1 The Facts About Harmonics and Power Factor Power Quality: Harmonics & Power Factor Correction 1
2 Agenda I. Harmonic Basics II. Harmonic Mitigation Methods III. Active Harmonic Filters IV. Applications V. Specification Recommendations VI. Summary Division - Name - Date - Language 2
3 Harmonic Basics 3 rd Harmonic Fundamental 5 t1h Harmonic 7 th Harmonic Harmonic Frequency Sequence 1 60Hz Hz Hz Hz Hz Hz Hz + : : : Hz + What are harmonics? Proliferated by power semiconductor devices Converts power (AC to DC) A harmonic is a component of a periodic wave having a frequency that is an integer multiple of the fundamental power line frequency Characteristic harmonics are the predominate harmonics seen by the power distribution system Predicted by the following equation: h C = characteristic harmonics to be expected n = an integer from 1,2,3,4,5, etc. p = number of pulses or rectifiers in circuit H c = np +/- 1 Division - Name - Date - Language 3
4 Multi-pulse Converters H n = np +/- 1 H n = characteristic harmonic order present n = an integer p = number of pulses Harmonic Orders Present Harmonics present by rectifier design Type of rectifier Hn 1 phase 4-pulse 2 phase 4-pulse 3 phase 6-pulse 3 phase 12-pulse 3 phase 18-pulse 3 x x 5 x x x 7 x x x 9 x x 11 x x x x 13 x x x x 15 x x 17 x x x x 19 x x x x 21 x x 23 x x x x 25 x x x x 27 x x 29 x x x 31 x x x 33 x x 35 x x x x x 37 x x x x x 39 x x 41 x x x 43 x x x 45 x x 47 x x x x 49 x x x x Division - Name - Date - Language 4
5 Harmonic Basics Nonlinear loads draw harmonic current from source Example: 6-Pulse VFD Converter Inverter DC bus M A B C Division - Name - Date - Language 5
6 Harmonic Basics I h Loads V h = I h x Z h Why a concern? Current distortion Added heating, reduced capacity Transformers Conductors and cables Nuisance tripping of electronic circuit breakers (thermal overload) Voltage distortion Interference with other electronic loads AC Motor winding & bearing failures Potential resonance condition (PF caps) Excessive voltage Overheating of PF correction capacitors Tripping of PF protection equipment Shutdown / damage to electronic equipment Division - Name - Date - Language 6
7 Total Power Factor TPF = (DPF) x (Distortion factor) DPF = KW KVA f = Cos φ Distortion Factor = THD(I) 2 = Cos δ TPF = Total or true power factor DPF = Displacement power factor Distortion Factor = Harmonic power factor Division - Name - Date - Language 7
8 Total Power Factor Example Variable frequency drive (PWM type) DPF =.95 THD(I) = 90% (no DC choke & no input line reactor) Distortion Factor = =.7433 TPF =.95 x.7433 =.7061 Division - Name - Date - Language 8
9 Harmonic Mitigation Methods Typically applied per device Line reactors/dc bus chokes/isolation transformers 5 th harmonic filters (trap filters) Broadband filters Multi-pulse transformers/converters Active front end (AFE) converter System solution Active harmonic filter Division - Name - Date - Language 9
10 Harmonic mitigation methods (Applied per VFD) Solution Advantage Disadvantage Typical % TDD Typical Price Multiplier* Increase short circuit capacity Reduces THD(V) Increases TDD Not likely to occur** Dependent upon SCR*** Cost of transformer and installation change out C-Less Technology Lower TDD Simplified design Less cost Compliance is limited Application limited Size limited 30-50% TDD Impedance (3% LR or 5% DC choke) Low cost adder Simple Compliance difficult 30-40% TDD th Harmonic filter Reduces 5th & total TDD Does not meet harmonic levels at higher orders^ 18-22% TDD Broadband filter Reduces TDD (thru 13th) Large heat losses Application limited 8-15% TDD pulse rectifiers Reduces TDD Reliable Large footprint/heavy Good for >100 HP 8-15 % TDD pulse rectifiers Reduces TDD Reliable Large footprint/heavy Good for >100 HP 5-8% TDD Active front end converter Very good TDD Regeneration possible Large footprint/heavy Very high cost per unit High heat losses < 5% TDD * Price compared to a standard 6-pulse VFD. ** Utilities and users are not likely to change their distribution systems. *** Increasing short circuit capacity (lower impedance source or larger KVA capacity) raises TDD but lowers THD(V). ^ Can be said for all methods listed. Division - Name - Date - Language 1 0
11 Inductors/Transformers/DC Bus Chokes Description: Converter-applied inductors, DC bus chokes, or isolation transformers Pros: Inexpensive & reliable Transient protection for loads 1st Z yields big TDD reduction (90% to 35% w/3% Z) Cons: Limited reduction of TDD at equipment terminals after 1st Z Reduction dependent on source Z Division - Name - Date - Language 1 1
12 5th Harmonic Filter (Trap Filter) Inductor (L p ) and Capacitor (C) provide low impedance source for a single frequency (5 th ) Must add more tuned filters to filter more frequencies Z s L s Inductor L s required to detune filter from electrical system and other filters V s L p C Load If L s not present, filter is sink for all 5 th harmonics in system If L s not present, resonance with other tuned filters possible Injects leading reactive current (KVAR) at all times may not need Division - Name - Date - Language 1 2
13 Broadband Filters ~ L L Mitigates up to 13 th order or higher Each inductor (L) > 8% impedance V drops ~ 16% at load Trapezoidal voltage to load Can only be used on diode converters Prevents fast current changes (only good for centrifugal loads) When generators are present, re-tuning may be required Load Source L p C Capacitor (C) designed to boost V at load to proper level (injects leading VARs) Physically large High heat losses (>5%) Series device Division - Name - Date - Language 1 3
14 Multi-Pulse Drives Description: Drives/UPS with two (12 pulse) or three (18 pulse) input bridges fed by a transformer with two or three phase shifted output windings. Pros: Reduces TDD to 10% (12 pulse) & 5% (18 pulse) at loads Reliable Cons: High installation cost with external transformer Large footprint (even w/autotransformer) Series solution with reduction in efficiency One required for each product Cannot retrofit Division - Name - Date - Language 1 4
15 Harmonic mitigation methods VFD mitigation topologies 6-Pulse converter 12-Pulse converter 18-Pulse converter DC Link Reactor + DC Bus Load A Line Reactor 9 1 Multipulse Transformer A 2 Rectifier Assembly DC+ M AC Line Wye - B C C B Delta DC- Delta Transformer Tertiary C-less or 3% reactance min (if included); small footprint, simplified cabling Externally mounted 3 winding transformer; more wire and cabling; complicated Large footprint, more steel & copper (losses) A A A pulse 12 pulse 18 pulse Current waveform distorted TDD 30% to 40% with 3% reactor (depending on network impedance) Current slightly distorted TDD 8% to 15% (depending on network impedance) 0.0s 0.02s Current wave form good TDD 5% to 7% (depending on network impedance) Division - Name - Date - Language 1 5
16 AFE Converters Used in UPS and VFD Replaces diode converter with IGBT converter THE HYPE Permits current smoothing on AC lines (< 5% TDD) Permits 4-quadrant operation of VFD Maintains unity TOTAL PF Division - Name - Date - Language 1 6
17 Active Front End Converter A C IGBT AFE VFD DC Bus IGBT S o u r c e Filter Converter Inverter AC Motor Required to limit THDv on mains to <=5% Losses - ~5% of rated Losses 1.5 to 2% of rated Division - Name - Date - Language 1 7
18 AFE Converters Significant harmonics above 50 th order American Bureau of Shipping (ABS) requires examination to 100 th order when AFE applied Higher frequencies yield higher heating of current path & potential resonance with capacitors Division - Name - Date - Language 1 8
19 AFE Converters PCC EMC Filter Mains Choke Reactance, 4% Mains Filter Mains Filter Reactance, 12% Mains Pulse Converter, IGBT DC Bus Motor Pulse Inverter, IGBT M Motor Division - Name - Date - Language 1 9
20 AFE THDv < 50 th (Measurements on vessel) Division - Name - Date - Language 2 0
21 AFE THDv > 50 th (Measurements on vessel) The result is a Vthd >50Hz of around 3.25%; almost as much as below! Total Vthd is ~ 4.65%! Division - Name - Date - Language 2 1
22 AFE Converters 200 KVA rated AFE VFD 100 KVA rated PWM VFD DC Drive PF caps Cons Larger & more expensive than 6 pulse drives Approximately twice the size & price Larger & more expensive than 18-p VFD High heat losses (~8%) per VFD Mains voltage must be free of imbalance and voltage harmonics Generates more harmonics Without mains filter THD(V) can reach 40% Requires short circuit ratio > 40 at PCC Switched mode power supplies prohibited Capacitors prohibited on mains IGBT & SCR rectifiers prohibited on same mains No other nonlinear loads permitted Cause high DC bus ripple & pumps up the DC voltage at low loads to trip unit Division - Name - Date - Language 2 2
23 System Solution Active Harmonic Filter Applied to one or many nonlinear loads VFD, UPS, UV, DC drives, DC power supplies Provides DPF correction More cost effective for multiple loads Saves space Lower heat losses Not critical to operation Division - Name - Date - Language 2 3
24 Active Harmonic Filter ~ I s CT I l Source I a L AHF Parallel connected AHF Load I s + I a = I l Ia includes 2 nd to 25/50 th harmonic current I s <5% TDD Division - Name - Date - Language 2 4
25 Active Harmonic Filters Advantages Highly effective (2 nd to 25/50 th orders cancelled) Parallel connected not critical for equipment operation Scalable Parallel units as needed Universal solution Handles many loads Many types of loads at same time Can be installed as convenient Best cost for multiple loads Smallest footprint with std VFD/UPS Lowest system heat losses Disadvantages Heat from high speed switching of IGBT Cost issues possible for single load Considerations Load must have input impedance (3%) Protects load Limits size of AHF Need branch circuit protection Division - Name - Date - Language 2 5
26 System Solution AHF Sizing Example A 125 HP variable torque 6-pulse VFD with 3% LR Required AHF filtering capability = 47.5 amperes Two 125 HP VT 6-pulse VFD w/3% LR Required AHF size = 84.4 amps Three 125 HP VT 6-pulse VFD w/3% LR Required AHF size = amps Six 125 HP VT VFD w/3% LR Required AHF size = amps (not 6 x 47.5 = 285 amps) Division - Name - Date - Language 2 6
27 ANSI Standard IEEE Chapter 11 Addresses THD(V) delivered by utility to user THD(V) must be < 5% [< 69 KV systems] Chapter 10 Defines the amount of TDD a user can cause Based upon size of user in relation to power source Table 10.3 for systems < 69 kv Defines limits for voltage notches caused by SCR rectifiers Table 10.2 Defines PCC (point of common coupling) Division - Name - Date - Language 2 7
28 IEEE Table 10.2 Limits on Commutation Notches (Applies to SCR rectifiers only) Table 10.2 Low-Voltage System Classification and Distortion Limits *Special Applications General System **Dedicated System Notch Depth 10% 20% 50% THD (Voltage) 3% 5% 10% Notch Area, μvs 16,400 22,800 36,500 Note: Notch area for other than 480 V systems should be multiplied by V / 480. *Special Applications Airports, Hospitals ** Dedicated System Dedicated exclusive to converter loads Division - Name - Date - Language 2 8
29 IEEE Defines current distortion as TDD Total Demand Distortion Largest amplitude of harmonic current occurs at maximum load of nonlinear device if electrical system can handle this it can handle all lower amplitudes Always referenced to full load current Effective meaning of current distortion Defines voltage distortion as THD Total harmonic voltage distortion Does not use THD(I) Total harmonic current distortion Instrument measurement (instantaneous values) Uses measured load current to calculate THD(I) Division - Name - Date - Language 2 9
30 As load decreases, TDD decreases while THD(I) increases. IEEE TDD and THD(I) are not the same except at 100% load Example: with AHF operating Measured Total I, rms Fund I, rms Harm I, rms THD(I) TDD Full load % 3.8% % 3.7% % 3.4% % 2.9% % 2.3% % 1.8% % 1.4% Division - Name - Date - Language 3 0
31 IEEE Table 10.3 Current Distortion Limits for General Distribution Systems (<69 kv) Isc/Iload <11 11<=h<17 17<=h<23 23<=h<35 h>=35 TDD <20 4.0% 2.0% 1.5% 0.6% 0.3% 5.0% 20<50 7.0% 3.5% 2.5% 1.0% 0.5% 8.0% 50< % 4.5% 4.0% 1.5% 0.7% 12.0% 100< % 5.5% 5.0% 0.2% 1.0% 15.0% > % 7.0% 6.0% 2.5% 1.4% 20.0% Isc = short circuit current capacity of source Iload = demand load current (fundamental) TDD = Total Demand Distortion (TDD = Total harmonic current distortion measured against fundamental current at demand load.) Division - Name - Date - Language 3 1
32 Harmonic Standards Most harmonic problems are not at PCC with utility Occurs with generators & UPS Occurs where nonlinear loads are concentrated Occurs inside the plant Need to protect the user from self by moving the harmonic mitigation requirements to where harmonic loads are located Division - Name - Date - Language 3 2
33 AHF Harmonic Performance AHF injection At VFD Terminals Source current AS off AS on Order % I fund % I fund Fund % % % 0.478% % 0.674% % 0.679% % 0.297% % 0.710% % 0.521% % 0.052% % 0.464% % 0.639% % 0.263% % 0.409% % 0.489% % 0.170% % 0.397% % 0.243% % 0.325% % 0.279% % 0.815% % 0.240% % 0.120% % 0.337% % 0.347% % 0.769% % 0.590% % THD(I) 35.28% 2.67% Division - Name - Date - Language 3 3
34 Active Harmonic Filter Dual Mode Operation I as = I h2 + I r 2 I as = rms output current of AHF PCS I h = rms harmonic current I r = rms reactive current Examples Ias Ih Ir Division - Name - Date - Language 3 4
35 Typical W/WW Applications Pumping Stations Potable Wastewater Wastewater Plants Water Purification (potable) Division - Name - Date - Language 3 5
36 Typical W/WW Applications Pumping Stations Applications VFD for pump control Simple/repeatable control Remote control made easy Energy savings over discharge, on/off, & inlet flow control Division - Name - Date - Language 3 6
37 Typical W/WW Applications Wastewater Plants Many pumps for fluid movement (VFD) VT Centrifugal pumps CT Progressive cavity pumps (semi-solids) Solids handling (VFD) Conveyors Aeration blowers (VFD) CT & VT types Disinfectant UV systems (ultraviolet) Electronic ballasts 3Φ Ozone generators (SCR power supplies) HVAC Division - Name - Date - Language 3 7
38 Typical W/WW Applications Water Purification Many pumps (VFD) UV systems (electronic ballasts) Reverse osmosis Centrifugal pumps (VFD) Ozone generators Division - Name - Date - Language 3 8
39 Specification Recommendations for System Solution Write TDD specs not THD(I) Separate harmonic spec from nonlinear load spec Place AHF spec in Section 16 by itself Write standard nonlinear load specification Eliminates vendor hassles Need 3% impedance on each nonlinear load Universal solution Good for all nonlinear loads Apply AHF per electrical bus (best economics) Can attain 5% TDD per load or bus inside the plant Guarantees elimination of harmonic problems both TDD and THD(V) Division - Name - Date - Language 3 9
40 Summary Know the solution What does it accomplish harmonically Know the benefits and cautions Every device requires different considerations Make comparisons First cost Floor space required Heat losses/cooling requirements Cost of operating Select what you really need All 6-p rectifiers should have at least a 3% line reactor Reduces TDD to ~1/3 Protects diode rectifiers from transients Reduces voltage notch of SCR rectifiers Write the specification required Meet the standard at utility Protect the user from self Division - Name - Date - Language 4 0
41 Thank You Questions? 4 1
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY
VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY Carrier Corporation Syracuse, New York October 2005 TABLE OF CONTENTS INTRODUCTION..........................2
Variable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
Harmonic Distortion and Variable Frequency Drives
Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
Practical Overview of Mine Power System Harmonics
Practical Overview of Mine Harmonics Western Mining Electrical Association Tucson, Arizona November 1999 11/20/2003 10:26:46 PM wmea-harmonic-1.ppt Slide 1 Harmonic Topics What are harmonics? Where do
Introduction. Harmonics and IEEE 519 Page 1 of 19
Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms
Power System Harmonics
Pacific Gas and Electric Company Power System Harmonics What are power system harmonics? Ideally, voltage and current waveforms are perfect sinusoids. However, because of the increased popularity of electronic
Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications
Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications Copyright Material IEEE Paper No. PCIC-2003-15 Tony Hoevenaars, P. Eng. Kurt LeDoux, P.E. Matt Colosino Member IEEE Member,
POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS
A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
Advantages of 6-Pulse VFD with Lineator AUHF vs Active Front End (AFE) Drives
White Paper: AUHF-WP001-A1 August 20, 2015 Advantages of 6-Pulse VFD with Lineator AUHF vs Active Front End (AFE) Drives Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
Variable Frequency Drives and Energy Savings
Variable Frequency Drives and Energy Savings It s more than just fan and pump applications www.sea.siemens.com by: Stephen Prachyl www.usa.siemens.com/energysavings When discussing energy savings and variable
Meeting Harmonic Limits on Marine Vessels
Meeting Harmonic Limits on Marine Vessels I. C. Evans, A. H. Hoevenaars, P.Eng, Member, IEEE Abstract Recent advances in power electronic drive converters have led to an increased use of this technology
7-41 POWER FACTOR CORRECTION
POWER FTOR CORRECTION INTRODUCTION Modern electronic equipment can create noise that will cause problems with other equipment on the same supply system. To reduce system disturbances it is therefore essential
Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7
Application Note #45 Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7 Introduction This application note is the seventh in a series on delta conversion theory of operation.
Principles of Adjustable Frequency Drives
What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable
HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM
Technical Note No.3 March 2000 HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses harmonic distortion, its causes and adverse effects, what levels are unacceptable and how
HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS
White Paper: MIRUS-TP003-A January 15, 2014 HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc.
Power System Harmonic Fundamental Considerations: Tips and Tools for Reducing Harmonic Distortion in Electronic Drive Applications
Power System Harmonic Fundamental Considerations: Tips and Tools for Reducing Harmonic Distortion in Electronic Drive Applications October 2011/AT313 by Larry Ray, P.E. Louis Hapeshis, P.E. Make the most
Survey of Harmonics Measurements in Electrical Distribution Systems
Survey of Harmonics Measurements in Electrical Distribution Systems Leon M. Tolbert, Member, IEEE Oak Ridge National Laboratory* P.O. Box 28, Bldg Oak Ridge, TN 3783-6334 Alexandria, VA 2235-3862 Phone:
Power Quality Standards for Electric Service
Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as
FREQUENCY CONTROLLED AC MOTOR DRIVE
FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly
Considering the effects of UPS operation with leading power factor loads
Considering the effects of UPS operation with leading power factor loads Over the past five years, a new generation of data processing and communications equipment has become prevalent in modern data centers
Diode Applications. by Kenneth A. Kuhn Sept. 1, 2008. This note illustrates some common applications of diodes.
by Kenneth A. Kuhn Sept. 1, 2008 This note illustrates some common applications of diodes. Power supply applications A common application for diodes is converting AC to DC. Although half-wave rectification
Power Quality Issues, Impacts, and Mitigation for Industrial Customers
Power Quality Issues, Impacts, and Mitigation for Industrial Customers By Kevin Olikara, Power and Energy Management Products Rockwell Automation, Inc. Now, more than ever, electronic equipment and computing
EET272 Worksheet Week 9
EET272 Worksheet Week 9 answer questions 1-5 in preparation for discussion for the quiz on Monday. Finish the rest of the questions for discussion in class on Wednesday. Question 1 Questions AC s are becoming
Application Guide. Power Factor Correction (PFC) Basics
Power Factor Correction (PFC) Basics Introduction Power Factor, in simple terms, is a number between zero and one that represents the ratio of the real power to apparent power. Real power (P), measured
UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES
UNINTERRUPTIBLE POWER SUPPLIES 9900A >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES 9900A The 9900A UPS system uses the most advanced IGBT in both the converter and inverter with Digital Signal Processor (DSP)
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters
Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings
Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203 03/2013 Retain for future use. Introduction Short-circuit current s (SCCRs) for variable frequency drives (VFDs) is
The full wave rectifier consists of two diodes and a resister as shown in Figure
The Full-Wave Rectifier The full wave rectifier consists of two diodes and a resister as shown in Figure The transformer has a centre-tapped secondary winding. This secondary winding has a lead attached
Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor
International Journal of Engineering Inventions e-issn: 78-7461, p-issn: 319-6491 Volume 3, Issue 5 (December 013) PP: 36-41 Modelling, Simulation and Performance Analysis of A Variable Frequency Drive
The Different Types of UPS Systems
The Different Types of UPS Systems By Neil Rasmussen White Paper #1 Revision 5 Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics.
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Analog & Digital Electronics Course No: PH-218
Analog & Digital Electronics Course No: PH-18 Lec 3: Rectifier and Clipper circuits Course nstructors: Dr. A. P. VAJPEY Department of Physics, ndian nstitute of Technology Guwahati, ndia 1 Rectifier Circuits:
Control Development and Modeling for Flexible DC Grids in Modelica
Control Development and Modeling for Flexible DC Grids in Modelica Andreas Olenmark 1 Jens Sloth 2 Anna Johnsson 3 Carl Wilhelmsson 3 Jörgen Svensson 4 1 One Nordic AB, Sweden, [email protected].
Neutral Currents in Three Phase Wye Systems
POWER SYSTEMS ENGINEERING DATA PUBLISHED BY SQUARE D, OSHKOSH, WISCONSIN Subject: Neutral Currents in Three Phase Wye Systems by Robert Arthur Square D Company Oshkosh, Wisconsin (414) 46-80 and R. A.
Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module
Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working
Standards of Power Quality with reference to the Code of Practice for Energy Efficiency of Electrical Installations
Standards of Power Quality with reference to the Code of Practice for Energy Efficiency of Electrical Installations Ir. Martin WU Kwok-tin, Energy Efficiency Office, Electrical & Mechanical Services Department
CONTROL OF HARMONICS IN ELECTRICAL POWER SYSTEMS
GUIDANCE NOTES ON CONTROL OF HARMONICS IN ELECTRICAL POWER SYSTEMS MAY 006 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 186 Copyright 006 American Bureau of Shipping
Specification guide no. 9 Active harmonic conditioner from 20 to 480 A
Active harmonic conditioner from 20 to 480 A Contents 1 - Installations concerned... 2 1.1 - New installations... 2 1.2 - Existing installations... 2 2 - General... 2 2.1 - Scope... 2 2.2 - Applicable
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to
Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder
Robert W. Erickson University of Colorado, Boulder 1 1.1. Introduction to power processing 1.2. Some applications of power electronics 1.3. Elements of power electronics Summary of the course 2 1.1 Introduction
Diode Applications. As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off.
Diode Applications Diode Switching As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off. Voltage Rectifier A voltage rectifier is a circuit that converts an
Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE
Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements
How To Improve Power Quality
Power Quality Improvement Of Three Phase Four Wire Distribution System Using VSC With A Zig-Zag Transformer Sajith Shaik *, I.Raghavendar ** *(Department of Electrical Engineering, Teegala Krishna Reddy
Opportunity of Energy Saving in electrical path is lesser as compared to other areas
Data Centre Power Map ` Energy Optimization Techniques Data Center Power Chain Venkat Rao B Country Manager Power Products Data Center Power Draws Cooling About 35 40 % Sources of Energy Waste Fans / Blowers
The Different Types of UPS Systems
Systems White Paper 1 Revision 6 by Neil Rasmussen Contents Click on a section to jump to it > Executive summary There is much confusion in the marketplace about the different types of UPS systems and
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)
00-00-//$0.00 (c) IEEE IEEE Industry Application Society Annual Meeting New Orleans, Louisiana, October -, Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part
Harmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
Relationship between large subject matter areas
H02M APPARATUS FOR CONVERSION BETWEEN AC AND AC, BETWEEN AC AND DC, OR BETWEEN DC AND DC, AND FOR USE WITH MAINS OR SIMILAR POWER SUPPLY SYSTEMS; CONVERSION OF DC OR AC INPUT POWER INTO SURGE OUTPUT POWER;
21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
EXTENDING THE LIFE OF POWER FACTOR CAPACITORS
by John Houdek, President, Allied Industrial Marketing, Inc., and Cesar Chavez, Engineering Manager, ARTECHE / Inelap Abstract: The addition of power factor improvement capacitors to individual motors
UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS
Page 1 UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS By Henry Ott Consultants Livingston, NJ 07039 (973) 992-1793 www.hottconsultants.com [email protected] Page 2 THE BASIC
Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka
Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka S S B Udugampala, V Vijayarajah, N T L W Vithanawasam, W M S C Weerasinghe, Supervised by: Eng J Karunanayake, Dr. K T M U Hemapala
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE Karl M. Hink, Executive Vice President Originally presented at the Power Quality 99 Conference ABSTRACT Motor protection
Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers
Journal Journal of of Emerging Emerging Trends Trends in in Engineering Engineering and and Applied Applied Sciences Sciences (JETEAS) (JETEAS) 1 1 (1): (1): 72-78 72-78 Scholarlink Research Institute
DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT
DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT by Philip J. A. Ling, P.Eng. Cyril J. Eldridge, B. Sc. POWERSMITHS INTERNATIONAL
Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor
International Journal of Innovation and Scientific Research ISSN 2351-8014 Vol. 11 No. 2 Nov. 2014, pp. 445-449 2014 Innovative Space of Scientific Research Journals http://www.ijisr.issr-journals.org/
A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research
Session #3133 A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research Abdullatif Bagegni, Vance Poteat Merrimack College Abstract This paper describes the design
ULRASONIC GENERATOR POWER CIRCUITRY. Will it fit on PC board
ULRASONIC GENERATOR POWER CIRCUITRY Will it fit on PC board MAJOR COMPONENTS HIGH POWER FACTOR RECTIFIER RECTIFIES POWER LINE RAIL SUPPLY SETS VOLTAGE AMPLITUDE INVERTER INVERTS RAIL VOLTAGE FILTER FILTERS
Discover the power of e-learning! The Quick Guide to AC Variable Frequency
The Quick Guide to AC Variable Frequency This ebook is meant as an easy guide to any electrical or electronic engineer or technician, who would like to know how modern ac variable frequency drives work.
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
Module Title: Electrotechnology for Mech L7
CORK INSTITUTE OF TECHNOLOGY INSTITIÚID TEICNEOLAÍOCHTA CHORCAÍ Autumn Examinations 2012 Module Title: Electrotechnology for Mech L7 Module Code: ELEC7007 School: School of Mechanical, Electrical and Process
DIODE CIRCUITS LABORATORY. Fig. 8.1a Fig 8.1b
DIODE CIRCUITS LABORATORY A solid state diode consists of a junction of either dissimilar semiconductors (pn junction diode) or a metal and a semiconductor (Schottky barrier diode). Regardless of the type,
HVAC Applications. VFD considerations for HVAC systems...
HVAC Applications VFD considerations for HVAC systems... 1 COMMON TERMINOLOGY VFD (VARIABLE FREQUENCY DRIVES) AFC (ADJUSTABLE FREQ. CONTOLLER) ASD (ADJUSTABLE SPEED DRIVES) VSD (VARIABLE SPEED DRIVES)
What Is Regeneration?
What Is Regeneration? Braking / Regeneration Manual Regeneration Overview Revision 1.0 When the rotor of an induction motor turns slower than the speed set by the applied frequency, the motor is transforming
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES WHITE PAPER: TW0062 36 Newburgh Road Hackettstown, NJ 07840 Feb 2009 Alan Gobbi About the Author Alan Gobbi Alan Gobbi
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power
Impedance Matching and Matching Networks. Valentin Todorow, December, 2009
Impedance Matching and Matching Networks Valentin Todorow, December, 2009 RF for Plasma Processing - Definition of RF What is RF? The IEEE Standard Dictionary of Electrical and Electronics Terms defines
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International
HVDC Light, a tool for electric power transmission to distant loads
Presented at VI Sepope Conference, Salvador, Brazil, May 1998 HVDC Light, a tool for electric power transmission to distant loads by Gunnar Asplund Kjell Eriksson* Ove Tollerz ABB Power Systems AB ABB
Mitigating data center harmonics
Mitigating data center harmonics Patricia Matwijec Product Manager Eaton Ed Spears Product Marketing Manager Eaton Executive summary Line harmonics can have costly and disruptive effects on electrical
APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.
TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION Abstract This application note describes the four quadrant mode of operation of a linear AC Power
98% Efficient Single-Stage AC/DC Converter Topologies
16 POWER CONVERTERS www.teslaco.com 98% Efficient Single-Stage AC/DC Converter Topologies A new Hybrid Switching Method is introduced in this article which for the first time makes possible AC/DC power
Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters )
Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters ) Classification of AC to AC converters Same frequency variable magnitude AC power AC controllers AC power Frequency converters (Cycloconverters)
Rectifier circuits & DC power supplies
Rectifier circuits & DC power supplies Goal: Generate the DC voltages needed for most electronics starting with the AC power that comes through the power line? 120 V RMS f = 60 Hz T = 1667 ms) = )sin How
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International
Analysis of AC-DC Converter Based on Power Factor and THD
Website: www.ijetae.com (SSN 50-459, SO 900:008 Certified Journal, Volume 3, ssue, February 03) Analysis of AC-DC Converter Based on Power Factor and THD Shiney.S.Varghese, Sincy George Department of Electrical
The Different Types of UPS Systems
White Paper 1 Revision 7 by Neil Rasmussen > Executive summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics. Each of these UPS types is
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
Motor Efficiency and Power Factor ME 416/516
Motor Efficiency and Power Factor Motivation More than half of all electric energy generated goes to power electric motors. Electric motor converts electric power into shaft power. In thermodynamics terms,
Offshore Platform Powered With New Electrical Motor Drive System
Offshore Platform Powered With New Electrical Motor Drive System Authors: Jan O. Lamell, M.Sc E.E. ABB Automation Technologies Presenters: Thomas Johansson, M.Sc E.E. ABB Automation Technologies Timothy
Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile
Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile Michael Coddington National Renewable Energy Laboratory Golden, Colorado,
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta
GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran [email protected] Seyed Ali NABAVI NIAKI University of Mazandaran
Three phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009
PotashCorp New Brunswick Division Picadilly Potash Project ETAP SIMULATION Prepared by: Carlos Reinel Senior Engineer R&D Department Power Survey International Approved by: Pierre Archambault, PEng. VP
Chapter 4: Power Factor Correction
1 Chapter 4: Power Factor Correction Electronic equipment connected to the mains interacts with the supply grid to varying extents. Passive loads such as heaters sink current in a steady manner and do
Paralleling Power Sources Which Share a Common Neutral
Paralleling Power Sources Which Share a Common Neutral By: Tony Hoevenaars, P.E., President & CEO, Mirus International, Inc. Mike McGraw, President, NSOEM, Inc. When paralleling power sources that share
CYCLOCONVERTERS. Fig.1 Block diagram of a cycloconverter
CYCLOCONVERTERS Burak Ozpineci, Leon M. Tolbert Department of Electrical and Computer Engineering University of Tennessee-Knoxville Knoxville, TN 37996-2100 In industrial applications, two forms of electrical
Step Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
PHASE CONVERSION TECHNOLOGY OVERVIEW
Dr. Larry Meiners, Ph.D. PHASE CONVERSION TECHNOLOGY OVERVIEW Introduction A wide variety of commercial and industrial electrical equipment requires three-phase power. Electric utilities do not install
Power Electronics Testings
Power Electronics Testings PV Inverter Test Solution www.chromaate.com Turnkey Test & Automation Solution Provider w w w.chromaate.com A PV system is an energy system which directly converts energy from