1 F R C C FRCC Standards Handbook FRCC Automatic Underfrequency Load Shedding Program Revision Date: July 2003 FRCC Underfrequency Load Shedding Program Modification and Approval Process Requests to modify the FRCC UFLS program should be made to the chairperson of the FRCC Operating Committee (OC). The OC will direct the SWG and other appropriate groups to evaluate the proposed modifications. Final approval of FRCC UFLS program and modifications to the UFLS program rests with the FRCC OC. FRCC Underfrequency Load Shedding (UFLS) Requirements 1. All load serving members of the FRCC must install automatic underfrequency relays which will disconnect 56% of their customer demand in accordance with the following schedule. UFLS Step Frequency - (hertz) Time Delay 1 - (seconds) Amount of Load (% of member system) A B C D E F L M N Cumulative Amount of Load (%) 2. Deviations from the FRCC UFLS schedule must be assessed by the FRCC. Local area changes in the UFLS assignments must be compatible with the overall underfrequency protection for the FRCC. 1 Time Delay = Intentional delay + relay delay + breaker delay 2 FPL has 2/3 of Step A set at hertz as an aid to system stability. This high set Step A is concentrated in the Miami area.

2 3. All load serving members of the FRCC must annually provide the FRCC Relay Task Force with the amount of armed load connected to UFLS relays as a percentage of the entities projected summer peak load. The amount of UFLS in each of the four FRCC load shedding zones shall also be provided to the Relay Task Force. 4. The FRCC Stability Working Group ( SWG ) shall maintain a data base of the UFLS program. Equivalent representations of the UFLS program may be used in this data base provided they are consistent with the overall application of relays in each of the four load shedding zones. 5. The FRCC SWG shall assess the adequacy and effectiveness of the FRCC s UFLS program at least every five years or whenever there are significant changes in system conditions. The SWG shall review FRCC UFLS program requirements and documentation at least every five years. 6. All disturbance conditions involving operation of UFLS relays or frequencies below these relays setpoints shall be evaluated. The evaluation shall be assigned to the appropriate FRCC working group or ad-hoc working group as deemed appropriate. A report will be submitted to the FRCC Engineering and Operating Committees. 7. All load serving members of the FRCC must have an UFLS maintenance and testing program. Documentation of the program must be available to the FRCC on request. 8. FRCC members using frequency based automatic restoration of load must annually provide the Relay Task Force with the amount of automatically restored load as a percentage of the members projected summer peak load. 9. The system impact of frequency based automatic load restoration shall be assessed at least every five years or whenever there are significant changes in system conditions. FRCC Load Shedding Zones The FRCC load shedding zones are defined below in terms of the transmission circuits that form the zone boundary. The boundary terminal is underlined for those circuits that have tap load stations. FRCC Northeast Area Zone 1 Bradford-Deerhaven 138 Bunnell-Ormond 115 Bunnel-Volusia 230 Columbia-Suwanee 115 Duval-Hatch 500 Duval-Kingsland 230 Duval-Thalmann 500 Putnam-Volusia 230 Seminole-Silver Springs N. 230 #1 &2 Note: This zone definition represents a change from the currently defined UFLS zones. It moves Gainesville from zone 1 to zone 2 and Palatka/St. Augustine from zone 2 to zone1. The reason for making this change is the revised zone 1 boundaries coincide with the separation interfaces for the Poinsett North and Duval South 500 kv corridor outages. FRCC Central Area Zone 2 South Boundary is same as zone 3 North Boundary: Bradford-Deerhaven 138 Bunnel-Volusia 230 Duval-Poinsett 500

3 Ft.White N/S 230 Ft. White-High Springs 69 Poinsett-Rice 500 Putnam-Volusia 230 Seminole-Silver Springs North 230 #1&2 FRCC South Area - Zone 3 Brevard-Eau Galle 138 Brevard-Malabar 230 #1&2 Calusa-Ft. Myers 230 Cocoa Beach-Eau Galle 138 Charlotte-Ft.Myers 230 #1&2 Martin-Poinsett 500 Midway-Poinsett 500 FRCC Northwest Area Zone 4 Columbia-Suwanee 115 Ft.White N/S 230 Ft. White-High Springs 69 Jasper-Pinegrove 115 Jasper-Tarver 115 Pinegrove-Suwanee 230 Sub 20-South Bainbridge 230 Callaway-Port St. Joe 230 Scholz-Woodruff 115 Suwanee-Twinlakes 115 Background The FRCC UFLS program underwent a major revision in The addition of two 500 kv and one 230 kv interconnections with Southern Subregion Security Area raised FRCC import capability from zero to approximately 3600 MW. Although the potential for electrical separation was dramatically decreased by these interconnections, the potential consequences of a separation were increased because of the higher import capability. The required amount of automatic UFLS was raised from 36% to 41% with the setpoint of the first step raised from 59.0 to 59.7 hertz. Subsequent studies of the UFLS program s effectiveness have lead to an increase in the number of required UFLS steps. All load serving members of the FRCC must have 56% of their customer demand armed with automatic UFLS relays in accordance with the FRCC UFLS schedule. FRCC UFLS Coordination Issues Extreme contingencies such as loss of all lines on a 500kV right of way or all generators at a plant can cause a separation of the Florida transmission system if the outage occurs during conditions of high power import. While these types of events are rare, they have occurred and caused separations. Coordinated operation of controlled separation systems, UFLS, and reactive switching systems are essential for minimizing the impact on the bulk power system and customer service. Given the exposure to various extreme contingencies and the design of the controlled separation systems, the most likely separation point is in north Florida at Duval and Ft. White substations. This separation point disconnects most of the FRCC from the rest of the grid and necessitates a coordinated approach to load shedding and emergency controls throughout the FRCC. Unusual generator dispatch and/or line outage conditions can create a potential for separations within the FRCC region. The definition of the four FRCC load shedding zones is an attempt to assure uniform application of underfrequency relays. Non uniform application of underfrequency relays across a geographic area can adversely affect frequency recovery when an unforeseen separation occurs.

4 Loss of Generation The sudden trip of a Florida generator will result in the SOU-FRCC interconnection picking up about 90% of the lost generation. This increase in tie flow is due to the size of the Florida system relative to the rest of the Eastern Interconnection. The FRCC transmission systems are operated such that line loadings and voltages will not exceed rated values for the loss of the largest Florida generator. On line contingency analysis (the security analysis program) is used to assure secure operating conditions. The sudden loss of an entire power plant when the SOU to FRCC power transfer is at or close to its 3600 MW limit can cause low voltages and generator reactive overloads. A control center based, automatic load shedding scheme (see discussion of scheme LS1 in FRCC SPS Review and Coordination Procedure and Database documents) has been designed to recognize the low voltages, ties flow increases and generator reactive outputs associated with this condition and respond by tripping approximately 800MW of load in the South Florida area. A controlled separation of the transmission system will be initiated in the event the LS1 load shedding is insufficient to arrest voltage declines. This is accomplished by out-of-step relay systems installed at Duval and Ft. White substations. The loss of power plant followed by controlled separation is the most challenging disturbance scenario for underfrequency. The FRCC UFLS has been designed around the following generator protection and control practices: a) Steam turbine underfrequency protection set to respond to frequencies at or lower than 58.0 hertz for more than 12.0 seconds; b) Nuclear unit low reactor coolant flow protection can respond to frequencies below 57.0 hertz for more than 0.1 seconds; c) Digital turbine governor controls respond to 103% overspeed by closing intercept valves. These considerations establish frequency targets for the FRCC UFLS. The frequency should not fall below 57.0 hertz and should recover above 58.0 hertz in less than 12.0 seconds. Over shedding should not cause the frequency to exceed 103% overspeed (61.8 hertz). UFLS in an amount equal to the power deficit in the separated system will usually result in the frequency stabilizing at a level below 60 hertz. The FRCC UFLS schedule has been designed so that slightly more load is shed than the power deficit. This allows the frequency to recover to or slightly above 60 hertz and facilitates line reclosure via automatic synchronizing relays. All of the controlled separation schemes are coordinated with automatic synchronizing and synchronism check reclosing systems. The Florida system will generally experience temporary overvoltages following separation and UFLS. These temporary overvoltages generally get more severe with greater frequency declines and greater amounts of UFLS. Most transmission level shunt capacitor and reactor banks in South Florida have been equipped with underfrequency/overvoltage relays which result in faster switching than can be accomplished with the automatic voltage controllers normally used for automatic switching of reactive compensation. Loss of 500kV Right of Way A large portion of Florida imports flow on the 500kV lines on the east coast of Florida. From southeast Georgia to Midway substation (near Ft. Pierce, FL), there are two 500kV lines on separate towers sharing the same right of way. The simultaneous loss of both 500kV circuits on the same right of way can result in a controlled separation of the Florida transmission system if the outage occurs during a condition of high power imports. The exact location of the separation and the relay system involved depends on whether the right of way outage is north of Duval substation, south of Duval substation or north of Poinsett substation. All of the separation interfaces are in north Florida. Separations due to 500kV right of way outages are less severe than those caused by the loss of generation. The power deficit consists of the power that was flowing on the outaged 500kV lines and the lines opened by the controlled separation systems. The amount of power interrupted is always less than 3600MW (the maximum import).

5 Coordination with SERC The FRCC is interconnected only with the Southern Subregion of SERC. No contingencies, normal or extreme have been identified which would result in Florida and a sizeable portion of the Southern Subregion becoming separated from the Interconnected power system. Consequently, the FRCC s UFLS program is based on Florida specific concerns. Load Restoration No FRCC members currently use relays which automatically restore load disconnected by UFLS relays. The use of automatic load restoration systems is allowed under the policy stated below. Each utility shall be allowed to automatically restore no more than 15% of the amount of load that is shed by underfrequency relays after the frequency has recovered to hertz, under the following condition: 1. The relays shall be set so that 5% will be restored after 20 minutes of continuous operation at hertz, an additional 5% will be restored after 25 minutes of continuous operation at hertz, and the final 5% will be restored after 30 minutes of continuous operation at hertz. 2. Immediately if frequency is 60.3 hertz or above

Load Dispatcher (Class Code 5223) Task List

Load Dispatcher (Class Code 5223) Task List A. Load Dispatching, General Load Dispatcher (Class Code 5223) Task List 1. Prior to work shift speaks to Load Dispatcher(s), reviews hardcopy and computer logs, and looks at the dispatcher's diagram board

More information

Chapter 5. System security and ancillary services

Chapter 5. System security and ancillary services Chapter 5. System security and ancillary services 1 Introduction Markets for electrical energy can function only if they are supported by the infrastructure of a power system. System should continue to

More information

Scope of Restoration Plan

Scope of Restoration Plan RWG Area Restoration Review Worksheet (10/28/09) EOP-006-02 Directory 8 EOP-005 NYSRG Rule G Text Restoration Plan Requirement R1.Each Reliability Coordinator shall have a Reliability Coordinator Area

More information

Nuclear Power Plant Electrical Power Supply System Requirements

Nuclear Power Plant Electrical Power Supply System Requirements 1 Nuclear Power Plant Electrical Power Supply System Requirements Željko Jurković, Krško NPP, zeljko.jurkovic@nek.si Abstract Various regulations and standards require from electrical power system of the

More information

ATTACHMENT G. Network Operating Agreement

ATTACHMENT G. Network Operating Agreement ATTACHMENT G Network Operating Agreement 1. PURPOSE OF NETWORK OPERATING AGREEMENT The purpose of this Agreement is to identify contractual requirements related to Network Integration Transmission Service

More information

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Outline What is Reactive Power and where does it come from? Why is it important?

More information

Preliminary Feasibility Assessment For. The Rio Tinto Alcan to BCH Transfer Limit of 460 MW. With 50% Series Compensation on Both KMO KIT lines

Preliminary Feasibility Assessment For. The Rio Tinto Alcan to BCH Transfer Limit of 460 MW. With 50% Series Compensation on Both KMO KIT lines Preliminary Feasibility Assessment For The Rio Tinto Alcan to BCH Transfer Limit of 460 MW With 50% Series Compensation on Both KMO KIT lines Report : ASP2010-T001 July 2010 Asset Strategy & Planning,

More information

Generation Interconnection Feasibility Study Report-Web Version. PJM Generation Interconnection Request Queue Position Z1-055

Generation Interconnection Feasibility Study Report-Web Version. PJM Generation Interconnection Request Queue Position Z1-055 Generation Interconnection Feasibility Study Report-Web Version For PJM Generation Interconnection Request Queue Position Z1-055 South Bend Generation Project March 2014 PJM Interconnection 2014. All rights

More information

IESO Supply Deliverability Guidelines

IESO Supply Deliverability Guidelines PUBLIC IMO_GDL_0021 IESO Supply Deliverability Guidelines Issue 3.0 This document is to be used to evaluate long-term system adequacy and connection assessments Public Disclaimer The posting of documents

More information

Advanced Protection of Distribution Networks with Distributed Generators

Advanced Protection of Distribution Networks with Distributed Generators Date:- 8 10 March 2011 Venue: University of Manchester EES-UETP Course title Advanced Protection of Distribution Networks with Distributed Generators Peter Crossley Director of the Joule Centre School

More information

Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents

Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...

More information

Midwest Reliability Organization Procedure For NERC PRC-012

Midwest Reliability Organization Procedure For NERC PRC-012 Midwest Reliability Organization Procedure For NERC PRC-012 A. Introduction The following procedure developed by the MRO Protective Relay Subcommittee (PRS) and Transmission Assessment Subcommittee (TAS)

More information

16 West Coast Regional Plan

16 West Coast Regional Plan 16 West Coast Regional Plan 16.1 Regional overview 16.2 West Coast transmission system 16.3 West Coast demand 16.4 West Coast generation 16.5 West Coast significant maintenance work 16.6 Future West Coast

More information

ECE 586b Course Project Report. Auto-Reclosing

ECE 586b Course Project Report. Auto-Reclosing ECE 586b Course Project Report Auto-Reclosing Srichand Injeti May 5, 2008 Department Of Electrical and computer Engineering University Of Western Ontario, London Ontario Table of contents 1. Introduction...1

More information

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe

ESB Networks Response. ERGEG Consultation. Voltage Quality Regulation in Europe NETWORKS ESB Networks Response to ERGEG Consultation on Voltage Quality Regulation in Europe Date: 22 February 2007 Distribution System Operator ESB Networks Page 1 of 12 Contents 1.0 INTRODUCTION...3

More information

Guidelines for Large Photovoltaic System Integration

Guidelines for Large Photovoltaic System Integration 1 Guidelines for Large Photovoltaic System Integration Silviu Darie, PhD(EE), PE(EE) Abstract- The paper summarizes the result of a research project funded by the Department of Energy (DOE) in collaboration

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION CHAPTER 1 INTRODUCTION Power systems form the largest man made complex system. It basically consists of generating sources, transmission network and distribution centers. Secure and economic operation

More information

(2) Words and expressions used and not defined in these regulations but defined in the Act shall have the meaning assigned to them in the Act.

(2) Words and expressions used and not defined in these regulations but defined in the Act shall have the meaning assigned to them in the Act. (e) condition based maintenance means a set of maintenance actions based on continuous or frequent assessment of equipment condition, which is obtained from either of or a combination of embedded sensors,

More information

Wide Area Monitoring Current Continental Europe TSOs Applications Overview

Wide Area Monitoring Current Continental Europe TSOs Applications Overview Wide Area Monitoring Current Continental Europe TSOs Applications Overview Version 5 System Protection & Dynamics Working Group 20th September 2015 1. Content 1. Content... 2 2. Introduction... 3 3. Main

More information

HVDC. A firewall against disturbances in high-voltage grids. Lennart Carlsson

HVDC. A firewall against disturbances in high-voltage grids. Lennart Carlsson A firewall against disturbances in high-voltage grids Lennart Carlsson Interconnections between grids are desirable because they not only permit economies through the sharing of reserves, but they also

More information

Security Policy Review: Credible Event Management. Scope and Methodology Draft for Industry 2014

Security Policy Review: Credible Event Management. Scope and Methodology Draft for Industry 2014 Security Policy Review: Credible Event Management Scope and Methodology Draft for Industry 2014 Version Date Change 1 26/03/2014 Draft for industry Position Date Prepared By: Reviewed By: Ina Ilieva, Senior

More information

CURTAILABLE RATE PROGRAM FOR INDIVIDUAL CUSTOMER LOADS

CURTAILABLE RATE PROGRAM FOR INDIVIDUAL CUSTOMER LOADS Page 1 of 16 CURTAILABLE RATE PROGRAM FOR INDIVIDUAL CUSTOMER LOADS PROPOSED TERMS AND CONDITIONS January 2015 Page 2 of 16 TABLE OF CONTENTS 1. Definitions... 3 2. Curtailable Load Options... 6 3. Nomination

More information

FIXED CHARGE: This is a cost that goes towards making the service available, including

FIXED CHARGE: This is a cost that goes towards making the service available, including ELECTRICITY BILL COMPONENTS FIXED CHARGE: This is a cost that goes towards making the service available, including installation and maintenance of poles, power lines and equipment, and 24-hour customer

More information

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB

More information

Asset Management Business Update

Asset Management Business Update Asset Management Business Update Improvements through Asset Management Mark Davis, Director, Asset Management & AW October 29, 2008 1 From Maintenance to Asset Management Maintain the System -Initial Focus

More information

MAINTAINING SYSTEM BLACKSTART IN COMPETITIVE BULK-POWER MARKETS

MAINTAINING SYSTEM BLACKSTART IN COMPETITIVE BULK-POWER MARKETS MAINTAINING SYSTEM BLACKSTART IN COMPETITIVE BULK-POWER MARKETS BRENDAN KIRBY and ERIC HIRST Consulting in Electric-Industry Restructuring Oak Ridge, Tennessee Restructuring the electric-power industry

More information

Master/Local Control Center Procedure No. 13 (M/LCC 13) Communications Between the ISO and Local Control Centers

Master/Local Control Center Procedure No. 13 (M/LCC 13) Communications Between the ISO and Local Control Centers Master/LCC Procedure No. 13 - Communications Master/Local Control Center Procedure No. 13 (M/LCC 13) Communications 1. References... 2 2. Background... 3 3. Responsibilities... 3 4. Procedure... 4 4.1

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 21 December 2012 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

NPCC Regional Reliability Reference Directory # 8 System Restoration

NPCC Regional Reliability Reference Directory # 8 System Restoration NPCC Regional Reliability Reference Directory # 8 Task Force on Coordination of Operations Revision Review Record: October 21, 2008 Adopted by the Members of the Northeast Power Coordinating Council, Inc.

More information

Alberta Reliability Standard Cyber Security Configuration Change Management and Vulnerability Assessments CIP-010-AB-1

Alberta Reliability Standard Cyber Security Configuration Change Management and Vulnerability Assessments CIP-010-AB-1 A. Introduction 1. Title: 2. Number: 3. Purpose: To prevent and detect unauthorized changes to BES cyber systems by specifying configuration change management and vulnerability assessment requirements

More information

FRCC Coordination Procedure. Title: FRCC Reliability Coordinator Contingency Analysis Monitoring Criteria

FRCC Coordination Procedure. Title: FRCC Reliability Coordinator Contingency Analysis Monitoring Criteria A. Purpose: The FRCC Reliability Coordinator (RC) Contingency Analysis (CA) application is essential to maintaining the reliability of the FRCC Bulk Electric System. The application has the capability

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 AORC Technical meeting 2014 http : //www.cigre.org C4-1012 Alarm System Improvement in the Northern Region Dispatching Center of Thailand Mr. Manu PONGKAEW, Mr. Phathom TIPSUWAN Electricity Generating

More information

System Protection Schemes in Eastern Denmark

System Protection Schemes in Eastern Denmark System Protection Schemes in Eastern Denmark Joana Rasmussen COWI A/S, Energy Department System Protection Schemes in Eastern Denmark 1.Advanced system protection schemes are investigated and perspectives

More information

FULL ELECTRICAL LNG PLANTS: HIGHEST AVAILABILITY AND ENERGY EFFICIENCY THROUGH OVERALL SYSTEM DESIGN

FULL ELECTRICAL LNG PLANTS: HIGHEST AVAILABILITY AND ENERGY EFFICIENCY THROUGH OVERALL SYSTEM DESIGN FULL ELECTRICAL LN PLANTS: HIHEST AVAILABILITY AND ENERY EFFICIENCY THROUH OVERALL SYSTEM DESIN Dr. Edwin Lerch Siemens A Infrastructure and Cities Sector, IC S SE PTI, ermany Phone: 49-9131-7-34052 Fax:

More information

When this standard has received ballot approval, the text boxes will be moved to the Guidelines and Technical Basis section of the Standard.

When this standard has received ballot approval, the text boxes will be moved to the Guidelines and Technical Basis section of the Standard. CIP-002-5 Cyber Security BES Cyber System Categorization When this standard has received ballot approval, the text boxes will be moved to the Guidelines and Technical Basis section of the Standard. A.

More information

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Electric Power Systems An Overview Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas Overview Power Generation Conventional power generation Power generation from renewables

More information

Operating Security Standards

Operating Security Standards Version 1.1 Prishtina December 2009 TABLE OF CONTENTS 1 Introduction... 1 2 Definitions... 1 2.1 General...1 2.1.2 Kosovo Transmission System...1 2.1.3 Circuit...2 2.1.4 The N-1 Criterion...2 2.1.5 Normal

More information

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014 1 Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables Bob Yinger Southern California Edison April 15, 2014 Southern California Edison SCE provides power to: Nearly

More information

NTTG Study Plan for the 2014-2015 Public Policy Consideration Scenario

NTTG Study Plan for the 2014-2015 Public Policy Consideration Scenario NTTG Study Plan for the 2014-2015 Public Policy Consideration Scenario Table of Contents NTTG Study Plan for the 2014-2015 Public Policy Consideration Scenario Table of Contents... 2 1. Executive Summary...

More information

Section 1: Executive Summary

Section 1: Executive Summary Section 1: Executive Summary SECTION 1: EXECUTIVE SUMMARY 1.1 SECTION PURPOSE This report has been prepared for the Nevada Energy Assistance Corporation (NEAC), a 501(c)(3) non-profit agency; in support

More information

INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS

INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS INTRODUCTION It is the intention of this presentation to provide an explanation of the automatic synchronizing process,

More information

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3

Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System

More information

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse How the National Grid System Operates Chris Gorman Lead Account Executive Syracuse 2 Parts of the Electric System Parts of the Electric System 1. Generating Station: Produces Electricity. 2. Transmission

More information

How To Operate The Williston Uvls

How To Operate The Williston Uvls WND Winter Operating Guide 2012/2013 1 WND Operating Study Using EQ-890-2012WIN- FINAL.sav developed through the 890 process Got load updates from MDU, Central Power, UM G&T Made several topology updates

More information

SPECIFICATION COG-2007

SPECIFICATION COG-2007 Cleco Power LLC SPECIFICATION COG-2007 FOR PARALLEL OPPERATION OF CUSTOMER-OWNED GENERATION ON CLECO S ELECTRICAL SYSTEM Revised: March 7, 2014 CONTENTS ITEM NO. TITLE PAGE NO. 1.0 Scope 3 2.0 Policy On

More information

SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD

SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD SOUTHERN MARYLAND ELECTRIC COOPERATIVE, INC. HUGHESVILLE, MD HOLLAND CLIFF HEWITT ROAD 230 KV TRANSMISSION LINE PROJECT ELECTRIC ALTERNATIVE EVALUATION STUDY BLACK & VEATCH CORPORATION B&V Project 146026(G)

More information

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System Summary Report November 2009 Technical Report on using EHV

More information

Power products and systems. Intelligent solutions for power distribution Zone concept

Power products and systems. Intelligent solutions for power distribution Zone concept Power products and systems Intelligent solutions for power distribution Zone concept Securing continuous power supply ABB is one of the world's leading power and automation technology companies whose products,

More information

Integrating Renewable Electricity on the Grid. A Report by the APS Panel on Public Affairs

Integrating Renewable Electricity on the Grid. A Report by the APS Panel on Public Affairs Integrating Renewable Electricity on the Grid A Report by the APS Panel on Public Affairs 2 Integrating Renewable Electricity on the Grid Executive Summary The United States has ample renewable energy

More information

Electric Field Operations Organization

Electric Field Operations Organization NSTAR Electric Transmission Function Job Summaries Electric Field Operations Organization Vice President, Electric Field Operations (Transmission) This position has primary responsibility for the planning,

More information

Context: significant penetration of DG = increased risks for system security

Context: significant penetration of DG = increased risks for system security Distributed Generation: towards an effective contribution to power system security IEEE Tampa GM 2007: Panel on Impact of Dispersed Generation on Power System structure & security Bruno Meyer Outline Context:

More information

Specific amendments to the Capacity Allocation and Congestion Management Network Code

Specific amendments to the Capacity Allocation and Congestion Management Network Code Annex: Specific amendments to the Capacity Allocation and Congestion Management Network Code I. Amendments with respect to entry into force and application The Network Code defines deadlines for several

More information

Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid

Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid Pakistan Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid Final Report: Executive Summary - November 2015 for USAID Energy Policy

More information

Application of SVCs by CenterPoint Energy to Address Voltage Stability Issues: Planning and Design Considerations

Application of SVCs by CenterPoint Energy to Address Voltage Stability Issues: Planning and Design Considerations 1 Application of SVCs by CenterPoint Energy to Address Voltage Stability Issues: Planning and Design Considerations Wesley Woitt, Alberto Benitez, David Mercado; CenterPoint Energy Frank Schettler, Heinz

More information

ENTSO-E Network Code on Emergency and Restoration

ENTSO-E Network Code on Emergency and Restoration ENTSO-E Network Code on Emergency and Restoration Notice 25 March 2015 This Network Code represents ENTSO-E s final proposals in line with the ACER Framework Guidelines on Electricity System Operation

More information

Evolution of Control for the Smart Transmission Grid

Evolution of Control for the Smart Transmission Grid Evolution of Control for the Smart Transmission Grid Anjan Bose Washington State University Pullman, WA SCE Smart Grid Research Symposium California Institute Of Technology October, 2011 The Past (before

More information

SDG&E Electric Distribution System Interconnection Handbook. <Revised as of 10/21/2015>

SDG&E Electric Distribution System Interconnection Handbook. <Revised as of 10/21/2015> TABLE OF CONTENTS 1 Introduction... 1 1.1 Purposes... 1 1.2 Applicability and Related Tariffs... 1 1.3 Interconnection Agreement Required... 1 1.4 Technical Requirement... 1

More information

UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER GRANTING PETITION FOR DECLARATORY ORDER. (Issued March 15, 2007)

UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER GRANTING PETITION FOR DECLARATORY ORDER. (Issued March 15, 2007) UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Before Commissioners: Joseph T. Kelliher, Chairman; Suedeen G. Kelly, Marc Spitzer, Philip D. Moeller, and Jon Wellinghoff. Cottonwood Energy

More information

Methodology for Merit Order Dispatch. Version 1.0

Methodology for Merit Order Dispatch. Version 1.0 Methodology for Merit Order Dispatch Version 1.0 25 th April 2011 TABLE OF CONTENTS 1. OBJECTIVES... 1 2. ROADMAP FOR IMPLEMENTATION... 1 3. DEFINITIONS... 3 4. OPERATIONS PLANNING... 3 4.1. General Considerations...

More information

Transmission Function Employees Job Titles and Descriptions 18 C.F.R 358.7(f)(1)

Transmission Function Employees Job Titles and Descriptions 18 C.F.R 358.7(f)(1) Date of Last Change to the Provided Information August 27 th, 2015 Director, Transmission Operations The employee in this position is responsible for effectively managing the operation of FirstEnergy Utilities

More information

Summary of CIP Version 5 Standards

Summary of CIP Version 5 Standards Summary of CIP Version 5 Standards In Version 5 of the Critical Infrastructure Protection ( CIP ) Reliability Standards ( CIP Version 5 Standards ), the existing versions of CIP-002 through CIP-009 have

More information

Duke Energy Progress Standards of Conduct Transmission Function Employee Job Titles and Job Descriptions 9/1/13

Duke Energy Progress Standards of Conduct Transmission Function Employee Job Titles and Job Descriptions 9/1/13 Duke Energy Progress Standards of Conduct Transmission Function Employee Job Titles and Job Descriptions 9/1/13 Transmission Operations & Planning Carolinas Power System Operations Director Power System

More information

Operating Reserves and Variable Generation

Operating Reserves and Variable Generation Operating Reserves and Variable Generation A comprehensive review of current strategies, studies, and fundamental research on the impact that increased penetration of variable renewable generation has

More information

Alberta Reliability Standard Cyber Security Security Management Controls CIP-003-AB-5

Alberta Reliability Standard Cyber Security Security Management Controls CIP-003-AB-5 A. Introduction 1. Title: 2. Number: 3. Purpose: To specify consistent and sustainable security management controls that establish responsibility and accountability to protect BES cyber systems against

More information

TERMS AND CONDITIONS

TERMS AND CONDITIONS Virginia Electric and Power Company TERMS AND CONDITIONS XXIV. GENERATOR INTERCONNECTION STANDARD Electric generator interconnection service includes only the ability to interconnect an electric generator

More information

CONGESTION MANAGEMENT POLICY

CONGESTION MANAGEMENT POLICY 1 (8) CONGESTION MANAGEMENT POLICY Contents 1 General... 2 2 Principles of congestion management... 2 3 Congestion management in the Finnish transmission grid... 3 3.1 Normal situation... 3 3.2 Planned

More information

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING

More information

Part 7.6: Glossary of Standard Operating Terms

Part 7.6: Glossary of Standard Operating Terms NPCCGLOSSARY PUBLIC IMP_GOT_0002 Market Manual 7: System Operations Part 7.6: Glossary of Standard Operating Terms Issue 9.0 This document provides a glossary of terms with definitions used in the System

More information

This document should be reviewed at least every two years.

This document should be reviewed at least every two years. 1.0 Change Control Version Date Modification Author(s) Reviews and Approvals by Issue 1 06 August 2007 Initial Document Philip J. Tatro David Wright Issue 2 29 February Removed Confidential from Philip

More information

REQUIREMENTS FOR A REAL-TIME RISK MONITORING TOOL TO REDUCE TRANSMISSION GRID NUCLEAR PLANT VULNERABILITIES

REQUIREMENTS FOR A REAL-TIME RISK MONITORING TOOL TO REDUCE TRANSMISSION GRID NUCLEAR PLANT VULNERABILITIES REQUIREMENTS FOR A REAL-TIME RISK MONITORING TOOL TO REDUCE TRANSMISSION GRID NUCLEAR PLANT VULNERABILITIES M. D. Muhlheim, 1 L. C. Markel, 2 F. J. Rahn, 3 and B. P. Singh 4 1 Oak Ridge National Laboratory,

More information

Pressurized Water Reactor B&W Technology Crosstraining Course Manual. Chapter 9.0. Integrated Control System

Pressurized Water Reactor B&W Technology Crosstraining Course Manual. Chapter 9.0. Integrated Control System Pressurized Water Reactor B&W Technology Crosstraining Course Manual Chapter 9.0 Integrated Control System TABLE OF CONTENTS 9.0 INTEGRATED CONTROL SYSTEM... 1 9.1 Introduction... 1 9.2 General Description...

More information

UE Project N.261788. Assessment and applicability of the global risk assessment tool. Hanne Vefsnmo, hanne.vefsnmo@sintef.no SINTEF Energy Research

UE Project N.261788. Assessment and applicability of the global risk assessment tool. Hanne Vefsnmo, hanne.vefsnmo@sintef.no SINTEF Energy Research UE Project N.261788 Assessment and applicability of the global risk assessment tool Hanne Vefsnmo, hanne.vefsnmo@sintef.no SINTEF Energy Research Final workshop, Rome, 2014-11-27 Outline Short introduction

More information

The Application and Benefits of Multi-phase Auto-reclosing

The Application and Benefits of Multi-phase Auto-reclosing he Application and Benefits of Multi-phase Auto-reclosing etsuya Miyoshi*, Atsushi Kasai* Abstract - In this paper we explain the disadvantages in using single- and three-phase auto-reclosing on double

More information

Updated SYSTEM IMPACT STUDY OF NEW ENGLAND AREA

Updated SYSTEM IMPACT STUDY OF NEW ENGLAND AREA CROSS SOUND CABLE PROJECT 330MW HVdc INTERCONNECTION BETWEEN NEW HAVEN, CONNECTICUT AND SHOREHAM, NY Updated SYSTEM IMPACT STUDY OF NEW ENGLAND AREA Subordinate Status Removal and Amendment of Approved

More information

Chapter 7 System Operations and Physical Markets

Chapter 7 System Operations and Physical Markets MDP_RUL_0002_07 Market Rules Chapter 7 System Operations and Physical Markets Public Issue Date: June 3, 2015 Library Record No. MDP_RUL_0002_07 Document Name Market Rules for the Ontario Electricity Market

More information

Engineering innovation

Engineering innovation Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems

More information

Portland General Electric Company P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES

Portland General Electric Company P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES P.U.C. Oregon No. E-18 Original Sheet No. C-1 RULE C CONDITIONS GOVERNING CUSTOMER ATTACHMENT TO FACILITIES 1. Acceptance of Electricity Service By establishing or requesting a POD or by continuing an

More information

Generator Interconnection and Deliverability Study Methodology Technical Paper

Generator Interconnection and Deliverability Study Methodology Technical Paper Generator Interconnection and Deliverability Study Methodology Technical Paper July 2, 2013 Generator Interconnection and Deliverability Study Methodology Table of Contents Introduction... 1 Section One:

More information

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114.

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114. Generation Interconnection System Impact Study Report For PJM Generation Interconnection Request Queue Position X1-114 Sandyston January 2012 Preface The intent of the System Impact Study is to determine

More information

FACT SHEET. BSES, Delhi - Distribution Network. Power Systems Consultancy from ABB

FACT SHEET. BSES, Delhi - Distribution Network. Power Systems Consultancy from ABB BSES, Delhi - Distribution Network improve power quality System design for optimal techno-economic distribution network based on current and future load forecast Analysis of existing sub-transmission and

More information

Cahier technique no. 196

Cahier technique no. 196 Collection Technique... Cahier technique no. 196 Integration of local power generation in industrial sites and commercial buildings T. Hazel "Cahiers Techniques" is a collection of documents intended for

More information

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group

More information

Power System Operation Procedure: Short Term Projected Assessment of System Adequacy (ST PASA)

Power System Operation Procedure: Short Term Projected Assessment of System Adequacy (ST PASA) ELECTRICITY INDUSTRY ACT ELECTRICITY INDUSTRY (WHOLESALE ELECTRICITY MARKET) REGULATIONS 2004 WHOLESALE ELECTRICITY MARKET RULES Power System Operation Procedure: Short Term Projected Assessment of System

More information

ENTSO-E Working Draft Network Code on Emergency and Restoration

ENTSO-E Working Draft Network Code on Emergency and Restoration ENTSO-E Working Draft Network Code on Emergency and Restoration DRAFT FOR THE FOURTH PUBLIC WORKSHOP Notice 22 January 2015 This document reflects the status of the work of Transmission System Operator

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

Outage Scheduling Manual

Outage Scheduling Manual MANUAL 29 Outage Scheduling Manual July 2015 Version: 4.3.1 Effective Date: 07/29/2015 Committee Acceptance: 6/11/2015 OC This document was prepared by: NYISO Energy Market Operations New York Independent

More information

Electromagnetic Pulse: Effects on the U.S. Power Grid

Electromagnetic Pulse: Effects on the U.S. Power Grid Executive Summary The nation s power grid is vulnerable to the effects of an electromagnetic pulse (EMP), a sudden burst of electromagnetic radiation resulting from a natural or man-made event. EMP events

More information

Magnus Callavik, ABB Power Systems, HVDC, 721 64 Västerås, Sweden Phone: +46(0)21323226. e-mail: magnus.callavik@se.abb.com

Magnus Callavik, ABB Power Systems, HVDC, 721 64 Västerås, Sweden Phone: +46(0)21323226. e-mail: magnus.callavik@se.abb.com HVDC GRIDS FOR OFFSHORE AND ONSHORE TRANSMISSION Magnus Callavik, ABB Power Systems, HVDC, 721 64 Västerås, Sweden Phone: +46(0)21323226. e-mail: magnus.callavik@se.abb.com SUMMARY The objective with this

More information

Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report

Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives. Final Report Transmission Planning Study (Year 2022) for Cherokee 4 Replacement Alternatives (Required per CPUC Decision No. C10-1328) Final Report (Submitted with Public Service s 2011 ERP) Executive Summary The objective

More information

Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System

Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System Prepared By: Transmission Planning Unit Baltimore Gas & Electric Company Table of Contents 1. INTRODUCTION

More information

ENTSO-E Network Code on Emergency and Restoration

ENTSO-E Network Code on Emergency and Restoration ENTSO-E Network Code on Emergency and Restoration 25 March 2015 Notice This Network Code represents ENTSO-E s final proposals in line with the ACER Framework Guidelines on Electricity System Operation

More information

Conservation Voltage Reduction (CVR)

Conservation Voltage Reduction (CVR) Conservation Voltage Reduction (CVR) Nicholas Abi-Samra Senior Vice President October 15, 2013 DNV GL Energy Table of Contents What does CVR do? Why Does CVR Work? DNV GL s CVR Project Experience Needs

More information

Energy Systems Integration

Energy Systems Integration Energy Systems Integration Dr. Martha Symko-Davies Director of Partnerships, ESI March 2015 NREL is a national laboratory of the U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy,

More information

Network Consulting for Power Grid Optimization

Network Consulting for Power Grid Optimization Network Consulting for Power Grid Optimization Project experience in India Network Consulting Competences Page 1 Our worldwide representation Manchester The Hague Denver Schenectady San Diego Houston Mexico

More information

RELIABILITY PLANNING CRITERIA

RELIABILITY PLANNING CRITERIA RELIABILITY PLANNING CRITERIA Version 4.0 01/20/2016 Date Rev. No. Individual Making Edits REVISION HISTORY Reason / Comments 07/01/2013 1 J. Johnson Initial document 06/06/2014 2 R. Chapman Document review;

More information

SCADA Systems Automate Electrical Distribution

SCADA Systems Automate Electrical Distribution SCADA Systems Automate Electrical Distribution PC-based supervisory control and data acquisition systems increase uptime, cut costs and improve utilization. A White Paper from InduSoft Fabio Terezinho

More information

Grid Code - High and extra high voltage - Tennet TSO GmbH Bernecker Straße 70, 95448 Bayreuth

Grid Code - High and extra high voltage - Tennet TSO GmbH Bernecker Straße 70, 95448 Bayreuth Grid Code - High and extra high voltage - Tennet TSO GmbH Bernecker Straße 70, 95448 Bayreuth Status: 1. December 2012 1/45 Contents 1 Introduction... 3 1.1 Legal framew ork... 3 1.2 Technical framew ork...

More information

Public Utilities and Their Reliability in Florida - History

Public Utilities and Their Reliability in Florida - History UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Remedying Undue Discrimination Through Open Access Transmission Service And Standard Electricity Market Design GridFlorida, LLC Docket No.

More information

Solar Power Plant Design and Interconnection

Solar Power Plant Design and Interconnection Solar Power Plant Design and Interconnection Wind & Solar Super Session July 27, 2011 E.H. Camm, S.E. Williams S&C Electric Company Outline Introduction Utility-scale PV power plant Grounding Reactive

More information