Size template. Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer
|
|
|
- Jonas Ferguson
- 10 years ago
- Views:
Transcription
1 Size template Grid Connection Masterclass Energex John Lansley Senior Network Solutions Engineer
2 The average system size has doubled since 2010
3 Key Network Issues Reverse power on up to 12 off 11 kv feeders major impact on Regulators Around 100 voltage enquiries per month 40% solar related and remedial work required on 20 distribution substations (typically by balancing the LV network and dropping transformer tap) Remedial costs around $11 Mill per annum High voltage at customer supply points - can cause damage to customer equipment and lead to insurance claims (a $30 K claim where a non solar customer received up to 264 volts) 42 kw of Solar PV s on 100 kva transformer 1200 m of LV cable (240 mm2) 2 x 10 kw, 2 x 4.5 kw and 1 x 5.3 kw Solar PV systems Unbalance volts with one phase up to 264 Volts (at CP) High voltage can cause nuisance overvoltage protection tripping of customer Solar PV inverters leading to customer complaints due to loss of revenue.
4 Energex Connection Standards 1143 Connection guidelines for PV/IES Systems up to 30kVA 233 Connection guidelines for PV/IES systems 30kW 5MW (equivalent to Chapter 5A of NER) 1188 Connection guidelines for embedded generation >5MW (equivalent to Chapter 5 of NER) Location
5
6
7 Assessment Criteria Test 1 11kV Feeder penetration test (15% of 50POE rating) Test 2 Distribution transformer penetration test (25%) Test 3 Unbalanced generation test (S i < 8% nameplate rating transformer) Test 4 HV Disturbance Test (S i / S sc < 0.1%) at 11kV PCC Test 5 LV Disturbance Test (S i / S sc < 1.0%) at LV PCC S i = inverter rating (kva) S sc = short circuit rating (kva)
8 Alternatives Where Test Fails Test 1 & 2 nil export system, reduce size. Test 3 three phase system, reduce size Test 4 & 5 look at customer side mitigation for reducing voltage disturbance (eg. Varying power factor, lower emission inverters) Network side mitigations funded by customer are also options (eg dedicated transformer, HV feeder)
9 Network Solutions to address increasing levels of solar PV penetration Balancing the PV load is an effective action when there are large single phase solar PV systems on the smaller distribution transformers (less than 20 customers). Balancing is less effective on the larger distribution transformers (where there are up to 100 customers) and the loads are better balanced A change in transformer tap will reduce the voltage by 6 Volts (2.5%) this is the main action for addressing high voltage but may not be possible if the customer voltages fall below the regulated limit of V. Generally only one tap-change increment can be accommodated without compromising overall voltage regulation. An upgraded transformer will allow the opportunity to re-set the taps (by 6 volts) and allow higher penetrations of solar PV. This action may not be possible if the pole is not suitable for the additional loads. A new transformer is generally required where the high voltage is caused by long lengths of LV, typically in excess of 600 metres this may be all Energex LV conductors or part Energex and part consumer mains. The cost for a new transformer installation can be considerable if the 11 kv network has to be extended a long distance. Where there are smaller aged conductors (e.g 7/.080 copper) re-conductoring is an option to reduce voltage rise/drop and maintain LV within regulated limits. Modelling indicates that reconductoring 7/.080 with LVABC can halve the voltage rise. Some of the newer technologies (e.g on load tap changer) are expected to cost more than an upgraded transformer, but less than the installation of a new transformer, but others (e.g STATCOM) is expected to be at a similar cost to a new transformer. The STATCOM does have other advantages as it can offset peak load with the use of the battery storage.
10 Calculations Required Where Test 4 & 5 Fail Internal voltage rise Harmonics - ( Hi 3 ) Flicker calculate actual voltage rise at PCC based on source impedance. Ramping of inverters to match load for nil export. I V r IR IX V s
11 Other Items Approved relay list for backup anti-islanding Nil export requirements Inverter settings 257V overvoltage (260V 2 sec) Leave inverters OFF prior to metering being installed Parameter Vmax Vmin Fmax Fmin Disconnect time Reconnect time Setting 257V (260V 2 sec) 210V 52Hz 47Hz 2 secs seconds
12 Design Certification Report (DCR) Network connection diagram Protection line diagram Protection settings Inverter & panel details, incl settings Calculation of internal voltage rise to PCC If fails Test 4 & 5 calculations showing customer mitigation for power quality Test & Commissioning Report (TCR) Steady state voltage log Flicker and harmonics log before & after. Anti-islanding tests OV/UV setting on backup relay pickup test. Signed by a Registered Professional Engineer Qld (RPEQ) Signed by a Registered Professional Engineer Qld (RPEQ)
13 Example 2 Customer applies for 96kVA 3 phase off a shared transformer 315kVA nameplate rating. Source impedance j1.81 ohms on 11kV, Ztr = j15.01 ohms as seen at 11kV terminals. 11kV Feeder CRB15A Min feeder load estimated at 30% feeder load = 646kVA (Max PV penetration = 50% min feeder load). There is already 61kW connected PV to distribution transformer, and 250kVA off 11kV feeder. ENERGEX ASSESSMENT Test Limit Actual Pass/Fail 1. 11kV Feeder Penetration Test 323 kv.a 346 kv.a fail 2. Distribution Transformer Penetration 49.8% Test 25.0% fail 4. 11kV Feeder Voltage Fluctuation & Distortion Test 0.10% 0.24% fail 5. LV Feeder Voltage Fluctuation & Distortion Test 1.0% 0.1% pass ASSESSMENT RESULT FAIL Options Nil export (overcomes Test 1) Dedicated transformer (overcomes Test 2 & 5) Reduce size to pass Test 4 or prove by calculation & customer side mitigation that no quality of supply concerns on HV.
14 Summary Size Assessment Nil Export Backup Protection RPEQ Design RPEQ Testing Assessment Fee 5kW No N/A No No No No >5 to 30 kw Yes Option No No No No >30 to 150kW Yes Option Approved relay, no NVD for nil export >150kW Yes Option Approved relay, includes NVD on HV Yes If fails Test 4 or 5 $ $3000 Yes Yes Actual costs
Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process
Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process Presented by: Marianne Mannschreck Date: Welcome A Look at the Net Energy Metering
TECHNICAL INTERCONNECTION REQUIREMENTS FOR DISTRIBUTED GENERATION. Micro Generation & Small Generation, 3-phase, less than 30 kw
TECHNICAL INTERCONNECTION REQUIREMENTS FOR DISTRIBUTED GENERATION Micro Generation & Small Generation, 3-phase, less than 30 kw i COPYRIGHT 2010 HYDRO ONE NETWORKS INC. ALL RIGHTS RESERVED ii LIMITATION
APPLICATION NOTE. Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution
APPLICATION NOTE Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution INCREASING PV HOSTING WITH EMPOWER TM SOLUTION Executive Summary Distributed solar photovoltaic
Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114.
Generation Interconnection System Impact Study Report For PJM Generation Interconnection Request Queue Position X1-114 Sandyston January 2012 Preface The intent of the System Impact Study is to determine
Rule 5.500 Fast Track Analysis for National Life Insurance Co.
Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION
Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns
Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns Mehmet H. Cintuglu, [email protected], Armando Altamirano, [email protected] Osama A. Mohammed, [email protected] Energy Systems
Solar Power Plant Design and Interconnection
Solar Power Plant Design and Interconnection Wind & Solar Super Session July 27, 2011 E.H. Camm, S.E. Williams S&C Electric Company Outline Introduction Utility-scale PV power plant Grounding Reactive
PV INTEGRATION ON AUSTRALIAN DISTRIBUTION NETWORKS
PV INTEGRATION ON AUSTRALIAN DISTRIBUTION NETWORKS Literature Review By The Australian PV Association September 2013 Author: Ben Noone, Centre for Energy and Environmental Markets, University of NSW ACKNOWLEDGEMENTS
SDG&E Electric Distribution System Interconnection Handbook. <Revised as of 10/21/2015>
TABLE OF CONTENTS 1 Introduction... 1 1.1 Purposes... 1 1.2 Applicability and Related Tariffs... 1 1.3 Interconnection Agreement Required... 1 1.4 Technical Requirement... 1
DG Modeling Challenges & Results. Jens Schoene
DG Modeling Challenges & Results Jens Schoene December 13, 2013 2 Outline PV Caused Issues on Distribution Systems Modeling Challenges Case Study 3 PV Caused Issues on Distribution Systems 4 Potential
Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014
1 Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables Bob Yinger Southern California Edison April 15, 2014 Southern California Edison SCE provides power to: Nearly
Distributed Generation and the Impact on a Distribution System. Brian Lassiter Technical Sales Engineer
Distributed Generation and the Impact on a Distribution System Brian Lassiter Technical Sales Engineer Company Overview Founded in 1989 in Abilene, TX Industry leader in Engineering and Operations Utility
TERMS AND CONDITIONS
Virginia Electric and Power Company TERMS AND CONDITIONS XXIV. GENERATOR INTERCONNECTION STANDARD Electric generator interconnection service includes only the ability to interconnect an electric generator
ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe
NETWORKS ESB Networks Response to ERGEG Consultation on Voltage Quality Regulation in Europe Date: 22 February 2007 Distribution System Operator ESB Networks Page 1 of 12 Contents 1.0 INTRODUCTION...3
Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE
Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements
HIGH VOLTAGE CALCULATIONS / EVALUATIONS. West Virginia Office of Miners Health, Safety & Training
HIGH VOLTAGE CALCULATIONS / EVALUATIONS West Virginia Office of Miners Health, Safety & Training Helping You To Work More Safely In The Mining Industry DISCLAIMER The West Virginia Office of Miners Health,
Audit Report Rottnest Island 2015 Network Quality and Reliability of Supply Performance Audit - Operation of Compliance Monitoring Systems
ABN 20 009 454 111 Rottnest Island 2015 Network Quality and Reliability of Supply Performance Audit - Operation of Compliance Monitoring Systems Telephone: +61 8 9260 0003 Fax: +61 8 9225 7447 E-Mail:
Power Quality Standards for Electric Service
Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as
Customer connection enquiry form (For the connection of loads and generators)
Customer connection enquiry form (For the connection of loads and generators) Please provide as much detail as possible to ensure TasNetworks can meet your requirements. When completed please attach and
VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES
VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES C. Schwaegerl*, M.H.J. Bollen, K. Karoui #, A. Yagmur + *Siemens AG, # Tractebel STRI AB
Integration Capacity Analysis Workshop 11/10/15 California IOU s Approach
Integration Capacity Analysis Workshop 11/10/15 California IOU s Approach READ AND DELETE For best results with this template, use PowerPoint 2003 10 November 2015 Background and Importance of ICA Definition:
Distributed Generation: Feeder Hosting Capacity. Dean E. Philips, P.E. FirstEnergy Service Corp Manager, Distribution Planning & Protection
Distributed Generation: Feeder Hosting Capacity Dean E. Philips, P.E. FirstEnergy Service Corp Manager, Distribution Planning & Protection Distributed Generation: Feeder Hosting Capacity Factors that contribute
FIT TIER 2 Application
FIT TIER 2 Application Application Information The below information Auto-Fills from your registration information: Building Permit Application Date: Project Completion Date: Name: Address: City: State:
Advanced Protection of Distribution Networks with Distributed Generators
Date:- 8 10 March 2011 Venue: University of Manchester EES-UETP Course title Advanced Protection of Distribution Networks with Distributed Generators Peter Crossley Director of the Joule Centre School
ABB central inverters PVI-55.0/110.0 - PVI-165.0/220.0 - PVI-275.0/330.0 55 to 330 kw
Solar inverters ABB central inverters PVI-55.0/110.0 - PVI-165.0/220.0 - PVI-275.0/330.0 55 to 330 kw ABB s central inverters are extremely scalable, modular-inverter systems that are based on 55kW modular
Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile
Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile Michael Coddington National Renewable Energy Laboratory Golden, Colorado,
MicroFIT Connection Application Guidelines
MicroFIT Connection Application Guidelines These guidelines serve to ensure the efficient processing and implementation of your project. Please read and follow them carefully and completely in order to
NET METERING SUB-CODE. for Connecting Renewable Energy Generating Systems to the Distribution Network in Ghana
for Connecting Renewable Energy Generating Systems to the Distribution Network in Ghana JANUARY 2015 1 Table of Contents PART A: BACKGROUND... 1 1 Introduction... 1 1.1 Objective... 1 1.2 Status... 1 2
Distributed Generation Interconnection Manual
Distributed Generation Interconnection Manual Public Utility Commission of Texas Prepared by: Distributed Utility Associates Endecon Engineering 1062 Concannon Blvd. 347 Norris Court Livermore, CA 94550
Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply. www.siemens.com/siestorage
Totally Integrated Power SIESTORAGE The modular energy storage system for a reliable power supply www.siemens.com/siestorage Totally Integrated Power (TIP) We bring power to the point. Our products, systems,
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
Technical Requirements for Renewable Energy Systems Connected to the Low Voltage (LV) Network via Inverters
Technical Requirements for Renewable Energy Systems Connected to the Low Voltage (LV) Network via Inverters Specification Number: HPC-9FJ-12-0001-2012 CONTENTS 1 Introduction... 6 1.1 Context... 6 1.2
Context: significant penetration of DG = increased risks for system security
Distributed Generation: towards an effective contribution to power system security IEEE Tampa GM 2007: Panel on Impact of Dispersed Generation on Power System structure & security Bruno Meyer Outline Context:
Interconnection of Generators to EDI s Distribution System
Interconnection of Generators to EDI s Distribution System May 22, 2002 This document sets forth the guidelines for connecting a power producing facility to the Alberta Interconnected Electric System through
Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection
Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection (See ARSD chapter 20:10:36 for the requirements for a Tier 2, Tier 3, or Tier 4 Interconnection.) Applicant/Interconnection
Simulation of Cable Overloading Problem on a University Distribution System
Advance in Electronic and Electric Engineering. ISSN 2231-1297, Volume 3, Number 6 (2013), pp. 765-770 Research India Publications http://www.ripublication.com/aeee.htm Simulation of Cable Overloading
Three phase connection
Three phase connection with SUNNY MINI CENTRAL Contents The inverters of the Sunny Mini Central product family have been especially conceived for their use in threephase feed-in systems. This technical
Step Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS
3-PHASE LOW VOLTAGE NETWORK LOAD BALANCER : A COST EFFECTIVE SOLUTION TO LINE VOLTAGE VARIATIONS Pierre FRISTOT Olivier CONSTANT Catherine MONCET Omegawatt - France Omegawatt - France SDET - France [email protected]
EEL303: Power Engineering I - Tutorial 4
1. Determine the voltage at the generating station and the efficiency of the following system (Figure 1): Both transformers have ratio of 2kV/11kV. The resistance on LV side of both Figure 1: transformers
PSS SINCAL - Overview -
PSS SINCAL - Overview - PTI Day Buenos Aires, October 19/20, 2010 Dr. Michael Schwan,, Siemens PTI (Germany) www.siemens.com/energy/power-technologies PSS SINCAL Overview Page 3 Network Calculation Software
SCE Experience with PV Integration
SCE Experience with PV Integration EPRI High Penetration PV Grid Integration Workshop April 19, 2012 Tucson, AZ Leading the Nation in Renewable Power Delivery Actual 2010 Renewable Resources 14.5 billion
ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw
Solar inverters ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw PV energy, combined with energy storage systems, can help increase self-consumption and energy selfsufficiency*. One of the biggest challenges
Queensland Australia Smart Grid Trials
Queensland Australia Smart Grid Trials Grahame Foulger Director SmartGrid Partners [email protected] +61419502980 Company or Institution Logo 4 th International Conference on Integration
Inverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
Physical Address: City: State: Zip Code:
Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection (For Small Generator Facilities with Electric Nameplate Capacities of 10 MW and less) Applicant Contact
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
Power Electronics Testings
Power Electronics Testings PV Inverter Test Solution www.chromaate.com Turnkey Test & Automation Solution Provider w w w.chromaate.com A PV system is an energy system which directly converts energy from
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
SHE Transmission. 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015
SHE Transmission 2015_10_30 Transmission Losses Strategy Rev 2.0 October 2015 Summary This paper presents SHE Transmission s views and approach on the impact of transmission losses on the transmission
APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.
USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS Abstract This application note describes the necessary procedure to use a standard Pacific Power Source Model
PSEG-LONG ISLAND SMART GRID SMALL GENERATOR INTERCONNECTION SCREENING CRITERIA FOR OPERATING IN PARALLEL WITH LIPA S DISTRIBUTION SYSTEM
PSEG-LONG ISLAND SMART GRID SMALL GENERATOR INTERCONNECTION SCREENING CRITERIA FOR OPERATING IN PARALLEL WITH LIPA S DISTRIBUTION SYSTEM PSEG-LI SGSGIP DG Screening Criteria 5-29-14 Table of Contents I.
Final. TNB Technical Guidebook on Grid-interconnection of Photovoltaic Power Generation System to LV and MV Networks
TNB Technical Guidebook on Grid-interconnection of Photovoltaic Power Generation System to LV and MV Networks Final 1 Contributors Many individuals have made contributions to the Guidebook. However, the
Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM. Technical Note No. 7 August 2003
Technical Note No. 7 August 2003 Power Quality Centre VOLTAGE FLUCTUATIONS IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses voltage fluctuations, their causes and adverse effects, what levels
INFORMATION DOCUMENT
INFORMATION DOCUMENT For Design, manufacture, supply, installation and commissioning of different capacity Roof top Solar PV Power projects under Net Metering policy in the state of Punjab. PUNJAB ENERGY
Electricity Meter in the age of Photovoltaic
Electricity Meter in the age of Photovoltaic Avi Lugassi Introduction In this article we will learn how the electronic Energy Meter can deal with the massive penetration of renewable Photovoltaic energy
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems
LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems A. General This Net Metering Standard for Customer-Owned Grid Connected Electric Generating Systems sets forth the
Unitil Energy Systems, Inc. Interconnection Standards For Inverters Sized Up To 100 kva
Unitil Energy Systems, Inc. Interconnection Standards For Inverters Sized Up To 100 kva Issued: August 2009 SIZED UP TO 100 KVA TABLE OF CONTENTS 1.0 Introduction... 1 1.1 Applicability... 1 1.2 Definitions...
VOLUME 1 FINAL. Energex. Distribution Annual Planning Report. 2014 / 2015 to 2018 / 2019. Energex DAPR 2014/15 2018/19 Volume 1
VOLUME 1 FINAL Energex Distribution Annual Planning Report 2014 / 2015 to 2018 / 2019 Energex DAPR 2014/15 2018/19 Volume 1 Version Control Version Date Description 1.0 30/09/2014 Final version for publication
Advanced Inverter Overview
Advanced Inverter Overview Renewables on the Distribution Grid Minnesota Public Utilities Commission April 11, 2014 Lise Trudeau Senior Engineering Specialist Minnesota Department of Commerce Division
SA Power Networks Network Tariffs - Residential APPLIES TO USAGE FROM 1 JULY 2015
SA Power Networks Network Tariffs - Residential Low Voltage Residential - Single Rate DUOS excl TUOS excl PV JSO excl Total excl Total incl Block 1 Usage Rate $/kwh First 333.3 kwh/mth 0.0745 0.0300 0.0130
SA Power Networks Planning for Solar PV? Customer information guide to network connected solar PV inverter systems
SA Power Networks Planning for Solar PV? Customer information guide to network connected solar PV inverter systems Contents Introduction 3 How solar PV power systems work 4 Solar modules 5 Is solar power
Connecting to the network information pack Version 2
Connecting to the network information pack Version 2 Updated: Contents 1.0 What is a new connection or connection alteration?... 3 2.0 Connection enquiry... 3 3.0 Connection application... 3 3.1 Processing
Modeling and Testing of Unbalanced Loading and Voltage Regulation
National Renewable Energy Laboratory Innovation for Our Energy Future A national laboratory of the U.S. Department of Energy Office of Energy Efficiency & Renewable Energy Modeling and Testing of Unbalanced
GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta
GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for
NORTHERN IRELAND ELECTRICITY Ltd STATEMENT OF CHARGES FOR USE OF. THE NORTHERN IRELAND ELECTRICITY Ltd ELECTRICITY DISTRIBUTION SYSTEM
NORTHERN IRELAND ELECTRICITY Ltd STATEMENT OF CHARGES FOR USE OF THE NORTHERN IRELAND ELECTRICITY Ltd ELECTRICITY DISTRIBUTION SYSTEM BY AUTHORISED PERSONS Effective from 1 October 2011 to 30 September
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor
Transfer Equipment Controls
Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment
Introduction. Harmonics and IEEE 519 Page 1 of 19
Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms
TABLE OF CONTENTS 1.0 INTRODUCTION... 2 1.1 PURPOSE... 2 1.2 DEVIATION... 2 4.0 INTERTIE PROTECTION REQUIREMENTS... 4
Page: 1 of 14 KEY BULLETIN POINTS: THIS GUIDE OUTLINES MINIMUM REQUIREMENTS FOR CONNECTION OF CUSTOMER-OWNED EMERGENCY AND STANDBY (ESG) TO THE GEORGIA POWER COMPANY (GPC) DISTRIBUTION SYSTEM. THESE ARE
Key Concepts Of Distributed Generation
Key Concepts Of Distributed Generation National Grid - April 29, 2015 International Association of Electrical Inspectors Western Massachusetts Chapter - Springfield MA Bob Moran, Jim Kehrer, Patti Cox,
Executive summary 2. 1 Introduction 4
Flexible Networks for a Low Carbon Future Future Network Monitoring Strategy September 2015 Contents Executive summary 2 Glossary 3 1 Introduction 4 2 Fundamental principles of monitoring 5 2.1 LCT monitoring
Dakota Energy Cooperative, Inc. POLICY STATEMENT
Dakota Energy Cooperative, Inc. POLICY STATEMENT Subject: Member Owned Small Renewable Energy Policy No. 57 Rate and Interconnection Requirements Issue Date: May 21, 2008 Revised Date: December 16, 2014
0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N
55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils
FUNCTIONS AND CAPABILITIES OF PV INVERTERS TO BE PART OF A SMART GRID
FUNCTIONS AND CAPABILITIES OF PV INVERTERS TO BE PART OF A SMART GRID As the number of decentralized energy generators grows, also the need for an intelligent power grid rises. In the Smart Grid of the
Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE
Local Area Networks (LAN) Servers Data centers Internet centers (ISP/ASP/POP) Industrial PLCs EPOS (Electronic Point of Sale) Systems Emergency devices (lights/alarms) Electro-medical devices Telecommunication
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
Operating the power system while enabling more renewables : which solutions?
Operating the power system while enabling more renewables : which solutions? Sébastien GRENARD EDF R&D 22/06/2010 New environment for power systems design and operation European targets and attractive
About Southern California Edison
About Southern California Edison One of the nations largest investorowned utilities with 125 years of service. Service Area 50,000 square miles Over 430 cities and communities Population Served Nearly
RENEWABLE ENERGY INFEED R Herman, M Malengret and CT Gaunt University of Cape Town, South Africa
RENEWABLE ENERGY INFEED R Herman, M Malengret and CT Gaunt University of Cape Town, South Africa Technology and tariffs for renewable energy in-feed at LV and MV Ron Herman : Performance of LV feeders
Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems
Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems This Agreement is made and entered into this day of, 20, ( Effective Date ) by and between the Orlando Utilities Commission
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is
How To Understand The Electrical Power Supply Of A Power Supply System
17 Circuit diagram symbols E 18 CIRCUIT DIAGRAM SYMBOLS electrical network elements three-phase line or cable single-phase line or cable short circuit earth electrode outgoing feeder supply incoming feeder
ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1
ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1 Design and Planning Specification for New Low Voltage Installations for Housing Developments 1. SCOPE This appendix to ENA
3. TYPES OF SERVICE AVAILABLE. 3.1 Scope
3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service
EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID
Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group
Supply Standards: Electricity Supply Standard July 2011 4 JULY 2011 ISSUE 6 UNCLASSIFIED UNCONTROLLED COPY IF PRINTED
s: Electricity Supply Standard July 2011 4 JULY 2011 ISSUE 6 OPERATIONAL PROCEDURE - s: Electricity PREPARED BY: Power Quality Manager AUTHORISED BY: General Manager Network Support DOCUMENT NUMBER: -
T 3000. Substation Maintenance and Commissioning Test Equipment
T 3000 Substation Maintenance and Commissioning Test Equipment Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
TRANSMISSION SERVICE RATE SCHEDULE Effective from 1 April 2015
TRANSMISSION SERVICE RATE SCHEDULE Effective from 1 April 2015 A SERVICE CONNECTION CHARGES Note : All charges in this Schedule are exclusive of GST. 1 Service Connection This includes cables, associated
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
AUSTIN ENERGY INTERCONNECTION GUIDE FOR CUSTOMER-OWNED POWER PRODUCTION FOR FACILITIES UP TO 10MW A INTERCONNECTION CLASSIFICATIONS...
AUSTIN ENERGY INTERCONNECTION GUIDE FOR CUSTOMER-OWNED POWER PRODUCTION FOR FACILITIES UP TO 10MW TABLE OF CONTENTS PAGE INTRODUCTION... 4 A INTERCONNECTION CLASSIFICATIONS... 5 B. APPLICATION PROCESS
Network Price List and Explanatory Notes
Essential Energy Network Price List (Excluding GST) Effective 1 July 2014 Tariff Code Obsolete tariffs on same rate Description Network Energy Energy Energy Energy Energy Energy Energy Peak Shoulder OffPeak
Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
PG&E Transmission Interconnection Handbook. Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES
Section L3: SUBSTATION DESIGN FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES PURPOSE This section provides substation design information for Load Entities interconnected at transmission voltage