30 minutes to perform a retrofit of your Masterpact M

Size: px
Start display at page:

Download "30 minutes to perform a retrofit of your Masterpact M"

Transcription

1 30 minutes to perform a retrofit of your Masterpact M "Plug and Play" retrofit solution 2009 Fast and easy implementation Continuity of service guaranteed Certified "Plug and Play" solution

2 "Plug and Play" retrofit solution This solution enales retrofitting of Masterpact M devices with considerale reduction of on-site intervention time. The existing Masterpact M chassis is retained. Busar and cale connections are not distured, only the circuit concerned needs to e isolated (for as little as 30 minutes*). The original Masterpact M chassis is kept (no intervention on the switchoard structure) Masterpact NW adapted for the "Plug and Play" solution Masterpact M : Standard offer Circuit reaker Consult us for all devices not included in the standard offer. Switch-disconnector Original device N1 H1 H2 NI HI HF M08 3P/4P M10 3P/4P M12 3P/4P M16 3P/4P M20 3P/4P M25 3P/4P M32 3P/4P The STR control units (except for communication units) are replaced y the corresponding Micrologic control units according to the specifi cation of the existing STR.

3 Fast and simple implementation which keeps the original chassis 30 minutes* and 2 easy operations * Typical time for simple installations. The factory-modified and adapted "Plug and Play" Masterpact NW is designed for installation in the original Masterpact M chassis. On-site implementation is very simple: Replacement of original racks Wire guide support replacement Two new racks are installed in place of the original racks in the Masterpact M chassis. All Masterpact NW functions are pre-wired; our technician has only to connect the functions required according to the accessories fitted. Chassis spare parts replacement warranty With the "Plug and Play" retrofit solution we guarantee the availaility of spare parts for the Masterpact M chassis (plug-in clamps, shutter, wire guide support spring, auxiliary contacts). High performance of the Masterpact NW The monitoring and diagnostic functions (Micrologic control unit) of the Masterpact NW circuit reaker enales you to optimise the maintenance of your equipment. The electrical performance characteristics of the Masterpact NW offer equal or greater performance than Masterpact M (selectivity remains unchanged) in the event of a network fault. Mismatch Protection The mismatch protection ensures that a circuit reaker is installed only in a cradle with compatile characteristics. The kit can e ordered separately. Mechanical interlock using connecting rods for 2 or 3 uncked Mechanical interlock Mechanical interlock of two or three uncked devices using connecting rods and 2 devices installed side y side using cales are availale with the Plug&Play. The kit has to e ordered with the device. Mechanical interlock using cale for 2 devices installed side y side.

4 "Plug and Play" retrofit solution The retrofit solutions use a factory modified and adapted Masterpact NW which is installed in Masterpact M s original chassis. Merchant Marine "The Plug&Play is compliant with Merchant Marine standards. The reaking capacity test and the steady-state sinusoidal viration tests in accordance with IACS rules and standard IEC have een successfully performed on a circuit reaker NW32H1 3 poles draw out version mounted in a chassis of Masterpact M32. The technical documents that show the results of the tests are availale." The "Plug and Play" retrofit solutions keeps all Masterpact NW circuit reaker All specific parts are certified in compliance with the following standards: _ IEC _ IEC Conform to marine standards. More environmentally Masterpact NW units use non-polluting and recyclale materials, and are manufactured in ISO certified The environmental impact is minimised through eco-design. Schneider Electric France Projects and Engineering Center Grenole Cedex 9 Tel.:+33 (0) As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this pulication. This document has een printed on ecological paper. Design: Schneider Electric Photos: Schneider Electric Printed: Schneider Electric - All rights reserved SERED109001EN

5 Plug&Play Material List Plug&Play Description «Plug and Play» solution for Masterpact M 3phases The circuit reaker is equiped with specific power connections A special lael to identify the retrofit circuit reaker. Special racks for Masterpact NW The housing is modified and adapted to e compatile with the Masterpact M chassis Reference List Existing Circuit Breaker Plug&Play Solution Reference M08H1 3P STR28D P&P M08H1 3P y NW08H1 3P 5.0A M10H1 3P STR28D P&P M10H1 3P y NW10H1 3P 5.0A M12H1 3P STR28D P&P M12H1 3P y NW12H1 3P 5.0A M16H1 3P STR28D P&P M16H1 3P y NW16H1 3P 5.0A M20H1 3P STR28D P&P M20H1 3P y NW20H1 3P 5.0A M25H1 3P STR28D P&P M25H1 3P y NW25H1 3P 5.0A M32H1 3P STR28D P&P M32H1 3P y NW32H1 3P 5.0A 93701

6 Functions and characteristics Circuit reakers and switch-disconnectors NW08 to NW63 PB104423A35 Common characteristics Numer of poles 3/4 Rated insulation voltage (V) Ui 1000/1250 Impulse withstand voltage (kv) Uimp 12 Rated operational voltage (V AC 50/60 Hz) Ue 690/1150 Suitaility for isolation IEC Degree of pollution IEC (1000 V) / 3 (1250 V) Basic circuit-reaker Circuit-reaker as per IEC Rated current (A) at 40 C / 50 C (1) Rating of 4th pole (A) Sensor ratings (A) PB104433A65 (1) 50 C: rear vertical connected. Refer to temperature derating tales for other connection types. (2) See the current-limiting curves in the additional characteristics section. (3) Equipped with a trip unit with a making current of 90 ka peak. (4) External protection must comply with permissile thermal constraints of the circuit reaker (please consult us). No fault-trip indication y the SDE or the reset utton. (5) Availale for 480 V NEMA. (6) Suitale for motor control (direct-on-line starting). A-8 Type of circuit reaker Ultimate reaking capacity (ka rms) V AC 50/60 Hz Rated service reaking capacity (ka rms) Ics % Icu Utilisation category Rated short-time withstand current (ka rms) V AC 50/60 Hz Icw 1 s 3 s Integrated instantaneous protection (ka peak ±10 %) Rated making capacity (ka peak) V AC 50/60 Hz Break time (ms) etween tripping order and arc extinction Closing time (ms) Circuit-reaker as per NEMA AB1 Breaking capacity (ka) V AC 50/60 Hz Icu Icm 220/415/440 V 525 V 690 V 1150 V 220/415/440 V 525 V 690 V 1150 V 240/480 V 600 V Unprotected circuit-reaker Tripping y shunt trip as per IEC Type of circuit reaker Ultimate reaking capacity (ka rms) V AC 50/60 Hz Icu V Rated service reaking capacity (ka rms) Ics % Icu Rated short-time withstand current (ka rms) Icw 1 s 3 s Overload and short-circuit protection External protection relay: short-circuit protection, maximum delay: 350 ms (4) Rated making capacity (ka peak) V AC 50/60 Hz Icm V Switch-disconnector as per IEC and Annex A Type of switch-disconnector Rated making capacity (ka peak) AC23A/AC3 category V AC 50/60 Hz Rated short-time withstand current (ka rms) AC23A/AC3 category V AC 50/60 Hz Icm Icw V 1150 V 1 s 3 s Earthing switch Latching capacity (ka peak) 135 Rating short time withstand (ka rms) Icw 1 s 60 Hz 3 s 50 Hz Mechanical and electrical duraility as per IEC /3 at In/Ie Service life Mechanical with maintenance C/O cycles x 1000 without maintenance Type of circuit reaker Rated current In (A) C/O cycles x 1000 Electrical without maintenance 440 V (5) IEC V 1150 V Type of circuit reaker or switch-disconnector Rated operational current Ie (A) AC23A C/O cycles x 1000 Electrical without maintenance 440 V (5) IEC V Type of circuit reaker or switch-disconnector Rated operational current Ie (A) AC3 (6) Motor power 380/415 V (kw) 440 V (5) (kw) 690 V (kw) C/O cycles x 1000 Electrical without maintenance 440/690 V (5) IEC Annex M/IEC

7 Sensor selection Sensor rating (A) 250 (1) Ir threshold setting(a) to 250 to 400 to 630 to 800 to 1000 to 1250 to 1600 to 2000 to 2500 to 3200 to 4000 to 5000 to 6300 (1) For circuit-reaker NW02, please consult us. NW08 NW10 NW12 NW16 NW20 NW25 NW32 NW40 NW40 NW50 NW to to to to to to to to to to to 6300 N1 H1 H2 L1 (2) H10 H1 H2 H3 L1 (2) H10 H1 H2 H3 H10 H1 H % 100 % 100 % 100 % B B B B < 70 < 70 < 70 < HA HF (3) HA HF (3) HA HF (3) HA % 100 % 100 % 100 % NW08/NW10/NW12 NW16 NW20 NW25/NW32/NW40 NW40/NW50/NW63 NA HA HF HA10 HA HF HA10 HA HF HA10 HA HF HA10 HA N1/H1/H2 L1 H10 H1/H2 H3 L1 H10 H1/H2 H3 H10 H1 H2 800/1000/1250/ /3200/ /5000/ H1/H2/HA/HF H1/H2/H3/HA/HF H1/H2/H3/HA/HF H1/H2/HA 800/1000/1250/ /3200/ /5000/ H1/H2/HA/HF H1/H2/H3/HA/HF to to to to to to to to to to 1300 y to to to to A-9

8 Functions and characteristics Micrologic control units Overview of functions All Masterpact circuit reakers are equipped with a Micrologic control unit that can e changed on site. Control units are designed to protect Power circuits and loads. Alarms may e programmed for remote indications. Measurements of current, voltage, frequency, power and power quality optimise continuity of service and energy management. Dependaility Integration of protection functions in an ASIC electronic component used in all Micrologic control units guarantees a high degree of reliaility and immunity to conducted or radiated disturances. On Micrologic A, P and H control units, advanced functions are managed y an independent microprocessor. Accessories Certain functions require the addition of Micrologic control unit accessories, descried on page A-20. The rules governing the various possile cominations can e found in the documentation accessile via the Products and services menu of the we site. Micrologic name codes 2.0 A X Y Z X: type of protection 2 for asic protection 5 for selective protection 6 for selective + earth-fault protection 7 for selective + earth-leakage protection. Y: control-unit generation Identification of the control-unit generation. 0 signifies the first generation. Z: type of measurement A for ammeter P for power meter H for harmonic meter. DB DB Current protection Micrologic 2: asic protection Micrologic 5: asic protection Protection: long time + instantaneous Protection: long time + short time + instantaneous PB DB Micrologic 6: selective + earth-fault protection DB Protection: long time + short time + instantaneous + earth fault Micrologic 7: selective + earth-leakage protection DB DB Protection: long time + short time + instantaneous + earth leakage up to 3200A A-10

9 Measurements and programmale protection A: ammeter I 1, I 2, I 3, I N, I earth-fault, I earth-leakage and maximeter for these measurements fault indications settings in amperes and in seconds. P: A + power meter + programmale protection measurements of V, A, W, VAR, VA, Wh, VARh, VAh, Hz, V peak, A peak, power factor and maximeters and minimeters IDMTL long-time protection, minimum and maximum voltage and frequency, voltage and current imalance, phase sequence, reverse power load shedding and reconnection depending on power or current measurements of interrupted currents, differentiated fault indications, maintenance indications, event histories and time-stamping, etc. H: P + harmonics power quality: fundamentals, distortion, amplitude and phase of harmonics up to the 31st order waveform capture after fault, alarm or on request enhanced alarm programming: thresholds and actions. 2.0 A DB A DB P DB H DB A DB P DB H DB A DB P DB H DB A-11

10 Functions and characteristics Micrologic control units Micrologic A ammeter E46028 Micrologic A control units protect power circuits. They also offer measurements, display, communication and current maximeters. Version 6 provides earth-fault protection, version 7 provides earth-leakage protection. 1 long-time threshold and tripping delay 2 overload alarm (LED) at 1,125 Ir 3 short-time pick-up and tripping delay 4 instantaneous pick-up 5 earth-leakage or earth-fault pick-up and tripping delay 6 earth-leakage or earth-fault test utton 7 long-time rating plug screw 8 test connector 9 lamp test, reset and attery test 10 indication of tripping cause 11 digital display 12 three-phase argraph and ammeter 13 navigation uttons "Ammeter" measurements Micrologic A control units measure the true (rms) value of currents. They provide continuous current measurements from 0.2 to 20 In and are accurate to within 1.5 % (including the sensors). A digital LCD screen continuously displays the most heavily loaded phase (Imax) or displays the I1, I2, I3, IN, Ig,I n, stored-current (maximeter) and setting values y successively pressing the navigation utton. The optional external power supply makes it possile to display currents < 20 % In. Below 0.05 In, measurements are not significant. Between 0.05 and 0.2 In, accuracy is to within 0.5 % In % of the reading. Communication option In conjunction with the COM communication option, the control unit transmits the following: settings all ammeter measurements tripping causes maximeter readings. Protection Protection thresholds and delays are set using the adjustment dials. Overload protection True rms long-time protection. Thermal memory: thermal image efore and after tripping. Setting accuracy may e enhanced y limiting the setting range using a different long-time rating plug. Overload protection can e cancelled using a specific LT rating plug "Off". Short-circuit protection Short-time (rms) and instantaneous protection. Selection of I 2 t type (ON or OFF) for short-time delay. Earth-fault protection Residual or source ground return earth fault protection. Selection of I 2 t type (ON or OFF) for delay. Residual earth-leakage protection (Vigi). Operation without an external power supply. q Protected against nuisance tripping. k DC-component withstand class A up to 10 A. Neutral protection On three-pole circuit reakers, neutral protection is not possile. On four-pole circuit reakers, neutral protection may e set using a three-position switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral protection at Ir (4P 4d). Zone selective interlocking (ZSI) A ZSI terminal lock may e used to interconnect a numer of control units to provide total discrimination for short-time and earth-fault protection, without a delay efore tripping. Overload alarm A yellow alarm LED goes on when the current exceeds the long-time trip threshold. Fault indications LEDs indicate the type of fault: overload (long-time protection Ir) short-circuit (short-time Isd or instantaneous li protection) earth fault or earth leakage (Ig or I n) internal fault (Ap). Battery power The fault indication LEDs remain on until the test/reset utton is pressed. Under normal operating conditions, the attery supplying the LEDs has a service life of approximately 10 years. Test A mini test kit or a portale test kit may e connected to the test connector on the front to check circuit-reaker operation. For Micrologic 6.0 A and 7.0 A control units, the operation of earth-fault or earth-leakage protection can e checked y pressing the test utton located aove the test connector. Note: Micrologic A control units come with a transparent leadseal cover as standard. A-12

11 Protection Micrologic 2.0 A Long time Current setting (A) Tripping etween 1.05 and 1.20 x Ir Other ranges or disale y changing long-time rating plug Time setting tr (s) Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir Accuracy: 0 to -20 % 6 x Ir 0.7 (1) Accuracy: 0 to -20 % 7.2 x Ir 0.7 (2) Thermal memory 20 minutes efore and after tripping (1) 0 to -40 % - (2) 0 to -60 % Instantaneous Pick-up (A) Isd = Ir x Accuracy: ±10 % Time delay Max resettale time: 20 ms Max reak time: 80 ms DB Ammeter Micrologic 2.0 A Continuous current measurements Display from 20 to 200 % of In I1 I2 I3 IN Accuracy: 1.5 % (including sensors) No auxiliary source (where I > 20 % In) Maximeters I1 max I2 max I3 max IN max Protection Micrologic 5.0 / 6.0 / 7.0 A Long time Micrologic 5.0 / 6.0 / 7.0 A Current setting (A) Ir = In x Tripping etween 1.05 and 1.20 x Ir Other ranges or disale y changing long-time rating plug Time setting tr (s) Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir Accuracy: 0 to -20 % 6 x Ir 0.7 (1) Accuracy: 0 to -20 % 7.2 x Ir 0.7 (2) Thermal memory 20 minutes efore and after tripping (1) 0 to -40 % - (2) 0 to -60 % Short time Pick-up (A) Isd = Ir x Accuracy: ±10 % Time setting tsd (s) Settings I 2 t Off I 2 t On Time delay (ms) at 10 x Ir tsd (max resettale time) (I 2 t Off or I 2 t On) tsd (max reak time) Instantaneous Pick-up (A) Ii = In x off Accuracy: ±10 % Time delay Max resettale time: 20 ms Max reak time: 50 ms Earth fault Micrologic 6.0 A Pick-up (A) Ig = In x A B C D E F G H J Accuracy: ±10 % In y 400 A A < In < 1250 A In u 1250 A Time setting tg (s) Settings I 2 t Off I 2 t On Time delay (ms) tg (max resettale time) at In or 1200 A (I 2 t Off or I 2 t On) tg (max reak time) Residual earth leakage (Vigi) Micrologic 7.0 A Sensitivity (A) IDn Accuracy: 0 to -20 % Time delay Dt (ms) Settings Dt (max resettale time) Dt (max reak time) DB DB DB Ammeter Micrologic 5.0 / 6.0 / 7.0 A Continuous current measurements Display from 20 to 200 % of In I1 I2 I3 IN Ig IDn Accuracy: 1.5 % (including sensors) No auxiliary source (where I > 20 % In) Maximeters I1 max I2 max I3 max IN max Ig max IDn max Note: All current-ased protection functions require no auxiliary source. The test / reset utton resets maximeters, clears the tripping indication and tests the attery. A-13

12 Locking On the device DB Reset utton for mechanical trip indication. OFF pushutton. OFF position lock. Electrical closing pushutton. ON pushutton. Springs charged indication. Pushutton locking. Contact position indication. Operation counter. PB PB PB Access to pushuttons protected y transparent cover. Pushutton locking using a padlock. OFF position locking using a padlock. Pushutton locking VBP The transparent cover locks access to the pushuttons used to open and close the device. It is possile to independently lock the opening utton and the closing utton. The locking device is often comined with a remote operating mechanism. The pushuttons may e locked using either: three padlocks (not supplied) lead seal two screws. Device locking in the OFF position VCPO y padlocks, VSPO y keylocks The circuit reaker is locked in the OFF position y physically maintaining the opening pushutton pressed down: using padlocks (one to three padlocks, not supplied) using keylocks (one or two different keylocks, supplied). Keys may e removed only when locking is effective (Profalux or Ronis type locks). The keylocks are availale in any of the following configurations: one keylock one keylock mounted on the device + one identical keylock supplied separately for interlocking with another device two different key locks for doule locking. Profalux and Ronis keylocks are compatile with each other. A locking kit (without locks) is availale for installation of one or two keylocks (Ronis, Profalux, Kirk or Castell). Accessory-compatiility For Masterpact NT: 3 padlocks or 1 keylock For Masterpact NW: 3 padlocks and/or 2 keylocks Cale-type door interlock IPA This option prevents door opening when the circuit reaker is closed and prevents circuit reaker closing when the door is open. For this, a special plate associated with a lock and a cale is mounted on the right side of the circuit reaker. With this interlock installed, the source changeover function cannot e implemented. PB104365A40 OFF position locking using a keylock. A-35

13 Functions and characteristics Locking On the chassis DB Mismatch protection. Door interlock. Racking interlock. Keylock locking. Padlock locking. Position indicator. Chassis front plate (accessile with cuicle door closed). Racking-handle entry. Reset utton Racking-handle storage. PB104366A32 PB104352A32 PB A32 PB R_SE Disconnected position locking y padlocks. Door interlock. Racking interlock. Mismatch protection. PB104367A34 Disconnected position locking y keylocks. Disconnected position locking y padlocks (standard) or keylocks (VSPD option) Mounted on the chassis and accessile with the door closed, these devices lock the circuit reaker in the disconnected position in two manners: using padlocks (standard), up to three padlocks (not supplied) using keylocks (optional), one or two different keylocks are availale. Profalux and Ronis keylocks are availale in different options: one keylock two different keylocks for doule locking one (or two) keylocks mounted on the device + one (or two) identical keylocks supplied separately for interlocking with another device. A locking kit (without locks) is availale for installation of one or two keylocks (Ronis, Profalux, Kirk or Castell). Connected, disconnected and test position locking The connected, disconnected and test positions are shown y an indicator andc are mechanically indexed. The exact position is otained when the racking handle locks. A release utton is used to free it. As standard, the circuit reaker can e locked only in "disconnected position". On request, the locking system may e modified to lock the circuit reaker in any of the three positions: "connected", "disconnected" or "test". Door interlock catch VPEC Mounted on the right or left-hand side of the chassis, this device inhiits opening of the cuicle door when the circuit reaker is in connected or test position. It the reaker is put in the connected position with the door open, the door may e closed without having to disconnect the circuit reaker. Racking interlock VPOC This device prevents insertion of the racking handle when the cuicle door is open. Cale-type door interlock IPA This option is identical for fixed and drawout versions. Racking interlock etween crank and OFF pushutton IBPO (for NW only) This option makes it necessary to press the OFF pushutton in order to insert the racking handle and holds the device open until the handle is removed. Automatic spring discharge efore reaker removal DAE (for NW only) This option discharges the springs efore the reaker is removed from the chassis. Mismatch protection VDC Mismatch protection ensures that a circuit reaker is installed only in a chassis with compatile characteristics. It is made up of two parts (one on the chassis and one on the circuit reaker) offering twenty different cominations that the user may select. A-36

14 Indication contacts PB PB Indication contacts are availale: in the standard version for relay applications in a low-level version for control of PLCs and electronic circuits. M2C and M6C contacts may e programmed via the Micrologic P and H control units. ON/OFF indication contacts (OF) (microswitch type). Additional fault-trip indication contacts (SDE). PB ON/OFF indication contacts (OF) (rotary type). ON/OFF indication contacts OF Two types of contacts indicate the ON or OFF position of the circuit reaker: microswitch type changeover contacts for Masterpact NT rotary type changeover contacts directly driven y the mechanism for Masterpact NW. These contacts trip when the minimum isolation distance etween the main circuit-reaker contacts is reached. OF NT NW Supplied as standard 4 4 Maximum numer 4 12 Breaking capacity (A) Standard Minimum load: 100 ma/24 V p.f.: 0.3 V AC 240/ /6 (1) AC12/DC /6 (1) V DC 24/ /6 (1) /6 (1) Low-level Minimum load: 2 ma/15 V V AC 24/ V DC 24/48 5/ (1) Standard contacts: 10 A; optional contacts: 6 A. Fault-trip indication contacts SDE Circuit-reaker tripping due to a fault is signalled y: a red mechanical fault indicator (reset) one changeover contact SDE. Following tripping, the mechanical indicator must e reset efore the circuit reaker may e closed. One SDE is supplied as standard. An optimal SDE may e added. This latter is incompatile with the electrical reset after fault-trip option (RES). SDE NT/NW Supplied as standard 1 Maximum numer 2 Breaking capacity (A) Standard Minimum load: 100 ma/24 V p.f.: 0.3 V AC 240/380 5 AC12/DC V DC 24/ Low-level Minimum load: 2 ma/15 V V AC 24/ V DC 24/ PB Comined contacts. Comined connected/closed contacts EF The contact comines the device connected and the device closed information to produce the circuit closed information. Supplied as an option for Masterpact NW, it is mounted in place of the connector of an additional OF contact. EF NW Maximum numer 8 Breaking capacity (A) Standard Minimum load: 100 ma/24 V p.f.: 0.3 V AC 240/380 6 AC12/DC V DC 24/ Low-level Minimum load: 2 ma/15 V V AC 24/ V DC 24/ A-37

15 Functions and characteristics Indication contacts PB PB PB CE, CD and CT connected/disconnected/test position carriage switches. M2C programmale contacts: circuit-reaker internal relay with two contacts. Connected, disconnected and test position carriage switches Three series of optional auxiliary contacts are availale for the chassis: changeover contacts to indicate the connected position CE changeover contacts to indicate the disconnected position CD. This position is indicated when the required clearance for isolation of the power and auxiliary circuits is reached changeover contacts to indicate the test position CT. In this position, the power circuits are disconnected and the auxiliary circuits are connected. Additional actuators A set of additional actuators may e installed on the chassis to change the functions of the carriage switches. NT NW Contacts CE/CD/CT CE/CD/CT Maximum numer Standard with additional actuators Breaking capacity (A) Standard Minimum load: 100 ma/24 V p.f.: 0.3 V AC AC12/DC V DC 24/ Low-level Minimum load: 2 ma/15 V V AC 24/ V DC 24/ M6C programmale contacts: circuit-reaker external relay with six independent changeover contacts controlled from the circuit reaker via a three-wire connection. (maximum length is 10 meters). M2C / M6C programmale contacts These contacts, used with the Micrologic P and H control units, may e programmed via the control unit keypad or via a supervisory station with the COM communication option. They require an external power supply module. They indicate: the type of fault instantaneous or delayed threshold overruns. They may e programmed: with instantaneous return to the initial state without return to the initial state with return to the initial state following a delay. Characteristics Minimum load Breaking capacity (A) p.f.: 0.7 M2C/M6C 100 ma/24 V V AC V DC DB M2C: 24 V DC power supplied y control unit (consumption 100 ma). DB M6C: external 24 V DC power supply required (consumption 100 ma). A-38

16 Remote operation Remote ON / OFF PB104349A68 Two solutions are availale for remote operation of Masterpact devices: a point-to-point solution a us solution with the COM communication option. The remote ON / OFF function is used to remotely open and close the circuit reaker. It is made up of: an electric motor MCH equipped with a springs charged limit switch contact CH two voltage releases: v a closing release XF v an opening release MX. Optionally, other functions may e added: a ready to close contact PF an electrical closing pushutton BPFE remote RES following a fault. A remote-operation function is generally comined with: device ON / OFF indication OF fault-trip indication SDE. Wiring diagram of a point-to-point remote ON / OFF function DB Note: an opening order always takes priority over a closing order. If opening and closing orders occur simultaneously, the mechanism discharges without any movement of the main contacts. The circuit reaker remains in the open position (OFF). In the event of maintained opening and closing orders, the standard mechanism provides an anti-pumping function y locking the main contacts in open position. Anti-pumping function. After fault tripping or intentional opening using the manual or electrical controls, the closing order must first e discontinued, then reactivated to close the circuit reaker. When the automatic reset after fault trip (RAR) option is installed, to avoid pumping following a fault trip, the automatic control system must take into account the information supplied y the circuit reaker efore issuing a new closing order or locking the circuit reaker in the open position (information on the type of fault, e.g. overload, short-time fault, earth fault, earth leakage, short-circuit, etc.). DB Wiring diagram of a us-type remote ON / OFF function Note: MX communicating releases are of the impulse type only and cannot e used to lock a circuit reaker in OFF position. For locking in OFF position, use the remote tripping function (2nd MX or MN). When MX or XF communicating releases are used, the third wire (C3, A3) must e connected even if the communication module is not installed. When the control voltage (C3-C1 or A3-A1) is applied to the MX or XF releases, it is necessary to wait 1.5 seconds efore issuing an order. Consequently, it is advised to use standard MX or XF releases for applications such as source-changeover systems. A-39

17 Functions and characteristics Remote operation Remote ON / OFF PB PB Electric motor MCH The electric motor automatically charges and recharges the spring mechanism when the circuit reaker is closed. Instantaneous reclosing of the reaker is thus possile following opening. The spring-mechanism charging handle is used only as a ackup if auxiliary power is asent. The electric motor MCH is equipped as standard with a limit switch contact CH that signals the charged position of the mechanism (springs charged). Characteristics Power supply V AC 50/60 Hz 48/60-100/ / / / V DC 24/30-48/60-100/ /250 Operating threshold 0.85 to 1.1 Un Consumption (VA or W) 180 Motor overcurrent 2 to 3 In for 0.1 s Charging time maximum 3 s for Masterpact NT maximum 4 s for Masterpact NW Operating frequency maximum 3 cycles per minute CH contact 10 A at 240 V DB PB PB Electric motor MCH for Masterpact NT. XF and MX voltage releases. Ready to close contacts PF. A-40 Electric motor MCH for Masterpact NW. Voltage releases XF and MX Their supply can e maintained or automatically disconnected. Closing release XF The XF release remotely closes the circuit reaker if the spring mechanism is charged. Opening release MX The MX release instantaneously opens the circuit reaker when energised. It locks the circuit reaker in OFF position if the order is maintained (except for MX communicating releases). Note: whether the operating order is maintened or automatically disconnected (pulse-type), XF or MX communicating releases ( us solution with COM communication option) always have an impulse-type action (see diagram). Characteristics XF MX Power supply V AC 50/60 Hz / / /480 V DC 12-24/30-48/60-100/ /250 Operating threshold 0.85 to 1.1 Un 0.7 to 1.1 Un Consumption (VA or W) Hold: 4.5 Pick-up: 200 (200 ms) Circuit-reaker response time at Un 55 ms ±10 (Masterpact NT) 50 ms ±10 70 ms ±10 (NW y 4000 A) 80 ms ±10 (NW > 4000 A) Hold: 4.5 Pick-up: 200 (200 ms) Ready to close contact PF The ready to close position of the circuit reaker is indicated y a mechanical indicator and a PF changeover contact. This signal indicates that all the following are valid: v v v v v v the circuit reaker is in the OFF position the spring mechanism is charged a maintained opening order is not present: MX energised fault trip remote tripping second MX or MN device not completely racked in device locked in OFF position device interlocked with a second device. Characteristics NT/NW Maximum numer 1 Breaking capacity (A) Standard Minimum load: 100 ma/24 V p.f.: 0.3 V AC 240/380 5 AC12/DC V DC 24/ Low-level Minimum load: 2 ma/15 V V AC 24/ V DC 24/

18 PB w DB Electrical closing pushutton BPFE Located on the front panel, this pushutton carries out electrical closing of the circuit reaker. It is generally associated with the transparent cover that protects access to the closing pushutton. Electrical closing via the BPFE pushutton takes into account all the safety functions that are part of the control/monitoring system of the installation. The BPFE connects to the closing release (XF com) in place of the COM module. The COM module is incompatile with this option. Different types of voltage exist and the XF electromagnet is compulsary if the BPFE option is selected. Electrical closing pushutton BPFE. Remote reset after fault trip Electrical reset after fault trip RES Following tripping, this function resets the fault trip indication contacts SDE and the mechanical indicator and enales circuit reaker closing. Power supply: 0 / 130 V AC and 200 / 240 V AC. The use of XF closing release is compulsory with this option. DB Automatic reset after fault trip RAR Following tripping, a reset of the mechanical indicator (reset utton) is no longer required to enale circuit-reaker closing. The mechanical (reset utton) and electrical SDE indications remain in fault position until the reset utton is pressed. The use of XF closing release is compulsory with this option. A-41

19 Functions and characteristics Remote operation Remote tripping PB104369A68 This function opens the circuit reaker via an electrical order. It is made up of: a shunt release second MX or an undervoltage release MN or a delayed undervoltage release MNR: MN + delay unit. These releases (2 nd MX or MN) cannot e operated y the communication us. The delay unit, installed outside the circuit reaker, may e disaled y an emergency OFF utton to otain instantaneous opening of the circuit reaker. Wiring diagram for the remote-tripping function DB DB DB DB MX or MN voltage release. Voltage releases second MX When energised, the MX voltage release instantaneously opens the circuit reaker. A continuous supply of power to the second MX locks the circuit reaker in the OFF position. Characteristics Power supply V AC 50/60Hz / / /480 V DC 12-24/30-48/60-100/ /250 Operating threshold 0.7 to 1.1 Un Permanent locking function 0.85 to 1.1 Un Consumption (VA or W) Pick-up: 200 (80 ms) Hold: 4.5 Circuit-reaker response time at Un 50 ms ±10 Instantaneous voltage releases MN The MN release instantaneously opens the circuit reaker when its supply voltage drops to a value etween 35 % and 70 % of its rated voltage. If there is no supply on the release, it is impossile to close the circuit reaker, either manually or electrically. Any attempt to close the circuit reaker has no effect on the main contacts. Circuitreaker closing is enaled again when the supply voltage of the release returns to 85 % of its rated value. Characteristics Power supply V AC 50/60 Hz / / /480 V DC 24/30-48/60-100/ /250 Operating threshold Opening 0.35 to 0.7 Un Closing 0.85 Un Consumption (VA or W) Pick-up: 200 (200 ms) Hold: 4.5 MN consumption Pick-up: 200 (200 ms) Hold: 4.5 with delay unit (VA or W) Circuit-reaker response time at Un 40 ms ±5 for NT 90 ms ±5 for NW MN delay units To eliminate circuit-reaker nuisance tripping during short voltage dips, operation of the MN release can e delayed. This function is achieved y adding an external delay unit in the MN voltage-release circuit. Two versions are availale, adjustale and non-adjustale. Characteristics Power supply Non-adjustale 100/ /250 V AC Hz /DC Adjustale 48/60-100/ / /480 Operating threshold Opening 0.35 to 0.7 Un Closing 0.85 Un Delay unit consumption Pick-up: 200 (200 ms) Hold: 4.5 Circuit-reaker response time at Un Non-adjustale 0.25 s Adjustale 0.5 s s s - 3 s A-42

20 Accessories PB Auxiliary terminal shield CB Optional equipment mounted on the chassis, the shield prevents access to the terminal lock of the electrical auxiliaries. PB104382A32 Operation counter CDM The operation counter sums the numer of operating cycles and is visile on the front panel. It is compatile with manual and electrical control functions. This option is compulsory for all the source-changeover systems. DB Escutcheon CDP Optional equipment mounted on the door of the cuicle, the escutcheon increases the degree of protection to IP 40 (circuit reaker installed free standing: IP30). It is availale in fixed and drawout versions. Blanking plate OP for escutcheon Used with the escutcheon, this option closes off the door cut-out of a cuicle not yet equipped with a device. It may e used with the escutcheon for oth fixed and drawout devices. Transparent cover CCP for escutcheon Optional equipment mounted on the escutcheon, the cover is hinged and secured y a screw. It increases the degree of protection to IP54, IK10. It adapts to drawout devices. Escutcheon CDP with lanking plate. PB Transparent cover CCP for escutcheon. A-43

21 Schneider Electric Industries SAS 35, rue Joseph Monier CS F Rueil Malmaison Cedex RCS Nanterre Capital social As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this pulication. This document has een printed on ecological paper Design: Schneider Electric Photos: Schneider Electric Printed: Imprimerie du Pont-de-Claix/JPF - made in France ART Schneider Electric - All rights reserved. LVPED208008EN

Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A

Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A Low voltage electrical distribution Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A User manual 09/2009 User manual for circuit breakers and switch-disconnectors Masterpact

More information

Compact, Interpact and Masterpact. Source changeover system. Catalogue 2007

Compact, Interpact and Masterpact. Source changeover system. Catalogue 2007 Compact, Interpact and Masterpact Source changeover system Catalogue 2007 PB100839 To ensure a continuous supply of electrical power, certain installations are connected to two sources: a normal source

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

LV power air circuit breakers and switch-disconnectors

LV power air circuit breakers and switch-disconnectors LV power air circuit breakers and switch-disconnectors Catalogue NT and NW Merlin Gerin We do more with electricity Industries SA 5, rue Nadar 92506 Rueil-Malmaison Cedex France Tel : +33 (0)1 41 29 82

More information

Catalogue. Merlin Gerin Compact LV circuit breakers and switch-disconnectors 80 to 3200A

Catalogue. Merlin Gerin Compact LV circuit breakers and switch-disconnectors 80 to 3200A Catalogue 01 Merlin Gerin Compact LV circuit breakers and switch-disconnectors 80 to 300A Compact NS 80 A Compact NS 100 to 50 A Things will never be the same Compact NS 400 to 630 A New Compact NS, setting

More information

Data Bulletin. Choosing a Trip Unit for PowerPact H-, J-, and L-Frame Circuit Breakers. Introduction. Thermal-Magnetic or Electronic Trip Unit?

Data Bulletin. Choosing a Trip Unit for PowerPact H-, J-, and L-Frame Circuit Breakers. Introduction. Thermal-Magnetic or Electronic Trip Unit? Data Bulletin 011DB110 07/01 Choosing a Trip Unit for PowerPact H-, J-, and L-Frame Circuit Breakers ENGLISH Inoduction Thermal-Magnetic or Eleconic Trip Unit? Thermal-Magnetic Trip Units 01171 t 0119

More information

Breaking and protection devices

Breaking and protection devices Breaking and protection devices 05 POWER GUIDE 2009 / BOOK 05 INTRO The purpose of selecting a protection device is to perform two essential functions: to protect people and to protect trunking, while

More information

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600 Data Bulletin 0600DB1104 03/2012 Retain for future use. Electronic Trip Circuit Breaker Basics 0600DB1104 Table of Contents

More information

more than a breaker it s a breakthrough Compact NSX

more than a breaker it s a breakthrough Compact NSX Compact NSX, more than a breaker it s a breakthrough Compact NSX 100-630 A Intelligent outlook Today, we are living in an increasingly booming and fast changing world where energy is key. More than ever,

More information

Issued by: Validated by: Last modification ABT Services Product Manager ABT Quality Manager Index A

Issued by: Validated by: Last modification ABT Services Product Manager ABT Quality Manager Index A Maintenance programme s Masterpact NT/NW Level II Issued by: Validated by: Last modification ABT Services Product Manager ABT Quality Manager Index A First edition 15 December 2004 Date (See last page

More information

SENTRON Switching and Protection Devices Air Circuit Breakers

SENTRON Switching and Protection Devices Air Circuit Breakers Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General

More information

Low Voltage. EasyPact CVS. Moulded-case circuit breakers and switch-disconnectors from 100 to 630 A. Catalogue 2011

Low Voltage. EasyPact CVS. Moulded-case circuit breakers and switch-disconnectors from 100 to 630 A. Catalogue 2011 Low Voltage EasyPact CVS Moulded-case circuit breakers and switch-disconnectors from 100 to 630 A Catalogue 2011 Safe Reliable Simple The easy choice for quality and value EasyPact CVS LV circuit breakers

More information

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800 Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement

More information

Low voltage electrical distribution. Electronic trip units. User manual 09/2009

Low voltage electrical distribution. Electronic trip units. User manual 09/2009 Low voltage electrical distribution Electronic trip units User manual 09/2009 Schneider Electric assumes no responsibility for any errors that may appear in this document. If you have any suggestions for

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination

More information

IZM ACB/Circuit-breakers. Robust safety. Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors

IZM ACB/Circuit-breakers. Robust safety. Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors IZM ACB/Circuit-breakers Robust safety Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors t [s] 0.1 0.05 0.04 0.03 0.02 0.01 20 1230DIA-125 (70C1043) 30 40 50 60 80 100

More information

Power Meter Series 700

Power Meter Series 700 PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required

More information

Arc Terminator Active Arc-Resistant Switchgear

Arc Terminator Active Arc-Resistant Switchgear Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers

More information

Current and voltage measuring relays

Current and voltage measuring relays Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application

More information

NDQ5 Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD

NDQ5 Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD Shanghai Liangxin Electrical CO.,LTD Address: No. 668 Heng An Road, Pu Dong New District, Shanghai Zip: 200137 Tel: 86-21-5012789 Fax: 86-21-58675966 E-mail: client@sh-liangxin.com LINE 1 LINE 3 LINE 5

More information

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits

More information

Tmax MCCBs. Molded case circuit breakers. Tmax

Tmax MCCBs. Molded case circuit breakers. Tmax Molded case circuit breakers Introduction ABB is once again demonstrating its commitment to new product development and its superiority in product performance. Never before has the industry seen such high

More information

Electrical auxiliaries 0 For i DPN (DPN), C60 and C120

Electrical auxiliaries 0 For i DPN (DPN), C60 and C120 Circuit protection For i DPN (DPN), C60 and C120 Function They remotely trip or indicate circuit-breakers, with or without Vigi module. Description b They are mounted to the left of the circuit-breaker

More information

Wiring diagrams. Compact NSX. Contents

Wiring diagrams. Compact NSX. Contents Compact NSX Wiring diagrams Contents Functions and characteristics A-1 nstallation recommendations B-1 Dimensions and connection C-1 Compact NSX100 to 630 Fixed circuit breakers D-2 Plug-in / withdrawable

More information

Modbus Communications System for Micrologic A, P, and H Trip Units

Modbus Communications System for Micrologic A, P, and H Trip Units Modbus Communications System for Micrologic A, P, and H Trip Units (Four-Wire Modbus System without Smart System Communication) Instruction Bulletin 0613IB1201 R06/15 06/2015 Retain for future use. Hazard

More information

Non-extensible circuit breakers

Non-extensible circuit breakers Specification Non-extensile circuit reakers 200A 0 CN2-T1 Indoor / outdoor Normal rated current 200A 12kV 16kA 3 seconds 75kV BIL 13.8kV 21kA 3 seconds 95kV BIL O O Cale earth switch 16kA 3 seconds Cale

More information

Technical catalogue - Ordering Codes. SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A 50 C rated

Technical catalogue - Ordering Codes. SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A 50 C rated Technical catalogue - Ordering Codes SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A 50 C rated New SACE Tmax XT. Simply XTraordinary. Today a highly advanced range of circuit-breakers

More information

Catalog. Arc Guard System TM TVOC-2

Catalog. Arc Guard System TM TVOC-2 Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already

More information

Gain energy insight and control with PowerLogic. PowerLogic EGX300 integrated gateway-server

Gain energy insight and control with PowerLogic. PowerLogic EGX300 integrated gateway-server Gain energy insight and control with PowerLogic PowerLogic EGX300 integrated gateway-server Plug into your energy usage with a simple mouse click The PowerLogic EGX300 is an integrated gateway-server that

More information

NEXT SOLUTION EXPERT SOLUTION EXCELLENT SOLUTION. Super Solution

NEXT SOLUTION EXPERT SOLUTION EXCELLENT SOLUTION. Super Solution NEXT SOLUTION EXPERT SOLUTION EXCELLENT SOLUTION Super Solution Low voltage circuit breakers Susol LV circuit breakers Super Solution Contents Overview Electrical characteristics Trip units Accessories

More information

Applications. diris_826_a_1_gb_cat

Applications. diris_826_a_1_gb_cat Measurement units NEW diris_824_a_1_cat Energy monitoring and management of low voltage/ high voltage electrical installations Function are measurement units which can provide all the functions offered

More information

GE Consumer & Industrial Electrical Distribution. Power Break II. Insulated Case Circuit Breakers

GE Consumer & Industrial Electrical Distribution. Power Break II. Insulated Case Circuit Breakers GE Consumer & Industrial Electrical Distribution Power Break II Insulated Case Circuit Breakers Table of Contents Power Break II Circuit Breakers......................... 3 Basic Configuration.......................................

More information

PowerLogic power-monitoring units. PM5350 power meter. Technical data sheet

PowerLogic power-monitoring units. PM5350 power meter. Technical data sheet PowerLogic power-monitoring units PM5350 power meter Technical data sheet Mid-range metering PM5350 Functions and characteristics PE86278 The PowerLogic PM5350 power meter offers all the measurement capailities

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

A project to optimise quality and energy efficiency must include metering

A project to optimise quality and energy efficiency must include metering EMDX 3 : Energy Metering A project to optimise quality and energy efficiency must include metering Metering upstream identifies the critical points and ensures optimum targeting of the actions to be taken,

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only

More information

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -

More information

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.

More information

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker

More information

RCA Remote Control ic60 Circuit Breakers Reference Manual

RCA Remote Control ic60 Circuit Breakers Reference Manual 9M01EN 01/2011 RC Remote Control ic60 Circuit reakers Reference Manual 01/2011 9M01EN www.schneider-electric.com The information provided in this documentation contains general descriptions and/or technical

More information

Energy Management Energy Meter Type EM23 DIN

Energy Management Energy Meter Type EM23 DIN Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Bulletin 150 SMC Flex Smart Motor Controller Specifications Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering

More information

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A Active harmonic conditioner from 20 to 480 A Contents 1 - Installations concerned... 2 1.1 - New installations... 2 1.2 - Existing installations... 2 2 - General... 2 2.1 - Scope... 2 2.2 - Applicable

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

GTEC transfer switch open transition

GTEC transfer switch open transition GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility

More information

General information Circuit breakers for power distribution T1 T3

General information Circuit breakers for power distribution T1 T3 Circuit breakers for power distribution T1 T3 T1 T2 T3 T1 1P T1 T2 T3 UL 489 CSA C22.2 Frame size A 100 100 100 225 Number of poles Nr 1 3, 4 3, 4 3, 4 Rated voltage AC (50-60 Hz) V 277 600Y / 347V 480

More information

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps

More information

Manual motor starter MS116

Manual motor starter MS116 Data sheet Manual motor starter MS116 Manual motor starters are electromechanical devices for motor and circuit protection. These devices offer local motor disconnect means, manual ON/ OFF control, and

More information

Fixed - Over/Under voltage limits, (0.75...1.2) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

Fixed - Over/Under voltage limits, (0.75...1.2) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits Features 71.11.8.230.0010 71.11.8.230.1010 1 - Phase 230 V Over & Under voltage monitoring relays 71.11.8.230.0010 - Fixed Over & Under voltage detection - Link selectable 5 or 10 minute lock-out delay

More information

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of

More information

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1

Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1 MainswitchSurfacemounting Partno. P3-63/I4/SVB Articleno. 207343 CatalogNo. SP3-063-I4CRQ IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual

More information

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals

NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.

More information

Technical catalogue - 2015.10. SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A

Technical catalogue - 2015.10. SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A Technical catalogue - 2015.10 SACE Tmax XT New low voltage moulded-case circuit-breakers up to 250 A Construction Characteristics 1 The SACE Tmax XT Ranges 2 Accessories 3 Characteristic Curves and Technical

More information

MASTERPACT Universal Power Circuit Breaker

MASTERPACT Universal Power Circuit Breaker MASTERPACT Universal Power Circuit Breaker Class 31 CONTENTS Description Page Introduction... 1 Advantages... 3 Description... Control Units... 7 Accessories... 3 Switch... 3 Trip Curves... 37 Wiring Diagrams...

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification

LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification 08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and

More information

Ring main units non-extensible 0

Ring main units non-extensible 0 Specification Ring main units non-extensile 0 RN2c-T1 TFL RN2c-T2 VIP 300 RN2c-T3 VIP 30 RN2c-T4 VIP 35 RN2c-T5 Glass TFL RN6c-T1 VIP 300 Indoor / outdoor Transformer mounted Freestanding O O O O O Busars

More information

How To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply

How To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply GTEC Transfer switch open transition 40 2000 amp Description GTEC transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator

More information

MasterINTERFACE 39 Series - Relay interface modules

MasterINTERFACE 39 Series - Relay interface modules MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy

More information

T 3000. Substation Maintenance and Commissioning Test Equipment

T 3000. Substation Maintenance and Commissioning Test Equipment T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy

More information

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

GE Protection and Control Business Department. Page 1 Date 5/11/99

GE Protection and Control Business Department. Page 1 Date 5/11/99 GE Protection and Control Business Department Page 1 GE Protection and Control Business Department Proven Overcurrent Protection with Power Management Communication The The Advantages of Microprocessor

More information

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus

More information

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D 7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values

More information

Maximum Demand Control

Maximum Demand Control Maximum Demand Control There are three terms that appear on the majority of electric company bills: Active energy consumption (kwh) Reactive energy consumption (kvarh) Maximum Demand Traditionally, utility

More information

E-STOP relays, safety gate monitors

E-STOP relays, safety gate monitors Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical

More information

Model 8220. POWER QUALITY ANALYZERS, METERS & LOGGERS Power Quality Meter

Model 8220. POWER QUALITY ANALYZERS, METERS & LOGGERS Power Quality Meter Special product features '''' ENERGY METER ''' MEASURES RPM POWER QUALITY ANALYZERS, METERS & LOGGERS Power Quality Meter Model A measurement tool for electrical parameters and distribution network disturbances

More information

McAfee Network Security Platform

McAfee Network Security Platform 10/100/1000 Copper Passive Fail-open Bypass Kit Guide Revision C McAfee Network Security Platform The 10/100/1000 passive fail-open ypass kit (the kit) minimizes the potential risks of in-line Network

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems LIETRAXX -A etwork and system protection (S protection) for monitoring the power feed-in of power generation systems TDB301021en/06.2013 LIETRAXX -A etwork and system protection (S protection) for monitoring

More information

Feeder protection. for overhead lines and cables in isolated neutral or compensated networks. Specification

Feeder protection. for overhead lines and cables in isolated neutral or compensated networks. Specification Feeder protection for overhead lines and cables in isolated neutral or compensated networks Specification Feeder protection for overhead lines and cables in isolated neutral or compensated networks Version

More information

Thermal-Magnetic Circuit Breaker 3120-...-M1-..

Thermal-Magnetic Circuit Breaker 3120-...-M1-.. Thermal-Magnetic Circuit Breaker -...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic tripping

More information

Multi-Protocol decoder 76 200 with Load regulation

Multi-Protocol decoder 76 200 with Load regulation Multi-Protocol decoder 76 2 with Load regulation For locomotives with universal motors on digital layouts operating in the DCC and Motorola data format. Features 76 2 Load regulated multi-protocol decoder

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

Sentron Series Circuit Breakers

Sentron Series Circuit Breakers Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of

More information

Safety automation solutions

Safety automation solutions Operating principle, characteristics Preventa safety s types XPS AV,, For and switch monitoring Operating principle Safety s XPS AV, and are used for monitoring circuits conforming to standards EN/ISO

More information

Low Voltage Products. Switches Automatic Transfer Switches

Low Voltage Products. Switches Automatic Transfer Switches Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,

More information

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A

38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A 38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

RM4TG20 three-phase network control relay RM4-T - range 200..500 V

RM4TG20 three-phase network control relay RM4-T - range 200..500 V Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking

More information

Emax DC. Annex to the technical catalogue. Low voltage Switch-disconnectors and Automatic circuit-breakers for Direct Current Applications

Emax DC. Annex to the technical catalogue. Low voltage Switch-disconnectors and Automatic circuit-breakers for Direct Current Applications Annex to the technical catalogue Emax DC Low voltage Switch-disconnectors and Automatic circuit-breakers for Direct Current Applications 1SDC200012D0201 Index SACE Emax DC automatic circuit-breakers...

More information

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager 2 1SDC200039B0201 New SACE Emax 2 for UL 1066 Circuit breakers switch power SACE Emax 2 manages it. SACE Emax 2 is the new benchmark of

More information

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,

More information

ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL

ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL INTRODUCTION... 2.. TECHNICAL DATA... 3 ACCESSORIES... 5. INSTALLATION... 7 OPERATION... 12. TECHNICAL INFORMATION... 13 MAINTENANCE... 14. CONFIGURATIONS...

More information

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A

AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Relion 605 series. Self-powered feeder protection REJ603 Product Guide Relion 605 series Relion 605 series Relion 605 series Self-powered feeder protection Product Guide Product version: 3.0 Contents 1.... 3 2. Relay functions... 3 3. Protection functions... 4 4. Application...

More information

Three-phase monitoring relay CM-PFE

Three-phase monitoring relay CM-PFE Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics

More information

Fundamentals of Power

Fundamentals of Power Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At

More information

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX 759 26-06-2007 759 M1 02 E MES FLOW CALCULATOR 759-02/1 BAMOPHOX 759 E - M FLOW CALCULATOR INSTRUCTION MANUAL MESURES 22, Rue de la Voie des Bans - Z.I. de la Gare - 95100 ARGENTEUIL Tél : (33) 01 30 25 83 20 - Web : www.bamo.fr Fax : (33) 01 34 10 16 05 -

More information