21 st Century Facilities

Similar documents
Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

ENGINEERING REPORT. XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613

Understanding Arc Flash

PMCS. Integrated Energy Management Solution. Unlock the Full Potential of Power Networks Through Integration. Complete Solution. Informed Decisions

Part 1 System Modeling & Studies for Existing Systems

Enhance Power Equipment Reliability with Predictive Maintenance Technologies

Arc Flash Energy Mitigation Techniques

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Fundamentals of Power

Introduction. Harmonics and IEEE 519 Page 1 of 19

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Power System Harmonics

UFES Active protection for switchgear

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

Electrical Network Management System

Arc Flash Hazards. Electrical Hazards. Dan Neeser Field Application Engineer Electrical Hazards 2/18/2015. Shock.

Power Quality Standards for Electric Service

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Neutral Currents in Three Phase Wye Systems

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

Fusible Disconnect Switch

Motor Protection Voltage Unbalance and Single-Phasing

CONSULTANT REPORT. Behavior of Two Capstone 30kW Microturbines Operating in Parallel with Impedance Between Them CALIFORNIA ENERGY COMMISSION

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

Predictive Maintenance

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Primary and Secondary Electrical Distribution Systems

Product Data Bulletin

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

GUIDE TO LV SWITCHGEAR & FORMS OF SEPARATION

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

7-41 POWER FACTOR CORRECTION

Transfer Equipment Controls

Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

Sentron Series Circuit Breakers

Electrical Shore Connections / Cold Ironing

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Survey of Harmonics Measurements in Electrical Distribution Systems

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

Electrical Resistance Resistance (R)

City of Leesburg, Florida I.T. Data Center APPENDIX A TOSHIBA UPS INFORMATION

WHAT IS INFRARED (IR) THERMOGRAPHY

Ultrasound Condition Monitoring

Litigation Services & Information

Choosing the Best Solution for Reducing Arc Energy

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17

Low Voltage Switchgear

Evaluating Water-Damaged Electrical Equipment

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

New standardized approach to arc flash protection

Arc flash can kill. Arc flash can be considered as a short circuit through

Specifying a Variable Frequency Drive s

4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Arc Terminator Active Arc-Resistant Switchgear

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

Harmonics in your electrical system

7. Reactive energy compensation

Why Buy HVI VLF Products?

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Square D Company P. O. Box 729 Houston, Texas Business Phone:

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

ABB Fuses Competitive Advantages

Safe and secure distribution of medium voltage with AX1

Arc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.

How To Choose A Transformer

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

Test & Data Management Software

How to reduce exposure to arc flash hazards

ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) J. Instruction Leaflet

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

Simulation of Ungrounded Shipboard Power Systems in PSpice

Power Quality for Information Technology System

employed to ensure the continuing reliability of critical systems.

Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection

MEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED

Titelgrau belassen! Leere Vorlage

Electrical Systems. <Presenter>

ABB PSPS Erich Steinmann; Generator control-2013

misconceptions about arc-flash hazard assessments

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

Eaton s Electrical Services & Systems. Technical Training Safety Training

QUESTIONS and ANSWERS RFB , Metal Clad Switchgear and Power Control Room

Power Monitoring for Modern Data Centers

Cahier technique no. 196

14. Troubleshooting Guide

Table of Contents. TransformerIQ FAQs 1

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Application of Four-Pole Circuit Breakers within Data Centers

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Evaluating Water-Damaged Electrical Equipment

Transcription:

Electrical Testing

21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer support from Utilities Pressure to hold energy costs down Compressed schedules for expanding facilities Effect of EMF on computers and equipment How to expand facilities to meet customer needs cost effectively Harsh environments

Formula For Successful Facilities Facility Planning and Scheduling Engineering Design Quality Installation Acceptance Testing Regular and Complete Maintenance Preventative Maintenance Testing

Testing for All Phases of Facility Improvements Load analysis for facility improvements Trouble shooting and correction of problems Acceptance Testing for New Projects Switchboards and/or Switchgear Circuit Breakers Preventative Maintenance Forensic Testing

Testing Load Analysis Measuring existing loads with portable test equipment 120V to 480V, 0 3000 Amps Recorded values Volts - Power Factor Amps - KVA KW - KVAR Measure harmonic distortion THD - Voltage & Current Individual harmonics Measure loads for emergency generator sizing Motor starting studies

CURRENT Trend Monitoring 75 68.25 61.5 Trend Plot For Device: 3 Phase Current 75 68.25 61.5 IAvg IA 54.75 54.75 48 48 10:50 AM 11:00 AM 11:10 AM 11:20 AM 11:30 AM 11:40 AM 11:50 AM 11/5/01 10:50:00 AM to 11/5/01 11:50:00 AM IB IC

Testing Acceptance Testing Equipment Acceptance Testing Medium Voltage Transformers Switchgear Cables PFC Air Switches SF6 Circuit Breakers Below 600V Switchboards and Switchgear Motor Control Centers Generator Load Testing

Acceptance Testing Cont d. Short Circuit and Coordination Studies Short Circuit Study verifies overcurrent protective devices meet requirement for interrupting available fault current. Coordination Study graphically shows how overcurrent protective devices coordinate to have the CB closest to the fault open. Ground Resistance Testing 3 Point Fall of Potential Method Ground Fault Interruption Testing Required by NEC

Transformer Testing Oil Filled Transformers On Line, no shutdown Excellent analytical technique developed by IEEE to evaluate condition of transformer IEEE/ANSI C57 Distribution, Power and Regulating Transformers. C57.104 is the Standard for Interpretation. NFPA 70B Section 7-2.81 Oil Tests Section 7-2.9.4 Dissolved Gas Analysis

Transformer Testing Cont. d Mineral Oil is complex hydrocarbon molecular compound At normal conditions it is very stable Heat, corona and arcing break molecule down to sub elements (combustible gases) (H 2, CH 4, etc.) Analysis of dissolved combustible gases gives the condition of the transformer. Trending of gases is very helpful in the analysis. DGA is one of the best ways to monitor the condition of the transformer and help the Owner plan repairs or replacements.

Infrared Thermography Scan Heat is the enemy for electrical equipment Heat breaks down electrical insulation 10 C Rule = ½ life Infrared thermography scanning Looks at thermal image of switchgear, busbars, connections, cables, etc. Hot spots and irregularities are discovered by trained technicians Problem areas can be corrected before they cause shutdowns or cause fires. Scanning Saves Equipment Technician scanning is much faster that tightening all bolts. Cannot see some circuit breaker problems without IR. Early detection and correction = preventative maintenance.

Infrared Thermography Scan 148.5 F SP02 SP01 140 130 120 110 95.8 F 100 Spot 1 Temperature Spot 2 Temperature Spot 1 Rise over Spot 2 Ambient Temperature 154.7 F 93.9 F 60.84 F 68.0 F

Circuit Breaker Testing Contact Resistance Results vary with size and construction of circuit breaker less than 100 microhms for medium voltage Contact resistance exposes problems not detectable with IR when there is little load current. Insulation Resistance Phase to ground Phase to phase Functionality Tests Close, Open Trip Kirk key interlocks, etc.

Circuit Breaker Testing Cont d. Overcurrent Trip Point Calibration and Testing Secondary Injection Testing Electronic CB test sets for accurate testing Square D Cutler Hammer GE Siemens New Circuit Breakers with on-board secondary injection testing Cutler Hammer 1150 Trip Unit

Medium Voltage (> 600 Volts) Cable Testing New Cables Insulation resistance testing using hi pot at manufacturer s recommended values NETA use Table 10.6 of Acceptance Testing Specs. Leakage current should be <10 micro Amps for new cables. Existing Cables Watch out! Be careful what voltage you use on old cables. Conservative approach RMS X Square Root of 2 = Peak voltage Use peak value as DC value

Relay Testing Relays are typically used on medium voltage systems Older electro mechanical style relays (typical single phase) Newer models microprocessor based, 1 Phase + 3 Phase Incorporate metering and relay tripping. Programmable on site Fault analysis logging for retrieval Short Circuit and Coordination Studies At least 50% of facilities are not coordinated Poor maintenance Poor installation

Power Quality - Today s Perspective The quality of power 30 years ago was not much of an issue Linear Devices Today many devices disrupt and corrupt the quality of the power Utility Side Voltage Sags Impulses Transient Disturbances Loss of One Phase Over voltage

Power Quality Today s Perspective Customer Side Switch mode power supplies (non-linear device) Harmonic Distortion Overloaded neutrals Transformer heating SCR (non-linear device) Loose wiring Large motor starting

PQ Testing Power Quality Analyzer 3 phase microprocessor based analyzer that samples the voltage waveform 128 times per second. We set thresholds for voltages. By exceeding the thresholds, the machine is activated to record the events as they occur. Harmonic testing and analysis Measure voltage and current THD Analyze individual harmonic values Engineering investigation of problem and surrounding power distribution system by power quality engineer.

Main Switchboard Voltage Sag Model 7100 350.0V RMS Sag Disturbance Three Phase Wye 340.0A Vc Ic 175.0V 170.0A 0.0V 0.00ns M SWBD 0.0A 5.83 ms/div 116.67ms 11/22/01 07:57:32.98 AM Channel Y1 Y2 Delta Voltage 285.185 205.967 79.218 Channel Y1 Y2 Delta Current 277.037 200.082 76.955 Time X1 X2 Delta

Main SWBD Voltage Sag on Phase C-N Model 7100 500.0V Impulse Disturbance Three Phase Wye 640.0A Vc 0.0V 0.0A -500.0V 0.00ns M SWBD -640.0A 2.50 ms/div 50.00ms 11/22/01 07:57:32.98 AM

Main SWBD Utility Capacitor Switching Transient Phase B-N Model 7100 500.0V Impulse Disturbance Three Phase Wye 2.1KA Vb 0.0V 0.0A -500.0V 0.00ns M SWBD -2.1KA 2.50 ms/div 50.00ms 12/03/01 09:48:07.93 AM

Time X1 X2 Delta Utility Capacitor Switching Transient Phase B-N Model 7100 550.0V Impulse Disturbance Three Phase Wye 2.3KA Vb 0.0V 0.0A -550.0V 0.00ns M SWBD -2.3KA 2.50 ms/div 50.00ms 12/03/01 11:43:11.90 AM Channel Y1 Y2 Delta Voltage -56.584-377.984 321.399 Channel Y1 Y2 Delta

Panel NEH1 Power Source Switching Transient Phase A-N Model 7100 650.0V Impulse Disturbance Three Phase Wye 575.0A Va 0.0V 0.0A -650.0V 0.00ns Pnl NEH1-575.0A 2.50 ms/div 50.00ms 01/03/02 02:00:54.74 PM

Panel NEH1 Power Source Switching Phase B-N Model 7100 700.0V Impulse Disturbance Three Phase Wye 570.0A Vb 0.0V 0.0A -700.0V 0.00ns Pnl NEH1-570.0A 2.50 ms/div 50.00ms 01/03/02 02:48:29.37 PM

Harmonic Distortion Voltage Waveform Model 7100 200.0V Snapshot Waveform Three Phase Wye 50.0A Va 0.0V 0.0A -200.0V -50.0A 0.00ns 833.33 16.67ms PDU PnlD us/div 01/17/02 01:06:45.97 PM 1.0% 0.5% 0.0% 60Hz 2940Hz Distortion: thd=1.41% Odd=1.36%

Harmonic Distortion - Current Model 7100 200.0V Snapshot Waveform Three Phase Wye 50.0A Ia 0.0V 0.0A -200.0V -50.0A 0.00ns 833.33 16.67ms PDU PnlD us/div 01/17/02 01:06:45.97 PM 32.0% 16.0% 0.0% 60Hz 2940Hz Distortion: thd=42.34% Odd=42.19%

How Do You Spot PQ Problems? Variable speed drives trip off line more than usual. Computer data errors that cannot be explained by hardware or software Lights flicker (not in a storm). Equipment power supplies have burned or damaged boards. Transformers overheating. Circuit breaker nuisance tripping. Motors overheating or failing easily. Voltages vary significantly from loose wiring. Computer screens wave or are disrupted.

Power Quality and Facility Maintenance Are Related Loose connections are one of the leading power quality problems Lack of coordination of overcurrent protection devices can cause blackouts that could have been avoided. Coordination Study Short Circuit Study Preventative Maintenance Infrared thermography scan looks for hot spots Transformer Testing Oil Quality Dissolved Gas Analysis Cable Testing Test Circuit Breakers Switchgear Maintenance

Conclusion Facilities today face tough problems: Harsh environments Power Quality Problems Need for 24/7 Reliability Compressed schedules A successful 21 st Century Facility needs four solid legs to stand on: Engineering Design Quality Installation Maintenance Testing

Conclusion Cont d. Excellent resources and standards from IEEE, NETA and NFPA for Testing and Maintenance A proper test is worth a thousand opinions. The right test equipment and experience will aid the Design Engineer in ensuring success for the Customer. Call IETC at 717-252-4730 for a quote today!