Advanced Protection of Distribution Networks with Distributed Generators



Similar documents
Context: significant penetration of DG = increased risks for system security

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014

Power products and systems. Intelligent solutions for power distribution Zone concept

FRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Solar Power Plant Design and Interconnection

Cahier technique no. 196

Guidelines for ATS selection: How to choose the right transfer solution for your power application.

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

Power System review W I L L I A M V. T O R R E A P R I L 1 0,

Size template. Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer

Operation and Control Microgrid and Distributed Generation. Mohammad Shahidehpour Illinois Institute of Technology

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES

Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply.

ESB Networks Perspective on Microgeneration

Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid

What Matters for Successful Integration of Distributed Generation

Agenda do Mini-Curso. Sérgio Yoshio Fujii. Ethan Boardman.

Transmission Protection Overview

HVDC-VSC: transmission technology of the future

Teleprotection Schemes and Equipment. James W. Ebrecht Young Power Equipment Scottsdale, AZ

Connection of micro-generation to the electricity distribution network

ABB PSPS Erich Steinmann; Generator control-2013

Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Paralleling Switchgear

MICROGRIDS FOR DATA CENTERS

Guidelines for Large Photovoltaic System Integration

Rule Fast Track Analysis for National Life Insurance Co.

IEEE Smart Grid Series of Standards IEEE 2030 TM (Interoperability) and IEEE 1547 TM (Interconnection) Status. #GridInterop

Test & Data Management Software

Nuclear Power Plant Electrical Power Supply System Requirements

Islanding detection in power electronic converter based distributed generation

SYNCHRONOUS MACHINES

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

RENEWABLE ENERGY INFEED R Herman, M Malengret and CT Gaunt University of Cape Town, South Africa

Coordinated and Optimized Control of Distributed Generation Integration

Physical Address: City: State: Zip Code:

Local Back-up Protection for an Electric Power System

Microgrid Building block for Smart Cities

Smart Grid: Concepts and Deployment

Energy Systems Integration

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

Paralleling and Protection Unit Type PPU multi-line E

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP

Basics of Electricity

Eaton s E-Series protective relay family

Engineering Recommendation G59 Issue 3 Amendment 1 August 2014

TABLE OF CONTENTS 1.0 INTRODUCTION PURPOSE DEVIATION INTERTIE PROTECTION REQUIREMENTS... 4

Value of storage in providing balancing services for electricity generation systems with high wind penetration

CERTS Microgrid Research and Lessons Learned

SPECIFICATION COG-2007

PSEG-LONG ISLAND SMART GRID SMALL GENERATOR INTERCONNECTION SCREENING CRITERIA FOR OPERATING IN PARALLEL WITH LIPA S DISTRIBUTION SYSTEM

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Power Quality Paper #3

TECHNICAL INTERCONNECTION REQUIREMENTS FOR DISTRIBUTED GENERATION. Micro Generation & Small Generation, 3-phase, less than 30 kw

NPCC Regional Reliability Reference Directory # 8 System Restoration

Brochure Introducing HVDC

SDG&E Electric Distribution System Interconnection Handbook. <Revised as of 10/21/2015>

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

TDMS Test & Data Management Software

International Review of Grid Connection Requirements related with Voltage Dips for Wind Farms

Arc Terminator Active Arc-Resistant Switchgear

Control of Distributed Generation Units in Stand-Alone Industrial Networks

Deep Dive on Microgrid Technologies

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

A vision of sustainable energy future: A multi-energy concept of smart energy systems Central European Student and Young Professionals Congress

Transfer Equipment Controls

ENA Customer Guide to Electricity Supply

Data center power dynamics within the settings of regional power grid

EVALUATION OF ALTERNATIVE BACKUP PROTECTION SCHEMES ON A 66KV DISTRIBUTION NETWORK

APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.

Chapter 5. System security and ancillary services

The State of the Electrical Grid in Washington State. Michael Pesin, PMP, P.E. Seattle City Light

FIT TIER 2 Application

Isolated-Parallel UPS Configuration

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

Transient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink

Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process

A.V.R. R250. Installation and maintenance R250 0V E+ E- VOLT STAB FREQ. & L.A.M. CONFIG. 50Hz. 47.5Hz. 57Hz LAM 1 13% 2 25% OFF LAM OFF 9

Solar Energy. Airports Going Green Aimee Fenlon

Grid Code - High and extra high voltage - Tennet TSO GmbH Bernecker Straße 70, Bayreuth

ECE 586b Course Project Report. Auto-Reclosing

Technical Challenges of Smart- and Microgrids

FIXED CHARGE: This is a cost that goes towards making the service available, including

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Sodium Sulfur Battery. ENERGY STORAGE SYSTEM for Reducing CO2 Emissions

AUSTIN ENERGY INTERCONNECTION GUIDE FOR CUSTOMER-OWNED POWER PRODUCTION FOR FACILITIES UP TO 10MW A INTERCONNECTION CLASSIFICATIONS...

300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal

How To Protect Your Power Supply From Dangerous Currents And Voltages

Transcription:

Date:- 8 10 March 2011 Venue: University of Manchester EES-UETP Course title Advanced Protection of Distribution Networks with Distributed Generators Peter Crossley Director of the Joule Centre School of Electrical & Electronic Engineering University of Manchester

Can we prevent Distributed Generation? Options: large numbers of bulk generators (coal, gas, nuclear, hydro) DC and UHV AC transmission links between regions limited role for renewables (mainly wind) conventional distributed generation & combined heat and power Is this option politically/socially/economically viable? 2

Existing distribution networks 132kV 11kV 415V 51, 51N 51, 51N power flows from grid supply to LV network protection based on phase & earth inverse overcurrent relays

Effect of distributed generation on existing overcurrent protection Fault current seen by relay may increase or decrease: depends on relay and fault location, network fault levels, strength and location of distributed generators Grading studies must consider: max & min infeed from all possible distributed generators problems:- intermittent nature of distributed generators Main problem: how to protect intertie between generator and utility network must correctly co-ordinate with network protection for all operating conditions

Gas company Power company Information network Is this the future of our urban distribution networks? Measure ment Photo Voltaic Wind power Hydraulic Fuel cell Buildings, hospitals, schools, etc. Control system Supply side Hydrogen Co-generation Demand side Sewage treatment Biomass power Residential load Public load Electricity Heat Refuse power Energy storage (NAS battery) 5

what about our rural communities? Are small self-sufficient rural islands viable? 牛 Biomass 糞 尿 バイオマスプラント plant (Night soil) PV power 太 陽 光 発 電 Bio Gas Engine Gen Load Generation 発 電 設 備 system Load 負 荷 6

new-build estates with micro-generators, PV & storage: Power Supply from the utility grid (constant) Load curve 0 Charge Charge energy DG output energy storage storage 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 hour 7

Does numerical protection & control relays (IEDs) solve your DG problems? Or just give you more panel space! 8

You have a lot of options, but can they deliver the solution? 9

An IED is much more than a relay! Protection relay M e t e r i n g k V, H z k A, M W M V a r c o s p h i F a u l t r e p o r t i n g if you use its power F a u l t r e c o r d i n g F a u l t l o c a t i o n k m Monitoring 10

Overcurrent protection of radial network with distributed generators 132kV 11kV 415V 51, 51N 51, 51N G G 11

Overcurrent protection: - radial network with distributed generators correct operation 51, 51N G 51, 51N correct but slow back-up G Can generator ride through fault? 12

Overcurrent protection: - radial network with distributed generators 51, 51N G Can generator ride through fault? 51, 51N correct operation G Will generator trip? 13

Overcurrent protection: - radial network with distributed generators How do we trip this breaker? G 51, 51N correct operation G? Can generator ridethrough fault? Will generator trip? Should generator trip? 14

Directional Comparison Protection: - radial network with distributed generators Dir.Comp Prot n Dir.Comp Prot n G G Can generator supply local utility load? If yes; should it? If no; can we shed load? What about protection of island? Is fault current sufficient to operate protection? How do we reconnect island? 15

Future?? Dir.Comp Prot n Dir.Comp Prot n G1 G2 Dir. Comp Prot n = high speed fault clearance Sync. generator G1 remains in sync & connected After fault clearance:- sync. gen. G2 governor picks up load (and if necessary sheds load). G2 then supplies local island at statutory volts & freq. Faulted line restored; requires sync check on breakers 16

Overcurrent protection: - radial network with distributed generators 51, 51N 51, 51N G Can generator ride through fault? G electronic interface = no fault current. trip using loss of grid 17

Protection & restoration of rural active radial network 51, 51N N/O point G 51, 51N 18

Protection of rural active radial network:- assumes G59 51, 51N N/O point 51, 51N G trip breaker trip breaker 19

Active radial network:- restoration: 51, 51N N/O closed open open G reclose 51, 51N Breaker closed 20

Protection & restoration of rural active radial network 51, 51N N/O point G Dir O/C Dir O/C 21

Protection of active radial network:- permanent fault 51, 51N Can generator ride through fault? N/O G Dir O/C trip breaker Dir O/C trip breaker Problem:- is I fault sufficient? 22

Restoration of rural active radial network: 51, 51N two sections dead Can generator supply island? G Dir O/C Dir O/C local island 23

Restoration of rural active radial network: 51, 51N section dead Open generator breaker close G Dir O/C close breaker open Dir O/C reconnect generator 24

Dir.comp protection of rural active radial network advantages:- high speed fault clearance (100ms) limited impact of ext. faults on generator stability disadvantages:- needs circuit breakers and communications Dir comp. Dir comp. G Dir comp. Dir comp. 25

Formation of an Island Cause:- opening of a circuit breaker in response to a downstream fault Ideally:- DG protection should detect the fault and trip DG before island formed If protection fails to detect the fault, or breaker is manually tripped, islanding can occur.

Prot n for distributed generator 87 Grid Supply Utility intertie 51N G MV 51V = voltage controlled overcurrent 40 = loss of excitation 87 = phase differential 81U/81O = under/over freq. 27/59 = under/over voltage 32 = reverse power Loss of grid:- requirement in UK 27 59 81U 81O Loss of Grid 51V 32 40 27

Prot n for generator supplying industrial load & embedded into utility network Utility interface MV utility industrial consumer 27 59 81U 81O 51 32 50 LOADS Loss of Grid G Generator Protection 28

Loss of grid protection Faults on utility network cleared by local relays: hence:- distributed generators may attempt to supply parts of network islanded from grid for safety:- protection on distributed generator intertie must detect loss of grid and trip intertie breaker Islanding of distributed generator: may leave section of network without earth fault level inadequate to operate protection relays distribution breakers do not include check synchronising hence:- reclosing of breaker could result in its destruction Immediately after removal of grid supply, G59 states: all distributed generators connected to island must be disconnected remain disconnected until grid supply restored

Islanding Detection Techniques

Island Detection Inter-tripping Schemes

Mediums of Inter-tripping Schemes: (a) leased line, (b) radio/microwave

Mediums of Inter-tripping Schemes: fibre/copper cables

Network with changeable feeder topology:

Power-line Signalling Scheme:

Operation of Power-line Signalling Scheme:

Phasor Measurement Unit based LOM: Voltage Signal from Substation Phase Measurement LOM Detection Unit Voltage Signal from DG Phase Measurement GPS Receiver GPS Receiver

Loss of mains protection Two techniques used to detect loss of mains: rate of change of frequency (ROCOF) vector shift ROCOF assumes most 11kV feeders loaded up to about 5MW loss of grid:- part of load supplied by embedded generator generation deficit, causes rate of change of frequency 2 df/dt = -(P LO x f r - P TO x f r 2)/(2 x H x P TNOM x f r )» P LO = load at rated frequency» P TO = output of distributed generator» P TNOM = rated capacity of generating plant» H = inertia constant of generating plant» f r = rated frequency

ROCOF Example: consider 800kW 1MVA generator with inertia constant H of 1.2s operating at 615kWwhen loss of grid occurs if load on generator suddenly increases to 677kW the initial rate of change of frequency is: df/dt = -(0.677 x 50 2-0.615 x 50 2 )/(2 x 1.2 x 0.800 x 50) = -1.6Hz/s Relay operating threshold = 0.1-10Hz/s (typ.:- 0.2-0.5Hz/s) Relay operating time = 0.04-2.0s (typ :- 0.2-0.5s) ROCOF sensitive and dependable method of detecting LOG concern about nuisance trips caused by loss of bulk generation UK:- loss of bulk generation regularly causes 0.2Hz/s, occasionally 1Hz/s incorrect tripping of large amounts of distributed generation risks integrity of national network

ROCOF Detection Method:

Impact of a freq dip on a ROCOF relay 41

Impact of a freq dip on a ROCOF relay 42

For those interested in stability! 43

Vector Shift normal operation:- terminal voltage of embedded generator (V t ) lags the synchronous emf (E f ) by rotor displacement angle ( ) V V = I 1.jX d I 1 I 2 E f V t E f V t Z Grid supply Z = local load

Vector Shift If grid lost:- load on generator increases; hence sudden increase in V V = I 1.jX d I 1 E f V t E f V t Z Grid supply

Voltage waveform of DG at instant of islanding:

Loss of grid protection Problem:- sensitivity.vs. stability can ROCOF/vector shift always detect loss of grid? can appropriate loss of grid setting prevent nuisance trips Nuisance trips often caused by bulk loss of generation Impact depends on strength of power system European network:- loss of bulk generator = negligible change in df/dt or voltage angle Great Britian network:- loss of bulk generator = occasional significant change in df/dt or voltage angle Ireland network:- loss of bulk generator = significant change in df/dt or voltage angle

LOM detection:- reverse reactive power scheme: parallel with grid DG operates close to unity power factor Reactive demand mainly supplied by utility islanded operation DG must now supply reactive demand reverse reactive power relay detects change of reactive power flow and trips DG after a time delay.

LOM detection: system impedance monitoring utility connected:- measured impedance low impedance increases significantly after islanding = fast operation, immune to network instigated nuisance trips

Islanded operation:- impact of load disturbance synchronous DG with appropriate governor and AVR control Voltage and frequency restored within recommended synchonisation limits Problem = phase deviation between utility and island systems

Control of frequency and phase of islanded network phase difference control added to conventional DG governor control phase deviation regulation effective if island has one sync.generator What happens with multiple generators in the island?

Problems with existing LOM detection schemes EMTDC/PSCAD distribution network model ROCOF relay model (100ms moving window)

Zero-crossing LOM detection technique

Impact of DG inertia constant on rate of change of freq.

Impact of DG inertia constant on ROCOF LOM detection A ROCOF relay with a typical maximum setting of 1Hz/s failed to detect LOM when H of DG is high (3.0s) Recommended setting in GB is 0.125Hz/s, in N.Ireland is 0.45-0.5Hz/s

Effect of voltage dependant loads on ROCOF LOM detection (insensitive setting of 1Hz/s)

Impact of load power factor on ROCOF LOM detection Load power factor changes the voltage profile and affects the dynamic behaviour of a voltage dependent load The smaller the load power factor the greater the voltage reduction at instant of islanding

Impact on ROCOF of islanding and system disturbances

Impact on ROCOF of islanding and system disturbances Network model used in simulation studies: Case 1:- islanding with 0.2pu power imbalance; B1 opened at 0.25s. Case 2:- islanding when load and generation are closely matched Case 3:- network disturbance, effect of switching action on ROCOF Case 4:- impact on ROCOF relay of network fault conditions

Case 1: islanding with 0.2pu power imbalance; B1 opened at 0.25s Immediately after islanding, voltage decreases and frequency starts to reduce (dotted lines represent voltages if islanding had not occurred).

Case 1: response of ROCOF relay to islanding with 0.2pu power imbalance; B1 opened at 0.25s (relay setting = 1.0Hz/s)

Case 2: islanding when load and generation are closely matched Frequency deviation is very small, hence ROCOF relay, set at 0.125Hz/s, failed to detect islanding

Case 3: Network disturbance, effect of switching action on ROCOF relay (LOM relay should not operate) higher the DG s loading, greater the effect of switching on ROCOF ROCOF relay set at 0.125Hz/s, incorrectly operated ROCOF relay set at 0.2Hz/s, correctly remained stable

Case 4: ROCOF relay behaviour during network fault conditions. 3Ф fault on adjacent feeder 2-4, fault removed after 0.25s

Case 4: ROCOF relay behaviour during network fault conditions. 3Ф fault on adjacent feeder 2-4, fault removed after 0.25s. ROCOF relay not expected to operate (not islanding event) ROCOF relay with setting of 1Hz/s incorrectly operated. Relay failed to distinguish between islanding event and adjacent feeder fault

Case 5: Switching on a 10MW/phase load at DG terminals ROCOF relay incorrectly operates if setting < 0.9Hz/s

Case 5: Switching off a 10MW/phase load at DG terminals ROCOF relay incorrectly operates if setting < 0.9Hz/s

Case 6: Impact of sudden loss of major generation infeed to test ROCOF stability, test signal used with freq increase of 0.16 Hz/s for 0.5s and then decreases at 0.16Hz/s for 0.5s.

To increase security of ROCOF relays, whilst attempting to preserve dependability, various solutions are proposed: time delays of 50 500ms used to reduce number of nuisance trips time delays = monitoring of rate of change of frequency over few cycles increasing duration of measuring window over which ROCOF calculated measuring windows = 40ms (2 cycles) to 2s (100cycles at 50Hz) Under-voltage interlock; block ROCOF if DG terminal voltage <0.8pu Difficult to completely prevent mal-operation of ROCOF during disturbance or non-islanding event Setting value must balance security and dependability Summary:- Operating performance of ROCOF relays Relay not capable of detecting LOM when load and generation in island are approximately matched Relay very susceptible to nuisance tripping; to increase stability higher Hz/s setting value required High setting value compromises relay dependability and increases non-detection zone

Future challenges Existing status very low levels of distributed generation not considered in existing passive distribution network design assumed to be of no importance in stability and reliability of overall system Short term projections increased levels of distributed generation (20% by 2010?) needs active distribution networks power electronics for generator interfaces & power quality enhancement requires safe, effective and economic protection and control Long term projections UK:- 60% reduction in CO2 emissions by 2050 micro-grids:- independent cells of dispersed generation power grid interconnects pseudo-autonomous micro-grids how to ensure stability and reliability of loose network? 70