1 A CASE STUDY ON: THE EFFECTS OF HIGHER OPERATING TEMPERATURES ON DATA CENTER EFFICIENCY Victor Garcia Director of Facilities Brocade October 24, 2012 Jeff Stein, PE Principal Taylor Engineering 2010 Brocade Communications Systems, Inc. Proprietary Information 1
2 Agenda Background Hypothesis Experiment Findings Next Steps 2
3 Brocade San Jose Labs 75,000 square feet of labs 1,900 racks 3 kw/rack 6 MW Total Building Load Hot aisle containment In-row cooling Water side economizer PUE of
4 Hypothesis Lowering the cold aisle temperature setpoint reduces IT power but the HVAC penalty is bigger than the IT savings IT fan power goes down But HVAC fan and chiller plant power goes up more 4
5 IRC Control Sequence 95% 75% Fan Speed Max SAT = 80F 50% Supply Air Temp Setpoint Min SAT = 66F 0% 50% 75% 100% IRC Group Reset Point 5
6 Temperature Sensors Before On rack In front of equipment After Hanging in cold row Uniform temperatures 6
7 Cold Aisle Setpoint Experiment Raise and lower cold aisle temperature setpoint in several cold aisles Monitor IRC fan power, IT gear power 7
8 Area of Experiments 3 rd Floor 12 rows 9 cold aisles 2 nd floor 6 rows 4 cold aisles 8
9 Row 2T 9
10 Row 2T (server/storage gear) 1.5% increase in IT KW per 5 degf 10
11 Row 2T 11
12 Row 2T 12
13 Row 2R,2S (mixed gear) 1.2% increase in KW per 5 deg F 13
14 Row 3C (IP gear) No relationship between kw and Max Temp 14
15 Row 3C, 3D (IP/Servers) 2% step change at 85F 15
16 Row 3E, 3F (mixed, storage) 4% step change at 84F 16
17 Summary of IT Power Changes Row Gear Increasing Cold Aisle Temp results in: 2R Mixed not valid due to IT changes 2R, 2S mixed 1.2% increase in IT per 5F increase in cold aisle setpt 2S, 2T mixed 1.5%/5F positive relationship 2T server/storage 1.5%/5F positive relationship 3A IP/Servers not valid due to IT changes 3A, 3B IP/Servers not valid due to IT changes 3B mixed positive but also some IT changes 3C IP no relationship 3C, 3D IP/Servers 2% step change at 85F 3D Servers no relationship 3E SAN/Server no relationship 3E, 3F mixed (E) and storage (F) 4% step change at 85F 3F, 3G servers 1.2%/5F positive relationship 17
18 8% avg decrease in fan speed for 5F increase in cold aisle setpoint 18
19 8% increase in fan speed is a 30-50% increase in fan power 19
20 Plant Power: 20% increase in plant power per 5F increase in wetbulb 5F increase in chilled water return temp. would have similar effect 20
21 Water economizer serves more load as supply and return water temperatures increase Water Entering Economizer Water Leaving Economizer Water Leaving Chiller 21
22 Water economizer serves more load as supply and return water temperatures increase Load served by Economizer Load served by Chillers 22
23 Economizer Operation Last 30 Days 23
24 Results: Lowering Setpoint Increases Total Power 24
25 Sensitivity Analysis Q: How big a decrease in IT power makes the IT savings greater than the HVAC penalty? A: IT power would have to decrease at least 8% per 5F decrease in cold aisle setpoint We saw only a 1.2% decrease per 5F A recent study by APC/Dell found a 3% decrease per 5F ( ) 25
26 Conclusions If the HVAC system has an economizer and has good part load performance (e.g. VFD fans) then the hotter the cold aisles the lower the total power consumption Commissioning is key Continuous monitoring Containment integrity Cold aisle sensor placement Incorrectly oriented gear Rogue zones 26
27 Next Steps More testing and data analysis Total building level experiment Monitor loads at equipment level Hotter cold aisles is more efficient but does it effect IT gear reliability? IT gear fan control algorithms More commissioning 27
28 Thank You 28
NetApp Data Center Design
NetApp Data Center Design Presentation for SVLG Data Center Efficiency Summit November 5, 2014 Mark Skiff, PE, CEM, CFM Director, IT Data Center Solutions Data Center Design Evolution Capacity Build Cost
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
GREEN DATA CENTER DESIGN
Jeffrey Menig Global Facilities Facility Engineering The application of multiple available technologies resulting in improved energy optimization without significantly increasing capital investment. A
Data Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013
Data Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013 Ted Brown Sr. Energy Management Analyst Data Center / IT Energy Efficiency [email protected]
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Legacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
How To Benchmark Power Production
Energy Benchmarking Service for Data Centre Industry in Hong Kong and Initial Findings Simon Lam Acting Deputy Director, Business Marketing & Development Department, CLP Power Agenda 1. Introduction: Why
University of St Andrews. Energy Efficient Data Centre Cooling
Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants
HIGH PERFORMANCE CHILLED WATER SYSTEMS EarthWise HVAC Simon Ho e: [email protected] 2012 EarthWise HVAC High Performance CHW Plants Low Flow Low Temperature Systems Variable Flow Systems Variable CHW Variable
FEAR Model - Review Cell Module Block
F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data
Data Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
Data Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
National Grid Your Partner in Energy Solutions
National Grid Your Partner in Energy Solutions National Grid Webinar: Enhancing Reliability, Capacity and Capital Expenditure through Data Center Efficiency April 8, 2014 Presented by: Fran Boucher National
Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1
WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however
Best Practices in HVAC Design/Retrofit
Best Practices in HVAC Design/Retrofit Little Server Room BIG $AVINGS Justin Lewis, P.E., LEED AP, DCEP Sr Energy Project Manager C:530.400.6042 O:530.754.4870 [email protected] 1 What s the problem here?
Control of Computer Room Air Handlers Using Wireless Sensors. Energy Efficient Data Center Demonstration Project
Control of Computer Room Air Handlers Using Wireless Sensors Energy Efficient Data Center Demonstration Project About the Energy Efficient Data Center Demonstration Project The project s goal is to identify
THE WORLD S MOST EFFICIENT DATA CENTER
THE WORLD S MOST EFFICIENT DATA CENTER HP POD 240a Ed Turkel Manager, WW HPC Marketing Hyperscale Business Unit 2011 Hewlett-Packard Development Company, L.P. The information contained herein is subject
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Greening Data Centers
Greening Data Centers Dallas Thornton SDSC Division Director, Cyberinfrastructure Services March 2, 2011 Data Centers Are Enormous Users of Power US Data Centers (TeraWatt Hours per Year) 125 US Televisions
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center [email protected] 402-559- 5301 402-630-
Data Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Automated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview
Automated Commissioning for Energy (ACE) Platform for Large Retail Property $62,900 dollars of energy savings identified during the first 6 weeks Overview The ability to pull large amounts of complex data
Energy Impact of Increased Server Inlet Temperature
Energy Impact of Increased Server Inlet Temperature By: David Moss, Dell, Inc. John H. Bean, Jr., APC White Paper #138 Executive Summary The quest for efficiency improvement raises questions regarding
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units
Hot-Aisle vs. Cold-Aisle Containment for Data Centers
Hot-Aisle vs. Cold-Aisle Containment for Data Centers White Paper 135 Revision 1 by John Niemann, Kevin Brown, and Victor Avelar > Executive summary Both hot-air and cold-air containment can improve the
How to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
AIRAH Presentation April 30 th 2014
Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining
Data Center RD&D at EPRI
Data Center RD&D at EPRI Mukesh Khattar Technical Executive Critical facilities Round Table Meeting Palo Alto, CA 16 October 2015 EPRI Focus for Data Centers RD&D Address problems facing the member electric
Data Centre/Server Room Containment: How to Get More Cooling Capacity without Adding Additional AC
Data Centre/Server Room Containment: How to Get More Cooling Capacity without Adding Additional AC About us Data centre consulting World-class products Expert national team Mike Hassaballa, Applications
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the
Enabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
How Row-based Data Center Cooling Works
How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that
How To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
CRITICAL COOLING FOR DATA CENTERS
IDEA 100 th Annual Conference & Trade Show CRITICAL COOLING FOR DATA CENTERS Presented by Ron Johanning, PE, LEED AP Mission Critical Market Leader Agenda EPA Report Data Center Energy Trends IT Best Practice
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers
Information Technology and Data Centers HVAC Showcase November 26, 2013 Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers Welcome. Today s webinar is being recorded and will be
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential
TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com
Submersion Cooling Evaluation
Submersion Cooling Evaluation ET Project Number: Project Manager: Jeff Beresini Pacific Gas and Electric Company Prepared By: Luke Werner, P.E. Energy Resources Integration (ERI) 251 Donahue St. Sausalito,
The Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric
Ee The Efficient Enterprise Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic! 30,000
Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings
Trends in Data Center Design ASHRAE Leads the Way to Large Energy Savings ASHRAE Conference, Denver Otto Van Geet, PE June 24, 2014 NREL/PR-6A40-58902 NREL is a national laboratory of the U.S. Department
High-density modular data center making cloud easier. Frank Zheng Huawei
High-density modular data center making cloud easier Frank Zheng Huawei 2012-10-10 Content 1 2 3 4 Cloud s impact to data center Concerns of DC construction 4S DC making cloud easier Success stories Cloud?
CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS
CANNON T4 MINI / MICRO DATA CENTRE SYSTEMS Air / Water / DX Cooled Cabinet Solutions Mini Data Centre All in One Solution: Where there is a requirement for standalone computing and communications, or highly
Measure Server delta- T using AUDIT- BUDDY
Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
EXAMPLE OF A DATA CENTRE BUILD
EXAMPLE OF A DATA CENTRE BUILD BT Harmondsworth Data Centre Hall 2 Upgrade Temperature Control have been involved in providing specialist to data centres for over 20 years, starting from providing specialist
Energy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
EMC DURHAM CLOUD DATA CENTER
EMC DURHAM CLOUD DATA CENTER Energy efficient design and construction EMC IT was hard at work reducing operational costs, increasing IT agility, and preparing for a dynamic future in the cloud when it
Impact of Virtualization on Data Center Physical Infrastructure White Paper #27. Tom Brey, IBM Operations Work Group
Impact of Virtualization on Data Center Physical Infrastructure White Paper #27 Tom Brey, IBM perations Work Group 1 Virtualization Two Steps WP #19 USING VIRTUALIZATIN T IMPRVE DATA CENTER EFFICIENCY
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
How To Find A Sweet Spot Operating Temperature For A Data Center
Data Center Operating Temperature: The Sweet Spot A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL
The Benefits of Supply Air Temperature Control in the Data Centre
Executive Summary: Controlling the temperature in a data centre is critical to achieving maximum uptime and efficiency, but is it being controlled in the correct place? Whilst data centre layouts have
Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
A Blueprint for a Smarter Data Center Data Center Services helps you respond to change
Bret W. Lehman, PE GTS Site and Facilities Services March 25, 2011 A Blueprint for a Smarter Data Center Data Center Services helps you respond to change 2011 IBM Corporation Change is accelerating IT
Outline. CC objectives Site and building description Typical data floor overview CC measures Results Lessons learned
Outline CC objectives Site and building description ypical data floor overview CC measures Results Lessons learned 2 CC Objectives Identify and solve existing operating problems Improve building thermal
Impact of Control System Technologies on Industrial Energy Savings
Impact of Control System Technologies on Industrial Energy Savings Priyam Parikh Industrial Assessment Center Texas A&M University Bryan P. Rasmussen Industrial Assessment Center Texas A&M University http://farolconsulting.com/?page_id=110
Capgemini UK Infrastructure Outsourcing
Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,
Optimization of energy consumption in HPC centers: Energy Efficiency Project of Castile and Leon Supercomputing Center - FCSCL
European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable Energies and Power Quality (ICREPQ 12) Santiago de Compostela
Airflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems
NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are
Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation
Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation Version 1.0 - November, 2011 Incorporating Data Center-Specific Sustainability Measures into
BRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
Paul Oliver Sales Director. Paul Oliver, Airedale Tom Absalom, JCA
Paul Oliver Sales Director Paul Oliver, Airedale Tom Absalom, JCA Airedale an overview 25,000m 2 UK premier test centre 450 staff Global distribution A Modine company Modine centre of excellence Airedale
Data Center Cooling. 1-800-693-0351 www.dpstele.com. A guide from: Your partners in UPS Monitoring Systems
Data Center Cooling A guide from: Your partners in UPS Monitoring Systems The air in your server room, especially nearest the processors in your equipment, will rise to dangerous temperatures quickly if