaker. Wiring diagram for the remote-tripping function E46043 opening order E46553 opening order E46554 delayed opening order time delay unit 10 12 3 6 056421 MX or MN voltage release C12 D2 instantaneous opening order D2 MX2 MN MN C11 D1 D1 Voltage releases (second MX) When energised, the MX voltage release instantaneously opens the circuit breaker. A continuous supply of power to the second MX locks the circuit breaker in the OFF position. characteristics power supplyv AC 50/60Hz 24-48 - 100/130-200/250-277- 380/480 V DC 12-24/30-48/60-100/130-200/250 operating threshold 0.7 to 1.1 Un permanent locking function 0.85 to 1.1 Un consumption (VA or W) pick-up: 200 hold: 4.5 circuit-breaker response 50 ms ± 10 time at Un Instantaneous voltage releases (MN) The MN release instantaneously opens the circuit breaker when its supply voltage drops to a value between 35% and 70% of its rated voltage. If there is no supply on the release, it is impossible to close the circuit breaker, either manually or electrically. Any attempt to close the circuit breaker has no effect on the main contacts. Circuit-breaker closing is enabled again when the supply voltage of the release returns to 85% of its rated value. characteristics power supplyv AC 50/60 Hz 24-48 - 100/130-200/250-380/480 V DC 24/30-48/60-100/130-200/250 operating opening 0.35 to 0.7 Un threshold closing 0.85 Un consumption (VA or W) pick-up: 200 hold: 4.5 circuit-breaker response 40 ms ± 5 pour NT time at Un 90 ms ± 5 pour NW MN delay units To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of the MN release can be delayed. This function is achieved by adding an external delay unit in the MN voltage-release circuit. Two versions are available, adjustable and non-adjustable. characteristics power supply non-adjustable 100/130-200/250 V AC 50-60 Hz /DC adjustable 48/60-100/130-200/250-380/480 operating threshold opening 0.35 to 0.7 Un closing 0.85 Un consumption (VA or W) pick-up: 200 hold: 4.5 circuit-breaker response non-adjustable 0.25 s time at Un adjustable 0.5 s - 0.9 s - 1.5 s - 3 s 43
Functions and characteristics Accessories 056463 Auxiliary terminal shield (CB) Optional equipment mounted on the craddle, the shield prevents access to the terminal block of the electrical auxiliaries. 056464 Operation counter (CDM) The operation counter sums the number of operating cycles and is visible on the front panel. It is compatible with manual and electrical control functions. E47535 Escutcheon (CDP) Optional equipment mounted on the door of the cubicle, the escutcheon increases the degree of protection to IP 40 (circuit breaker installed free standing: IP30). It is available in fixed and drawout versions. Blanking plate (OP) for escutcheon Used with the escutcheon, this option closes off the door cut-out of a cubicle not yet equipped with a device. It may be used with the escutcheon for both fixed and drawout devices. Transparent cover (CP) for escutcheon Optional equipment mounted on the escutcheon, the cover is hinged and secured by a screw. It increases the degree of protection to IP 54, IK10. It adapts to both fixed and drawout devices. Escutcheon (CDP) with blanking plate 016819 Transparent cover (CP) for Escutcheon 44
45
Functions and characteristics Source-changeover systems Presentation 87921 Remote-operated source-changeover systems This is the most commonly employed system. No intervention by human operators is required. The switch from the normal to the replacement source is controlled electrically. A remote-operated source-changeover system is made up of two or three circuit breakers or switch-disconnectors linked by an electrical interlocking system implemented in a number of manners. Device control is backed up by a mechanical interlocking system that protects against the consequences of an electrical malfunction and inhibits incorrect manual operation. 029693 Service sector: c hospital operating rooms c safety systems for tall buildings c computer rooms (banks, insurance companies, etc.) c lighting systems in shopping centres. Automatic source-changeover systems When a remote-operated source-changeover system is combined with an automatic controller, the sources can be controlled automatically according to a number of programmed operating modes. This solution provides optimal energy management: c switching to a replacement source depending on any external conditions; c management of power sources; c regulation; c emergency source replacement, etc. A communications function for dialogue with a supervisor is available for the automatic controller. Industry: c assembly lines c propulsion systems on ships c essential auxiliaries in thermal power stations. IMG0021 Infrastructure: c port and railway installations c runway lighting systems c control systems for military installations. 46
Mechanical interlocking Electrical interlocking of two or three devices is used to create a remoteoperated source-changeover system. A basic mechanical interlocking system enhances the reliability of system operation. To ensure a continuous supply of power, certain electrical installations are connected to two power sources: c a normal source N; c a replacement source R which supplies the installation when source N is not available. A source-changeover system switches between the two sources. The system may include an automatic controller which manages switching according to external conditions. A source-changeover system may comprise two or three circuit breakers or switch-disconnectors. 056427 Interlocking of two devices using connecting rods The two devices must be stack mounted. This function requires: c an adaptation fixture on the right side of each device; c a set of connecting rods with no-slip adjustments. The complete interlock kit is supplied for assembly by the customer. Maximum vertical distance between the fixing planes: 900 mm Combinations of Normal and Replacement devices NT and NW devices may not be used together in a source-changeover system. The two devices must both be fixed devices or drawout devices to maintain correct alignment of the mechanisms. Interlocking of two or three devices using cables Using cables, the devices may be stack mounted or installed side-by-side. Interlocking of two devices ( NT or NW) This function requires: c an adaptation fixture on the right side of each device; c a set of cables with no-slip adjustments. Maximum distance between the fixing planes (vertical or horizontal): 2000 mm Interlocking of three devices (only NW) This function requires: c an adaptation fixture (different for each type of interlocking) on the right side of each device; c two or three sets of cables with no-slip adjustments. Maximum distance between the fixing planes (vertical or horizontal): 1000 mm Installation The complete interlock kit is supplied for assembly by the customer. Combinations of Normal and Replacement devices All combinations of NT and NW devices may be used together in a sourcechangeover system. Interlocked devices may be fixed or drawout, three or four pole, with different ratings and sizes. 47
Functions and characteristics Source-changeover systems Electrical interlocking Electrical interlocking is used with the mechanical interlocking system. It controls switching between sources. An automatic controller may be added to take into account information from the distribution system. Electrical interlocking requires an electrical control device. This function can be implemented in one of two ways: c using the IVE electrical interlocking unit c by an electrician using the electrical systems presented in the diagrams in the Source-changeover systems section of this catalogue. Characteristics of the IVE unit c external connection terminal block: v inputs: control of devices v outputs: status of the SDE contacts on the Normal and Replacement devices. c connector to the two Normal and Replacement devices: v inputs: - status of the OF contacts on each device (ON or OFF) - status of the SDE contacts on the Normal and Replacement devices v outputs: power supply for motor mechanisms. c control voltage: v 24 to 250 V DC v 48 to 415 V 50/60 Hz v 440 V 60 Hz. The control voltage for the IVE electrical interlocking unit must be identical to that of the operating mechanism. Necessary equipment Each device must be equipped with: c a remote-operation system made up of: v MCH gear motor v MX or MN opening release v XF closing release v PF ready to close contact c an available OF contact c a CE connected-position carriage switch on drawout devices. E30738 E30739 E30737 E30736 types of mechanical interlocking possible combinations standard configurations ref. (presented in section Source-changeover systems ) 2 devices Q1 Q2 3 devices: 2 Normal sources and 1 Replacement source Q1 Q2 Q3 3 devices: 3 sources, only 1 device closed Q1 Q2 Q3 3 devices: 2 sources and 1 coupling Q1 Q2 Q3 Q1 Q2 electrical interlocking 51156903 0 0 automatic controller with permanent replacement source 51156904 0 1 automatic controller with engine generator set 51156905 1 0 Q1 Q2 Q3 automatic controller with permanent replacement source: 0 0 0 without lockout after fault 51156906 1 0 0 with lockout after fault 51156907 0 0 1 automatic controller with engine generator set: 1 1 0 without lockout after fault 51156908 0 1 0 with lockout after fault 51156909 Q1 Q2 Q3 electrical interlocking: 0 0 0 without lockout after fault 51156910 1 0 0 with lockout after fault 51156911 0 1 0 0 0 1 Q1 Q2 Q3 electrical interlocking: 0 0 0 without lockout after fault 51156912 1 0 0 with lockout after fault 51156913 0 1 0 automatic controller 51156914 0 0 1 1 1 0 0 1 1 1 0 1 Lockout after fault option: this option makes it necessary to manually reset the device following fault tripping. 48
Associated automatic controllers 053058R 053058 By combining a remote-operated sourcechangeover system with an integrated BA or UA automatic controller, it is possible to automatically control source transfer according to user-selected sequences. These controllers can be used on sourcechangeover systems comprising 2 circuit breakers. For source-changeover systems comprising 3 circuit breakers, the automatic control diagram must be prepared by the installer as a complement to to diagrams provided in the electrical diagrams section of this catalogue. BA controller UA controller controller BA UA compatible circuit breakers All Compact NS and circuit breakers 4-position switch Automatic operation c c Forced operation on Normal source c c Forced operation on Replacement source c c Stop (both Normal and Replacement sources off) c c automatic operation Monitoring of the Normal c c source and automatic changeover Generator set startup control c Generator set shutdown control c Load shedding and reconnection of non-priority circuits c Changeover to the Replacement c source if one of the phases of the Normal phase is absent test By opening the P25M circuit breaker c supplying the controller By pressing the test button on the front of the controller c indications Circuit breaker status indication on the front c c of the controller: on, off, fault trip Automatic mode indicating contact c c other functions Selection of type of Normal source c (single-phase or three-phase) Voluntary transfer to Replacement source c c (e.g. energy management commands) During peak-tariff periods (energy management commands), c forced operation on Normal source if Replacement source not operational Additional contact (not part of controller). c c Transfer to Replacement source only if contact is closed. (e.g. used to test the frequency of UR). Setting of maximum startup time c for the replacement source options communication option c power supply control voltages (1) 220 to 240 V 50/60 Hz c c 380 to 415 V 50/60 Hz c c 440 V 60 Hz c c operating thresholds undervoltage 0.35 Un i voltage i 0.7 Un c c phase failure 0.5 Un i voltage i 0.7 Un c voltage presence voltage u 0.85 Un c c characteristics of output contacts rated thermal current (A) 8 minimum load 10 ma at 12 V AC DC utilisation category (IEC 947-5-1) AC12 AC13 AC14 AC15 DC12 DC13 operational current (A) 24 V 8 7 5 6 8 2 48 V 8 7 5 5 2-110 V 8 6 4 4 0.6-220/240 V 8 6 4 3 - - 250 V - - - - 0.4-380/415 V 5 - - - - - 440 V 4 - - - - - 660/690 V - - - - - - (1) The controller is powered by the ACP auxiliaries control plate. The same voltage must be used for the ACP plate, the IVE unit and the circuit breaker motor mechanisms. If this voltage is the same as the source voltage, then the Normal and Replacement sources can be used directly for the power supply. If not, a BC type or equivalent isolation transformer must be used. 49
Functions and characteristics Display modules 057454 E79078 Perfectly integrated in the Compact and ranges, Display modules are designed for use with Micrologic control units to provide instant and highly intuitive access to all the information provided by the circuit breakers, including device status, current, voltage and power values, etc. DMB300 display module: basic and harmonic measurements DMC300 display module: measurements, harmonic analysis, diagnosis Associated Micrologic control unit A = Micrologic A P = Micrologic P H = Micrologic H DMB300 and DMC300 display modules use the power and communications capabilities of the Micrologic control units to centralise the display of electrical values, status conditions and alarms of one or more Compact or circuit breakers. The mounting and cabling system for the display modules ensures fast, easy and reliable installation. Start-up is immediate with no configuration or programming required. Digipact display modules are high-performance devices combining: c simple and easy-to-read dials c powerful and accurate digital processing. Their small size and extensive communications capabilities make for easy and flexible installation and operation. Display modules DMB300 DMC300 Associated circuit breakers Type Compact or equipped with Micrologic control units Number 1 to 4 1 to 16 Display Screen type Black and white Colour, touch screen Screen size 240 x 64 pixels 5, 320 x 240 pixels Entry 5 buttons Touch screen Information displayed Currents (per phase) Currents I1, I2, I3, IN A P H A P H Maximum current A P H A P H Earth-fault and earth-leakage currents A P H A P H Demand current P H P H Maximum demand current P H P H Total harmonic distortion (THD) H H Maximum total harmonic distortion H H Amplitudes of individual harmonics H Waveform capture H Voltages Phase-to-phase voltages (U1-2, U2-3, U3-1) P H P H Minimum/maximum phase-to-phase voltages P H P H Phase-to-neutral voltages (V1-N, V2-N, V3-N) P H P H Minimum/maximum phase-to-neutral voltages P H Frequency P H P H Voltage imbalance (% per phase) P H P H Total harmonic distortion (% per phase) H H Maximum total harmonic distortion (% per phase) H H Amplitudes of individual harmonics H H Power Active (P), reactive (Q) and apparent (S) power P H P H Power factor and cos P H P H Maximum power (P, Q, S) P H P H Demand power (P, Q, S) P H P H Maximum demand power (P, Q, S) P H P H Metering Active, reactive and apparent energy P H P H On-line help On-line help is available for each type of information supplied by the module Circuit-breaker diagnostics Identification of control units A P H A P H Reading of protections A P H A P H Circuit-breaker status A P H A P H Type of trip A P H A P H Current alarms P H P H Maintenance indicator P H Installation diagnosis Indication of faulty devices A P H Fault log A P H Installation and start-up Mounting Mounted through door, without tools, using 6 spring-clips supplied with the mod. Connection Prefabricated wiring systems 50
Ir Isd I i Reset Micrologic 70 Ig I n Ap reset Ir Isd I i Reset Micrologic 70 Ig I n Ap reset NX 32 H 2 Ue Icu 220/440 100 525 100 690 85 cat.b Icw 85kA/1s Ics = 100% Icu IEC 947-2 EN 60947-2 (V) (ka) 50/60Hz UTE VDE BS CEI UNE AS NEMA NX 32 H 2 Ue Icu 220/440 100 525 100 690 85 cat.b Icw 85kA/1s Ics = 100% Icu IEC 947-2 EN 60947-2 (V) (ka) 50/60Hz UTE VDE BS CEI UNE AS NEMA Ir Micrologic 70 Isd I i Ig I n Ap reset Ir Micrologic 70 Isd I i Ig I n Ap reset O push OFF 0 1 2 5 3 O push OFF 0 1 2 5 3 O push OFF 0 1 2 5 3 I push ON I push ON I push ON NW 1251 H1 Ics = 100% Icu IEC 947-2 UTE VDE BS CEI UNE NEMA Ics = 100% Icu IEC 947-2 UTE VDE BS CEI UNE NEMA Ui 1000V Uimp 12kV Uimp 8kV Ue Icu (V) (ka) 220/240 100 480/690 85 NW 1251 H1 Ics = 100% Icu IEC 947-2 UTE VDE BS CEI UNE NEMA Ir Micrologic 70 Isd I i Ig I n Ap reset Ui 1000V Uimp 12kV Uimp 8kV Ue Icu (V) (ka) 220/240 100 480/690 85 NW 1251 H1 Ui 1000V Uimp 12kV Uimp 8kV Ue Icu (V) (ka) 220/240 100 480/690 85 4 3 2 1 select Digipact DMB300 IN IN I U P com Ir Micrologic 70 Isd I i Ig I n Ap reset Ir Micrologic 70 Isd I i Ig I n Ap reset Ir Micrologic 70 Isd I i Ig I n Ap reset 2 O push OFF 0 1 2 5 3 I push ON O push OFF 0 1 2 5 3 I push ON NW 1251 H1 NW 1251 H1 Ics = 100% Icu IEC 947-2 UTE VDE BS CEI UNE NEMA Ir Micrologic 70 Isd I i Ig I n Ap reset Ui 1000V Uimp 12kV Uimp 8kV Ue Icu (V) (ka) 220/240 100 480/690 85 ON Ics = 100% Icu IEC 947-2 ON UTE VDE BS CEI UNE NEMA Ir Reset Micrologic 70 Isd Ig Ap reset I i I n 0 1 2 5 3 O push OFF 0 1 2 5 3 O push OFF 0 1 2 5 3 O push OFF 0 1 2 5 3 I push ON I push ON I push ON Ics = 100% Icu IEC 947-2 UTE VDE BS CEI UNE NEMA Ui 1000V Uimp 12kV Uimp 8kV Ue Icu (V) (ka) 220/240 100 480/690 85 NW 1251 H1 Ics = 100% Icu IEC 947-2 UTE VDE BS CEI UNE NEMA Ui 1000V Uimp 12kV Uimp 8kV Ue Icu (V) (ka) 220/240 100 480/690 85 NW 1251 H1 Ics = 100% Icu IEC 947-2 UTE VDE BS CEI UNE NEMA Ir Micrologic 70 Isd I i Ig I n Ap reset Ui 1000V Uimp 12kV Uimp 8kV Ue Icu (V) (ka) 220/240 100 480/690 85 NW 1251 H1 Ui 1000V Uimp 12kV Uimp 8kV Ue Icu (V) (ka) 220/240 100 480/690 85 Test volets shutters NX 32 H 2 Ue Icu 220/440 100 525 100 690 85 cat.b Icw 85kA/1s Ics = 100% Icu IEC 947-2 EN 60947-2 (V) (ka) 50/60Hz UTE VDE BS CEI UNE AS NEMA Wiring system The wiring system is designed for low-voltage power switchboards. Installation requires no tools or special skills. The prefabricated wiring ensures both data transmission (ModBus protocol) and 24V DC power distribution for the display module and the communications modules on the Micrologic control units. Connection of DMB300 display module E59081A 24 V DC power OUT n 1 n 2 n 3 n 4 IN OUT n 1 n 2 n 3 n 4 ON 1 2 IN OUT n 1 n 2 n 3 n 4 ON 4? n 2 n 3 n 4 ON 3 push OFF push ON O OFF discharged E59178 1 CDM 303: Connection cable between display module and junction block E59180A 2 discharged O OFF ON IN OUT n 1 n 2 n 3 n 4 ON discharged O OFF CJB 306 junction block E59179 3 E59082A Connection of DMC300 display module Maximum distance between module and circuit breaker: 1200 m 2 5 1 4 2 circuit breakers equipped with Micrologic control units and the ModBus eco COM option 2 E59176A CCP 303: Connection cable between or Compact and junction block 4 discharged O OFF discharged O OFF 3 push OFF push ON O OFF discharged 3 3 CCR 301: Roll of RS485 cable (2 RS485 wires + 2 power supply wires) discharged O OFF discharged O OFF E59177A 5 push OFF push ON O OFF discharged discharged O OFF discharged O OFF CSD 309: SubD 9-pin connector for colour-coded connection of wires to screw terminals circuit breakers equipped with Micrologic control units and the ModBus eco COM option 51
52
Dimensions and connection Presentation 1 Functions and characteristics 9 NT06 to NT16 Fixed 3/4-pole device 54 Drawout 3/4-pole device 58 NW08 to NW32 Fixed 3/4-pole device 62 Drawout 3/4-pole device 64 NW40 Fixed 3/4-pole device 66 Drawout 3/4-pole device 68 NW40b to NW63 Fixed 3/4-pole device 70 Drawout 3/4-pole device 72 NT/NW accessories 74 NT/NW external modules 76 Electrical diagrams 81 Installation recommendations 91 Additional characteristics 115 References 121 53
Dimensions and connection NT06 to NT16 circuit breakers Fixed 3/4-pole device Dimensions E47191B 105 (3P) 175 (4P) 188 105 94 Y E47190B 178 136 105 210 X X 123 6,5 39 15 150,5 F 3 13 125 (3P) 195 (4P) 125 13 Bottom mounting (on base plate or rails) Rear mounting detail (on upright or backplate) E47193A X E47192B Y 6 Ø6,5 25 100 E47194B Y 4 Ø6,5 18 mini 39 maxi 39 100 136,5 F 125 (3P) 195 (4P) 125 F X 125 154 62,5 77 125 (3P) 195 (4P) 125 Safety clearances Door cutout Rear panel cutouts E59443A A (*) E47195A B A (*) B E47196A 194 mini (3P) 264 mini (4P) Y 194 mini E47197A Y 62 44 X 216 (1) 266 (2) X 40 130 F 194 (1) 244 (2) 97 (1) 122 (2) 108 (1) 133 (2) 100 (3P) 170 (4P) 100 62 106 Insulated Metal Energised parts parts parts A 0 0 100 B 0 0 60 F : Datum. (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 50 mm is required to remove the arc chutes. An overhead clearance of 20 mm is required to remove the terminal block. 54
E47210A Connections Horizontal rear connection Detail E47198A E47199A 43,5 15 E47200A 70 70 70 123 67,5 N Y X 67,5 15 123 E47201B 44 25 9,5 12,5 F 167,5 12,5 60 2 Ø11 Vertical rear connection Detail E47202A E47203A 43,5 E47204A 70 70 70 15 View A 97 X N Y 97 167,5 E47205B 60 12,5 12,5 9,5 F 44 2 Ø11 25 View A detail Front connection Detail E47206A E47207B 12 E47208A 70 70 70 View A 150 N Y Top connection Bottom connection X 326 E47209B 44 25 9,5 2 Ø11 13 150 2 Ø11 13 25 44 9,5 164 View A detail F Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer 55
Dimensions and connection NT06 to NT16 circuit breakers Fixed 3/4-pole device Connection Front connection with spreaders E47211A E47212A E47213A 95 95 70 70 View A 202 15 Y X 434 E47214A 95 95 95 70 70 70 View A 202 12,5 12,5 15 N Y 179 F Rear connection with spreaders E47219A E47220A 98 E47221A 95 95 70 70 123 15 82,5 X 15 52,5 219,5 123 E47222A Y 95 95 95 70 70 70 234,5 12,5 12,5 F N Y Spreader detail Middle left or middle right spreader for 4P Middle spreader for 3P Left or right spreader for 4P Left or right spreader for 3P E47234A 77 38,5 25 = = 13,5 E47292A 77 38,5 25 = = 13,5 E47293A 77 38,5 25 = = 13,5 E47294A 77 38,5 25 = = 13,5 82 52 30 15 5 Ø11 82 52 15 30 5 Ø11 82 52 30 15 5 Ø11 82 52 30 15 5 Ø11 25 25 25 25 52 52 52 52 View A detail F : Datum Note: X and Y are the symmetry planes for a 3-pole device. 56
E47210A Connections Front connection via vertical connection adapters E47215A E47216A 116,5 E47217A 70 70 70 15 View A 21 221 N Y X 472 E47218A 25 = 89 = 12,5 15 21 221 21 (1) 101 3 Ø11 21 15 20 F 190,5 253 View A detail Front connection via vertical connection adapters fitted with bare cable connectors. E47231A E47232A 221 50 15 E47233A 70 70 70 15 View A 271 21 221 N Y 15 X 572 E47230A 17 184 50 50 50 80 50 21 221 271 5 Ø13 5 Ø11 View A detail 50 340,5 15 357,5 F Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer (1) 2 connection possibilities on vertical connection adapters (21 mm between centres) 57
Dimensions and connection NT06 to NT16 circuit breakers Drawout 3/4-pole device Dimensions E47171C 210 mini E47172A 127,5 (3P) 197,5 (4P) 188 Y 94 160,5 46 (*) 199 X X 5 123 60 mini 45,5 F 231 90 (3P) 160 (4P) 90 (*) disconnected position Bottom mounting (on base plate or rails) Rear mounting detail (on upright or backplate) E47174B X E47173B Y E47175B Y 4 Ø6,5 6 Ø6,5 X 150 24 25 100 25 100 50 216 231 F 90 (3P) 160 (4P) 90 F 109 (3P) 179 (4P) 109 Safety clearances Door cutout Rear panel cutout E59444A A E47176B B C C B E47177B 170 mini (3P) 240 mini (4P) 230 mini Y E47178A Y X 259 (1) 303 (2) X 117 234 40 180 F 161 (1) 183 (2) 109 (1) 130,8 (2) 259 (1) 307 (2) 102,5 (3P) 172,5 (4P) 102,5 Insulated Metal Energised parts parts parts A 0 0 30 B 10 10 60 C 0 0 30 F : Datum. (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. 58
E47189A Connections Horizontal rear connection Detail E47179A E47180A 49 15 E47181A 70 70 70 67,5 X 228 67,5 114 N Y 267,5 15 E47201B 44 25 9,5 12,5 F 12,5 60 2 Ø11 Vertical rear connection Detail E47182A E47183A 49 70 70 70 15 View A 97 E47184A X 97 N Y 267,5 E47205B 60 12,5 12,5 9,5 F 44 2 Ø11 25 View A detail Front connection Detail E47185A E47186B 15 12,5 E47187A 70 70 70 View A 171 N Y X 336 Top connection Bottom connection 140 9,5 44 25 2 Ø11 37,9 9,5 F 235 12,5 E47188B 83 131 26 100 52 Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer 26 37,9 9,5 View A detail 25 44 2 Ø11 9,5 59
Dimensions and connection NT06 to NT16 circuit breakers Drawout 3/4-pole device Connection Front connection with spreaders E47223A E47224A E47225A 95 95 70 70 View A 238 223 X Y 207 192 E47226A 95 95 95 70 70 70 12,5 12,5 View A 250 F N Y Rear connection with spreaders Middle left or middle right spreader for 4P Middle spreader for 3P Left or right spreader for 4P Left or right spreader for 3P E47234A 77 38,5 25 = = 13,5 E47292A 77 38,5 25 = = 13,5 E47293A 77 38,5 25 = = 13,5 E47294A 77 38,5 25 = = 13,5 82 52 30 15 5 Ø11 82 52 15 30 5 Ø11 82 52 30 15 5 Ø11 82 52 30 15 5 Ø11 25 25 25 25 52 52 52 52 View A detail F : Datum Note: X and Y are the symmetry planes for a 3-pole device. 60
E47189A Connections Front connection via vertical connection adapters fitted with bare cable connectors. E47227A E47228A 50 15 E47229A 70 70 70 15 View A 71 292 21 171 N Y 15 X 583 E472230A 17 184 50 50 50 140 21 261 80 50 71 50 View A detail 5 Ø13 5 Ø11 F 193,5 15 Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer 61
Dimensions and connection NW08 to NW32 circuit breakers Fixed 3/4-pole device Dimensions E46050A 189 (3P) 304 (4P) 308 189 154 Y E46055A 191 150 260 X X 161 11 7 57 233 11 200 (3P) 315 (4P) 200 11 Mounting on base plate or rails Mounting detail E46051A X E46052A Y Ø9,5 25 124 162 15 mini 60 maxi 72 38 162 218,5 F F 200 (3P) 315 (4P) 200 Ø9,5 Safety clearances Door cutout E59445A A (*) E46054A B A (*) B E46053A 295 mini (3P) 410 mini (4P) Y 295 mini X 270 (1) 316 (2) 135 (1) 158 (2) 15 205 F 325 (1) 364 (2) 162,5 (1) 182 (2) Insulated Metal Energised parts parts parts A 0 0 100 B 0 0 60 F : Datum. (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 110 mm is required to remove the arc chutes. An overhead clearance of 20 mm is required to remove the terminal block. 62
masterpact II Ue (V) 690 50kA/1s E46004A NX 08 HA10 Ui 1000V Uimp 12kV IEC 947-2 50/60Hz EN 60947-2 UTE VDE BS CEI UNE AS NBMA MERLIN GERIN Connections Horizontal rear connection Détail E46086A E46351A 27 E46056A 115 115 115 E46087A X Vertical rear connection Detail X F E46089A 233,5 20 20 150 20 68 27 141 93 161 E46059A E46058A E46057A 25 14,5 N = N 76 38 = 3 Ø11,5 47 115 13 12,5 13 12,5 47 14,5 115 Y Y 115 20 View A F 233,5 = = 76 38 3 Ø11,5 25 View A detail Front connection Detail E46088A E46090A 20 12,5 E46060A 115 115 115 View A 230,5 N Y Top connection Bottom connection X 475 E46061B 76 25 25 13 12,5 219,5 3 Ø11,5 3 Ø11,5 12,5 F 219 12,5 View A detail 25 25 13 Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer 63
Dimensions and connection NW08 to NW32 circuit breakers Drawout 3/4-pole device Dimensions E46506A 400 mini E46352A 220,5 (3P) 335,5 (4P) 308 Y 154 220,5 56 (*) 238,5 X X 200,5 128 60 mini 11 383,5 400 200 (*) Disconnected position Mounting on base plate or rails Mounting detail E46354A X E46353B Y 2 Ø11,5 x 22 10 Ø11,5 110 103 175 283 F Ø10,5 175 F 167,5 (3P) 282,5 (4P) 162,5 Safety clearances Door cutout E59446A A E46356A B A B E46355A 300 mini (3P) 415 mini (4P) Y 300 mini 270 (1) 379 (2) X 135 (1) 222 (2) 153,3 (1) 100 225 F F : Datum. Insulated Metal Energised parts parts parts A 0 0 0 B 0 0 60 64 (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 110 mm is required to remove the arc chutes. 325 (1) 364 (2) 162,5 (1) 182 (2) 47 (1)
MERLIN GERIN masterpact II NX 08 HA10 Ui 1000V Uimp 12kV Ue (V) 690 50kA/1s IEC 947-2 50/60Hz EN 60947-2 UTE VDE BS CEI UNE AS NBMA E46005A Connections Horizontal rear connection Detail E46357A E46360A E46363A 115 115 115 27 20 20 N Y X 296 93 184 E46057A 25 76 38 = = 13 12,5 20 47 3 Ø11,5 14,5 298,5 F Vertical rear connection Detail E46358A E46361A E46364A 115 115 115 20 27 View A 68 N Y X 141 E46059A 14,5 47 12,5 13 = = 76 38 F 298,5 3 Ø11,5 View A detail 25 Front connection Detail E46359A E46362A 20 12,5 E46365A 115 115 115 View A 151 N Y X 400 E46819B Top connection 76 25 25 13 Bottom connection 224 12,5 3 Ø11,5 3 Ø11,5 F 284 12,5 12,5 Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer View A detail 25 25 13 65
Dimensions and connection NW40 circuit breakers Fixed 3/4-pole device Dimensions E46050A 189 (3P) 304 (4P) 308 189 154 Y E46055A 191 150 260 X X 161 11 7 57 233 11 200 (3P) 315 (4P) 200 11 Mounting on base plate or rails Mounting detail E46051A X E46052A Y Ø9,5 25 124 162 15 mini 60 maxi 72 38 162 218,5 F 200 (3P) 315 (4P) 200 Ø9,5 F Safety clearances Door cutout E59445A A (*) E46054A B A (*) B E46053A 295 mini (3P) 410 mini (4P) Y 295 mini X 270 (1) 316 (2) 135 (1) 158 (2) 15 205 F 325 (1) 364 (2) 162,5 (1) 182 (2) F : Datum. Insulated Metal Energised parts parts parts A 0 0 100 B 0 0 60 (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 110 mm is required to remove the arc chutes. An overhead clearance of 20 mm is required to remove the terminal block. 66
masterpact II Ue (V) 690 50kA/1s E46484A NX 08 HA10 Ui 1000V Uimp 12kV IEC 947-2 50/60Hz EN 60947-2 UTE VDE BS CEI UNE AS NBMA MERLIN GERIN Connections Horizontal rear connection E46485A E46351A 27 20 20 150 X 93 161 20 F 233,5 Detail E46489B 52,5 150 150 150 115 115 115 17,5 17,5 52,5 E46490A 12,5 135 12,5 25 25 25 14,5 47 4 Ø11,5 N 332,5 (4P) Y 217,5 E46550A 12,5 100 12,5 25 25 25 14,5 47 Vertical rear connection E46486A E46488A 27 117,5 X 190,5 F 233,5 Detail E46058A 115 115 115 20 View A E46491A 47 14,5 12,5 12,5 25 N Y 20 25 125 25 25 Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer 5 Ø11,5 67
Dimensions and connection NW40 circuit breakers Drawout 3/4-pole device Dimensions E46506A 400 mini E46352A 220,5 (3P) 335,5 (4P) 308 Y 154 220,5 56 (*) 238,5 X X 200,5 128 60 mini 11 383,5 400 200 (*) Disconnected position Mounting on base plate or rails Mounting detail Y E46354A X E46353B 2 Ø11,5 x 22 10 Ø11,5 175 110 103 175 283 F Ø10,5 F 167,5 (3P) 282,5 (4P) 162,5 Safety clearances Door cutout E59446A A E46356A B A B E46355A 300 mini (3P) 415 mini (4P) Y 300 mini 270 (1) 379 (2) X 135 (1) 222 (2) 153,3 (1) 100 225 F F : Datum. Insulated Metal Energised parts parts parts A 0 0 0 B 0 0 60 68 (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. The safety clearances take into account the space required to remove the arc chutes. 325 (1) 364 (2) 162,5 (1) 182 (2) 47 (1)
MERLIN GERIN masterpact II NX 08 HA10 Ui 1000V Uimp 12kV Ue (V) 690 50kA/1s IEC 947-2 50/60Hz EN 60947-2 UTE VDE BS CEI UNE AS NBMA E46005A Connections Horizontal rear connection E46360A E46492A 27 20 20 X 20 93 184 296 F 298,5 Detail E46496B 52,5 150 115 17,5 150 115 115 150 17,5 52,5 E46490A 12,5 135 12,5 25 25 25 14,5 47 4 Ø11,5 N Y 332,5 217,5 E46550A 12,5 100 12,5 25 25 25 14,5 47 Vertical rear connection E46493A E46495A X 27 117,5 E46491A 20 47 14,5 12,5 25 25 125 25 25 12,5 5 Ø11,5 190,5 View A detail F 298,5 Detail E46364A 115 115 115 20 View A Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer N Y 69
Dimensions and connection NW40b to NW63 circuit breakers Fixed 3/4-pole device Dimensions E46282A 534 3P) 764 (4P) 308 189 154 Y E46055A 191 150 260 X X 161 7 57 233 11 545 (3P) 775 (4P) 200 11 Mounting on base plate or rails Mounting detail E46284A X E46283A Y Ø9,5 25 124 162 15 mini 60 maxi 72 38 162 218,5 F F 545 (6P) 775 (8P) 200 Ø9,5 Safety clearances Door cutout E59445A A (*) E46286A B A (*) B 639 mini (3P) 839 mini (4P) Y 295 mini E46285A 270 (1) X 316 (2) 135 (1) 158 (2) 15 205 F 325 (1) 364 (2) 162,5 (1) 182 (2) Insulated Metal Energised parts parts parts A 0 0 100 B 0 0 60 F : Datum (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. A(*) An overhead clearance of 110 mm is required to remove the arc chutes. An overhead clearance of 20 mm is required to remove the terminal block. 70
MERLIN GERIN masterpact II NX 63 HA Ue (V) 690 Icw 85kA/1s IEC 947-2 50/60Hz EN 60947-2 UTE VDE BS CEI UNE AS NBMA E46281A Ui 1000V Uimp 12kV Connections Horizontal rear connection (NW40b - NW50) E46551A 47 E46289A 115 230 115 115 230 115 115 230 115 115 E46287A 20 20 150 X F 253,5 20 93 161 E46057A 25 N 76 38 = = 13 12,5 47 Y 3 Ø11,5 14,5 Prises arrière verticales (NW40b - NW50) Détail E46288A E46552A 47 68 E46290A 115 230 115 115 230 115 115 230 115 115 20 View A X F 253,5 141 E46059A 14,5 N 47 12,5 13 = 76 = 38 Y 3 Ø11,5 View A detail 25 Vertical rear connection (NW63) Detail E59535A E59536A 47 117,5 E46290A 115 230 115 115 230 115 115 230 115 115 20 View A X 190,5 N 47 Y F 253,5 14,5 12,5 12,5 25 E46491A 20 25 125 25 25 Note: Recommended connection screws: M10 s/s class A4 80 Tightening torque: 50 Nm with contact washer. View A detail 5 Ø11,5 71
Dimensions and connection NW40b to NW63 circuit breakers Drawout 3/4-pole device Dimensions E46487A 400 mini E46498A 565,5 (3P) 795,5 (4P) 308 Y 154 220,5 56 (*) 238,5 X X 200,5 128 40 60 mini 11 383,5 (*) Disconnected position 400 200 Mounting on base plate or rails Mounting detail E46508A X E46499A Y 250 53 250 F 333 23 6 Ø11 x 34 F 325 (3P) 450 (4P) 174 (3P) 287,5 (4P) 151 (3P) 162,5 (4P) Safety clearances Door cutout E59446A A E46501A B A B 646 mini (3P) 876 mini (4P) Y 300 mini E46500A X 135 (1) 222 (2) 270 (1) 379 (2) 153,3 (1) 150 275 F Insulated Metal Energised parts parts parts A 0 0 0 B 0 0 60 F : Datum. 325 (1) 364 (2) (1) Without escutcheon (2) With escutcheon Note: X and Y are the symmetry planes for a 3-pole device. 162,5 (1) 182 (2) 47 (1) 72
MERLIN GERIN masterpact II NX 08 HA10 Ui 1000V Uimp 12kV Ue (V) 690 50kA/1s IEC 947-2 50/60Hz EN 60947-2 UTE VDE BS CEI UNE AS NBMA E46497A Connections Horizontal rear connection (NW40b - NW50) Detail E46507A 115 115 115 115 115 115 115 E46502A 27 20 20 E46504A N Y X 291 93 179 E46057A 25 76 38 = = 13 12,5 20 47 F 348,5 3 Ø11,5 14,5 Vertical rear connection (NW40b - NW50) Detail E46503A E46494A 68 27 E46505A 115 115 115 115 115 115 115 20 View A X 141 E46059A 14,5 N 47 12,5 13 Y F 348,5 = 76 = 38 3 Ø11,5 25 View A detail Vertical rear connection (NW63) Detail E59533A E59534A 27 E46505A 115 115 115 115 115 115 115 20 View A X 117,5 190,5 E46491A N 47 14,5 12,5 12,5 Y 25 F 348,5 20 25 125 25 25 View A detail 5 Ø11,5 Note: Recommended connection screws: M10 s/s class A4 80 Tightening torque: 50 Nm with contact washer 73
Dimensions and connection NT/NW accessories Mounting on backplate with special brackets ( NW08 to NW32 fixed). E46805A 429 (3P) 544 (4P) Y E46806A 4 Ø12 X 159 113 X 96 125 F 218,5 4,5 11 407 (3P) 522 (4P) 203,5 11 Disconnectable front-connection adapter ( NW08 to NW32 fixed) Horizontal rear connection Detail E46807A E46809A 67 20 E46812A 115 115 115 183 N Y X E46057A 25 76 38 = = 13 12,5 172 47 3 Ø11,5 14,5 F 253,5 20 Vertical rear connection Detail E46808A E46810A 67 E46811A 115 115 115 20 View A 231 N Y X E46059A 14,5 47 12,5 13 220 = = 76 38 Note: Recommended connection screws: M10 class 8.8 Tightening torque: 50 Nm with contact washer F Datum F 253,5 3 Ø11,5 View A detail 25 74
Rear panel cutout (drawout devices) NW08 to NW40 E46272A Y E46271A X 187 302 X 200,5 401 (3P) 516 (4P) NW40b to NW63 200,5 (3P) 315,5 (4P) 264 F E46274A Y E46273A X 182 297 X 200,5 679 (3P) 909 (4P) 478,5 (3P) 708,5 (4P) 314 F Escutcheon NT Fixed device E59885A Y Drawout device Y E59887A X 275 X 313 27 27 253 27 27 317 13 27 NW Fixed device E59890A Y E59889A Drawout device Y X 324 X 387 25 18 F Datum 372 25 372 25 45 25 75
Dimensions and connection NT/NW external modules Connection of auxiliary wiring to terminal block E47683A S : 0,6 mm 2 E47684A S : 2,5 mm 2 2 1 8 Ø3,5 One conductor only per connection point M6C relay module 99 E47688A 66 1 3 5 7 9 11 13 15 17 19 21 23 M6c 1 3 5 7 9 11 17 19 21 23 25 S1 S2 24V 0V com. S3 S4 S5 S6 2 4 6 8 10 12 14 16 18 20 22 24 99 25 S1 S2 S3 S4 S5 S6 46 81 E47689A 1 3 5 7 9 11 13 15 17 19 21 23 25 M6c 1 3 5 7 9 11 17 19 21 23 25 S1 S2 24V 0V com. S3 S4 S5 S6 2 4 6 8 10 12 14 16 18 20 22 24 S1 S2 S3 S4 S5 S6 46 External power supply module (AD) E47690A 60 2 Ø6 L3 AD 220A Input 24VDC G1 Output 24VDC L4 + G2 73 60 112 75 E47691A AD 220A L3 G1 Input 24VDC Output 24VDC + G2 L4 Battery module (BAT) Mounting 60 2 Ø6 E47692A H3 Input 24VDC H4 + 73 60 BAT 24V + Output H2 24VDC H1 112 75 E47693A BAT 24V H3 H2 Input 24VDC + Output 24VDC H4 + H1 76
B A B A Delay unit for MN release MNR 57 2 Ø4,2 E47694A 1 2 3 4 5 6 81 42 73,5 1 2 3 MN UVR 100/130 V AC/DC 3 6 1012 S 72 0.5 1 3 1.5 Retardateur de MN Time delay for UVR E47695A 66 1 2 3 4 5 6 73 3 6 MN UVR 100/130 V AC/DC 1012 S 0.5 1 3 1.5 Retardateur de MN Time delay for UVR 46 1 2 3 Craddle communication module ModBUS BatiBUS E47685A E47686A + + 90 CT CCM modbus CD Fault Com. Address sync. CE Réseau shield B A Disjoncteur B A + Network Breaker 45 58 54 External sensor for source ground return (SGR) protection Sensor MGDF summer module E58561 E47687A 200 130 90 45 MDGF 45 76 150 58 106 77
Dimensions and connection NT/NW external modules External sensor for external neutral Dimensions 400/1600 A (NT06 to NT16) 400/2000 A (NW08 to NW20) 4 Ø14 4 Ø14 E47699 H1 GND VN VC X2 X1 SG2 SG1 177 208 H2 35 76 E47700 H1 SG1 SG2 X1 X2 GND VN VC H2 44 102 174 206 1000/4000 A (NW025 to NW40) 2000/6300 A (NW40b to NW63) 8 Ø14 16 Ø14 E47701 H1 SG1 SG2 X1 X2 GND VN VC H2 44 127 E47702 H1 SG1 SG2 X1 X2 GND VN VC H2 127 44 44 174 44 295 H1 SG1 SG2 X1 X2 GND VN VC H2 70 44 127 44 174 44 295 Installation 400/1600 A (NT06 to NT16) 400/2000 A (NW08 to NW20) E47697A E47696 1000/4000 A (NW25 to NW40) 2000/6300 A (NW40b to NW63) E47696A E67969 2 identical external sensor shipped as loosed part 78
Rectangular sensor for earth leakage protection (Vigi) 280 x 115 mm window 4 Ø9 E47703A M1 M2 M3 E47704B 197 115 215 M1 M2 M3 280 362 380 70 470 x 160 mm window 8 Ø9 E47717A E47718B 146 160 242 260 M1 M2 M3 M1 M2 M3 456 470 552 570 70 Busbars I i 1600 A I i 3200 A window (mm) 280 x 115 470 x 160 weight (kg) 14 18 Busbars path 280 x 115 window Busbars spaced 70 mm centre-to-centre 470 x 160 window Busbars spaced 115 mm centre-to-centr E47707 E47708 M1 M2 M3 2 bars 50 x 10 M1 M2 M3 4 bars 100 x 5 E67970 E67971 M1 M2 M3 2 bars 100 x 5 M1 M2 M3 4 bars 125 x 5 79
80
Electrical diagrams Presentation 1 Functions and characteristics 9 Dimensions and connection 53 NT06 to NT16 82 NW08 to NW63 84 NT and NW 86 Installation recommendations 91 Additional characteristics 115 References 121 81
Electrical diagrams NT06 to NT16 Fixed and drawout devices The diagram is shown with circuits de-energised, all devices open, connected and charged and relays in normal position. Power Control unit Remote operation power N L1 L2 L3 upstream cb Z1 Z2 Z3 Z4 Z5 downstream cb Z1 Z2 Z3 Z4 Z5 M6C fault fault AT BPO BPF readyto-close Micrologic T1 T2 T3 T4 VN V1 V2 V3 Z1 Z2 Z3 Z4 Z5 charged Q MCH I U M1 M2 M3 F1 F2+ B1 B3 B2 CH E46555B E46132A 471 474 484 Q1 Q2 Q3 S1 S2 M2C or M6C MX1 E46133 C1 C2 C3 A2 A3 XF PF 181 E46135A E46136A E46137A A1 E46138A 251 182 184 252 254 SDE2 81 K2 82 84 or Res SDE1 K1 D1 D2 C12 MN or MX2 C11 E46139A SG1 SG2 X1 X2 24 V DC Terminal block marking Control unit Com UC1 UC2 UC3 UC4 / M2C / M6C E5 E6 Z5 M1 M2 M3 F2+ V3 / 484 / Q3 Remote operation SDE2 / Res SDE1 MN / MX2 MX1 XF PF MCH 184 / K2 84 D2 / C12 C2 A2 254 B2 E3 E4 Z3 Z4 T3 T4 VN V2 / 474 / Q2 182 82 C3 A3 252 B3 E1 E2 Z1 Z2 T1 T2 F1 V1 / 471 / Q1 181 / K1 81 D1 / C11 C1 A1 251 B1 A P H c c c c c c c c c c c c c c c c c c c c c c c c c c Control unit Com: E1-E6 communication UC1 : Z1-Z5 zone selective interlocking; Z1 = ZSI OUT SOURCE Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault) M1 = Vigi module input (Micrologic 7) UC2 : T1, T2, T3, T4 = external neutral; M2, M3 = Vigi module input (Micrologic 7) UC3 : F2+, F1 external 24 DC power supply VN external voltage connector (optional) UC4 : optional external voltage connector or M2C : 2 programmable contacts (internal relay); ext. 24V DC power supply required or M6C : 6 programmable contacts (external relay); ext. 24V DC power supply required. Remote operation SDE2: Fault-trip indication contact or Res : Remote reset SDE1: Fault-trip indication contact (supplied as standard) MN : Undervoltage release or MX2 : Shunt release MX1 : Shunt release (standard or communicating) XF PF : Closing release (standard or communicating) : Ready-to-close contact MCH: electric motor Note: When communicating MX or XF releases are used, the third wire (C3,A3) must be connected even if the communication module is not installed. A : Digital ammeter P: A + power meter + additional protection H: P + harmonics 82
Indication contacts Craddle contacts open closed disconnected connected Test E46141A 31 21 11 42 44 32 34 22 E47075A 24 E46134A 12 E47074A 14 OF4 OF3 OF2 OF1 41 331 332 334 CE3 321 322 324 CE2 311 312 314 CE1 821 811 822 824 812 814 914 912 CD2 CD1 CT1 911 Indication contacts OF4 OF3 OF2 OF1 44 34 24 14 42 32 22 12 41 31 21 11 Craddle contacts CD2 CD1 CE3 CE2 CE1 CT1 824 814 334 324 314 914 822 812 332 322 312 912 821 811 331 321 311 911 Indication contacts OF4 / OF3 / OF2 / OF1 : ON/OFF indication contacts (*) Spring charging motor 440/480 V AC (380 V motor + additional resistor) Craddle contacts CD2: Disconnected CD1 position contacts CE3: Connected CE2 position CE1 contacts CT1: Test position contacts E47484 spring charged light 440/480 V CN1 B3-440/480 V 9 11 R B2 MCH 380V CH CN2 B1-440/480 V key: Drawout device only XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard Interconnected connections (only one wire per connection point) 83
Electrical diagrams NW08 to NW63 Fixed and drawout devices The diagram is shown with circuits de-energised, all devices open, connected and charged and relays in normal position. Power Control unit Remote operation power N L1 L2 L3 upstream cb Z1 Z2 Z3 Z4 Z5 downstream cb Z1 Z2 Z3 Z4 Z5 M6C fault fault AT BPO BPF readyto-close Micrologic T1 T2 T3 T4 VN V1 V2 V3 charged Z1 Z2 Z3 Z4 Z5 Q I U S1 M1 M2 M3 F1 F2+ E46132A 471 474 484 Q1 Q2 Q3 C2 C3 S2 M2C ou M6C MX1 E46133 C1 A1 A2 A3 252 254 MCH XF PF 251 E46139A B1 B3 B2 CH 181 182 184 SDE2 81 K2 82 84 Res SDE1 K1 D2 or MN MX2 E46135A D1 C11 C12 or E46136A E46137A E46138A SG1 SG2 X1 X2 24 V DC E46555B Terminal block marking Control unit Com UC1 UC2 UC3 UC4 M2C / M6C Remote operation SDE2 / Res SDE1 MN / MX2 MX1 XF PF MCH E5 E6 Z5 M1 M2 M3 F2+ V3 484 / Q3 184 / K2 84 D2 / C12 C2 A2 254 B2 E3 E4 Z3 Z4 T3 T4 VN V2 474 / Q2 182 82 C3 A3 252 B3 E1 E2 Z1 Z2 T1 T2 F1 V1 471 / Q1 181 / K1 81 D1 / C11 C1 A1 251 B1 A P H c c c c c c c c c c c c c c c c c c c c c c Control unit Com: E1-E6 communication UC1 : Z1-Z5 zone selective interlocking; Z1 = ZSI OUT SOURCE Z2 = ZSI OUT ; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault) M1 = Vigi module input (Micrologic 7) UC2 : T1, T2, T3, T4 = external neutral; M2, M3 = Vigi module input (Micrologic 7) UC3 : F2+, F1 external 24 DC power supply VN external voltage connector (optional) UC4 : V1, V2, V3 optional external voltage connector Remote operation SDE2: Fault-trip indication contact or Res : Remote reset SDE1: Fault-trip indication contact (supplied as standard) MN : Undervoltage release or MX2 : Shunt release MX1 : Shunt release (standard or communicating) XF PF : Closing release (standard or communicating) : Ready-to-close contact MCH: electric motor c c c c M2C : 2 programmable contacts (internal relay); ext. 24V DC power supply required or M6C : 6 programmable contacts (to be connected to the external module M6C); ext. 24V DC power supply required Note: When communicating MX or XF releases are used, the third wire (C3,A3) must be connected even if the communication module is not installed. A : Digital ammeter P: A + power meter + additional protection H: P + harmonics 84
Indication contacts Craddle contacts open closed closed not connected or connected and open connected and closed disconnected connected Test E46141A 31 21 11 42 44 32 34 22 24 12 14 OF4 OF3 OF2 OF1 41 E46140 E46131A 821 811 E46134A 832 834 822 E46142A 824 812 814 CD3 CD2 CD1 831 331 332 334 CE3 321 322 324 CE2 311 312 314 OF.. OF CE1 CE.. 1.. 2.. 4.. 8.. 6 EF.. or.. 5 921 911 934 932 924 922 914 912 CT3 CT2 CT1 931 Indication contacts OF4 OF3 OF2 OF1 OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11 Craddle contacts CD3 CD2 CD1 CE3 CE2 CE1 CT3 CT2 CT1 44 34 24 14 244 234 224 214 144 134 124 114 834 824 814 334 324 314 934 924 914 42 32 22 12 242 232 222 212 142 132 122 112 832 822 812 332 322 312 932 922 912 41 31 21 11 241 231 221 211 141 131 121 111 or or or or or or or or EF24 EF23 EF22 EF21 EF14 EF13 EF12 EF11 831 821 811 331 321 311 931 921 911 or or CE6 CE5 CE4 CE9 CE8 CE7 248 238 228 218 148 138 128 118 364 354 344 394 384 374 246 236 226 216 146 136 126 116 362 352 342 392 382 372 245 235 225 215 145 135 125 115 361 351 341 391 381 371 Indication contacts Craddle contacts OF4 OF3 OF2 OF1 :ON/OFF indication contacts OF24 or EF24 OF23 or EF23 OF22 or EF22 OF21 or EF21 OF14 or EF14 OF13 or EF13 OF12 or EF12 OF11 or EF11 :ON/OFF indication contacts Combined connected-deconnected indication contacts CD3: Disconnected CD2 position CD1 contacts or CE6: Connected CE5 position CE4 contacts key: XXX Drawout device only CE3: Connected CE2 position CE1 contacts SDE1, OF1, OF2, OF3, OF4 supplied as standard Interconnected connections (only one wire per connection point) CT3: Test CT2 position CT1 contacts or CE9:Connected CE8 position CE7 contacts or CD6:Disconnected CD5 position CD4 contacts 85
Electrical diagrams NT and NW Communications option 24 VDC external power supply Connection of the communications option E47593 N L1 L2 L3 microswitch built into COM module OF 914 812 314 912 812 312 VN V1 V2 V3 Z1 Z2 Z3 Z4 Z5 SDE PF MX1 com 911 811 311 911 811 311 Q I U Micrologic CH XF com device communication module CT B' A' B A + CD CE Modbus COM craddle + CT + BB BB CD CE Digipact COM craddle shield B' A' B A + BB BB CCP 303 (2) M1 M2 M3 T1 T2 T3 T4 F1 H1 H2 F2+ E1 E2 E3 E4 E5 E6 5 4 CCP 303 BAT module H3 H4 G1 G2 (1) (2) 3 2 1 0 Modbus junction block CJB306 Digipact junction block AD module red black brown yellow white blue 24 V 0 V L3 L4 110/240 V AC 24/125 V DC E1 E2 E3 E4 E5 E6 + A B A' B' Modbus + / / BB BB + Digipact E3 / E4 twisted pair E5 / E6 twisted pair 24 VDC 1A communication power supply 0 V 24 VDC DC 150 24 V None of the control-unit protection functions require an auxiliary source. However, the 24 V DC external power-supply (AD module) is required for certain operating configurations as indicated in the table below. circuit breaker closed open voltage measurement inputs powered powered not powered M2C, M6C programmable contacts option yes yes yes Protection function no no no Display function no (3) no (4) yes Time-stamping function no no yes (5) Circuit-breaker status indications and no no no control via communications bus Identification, settings, operation and no (3) no (4) yes maintenance aids via communications bus (1) draw-out device equipped with Modbus craddle COM. (2) draw-out device equipped with Digipact craddle COM. (3) except for Micrologic A control units (if current < 20% In). (4) except for Micrologic A control units. (5) time setting is manual and can be carried out automatically by the supervisor via the communications bus. The communications bus requires its own 24 V DC power source (E1, E2). This source is not the same as the 24 V DC external power-supply module (F1-, F2+). In case of using the 24 VDC external power supply (AD module), maximum cable length between 24 VDC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters. The BAT battery module, mounted in series upstream of the AD module, ensures an uninterrupted supply of power if the AD module power supply fails. The voltage measurement inputs are standard equipment on the downstream connectors of the circuit breaker. External connections are possible using the PTE external voltage measurement input option. With this option, the internal voltage measurement inputs are disconnected and terminals VN, V1 and V2 are connected only to the control unit (Micrologic P and H only). The PTE option is required for voltages less than 100 V and greater than 690 V (in which case a voltage transformer is compulsory). For three-pole devices, the system is supplied with terminal VN connected only to the control unit (Micrologic P and H). When the PTE option is implemented, the voltage measurement input must be protected against short-circuits. Installed as close as possible to the busbars, this protection function is ensured by a P25M circuit breaker (1 A rating) with an auxiliary contact (cat. no. 21104 and 21117). This voltage measurement input is reserved exclusively for the control unit and must not ever be used to supply other circuits outside the switchboard. 86
Examples using the COM communications option Switchboard display unit This architecture provides remote display of the variables managed by Micrologic control units equipped with the eco COM Modbus module. c I (Micrologic A) c I, U, P, E (Micrologic P) c I, U, P, E, THD (Micrologic H) No programming is required. For Micrologic A control unit (if current < 20% In), it is recommended to use the 24 VDC external power supply (AD module). E47976 DMB300 1 2 3 4 I U P? switchboard display unit CDM303 + CSD309 d < 1 km 5 4 3 2 1 0 Modbus junction block CJB 306 24 V 0 V 24 VDC 1A CCP303 power circuit breaker Communicating switchboard This configuration provides remote display and control of s equipped with the Modbus or Digipact COM module. The Digipact bus can be combined with the Modbus bus. E47977 Software PC running PC running PLC Micrologic utilities SMS PLC Micrologic utilities SMS TCP/IP Communication interface RS 232C RS 485 Ethernet RS 485 Bus Modbus Bus Modbus communication Bus Data concentrator DC150 Device UA150 source change-ower SC150 contraf interface PM150 measure COM Digipact COM Modbus PM300 measure Sepam Vigilohm Altivar Digipact Bus Modbus Bus 87
Electrical diagrams NT and NW Earth-fault and earth-leakage protection Neutral protection Zone selective interlocking External sensor (CT) for residual earth-fault protection Connection of current-transformer secondary circuit for external neutral equipped with a Micrologic 6 A/P/H: c shielded cable with 2 twisted pairs c SG1 twisted with SG2 c X1 twisted with X2 c shielding connected to GND on one end only c maximum length 5 meters c cable cross-sectional area 0.4 to 1.5 mm 2 c recommended cable: Belden 9552 or equivalent. If supply is via the top, follow the shematics. If supply is via the bottom, control wiring is identical; for the power wiring, H1 is connected to the source side, H2 to the load side. For four-pole versions, for residual earth-fault protection, the current transformer for the external neutral is not necessary. If the 2000/6300 current transformer is used: c signals SG1 and SG2 must be wired in series c signals X1 and X2 must be wired in parallel. Connection for signal VN is required only for power measurements (3 Ø, 4 wires, 4CTs). E47591B N L1 Q VN H2 L2 L3 SG1 SG2 X1 Micrologic 6 T1 VN T2 V1 T3 T4 V2 V3 Z1 Z2 Z3 Z4 Z5 Q I U M1 M2 M3 F1 F2+ VN V1 V2 V3 Z1 Z2 Z3 Z4 Z5 I Micrologic 6 U M1 M2 M3 T1 T2 T3 T4 F1 F2+ H1 GND X2 External transformer for source ground return (SGR) earth-fault protection Connection of the secondary circuit equipped with a Micrologic 6 A/P/H: c unshielded cable with 1 twisted pair c maximum length 150 meters c cable cross-sectional area 0.4 to 1.5 mm 2 c terminals 5 and 6 may not be used at the same time c use terminal 5 for NW08 to 40 c use terminal 6 for NW40b to 63 c recommended cable: Belden 9409 or equivalent. or E47592 H1 H2 X1 X2 PE 12 5 6 7 10 11 1 MDGF module 3 13 14 9 8 88
Earth-leakage protection Connection of the rectangular-sensor secondary circuit E47974B N L1 L2 L3 equipped with a Micrologic 7 A/P/H: c unshielded cable with 3 twisted conductors: v M1, M2, M3 twisted together c maximum length 4 metres c cable cross-sectional area 0.4 to 1.5 mm 2 c recommended cable: Belden 9493 or equivalent. VN V1 V2 V3 Micrologic 7 T1 T2 T3 T4 Z1 Z2 Z3 Z4 Z5 Q I U M1 M2 M3 F1 F2+ M1 M2 M3 Neutral protection c Three pole breaker: v equipped with Micrologic P or H v the current transformer for external neutral is necessary (the wiring diagram is identical to the one used for the residual earth-fault protection). c Four pole breaker: v equipped with Micrologic A, P or H v the current transformer for external neutral is not necessary. Zone selective interlocking A pilot wire interconnects a number of circuit breakers equipped with Micrologic A/P/H control units, as illustrated in the diagram above. The control unit detecting a fault sends a signal upstream and checks for a signal arriving from downstream. If there is a signal from downstream, the circuit breaker remains closed for the full duration of its tripping delay. If there is no signal from downstream, the circuit breaker opens immediately, whatever the tripping-delay setting. Fault 1. Only circuit breaker A detects the fault. Because it receives no signal from downstream, it immediately opens in spite of its tripping delay set to 0.3. Fault 2. Circuit breakers A and B detect the fault. Circuit breaker A receives a signal from B and remains closed for the full duration of its tripping delay set to 0.3. Circuit breaker B does not receive a signal from downstream and opens immediately, in spite of its tripping delay set to 0.2. E47975B B upstream circuit breaker Z1 Z2 Z3 Z4 Z5 fault 2 A tsd = 0,2 Z1 Z2 Z3 Z4 Z5 fault 1 tsd = 0,3 Note: the maximum permissible distance between two devices is 3000 m and the maximum number of devices is 100. Z1 Z2 Z3 Z4 Z5 downstream circuit breaker Z1 Z2 Z3 Z4 Z5 89
90
Installation recommendations Presentation 1 Functions and characteristics 9 Dimensions and connection 53 Electrical diagrams 81 Operating conditions 92 Installation in switchboard 94 Door interlock catch 96 Cable-type door interlock 97 Connection of MN, MX and XF voltage releases 97 Power connection 98 Recommended busbars drilling 100 Busbar sizing 102 Temperature derating 104 Power dissipation and input/output resistance 104 Derating in switchboards 105 Substitution kit 112 Additional characteristics 115 References 121 91
Test Test Test Installation recommendations Operating conditions E51260B Ambient temperature devices can operate under the following temperature conditions: c the electrical and mechanical characteristics are stipulated for an ambient temperature of -5 C to +70 C; c circuit-breaker closing is guaranteed down to -35 C; Storage conditions are as follows: c -40 to +85 C for a device without its control unit c -25 C to +85 C for the control unit. E51261B Extreme atmospheric conditions devices have successfully passed the tests defined by the following standards for extreme atmospheric conditions: c IEC 68-2-1: dry cold at -55 C; c IEC 68-2-2: dry heat at +85 C; c IEC 68-2-30: damp heat (temperature +55 C, relative humidity 95%); c IEC 68-2-52 level 2: salt mist. devices can operate in the industrial environments defined by standard IEC 947 (pollution degree up to 4). It is nonetheless advised to check that the devices are installed in suitably cooled switchboards without excessive dust. E51262B Vibrations devices are guaranteed against electromagnetic or mechanical vibrations. Tests are carried out in compliance with standard IEC 68-2-6 for the levels required by merchant-marine inspection organisations (Veritas, Lloyd s, etc.): c 2 to 13.2 Hz: amplitude ±1 mm; c 13.2 to 100 Hz: constant acceleration 0.7 g. Excessive vibration may cause tripping, breaks in connections or damage to mechanical parts. 92
Test Test E51263B 2000 m Altitude At altitudes higher than 2000 metres, the modifications in the ambient air (electrical resistance, cooling capacity) lower the following characteristics as follows: Altitude (m) 2000 3000 4000 5000 Dielectric resistance 3500 3150 2500 2100 voltage (V) Average insulation 1000 900 700 600 level (V) Maximum utilisation 690 590 520 460 voltage (V) Average thermal 1 x In 0.99 x In 0.96 x In 0.94 x In current (A) at 40 C E51264B Electromagnetic disturbances devices are protected against: c overvoltages caused by devices that generate electromagnetic disturbances; c overvoltages caused by atmospheric disturbances or by a distribution-system outage (e.g. failure of a lighting system); c devices emitting radio waves (radios, walkie-talkies, radar, etc.); c electrostatic discharges produced by users. devices have successfully passed the electromagnetic-compatibility tests (EMC) defined by the following international standards: c IEC 60947-2, appendix F; c IEC 60947-2, appendix B (trip units with earth-leakage function). The above tests guarantee that: c no nuisance tripping occurs; c tripping times are respected. 93
Installation recommendations Installation in switchboard E47658A E47656A E47653A E47650A Possible positions Power supply devices can be supplied either from the top or from the bottom without reduction in performance, in order to facilitate connection when installed in a switchboard. Mounting the circuit-breaker It is important to distribute the weight of the device uniformily over a rigid mounting surface such as rails or a base plate. This mounting plane should be perfectly flat (tolerance on support flatness: 2 mm). This eliminates any risk of deformation which could interfere with correct operation of the circuit breaker. devices can also be mounted on a vertical plane using the special brackets. Mounting on rails. E47651A E47657A E47652A Mounting with vertical brackets. 94
Partitions Sufficient openings must be provided in partitions to ensure good air circulation around the circuit breaker; For high currents, of 2500 A and upwards, the metal supports or barriers in the immediate vicinity of a conductor must be made of non-magnetic material A; Metal barriers through which a conductor passes must not form a magnetic loop. Busbars The mechanical connection must be exclude the possibility of formation of a magnetic loop around a conductor. E47659A Interphase barrier Increases the length of the tracking path between phases; Reduces the risk of short circuits being caused by objects falling from above onto circuit breaker connections. 95 E47662B A non magnetic Dimensions and weights Main dimensions in mm (H x W x D) A : non magnetic material material F NT06/12 NW08/40 NW40b/63 drawout 3P 322 x 288 x 280 439 x 441 x 395 479 x 786 x 395 4P 322 x 358 x 280 439 x 556 x 395 479 x 1016 x 395 fixed 3P 301 x 276 x 211 352 x 422 x 297 352 x 767 x 297 4P 301 x 346 x 211 352 x 537 x 297 352 x 997 x 297 E47663A Weight (kg) E47661A E47660A E47664 351 (NT) 453 (NW) NT06/12 NW08/40 NW40b/63 drawout 3P 30 90 225 4P 39 120 300 fixed 3P 14 60 120 4P 18 80 160
Installation recommendations Door interlock catch Mounted on the right or left-hand side of the craddle, this device inhibits opening of the cubicle door when the circuit breaker is in «connected» or «test» position. It the breaker is put in the «connected» position with the door open, the door may be closed without having to disconnect the circuit breaker. E47669B Y X 15 8 Catch not supplied (1) (2) 5 17 Dimensions (mm) Type (1) (2) NT08-16 (3P) 135 168 NT08-16 (4P) 205 168 NW08-40 (3P) 215 215 NW08-40 (4P) 330 215 NW40b-63 (3P) 660 215 NW40b-63 (4P) 775 215 Breaker in connected or test position Door cannot be opened E47670A door F (1) (2) Dimensions (mm) Type (1) (2) NT 5 23 NW 83 103 Breaker in disconnected position Door can be opened E47671A Note: The door interlock can either be mounted on the right side or the left side of the breaker. F Datum. 96
Cable-type door interlock Connection of MN, MX and XF voltage releases NT/NW Cable-type door interlock This option prevents door opening when the circuit breaker is closed and prevents circuit breaker closing when the door is open. For this, a special plate associated with a lock and a cable is mounted on the right side of the circuit breaker. With this interlock installed, the source changeover function cannot be implemented. E59113A E59115A E59114B 46 165 121 10 79 52 84 Wiring of voltage releases During pick-up, the power consumed is approximately 150 to 200 VA. For low control voltages (12, 24, 48 V), maximum cable lengths are imposed by the voltage and the cross-sectional area of cables. Recommanded maximum cable lengths (meter) 12 V 24 V 48 V 2,5 mm 2 1,5 mm 2 2,5 mm 2 1,5 mm 2 2,5 mm 2 1,5 mm 2 MN U source 100 % 58 35 280 165 U source 85 % 16 10 75 45 MX-XF U source 100 % 21 12 115 70 550 330 U source 85 % 10 6 75 44 350 210 Note: the indicated length is that of each of the two wires 97
Installation recommendations Cables connections If cables are used for the power connections, make sure that they do not apply excessive mechanical forces to the circuit breaker terminals. For this, make the connections as follows: c extend the circuit breaker terminals using short bars designed and installed according to the recommendations for bar-type power connections: v for a single cable, use solution B opposite v for multiple cables, use solution C opposite. c in all cases, follow the general rules for connections to busbars: v position the cable lugs before inserting the bolts v the cables should firmly secured to the framework of the switchboard. Busbars connections The busbars should be suitably adjusted to ensure that the connection points are positioned on the terminals before the bolts are inserted B The connections are held by the support which is solidly fixed to the framework of the switchboard, such that the circuit breaker terminals do not have to support its weight C. (This support should be placed close to the terminals). E47674A E47677A E47675A 98 Power connection E47672A B E Electrodynamic stresses The first busbar support or spacer shall be situated within a maximum distance from the connection point of the breaker (see table below). This distance must be respected so that the connection can withstand the electrodynamic stresses between phases in the event of a short circuit. Maximum distance A between busbar to circuit breaker connection and the first busbar support or spacer with respect to the value of the prospective short-circuit current. Isc (ka) 30 50 65 80 100 150 distance A (mm) 350 300 250 150 150 150 B A E C B C E47673A E47676A
E47678A 1 2 3 4 5 Clamping Correct clamping of busbars depends amongst other things, on the tightening torques used for the nuts and bolts. Over-tightening may have the same consequences as under-tightening. For connecting busbars (Cu ETP-NFA51-100) to the circuit breaker, the tightening torques to be used are shown in the table below. These values are for use with copper busbars and steel nuts and bolts, class 8.8. The same torques can be used with AGS-T52 quality aluminium bars (French standard NFA 02-104 or American National Standard H-35-1). Examples E47665 E47667B E47668 6 1 terminal screw factory-tightened to 16 Nm (NW), 13 Nm (NT) 2 breaker terminal 3 busbar 4 bolt 5 washer 6 nut Tightening torques Ø Ø tightening torque (Nm) with contact nominal (mm) drilling (mm) with grower or or corrugatec flat washers washers 10 11 37.5 50 Busbar drilling Examples E47329A E47330A E47331A Isolation distance E47679A E47680A Dimensions (mm) Ui X min 600 V 8 mm 1000 V 14 mm Busbar bending When bending busbars maintain the radius indicated below(a smaller radius would cause cracks). r e X Dimensions (mm) e radius of curvature r min recommended 5 5 7.5 10 15 18 to 20 99
Installation recommendations Recommended busbars drilling NT06 to NT16 Rear connection Rear connection with spreaders E59308A 12,5 50 E59308A 12,5 12,5 Ø12 maxi 50 E59309A 12,5 25,5 Ø12 maxi 63 12,5 Ø12 maxi E59310A 15 80 15 Ø12 maxi 25 12,5 25 12,5 25 12,5 25 25 12,5 Middle left or middle Middle spreader Left or right spreader Left or right spreader right spreader for 4P for 3P for 4P for 3P E59324A 44 25 9,5 12,5 E59325A 77 38,5 25 = = 13,5 E59326A 77 38,5 25 = = 13,5 E59327A 77 38,5 25 = = 13,5 E59328A 77 38,5 25 = = 13,5 2 Ø11 12,5 60 82 52 52 30 15 5 Ø11 25 82 52 52 30 30 15 82 52 15 5 Ø11 5 Ø11 25 25 52 82 52 52 30 15 5 Ø11 25 Vertical rear connection E59311A 32 E59312A 40 E59313A 50 E59314A 63 E59315 A 80 25 Ø12 maxi 25 Ø12 maxi 25 Ø12 maxi 25 Ø12 maxi 25 Ø12 maxi 12,5 12,5 12,5 12,5 12,5 12,5 12,5 12,5 12,5 12,5 E59329A 60 12,5 12,5 9,5 25 44 2 Ø11 Front connection Front connection via vertical connection adapters E59308A 12,5 50 12,5 12,5 12,5 25,5 Ø12 maxi Ø12 maxi E59308A 50 E59309A 63 12,5 Ø12 maxi E59310A 15 80 15 Ø12 maxi 25 12,5 25 12,5 25 12,5 25 25 12,5 E59330A Top connection 44 25 9,5 13 2 Ø11 E59331A Bottom connection 2 Ø11 13 25 9,5 44 E59332A 21 101 15 25 = 89 20 = 3 Ø11 12,5 15 21 100
NW08 to NW63 Horizontal rear connection NW08 to NW38 NW40b to NW50 E59308A 12,5 50 E59309A 12,5 25,5 Ø12 maxi 63 12,5 Ø12 maxi E59310A 15 80 Ø12 maxi E59316A 15 22 100 Ø12 maxi E59317A 28 28 100 22 Ø12 maxi 25 12,5 25 12,5 25 25 12,5 25 25 12,5 25 25 12,5 E59333A 25 76 38 = = 13 12,5 E59323A 115 115 115 115 115 39 39 39 39 39 47 3 Ø11,5 14,5 Y Vertical rear connection NW08 to NW32, NW40b to NW50 E59318A 40 E59319A 50 E59320A 63 E59321A 80 E59322A 100 25 25 Ø12 maxi 25 25 Ø12 maxi 25 25 Ø12 maxi 25 25 Ø12 maxi 25 25 Ø12 maxi 12,5 12,5 12,5 12,5 12,5 12,5 12,5 12,5 12,5 12,5 E59334A 14,5 47 12,5 13 = = 76 38 3 Ø11,5 25 Front connection NW08 to NW32 E59308A 12,5 50 E59309A 12,5 25,5 Ø12 maxi 63 12,5 Ø12 maxi E59310A 15 80 15 Ø12 maxi 25 12,5 25 12,5 25 25 12,5 Top connection Bottom connection E59335A 76 25 25 13 12,5 3 Ø11,5 E59336A 3 Ø11,5 12,5 25 25 13 101
Installation recommendations Busbar sizing Basis of tables: c maximum permissible busbars temperature: 100 C c Ti: temperature around the circuit breaker and its connection c busbar material is unpainted copper. Front or rear horizontal connection E47681A maximum Ti : 40 C Ti : 50 C Ti : 60 C service no. of 5 mm no. of 10 mm no. of 5 mm no. of 10 mm no. of 5 mm no. of 10 mm current thick bars thick bars thick bars thick bars thick bars thick bars NT06 400 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10 NT06 630 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10 NT08 or NW08 800 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.63 x 10 NT10 or NW10 1000 3b.50 x 5 1b.63 x 10 3b.50 x 5 2b.50 x 10 3b.63 x 5 2b.50 x 10 NT12 or NW12 1250 3b.50 x 5 2b.40 x 10 3b.50 x 5 2b.50 x 10 3b.63 x 5 2b.50 x 10 2b.80 x 5 2b.40 x 10 2b.80 x 5 NT16 or NW16 1400 3b.50 x 5 2b.40 x 10 2b.80 x 5 2b.50 x 10 3b.80 x 5 2b.63 x 10 NT16 or NW16 1600 3b.63 x 5 2b.50 x 10 3b.80 x 5 2b.63 x 10 3b.80 x 5 3b.50 x 10 NW20 1800 3b.80 x 5 2b.63 x 10 3b.80 x 5 2b.63 x 10 3b.100 x 5 2b.80 x 10 NW20 2000 3b.100 x 5 2b.80 x 10 3b.100 x 5 2b.80 x 10 3b.100 x 5 3b.63 x 10 NW25 2200 3b.100 x 5 2b.80 x 10 3b.100 x 5 2b.80 x 10 4b.80 x 5 2b.100 x 10 NW25 2500 4b.100 x 5 2b.100 x 10 4b.100 x 5 2b.100 x 10 4b.100 x 5 3b.80 x 10 NW32 2800 4b.100 x 5 3b.80 x 10 4b.100 x 5 3b.80 x 10 5b.100 x 5 3b.100 x 10 NW32 3000 5b.100 x 5 3b.80 x 10 6b.100 x 5 3b.100 x 10 8b.100 x 5 4b.80 x 10 NW32 3200 6b.100 x 5 3b.100 x 10 8b.100 x 5 3b.100 x 10 4b.100 x 10 NW40 3800 4b.100 x 10 5b.100 x 10 5b.100 x 10 NW40 4000 5b.100 x 10 5b.100 x 10 6b.100 x 10 NW50 4500 6b.100 x 10 6b.100 x 10 7b.100 x 10 NW50 5000 7b.100 x 10 7b.100 x 10 With NT, it is recommanded to use 50 mm wideness bars (see "Recommended busbars drilling") Example Conditions: c drawout version c horizontal busbars c Ti: 50 C c service current: 1800 A. Solution: For Ti = 50 C, use an NW20 which can be connected with three 80x5 mm bars or two mm 63x10 bars. Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 102
Basis of tables: c maximum permissible busbars temperature: 100 C c Ti: temperature around the circuit breaker and its connection c busbar material is unpainted copper. Rear vertical connection E47682A Maximum Ti: 40 C Ti: 50 C Ti: 60 C service no. of 5 mm no. of 10 mm no. of 5 mm no. of 10 mm no. of 5 mm no. of 10 mm current thick bars thick bars thick bars thick bars thick bars thick bars NT06 400 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10 2b.30 x 5 1b.30 x 10 NT06 630 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10 2b.40 x 5 1b.40 x 10 NT08 or NW08 800 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 NT10 or NW10 1000 2b.50 x 5 1b.50 x 10 2b.50 x 5 1b.50 x 10 2b.63 x 5 1b.63 x 10 NT12 or NW12 1250 2b.63 x 5 1b.63 x 10 2b.63 x 5 1b.63 x 10 3b.50 x 5 2b.50 x 10 NT16 or NW16 1400 2b.63 x 5 1b.63 x 10 2b.63 x 5 1b.63 x 10 3b.50 x 5 2b.50 x 10 NT16 or NW16 1600 2b.80 x 5 1b.80 x 10 2b.80 x 5 1b.80 x 10 3b.63 x 5 2b.50 x 10 NW20 1800 2b.80 x 5 1b.80 x 10 2b.80 x 5 2b.50 x 10 3b.80 x 5 2b.63 x 10 NW20 2000 2b.100 x 5 2b.63 x 10 2b.100 x 5 2b.63 x 10 3b.100 x 5 2b.80 x 10 NW25 2200 2b.100 x 5 2b.63 x 10 2b.100 x 5 2b.63 x 10 3b.100 x 5 2b.80 x 10 NW25 2500 4b.80 x 5 2b.80 x 10 4b.80 x 5 2b.80 x 10 4b.100 x 5 3b.80 x 10 NW32 2800 4b.100 x 5 2b.100 x 10 4b.100 x 5 2b.100 x 10 4b.100 x 5 3b.80 x 10 NW32 3000 5b.100 x 5 3b.80 x 10 6b.100 x 5 3b.100 x 10 5b.100 x 5 4b.80 x 10 NW32 3200 6b.100 x 5 3b.100 x 10 6b.100 x 5 3b.100 x 10 4b.100 x 10 NW40 3800 4b.100 x 10 4b.100 x 10 4b.100 x 10 NW40 4000 4b.100 x 10 4b.100 x 10 4b.100 x 10 NW50 4500 5b.100 x 10 5b.100 x 10 6b.100 x 10 NW50 5000 5b.100 x 10 6b.100 x 10 7b.100 x 10 NW63 5700 7b.100 x 10 7b.100 x 10 8b.100 x 10 NW63 6300 8b.100 x 10 8b.100 x 10 Example Conditions: c drawout version c vertical connections c Ti: 40 C c service current: 1100 A. Solution : For Ti = 40 C use an NT12 or NW12 which can be connected with two 63 x 5 mm bars or with one 63 x 10 mm bar. Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 103
Installation recommendations Temperature derating Temperature derating The table below indicates the maximum current rating, for each connection type, as a function of the ambient temperature around the circuit breaker and the busbars. Circuit breakers with mixed connections have the same derating as horizontally connected breakers. For ambient temperatures greater than 60 C, consult us. Ti: temperature around the circuit breaker and its connection version drawout fixed connection front or rear horizontal rear vertical front or rear horizontal rear vertical temp. Ti 40 45 50 55 60 40 45 50 55 60 40 45 50 55 60 40 45 50 55 60 NT06 H1/L1 630 630 630 630 NT08 H1/L1 800 800 800 800 NT10 H1/L1 1000 1000 1000 1000 NT12 H1 1250 1250 1250 1250 NT16 H1 1600 1520 1480 1430 1600 1560 1510 1600 1550 1600 NW08 N/H/L 800 800 800 800 NW10 N/H/L 1000 1000 1000 1000 NW12 N/H/L 1250 1250 1250 1250 NW16 N/H/L 1600 1600 1600 1600 NW20 H1/H2/H3 2000 1980 1890 2000 2000 1920 2000 NW20 L1 2000 1900 1850 1800 2000 NW25 H1/H2/H3 2500 2500 2500 2500 NW32 H1/H2/H3 3200 3100 3000 2900 3200 3200 3200 NW40 H1/H2/H3 4000 3900 3750 3650 4000 3850 4000 3900 3800 4000 NW40b H1/H2 4000 4000 4000 4000 NW50 H1/H2 5000 5000 5000 5000 NW63 H1/H2 6300 6200 6300 Power dissipation and input / output resistance Total power dissipation is the value measured at IN, 50/60 Hz, for a 3 pole or 4 pole breaker (values above the power P=3RI 2 ). The resistance between input / output is the value measured per pole (cold state). version drawout fixed power dissipation (Watts) input/output resistance (µohm) power dissipation (Watts) input/ouput resistance (µohm) NT06 H1/L1 55/115 (H1/L1) 38/72 30/45 26/39 NT08 H1/L1 90/140 (H1/L1) 38/72 50/80 26/39 NT10 H1/L1 150/230 (H1/L1) 38/72 80/110 26/39 NT12 H1 250 36 130 26 NT16 H1 460 36 220 26 NW08 N1 137 42 62 19 NW08 H/L 100 30 42 13 NW10 N1 220 42 100 19 NW10 H/L 150 30 70 13 NW12 N1 330 42 150 19 NW12 H/L 230 27 100 13 NW16 N1 480 37 220 19 NW16 H/L 390 27 170 13 NW20 H/L 470 27 250 13 NW25 H1/H2/H3 600 19 260 8 NW32 H1/H2/H3 670 13 420 8 NW40 H1/H2/H3 900 11 650 8 NW40b H1/H2 550 7 390 5 NW50 H1/H2 590 7 420 5 NW63 H1/H2 950 7 660 5 104
Derating in switchboard Factors affecting switchboard design The temperature around the circuit breaker and its connections: This is used to define the type of circuit breaker to be used and its connection arrangement. Vents at the top and bottom of the cubicles: Vents considerably reduce the temperature inside the switchboard, but must be designed so as to respect the degree of protection provided by the enclosure. For weatherproof heavy-duty cubicles, a forced ventilation system may be required. The heat dissipated by the devices installed in the switchboard: This is the heat dissipated by the circuit breakers under normal conditions (service current). The size of the enclosure: This determines the volume for cooling calculations. Switchboard installation mode: Free-standing, against a wall, etc. Horizontal partitions: Partitions can obstruct air circulation within the enclosure. Basis of tables c switchboard dimensions c number of circuit-breakers installed c type of breaker connections c drawout versions c ambient temperature outside of the switchboard: Ta (IEC 60439-1). NT06-16 H1/L1 (switchboard 2000 x 400 x 400 mm) Type NT06 H1/L1 NT08 H1/L1 NT10 H1/L1 NT12 H1 NT16 H1 Switchboard composition 4 3 2 1 E47710A E47709A Connection type Busbar dimensions (mm) 2b. 40x5 2b. 50x5 3b. 63x5 3b. 63x5 3b. 80x5 2b. 63x5 3b. 50x5 3b. 63x5 Ventilated switchboard 4 H1/L1 H1/L1 ( IP31) 3 630 630 800 800 1000/1000 1000/1000 1250 1250 1400 1520 T a = 35 C 2 1 4 3 630 630 800 800 1000/950 1000/1000 1250 1250 1330 1440 T a = 45 C 2000 2 1 4 3 630 630 800 800 1000/890 1000/960 1200 1250 1250 1340 T a = 55 C 2 1 400 400 Non ventilated switchboard ( IP54) 400 400 2000 T a = 35 C T a = 45 C T a = 55 C 4 3 630 630 800 800 1000/960 1000/1000 1250 1250 1330 1400 2 1 4 3 630 630 800 800 1000/910 1000/980 1220 1250 1260 1330 2 1 4 3 630 630 800 800 1000/860 1000/930 1150 1230 1200 1260 2 1 Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 105
Installation recommendations Derating in switchboards NT06-08 H1/L1 (switchboard 2300 x 1100 x 500 mm) Type NT06 H1/L1 NT08 H1/L1 Switchboard composition Connection type 5 4 3 2 1 E47711B E47712B Busbar dimensions (mm) Ventilated switchboard ( IP31) T a = 35 C 2300 T a = 45 C 200 600 300 T a = 55 C 500 Non ventilated switchboard ( IP54) T a = 35 C 2300 200 600 300 500 T a = 45 C T a = 55 C 2b. 40x5 2b. 50x5 5 630 630 800 4 630 630 630 800 800 3 630 630 630 630 800 800 800 2 630 630 630 630 630 630 800 800 800 800 800 1 630 5 630 630 800 4 630 630 630 800 800 3 630 630 630 630 800 800 800 2 630 630 630 630 630 630 800 800 800 800 800 1 630 5 630 630 800 4 630 630 630 800 800 3 630 630 630 630 800 800 800 2 630 630 630 630 630 630 800 800 800 800 800 1 630 5 630 630 800 4 630 630 630 800 800 3 630 630 630 630 800 800 800 2 630 630 630 630 630 630 800 800 800 800 800 1 630 5 630 630 800 4 630 630 630 800 800 3 630 630 630 630 800 800 800 2 630 630 630 630 630 630 800 800 800 800 800 1 630 5 630 630 800 4 630 630 630 800 800 3 630 630 630 630 800 800 800 2 630 630 630 630 630 630 800 800 800 800 800 1 630 Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 106
NT10-16 H1/L1 (switchboard 2300 x 1100 x 500 mm) Type NT10 H1/L1 NT12 H1 NT16 H1 Switchboard composition Connection type 5 4 3 2 1 E47711B E47712B Busbar dimensions (mm) Ventilated switchboard ( IP31) T a = 35 C 2300 T a = 45 C 200 600 T a = 55 C 300 500 Non ventilated switchboard ( IP54) T a = 35 C 2300 200 600 300 500 T a = 45 C T a = 55 C 3b. 63x5 3b. 63x5 3b. 50x5 3b. 80x5 3b. 63x5 2b. 63x5 5 H1/L1 H1/L1 H1/L1 H1/L1 4 1000/1000 1250 3 1000/1000 1000/1000 1250 1250 1500 2 1000/1000 1000/1000 1000/1000 1000/1000 1250 1250 1250 1250 1460 1600 1550 1 5 4 1000/1000 1250 3 1000/1000 1000/1000 1250 1250 1420 2 1000/960 1000/1000 1000/1000 1000/1000 1250 1250 1250 1250 1400 1500 1480 1 5 4 1000/920 1250 3 1000/950 1000/930 1250 1250 1330 2 1000/900 1000/1000 1000/970 1000/950 1250 1250 1250 1250 1300 1400 1370 1 5 4 1000/950 1250 3 1000/1000 1000/960 1250 1250 1370 2 1000/1000 1000/1000 1000/1000 1000/970 1250 1250 1250 1250 1400 1500 1400 5 4 1000/900 1180 3 1000/950 1000/910 1250 1190 1300 2 1000/950 1000/1000 1000/960 1000/930 1250 1250 1250 1220 1350 1430 1320 5 4 1000/850 1120 3 1000/900 1000/860 1200 1130 1210 2 1000/880 1000/970 1000/910 1000/870 1210 1250 1210 1150 1250 1350 1250 Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 107
Installation recommendations Derating in switchboards NW08-10 N/H/L (switchboard 2300 x 800x 900 mm) Type NW08 N/H/L NW10 N/H/L Switchboard composition 4 3 2 1 Connection type E47713A E47714A Busbar dimensions (mm) Ventilated switchboard ( IP31) T a = 35 C 2300 900 800 T a = 45 C T a = 55 C Non ventilated switchboard ( IP54) T a = 35 C 2300 T a = 45 C T a = 55 C 900 800 2b. 50x5 3b. 63x5 2b. 63x5 4 800 3 800 800 1000 2 800 800 800 1000 1000 1 800 800 800 800 800 1000 1000 1000 1000 4 800 3 800 800 1000 2 800 800 800 1000 1000 1 800 800 800 800 800 1000 1000 1000 1000 4 800 3 800 800 1000 2 800 800 800 1000 1000 1 800 800 800 800 800 1000 1000 1000 1000 4 800 3 800 800 1000 2 800 800 800 1000 1000 1 800 800 800 800 800 1000 1000 1000 1000 4 800 3 800 800 1000 2 800 800 800 1000 1000 1 800 800 800 800 800 1000 1000 1000 1000 4 800 3 800 800 1000 2 800 800 800 1000 1000 1 800 800 800 800 800 1000 1000 1000 1000 Note The values indicated in these tables have been extrapolated from test data arnd theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 108
NW12-16 N/H/L (switchboard 2300 x 800 x 900 mm) Type NW12 N1 NW12 H/L NW16 N1 NW16 H/L Switchboard composition 4 3 2 1 Connection type E47713A E47714A Busbar dimensions (mm) Ventilated switchboard ( IP31) T a = 35 C 2300 900 800 T a = 45 C T a = 55 C Non ventilated switchboard ( IP54) T a = 35 C T 2300 a = 45 C T a = 55 C 900 800 3b. 63x5 3b. 50x5 3b. 63x5 3b. 50x5 3b. 80x5 3b. 63x5 3b. 80x5 3b. 63x5 4 3 1250 1250 2 1250 1250 1250 1250 1600 1600 1 1250 1250 1250 1250 1250 1250 1250 1250 1550 1600 1600 1600 1600 1600 4 3 1250 1250 2 1250 1250 1250 1250 1500 1600 1 1250 1250 1250 1250 1250 1250 1250 1250 1470 1600 1600 1600 1600 1600 4 3 1250 1250 2 1250 1250 1250 1250 1380 1470 1 1200 1250 1250 1250 1250 1250 1250 1250 1380 1500 1500 1520 1600 1600 4 3 1240 1250 2 1250 1250 1250 1250 1425 1600 1 1250 1250 1250 1250 1250 1250 1250 1250 1440 1550 1550 1600 1600 1600 4 3 1170 1250 2 1210 1210 1250 1250 1360 1500 1 1200 1250 1250 1250 1250 1250 1250 1250 1360 1470 1470 1500 1600 1600 4 3 1100 1250 2 1140 1170 1250 1250 1280 1400 1 1130 1200 1200 1200 1250 1250 1250 1250 1280 1380 1380 1400 1520 1520 Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 109
Installation recommendations Derating in switchboards NW20-40 N/H/L (switchboard 2300 x 800 x 900 mm) Type NW20 H1/H2/H3 NW20 L1 NW25 H1/2/3 NW32 H1/2/3 NW40 H1/2/3 Switchboard composition 4 3 2 1 Connection type E47714A E47713A Busbar dimensions (mm) Ventilated switchboard ( IP31) T a = 35 C 2300 T a = 45 C T a = 55 C 900 800 Non ventilated switchboard ( IP54) T a = 35 C T 2300 a = 45 C T a = 55 C 900 800 3b. 100x5 3b. 100x5 4b. 100x5 3b. 100x10 4b. 100x10 4 3 2000 1830 2 2000 2000 2000 2000 2000 2000 2375 2500 3040 3200 3320 3700 1 4 3 2000 1750 2 2000 2000 2000 1810 1960 1920 2250 2380 2880 3100 3160 3500 1 4 3 1880 1640 2 2000 2000 2000 1700 1850 1800 2100 2250 2690 2900 2960 3280 1 4 3 2000 1750 2 2000 2000 2000 1800 1900 1890 2125 2275 2650 2850 3040 3320 1 4 3 1900 1660 2 1900 1960 1960 1680 1810 1800 2000 2150 2550 2700 2880 3120 1 4 3 1780 1550 2 1800 1920 1920 1590 1700 1700 1900 2020 2370 2530 2720 2960 1 Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 110
NW40b-63 H1/H2 (switchboard 2300 x 1400 x 1500 mm) Type NW40b H1/H2 NW50 H1/H2 NW63 H1/H2 Switchboard composition 4 3 2 1 Connection type E47716B Busbar dimensions Ventilated switchboard ( IP31) 2300 T a = 35 C T a = 45 C T a = 55 C 5b. 100x10 7b. 100x10 8b. 100x10 4 3 2 4000 4000 4700 5000 6050 1 4 3 2 4000 4000 4450 4850 5670 1 4 3 2 4000 4000 4200 4600 5350 1 1500 1400 E47715B Non ventilated switchboard ( IP54) T a = 35 C T a = 45 C 2300 T a = 55 C 4 3 2 4000 4000 4350 4650 5290 1 4 3 2 4000 4000 4100 4400 5040 1 4 3 2 3840 3840 3850 4150 4730 1 1500 1400 Note The values indicated in these tables have been extrapolated from test data and theoretical calculations. These tables are only intended as a guide and cannot replace industrial experience or a temperature rise test. 111
Installation recommendations Substitution kit Fixed / drawout devices 800 to 3200 A It is possible to replace a (M08 to M32) with a new (NW08 to NW32) with the same power rating. Substitution is possible for the following types of circuit breakers: c N1, H1, H2 for both fixed and drawout versions c L1 for drawout versions up to 2000 A. Mounting diagram Fixed version Drawout version E59218B Ø14 Y 2Ø9,5 X 25 E59219A 2 Ø11,5 x 22 Y Ø14 4 Ø6,5 Ø9,5 2Ø11 X 6 124 150 162 10 Ø11,5 110 175 Ø11 F Ø11 Ø10,5 200 (3P) 315 (4P) 200 2 Ø11 X 6 F 167,5 (3P) 282,5 (4P) 267,5 (4P) 162,5 : NW : M Fixing points are identical for (M08 to M32) and (NW08 to NW32), except for the four-pole craddle. Door cut-out Fixed version c without an escutcheon, the cut-out is identical (270 x 325 mm). c with the former escutcheon, the cut-out is identical (270 x 325 mm). c with the new escutcheon, the cut-out is different. Drawout version E59220A 295 mini (3P) 410 mini (4P) 295 mini Y E59221A 300 mini (3P) 415 mini (4P) Y 300 mini X 270 (1) 316 (2) 135 (1) 158 (2) 270 (1) 379 (2) X 135 (1) 222 (2) 153,3 (1) 325 (1) 364 (2) 162,5 (1) 182 (2) 325 (1) 364 (2) 162,5 (1) 182 (2) 47 (1) Power connections Select a set of retrofit connectors to replace the standard connectors and avoid any modifications to the busbars (see the retrofit section in "orders and quotations") Note: (1) Without escutcheon (2) With escutcheon References X and Y represent the symmetry planes for three-pole devices 112
E59217A M08 to M32 NW08 to NW32 Electrical diagrams Correspondences between NW and M terminal blocks Power Control unit Remote operation E59222A power N L1 L2 L3 ALR, V, MR6, R options equivalent functions using M2C or M6C fault fault AT BPO BPF ready to close charged Micrologic T1 T2 T3 T4 VN V1 V2 V3 Z1 Z2 Z3 Z4 Z5 Q I U S1 M1 M2 M3 F1 F2+ 471 474 484 Q1 Q2 Q3 S2 M2C M6C 181 182 184 SDE2 81 K2 82 84 Res SDE1 K1 D1 D2 C12 MN MX2 MX1 C11 C1 A1 C2 C3 A2 A3 252 254 MCH XF PF 251 B1 B3 B2 Z12 Z11 Z22 Z21 Z21 82 84 D4 C12 C2 A4 252 254 262 B4 or or or CH (1) SG1 SG2 X1 X2 F1 F2+ 81 D1 C11 C1 A1 251 B1 24 V DC Indication contacts Craddle contacts E59223A open closed closed not connected or connected and open connected and closed disconnected connected Test 12 14 CT3 31 21 11 42 44 32 34 22 24 OF4 OF3 OF2 OF1 41 31 21 11 41 42 44 32 34 22 24 12 14 OF.. OF CE.. 1.. 5.. 2.. 4.. 6.. 8.. 2.. 4 EF.... 1 931 911 934 932 924 922 912 CT2 CT1 371 331 921 332 334 914 372 374 CE3 321 322 324 CE2 311 312 314 334 332 324 322 314 312 CE1 331 321 311 831 821 811 832 834 822 824 812 814 362 364 352 354 CD3 CD2 CD1 or 361 351 Identical to M New or additional functions Different than M (1) The current transformer for the external neutral must be replaced 113
114
Additional characteristics Presentation 1 Functions and characteristics 9 Dimensions and connection 53 Electrical diagrams 81 Installation recommendations 91 Tripping curves 116 Limitation curves 118 References 121 115
Additional characteristics Tripping curves Micrologic 2.0 E46350 10 000 5 000 Ir = 0,4 1 x In 2 000 1 000 500 200 100 50 tr = 0,5...24 s t(s) 20 10 5 2 1.5.2.1.05.02.01.005 Isd = 1,5 10 x Ir.002.001.5.7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 I / Ir Micrologic 5.0, 6.0, 7.0 E46276 10 000 5 000 2 000 1 000 500 200 100 50 Ir = 0,4 1 x In tr = 0,5 24 s 20 10 t(s) 5 2 1.5.2.1.05 0,4 0,3 0,2 0,1 I 2 t OFF 0 I 2 t ON 0,4 0,3 0,2 0,1 0 Isd = 1,5 10 x Ir.02.01.005 Ii = 2 15 x In. OFF.002.001.5.7 1 2 3 4 5 7 10 20 3 5 7 10 20 30 x Ir x In 116
Earth-fault protection (Micrologic 6.0) E46266 10 000 5 000 2 000 1 000 500 Ig = A J x In (1) 1200 A max. t(s) 200 100 50 20 10 5 2 1.5.2.1.05.02.01.005 I 2 t ON 0.4 0.4 0.3 0.3 0.2 0.2 I 2 0.1 0.1 t OFF 0 0 (1).002.001.05.07.1.2.3.4.5.7 1 2 3 5 7 10 200 300 I / In Ig = In x A B C D E F G H J Ig < 400 A 0,3 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 400 A i Ig i 1200 A 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1 Ig > 1200 A 500 640 720 800 880 960 1040 1120 1200 IDMTL curve (Micrologic P and H) E47587 100 000 10 000 5 000 HVF 2 000 1 000 500 EIT t(s) 200 100 50 20 10 5 VIT SIT DT 2 1.5.5.7 1 2 3 4 5 7 10 20 I / Ir 117
Additional characteristics Limitation curves Current limiting E47519 Voltage 380/415 V AC 300 NW H3 200 NW L1 kâ 100 80 70 60 50 40 30 NT L1 20 10 20 30 40 60 100 200 ka rms Voltage 660/690 V AC E47520 300 200 NW H3 NW L1 kâ 100 80 70 60 50 40 30 NT L1 20 10 20 30 40 60 100 200 ka rms 118
Energy limiting Voltage 380/415 V AC E47521 10 9 5 3 2 NW H3 A 2 s 10 8 5 3 2 NW L1 10 7 5 3 2 NT L1 10 6 10 20 30 40 60 100 150 200 300 ka rms Voltage 660/690 V AC E47522 10 9 5 3 2 NW H3 A 2 s 10 8 5 3 2 NW L1 10 7 5 NT L1 3 2 10 6 10 20 30 40 60 100 150 200 300 ka rms 119
120
References Presentation 1 Functions and characteristics 9 Dimensions and connection 53 Electrical diagrams 81 Installation recommendations 91 Additional characteristics 121 Accessories for communication Bus 122 Order form 123 NT06 to NT16 fixed circuit breakers Circuit breaker selection 124 Indication contacts 126 Remote operation 127 NT06 to NT16 drawout circuit breakers 128 Circuit breaker selection 128 Chassis locking and accessories 130 Indication contacts 131 Remote operation 132 Accessories for NT06 to NT16 fixed 133 and drawout circuit breakers NT06 to NT16 fixed switch-disconnectors Circuit breaker selection 136 NT06 to NT16 drawout switch-disconnectors Circuit breaker selection 138 NW08 to NW63 fixed circuit breakers Circuit breaker selection 140 Indication contacts 142 Remote operation 143 NW08 to NW63 drawout circuit breakers Circuit breaker selection 144 Chassis locking and accessories 146 Indication contacts 148 Remote operation 149 Accessories for NW08 to NW63 fixed 150 and drawout circuit breakers NW08 to NW63 fixed switch-disconnectors Circuit breaker selection 152 NW08 to NW63 drawout switch-disconnectors Circuit breaker selection 154 Retrofit solutions 156 Connection for fixed devices 156 Connection for drawout devices 157 121
Orders and quotations Accessories for communication Bus Digipact display module DMB300 display module 50894 E67954 DMC300 display module 50895 E67955 Spare parts Memory card DMC300PCM 50959 Digipact Bus pre-wired system Data concentrator DC150 Auxiliary supply voltage 110-240 V AC, 50/60 Hz and 115-125 V DC 50823 E79014 Junction block Junction block for internal Bus 50778 E67956 Cables E67957 Cable for internal bus 20-meter roll (0.75 mm 2 ) 50779 100-meter roll (0.75 mm 2 ) 50780 Modbus pre-wired system Connection block CJB306 6 connections RS485 block + power 50963 E67959 E67958 CSD309 RS485 9 pins SubD connector 50964 Cables CDM303 display module cable (L: 3 m) 50960 E79015 E67960 CCP303 RS485 Modbus cable + power (L: 3 m) (Micrologic) 50961 CCS303 RS485 Modbus cable (L: 3 m) (Modbus slave) 50962 CCR301 power + RS485 roll cable (L: 60 m) (Bus Modbus) 50965 E67961 Converter RS485/RS232 (ACE909) 12 V DC power supply included 50786 RS485/RS232 TSX SCA72 (1) RS485/Ethernet 174 CEV 300-10 (1) RS485/Ethernet (SMS compatible) 3050 EGW2 (2) (1) see catalogue Telemecanique. (2) see catalogue Square D. 122
Order form NT and NW To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles Basic device Quantity type NT, NW Frame size 06 to 63 Sensor rating A Circuit breaker N1, H1, H2, H3, L1 Switch-disconnector NA, HA, HF Number of poles 3 or 4 Option : Neutral on right side Type of device Fixed Drawout with chassis Chassis alone Drawout without chassis Micrologic control unit A - ammeter 2.0 A 5.0 A 6.0 A 7.0 A P - power meter 5.0 P 6.0 P 7.0 P H - harmonic meter 5.0 H 6.0 H 7.0 H TCE - external sensor (CT) for neutral + earth-fault protection TCE - external sensor (CT) for double neutral protection (Micrologic P and H with 3-poles) TCW - external sensor for SGR protection Rectangular sensor for earth-leakage protection 280 x 115 470 x 160 LT - long-time rating plug (standard setting 0.4 to 1 x Ir) Low setting option 0.4 to 0.8 Ir High setting option 0.8 to 1 Ir LT OFF option PTE - external voltage measurement input AD - external power-supply module BAT - battery module Communication COM Eco COM Connection Digipact Modbus Modbus Horizontal Top Bottom Vertical Top Bottom Front Top Bottom Bare-cable connectors NT-FC fixed 4 x 240 mm 2 + connector shield Vertical-connection adapters NT-FC, fixed, draw. Cable-lug adapters NT-FC, fixed, draw. Interphase barriers NT, NW-fixed, draw. Spreaders NT-fixed, drawout Disconnectable front-connection NW-fixed adapter VO - safety shutters on chassis NT, NW VIVC - shutter position indication NW and locking Key for Micrologic control units: 2.0 : basic protection (long-time + inst.) 5.0 : selective protection (long-time + short-time + inst.) 6.0 : selective + earth-fault protection (long-time + short-time + inst. + earth-fault) 7.0 : selective + earth-leakage protection (long-time + short-time + inst. + earth-leakage) Locking VBP - ON/OFF pushbutton locking OFF position locking VCPO - by padlocks VSPO - by keylocks Locking kit Profalux Ronis without keylocks 1 lock 1 lock + 1 lock with same key profile 2 locks (different key profiles) for NW VSPD - chassis locking in ''disconnected'' position VPEC - door interlock Locking kit Profalux Ronis without keylocks 1 lock 1 lo ck + 1 lock with same key profile 2 locks (different key profiles) Optional connected - disconnected - test position locking Latch on right-hand side of chassis Latch on left-hand side of chassis VPOC - racking interlock IPA - cable-type door interlock IBPO - racking interlock between crank and OFF pushbutton for NW DAE - automatic spring discharge before breaker removal for NW VDC - mismatch protection Indication contacts OF - ON/OFF indication contacts Standard 4 OF 6 A - 240 V AC (10 A - 240 V AC and low-level for NW) Alternate 1 OF low-level for NT Max. 4 qty (replaces a standard contact) Additional 1 block of 4 OF for NW Max. 2 qty EF - combined ''connected/closed'' contacts 1 EF 5 A - 240 V AC for NW Max. 8 qty 1 EF low-level for NW Max. 8 qty SDE - ''fault-trip'' indication contacts Standard 1 SDE 5 A - 240 V AC Additional 1 SDE 5 A - 240 V AC 1 SDE low-level Programmable contacts 2 M2C contacts 6 M6C contacts Carriage switches low-level 6 A - 240 V AC CE - ''connected'' position Maxi. 3 for NT and NW qty CD - ''disconnected'' position Maxi. 2 for NT and 3 for NW qty CT - ''test'' position Maxi. 1 for NT and 3 for NW qty AC - actuator for additional carriage switches qty Remote operation Remote ON/OFF MCH - gear motor V XF - closing voltage release V MX - opening voltage release V PF - ''ready to close'' contact low-level 6 A - 240 V AC BPFE - electrical closing pushbutton Res - electrical reset option RAR - automatic reset option Remote tripping MN - undervoltage release V R - delay unit (non-adjustable) Rr - adjustable delay unit 2 nd MX - shunt release V Accessories CDM - mechanical operation counter CB - auxiliary terminal shield for chassis CDP - escutcheon CP - transparent cover OP - blanking plate Brackets for mounting on backplates 123
Orders and quotations NT06 to NT16 fixed circuit breakers Circuit breaker selection E46423 A fixed circuit breaker is described by 4 catalogue numbers corresponding to: b the basic circuit breaker b a control unit b a top connection b a bottom connection A communication option and various auxiliaries and accessories many also be added.. Basic circuit breaker Type H1 3P 4P In (A at 40 C) Icu (ka for U = 220/415 V) - Ics = 100% Icu NT06 630 42 47110 47115 NT08 800 42 47120 47125 NT10 1000 42 47130 47135 NT12 1250 42 47140 47145 NT16 1600 42 47150 47155 Type L1 3P 4P In (A at 40 C) Icu (ka for U = 220/415 V) - Ics = 100% Icu NT06 630 150 47112 47117 NT08 800 150 47122 47127 NT10 1000 150 47132 47137 Option Neutral on the right (*) Micrologic control unit "ammeter" A 3P/4P Micrologic 2.0 A basic protection 47282 Micrologic 5.0 A selective protection 47285 Micrologic 6.0 A selective + earth-fault protection 47286 Micrologic 7.0 A selective + earth-leakage protection 47287 "power meter" P 3P/4P Micrologic 5.0 P selective protection 47289 Micrologic 6.0 P selective + earth-fault protection 47290 Micrologic 7.0 P selective + earth-leakage protection 47291 "harmonic meter" H 3P/4P Micrologic 5.0 H selective protection 47293 Micrologic 6.0 H selective + earth-fault protection 47294 Micrologic 7.0 H selective + earth-leakage protection 47295 Communication option Modbus COM 47405 Modbus COM eco 47406 Digipact COM 47409 (*) consult us Auxiliaries and accessories: b for fixed devices: see page 126 b for fixed or drawout devices: see page 133 Switch-disconnector version: see page 136 Source changeover assembly: see page 133 124
Front connection E47757 3P 4P 630/1600 A Top 47328 47330 Bottom 47329 47331 Front connection accessories Bare-cable connectors + 1 connector shield for 4 x 240 mm 2 cables 3P (3 parts) 47333 4P (4 parts) 47334 E46887 Vertical connection adapters 630/1600 A 3P (3 parts) 33642 4P (4 parts) 33643 E46426 Cable lug adapters 630/1600 A 3P (3 parts) 33644 4P (4 parts) 33645 E46427 Interphase barriers 3P/4P (3 parts) 33648 E79060 Arc chute screen E74437 E46429 E46430 3P 47335 4P 47336 Rear connection Vertical connection 3P 4P 630/1600 A Top 33604 33614 Bottom 33605 33615 Horizontal connection 3P 4P 630/1600 A Top 33606 33616 Bottom 33607 33617 Rear connection accessories Interphase barriers 3P/4P (3 parts 33648 E79060 Common accessories for front and rear connections Spreaders E46431 630/1600 A 3P 33622 4P 33623 For front and horizontal rear connection Cable lug kits E47820 240 mm 2 3P (6 lug kit) 33013 4P (8 lug kit) 33014 300 mm 2 3P (6 lug kit) 33015 4P (8 lug kit) 33016 125
Orders and quotations NT06 to NT16 fixed circuit breakers (cont.) Indication contacts ON/OFF indication contacts (OF) Changeover contacts (6 A - 240 V) 4 (standard) 1 low-level OF to replace 1 standard OF (4 max.) 47339 E46463 "Fault trip" indication contacts (SDE) Changeover contact (5 A - 240 V) 1 (standard) 1 additional SDE (5 A - 240 V) 47340 1 additional low-level SDE 47341 E47758 Programmable contacts (*) (programmed via Micrologic control unit) 2 contacts (M2C) (5 A - 240 V) 47403 6 changeover contacts (M6C) (5 A - 240 V) 47404 (*) for Micrologic control units P and H only. E46434 M2C E46435 M6C 126
Remote operation Remote ON/OFF Gear motor MCH AC 50/60 Hz 48 V 47391 100-130 V 47395 200-240 V 47396 277-415 V 47398 440-480 V 47400 DC 24-30 V 47390 48-60 V 47391 100-130 V 47392 200-250 V 47393 Instantaneous voltage releases Closing release Opening release Standard XF MX AC 50/60 Hz 12 V DC 47349 47359 DC 24-30 V DC, 24 V AC 47350 47360 48-60 V DC, 48 V AC 47351 47361 100-130 V 47352 47362 200-250 V 47353 47363 277 V AC 47354 47364 380-480 V AC 47355 47365 Communicating XF com MX com AC 50/60 Hz 12 V DC 47310 47320 DC 24-30 V DC, 24 V AC 47311 47321 48-60 V DC, 48 V AC 47312 47322 100-130 V 47313 47323 200-250 V 47314 47324 277 V AC 47315 47325 380-480 V AC 47316 47326 "Ready to close" contact (1 max.) PF 1 changeover contact (5 A - 240 V) 47342 1 low-level changeover contact 47343 E46436 E46437 E46438 Electrical closing pushbutton BPFE 1 pushbutton 47512 E46439 Remote reset after fault trip Electrical reset Res 110-130 V AC 47344 220-240 V AC 47345 Automatic reset RAR Adaptation 47346 (*) E46660 Remote tripping Instantaneous voltage release E46437 MN delay unit E46694 (*) no charge. 2 nd MX or MN AC 50/60 Hz 12 V DC 47369 DC 24-30 V DC, 24 V AC 47370 47380 48-60 V DC, 48 V AC 47371 47381 100-130 V 47372 47382 200-250 V 47373 47383 277 V AC 47374 380-480 V AC 47375 47385 R (non-adjustable) Rr (adjustable) AC 50/60 Hz 48-60 V 33680 DC 100-130 V 33684 33681 200-250 V 33685 33682 380-480 V 33683 127
Orders and quotations NT06 to NT16 drawout circuit breakers Circuit breaker selection E46441 A drawout circuit breaker is described by 5 catalogue numbers corresponding to: b the basic circuit breaker b a control unit b a chassis b a top connection b a bottom connection A communication option and various auxiliaries and accessories many also be added.. Basic circuit breaker Type H1 3P 4P In (A at 40 C) Icu (ka for U = 220/415 V) - Ics = 100% Icu NT06 630 42 47200 47205 NT08 800 42 47210 47215 NT10 1000 42 47220 47225 NT12 1250 42 47230 47235 NT16 1600 42 47240 47245 Type L1 3P 4P In (A at 40 C) Icu (ka for U = 220/415 V) - Ics = 100% Icu NT06 630 150 47202 47207 NT08 800 150 47212 47217 NT10 1000 150 47222 47227 Option Neutral on the right (*) Micrologic control unit "ammeter" A 3P/4P Micrologic 2.0 A basic protection 33525 Micrologic 5.0 A selective protection 33532 Micrologic 6.0 A selective + earth-fault protection 33533 Micrologic 7.0 A selective + earth-leakage protection 33534 "power meter" P 3P/4P Micrologic 5.0 P selective protection 47297 Micrologic 6.0 P selective + earth-fault protection 47298 Micrologic 7.0 P selective + earth-leakage protection 47299 "harmonic meter" H 3P/4P Micrologic 5.0 H selective protection 47301 Micrologic 6.0 H selective + earth-fault protection 47302 Micrologic 7.0 H selective + earth-leakage protection 47303 Chassis For type H1 3P 4P 630/1250 A 33722 33725 1600 A 33723 33726 For type L1 3P 4P 630/1000 A 33723 33726 Communication option Chassis + Circuit breaker Modbus COM 33852 47485 Modbus eco COM 33843 Digipact COM 33855 47489 (*) consult us Auxiliaries and accessories: b for drawout devices: see page 130 b for fixed or drawout devices: see page 133 Switch-disconnector version: see page 136 Source changeover assembly: see page 133 128
Chassis front connection 3P 4P 630/1600 A Top 33727 33733 Bottom 33728 33734 E46440 Front connection accessories Vertical connection adapters 630/1600 A 3P (3 parts) 33642 4P (4 parts) 33643 E46426 Cable lug adapters 630/1600 A 3P (3 parts) 33644 4P (4 parts) 33645 E46427 Chassis rear connection Vertical connection 3P 4P 630/1600 A Top 33729 33735 Bottom 33730 33736 Horizontal connection 3P 4P 630/1600 A Top 33731 33737 Bottom 33732 33738 Rear connection accessories Interphase barriers 3P/4P (3 parts) 33768 E46429 E46430 E46428 Common accessories for front and rear connection Spreaders E46431 630/1600 A 3P 33622 4P 33623 For front and horizontal rear connection. Cable lug kits E47820 240 mm 2 3P (6 lug kit) 33013 4P (8 lug kit) 33014 300 mm 2 3P (6 lug kit) 33015 4P (8 lug kit) 33016 129
Orders and quotations NT06 to NT16 drawout circuit breakers (cont.) Chassis locking and accessories Chassis locking "Disconnected" position locking E46685 Door interlock (1 part) E46464 By padlocks Standard By keylocks Profalux 1 lock 33773 1 lock + 1 lock with same key profile 33774 2 locks (different key profiles) 33775 Ronis 1 lock 33776 1 lock + 1 lock with same key profile 33777 2 locks (different key profiles) 33778 Optional disconnected/test/connected position locking 33779 (*) Locking kit without locks for Profalux 33769 Ronis 33770 Castell 33771 Kirk 33772 Right-hand side of chassis (VPECD) 33786 Left-hand side of chassis (VPECG) 33787 Racking interlock Racking interlock (VPOC) 33788 E46465 Breaker mismatch protection Breaker mismatch protection (VDC) 33767 E47765 Chassis accessories Arc chute cover 3P/4P Standard E46700 Auxiliary terminal shield (CB) Terminal shield 3P 33763 4P 33764 E46698 Safety shutters E46699 Safety shutters (VO) 3P 33765 4P 33766 (*) no charge. 130
Indication contacts ON/OFF indication contacts (OF) Changeover contacts (6 A - 240 V) 4 (standard) E46467 1 low-level OF to replace 1 standard OF (4 max.) 33806 "Fault trip" indication contacts (SDE) Changeover contact (5 A - 240 V) 1 (standard) E47759 1 additional SDE (5 A - 240 V) 47430 1 additional low-level SDE 47431 Programmable contacts (*) (programmed via Micrologic control unit) 2 contacts M2C (5 A - 240 V) 47483 6 changeover contacts M6C (5 A - 240 V) 47484 (*) for Micrologic control units P and H only. E46686 M2C E46687 M6C Carriage switches (connected / disconnected / test position) Changeover contacts (6A - 240 V) 1 connected position contact (3 max.) 33751 1 test position contact (1 max.) 33752 1 disconnected position contact (2 max.) 33753 And/or low-level changeover contacts 1 connected position contact (3 max.) 33754 1 test position contact (1 max.) 33755 1 disconnected position contact (2 max.) 33756 Auxiliary terminals for chassis alone 3 wire terminal (30 parts) 47071 6 wire terminal (10 parts) 47072 Jumpers (10 parts) 47900 E46661 131
Orders and quotations NT06 to NT16 drawout circuit breakers (cont.) Remote operation Remote ON/OFF Gear motor MCH AC 50/60 Hz 48 V 47461 100-130 V 47465 200-240 V 47466 277-415 V 47468 440-480 V 47470 DC 24-30 V 47460 48-60 V 47461 100-130 V 47462 200-250 V 47463 Instantaneous voltage release Closing release E46662 Opening release Standard XF MX AC 50/60 Hz 12 V DC 47439 33809 DC 24-30 V DC, 24 V AC 47440 33810 48-60 V DC, 48 V AC 47441 33811 100-130 V 47442 33812 200-250 V 47443 33813 277 V AC 47444 33814 380-480 V AC 47445 33815 Communicating XF com MX com AC 50/60 Hz 12 V DC 47411 33791 DC 24-30 V DC, 24 V AC 47412 33792 48-60 V DC, 48 V AC 47413 33793 100-130 V 47414 33794 200-250 V 47415 33795 277 V AC 47416 33796 380-480 V AC 47417 33797 "Ready to close" contact (1 max.) PF 1 changeover contact (5 A - 240 V) 47432 1 low-level changeover contact 47433 E46664 Electrical closing pushbutton BPFE 1 pushbutton 47512 E46439 Remote reset after fault trip Electrical reset Res 110-130 V AC 47434 220-240 V AC 47435 Automatic reset RAR Adaptation 47346 (*) E46660 Remote tripping Instantaneous voltage release E46663 MN delay unit E46694 (*) no charge. 2 nd MX or MN AC 50/60 Hz 12 V DC 47449 DC 24-30 V DC, 24 V AC 47450 33819 48-60 V DC, 48 V AC 47451 33820 100-130 V 47452 33821 200-250 V 47453 33822 277 V AC 47454 380-480 V AC 47455 33824 R (non-adjustable) Rr (adjustable) AC 50/60 Hz 48-60 V 33680 DC 100-130 V 33684 33681 200-250 V 33685 33682 380-480 V 33683 132
Accessories for NT06 to NT16 fixed and drawout circuit breakers Circuit breaker locking Pushbutton locking device By padlocks 33897 E46666 OFF position locking E46666 By padlocks + BPFE support By keylocks + BPFE support Profalux 1 lock 47519 1 lock + 1 lock with same key profile 47520 Ronis 1 lock 47521 1 lock + 1 lock with same key profile 47522 Locking kit without locks for Profalux 47515 Ronis 47516 Kirk 47517 Castell 47518 Other circuit breaker accessories Mechanical operation counter 47514 operation counter CDM 33895 E46667 Escutcheon and accessories E46668 E46669 E46670 Fixed Drawout Escutcheon 33718 33857 Transparent cover (IP 54) 33859 Escutcheon blanking plate 33858 EscutcheonCoverBlanking plate Mechanical interlocking for source changeover Interlocking using connecting rods E47760 Complete assembly with 2 adaptation fixtures + rods 2 NT fixed devices 33912 2 NT drawout devices 33913 Interlocking using cables (*) Choose 2 adaptation fixtures (1 for each breaker) + 1 set of cables 1 adaptation fixture for NT fixed devices 33200 1 adaptation fixture for NT drawout devices 33201 1 set of 2 cables 33209 (*) Can be used with any combination of NT or NW, fixed or drawout devices. Cable-type door interlock E70742 1 complete assembly for NT fixed devices 33920 1 complete assembly for NT drawout devices 33921 133
Orders and quotations Accessories for NT06 to NT16 fixed or drawout circuit breakers (cont.) Accessories for Micrologic control units External sensors External sensor for earth-leakage protection (TCE) Sensor rating 400/1600 A (for Micrologic P and H with 3P devices) 33576 E46671 Rectangular sensor for earth-leakage protection 280 mm x 115 mm 33577 E46672 Source ground return (SGR) earth fault protection External sensor (SGR) 33579 E46671 MDGF summing module 48891 Voltage measurement input (for breakers supplied via bottom terminals) Voltage measurement input Fixed 47506 E46674 Drawout 47507 Long-time rating plug (limits setting range for higher accuracy) Standard 0.4 to 1 x Ir 33542 Low-setting option 0.4 to 0.8 x Ir 33543 High-setting option 0.8 to 1 x Ir 33544 Without long-time protection off 33545 E46674 Zone Selective Interlocking option for Micrologic P and H ZSI External power supply module E47787 Battery module L3 AD 220A Input 24VDC Test equipment Mini test kit G1 Output 24VDC L4 G2 Standard 24-30 V DC 54440 48-60 V DC 54441 125 V DC 54442 110 V AC 54443 220 V AC 54444 380 V AC 54445 1 24 V battery 54446 33594 E59921 Portable test kit 33595 E59554 Special settings For circuit breaker derating Catalogue number to be added to those describing the circuit breaker rating Rating NT08 NT10 NT12 NT16 400 47053 47053 630 33091 33091 33091 800 33092 33092 33092 1000 33093 33093 1250 33094 Note: for ratings In = 100 or 250 A, please contact us. 134
135
Orders and quotations NT06 to NT16 fixed switch-disconnectors Switch-disconnector selection A fixed switch-disconnector is described by 3 catalogue numbers corresponding to: b the basic switch-disconnector b a top connection b a bottom connection A communication option and various auxiliaries and accessories many also be added.. Basic switch-disconnector Type HA 3P 4P In (A at 40 C) Icm (ka peak for U = 220/690 V) NT06 630 60 47159 47160 NT08 800 60 47161 47162 NT10 1000 60 47163 47164 NT12 1250 60 47165 47166 NT16 1600 60 47167 47168 Communication option Modbus COM 47405 Digipact COM 47409 E46675 Auxiliaries and accessories: b for fixed devices: see page 126 b for fixed or drawout devices: see page 133 Source changeover assembly: see page 133 136
Front connection E47757 3P 4P 630/1600 A Top 47328 47330 Bottom 47329 47331 Front connection accessories Bare-cable connectors + 1 connector shield for 4 x 240 mm 2 cables 3P (3 parts) 47333 4P (4 parts) 47334 E46887 Vertical connection adapters 630/1600 A 3P (3 parts) 33642 4P (4 parts) 33643 E46426 Cable lug adapters 630/1600 A 3P (3 parts) 33644 4P (4 parts) 33645 E46427 Interphase barriers 3P/4P (3 parts) 33648 E79060 Rear connection Vertical connection 3P 4P 630/1600 A Top 33604 33614 Bottom 33605 33615 Horizontal connection 3P 4P 630/1600 A Top 33606 33616 Bottom 33607 33617 Rear connection accessories Interphase barriers 3P/4P (3 parts) 33648 E46429 E46430 E79060 Common accessories for front and rear connection Spreaders E46431 630/1600 A 3P 33622 4P 33623 For front and horizontal rear connection Cable lug kits E47820 240 mm 2 3P (6 lug kit) 33013 4P (8 lug kit) 33014 300 mm 2 3P (6 lug kit) 33015 4P (8 lug kit) 33016 137
Orders and quotations NT06 to NT16 drawout switch-disconnectors Switch-disconnector selection E00000 A drawout switch-disconnector is described by 4 catalogue numbers corresponding to: b the basic switch-disconnector b a chassis b a top connection b a bottom connection A communication option and various auxiliaries and accessories many also be added.. Basic switch-disconnector Type HA 3P In (A at 40 C) Icm (ka peak for U = 220/690 V) NT06 630 60 47248 47249 NT08 800 60 47250 47251 NT10 1000 60 47252 47253 NT12 1250 60 47254 47255 NT16 1600 60 47256 47257 Chassis 630/1250 A 33722 33725 1600 A 33723 33726 Communication option 3P Chassis + Switch-disconnector COM Modbus 33852 47485 COM Digipact 33855 47489 4P 4P Auxiliaries and accessories: b for drawout devices: see page 130 b for fixed or drawout devices: see page 133 Source changeover assembly: see page 133 138
Chassis front connection 3P 4P 630/1600 A Top 33727 33733 Bottom 33728 33734 E46440 Front connection accessories Vertical connection adapters 630/1600 A 3P (3 parts) 33642 4P (4 parts) 33643 E46426 Cable lug adapters 630/1600 A 3P (3 parts) 33644 4P (4 parts) 33645 E46427 Chassis rear connection Vertical connection 3P 4P 630/1600 A Top 33729 33735 Bottom 33730 33736 Horizontal connection 3P 4P 630/1600 A Top 33731 33737 Bottom 33732 33738 Rear connection accessories Interphase barriers E46429 E46430 E46428 3P/4P (3 parts) 33768 Common accessories for front and rear connection Spreaders E46431 630/1600 A 3P 33622 4P 33623 For front and horizontal rear connection Cable lug kits E47820 240 mm 2 3P (6 lug kit) 33013 4P (8 lug kit) 33014 300 mm 2 3P (6 lug kit) 33015 4P (8 lug kit) 33016 139
: price list NW08 to NW63 fixed circuit breakers Circuit breaker selection Unit price (excl.vat) in French francs E46442 E46443 A fixed circuit breaker is described by 4 catalogue numbers corresponding to: b the basic circuit breaker b a control unit b a top connection b a bottom connection A communication option and various auxiliaries and accessories may also be added. Basic circuit breaker y 4000 A Basic circuit breaker u 4000 A. Basic circuit breaker Type N1 3P 4P In (A at 40 C) Icu (ka for U = 220/440 V) - Ics = 100% Icu NW08 800 42 48000 48007 NW10 1000 42 48014 48021 NW12 1250 42 48028 48035 NW16 1600 42 48042 48049 Type H1 3P 4P In (A at 40 C) Icu (ka for U = 220/440 V) - Ics = 100% Icu NW08 800 65 48001 48008 NW10 1000 65 48015 48022 NW12 1250 65 48029 48036 NW16 1600 65 48043 48050 NW20 2000 65 48057 48064 NW25 2500 65 48070 48076 NW32 3200 65 48082 48087 NW40 4000 65 48092 48097 NW40b 4000 100 48106 48109 NW50 5000 100 48112 48115 NW63 6300 100 48118 48121 Type H2 3P 4P In (A at 40 C) Icu (ka for U = 220/440 V) - Ics = 100% Icu NW08 800 100 48002 48009 NW10 1000 100 48016 48023 NW12 1250 100 48030 48037 NW16 1600 100 48044 48051 NW20 2000 100 48058 48065 NW25 2500 100 48071 48077 NW32 3200 100 48083 48088 NW40 4000 100 48093 48098 NW40b 4000 150 48107 48110 NW50 5000 150 48113 48116 NW63 6300 150 48119 48122 Option Neutral on the right (*) Micrologic control unit "ammeter" A 3P/4P Micrologic 2.0 A basic protection 47282 Micrologic 5.0 A selective protection 47285 Micrologic 6.0 A selective + earth-fault protection 47286 Micrologic 7.0 A selective + earth-leakage protection 47287 "power meter" P 3P/4P Micrologic 5.0 P selective protection 47289 Micrologic 6.0 P selective + earth-fault protection 47290 Micrologic 7.0 P selective + earth-leakage protection 47291 "harmonic meter" H 3P/4P Micrologic 5.0 H selective protection 47293 Micrologic 6.0 H selective + earth-fault protection 47294 Micrologic 7.0 H selective + earth-leakage protection 47295 Communication option Modbus COM 48188 Modbus COM eco 47406 Digipact COM 48192 (*) consult us. Auxiliaries and accessories: b for fixed devices: see page 22 b for fixed or drawout devices: see page 30 Switch-disconnector version: see page 32 Source changeover assembly: see page 30 BTP207E-50200-NW.fm/20
: price list NW08 to NW63 fixed circuit breakers (cont.) Circuit breaker selection (cont.) Unit price (excl.vat) in French francs Front connection E46444 3P 4P 800/1600 A Top 48128 48153 Bottom 48130 48155 2000 A Top 48124 48126 Bottom 48125 48127 2500/3200 A Top 48129 48154 Bottom 48131 48156 Front connection accessories Disconnectable front connection 3P 4P 1600 A 48421 48424 2000/3200 A 48422 48425 E46889 Rear connection Vertical connection E46445 Horizontal connection E46446 3P 4P 800/2000 A Top 48133 48158 Bottom 48138 48163 2500/3200 A Top 48134 48159 Bottom 48139 48164 4000 A Top 48135 48160 Bottom 48140 48165 4000b/5000 A Top 48136 48161 Bottom 48141 48166 6300 A Top 48137 48162 Bottom 48142 48167 3P 4P 800/2000 A Top 48143 48168 Bottom 48148 48173 2500/3200 A Top 48144 48169 Bottom 48149 48174 4000 A Top 48145 48170 Bottom 48150 48175 4000b/5000 A Top 48146 48171 Bottom 48151 48176 Rear connection accessories Interphase barriers 3P/4P (3 parts) 48599 E46428 Brackets for mounting on a backplate 2 parts 47829 E47788 BTP207E-50200-NW.fm/21
: price list NW08 to NW63 fixed circuit breakers (cont.) Indication contacts Unit price (excl.vat) in French francs ON/OFF indication contacts (OF) Block of 4 changeover contacts (6 A - 240 V) 1 block (standard) 1 additional block of 4 contacts (2 max.) 48198 E46432 "Fault trip" indication contacts (SDE) Changeover contact (5 A - 240 V) 1 (standard) 1 additional SDE (5 A - 240 V) 48200 1 additional low-level SDE 48201 E46665 Programmable contacts (*) (programmed via Micrologic control unit) 2 contacts M2C (5 A - 240 V) 47403 6 changeover contacts M6C (5 A - 240 V) 47404 (*) for Micrologic control units P and H only. E46434 M2C E46435 M6C BTP207E-50200-NW.fm/22
: price list NW08 to NW63 fixed circuit breakers (cont.) Remote operation Unit price (excl.vat) in French francs Remote ON/OFF Gear motor MCH AC 50/60 Hz 48 V 48207 100-130 V 48211 200-240 V 48212 250-277 V 48213 380-415 V 48214 440-480 V 48215 DC 24-30 V 48206 48-60 V 48207 100-130 V 48208 200-250 V 48209 Instantaneous voltage releases Closing release Opening release Standard XF MX AC 50/60 Hz 12 V DC 47349 47359 DC 24-30 V DC, 24 V AC 47350 47360 48/60 V DC, 48 V AC 47351 47361 100-130 V 47352 47362 200-250 V 47353 47363 277 V AC 47354 47364 380-480 V AC 47355 47365 Communicating XF com MX com AC 50/60 Hz 12 V DC 47310 47320 DC 24-30 V DC, 24 V AC 47311 47321 48-60 V DC, 48 V AC 47312 47322 100-130 V 47313 47323 200-250 V 47314 47324 277 V AC 47315 47325 380-480 V AC 47316 47326 "Ready to close" contact (1 max.) PF 1 changeover contact (5 A - 240 V) 47342 1 low-level changeover contact 47343 E46447 E46437 E46438 Electrical closing pushbutton BPFE 1 pushbutton 48534 E46677 Remote reset after fault trip Electrical reset Res 110-130 V AC 48202 220-240 V AC 48203 Automatic reset RAR Adaptation 47346 (*) Remote tripping Instantaneous voltage release 2 nd MX or MN AC 50/60 Hz 12 V DC 47369 DC 24-30 V DC, 24 V AC 47370 47380 48-60 V DC, 48 V AC 47371 47381 100-130 V 47372 47382 200-250 V 47373 47383 277 V AC 47374 380-480 V AC 47375 47385 E46665 E46437 MN delay unit E46694 (*) no charge. R (non-adjustable) Rr (adjustable) AC 50/60 Hz 48-60 V 33680 DC 100-130 V 33684 33681 200-250 V 33685 33682 380-480 V 33683 BTP207E-50200-NW.fm/23
: price list NW08 to NW63 drawout circuit breakers Circuit breaker selection Unit price (excl.vat) in French francs E46448 E46449 A drawout circuit breaker is described by 5 catalogue numbers corresponding to: b the basic circuit breaker b a control unit b a chassis b a top connection b a bottom connection A communication option and various auxiliaries and accessories may also be added. Basic circuit breaker + chassis y 4000 A Basic circuit breaker + chassis u 4000 A. Basic circuit breaker 3P 4P Type N1 In (A at 40 C) Icu (ka for U = 220/440 V) - Ics = 100% Icu NW08 800 42 48230 48237 NW10 1000 42 48244 48251 NW12 1250 42 48258 48265 NW16 1600 42 48272 48279 Type H1 In (A at 40 C) Icu (ka for U = 220/440 V) - Ics = 100% Icu NW08 800 65 48231 48238 NW10 1000 65 48245 48252 NW12 1250 65 48259 48266 NW16 1600 65 48273 48280 NW20 2000 65 48287 48294 NW25 2500 65 48300 48306 NW32 3200 65 48312 48317 NW40 4000 65 48322 48327 NW40b 4000 100 48336 48339 NW50 5000 100 48342 48345 NW63 6300 100 48348 48351 Type H2 In (A at 40 C) Icu (ka for U = 220/440 V) - Ics = 100% Icu NW08 800 100 48232 48239 NW10 1000 100 48246 48253 NW12 1250 100 48260 48267 NW16 1600 100 48274 48281 NW20 2000 100 48288 48295 NW25 2500 100 48301 48307 NW32 3200 100 48313 48318 NW40 4000 100 48323 48328 NW40b 4000 150 48337 48340 NW50 5000 150 48343 48346 NW63 6300 150 48349 48352 Type H3 In (A at 40 C) Icu (ka for U = 220/440 V) - Ics = 100% Icu NW20 2000 150 48289 48296 NW25 2500 150 48302 48308 NW32 3200 150 48314 48319 NW40 4000 150 48324 48329 Type L1 In (A at 40 C) Icu (ka for U = 220/440 V) - Ics = 100% Icu NW08 800 150 48233 48240 NW10 1000 150 48247 48254 NW12 1250 150 48261 48268 NW16 1600 150 48275 48282 NW20 2000 150 48290 48297 Option Neutral on the right (*) Micrologic control unit "ammeter" A 3P/4P Micrologic 2.0 A basic protection 48358 Micrologic 5.0 A selective protection 48360 Micrologic 6.0 A selective + earth-fault protection 48361 Micrologic 7.0 A selective + earth-leakage protection 48362 "power meter" P 3P/4P Micrologic 5.0 P selective protection 48363 Micrologic 6.0 P selective + earth-fault protection 48364 Micrologic 7.0 P selective + earth-leakage protection 48365 "harmonic meter" H 3P/4P Micrologic 5.0 H selective protection 48366 Micrologic 6.0 H selective + earth-fault protection 48367 Micrologic 7.0 H selective + earth-leakage protection 48368 (*) consult us. BTP207E-50200-NW.fm/24
: price list NW08 to NW63 drawout circuit breakers (cont.) Circuit breaker selection (cont.) Unit price (excl.vat) in French francs E70740 Chassis y 4000 A Auxiliaries and accessories: b for drawout devices: see page 26 b for fixed or drawout devices: see page 30 Switch-disconnector version: see page 32 Source changeover assembly: see page 30 Chassis For type N1 800/1250 A 48391 48403 1600 A 48392 48404 For type H1/H2 800/1600 A 48392 48404 2000 A 48393 48405 2500 A 48394 48406 3200 A 48395 48407 4000 A 48396 48408 4000b/6300 A 48397 48409 For type H3 2000/2500 A 48394 48406 3200 A 48395 48407 4000 A 48396 48408 For type L1 800/1600 A 48399 48411 2000 A 48400 48412 Communication option 3P Chassis + Circuit breaker Modbus COM 33852 48384 Modbus eco COM 48385 Digipact COM 33855 48388 4P Chassis front connection E46450 3P 4P 800/1600 A Top 48415 48441 Bottom 48418 48444 2000 A Top 48413 48417 Bottom 48414 48420 2500/3200 A Top 48416 48442 Bottom 48419 48445 Chassis rear connection Vertical connection E46445 Horizontal connection E46446 800/2000 A Top 48133 48158 800/1600 A type L1 Bottom 48138 48163 2500/3200 A Top 48134 48159 2000 A types H3/L1 Bottom 48139 48164 4000 A Top 48135 48160 Bottom 48140 48165 4000b/5000 A Top 48136 48161 Bottom 48141 48166 6300 A Top 48137 48162 Bottom 48142 48167 800/2000 A Top 48143 48168 800/1600 A type L1 Bottom 48148 48173 2500/3200 A Top 48144 48169 2000 A types H3/L1 Bottom 48149 48174 4000 A Top 48145 48170 Bottom 48150 48175 4000b/5000 A Top 48146 48171 Bottom 48151 48176 Rear connection accessories Interphase barriers 3P/4P (3 parts) 48600 E46428 3P 4P BTP207E-50200-NW.fm/25
: price list NW08 to NW63 drawout circuit breakers (cont.) Chassis locking and accessories Unit price (excl.vat) in French francs Chassis locking "Disconnected" position locking E46451 Door interlock (1 part) E46452 By padlocks Standard By keylocks Profalux 1 lock 48568 1 lock + 1 lock with same key profile 48569 2 locks (different key profiles) 48570 Ronis 1 lock 48572 1 lock + 1 lock with same key profile 48573 2 locks (different key profiles) 48574 Optional disconnected/test/connected position locking 33779 (*) Locking kit without locks for Profalux, Ronis 48564 Kirk 48565 Castell 48566 Right-hand side of chassis 48579 Left-hand side of chassis 48580 Racking interlock 1 part 48582 E46453 Racking interlock between crank and OFF pushbutton 1 part 48585 Automatic spring discharge before breaker removal 1 part 48554 E46688 Breaker mismatch protection Breaker mismatch protection VDC 33767 E46456 (*) no charge. BTP207E-50200-NW.fm/26
: price list NW08 to NW63 drawout circuit breakers (cont.) Chassis locking and accessories (cont.) Unit price (excl.vat) in French francs Chassis accessories Arc chute cover 3P/4P Standard E46457 Auxiliary terminal shield (CB) 800/4000 A 3P 48595 4P 48596 4000b/6300 A 3P 48597 4P 48598 E46458 Safety shutters + locking block 800/4000 A 3P 48587 4P 48589 4000b/6300 A 3P 48588 4P 48590 E46459 Shutter locking block (for remplacement) 2 parts for 800/4000 A 48591 E46460 Front face shutter position indication and locking 800/4000 A 3P/4P 48592 4000b/6300 A 3P 48593 4P 48594 E46702 BTP207E-50200-NW.fm/27
: price list NW08 to NW63 drawout circuit breakers (cont.) Indication contacts Unit price (excl.vat) in French francs ON/OFF indication contacts (OF) Block of 4 changeover contacts (6 A - 240 V) 1 block (standard) 1 additional block of 4 contacts (2 max.) 48468 E46689 Combined closed / connected contacts for use with 1 auxiliary contact 1 contact (5 A - 240 V) (8 max.) 48477 or 1 low-level contact (8 max.) 48478 E46690 "Fault trip" indication contacts (SDE) Changeover contact (5 A - 240 V) 1 (standard) 1 additional SDE (5 A - 240 V) 48475 or 1 additional low-level SDE 48476 E46691 Programmable contacts (*) (programmed via Micrologic control unit) 2 contacts M2C (5 A - 240 V) 48382 or 6 contacts M6C (5 A - 240 V) 48383 (*) for Micrologic control units P and H only. E46703 M2C E46734 M6C Carriage switches (connected / disconnected / test position) Changeover contacts (8 A - 240V) 1 connected position contact (3 max.) 33751 1 test position contact (3 max.) 33752 1 disconnected position contact (3 max.) 33753 and/or low-level changeover contacts 1 connected position contact (3 max.) 33754 1 test position contact (3 max.) 33755 1 disconnected position contact (3 max.) 33756 Actuator for additional carriage switches 48560 Auxiliary terminals for chassis alone 3 wire terminal (30 parts) 47898 6 wire terminal (10 parts) 47899 Jumpers (10 parts) 47900 E46661 BTP207E-50200-NW.fm/28
: price list NW08 to NW63 drawout circuit breakers (cont.) Remote operation Unit price (excl.vat) in French francs Remote ON/OFF Gear motor MCH AC 50/60 Hz 48 V 48522 100-130 V 48526 200-240 V 48527 250-277 V 48528 380-415 V 48529 440-480 V 48530 DC 24-30 V 48521 48-60 V 48522 100-130 V 48523 200-250 V 48524 Instantaneous voltage releases Closing release Opening release Standard XF MX AC 50/60 Hz 12 V DC 48480 48490 DC 24-30 V DC, 24 V AC 48481 48491 48-60 V DC, 48 V AC 48482 48492 100-130 V 48483 48493 200-250 V 48484 48494 277 V AC 48485 48495 380-480 V AC 48486 48496 Communicating XF com MX com AC 50/60 Hz 12 V DC 48448 48457 DC 24-30 V DC, 24 V AC 48449 48458 48-60 V DC, 48 V AC 48450 48459 100-130 V 48451 48460 200-250 V 48452 48461 277 V AC 48453 48462 380-480 V AC 48454 48463 "Ready to close" contact (1 max.) PF 1 changeover contact (5 A - 240 V) 48469 1 low-level changeover contact 48470 E46692 E46693 E46695 Electrical closing pushbutton BPFE 1 pushbutton 48534 E46677 Remote reset after fault trip Electrical reset Res 110-130 V AC 48472 220-240 V AC 48473 Automatic reset RAR Adaptation 47346 (*) E46691 Remote tripping Instantaneous voltage release E46693 MN delay unit E46694 (*) no charge. 2 nd MX or MN AC 50/60 Hz 12 V DC 48510 DC 24-30 V DC, 24 V AC 48511 48501 48-60 V DC, 48 V AC 48512 48502 100-130 V 48513 48503 200-250 V 48514 48504 277 V AC 48515 380-480 V AC 48516 48506 R (non-adjustable) Rr (adjustable) AC 50/60 Hz 48-60 V 33680 DC 100-130 V 33684 33681 200-250 V 33685 33682 380-480 V 33683 BTP207E-50200-NW.fm/29
: price list Accessories for NW08 to NW63 fixed and drawout circuit breakers Unit price (excl.vat) in French francs Circuit breaker locking Pushbutton locking device By padlocks 48536 E46666 OFF position locking E46735 By padlocks By padlocks and keylocks Profalux 1 lock 48545 1 lock + 1 lock with same key profile 48546 2 locks (different key profiles) 48547 Ronis 1 lock 48549 1 lock + 1 lock with same key profile 48550 2 locks (different key profiles) 48551 Locking kit without locks for Profalux, Ronis 48541 Kirk 48542 Castell 48543 Other circuit breaker accessories Mechanical operation counter 48539 operation counter CDM 48535 E46667 Escutcheon and accessories E46679 E46680 E46736 Fixed Drawout Escutcheon 48601 48603 Transparent cover IP 54 48604 Escutcheon blanking plate 48605 48605 Escutcheon Cover Blanking plate Mechanical interlocking for source changeover Interlocking of 2 devices using connecting rods E47762 Complete assembly with 2 adaptation fixtures + rods 2 NW fixed devices 48612 2 NW drawout devices 48612 Can be used with 1 NW fixed + 1 NW drawout. Interlocking of 2 devices using cables (*) Choose 2 adaptation fixtures (1 for each device + 1 set of cables) 1 adaptation fixture for NW fixed devices 47926 1 adaptation fixture for NW drawout devices 47926 1 set of 2 cables 33209 (*) Can be used with any combination of NT or NW, fixed or drawout devices. Interlocking of 3 devices using cables Choose 3 adaptation fixtures (1 complete set with 3 adaptation fixtures + cables 3 sources, only 1 device closed, fixed or drawout devices 48610 2 sources + 1 coupling, fixed or drawout devices 48609 2 normal + 1 replacement source, fixed or drawout devices 48608 Cable-type door interlock 1 complete assembly for NW fixed or drawout device 48614 BTP207E-50200-NW.fm/30
: price list Accessories for NW08 to NW63 fixed and drawout circuit breakers (cont.) Unit price (excl.vat) in French francs Accessories for Micrologic control units External sensors External sensor for earth-fault protection (TCE) E46671 Sensor rating 400/2000 A 34035 1000/4000 A 34036 4000/6300 A (for NW40b, NW50, NW63) 48182 Rectangular sensor for earth-leakage protection 470 mm x 160 mm 33578 E46672 Source ground return (SGR) earth fault protection External sensor (SGR) 33579 MDGF summing module 48891 E46671 Voltage measurement input (for breakers supplied via bottom terminals) Voltage measurement input Fixed 47506 Drawout 48533 E46890 Long-time rating plug (limits setting range for higher accuracy) Standard 0.4 at 1 x Ir 33542 Low-setting option 0.4 at 0.8 x Ir 33543 High-setting option 0.8 at 1 x Ir 33544 Without long-time protection off 33545 E46674 Zone Selective Interlocking option for Micrologic P and H ZSI External power supply module E47787 Battery module Test equipment Mini test kit E59921 L3 AD 220A Input 24VDC G1 Output 24VDC L4 G2 Standard 24-30 V DC 54440 48-60 V DC 54441 125 V DC 54442 110 V AC 54443 220 V AC 54444 380 V AC 54445 1 24 V battery 54446 33594 Portable test kit 33595 E59554 Special settings For circuit breaker derating Catalogue number to be added to those describing the circuit breaker Rating NW08 NW10 NW12 NW16 NW20 NW25 NW32 400 47053 47053 630 33091 33091 33091 800 33092 33092 33092 1000 33093 33093 33093 1250 33094 33094 33094 1600 33095 33095 33095 2000 33982 33982 2500 33983 Rating NW40 NW40b NW50 NW63 2000 33982 47821 2500 33983 47822 47822 3200 33984 47823 47823 47823 4000 47824 47824 5000 47825 Note: for ratings In = 100 or 250 A, please consult us. BTP207E-50200-NW.fm/31
: price list NW08 to NW63 fixed switch-disconnectors Switch-disconnector selection Unit price (excl.vat) in French francs E46681 E46682 A fixed switch-disconnector is described by 3 catalogue numbers corresponding to: b the basic switch-disconnector b a top connection b a bottom connection A communication option and various auxiliaries and accessories may also be added. Basic switch-disconnector y 4000 A Basic switch-disconnector u 4000 A. Basic switch-disconnector Type NA 3P In (A at 40 C) Icm (ka peak for U = 220/690 V) NW08 800 88 48004 48011 NW10 1000 88 48018 48025 NW12 1250 88 48032 48039 NW16 1600 88 48046 48053 Type HA 3P 4P In (A at 40 C) Icm (ka peak for U = 220/690 V) NW08 800 105 48005 48012 NW10 1000 105 48019 48026 NW12 1250 105 48033 48040 NW16 1600 105 48047 48054 NW20 2000 105 48061 48068 NW25 2500 135 48074 48080 NW32 3200 135 48085 48090 NW40 4000 135 48095 48100 NW40b 4000 187 48108 48111 NW50 5000 187 48114 48117 NW63 6300 187 48120 48123 Type HF 3P 4P In (A at 40 C) Icm (ka peak for U = 220/690 V) NW08 800 187 48006 48013 NW10 1000 187 48020 48027 NW12 1250 187 48034 48041 NW16 1600 187 48048 48055 NW20 2000 187 48062 48069 NW25 2500 187 48075 48081 NW32 3200 187 48086 48091 NW40 4000 187 48096 48101 Communication option Modbus COM 48188 Digipact COM 48192 4P Auxiliaries and accessories: b for fixed devices: see page 22 b for fixed or drawout devices: see page 30 Source changeover assembly: see page 30 BTP207E-50200-NW.fm/32
: price list NW08 to NW63 fixed switch-disconnectors (cont.) Switch-disconnector selection (cont.) Unit price (excl.vat) in French francs Front connection E46444 3P 4P 800/1600 A Top 48128 48153 Bottom 48130 48155 2000 A Top 48124 48126 Bottom 48125 48127 2500/3200 A Top 48129 48154 Bottom 48131 48156 Front connection accessories Disconnectable front connection 3P 4P 1600 A 48421 48424 2000/3200 A 48422 48425 E46889 Rear connection Vertical connection E46445 Horizontal connection E46446 3P 4P 800/2000 A Top 48133 48158 Bottom 48138 48163 2500/3200 A Top 48134 48159 Bottom 48139 48164 4000 A Top 48135 48160 Bottom 48140 48165 4000b/5000 A Top 48136 48161 Bottom 48141 48166 6300 A Top 48137 48162 Bottom 48142 48167 3P 4P 800/2000 A Top 48143 48168 Bottom 48148 48173 2500/3200 A Top 48144 48169 Bottom 48149 48174 4000 A Top 48145 48170 Bottom 48150 48175 4000b/5000 A Top 48146 48171 Bottom 48151 48176 Rear connection accessories Interphase barriers 3P/4P (3 parts) 48599 E46428 Brackets for mounting on a backplate 2 parts 47829 E47788 BTP207E-50200-NW.fm/33
: price list NW08 to NW63 drawout switch-disconnectors Switch-disconnector selection Unit price (excl.vat) in French francs E46683 E46684 A drawout switch-disconnector is described by 4 catalogue numbers corresponding to: b the basic switch-disconnector b a chassis b a top connection b a bottom connection A communication option and various auxiliaries and accessories may also be added. Basic switch-disconnector + chassis y 4000 A Basic switch-disconnector + chassis u 4000 A. Basic switch-disconnector Type NA 3P In (A at 40 C) Icm (ka peak for U = 220/690 V) NW08 800 88 48234 48241 NW10 1000 88 48248 48255 NW12 1250 88 48262 48269 NW16 1600 88 48276 48283 Type HA 3P 4P In (A at 40 C) Icm (ka peak for U = 220/690 V) NW08 800 105 48235 48242 NW10 1000 105 48249 48256 NW12 1250 105 48263 48270 NW16 1600 105 48277 48284 NW20 2000 105 48291 48298 NW25 2500 135 48304 48310 NW32 3200 135 48315 48320 NW40 4000 135 48325 48330 NW40b 4000 187 48338 48341 NW50 5000 187 48344 48347 NW63 6300 187 48350 48353 Type HF 3P 4P In (A at 40 C) Icm (ka peak for U = 220/690 V) NW08 800 187 48236 48243 NW10 1000 187 48250 48257 NW12 1250 187 48264 48271 NW16 1600 187 48278 48285 NW20 2000 187 48292 48299 NW25 2500 187 48305 48311 NW32 3200 187 48316 48321 NW40 4000 187 48326 48331 Chassis Type NA 3P 4P 800/1250 A 48391 48403 1600 A 48392 48404 Type HA/HF 3P 4P 800/1600 A 48392 48404 2000 A 48393 48405 2500 A 48394 48406 3200 A 48395 48407 4000 A 48396 48408 4000b/6300 A 48397 48409 Communication option Chassis + Switch-disconnector Modbus COM 33852 48384 Digipact COM 33855 48388 4P Auxiliaries and accessories: b for drawout devices: see page 26 b for fixed or drawout devices: see page 30 Source changeover assembly: see page 30 BTP207E-50200-NW.fm/34
: price list Unit price (excl.vat) in French francs NW08 to NW63 drawout switch-disconnectors (cont.) Switch-disconnector selection (cont.) Chassis front connection 800/1600 A Top 48415 48441 Bottom 48418 48444 2000 A Top 48413 48417 Bottom 48414 48420 2500/3200 A Top 48416 48442 Bottom 48419 48445 Chassis rear connection Vertical connection E46450 E46445 Horizontal connection E46446 3P 4P 800/2000 A Top 48133 48158 800/1600 A type L1 Bottom 48138 48163 2500/3200 A Top 48134 48159 2000 A types H3/L1 Bottom 48139 48164 4000 A Top 48135 48160 Bottom 48140 48165 4000b/5000 A Top 48136 48161 Bottom 48141 48166 6300 A Top 48137 48162 Bottom 48142 48167 3P 4P 800/2000 A Top 48143 48168 800/1600 A type L1 Bottom 48148 48173 2500/3200 A Top 48144 48169 2000 A types H3/L1 Bottom 48149 48174 4000 A Top 48145 48170 Bottom 48150 48175 4000b/5000 A Top 48146 48171 Bottom 48151 48176 Rear connection accessories Interphase barriers 3P/4P (3 parts) 48600 E46428 3P 4P BTP207E-50200-NW.fm/35
: price list Retrofit solutions Connection for fixed devices Unit price (excl.vat) in French francs To replace a M with a NW, order a retrofit device (without connections) and select a set of connectors corresponding to the replaced device. The NW is installed in exactly the same place as the old M device, without any modifications required on the switchboard. Horizontal rear connection Device to be replaced Connection to be ordered M08 to M12 Type N1/NI 3P 4P Top 3 x 48951 4 x 48951 Bottom 3 x 48964 4 x 48964 Type H1/H2/HI/HF Top 3 x 48954 4 x 48954 Bottom 3 x 48965 4 x 48965 M16 Type N1/NI/H1/H2/HI/HF Top 3 x 48954 4 x 48954 Bottom 3 x 48965 4 x 48965 M20 and M25 Type N1/NI/H1/H2/HI/HF Top 3 x 48957 4 x 48957 Bottom 3 x 48958 4 x 48958 M32 Type H1/H2/HI/HF Top 1 x 48962 1 x 48960 Bottom 1 x 48961 1 x 48960 BTP207E-50200-NW.fm/36
: price list Retrofit solutions (cont.) Connection for drawout devices Unit price (excl.vat) in French francs To replace a M with a NW, order a retrofit device (without connections) and select a set of connectors corresponding to the replaced device. The NW is installed in exactly the same place as the old M device, without any modifications required on the switchboard. Vertical rear connection Device to be replaced Connection to be ordered M08 to M12 Type N1/NI 3P 4P Top 3 x 48966 4 x 48966 Bottom 3 x 48966 4 x 48966 Type H1/H2/HI/HF Top 3 x 48969 4 x 48969 Bottom 3 x 48969 4 x 48969 M16 Type N1/NI/H1/H2/HI/HF Top 3 x 48969 4 x 48969 Bottom 3 x 48969 4 x 48969 M20 and M25 Type N1/NI/H1/H2/HI/HF Top 3 x 48970 4 x 48970 Bottom 3 x 48970 4 x 48970 M32 Type H1/H2/HI/HF Top 1 x 48974 1 x 48978 Bottom 1 x 48974 1 x 48978 Horizontal rear connection Device to be replaced Connection to be ordered M08 to M12 Type N1/NI 3P 4P Top 3 x 48951 4 x 48951 Bottom 3 x 48964 4 x 48964 Type H1/H2/HI/HF Top 3 x 48954 4 x 48954 Bottom 3 x 48965 4 x 48965 M16 Type N1/NI/H1/H2/HI/HF Top 3 x 48954 4 x 48954 Bottom 3 x 48965 4 x 48965 M20 and M25 Type N1/NI/H1/H2/HI/HF Top 3 x 48957 4 x 48957 Bottom 3 x 48958 4 x 48958 M32 neutral on left-hand side Type H1/H2/HI/HF Top 1 x 48973 1 x 48976 Bottom 1 x 48973 1 x 48977 M32 neutral on right-hand side Type H1/H2/HI/HF Top 1 x 48973 1 x 48977 Bottom 1 x 48973 1 x 48976 BTP207E-50200-NW.fm/37
: price list Communication bus accessories and Display Modules Unit price (excl.vat) in French francs Display modules DMB300 Monochrome display module Max. 4 breakers 50894 4900 E67954 DMC300 Color display module Max. 16 breakers 50895 13388 E67955 Spare parts DMC300PCM: DMC300 memory card 50959 1715 RS485 Modbus pre-wired system RS485 Modbus junction block CJB306: 6 SubD 9 pins connectors junction block 50963 502 E67958 RS485 Modbus connector CSD309: 9 pins SubD with screw terminals 50964 220 E67959 RS485 Modbus cables CDM303: display module pre-wired cable, 3 m length 50960 268 E67960 CCP303: or Compact pre-wired cable (4 RS485 wires + 2 power wires) 3 m length 50961 192 E79015 CCR301: RS485 roll cable (2 RS485 wires + 2 power wires) 60 m length 50965 2129 E67961 Digipact Bus pre-wired system Data concentrator DC150 Auxiliary supply voltage 110-240 V AC, 50/60 Hz and 115-125 V DC 50823 6737 E79014 Junction block Junction block for internal Bus 50778 411 E67956 Cables E67957 Cable for internal bus 20-meter roll (0.75 mm 2 ) 50779 385 100-meter roll (0.75 mm 2 ) 50780 1883 Converter RS485/RS232 (ACE909) 12 V DC power supply included 50786 8194 RS485/RS232 TSX SCA72 (1) RS485/Ethernet 174 CEV 300-10 (1) RS485/Ethernet (SMS compatible) 3050 EGW2 (2) (1) see catalogue Telemecanique. (2) see catalogue Square D. BTP207E-50200-NW.fm/38
: price list Order form NT and NW Unit price (excl.vat) in French francs To indicate your choices, check the applicable square boxes and enter the appropriate information in the rectangles Basic device Quantity type NT, NW Frame size 06 to 63 Sensor rating A Circuit breaker N1, H1, H2, H3, L1 Switch-disconnector NA, HA, HF Number of poles 3 or 4 Option : Neutral on right side Type of device Fixed Drawout with chassis Chassis alone Drawout without chassis Micrologic control unit A - ammeter 2.0 A 5.0 A 6.0 A 7.0 A P - power meter 5.0 P 6.0 P 7.0 P H - harmonic meter 5.0 H 6.0 H 7.0 H TCE - external sensor (CT) for neutral + earth-fault protection TCE - external sensor (CT) for double neutral protection (Micrologic P and H with 3-poles) TCW - external sensor for SGR protection Rectangular sensor for earth-leakage protection 280 x 115 470 x 160 LT - long-time rating plug (standard setting 0.4 to 1 x Ir) Low setting option 0.4 to 0.8 Ir High setting option 0.8 to 1 Ir LT OFF option PTE - external voltage measurement input AD - external power-supply module BAT - battery module Communication COM Eco COM Connection Digipact Modbus Modbus Horizontal Top Bottom Vertical Top Bottom Front Top Bottom Bare-cable connectors NT-FC fixed 4 x 240 mm 2 + connector shield Vertical-connection adapters NT-FC, fixed, draw. Cable-lug adapters NT-FC, fixed, draw. Interphase barriers NT, NW-fixed, draw. Spreaders NT-fixed, drawout Disconnectable front-connection NW-fixed adapter VO - safety shutters on chassis NT, NW VIVC - shutter position indication NW and locking Key for Micrologic control units: 2.0 : basic protection (long-time + inst.) 5.0 : selective protection (long-time + short-time + inst.) 6.0 : selective + earth-fault protection (long-time + short-time + inst. + earth-fault) 7.0 : selective + earth-leakage protection (long-time + short-time + inst. + earth-leakage) Locking VBP - ON/OFF pushbutton locking OFF position locking VCPO - by padlocks VSPO - by keylocks Locking kit Profalux Ronis without keylocks 1 lock 1 lock + 1 lock with same key profile 2 locks (different key profiles) for NW VSPD - chassis locking in ''disconnected'' position VPEC - door interlock Locking kit Profalux Ronis without keylocks 1 lock 1 lock + 1 lock with same key profile 2 locks (different key profiles) Optional connected - disconnected - test position locking Latch on right-hand side of chassis Latch on left-hand side of chassis VPOC - racking interlock IPA - cable-type door interlock IBPO - racking interlock between crank and OFF pushbutton for NW DAE - automatic spring discharge before breaker removal for NW VDC - mismatch protection Indication contacts OF - ON/OFF indication contacts Standard 4 OF 6 A - 240 V AC (10 A - 240 V AC and low-level for NW) Alternate 1 OF low-level for NT Max. 4 qty (replaces a standard contact) Additional 1 block of 4 OF for NW Max. 2 qty EF - combined ''connected/closed'' contacts 1 EF 5 A - 240 V AC for NW Max. 8 qty 1 EF low-level for NW Max. 8 qty SDE - ''fault-trip'' indication contacts Standard 1 SDE 5 A - 240 V AC Additional 1 SDE 5 A - 240 V AC 1 SDE low-level Programmable contacts 2 M2C contacts 6 M6C contacts Carriage switches low-level 6 A - 240 V AC CE - ''connected'' position Maxi. 3 for NT and NW qty CD - ''disconnected'' position Maxi. 2 for NT and 3 for NW qty CT - ''test'' position Maxi. 1 for NT and 3 for NW qty AC - actuator for additional carriage switches qty Remote operation Remote ON/OFF MCH - gear motor V XF - closing voltage release V MX - opening voltage release V PF - ''ready to close'' contact low-level 6 A - 240 V AC BPFE - electrical closing pushbutton Res - electrical reset option RAR - automatic reset option Remote tripping MN - undervoltage release V R - delay unit (non-adjustable) Rr - adjustable delay unit 2 nd MX - shunt release V Accessories CDM - mechanical operation counter CB - auxiliary terminal shield for chassis CDP - escutcheon CP - transparent cover OP - blanking plate Brackets for mounting on backplates BTP207E-50200-NW.fm/39