FAQ configuration profibus example for series SX502



Similar documents
Siemens S7 PLC and FC 300 Profibus

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE A5 Programming the CPU 314C-2DP

CPU PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU PN/DP: Configuring an ET 200S as PROFINET IO device

SIMATIC NET. CP AS-Interface Master B C. Preface Contents. Technical Description and Installation Instructions Interface to the User Program

SIMATIC S Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E

1 Application Description Objective Goals... 3

DVPPF02-H2. PROFIBUS DP Slave Communication Module Application Manual

SIMATIC NET. AS-Interface - Introduction and Basics A B. Preface, Contents

Programming Logic controllers

S7 OPC Server Tutorial

Configuration a Profibus-DP node using Step7 and WAGO-I/O components Application note

Service & Support. How can you establish a connection between a S PLC and SIMATIC NET OPC? S PLC, SIMATIC NET OPC.

Programmable set for Ethernet Modbus/TCP in IP67 TI-BL67-PG-EN-2

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

OZW30. Central Unit SYNERGYR

DP-DMX20L 4 CHANNEL DMX DIMMER PACK MODE MENU DISPLAY. OUTPUT: 10A/CH, TOTAL 20A Max. DMX CHANNEL RECEIVE TOTAL DMX CHANNEL DIMMER / SWITCH

HERZ-Thermal Actuators

Start-up of IVI-KHD2-4HRX, IVI-KHA6-4HRX at S7-300 V1.1. Table of Contents TABLE OF CONTENTS... 1

Cover sheet. Reading out the topology data of a PROFINET IO system SFB52 "RDREC" FAQ September Service & Support. Answers for industry.

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

Surf it Easy. User Guide

SOFTLINK 300. CPU Specifications. Reference Manual

Operating Precautions: User configuration options:

FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK

Notice. Reverse engineering and disassembly are prohibited.

Development of a Gateway to PROFIBUS for Remote Diagnostics

SIMATIC. Automation System S7-400 Hardware and Installation A B. Preface, Contents. Product Overview. Installing the S Addressing the S7-400

Commercial Refrigeration Temperature and Defrost Controls

TX OPEN RS232/485 module

1 Application Description System Topology Hardware and Software Requirements... 3

PROFIBUS AND MODBUS: A COMPARISON

Commissioning IDENTControl Compact IC-KP2-2HB17-2V1D Profinet Protocol with a Siemens S7 PLC

PROCESS AUTOMATION PLANNING AND INTEGRATION INFORMATION LB8106* Integration in Siemens SIMATIC PCS 7

Using installed Fieldbus Wiring to carry Ethernet Communications

Service & Support. How can you establish a connection between an S PLC and SIMATIC NET OPC? S PLC, SIMATIC NET OPC.

Relay mounting systems

Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits and

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODUL E04

KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184

Continuous PROFIBUS PA Instruments and Step 7. Configuring a Siemens Continuous Level PROFIBUS PA device in a S7-300 or S7-400 PLC

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Instruction Manual Differential Pressure Transmitter

Cover PROFINET IO. Code Reader System SIMATIC MV440 / MV420. FAQ June Service & Support. Answers for industry.

BK MIKRO9. Tool monitoring system. Getting Started with Profibus Release 1.00 /

Digital input modules

Cooktop Low-Profile Ventilation Hoods

SYNCHRONIZE DIGITAL CLOCK SYSTEM NETWORK DIGITAL CLOCK VER 1.0 DYNATEK

Contractors Guide Central Inverter System Installation

MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE. USER GUIDE Document reference :

CompactLogix Power Supplies Specifications

Hard Disk Drive (HDD)

User Manuals. Connection to Siemens S5 PU (AS511) Part Number: Version: 2. Date:

LINK GPS MGMT DATA. 5 GHz Carrier Backhaul Radio DATA MGMT GPS. Model: AF-5X LINK

Contact expander modules

Dupline Field- and Installationbus Dupline Profibus-DP Gateway Type G

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Configuration limits for products of the SIMATIC NET PC Software V12 SIMATIC NET. Configuration limits for products of the SIMATIC NET PC Software V12

Specifying a Variable Frequency Drive s

CMP30. User Manual.

2XWSXWFKDQQHOV 3KDVH &+ CH 2 &+ CH 4 &+ CH 6 L1 X X L2 X X L3 X X

Cover sheet PROFINET IO. SIMATIC MV440 Code Reading System. FAQ February Service & Support. Answers for industry.

IMPORTANT SAFETY INSTRUCTIONS

SIMATIC HMI. WinCC flexible 2008 Getting Started - First-Time Users Getting Started. Printout of the Online Help 06/2008 A5E

SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

Contact expansion modules

CMC-PD01 PROFIBUS DP Slave Communication Card Operation Manual

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

Heavy Duty Solenoid Controlled Access Lock. User Manual - Original Language Version

Comfort Control Relay Panel (CCRP)

CB15/CB155. PROFIBUS Module

LASER-PROTECTION INFORMATION

What ensures easy and fast wiring?

Using a Laptop Computer with a USB or Serial Port Adapter to Communicate With the Eagle System

WAGO PFC 750-8xx Interface to Horner HMI Application note

FAQ about Drive Technology

How To Use A Power Supply On A Powerline 2.2 (Ai)

How To Write A Profibus Dpl (Profibus) Program

Using the WAGO PROFINET Coupler as Remote I/O with a Siemens S7 PLC

100 - SERIES NETWORK SWITCHES QUICK START GUIDE

8146/5 Series Breaker Panelboards

IBS IP KIS A. Data Sheet INTERBUS-S. Digital I/O Module

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

SIMATIC NET. DP Base Programming Interface for CP 5613/CP Preface, Contents. Basic Steps in Creating a DP Application 1

Configuring the Siemens TC35 modems for use with the MI2292

PNOZsigma - Base units

webampl Training December 2015

Shrinking a power supply and the challenge to maintain high reliability.

S7 for Windows S7-300/400

ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS

Actuator controls AUMATIC ACExC 01.2 Profibus DP

ALARMS-xx. Remote Alarm Unit Setup Guide RESET ALL

DE1600 DSA E-Series iscsi Disk Arrays. en Quick Install Guide

CelluLine CGW-TS GSM Cellular Gateway. Installation and Programming Manual

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE C2. High Level Programming with S7-SCL

User Manual Revision English

DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.:

ND48-RS ASCII A2.04 Communication Protocol

=============================== WARNING

Transcription:

Safety precautions Important Information Read these operating instructions before starting the unit. They provide you with important information on the use, safety and maintenance of the units. This helps you to protect yourself and prevent damage to the unit. Information intended to help you to avoid death, bodily harm or considerable damage to property are highlighted by the waring Triangle shown here; it is imperative that this information be properly heeded. Safety components inside the units are energized with electricity during operation. For this reason, mounting and maintenance work may only be performed by professionally-trained personnel while observing the corresponding safety regulations. The units do not have a power switch. They are operative as soon as the operating voltage is applied. Intended use The units are intended for use in industrial environments. They may only be operated within the limit values stipulated by the technical data. When configuring, installing, maintaining and testing the units, the safety and accident-preventation regulations relevant to use in each individual case must be comlied with. Trouble-free, safe operation of the units requires proper transport, storage, installation, mounting and careful operation and maintenance of the units. Mounting and Installation The attachment options for the units were conceived in such a way as to ensure safe, reliable mounting. The user must ensure that the attechment hardware, the unit carrier and the anchoring at the unit carrier are sufficient to securely support the unit under the given surrounding conditions. The units are to be mounted in such a way that they can be opened up while mounted. Sufficient space for the cables must be available in the unit near the cable infeed. Sufficient space is to be kept clear around the units to ensure air circulation and to prevent the biuld-up of heat resulting from use. The relevant information must be heeded in the case of units ventilated by other means. FAQ - configuration profibus example 07.01.2013 Seite 1/13

When the housing fasteners are opened, the front frame of the housing hinges out upward or downward (depending on the unit version) automatically. Grounding Other All devices are equipped with a metal housing. They comply with safety class I and require a protective earth connection. The connecting cable for the operating voltage must contain a protective earth wire of a sufficient cross section (DIN VDE0106 part 1, DIN VDE 0411 part 1). Read first the chapter 1 of the manual. 1. connect your new SX502 over profibus dp on your plc and power supply the best configuration to learn communicate SX502 over profibus dp is to connect only one display on plc and no other functions will be on plc than the example file. Profibus DP 230V AC 50Hz FAQ - configuration profibus example 07.01.2013 Seite 2/13

2. Start Siemens Simatic Manager 3. extract the example file from the file folder FAQ - configuration profibus example 07.01.2013 Seite 3/13

4. open the hardware configuration FAQ - configuration profibus example 07.01.2013 Seite 4/13

5. change the profibus slave address on your favorite address FAQ - configuration profibus example 07.01.2013 Seite 5/13

6. choose a configuration from hardware catalog and set it on the plug-in position of the profibus slave (for example Online Text 1 (byte) In 8 (bytes) consistent out) Attention! Please remember the definition of consistent data bytes out (in this example is 8 Bytes) If you choose another configuration (for example 16 Bytes) you must set this value in FC3 at the hardware settings but in HEX. FAQ - configuration profibus example 07.01.2013 Seite 6/13

7. change the E/A Address of the profibus slave configuration Attention! Please remember the definition of E/A addresses. If you choose another definition (for example E-address 4 and A-address 10) you must set this value in FC3 at the hardware settings but in HEX. FAQ - configuration profibus example 07.01.2013 Seite 7/13

8. save and translate hardware configuration and send it to the plc. FAQ - configuration profibus example 07.01.2013 Seite 8/13

9. open FC3 ( SX502 Communication ) and scroll down until displayed set H E R E datas of hardware configuration change there the values that is set in the hardware configuration Attention! Values must be enter in HEX. In hardware configuration the values are in DEC. OutputAddr = 32 HEX (in hardware configuration 50 DEC) InputAddr = 2 HEX (in hardware configuration 2 DEC) LenConsData = 8 HEX (in hardware configuration 8 DEC) FAQ - configuration profibus example 07.01.2013 Seite 9/13

10. also in FC3 you set the marker bytes for choose the DB that will send if you control this marker byte Marker byte DB no. to send FAQ - configuration profibus example 07.01.2013 Seite 10/13

11. save everything to the plc FAQ - configuration profibus example 07.01.2013 Seite 11/13

12. open the variables sheet 13. control the marker byte with keys CTRL + 1 Now on the display of the SX502 will be text : Welcome to Siebert Industrieelektronik GmbH This is the text in DB3. If you control M0.1 the text that display called: Innovation in display This is the text in DB4. If you control M0.2 you set a text with variables : SOLL: $VS$VS$VS This is the text in DB5. IST: $VS$VS$VS And if you control M0.3 you only send variables on the text from DB5: 1 2 3 4 5 6 This is the text in DB6. FAQ - configuration profibus example 07.01.2013 Seite 12/13

14. If you want to send an individual text change only the text in DB3 and control the marker byte M0.0 In FC3 you can expand the function with the control of marker bytes if you have more text you would send. Then make a new DB with text and control it with a new marker byte. FAQ - configuration profibus example 07.01.2013 Seite 13/13