Data center power dynamics within the settings of regional power grid
|
|
|
- Norma Atkins
- 10 years ago
- Views:
Transcription
1 Data center power dynamics within the settings of regional power grid Gulnara Zhabelova 1, Alireza Yavarian 1, Valeriy Vyatkin 1,2 1 Department of Computer Science, Electrical and Space Engineering Lulea University of Technology, Lulea, Sweden 2 Department of Electrical Engineering and Automation, Aalto University, 02150, Helsinki, Finland [email protected], [email protected], [email protected] Abstract Data centers have grown to become big energy consumers, comparable to traditional industries. At this scale of power consumption, data centers play considerable role in electric networks operation. However, being a relatively new industrial scale consumer, data center requires more careful consideration and research to uncover its specifics and better understand its requirements; and investigate data center s impact on regional grid. Data centers have proven to be not just a collection of computers, but rather complex infrastructure with complex dynamics and subsystem dependencies. This paper reports on the work in progress and at this stage details an effort to understand the impact of dynamic server load of a data center on its power infrastructure and further on the grid; the effects of transient faults in power grid on performance of a data center. This will help regional grid operators to improve power balancing within the network to maintaining network stability avoiding failures and blackouts. The results of this work will be used in developing dynamic power balancing strategy for a smart grid containing large data centers. Keywords data center; power quality; power factor; data center efficiency; data center model; transient fault; power system. I. INTRODUCTION Within the last decade, data centers have become a part of everyday life for many people. Internet and computing technologies have enabled so called online era bringing new ways of interactions and re-inventing old. Social media has grown, connecting people throughout the world and enabling fast information exchange (e.g. disaster warnings, fund raising etc.). Retailers and customers across the world engage via online shopping. , online storage, online video and music streaming, online games, and many other over the internet services are continuing to shape modern societies. Internet connectivity has become a must requirement for businesses of any size and occupation. Companies use servers for s, storage, communication, databases, intensive computations, custom application hosting and many other internet services depending on business needs. Moreover, business requirements demand highly reliable and available data centers. This global growth in over the internet service drives service providers to search for bigger, more powerful and efficient datacenters. As a result, a number of servers and data centers throughout the world grows. That results in large data centers, aggregated power consumption of which is becoming an issue [1][2]. Data centers have grown to become big energy consumers, comparable to traditional industries. Facebook total energy use in 2013 made up 822M kwh, and this trend is rising: energy consumption grew from 532M kwh in 2011 to 704M kwh in 2012 [3]. As any other industrial consumers, at this scale of power consumption, data centers play considerable role in electric networks operation. Regional network operators have to account for data center load and its fluctuation in their short and long term network planning. Furthermore, as high-tech industrial consumer, data center demands stable, reliable and highly available power with good quality. However, being a relatively new industrial scale consumer, compared to traditional industry such as steel production and mining, data center requires more careful consideration and research to uncover its specifics and better understand its requirements; and investigate data center s impact on regional grid. This will help regional grid operators (RGO) to improve power balancing within the network to maintaining network stability avoiding failures and blackouts. Understanding the consumer will facilitate RGOs to efficiently utilize available power and resources in the network, and better accommodate customer requirements. This paper investigates data center dynamics and mutual effect of data center and regional grid. This paper is an effort to understand the dependencies of data center power infrastructure on the utilization of the IT equipment; the effects of power instability on performance of data centers; the impact of data center activity on power networks. Data centers have proven to be not just a collection of computers, but rather complex infrastructure with complex dynamics and subsystem dependencies. Data center s IT equipment is sensitive to the variations and spikes in voltage, current and frequency of the supplied power [4]. At the same time power grid has known issues of power quality, voltage and frequency variations which might lead to system instability. Poor power quality supplied to the critical load can affect performance of the equipment and even damage it. Moreover, data center is a relatively volatile load. The power consumption not only depends on a number of servers used in the facility, but also on workload of an individual server. The power consumed by a server on a light to heavy load can vary up to 100% [5]. IBM BladeCenter HS20 Full Chasis 14 blades server consumes 2.16 kw of power on low server utilization and up to 4.05 kw on high utilization [5]. The
2 higher is the workload on the servers, the more heat is generated. This heat needs to be removed and servers need to be cooled down and kept at the operational temperatures. This requires an entire cooling infrastructure which in turn consumes power to operate. Therefore, the variation in workload on the servers translates into the power consumed by the data center and the fluctuations of power in the regional grid. At the same time the workload on the servers is relatively hard to control. The workload depends on the behavior of the end users, for example, users of the social media. The behavior of the business users is relatively predictable, as they often are active during the office hours. However, with the trend of flexible hours and home offices, that is changing as well. The main contribution of the paper is detailed below: We show the effect of transient fault in regional power network on data center dynamics. During transient period, servers are shield by the uninterruptable power supply (UPS). In an effort to understand boundaries of safe operation, we show that capacity and state of charge of UPS play crucial role in protecting data center from transient faults (section IV). We show data center dynamics, e.g. the effect of power factor (PF) of IT equipment on power loss and hence the efficiency (section IV). This contributes towards understanding data center dynamics and further consideration of data center as an industrial consumer. We demonstrate that by building the data center model described in section III and simulating developed use cases (section II) imitating various conditions within the power network and data center (section IV). II. USE CASES A. Data center and regional grid: transient fault condition This scenario studies effect of transient faults such as oneand three-phase earth faults. Transient fault is the fault which is no longer present in the power network. Consider sample distribution feeder as shown in Figure 1. The model is based on the IEEE 13 node test feeder model [9]. The fault is simulated near the data center location. Protection scheme of the distribution network clears the fault typically within 2-3 cycles [10]. This period of 40 ms 60 ms is enough to create voltage and current sag. These short transient conditions will not damage equipment, however, may cause malfunctioning of server components, such as hard drive and memory, which can result in corrupted data. In order to compensate for the voltage sag, IT equipment will draw more current to maintain required power levels. However, when both current and voltage levels drop, then equipment cannot obtain required power levels. Acknowledging this, IEEE standard defines recommended practice for voltage sag for electronic equipment [11]. The voltage should be more than 50% of nominal voltage in a 200 millisecond time period [11]. UPS is used to dampen these voltage and current variations within the allowed range. Figure 1. Sample regional distribution network based on IEEE 13 node test feeder [9]. There are several UPS configuration used in data centers. Most data centers have configuration of N+2, 2N, 2N+1 [12]. N denotes the power capacity required to feed the protected equipment. This implies that UPS configurations carry extra capacity to provide highest reliability up to % [12]. UPS batteries with full charge provide safe operation for critical loads even under the short power interruptions. However, we want to investigate the boundaries of safe operation considering limits of protecting equipment: what is the safe minimum charge of UPS batteries? Additionally, knowing safe limits of UPS batteries is useful for demand response applications in a smart grid environment. Data center can participate in the power balancing mechanisms of the grid operators and provide ancillary services. The capacity of UPS configuration is designed to take on critical load at its peak. Hence, data center can get disconnected from the grid and move to UPS supply for a short period of time, sufficient to help network operators to meet reliability standards. To perform these types of demand response actions, data centers should be aware of boundaries of safe operation e.g. minimum UPS capacity and limitations of protection devices. This scenario investigates the effect of transient fault in the distribution feeder on to the data center IT equipment under various levels of UPS state of charge. B. Data center dynamics: power factor of critical load IT equipment has dynamic PF. During the data center life span, IT equipment gets changed, updated and often new more powerful devices are installed. This may impact the total PF of the server room. Also, PF of the server power supply changes with the load [6]. The Figure 2 shows the relation between power factor and load in the server HP DL360 [13]. The lower the load is, the lower the PF. At 10% load on the server, its PF drops to 0.8. Servers often operate at medium to low load and occasionally reach their peak load [7]. This constantly evolving IT load affects PF. Low PF affects power quality in the electrical distribution network of data center. PF is a ratio of true power to apparent
3 power, i.e. ratios between consumed power (useful power) and absorbed power (total power). True power PF = Apparent power The circuit containing reactive components (inductive and capacitive) has PF<1. This means that the circuit wiring (cables) have to carry more current to deliver the same amount of true power than in the circuits with no reactance. The reactive power dissipates in the circuit. Higher current in the wiring means more lines losses and require equipment with higher capacity. Poor PF results in an inefficient power delivery system [14]. Figure 2. IT load to power factor curve of HP DL360 server [13]. Data centres, as industrial facilities, will be charged penalty by the network operators, if their PF is much different from 1. The correction of PF of thousands of servers can be done individually or aggregated in power distribution units (PDUs). Power factor depends on reactive power (inductive or capacitive). The reactive power in data centre power infrastructure can be compensated using special equipment such as compensators. Additionally, power quality is affected by non-linear loads, which draw a distorted waveform that contains harmonics. Harmonic is a higher order frequency (e.g. 100Hz, 150Hz, 200 Hz) current and voltage distortion of fundamental waveform (50 Hz) [15]. Added together they produce distorted waveform. Electronics equipment can behave as a non-linear load, due to their switching power supplies [14][15], which exhibit lower PF. The main issue of harmonic distortion, besides the energy waste, is overheating of equipment or conductors [14]. To limit the harmonic injection into AC mains, many computer vendors developed PF corrected (PFC) power supplies. Main goal of PFC is to bring PF as close as possible to 1. In this scenario the effect of various PF of IT load on data center power dynamics (power quality) is investigated. It is important to understand the mutual effects of various subsystems, designed as an independent arrangements, however, working together within one facility. III. SIMULATION MODEL For the simulation of the above scenarios, data center model was developed. The power infrastructure of a data center consists of several main building blocks, which is common for all data center such as utility transformer, automatic transfer switch (ATS), switchgear, UPS, backup generator, power distribution units (PDU), cooling system and servers. Figure 3 shows developed model. The critical load consists of IT equipment such as servers, network and storage devices, and modeled as RLC load of 105 kw. This power capacity was estimated using HP Power advisor calculator [8], by modeling 6 racks of BL460c Gen8 blade servers (384 servers) and 4 racks of network and storage devices. Critical load changes during the day, as the server utilization and load on other IT equipment follows the endusers behavior pattern. IT load needs to be protected from the fluctuations in the utility power and power failure and therefore power is supplied via UPS. UPS model contains battery with charge and discharge curves of Li-Ion battery. It is important to correctly select capacity of the UPS battery, since it has to be able to supply peak critical load when utility power fails. UPS contains AC/DC and DC/AC converters, thus filtering out voltage and frequency fluctuations present in incoming utility power. The developed model has tier III 2N+1 UPS configuration. The power from UPS is distributed and delivered to the servers and other equipment by the PDUs. PDUs also step down the voltage to the right level for the equipment. In our model, each PDU unit consists of a transformer with capacity of 500 kw and rating 480/208 V, fuses as protection devices and miniature circuit breakers. The lighting loads have fixed power; they constitute nonessential loads and connected to the substation via PDU. The size of lighting loads is kw, calculated according to the method described in [4], taking into account size of the server room (3m 10m 5m). The motor of fans and pumps of cooling Figure 3. Model of a typical data center, developed in Matlab Simulink.
4 system are the essential loads; a 72 kw induction motor is considered as the aggregated cooling fan load and another 72 kw is modeled as equivalent RLC load. The distribution network shown in Figure 1 for the purpose of this exercise is modeled as Three phase source block with large capacity. The power is stepped down by the power transformer, modeled as 2-winding transformer with configuration parameters of capacity 2MVA and rating 145 kv/0.48 kv. The data center model has 500 kva standby generators set. The generators provide backup power in case of utility failure. ATS has an interlock; when the utility is not available ATS disconnects the utility and connects the generators set to data center power infrastructure. UPS batteries allow time for standby generators to start up, and pick up the critical load in order to keep the power uninterrupted. The Table 1summarizes the parameters of the data center model. TABLE 1. DATA CENTER PARAMETERS. Item Size (kw) Critical load 105 Lighting Cooling load (induction motor) 72 Cooling load (RLC load) 72 Standby generator set 500 kva UPS 262 IV. SIMULATION AND RESULTS A. Simulation of a transient fault The simulation was carried out in Matlab Simulink. Simulation model is shown in Figure 3. Three cases are considered with UPS at 20%, 50% and 100% of its statement of charge. One- and Three-phase earth faults are simulated close to the data center, using Three phase fault block. The fault is injected at 0.15 sec. The protection scheme clears the fault within 50 ms, and transient conditions end at 0.2 sec. The transient behavior of current and voltage of data center is then studied. Figure 4 and Figure 5 show current and voltage of critical loads under one-phase fault respectively. At 0.15 sec current and voltage drop in all three cases. However, UPS at full capacity prevents dramatic power dip and controls the power level at 9% of initial value. Figure 4. Transient of critical loads: current curve under 1-phase earth fault. UPS with 50% and 20 % of charge allow the voltage to keep falling till 0.18 sec where is stabilizes at around 180 V (Figure 5). The power dip in first case is 13% and in the second case is 15%. Thanks to the extra capacity of the UPS (2.5N, where N is 105 kw), the conditions of the transient fault do not threaten the stability of the data center and do not reach dangerous level to damage equipment. The voltage and current levels are well above IEEE standard. Figure 5. Transient of critical loads: voltage curve under 1-phase earth fault. The results of this simulation show that data center, even at low UPS capacity, can well safely endure transient one phase earth fault. After three phase earth fault, the similar transient behavior is exhibited by current and voltage as depicted on Figure 6 and Figure 7 correspondingly. At 0.15 sec power starts falling and by 0.17 sec all three configurations of the UPS manage to stabilize the power. However, the drops are lower. UPS with 100% charge allows voltage and current to drop to about 10% of their nominal values. The UPS with 50% and 20% of charge lets the sag to reach 14.5% and 16% respectively. Even under transient three-phase earth fault, the levels are still within the recommended IEEE limits.
5 Figure 6. Transient of critical loads: current curve under 3-phase earth fault. Figure 8. Current of incoming power transformer under various PF of critical load: (a) PF=0.8, (b) PF=0.9, (c) PF=0.91, (d) PF=0.98. Figure 7. Transient of critical loads: voltage curve under 3-phase earth fault. The simulation demonstrates that large UPS capacity and its batteries state of charge is important for safe operation of the data center. Up to 80% of the UPS battery charge can be exploited in demand response applications without threatening reliable operation of the data center. UPS battery can be charged in the period following the demand response action when price of electricity is lower. The decision to provide ancillary services needs to take into account risk of resulting low UPS charge, prediction of data center server utilization and other parameters such as required availability. B. Power factor of critical load The simulation is carried out in Matlab Simulink, using the model depicted in Figure 3. The state of UPS battery charge is taken at 70%. The size of critical load is changed according to the curve depicted on Figure 2. The several simulations are carried out with the PF of 0.8, 0.9, 0.91 and The results of simulation show that the PF of IT equipment has significant effect on the current and voltage harmonics as depicted on Figure 8 and Figure 9 respectively. Figure 9. Voltage of incoming power transformer under various PF of critical load: (a) PF=0.8, (b) PF=0.9, (c) PF=0.91, (d) PF=0.98. At the highest PF=0.98, harmonics of current and voltage waveforms are reduced to the minimum (Figure 8, d and Figure 9,d). As a result data center with high PF will have less power loss and more efficiency, providing high quality power. There is a noticeable degradation of power quality from PF 0.98 to 0.91 and lower. Servers in data center rarely work at full utilization, i.e. 100% capacity. Typically servers operate at medium utilization [7], exhibiting PF<1. This results in increased power loss, heating of cables and contributes to reduced data center efficiency. Moreover, these harmonic distortions can have effect on power transformer connecting data center to the grid, and therefore on the regional grid. Thus, dynamic PF of data center, fluctuating following server utilization, affects the power grid. It is important for data center to keep PF as close to 1 as possible throughout the life span of the facility and daily server load. These results will be taken into consideration when developing dynamic power balancing strategy for the regional networks containing large data centers. Data centers need to monitor their PF while participating in demand response actions, providing ancillary services by either shedding their load or compensating for reactive power.
6 CONCLUSION This paper presents a study on data center power dynamics within the settings of regional grid. The challenging task was developing appropriate models of a data center considering dynamics of various subsystems within the facility. Simulation shows the importance of UPS battery in the events of transient faults occurring in the supplying power network. Proper sizing of UPS system can ensure reliable operation of the data center. Moreover, UPS may unlock the potential of a data center to provide ancillary services for regional network operators. The paper also studied effect of power factor on the power loss and data center efficiency. Understanding boundaries of safe operation of a data center and its potential is necessary in power management of future smart grid and in automation of data centers themselves. Immediate future work is to further improve developed models to include dynamic load profile reflecting end user behavior, to extend model of the essential loads considering complete cooling system and to model IEEE 13 node feeder as a regional network. Building on these results, the next step will be developing an optimal dynamic power balancing strategy for RGO with several data centers and distributed generation. This is an important topic relating to stability and reliability of the grid. REFERENCES [1] Greenpeace. (2011). Greenpeace Likes Facebook s New Datacenter, But Wants a Greener Friendship [Online]. Available: new- datacenter- but-wants-a-greener-friendship. [2] J. Koomey. (2011, Aug. 1). Growth in Data Center Electricity Use: 2005 to 2010 [Online]. Available: [3] Facebook. Green on Facebook. Internet/Software. 2014; Available from: [4] R. Sawyer, Calculating total power requirements for data centers, APC white paper 3 [5] J. Spitaels. Dynamic power variations in data centers and network rooms, APC whilte paper 42, Schnider electric data center science center, Available from 5TNRK4/SADE-5TNRK4_R3_EN.pdf?sdirect=true [6] N. Rasmussen, (2014). Impact of leading power factor on data center generator systems, white paper 200, Schneider electric Data center science center, [7] M. D. Hill. (2009). The Datacenter as a computer: An introduction to the design of warehouse-scale machines in Synthesis lectures on computer architecture, lectuer 6, Morgan&Claypool, ISSN [8] Hewlett-Packard development Company, L.P., Hp Power Advisor [9] IEEE Power and Energy Society (PES), Distribution Test Feeders, ewh.ieee.org/soc/pes/dsacom/testfeeders/index.html [10] T. Ghanbari, E. Farjah, A multiagent-based fault-current limitting scheme for the microgrids, IEEE Transactions on Power Delivery, vol.29 (2), April [11] IEEE Trial-Use Recommended Practice for Voltage Sag and Short Interruption Ride-Through Testing for End-Use Electrical Equipment Rated Less than 1000 V, IEEE Std , vol., no., pp.1,92, Sept [12] K. McCarthy, V. Avelar, Comparing UPS system design configurations, APC white paper 75, Schneider electric Data center science center, [13] D. Fiedler. (2013)."Server Power Factor: Thoughts on Bridging IT- Facilities Conversations", The Data center journal, URL: [14] Universal Electric Corporation. (2013). Starline: Neutral ratings for power distribution systems in the data center, [15] M. Glinkowski, L. Simmons, D. Loucks and etc., Data center power system harmonics: an overview of effects on data center efficiency and reliability, whilte paper, Schneider electric Data center science center,
Data center energy efficiency and power quality: an alternative approach with solid state transformer
Data center energy efficiency and power quality: an alternative approach with solid state transformer Gulnara Zhabelova 1, Alireza Yavarian 1, Valeriy Vyatkin 1,2 1 Department of Computer Science, Electrical
Dynamic Power Variations in Data Centers and Network Rooms
Dynamic Power Variations in Data Centers and Network Rooms By Jim Spitaels White Paper #43 Revision 2 Executive Summary The power requirement required by data centers and network rooms varies on a minute
Dynamic Power Variations in Data Centers and Network Rooms
Dynamic Power Variations in Data Centers and Network Rooms White Paper 43 Revision 3 by James Spitaels > Executive summary The power requirement required by data centers and network rooms varies on a minute
The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity
The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price
Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply. www.siemens.com/siestorage
Totally Integrated Power SIESTORAGE The modular energy storage system for a reliable power supply www.siemens.com/siestorage Totally Integrated Power (TIP) We bring power to the point. Our products, systems,
Selecting a UPS Topology for your Data Center. by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions
Selecting a UPS Topology for your Data Center by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions Uninterruptible Power Supplies (UPS) are both reaching into new markets and expanding in new ways
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
Harmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
Nuclear Power Plant Electrical Power Supply System Requirements
1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, [email protected] Abstract Various regulations and standards require from electrical power system of the
Electrical Network Management System
Electrical Network Management System Optimisation of the electrical network Measure to understand Understand to control Control to optimise Cost of power and fluids Power quality Power availability 2 Improvement
Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION
Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Outline What is Reactive Power and where does it come from? Why is it important?
Power Quality Standards for Electric Service
Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
Engineering innovation
Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
EssPro Energy Storage Grid Substation The power to control energy
EssPro Energy Storage Grid Substation The power to control energy EssPro Grid gives you the power to control energy helping to keep smart grids in balance Maximizing the value and performance of energy
Electrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
Power Factor Correction for Power Systems First Semester Report Spring Semester 2007
Power Factor Correction for Power Systems First Semester Report Spring Semester 2007 by Pamela Ackerman Prepared to partially fulfill the requirements for EE401 Department of Electrical and Computer Engineering
HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM
Technical Note No.3 March 2000 HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses harmonic distortion, its causes and adverse effects, what levels are unacceptable and how
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution
Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution Nandita Dey, Dr.A.K.Chakraborty Lecturer, Electrical Engineering Department, Tripura University Suryamaninagar
PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions
PMCS Integrated Energy Management Solution Unlock the Full Potential of Power Networks Through Integration Power Management Control System (PMCS) is a highly customizable, fully integrated end-to-end Energy
Cahier technique no. 196
Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for
Mitigating data center harmonics
Mitigating data center harmonics Patricia Matwijec Product Manager Eaton Ed Spears Product Marketing Manager Eaton Executive summary Line harmonics can have costly and disruptive effects on electrical
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to
Power Solutions for Data Centers Metering and protection architecture guide
Power Solutions for Data Centers Metering and protection architecture guide The purpose of this guide is to provide technical guidelines to designers and field engineers who specify metering and protection
Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns
Modeling of PV Based Distributed Generator Systems with Diverse Load Patterns Mehmet H. Cintuglu, [email protected], Armando Altamirano, [email protected] Osama A. Mohammed, [email protected] Energy Systems
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International
Technical Comparison of On-line vs. Line-interactive UPS designs
Technical Comparison of On-line vs. Line-interactive UPS designs By Jeffrey Samstad Michael Hoff White Paper #79 Executive Summary UPS systems below 5000VA are available in two basic designs: line-interactive
Common Power Problems & Power Protection Solutions
W H I T E P A P E R Common Power Problems & Power Protection Solutions Executive Summary All systems, from home theaters and office desktops to enterprise IT equipment in data centers, are prone to downtime,
POWER FACTOR CORRECTION
[CATALOGUE PFC-SFC] POWER FACTOR CORRECTION INDUSTRIAL SWITCHGEAR & AUTOMATION SPECIALISTS A component of nhp s green star solution... www.nhp.com.au Power Factor - What does it mean? Where open electricity
Alternative data center power
Alternative data center power A quantitative TCO comparison of 400V AC and 600V AC power systems Abstract Power efficiency has become a critical focus for IT and facilities managers as they struggle to
Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17
Understanding Power Factor, Crest Factor, and Surge Factor White Paper #17 Executive Summary This paper explains the technical terms of Power Factor, Crest Factor, and Surge Factor. The use of these terms
Power Quality. Uninterruptible Power Supply
Quality Uninterruptible Supply In the electrical system environment, power disturbances will occur. These can be caused by faults on the distribution system, the operation of nearby equipment, lightning
Impact of Leading Power Factor on Data Center Generator Systems
Impact of Leading Power Factor on Data Center Generator Systems White Paper 200 Revision 0 by Neil Rasmussen Executive summary IT devices may exhibit electrical input current with a characteristic called
21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
Power Monitoring for Modern Data Centers
Power Monitoring for Modern Data Centers December 2010/AT304 by Reza Tajali, P.E. Square D Power Systems Engineering Make the most of your energy SM Revision #1 12/10 By their nature, mission critical
HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS
White Paper: MIRUS-TP003-A January 15, 2014 HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc.
The Different Types of UPS Systems
The Different Types of UPS Systems By Neil Rasmussen White Paper #1 Revision 5 Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics.
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International
Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE
Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
High-Efficiency AC Power Distribution for Data Centers
High-Efficiency AC Power Distribution for Data Centers White Paper 128 Revision 2 by Neil Rasmussen > Executive summary The use of 240 volt power distribution for data centers saves floor space, simplifies
HP Power Advisor utility: a tool for estimating power requirements for HP ProLiant server systems
HP Power Advisor utility: a tool for estimating power requirements for HP ProLiant server systems technology brief Abstract... 2 Introduction... 2 Key power parameters... 2 Input line voltage... 2 Device
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
UPS Applications and VRLA Battery Sizing
TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the
> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.
The Role of Isolation Transformers in Data Center UPS Systems White Paper 98 Revision 0 by Neil Rasmussen > Executive summary Most modern UPS systems do not include the internal s that were present in
Green Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor
International Journal of Engineering Inventions e-issn: 78-7461, p-issn: 319-6491 Volume 3, Issue 5 (December 013) PP: 36-41 Modelling, Simulation and Performance Analysis of A Variable Frequency Drive
Advanced Protection of Distribution Networks with Distributed Generators
Date:- 8 10 March 2011 Venue: University of Manchester EES-UETP Course title Advanced Protection of Distribution Networks with Distributed Generators Peter Crossley Director of the Joule Centre School
Fronius IG Plus. The next generation grid-connected PV inverter
Fronius IG Plus The next generation grid-connected PV inverter Maximum energy harvest cloudy or clear The first complete inverter solution. Reliable. Proven. Smart. An outstanding addition to the family:
2012 San Francisco Colloquium
2012 San Francisco Colloquium http : //www.cigre.org HVDC and Power Electronic Systems for Overhead Line and Insulated Cable Applications B4-8 Trans Bay Cable A Breakthrough of VSC Multilevel Converters
Designed for uptime. Defining data center availability via a tier classification system
Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center
Considering the effects of UPS operation with leading power factor loads
Considering the effects of UPS operation with leading power factor loads Over the past five years, a new generation of data processing and communications equipment has become prevalent in modern data centers
7. Reactive energy compensation
593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical
ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS
Sawsan Henein AIT Austrian Institute of Technology Electric Energy Systems Research Group SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS Sustainable Places 2015 Savona,
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
Power System Harmonics
Pacific Gas and Electric Company Power System Harmonics What are power system harmonics? Ideally, voltage and current waveforms are perfect sinusoids. However, because of the increased popularity of electronic
Rule 5.500 Fast Track Analysis for National Life Insurance Co.
Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES WHITE PAPER: TW0062 36 Newburgh Road Hackettstown, NJ 07840 Feb 2009 Alan Gobbi About the Author Alan Gobbi Alan Gobbi
Power Quality for Information Technology System
Power Quality for Information Technology System ITS OBVIOUS THE TOLERANCE IS DIFFRENT But What isn t Tobvious? HOW MANY OF YOU HAVE : A COMPUTER AT HOME? = Computers are not screens and Keyboards COMPUTERS
Inverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
Measurement, Modeling and Simulation of Capacitor Bank Switching Transients
Measurement, Modeling and Simulation of Capacitor Bank Switching Transients Mirza Softić*, Amir Tokić**, Ivo Uglešić*** *Kreka - Dubrave e, Dubrave, Bosnia and Herzegovina (e-mail: [email protected]).
Standards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208
Standards in Marine Power Systems APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Need is Driven by Electrification Oasis of the Seas DDG
Power factor correction. An introduction to technology and techniques
Power factor correction An introduction to technology and techniques 2 Contents Understanding power factor 03 Power factor correction 05 Implementing power factor correction techniques 06 Glossary 07 Further
4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS
4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED MEDIUM VOLTAGE
Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms
Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity
Design of electrical power system for a 1000MW nuclear power generating station
Design of electrical power system for a 1000MW nuclear power generating station K Raja, K Yesunadam Dept. of Electrical & Electronics Engineering, Lingaya s Institute of Management & Technology, Vijayawada,
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran [email protected] Seyed Ali NABAVI NIAKI University of Mazandaran
The Different Types of UPS Systems
Systems White Paper 1 Revision 6 by Neil Rasmussen Contents Click on a section to jump to it > Executive summary There is much confusion in the marketplace about the different types of UPS systems and
Control Development and Modeling for Flexible DC Grids in Modelica
Control Development and Modeling for Flexible DC Grids in Modelica Andreas Olenmark 1 Jens Sloth 2 Anna Johnsson 3 Carl Wilhelmsson 3 Jörgen Svensson 4 1 One Nordic AB, Sweden, [email protected].
APPLICATION NOTE USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS. Abstract.
USING A MODEL 3060-MS SERIES AS A REGENERATIVE AC SOURCE FOR PV INVERTER TEST APPLICATIONS Abstract This application note describes the necessary procedure to use a standard Pacific Power Source Model
Green Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
GPS Interfacing of Banediya Feeder (M.P) Using MI Power Software
GPS Interfacing of Banediya Feeder (M.P) Using MI Power Software Swati Paliwal 1, V.K Tayal 2, H.P Singh 3 Assistant professor, Department of Electrical & Electronics Engineering, Northern India Engineering
Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering
Brochure More information from http://www.researchandmarkets.com/reports/2171489/ Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering Description: A forward
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power
The Different Types of UPS Systems
White Paper 1 Revision 7 by Neil Rasmussen > Executive summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics. Each of these UPS types is
By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document
By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document By the Authority Vested By Part 5 of the United States Code 552(a) and Part 1 of the Code of Regulations 51 the attached document has
Equipment Performance Due to Voltage Sags Test Results for Contactor and Induction Motor
DOI 10.7603/s40707-013-0008-5 Equipment Performance Due to Voltage Sags Test Results for Contactor and Induction Motor Surya Hardi, Muhd. Hafizi, Muzamir Isa, Rohana Ismail Abstract This paper presents
Opportunity of Energy Saving in electrical path is lesser as compared to other areas
Data Centre Power Map ` Energy Optimization Techniques Data Center Power Chain Venkat Rao B Country Manager Power Products Data Center Power Draws Cooling About 35 40 % Sources of Energy Waste Fans / Blowers
A Comparison of AC and DC Power Distribution in the Data Center Transcript
A Comparison of AC and DC Power Distribution in the Data Center Transcript Slide 1 Welcome to the Data Center University course on the A Comparison of AC and DC Power Distribution in the Data Center. Slide
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
BU Control Technologies, Decathlon TM Product Overview. ABB in the Data Center Overview
BU Control Technologies, Decathlon TM Product Overview ABB in the Data Center Overview Introduction to ABB ABB is a global leader in power and automation technologies that enable utility and industrial
Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications
W H I T E P A P E R Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications Executive Summary One of the fundamental decisions in the design of data centers, server rooms
System configuration of v-f control with solar PV generator operating at MPPT with a battery storage System
ISSN: 2278 1323 All Rights Reserved 2015 IJARCET 4222 International Journal of Advanced Research in Computer Engineering & Technology (IJARCET) System configuration of v-f control with solar PV generator
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
Asia Pacific Regional Power Quality Seminar 28-31 March 2005, Marriot Putrajaya, Malaysia. Voltage Source Converter based Power Quality Solutions
Asia Pacific Regional Power Quality Seminar 28-31 March 2005, Marriot Putrajaya, Malaysia Voltage Source Converter based Power Quality Solutions Olivier Suter ABB Holdings Sdn. Bhd., Div. APAN Automation
TECHNICAL DESCRIPTION OF THE DISTRIBUTION SUBSTATION REMOTE MONITORING SYSTEM
HELLENIC ELECTRICITY DISTRIBUTION NETWORK OPERATOR S.A. NOTICE OF CALL FOR TENDERS No ND-xxx PROJECT: Pilot Telemetering and Management System for the Electric Power Supply Demand by Residential and Small
A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS
A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS October 22, 2010 Authored by: Kevin Binnie, Senior Product Portfolio Manager ALPHA TECHNOLOGIES LTD. Executive Summary
Green Energy Solutions
Green Energy Solutions Power Electronics for Photovoltaic Inverter Systems 1 Energy Management Product Line-up Energy Management Product Line-up Power Conversion and Stabilization Frequency Converter Static
MEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED
MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED CCG Facilities Integration Incorporated
Typical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com [email protected] Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
Energy Cost Reduction through Load Balancing & Load Shedding
white paper Energy Cost Reduction through Load Balancing & Load Shedding SCR controllers firing in phase angle degrade the power factor while increasing harmonics and electrical noise. A poor power factor
Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications
Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications Copyright Material IEEE Paper No. PCIC-2003-15 Tony Hoevenaars, P. Eng. Kurt LeDoux, P.E. Matt Colosino Member IEEE Member,